ASHE_12-1039_SEP-2018_Tech_Specs_Rev.2.pdf

PDF 3 MB Posted

Attached to
ASHE 12-1039 Renovate Bldg 1469 for Community Center, Area F, Aviano AB, Italy
Solicitation number
FA568219RA002
Issued by

About this file

REVISED TECHNICAL SPECIFICATIONS - REV 2

View the file

Other files

File Type Posted
ATTACHMENT_4_REV.1.pdf PDF
FA568219RA0020004.pdf PDF
FA568219RA002_RFIs_Q_&_A_(5).pdf PDF
FA568219RA19RA002_RFIs_Q_&_A_(4).pdf PDF
FA568219RA19RA002_RFIs_Q_&_A_(2)_REV.1.pdf PDF
FA568219RA19RA002_RFIs_Q_&_A_(1).pdf PDF
FA568219RA19RA002_RFIs_Q_&_A_(3).pdf PDF
ASHE12~3.PDF PDF
ASHE12~2.PDF PDF
ASHE12~1.PDF PDF
F6B57A99.PDF PDF
SOVRIN~4.PDF PDF
SOVRIN~3.PDF PDF
SOVRIN~1.PDF PDF
ASHE12~2.PDF PDF
SOVRIN~2.PDF PDF
ASHE12~4.PDF PDF
7E8D02FB.PDF PDF
ASHE12~3.PDF PDF
E02E9BD8.PDF PDF
ASHE12~4.PDF PDF
ASHE12~1.PDF PDF
ASHE12~1.PDF PDF
ASHE12~2.PDF PDF
FA568219RA0020003.pdf PDF
REV_1-_Drawings_Pack_1.zip ZIP file
REV_1-Drawings_Pack_3.zip ZIP file
REV_1-Drawings_Pack_2.zip ZIP file
ASHE_12-1039_CCEB_Rev.01.xls XLS spreadsheet
Solicitation_Amendment_FA568219RA0020002_SF_30.pdf PDF
Solicitation_Amendment_FA568219RA0020001_SF_30_-1.pdf PDF
Solicitation_-_FA568219RA002_Final.pdf PDF
AUTORI~1.PDF PDF
COMMDA~1.PDF PDF
ASHE_12-1039_CCEB_SEP-2018.xls XLS spreadsheet
ASHE_12-1039_ATTACHMENT_1.pdf PDF
ASHE_12-1039_SEP-2018_DWG.pdf PDF
Comment_Matrix_for_new_Comm_Requirements_ATTACHMENT_3.docx DOCX document
Design_Comments_ATTACHMENT_4.doc DOC document
ASHE_12-1039_SEP-2018_Tech_Specs_Rev.1.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. AIR FORCE

31ST FIGHTER WING

31ST CES/CENM

AVIANO AIR BASE, ITALY

mailto:studio@contiassociati.it

PROJECT : ASHE 12-1039

SUBMITTAL : REV.2

SUBMITTAL DATE : JUN 19

Technical specification

Project:

Location:

Project Phase:

Date:

ASHE 12-1039 RENOVATE FOR COMMUNITY CENTER

FAC. 1469, Area F, Aviano AB, Italy

100%

REVISION JUN 2019 - REV2

DOOR SCHEDULE

SCOPE OF PROJECT

The project has been approved by The Construction Mix Commission during the “out of Cycle” Session on 17 Apr 17. has been designed valid at that time.

contractor during project works execution.

P

AND

- , including plaster

- , including chimneys, gaskets,

- PACM .Potential Asbestos Containing Material (PACM) and/or Asbestos Containing Material (ACM) is present in the facilities to be renovated (flashing, gutters, downspouts, protective shed at main entrance, fireplace stacks, all chimney and stacks, all insulations, interior and exterior plaster, false ceiling, toilettes drains, mineral wool, plant engineering insulation, vinyl floor tiles, windows and doors gaskets). Contractor shall abate and dispose ACM in accordance with Italian laws and regulations. Before starting of any demolition, contractor shall provide certificate of abatement/disposal. PACM shall be treated in an equal manner as ACM, unless tested and verified by the contractor to be free of ACM. These test results shall be submitted to the government before starting any demolition.

