DESIGN COORDINATION AND REVIEW COMMENTS
JOB ORDER NO.
ASHE 12-1039
| COMMENTS BY |
| CODE |
| PHONE |
| DATE |
Andrew Haas, Cheryl Duggan, Andelo Zanot, Riccardo Antonini
March 2017
| PROJECT TITLE AND LOCATION |
| TYPE OF REVIEW |
| RENOVATE BLDG 1469 FOR COMMUNITY CENTER |
| Final Design Review |
| NO. |
| DWG. NO. OR PARA. NO. |
| COMMENTS |
(MAKE GENERAL COMMENTS AFTER SPECIFIC COMMENTS)
ACTION TAKEN
(& REASONS WHERE SIGNIFICANT)
| Layout |
| End User requests layout changes to allow for improved functionality of the building. See attached floor plans |
| 2 |
| General |
| Provide stage in each of the new ballrooms, including stairs and parapets |
| 3 |
| General |
| Both ball rooms need electrical / Audio visual in both ceilings and floors and one electrical outlet box in each room with (380x1 + 220x2). Exact location needs to be coordinate with end users |
| 4 |
| General |
| CATV conduit on all floors at the stair / elevator lobby - Location to be determined |
| 5 |
| General |
| Computer data drops for VOIP and DATA in computer lab – need to coordinate number of drops |
| 6 |
| General |
| Conduit back to reception desk for camera system - Camera system by others, Location of cameras and monitor to be determined |
Not Used.
| 8 |
| General |
| For all classrooms and studios on 2nd floor to have STC 60 partition walls |
| 9 |
| General |
| Existing circle opening at stairwell to remain |
| 10 |
| General |
| R-22 not allowed as well. |
| 11 |
| General |
| Provide electrostatic filters as per UNI 11254:07 with extractable aluminum plates. |
| 12 |
| General |
| Electrical motors have to be IE3 efficiency class. |
| 13 |
| General |
| For VVF application VSM motors with proper electrical insulation must be provided. |
| 14 |
| General |
| Energy efficiency must be included on the nameplate. |
| 15 |
| General |
| LED fixture to be used instead of Fluorescent. |
In case of Fluorescent must be used T5 (G5 cap)
· 14W and 28W
No correspondences with PART IV – ELECT WORK pt.49 (pag 255) and Drawings (E1, E14 to E22)
| 16 |
| General |
| Ballast/Driver must be in accordance to the Fluorescent light type or LED |
| 17 |
| General |
| HID lamps: No correspondences with PART IV – ELECT WORK pt.49 (pg. 255) and Drawings (E1, E14 to E22) |
| 18 |
| General |
| No references about HVAC controls. |
HVAC controls should be design in accordance with USACE / NAVFAC / AFCEC / NASA UFGS-23 09 23.13 20 (November 2015).
| 19 |
| General |
| Include electrostatic filters as per UNI 11254:07 with extractable aluminum plates. |
| 20 |
| General |
| Supply and install one water meter at each of two water feeding lines of the building, therefore one will be inside the boiler room for sanitary and boiler room supply and the other one will be for the Fire system supply. |
Meters must be connected to the HVAC Control system as per USACE / NAVFAC / AFCEC / NASA UFGS-23 09 23.13 20 (November 2015).
| 21 |
| General |
| Supply and install inside the gas counter box the gas meter with digital output and bring the data cable inside the boiler room. |
| 22 |
| General |
| Delay set to 15min. Settings (delay and light level) can be modified if required. All rooms where usage of projector is foreseen, need to be equipped also with manual override. |
| 23 |
| General |
| Fixtures as reference are not produced anymore. As product reference can be used either DISANO 842 led Panel 35W (for entire fixture) 4300 Lumen with UGR<19 or DISANO 841 Minicomfort 33W 5200 Lumen with UGR<19. So total qty will be 313. Qty and position of lights must be analyzed based on the application of each room. |
Not Used.
| 25 |
| General |
| Documentation about Summer Cooling loss and Winter Heating loss are missing. |
| 26 |
| General |
| Preferred as reference product for exterior lights DISANO LED Ministelvio 3276 39W or IGuzzini LED Quid 35W. |
| 27 |
| General |
| Electrical meter is highly preferred Schneider PM810 series as it is installed in every Electrical Substation at Aviano AB. |
| 28 |
| General |
| Wrong indication for minimum receptacle section 2.5sqmm for receptacle (instead of 1.5sqmm) |
| 29 |
| General |
| Avoid red color for LV phase L3 (use grey). Red color is usually reserved for MV cables and fire alarm cables. |
| 30 |
| General |
| Wrong indication N07V-K cable to be corrected with LSOH cable N07G9-K as indicated at page 252 and following. |
The use of Low smoke halogen LSOH cables is strongly suggested for cables installations different from embedded conduits and metallic conduits in accordance to CEI 64-8 “luoghi maggior rischio in caso di incendio” (places with high risk of fire) where exist highly crowd areas risk.
| 31 |
| General |
| Wrong indication for fire alarm cable. Fire alarm cables to be 30minutes fire rated cables in accordance to EN50200. |
-For rated voltage up to 100V the standard CEI 20-105 should be considered (with minimum section 0.5sqmm).
-For rated voltage upper than 100V the standard CEI 20-45 should be followed for cables with rated voltage 0.6/1kV (with minimum section 1.5sqmm as indicated at page 259 indicating FTG10M1 cables)
| 32 |
| General |
| Indicated protection degree IP40 do not protect against water falling. IP41 should be the least requirement. IP level to be defined according installation conditions. |
IP44 to be used at least in the HVAC & water rooms.
IP55 to be used for external installations.
| 33 |
| General |
| Indicate the connections of conditioning units (path/conduits/cables to be used). |
| 34 |
| General |
| Building 1465 is not identified. To be verified availability of circuit breaker and power in Building 14001 (substation F39) power center. Building number has changed since design was issued. |
| 35 |
| General |
| Close out documentation (as built layout diagrams, O&M manuals) and warranty plan documentation to be required. 5 hardcopies and 2DVDs with PDFs and DWGs |
| 36 |
| General |
| As required for new layout design |
| 37 |
| General |
| Building design and specifications should be updated to meet current code / UFC technical requirements and base design requirements. |
| 38 |
| General |
| Provide 60 month mechanical system warranty to include annual maintenance. |
| 39 |
| General |
| Cables to comply with New July 2017 Construction Product Regulations |
| 40 |
| General |
| All lighting to be replaceable type LED lights |