Specification Section 09 51 13 Acoustical Panel Ceilings

View the file

Other files

File Type Posted
Q Aas of 28 August 2009 B104.doc DOC document
Attendes Site VisitB104.xls XLS spreadsheet
scan166.pdf PDF
Q Aas of20 August 2009 B104.doc DOC document
FA665609R0005Amendment1B104.doc DOC document
scan165.pdf PDF
scan168.pdf PDF
scan169.pdf PDF
scan164.pdf PDF
scan167.pdf PDF
WDupdateB104.doc DOC document
Q Aas of 19 August 2009 B104.doc DOC document
SiteVisitMinutesB104.docx DOCX document
Attendes Site VisitB104.xls XLS spreadsheet
SolDocB104.doc DOC document
230713 - ductwork insulation.doc DOC document
260529 - hangers and supports for electrical systems.doc DOC document
312300 excavation and fill.doc DOC document
072216 roof board insulation.doc DOC document
081113 hollow-metal doors and frame.doc DOC document
329213 hydro-mulching.doc DOC document
081416 flush wood doors.doc DOC document
a_01.pdf PDF
220529 - pipe hangers supports for plumbing piping.doc DOC document
s_01.pdf PDF
s_06.pdf PDF
122100 window blinds.doc DOC document
FA665609R0005Atch4ResQues.doc DOC document
e_02.pdf PDF
013280 removal of asbestos.doc DOC document
083100 access doors and panels.doc DOC document
262726 - wiring devices.doc DOC document
238126 - duct-free split system air conditioners.doc DOC document
054000_cold formed metal framing.doc DOC document
f_01.pdf PDF
220719 - plumbing piping insulation.doc DOC document
260101 - electrical demolition.doc DOC document
s_03.pdf PDF
072719 plastic sheet air barriers.doc DOC document
USAFR Asbestos Areas1.pdf PDF
052100_steel joist framingf.doc DOC document
024119.13 selective building demolition.doc DOC document
p_02.pdf PDF
p_03.pdf PDF
223000 - plumbing equipment.doc DOC document
260526 - grounding and bonding for electrical systems.doc DOC document
AF Form 3065.pdf PDF
335100 - natural-gas distribution.doc DOC document
a_03.pdf PDF
000110 table of contents.doc DOC document
Show 40 more

Latest 50 of 145 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 09 51 13

ACOUSTICAL Panel CEILINGS

PART 1 – GENERAL

1.01 Related Documents

A.

Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.02 Summary

A.

Section Includes:

1.

Suspended exposed‑metal grid systems, complete with wall trim.

2.

Lay‑in square edge ceiling panels.

B.

Related Sections:

Division 15 – Mechanical: Air outlets and inlets within ceiling system.

Division 16 – Electrical: Lighting fixtures within ceiling system. Support of the lighting fixtures shall be independent of the suspended ceiling grid.

1.03

REFERENCES

ASTM International:

Standard Specification for Zinc‑Coated (Galvanized) Carbon Steel Wire (ASTM A‑641 / A‑641M‑98).

Standard Specification for Steel Sheet, Zinc‑Coated (Galvanized) or Zinc‑Iron Alloy‑Coated (Galvannealed) by the Hot‑Dip Process (ASTM A‑653 / A‑653M‑02).

3.

Standard Specification for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustic Tile and Lay‑in Panel Ceilings (ASTM C‑635‑00).

4.

Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustic Tile and Lay‑in Panels (ASTM C‑636‑96).

5.

Standard Test Methods for Strength of Anchors in Concrete and Masonry Elements (ASTM E‑488‑96).

6.

Standard Classification for Acoustical Ceiling Products (ASTM E‑1264‑98):

B.

Ceilings and Interior Systems Contractors Association (CISCA): Ceiling Systems Handbook.

1.04

SUBMITTALS

Submit the following in accordance with the General Requirements.

Samples of acoustical ceiling panels for verification.