- , and existing mechanical system

ARCHITECTURE, MONUMENTL AND HYSTORICAL CONSTRAINTS

SUBMITTAL OF MATERIALS

CONSTRUCTION AREA SCREENING

PROJECT SIGN

JOB SITE MOBILIZATION

SAFETY

HAZMAT/HAZWASTE HOUSEKEEPING

PRESERVATION OF EXISTING CONDITIONS

WORK SITE CONDITIONS

AIRFIELD SAFETY TRAINING

PARKING

ACCESS ROUTES

TRUCKING AND ROADS

NOISE CONTROL

EXCAVATIONS

LAWN MAINTENANCE

LAWN ESTABLISHMENT

CONSTRUCTION SITE RESTORATION

PROCEDURES AND WORK PHASES

SALVAGEABLE MATERIALS

CONSTRUCTION DRAWINGS

X

X

X

X-3 REV.01

X-4 REV.01

X

X

X

X

X

X

-REV.01

1 -REV.01

-REV.01

-REV.01

6--REV.01

-REV.01

TECHNICAL SPECIFICATION

ADDITIONAL SPECIFICATIONS

REVISED MASTER SPECIFICATIONS

ADDITIONAL NORMS AND STANDARDS

FINAL ACCEPTANCE TEST, CERTIFICATIONS AND OTHER REQUIREMENTS

REVISED MASTER SPECIFICATIONS

SECTION 01100/R GENERAL CONDITIONS

SECTION 01101/R PROJECT SIGN

SECTION 02220/R SITE DEMOLITION

SECTION 02630/R STORM DRAINAGE

SECTION 03300/R CAST-IN-PLACE CONCRETE

SECTION 04200/R MASONRY

SECTION 05120/R STRUCTURAL STEEL

SECTION 05500/R METAL FABRICATIONS

SECTION 07220/R ROOF INSULATION

SECTION 07231/R WALL INSULATION

SECTION 07600/R FLASHING AND SHEET METAL

SECTION 07920/R JOINT SEALANTS

SECTION 08110/R STEEL DOORS AND STEEL FRAMES

SECTION 08120/R ALUMINUM DOORS, FRAMES AND SIDELIGHTS

SECTION 09212/R EXTERIOR STUCCO

SECTION 09220/R INTERIOR PLASTER

SECTION 09250/R GYPSUM AND CEMENT BOARD

SECTION 09900/R PAINTS AND COATINGS

SECTION 15080R INSULATION FOR MECHANICAL SYSTEMS

SECTION 15181R CHILLED WATER AND HOT WATER PIPING

SECTION 15720R AIR HANDLING AND DISTRIBUTION EQUIPMENT

SECTION 15810R DUCTWORK AND DUCTWORK ACCESSORIES

SECTION 15400R PLUMBING

SECTION 15601R CENTRAL REFRIGERATION EQUIPMENT FOR AIR CONDITIONING

SECTION 16050R BASIC ELECTRICAL MATERIALS AND METHODS

SECTION 16303R UNDERGROUND TRANSMISSION AND DISTRIBUTION LINES

SECTION 16316R SWITCHBOARDS

SECTION 16402R INTERIOR DISTRIBUTION SYSTEMS

SECTION 16510R INTERIOR LIGHTING

SECTION 16710R STRUCTURED TELECOMMUNICATIONS CABLING & PATHWAY SYSTEM .. 184

Section 01100/R 21

SECTION 01100/R

GENERAL CONDITIONS

Revise Paragraph "3.2 UTILITY CUT-OFF" as follows:

Delete "ten (10) days" and insert "three (3) weeks" .

-- End of Section -

Section 01101/R 22

SECTION 01101/R

PROJECT SIGN

PART 1 - PROJECT SIGN

1.1 Scope

Furnish labor and material required for the construction and painting of a sign as shown on the attached sketch.

PART 2 - GENERAL

The Contractor shall identify the project by means of an appropriate sign mounted in a conspicuous area of the work site, as indicated by the Contracting Officer or his designated representative. The sign shall be erected within 10 days of initiation of work at the job site.

The sign shall contain the following information in English:

a. Project No.

b. Project description

c. Constructed under Supervision of Base Civil Engineering

d. Contracted by 31st Contracting Squadron

e. Contractor

f. Design Engineer

g. Inspector

h. Contract Management: 31 CONS Construction Flight

i. ERP Coordinates

Lettering of the sign will be as shown on the following sketch, and may be painted or stenciled directly on sign. The sign will remain the property of the Contractor, and shall be promptly removed upon completion of the project.

Additionally, standard signs as per Italian Legislative Decree 81/08, and specifically per direction of the Safety Coordinator, will need to be installed at the site.

Section 01101/R 23

-- End of Section –-

ASHE 12-1039 RENOVATE FAC. 1469 FOR COMMUNITY

CENTER

AREA F, AVIANO AIR BASE ITALY

Section 02220/R 24

SECTION 02220/R

SITE DEMOLITION

Add the following paragraph:

1.1.5 Electrical and Electronic Equipment Waste Disposal (RAEE)

Disposal of the Electrical and Electronic Equipment Waste (RAEE) shall be in compliance with Legislative Decree No. 151 dated 25 July 2005: Accomplishment of the European Directive Relevant to the Electrical and Electronic Equipment Waste.

Additionaly, comply to D.Lgs.152/2006 and subsequent amendments thereto.

-- End of Section –-

Section 02630/R 25

SECTION 02630/R

STORM DRAINAGE

Paragraph 1.1:

Delete:

UNI 7613 (1976) High Density Polyethylene Pipes for Buried Sewer Drain. Types, Dimensions, and Requirements.

Add:

UNI EN 12666 (2006) Plastic Pipe Systems for Non-pressure Underground Drainage and Sewerage – Polyethilene (PE) – Part 1: Specifications for Pipes, Fittings and the System.

Add at the end of Paragraph 2.1.1 the following sentence:

“Other manufacturers meeting the requirements of this specification are acceptable.”

-- End of Section --

Section 03300/R 26

SECTION 03300/R

CAST-IN-PLACE CONCRETE

UNI EN 10002-1 (1992)Metallic Materials. Tensile Testing. Method of Test

(At Ambient Temperature).

UNI ENV 10080 (1997) Steel for the Reinforcement of Concrete.

Weldable Ribbed Reinforcing Steel B500. Technical Delivery Conditions for Bars, Coils and Welded Fabric.

UNI EN 934-2 (2002) Admixtures for Concrete, Mortar and Grout.

Concrete Admixtures. Definitions, Requirements, Conformity, Marking and Labeling.

UNI EN 206-1 (2001) Concrete. Specification, Performance, Production and Conformity.

UNI 8520 (1999)Aggregates for Concrete Mixes.

Definition, Classification and Properties.

UNI EN 10002-1 (2004)Metallic Materials. Tensile Testing. Part 1: Method of Test at Ambient Temperature.

UNI ENV 10080 (2005) Steel for the Reinforcement of Concrete.

UNI EN 934-2 (2007) Admixtures for Concrete, Mortar and Grout. Part

2: Concrete Admixtures. Definitions, Requirements, Conformity, Marking and Labeling.

UNI EN 206-1 (2006) Concrete. Part 1: Specification, Performance, Production and Conformity.

UNI 8520-1 (2005)Aggregates for Concrete.

Additional Provisions for the Application of EN 12620.

Part 1: Conformity Criteria.

Ministerial Decree dated 14 January 2008: “Technical Norms for Constructions”.

Circolare n.617 Dated 02 February 2009 “Application Guidance for Technical Norms for

Constructions”.

Section 04200/R 27

SECTION 04200/R

MASONRY

UNI 8942-1 (1986) Clay Bricks and Blocks:

Terminology and Classification System.

UNI 8942-2 (1986) Clay Bricks and Blocks for Masonry:

Acceptance Limits.

UNI 8942-3 (1986) Clay Bricks and Blocks:

Test Methods.

UNI-EN 196.1-7 Test Method of Concrete.

UNI ENV 10080 (1997) Steel for the Reinforcement of Concrete.

UNI 771-1 (2005)Specification for Masonry Units.

Part 1: Clay Masonry Units.

UNI-EN 196.1-7 (2005) Test Method of Concrete.

UNI ENV 10080 (2005) Steel for the Reinforcement of Concrete.