1.05

DELIVERY, STORAGE, AND HANDLING

A.

Deliver acoustical ceiling units to the Site in original, unopened packages. Store in a fully enclosed space where they will be protected against damage from moisture, direct sunlight, surface contamination, and other causes.

B.

Before installing acoustical ceiling units, permit them to reach room temperature and a stabilized moisture content.

C.

Handle acoustical ceiling units carefully to avoid chipping edges or damaging units in any way.

1.06 Project CONDITIONS

Environmental Requirements: Install acoustical ceiling systems only when temperature and humidity conditions closely approximate interior conditions to exist when building is occupied. Maintain this condition prior to, during, an after installation. However, as a minimum, maintain between 60 and 85 degrees Fahrenheit. Prior to installation, ensure that the following conditions exist:

Windows and exterior doors shall be in place. Roof shall be watertight.

Wet work of other Trades shall be completed and thoroughly dried prior to start of installation of system components.

Mechanical and Electrical Trades shall have completed their work above ceiling line prior to acoustical ceiling systems installation. Coordinate with Mechanical and Electrical Trades prior to start of installation.

PART 2 – PRODUCTS

2.01

MANUFACTURERS

A.

Armstrong Building Products (ABP), Armstrong World Industries, Incorporated, Armstrong Holdings, Incorporated, Lancaster PA (Website: www.armstrong.com/commercialceilingsna/index.html, Voice: 877.276.7876).

B.

BPB North America, Compagnie de Saint‑Gobain, Tampa FL (Website: www.us.bpb‑na.com/index2.html, Voice: 866.427.2872).

C.

Suspension Systems Only: Chicago Metallic Corporation, Chicago IL (Website: www.chicago‑metallic.com, Voice: 800.323.7164).

D.

USG Interiors Incorporated, USG Corporation, Chicago IL (Website: www.usg.com, Voice: 800.874.4968).

2.02 Manufactured Units

Suspension Systems:

Exposed Direct Hung Suspension Systems, Non‑Fire‑Resistance‑Rated (Non‑FRR):

a.

Structural Classification: Intermediate duty per ASTM C‑635.

b.

Construction: Capped double web, hot‑dip galvanized steel.

1) G‑30 coating per ASTM A‑653 / A‑653M.

c.

Face: 15/16‑inch wide steel, with baked‑on enamel paint finish in white d.

Suspension System Accessories: Attachment devices and hangers per ASTM C‑635.

Concrete Anchors: Corrosion‑resistant design tested per ASTM E‑488.

e.

Hangers: Of size and type to suit intended application, per ASTM C‑635 and ASTM A‑641 / A‑641M.

f.

Moldings: Cold‑rolled galvanized steel wall design suitable for suspension system and ceiling unit profile with white baked‑on enamel paint finish.

Panels for Exposed‑Metal Grid Ceilings:

ACT-1: Mineral Base Panels (Water‑Felted): ASTM E‑1264, Type III, Form 2 with painted finish, lightly perforated and lightly textured.

Edge Detail: Square edge.

Panel Size: 24‑inch wide by 24‑inch long.

Pattern:

Cortega by ABP.

2) Baroque by BPB.

3) Radar ClimaPlus by USG.

Color: White.

ACT -2: High Density Ceramic Base Panels with Scrubbable Finish (Cleanable): ASTM E‑1264, Type XX, smooth pattern.

Edge Detail: Square edge.

Ceiling Attenuation Class (CAC): Minimum of 40 as tested and classified by UL per ASTM E‑1414 and ASTM E‑413.

Panel Size: as indicated on the Drawings.

e.

Pattern:

Fine Fissured Ceramaguard Perforated 608 by ABP.

Celotex by BPB.

Radar Ceramic ClimaPlus 55644 and 56645 by USG.

f.

Color: White.

PART 3 – EXECUTION

3.01 ExaminaTION

A.

Determine acceptability of substrates and conditions under which acoustical ceiling systems are to be installed. Do not proceed until unacceptable conditions have been corrected. Commencement of installation constitutes Installer's acceptance of substrates and conditions.

3.02 Preparation

A.

Coordinate layout and installation with other work supported by, or penetrating through ceiling, including, as applicable, light fixtures, HVAC equipment, fire suppression system components, partition systems, and the like.

B.

Install after major above‑ceiling work is complete. Coordinate the location of hangers with other work. Ensure that the layout of hangers and carrying channels are located to accommodate fittings and units of equipment that are to be placed after the installation of ceiling grid system.

C.

Supply hangers or inserts for installation to the respective Trades in ample time and with clear instructions for their correct placement. Provide additional hangers and inserts as required at no additional cost to the Owner.

3.03

INSTALLATION

A.

Install acoustical ceiling system per the Ceiling System Manufacturer's recommendations, ASTM C‑636, and CISCA Handbook to produce finished ceiling true to lines and levels and free from warped, soiled or damaged grid or lay‑in panels.

B.

Refer to the Drawings for ceiling layout. In general, center the ceiling layout on room axes leaving equal border pieces. Avoid using less than half width panels at borders.

C.

Install ceiling systems in a manner capable of supporting superimposed loads, with maximum permissible deflection of 1/360 of span and maximum surface deviation of 1/8 inch in 10 feet (1/960).

D.

Hang independently of walls, columns, ducts, pipes, and conduit.

Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

Splay hangers only where required to miss obstructions. Offset resulting horizontal forces by bracing, counter‑splaying, or other effective means.

Where width of ducts or other construction within the ceiling plenum prevent the regular spacing of hangers, install supplemental suspension members and hangers in the form of trapezes or equivalent devices.

Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

Secure wire hangers to ceiling suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that:

Are secure.

Are appropriate for the substrate.

Will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

4.

Space hangers not more than 48‑inches on center along each member supported directly from hangers. Provide hangers not more than 8 inches from ends of each member.

E.

Install suspension system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.

Where carrying members are spliced, avoid visible displacement of the longitudinal axis or face plane of adjacent members.

F.

Do not support lighting fixtures from – or on – main runners or cross runners. Support the lighting fixtures independently.

G.

Install edge moldings at intersection of ceiling and vertical surfaces, using maximum lengths, straight, true to line and level. Miter corners. Provide edge moldings at junctions with other ceiling finishes. Where bullnose concrete block corners occur, provide preformed closers to match edge molding.

H.

Fit acoustic ceiling units in place, free from damaged edges or other defects detrimental to appearance and function.

Install ceiling units level, in uniform plane and free from twist, warp, and dents.

Install ceiling units in any unbroken area of ceiling from the same product lot as indicated by lot number on each carton.

At borders and penetrations, scribe and cut ceiling units against abutting surfaces to provide a neat, precise fit.

For square‑edged panels, install panels with edges fully hidden from view by flanges of suspension system runners and moldings.

I.

Rework existing exhaust ductwork to accommodate layout of ceiling system.

J.

Install hold‑down clips on cross tees spaced 24‑inches on center to hold lay‑in panels tight to grid system.

Where within 20 feet of exterior door(s).

Where acoustical panels weigh less than 1 PSF.

3.04

ADJUSTMENTS

A.

Adjust any sags or twists that develop in the ceiling system(s) and replace any part that is damaged or faulty.

3.05

CLEANING

Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension system members.

Comply with the Ceiling System Manufacturer's written instructions for cleaning and touch‑up of minor finish damage.

Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

Remove debris that may have been caused during installation of this Work.

END OF SECTIOn this page is intentionally blank 09 51 13 – 2

ACOUSTICAL PANEL CEILINGS

12910‑330

Revised 6/24/06 12910‑330

ACOUSTICAL PANEL CEILINGS

09 51 13 – 1

Revised 6/24/06