Weldable Ribbed Reinforcing Steel B500. Technical Delivery Conditions for Bars, Coils and Welded Fabric.

Ministerial Decree dated 14 January 2008: “Technical Norms for Constructions”.

Circolare n.617

Section 05120/R 28

SECTION 05120/R

STRUCTURAL STEEL

Paragraph 1.1 References:

UNI 5712 (1975) High-Strength Large Hexagon Screws for Structural Engineering - ISO Metric Coarse Thread.

UNI 5713 (1975) High-Strength Large Hexagon Nuts for Structural

Engineering - ISO Metric Coarse Thread.

UNI 5714 (1975) Chamfered Plain Washers for High-Strength Bolts for Structural Engineering.

UNI 8863/A1 (1987/89) Unalloyed Steel Seamless and Welded Tubes

Suitable for Screwing in Accordance with UNI ISO 7/1.

CNR UNI 10011 (1988) Steel Structures - Instructions for Design, Construction, Testing and Maintenance.

UNI EN 10083-1+A1 (1998) Quenched and Tempered Steels – Part 1:

Technical Delivery Conditions for Special Steels (Includes Amendment A1:1996).

UNI EN 14399-3 (2005) High-Strength Structural Bolting Assemblies for Preloading.

Part 3: System HR – Hexagon Bolt and Nut Assemblies.

UNI EN 14399-4 (2005) High-Strength Structural Bolting Assemblies for

Preloading.

Part 4: System HV – Hexagon Bolt and Nut Assemblies.

UNI EN 14399-5 (2005) High-Strength Structural Bolting Assemblies for

Preloading.

Part 5: Plain Washers.

UNI EN 14399-6 (2005) High-Strength Structural Bolting Assemblies for

Preloading.

Part 6: Plain Chamfered Washers.

UNI EN 10255 (2007) Non-Alloy Steel Tubes Suitable for Welding and

Threading – Technical Delivery Conditions.

UNI EN 10083-1 (2006) Steel for Quenching and Tempering. Part 1:

General Technical Delivery Conditions.

CNR UNI 10011 (1997) Steel Structures - Instructions for Design, Construction, Testing and Maintenance.

Ministerial Decree dated 14 January 2008: “Technical Norms for Constructions”.

Circolare n.617

Section 05120/R 29

Paragraph 1.2 System Description:

Replace:

“CNR UNI 10011” with “CNR 10011”

Paragraph 1.3.1 Shop Drawings:

Shop Drawings

Paragraph 1.4.1 Drawing Requirements

Paragraph 2.2.1 Structural steel:

Paragraph 2.1.1 Steel Shapes:

Other manufacturers meeting the requirements of this specification are acceptable.”

Paragraph 2.2.3 Steel Pipe:

“UNI 8863-A1” with “UNI EN 10255”

Paragraph 2.3.1 High-Strength bolts:

“UNI 5712” with “UNI EN 14399-3 and UNI EN 14399-4”

Paragraph 2.3.2 Nuts:

“UNI 5713” with “UNI EN 14399-3 and UNI EN 14399-4”

Paragraph 2.3.3 Washers:

“UNI 5714” with “UNI EN 14399-5 and UNI EN 14399-6” “UNI 5712” with “UNI EN 14399-3 and UNI EN 14399-4”

Paragraph 2.3.4.1 Bolts:

Section 05120/R 30

“UNI EN 10083-1+A1” with “UNI EN 10083-1”

Paragraph 2.3.4.2 Nuts:

Replace:

“UNI 5713” with “UNI EN 14399-3 and UNI EN 14399-4”

Paragraph 2.3.4.3 Washers:

Replace:

“UNI 5714” with “UNI EN 14399-5 and UNI EN 14399-6”

Paragraph 2.6.2 Shop Primer:

Replace:

“CNR UNI 10011” with “CNR 10011 norm”

Paragraph 3.3 Connections:

Replace:

“CNR UNI 10011” with “CNR 10011 norm”

Paragraph 3.3.1 High-Strength bolts:

Replace:

“UNI 5712” with “UNI EN 14399-3 and UNI EN 14399-4”

“CNR UNI 10011” with “CNR 10011”

Paragraph 3.4 Welding:

Replace:

“UNI EN 10083-1+A1” with “UNI EN 10083-1”

Paragraph 3.6.2.1 Testing bolt, nut, and washer assemblies:

Replace:

Section 05500/R 31

SECTION 05500/R

METAL FABRICATIONS

Paragraph 1.1 Applicable Publications:

UNI EN 10025 (1995) Hot Rolled Products of Non - Alloys Structural Steel. Technical Delivery Conditions.

UNI EN 10002-1 (1992) Metallic Materials. Tensile Testing. Method of Test

(at Ambient Temperature).

UNI 564 (1960) Metal Materials Mechanical Tests. Bend Test.

CNR 10011/85 Steel Constructions - Calculation, Execution and

Maintenance Instructions.

CNR 10016/85 Steel and Concrete Compound Truss - Calculation and

Execution Instructions.

CNR 10022/85 Cold Sections - Instruction for the Use in Constructions.

CNR 10029/85 High Resistance Steel Constructions. Calculation, Execution, Test and Maintenance Instructions.

UNI EN 10025-1 (2005) Hot Rolled Products of Structural Steels. Part 1:

General Technical Delivery Conditions.

UNI EN 10025-2 (2005) Hot Rolled Products of Structural Steels. Part 2:

Technical Delivery Conditions for Non-Alloy Structural Steels.

UNI EN 10002-1 (2004) Metallic Materials. Tensile Testing. Part 1: Method of Test Ambient Temperature.

UNI EN ISO 7438 (2005) Metallic Materials. Bend Test.

UNI EN 10029 (1992) Hot Rolled Steel Plates 3 mm Thick or Above.

Tolerances on Dimensions, Shape and Mass.

Ministerial Decree dated 14 January 2008: “Technical Norms for Constructions”.

Circolare n.617

-- End of Section –

Section 07220/R 32

SECTION 07220/R

ROOF INSULATION

Paragraph 1.1 Applicable publications:

UNI EN 13165 (2003) Thermal Insulation Products for Buildings - Factory Made Rigid Polyurethane Foam (PUR) Products

– Specification.

UNI EN 13165 (2016) Thermal Insulation Products for Buildings - Factory Made Rigid Polyurethane Foam (PUR) Products

– Specification.

Use a Cool Roof system.

Section 07231/R 33

SECTION 07231/R

WALL INSULATION

Add to Paragraph 1.1:

UNI 7745 (1977) Insulating Materials. Determination of Thermal Conductivity by Means of the Guarded Hot Plate Method.

UNI 7891 (1978) Insulating Materials. Determination of Thermal

Conductivity by Means of the Heat Flow Meter Method.

UNI EN 13164 (2003) Thermal Insulation Products for Buildings -

Factory Made Products of Extruded Polystyrene Foam (XPS) - Specification

Read Paragraph 2.1.a as follows:

a. Foamed extruded closed cell polystyrene board:

Density 33-35 kg/cm Thermal conductivity as per UNI 7745, UNI 7891, and UNI EN 13164 0.033 W/mK Compressive strength 3 kg/sq.cm Fire behavior Class 1 Water absorption 0.1% Resistance to steam migration 80-150

In order to reduse the Government cost for dismantling material, when feasible adopt insulation with natural /recyclable materials.

Section 07600/R 34

SECTION 07600/R

FLASHING AND SHEET METAL

UNI 9001-2 (1987) Wrought Primary Aluminum and Aluminum Alloys.

Aluminum Group. Al 99,5 (1050 A).

UNI 5649-1-2 (1988) Copper. Wrought Coppers. Qualities, Requirements and Tests.

UNI EN 10142 (2002) Continuously Hot-Dip Zinc Coated Low Carbon

Steels Strip and Sheet for Cold Forming. Technical Delivery Conditions.

UNI EN 10130 (2000) Cold Rolled Low Carbon Steel Flat Products for

Cold Forming. Technical Delivery Conditions.

UNI EN 10152 (1994) Electrolytically Zinc Coated Cold Rolled Steel Flat

Products. Technical Delivery Conditions.

UNI EN 10327 (2004) Continuously Hot-Dip Coated Strip and Sheet of

Low Carbon Steel for Cold Forming. Technical Delivery Conditions.

UNI EN 10130 (2007) Cold Rolled Low Carbon Steel Flat Products for

Cold Forming. Technical Delivery Conditions.

UNI EN 10152 (2004) Electrolytically Zinc Coated Cold Rolled Steel Flat

Products. Technical Delivery Conditions.

Paragraph 2.2.1 Steel Sheet, Zinc Coated (Galvanized):

“UNI EN 10142” with “UNI EN 10327”.-- End of Section --

Section 07920/R 35

SECTION 07920/R

JOINT SEALANTS

Add at the end of Paragraph 2.2 the following sentence:

"Other manufacturers meeting the requirements of this specification are acceptable.”

Section 08110/R 36

SECTION 08110/R

STEEL DOORS AND STEEL FRAMES

Paragraph 1.1 Applicable publications:

Delete:

EN 9774 (1990) Thermal Insulation Materials -Application Categories and Basic Requirements - Guidelines for the Harmonization of International Standards and Other Specifications.

ISO 834 (1975) Fire Resistance Tests – Elements of Building Construction; Amendment 1:1979; Amendment 2: 1980.

ISO 3008 (1976) Fire-Resistance Tests - Door and Shutter Assemblies.

ISO 3009 (1976) Fire Resistance Tests – Glazed Elements.

ISO 4898 (1984) Cellular Plastics – Specification for Rigid Materials Used in the Thermal Insulation of Buildings.

ISO 5925/1 (1981) Fire Tests - Evaluation of Performance of Smoke Control Door Assemblies - Part 1: Ambient Temperature Test.

UNI 7962 Buildings, Doors, Terminology and Symbology.

Add:

EN 9774 (1990) Thermal Insulation for Building Application - Guidelines for Selecting Properties.

ISO 834 (2003) Fire Resistance Tests – Elements of Building Construction.

ISO 3008 (2007) Fire-Resistance Tests - Door and Shutter Assemblies.

ISO 3009 (2003) Fire Resistance Tests - Elements of Building Construction – Glazed Elements.

ISO 4898 (2006) Rigid Cellular Plastics – Thermal Insulation Products for Buildings.

ISO 5925-1 (2007) Fire Tests – Smoke-control Door and Shutter Assemblies - Part 1: Ambient Temperature and Medium Temperature Leakage Tests.

ASTM E 90 (2001) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements

UNI EN 12519 (2005) Windows and Pedestrian Doors. Terminology.

Section 08110/R 37

UNI EN 10327 (2004) Continuously Hot-Dip Coated Strip and Sheet of Low Carbon Steels for Cold Forming. Technical Delivery Conditions.

UNI EN ISO 140-4 (2000) Measurement of Sound Insulation in Buildings and of Building Elements. Field Measurements of Airborne Sound Insulation Between Rooms.

Paragraph 1.2.1 Shop Drawings:

Delete:

“blast resistant”

Read the sentence as follows:

“Submit door and frame locations, architectural door number, fire rating and indication of the construction details referring to the submitted shop drawings.”

Paragraph 1.2.4 Design Data:

Delete:

“blast loads”

Read the sentence as follows:

“Structural calculations.”

Paragraph 1.2.5 Test Reports:

Delete:

“Resistance to blast loads”

Add:

“REI tests.”

Paragraph 1.3.2 Rated Assembly Coordination:

Delete:

“and/or blast resistant”

Read the sentence as follows:

“Contractor shall coordinate selection of steel door and frame materials and products specified herein with door hardware to ensure that fire rated assemblies meet all U.S. and Italian related requirements.”

Paragraph 1.4.1 Blast Resistance Criteria

Delete the whole paragraph

Section 08110/R 38

Paragraph 2.1.4 Blast Resistance Fabrication:

Delete the whole paragraph.

Paragraph 3.1.4:

Delete from title and sentence:

“Blast resistant”

Section 08120/R 39

SECTION 08120/R

ALUMINUM DOORS, FRAMES AND SIDELIGHTS

UNI EN 288-4 (1993) Specification and Qualification of Welding Procedures for Metallic Materials

- Part 4: Welding Procedure Tests for the Arc Welding of Aluminum and its Alloys.

UNI EN ISO 10077-1 (2002) Thermal Performance of Windows, Doors and

Shutters - Calculation of Thermal Transmittance - Simplified Method.

UNI 10680 (1997) Aluminum and Aluminum Alloys. Aluminum

Alloys Thermal Break Profiles. Requirements and Test Methods.

UNI EN ISO 15614-2 (2006) Specification and Qualification of Welding Procedures for Metallic Materials - Welding Procedure Test - Part 2: Arc Welding of Aluminum and its Alloys.

UNI EN ISO 10077-1 (2007) Thermal Performance of Windows, Doors and

Shutters - Calculation of Thermal Transmittance - Part 1:

General.

UNI EN 14024 (2005) Metal Profiles with Thermal Barrier - Mechanical

Performance - Requirements, Proof and Tests for Assessment.

Paragraph 1.2.4 Design data:

Paragraph 1.2.5 Test Reports:

Paragraph 2.2.1 Doors, Frames and Accessories:

Delete at the end of fourth sentence:

“in any case they shall resist to the blast.”

Subparagraph “c.”:

“UNI EN 288-4.” in first sentence and the whole second sentence.

Section 08120/R 40

“UNI EN ISO 15614-2.”

Subparagraph “f.”:

Delete the whole paragraph

Paragraph 2.2.4 Provisions for Glazing:

Delete last sentence.

Paragraph 2.2.5 Anchors:

Delete second sentence.

Paragraph 2.4.1 Available Manufacturers:

NORMANT SECURITY GROUP

3224 Mobile Hwy Montgomery, AL 36108 ATTN: Steve Scoggin Tel: (334) 286-4246 Fax: (334) 286-4399 Email: steve-scoggin@normantind.com

SAELZER GMBH

Dietrich-Bonhoeffer-Str.1-3 D-35037 Marburg ATTN: Frank Rummler Tel: 49 (0) 6421/938-100 Fax: 49 (0) 6421/938-190 Email: rummler@saelzer.de Or suelzer@saelzer.de

PENSHER SKYTECH LTD

Felling Works, William Street, Felling, Gateshead Tyne & Wear NE 100JP – U.K.

Tel: 0044(0)1914380455 Fax: 0044(0)19114302328

METRA SERVICE

37169 Villafranca (VR) Italia Via 1° Maggio, 12 Tel: +39(0)45/6303320 Fax: +39(0)45/6303318

SCHÜCO INTERNATIONAL srl 35030 Sarmeola (PD) Italia Via Della Provvidenza,141 Tel: +39(0)49/8226900 Fax: +39(0)49/8226952

Section 08120/R 41

Paragraph 2.9 FABRICATION OF ALUMINUM FRAMES:

Delete second and third sentence.

Paragraph 2.10.1 Sizes, Clearance and Edge Treatment:

Delete from first sentence:

“and not less than 75 mm thick, and in any case they shall resist to the blast.”

Section 09212/R 42

SECTION 09212/R

EXTERIOR STUCCO

UNI ENV 413-1 (1994) Masonry Cement - Part 1: Specification.

UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria.

UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods.

UNI EN 932-1 (1998) Tests for General Properties of Aggregates - Part 1: Methods for Sampling.

UNI EN 932-3 (1998) Tests of General Properties of Aggregates - Part

3: Procedure and Terminology for Simplified Petrographic Description.

UNI ENV 413-1 (2004) Masonry Cement - Part 1: Specification.

Composition, Specifications and Conformity Criteria.

UNI EN 459-1 (2002) Building Lime. Definitions, Specifications and

Conformity Criteria.

UNI EN 459-2 (2002) Building Lime. Test Methods.

Aggregates. Methods for Sampling.

UNI EN 932-3 (2004) Tests of General Properties of Aggregates - Part

Add the following sentence at the end of Paragraph 2.1.8:

Section 09220/R 43

SECTION 09220/R

INTERIOR PLASTER

UNI ENV 413-1 (1994) Masonry Cement - Part 1: Specification.

UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria.

UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods.

Aggregates - Part 1: Methods for Sampling.

UNI EN 932-3 (1998) Tests of General Properties of Aggregates - Part

UNI ENV 413-1 (2004) Masonry Cement - Part 1: Specification.

Composition, Specifications and Conformity Criteria.

UNI EN 459-1 (2002) Building Lime. Definitions, Specifications and

Conformity Criteria.

UNI EN 459-2 (2002) Building Lime. Test Methods.

Aggregates. Methods for Sampling.

UNI EN 932-3 (2004) Tests of General Properties of Aggregates - Part

Add the following sentence at the end of Paragraph 2.11:

Section 09250/R 44

SECTION 09250/R

GYPSUM AND CEMENT BOARD

Add the following sentence at the end of Paragraph 2.1:

-- End of Section

Section 09900/R 45

SECTION 09900/R

PAINTS AND COATINGS

UNI ISO 6504-1 (1990) Paints and Varnishes - Determination of Hiding Power - Part 1: Kubelka-Munk Method for White and Light-Colored Paints.

UNI EN ISO 3251 (1998) Paints and Varnishes - Determination of Non-

Volatile Matter of Paints, Varnishes and Binders for Paints and Varnishes.

UNI EN ISO 6504-1 (2006) Paints and Varnishes - Determination of Hiding

Power - Kubelka-Munk Method for White and Light- Colored Paints.

UNI EN ISO 3251 (2005) Paints, Varnishes and Plastic - Determination of

Non-Volatile Matter Content.

Color samples and data sheets must be in accordance with the Aviano Design Guide Rev. 2017 and approved by BCE and C.O.

If applicable Contractor shall use piant with low VOC or zero VOC.

Section 15080/R 46

Section 15080/R 47

Section 15080/R 48

Section 15080/R 49

Section 15080/R 50

Section 15080/R 51

Section 15080/R 52

Section 15080/R 53

Section 15080/R 54

Section 15181/R 55

Section 15181/R 56

Section 15181/R 57

Section 15181/R 58

Section 15181/R 59

Section 15181/R 60

Section 15181/R 61

Section 15181/R 62

Section 15181/R 63

Section 15181/R 64

Section 15181/R 65

Section 15181/R 66

Section 15181/R 67

Section 15181/R 68

Section 15181/R 69

Section 15181/R 70

Section 15181/R 71

Section 15181/R 72

Section 15181/R 73

Section 15181/R 74

Section 15181/R 75

Section 15720/R 76

Section 15720/R 77

Section 15720/R 78

Section 15720/R 79

Section 15720/R 80

Section 15720/R 81

Section 15720/R 82

Section 15720/R 83

Section 15720/R 84

Section 15720/R 85

Section 15720/R 86

Section 15720/R 87

Section 15720/R 88

Section 15720/R 89

Section 15720/R 90

Section 15720/R 91

Section 15720/R 92

Section 15810/R 93

Section 15810/R 94

Section 15810/R 95

Section 15810/R 96

Section 15810/R 97

Section 15810/R 98

Section 15810/R 99

Section 15810/R 100

Section 15810/R 101

Section 15810/R 102

Section 15810/R 103

Section 15810/R 104

Section 15810/R 105

Section 15810/R 106

Section 15810/R 107

Section 15810/R 108

Section 15810/R 109

Section 15810/R 110

Section 15810/R 111

Section 15810/R 112

Section 15810/R 113

Section 15810/R 114

Section 15810/R 115

Section 15810/R 116

Section 15810/R 117

Section 15400/R 118

Section 15400/R 119

Section 15400/R 120

Section 15400/R 121

Section 15400/R 122

Section 15400/R 123

Section 15400/R 124

Section 15400/R 125

Section 15400/R 126

Section 15400/R 127

Section 15400/R 128

Section 15400/R 129

Section 15400/R 130

Section 15601/R 131

Section 15601/R 132

Section 15601/R 133

Section 15601/R 134

Section 15601/R 135

Section 15601/R 136

Section 15601/R 137

Section 15601/R 138

Section 15601/R 139

Section 16050/R 140

SECTION 16050R

BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 - GENERAL

1.1 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

ITALIAN ELECTROTECHNICAL COMMITTEE (C.E.I.) PUBLICATIONS

CEI 11-1 (2001) Power installation exceeding 1 kV a.c..

INTERNATIONAL ELECTROTECHNICAL COMMISSION (I.E.C.) PUBLICATIONS

CEI 64-8 (2007) Electrical Systems with Rated Voltage Below

1000 V a.c. and 1500 V d.c.

CEI 16-2 (2007) Identification of Equipment Terminals.

IEC 60706 (2006) Guide on Equipment Maintenance.

UNI ISO 9227 (1993) Corrosion of Metallic Materials. Behavior Tests.

Salt Spray Test.

UNI EN ISO 6988 (1998) Metallic and other non-organic coatings. Sulfur dioxide test with general condensation of moisture.

ITALIAN LAW

D.P.R. 547/1955 Accident Prevention Norms.

Law 186/1968 Disposition about production material, devices, installation and electrical and electronic plant.

Law 46/1990 Plant safety norm

D.P.R. 447/1991 Norm for implementation of Law 46/1990, plant safety norm.

D.P.R. 380/2001 Norms collections about buildings construction.

INTERNATIONAL STANDARDS ORGANIZATION (ISO) PUBLICATION

Section 16050/R 141

1.2 APPLICATION

This section applies to all sections of Division 16: ELECTRICAL of this project except as specified otherwise in each individual section.

1.3 SUBMITTALS

Submittals shall conform to Aviano AB, Contracting Office requirements and to the following additional requirements. Obtain submittals approval before procurement, fabrication, or delivery of items to the job site. Partial submittals will not be acceptable and will be returned without review.

Submittals shall include the manufacturer's name, trade name, place of manufacture, catalog model or number, nameplate data, size, layout dimensions, capacity, project specification and paragraph reference, applicable industry and technical society publication references, and other information necessary to establish contract compliance of each item to be furnished.

1.3.1 Shop Drawings

In addition to the requirements of the Contract Clauses, shop drawings shall meet the following requirements: Drawings shall be a minimum of 210 mm by 275 mm in size, except as specified otherwise. Drawings shall include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings shall indicate adequate clearance for operation, maintenance and replacement of operating equipment devices. If equipment is disapproved, drawings shall be revised to show acceptable equipment and be resubmitted.

1.3.2 Manufacturer's Data

Submittals for each manufactured item shall be current manufacturer's descriptive literature of cataloged products, equipment drawings, diagrams, performance and characteristic curves, and catalog cuts. When data that describe more than one type or size of equipment or material are submitted, the submittal shall be clearly marked to indicate which type or size of equipment or material the Contractor is proposing to supply.

1.3.3 Publication Compliance

Where equipment or materials are specified to conform to industry and technical society publications of organizations such as CEI, IEC, and UNI, shall have CEE certifications, and proof of such compliance shall be submitted. The label or listing by the specified organization will be acceptable evidence of compliance. In lieu of the label or listing, submit a certificate from an approved independent testing organization adequately equipped and competent to perform such services, and approved by the Contracting Officer’s Technical Representative, stating that the item has been tested in accordance with the specified organization's test methods and that the item conforms to the specified organization's applicable publication.

1.3.4 Certified Test Reports

1.3.5 Certificate of Compliance

Submit manufacturer's certifications as required on products, materials, finish, and equipment indicated in the technical sections. Certifications shall be documents prepared specifically for this contract. Preprinted certifications and copies of previously submitted documents will not be acceptable. The manufacturer's certifications shall name the appropriate products, equipment, or materials and the publication specified as controlling the quality of that item. Certification shall not contain statements to imply that the item does not meet requirements specified, such as "as good as," "achieve the same end use and results as materials formulated in accordance with the

Section 16050/R 142 referenced publications," or "equal or exceed the service and performance of the specified material." Certifications shall simply state that the item conforms to the requirements specified.

Certificates shall be printed on the manufacturer's letterhead and shall be signed by the manufacturer's official authorized to sign certificates of compliance.

1.4 OPERATION AND MAINTENANCE MANUAL

Comply with the requirements of the technical sections of Division 16.

1.5 QUALITY ASSURANCE

1.5.1 Material and Equipment Qualifications

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2-years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.

1.5.2 Service Support

The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract. Where two or more items of the same class equipment are required, these items shall be products of a single manufacturer;

however, the component parts of the item need not be the products of the same manufacturer unless stated in the technical section.

1.5.3 Manufacturer's Nameplate

Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.

1.5.4 Modification of References

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction", or words of similar meaning, to mean the Contracting Officer.

1.5.5 DELIVERY AND STORAGE

Handle, store, and protect equipment and materials in accordance with the manufacturer's recommendations and with the requirements of IEC 706. Replace damaged or defective items with new items.

1.6 MANUFACTURER'S RECOMMENDATIONS

Where installation procedures or any part thereof are required to be in accordance with manufacturer's recommendations, furnish printed copies of the recommendations prior to installation.

1.7 ELECTRICAL REQUIREMENTS FOR MECHANICAL EQUIPMENT

Motors, controllers, contactors, and integral disconnects shall be provided with their respective pieces of equipment. Motors, controllers, contactors, and disconnects shall conform to Section

Section 16050/R 143

16402, "Interior Distribution System." Internal wiring for components of packaged equipment shall be furnished as an integral part of the equipment Control voltage for controllers and contactors shall not exceed 220 V nominal. When motors and equipment furnished are larger than size indicated, the cost of additional electrical service and related work shall be included under the section that specified the equipment.

1.8 SERVICE INTERRUPTIONS

Where interruption of existing service is necessary, the Contracting Officer’s Technical

Representative shall be notified in writing at least 15 days in advance. The interruption shall not be made unless authorized. The outage shall be as short a duration as possible and shall take place at a time that will least interfere with normal station activities. The Government will not be responsible for a premium time to perform the work scheduled during the outage.

PART 2 - PRODUCTS

2.1 NAMEPLATES

CEI 16-2. Provide laminated plastic nameplates on each switchboard to identify the load served by each circuit breaker, on the cover of each panelboard indicating panel designation and voltage (i.e.

PANEL L1A 380/220 volt) and on the cover of disconnect switches to identify the load served by the switch. Each nameplate inscription shall identify the function and, when applicable, the position. Nameplates shall be melamine plastic, 2 mm thick, white with black center core. Surface shall be matte finish. Corners shall be square. Accurately align lettering and engrave into the black core. Minimum size of nameplates shall be 25 mm x 60 mm. Lettering shall be a minimum of 6 mm high normal block style.

PART 3 - EXECUTION

3.1 PAINTING OF EQUIPMENT

Equipment painting, factory applied or shop applied, shall be as specified herein, and provided under each individual section of this specification.

3.1.1 Factory Painting System

Manufacturer's standard factory painting system may be provided. If manufacturer's standard factory painting system is being proposed for use in lieu of shop painting systems, the manufacturer's standard factory painting system shall conform to UNI 5687 corrosion resistant test except where UNI 5085 requirements are specified.

3.1.2 Shop Painting Systems

Clean, pretreat, prime and paint metal surfaces; aluminum surfaces shall not be painted. Apply coatings to clean dry surfaces. Clean the surfaces to remove dust, dirt, rust, oil and grease by wire brushing and solvent degreasing prior to application of paint; metal surfaces subject to temperatures in excess of 50 degrees Centigrade (C) shall be cleaned to bare metal. Where more than one coat of paint is specified, apply the second coat after the preceding coat is thoroughly dry.

Lightly sand damaged paint and retouch before applying the succeeding coat.

Section 16303/R 144

SECTION 16303R

UNDERGROUND TRANSMISSION AND DISTRIBUTION LINES

PART 1 - GENERAL

1.1 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

Italian Quality Mark Institute (Instituto Italiano per il Marchio di Qualita’) (IMQ)

Testing and Approval of Materials.

ITALIAN NATIONAL INSTITUTE FOR THE UNIFICATION OF STANDARDS (UNI)

PUBLICATIONS

UNI 6125 (1974) Pipe Threads for Cable Conduits and Screwed Fittings for Explosion Proof Electrical Plants

UNI 7683 (1977 )Threaded Tubes and Fittings for Cable Conduits for Explosion Proof Electrical Installations. Unalloyed Steel Seamless and Welded Tubes, Galvanized.

INTERNATIONAL ELECTROTECHNICAL COMMITTEE (IEC) PUBLICATIONS

IEC 60811 (2001) Common test methods for insulating and sheathing materials of electric cables and optical cables.

IEC 614 (1994) Conduits for electrical installation.

IEC 60454-1-3 (1992) Specification for pressure-sensitive adhesive tapes for electrical purposes.

Italian Electrotechnical Committee (Comitato Elettrotecnico Italiano) (CEI) Publications

CEI 11-1 (1999) Power installation exceeding 1 kV a.c.

CEI 15-15 (2002) Adhesive Tapes for Electrical Purposes.

CEI 20-13 (1999) Cables Insulated with extruded rubber, from 1 kV to 30 kV.

CEI EN 50086 (1996) Protective PVC duct and accessories

CEI 64-8 (2004) Electrical System with Rated Voltage Below 1000 V a.c. and 1500 V d.c.

EN 10255:2007 (2007) Non-Alloy steel tubes suitable for welding and threading - Technical delivery conditions.

IEC 60614 (2002) Conduits for electrical installation.

Section 16303/R 145

IEC 60502 (2007) Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV).

CEI 11-17 (2006) Plant for production, transmission and distribution of electrical power. Cable lines.

CEI 20-62/1 (2006)Requisiti di prova degli accessori per cavi di energia con tensione nominale da 3,6/6 (7,2) kV a 20,8/36 (42) kV.

UNEL 00722 (2000) Cable Color Code for Cable.

UNEL 35026 (2000) Elastomeric or thermoplastic insulated electrical cable rated voltage 1000V a.c. or 1500 V d.c. Ampacity for underground.

Electrotechnical Standardization (Unificazione Elettrotecnica) (UNEL) Publications

UNEL 37118 (1972) Rigid Protective Conduits and Accessories in

Thermoplastic Material. Polyvinyl Chloride Conduit;

Heavy Duty Type.

1.2 GENERAL REQUIREMENTS

Section 16050, "Basic Electrical Materials and Methods", applies to this section with additions and modifications specified herein.

1.2.1 Underground Service

Underground service into buildings shall terminate at a point 1.5 meters outside the building and projections thereof, except that service conductors shall be continuous to the interior terminating point indicated. Connections of the underground service to the substation are included in this section. Ends of underground conduit shall be protected with removable caps until connections are made.

1.2.2 Laboratory Tests

Determine soil-density relationships as specified for soil tests in Section 02315, "Excavation and

Fill".

1.3 SUBMITTALS

1.3.1 Shop Drawings (S) or , Manufacturer's Data (M)

a. Conduit (M)

b. Insulating tape (M)

c. Medium-voltage cables (M)

d. Medium-voltage terminating kits (M)

e. Manhole cast in place (S)

f. Manhole frame and cover (M)

g. Ground rods (M)

h. Low Voltage Cable (M)

Section 16303/R 146

1.3.2 Manufacturer's Instructions

a. Manufacturer's directions for use of ground megger with proposed method indicated.

b. Terminator manufacturer's installation instructions.

1.3.3 Certificates of Compliance

1.3.3.1 Material and Equipment

Provide manufacturer's statement certifying that the product supplied conforms to the requirements specified.

a. Manhole frame and cover.

b. High-voltage cable.

c. High-voltage terminating and splice kits.

1.3.3.2 Workmen's Competency

Thirty days before splicing or terminating is scheduled to begin, submit cable slicer's certificate of competency which shall include a certificate of completion from a splice/terminating kit manufacturer's instruction course, number of years of experience splicing high-voltage cable, and number of successful splices.

PART 2 - PRODUCTS

2.1 MATERIALS AND EQUIPMENT

Provide materials and equipment listed by CEI or approved by IMQ and complete with CE certifications, when such equipment is listed or approved.

2.1.1 Conduit

Conduit for use above grade and as indicated on the drawings shall be rigid hot dipped galvanized steel; conduit for use below grade shall be heavy wall plastic, either direct buried or encased in concrete as indicated. Conduit shall conform to the following:

2.1.1.1 Rigid steel conduit UNI 7683, IEC 614 and UNI 6125 shall have an interior and exterior zinc-coating of uniform quality and appearance throughout all surfaces. They shall consist of steel tubes with threaded fittings, couplings and connecting devices. The tubes shall have nominal trade sizes in inches, outside diameters and wall thickness equal to standard American "Schedule 40" steel pipe. Rigid conduit and fittings shall be manufactured specially for electric wiring purposes.

When manufactured by a continuous weld process, weld beads both inside and outside the tube shall be completely removed prior to galvanizing. Conduit, coupling and fitting threads shall be tapered to conform to the normal iron pipe thread taper of 3/4 inch per foot (6.2%).

2.1.1.2 Plastic conduit and fittings shall be PVC and shall conform to CEI Norms 23-8 for underground large diameter pipes with the Italian mark of Quality, CE certifications. Wall thickness shall be minimum 4.5 millimeters.

2.1.2 Tape

Plastic insulating tape shall conform to the requirements of IEC Section 454 and CEI 15-15.

2.1.3 Wire and Cable

Section 16303/R 147

2.1.3.1 Wire and cable conductor sizes are designated by their nominal cross sectional area given in square millimeters.

2.1.3.2 Conductors rated 600/1000 volts and less, including service entrances, shall conform to C.E.I.

Norm 20-13. All conductors shall be stranded copper. Conductor size and number of conductors in each cable shall be as indicated. Cable shall be color coded. Conductor identification shall be provided within each enclosure where a tap, splice or termination is made. Conductor identification shall be by color coded insulated conductors or plastic coated self sticking tape or markers.

Control circuit terminations shall be identified.

Colors for coding conductors shall be:

380/220 Volt System

Phase L1 - Black Phase L2 - Brown Phase L3 - Red Neutral - Light Blue Grounding Conductor - Green Yellow

2.1.3.3 Cable for 20 kV underground distribution system shall be ozone resistant ethylene propylene rubber insulated cable conforming to CEI 20-13 and IEC Publication 502. Cable shall be single conductor, employing compact round stranded copper conductors. Cable shall have conductor and insulation shielding. Insulation shielding shall be helically applied copper wire or tape. Cable shall be rated 24 kV with insulation and jacket thickness of 8.5 mm and 2.0 mm respectively. Cable shall have a polyvinyl chloride jacket.

2.1.3.4 Termination; Porcelain Insulator Type Terminator

Except as otherwise indicated, terminators for solid insulation non-metallic jacketed cables shall be porcelain insulator type. Apply terminators to single-conductor cables or to each conductor of multiple-conductor cables which are exposed to the weather. The terminator and components shall be the product of one manufacturer and furnish in a package or kit form compatible with the insulation and conductor material. The kit shall include complete assembly and installation instructions. Contractor shall supply one complete copy of manufacturer's instructions and information. The terminator shall conform to CEI NORM 20-26. The terminator shall not exude any insulating filler compound under either test or service. The terminator shall consist of a porcelain insulator, copper cable connector-hoodnut assembly and copper aerial lug as required, metal body and supporting bracket, sealed cable entrance, internal stress relief device for shielded cable, and insulating filler compound or material.

2.1.3.5 Pull Wire

Pull wire shall be plastic having a minimum tensile strength of 100 kg force. Minimum 1 meter of slack shall be left at each end of raceway.

2.1.3.6 Connectors and Terminals

Connectors and terminals shall be designed and approved for use with the associated conductor material, and shall provide a uniform compression over the entire contact surface. Solderless terminal lugs shall be used on all stranded conductors.

2.1.4 Grounding Equipment

Section 16303/R 148

CEI 11-8, ground rods shall be commercially rolled round shape from a welded copper-clad steel manufactured by the molten-welding process or by the electro-formed process (molecularly bonded). They shall have an ultimate tensile strength of 5,270 kg/sq cm. The rods shall be not less than 20 millimeters in diameter by 3.0 meters in length and shall have a hard, clean, smooth, continuous copper surface and the proportion of copper shall be uniform throughout the length of the rod. The copper shall have a minimum wall thickness of 0.5 millimeters at any point on the rod.

Sectional rods are not acceptable.

2.1.5 Manholes

Manholes are referred to throughout this section as "structures" or "underground structure".

2.1.5.1 Provide manholes, frames, covers and accessories as indicated on the drawings and specified herein.

2.1.6 Concrete

Concrete for electrical requirements shall have a compressive strength of Rck=250 (250 kilograms per square centimeter) conforming to the requirements of Section 03300, "Cast-in-Place Concrete".

PART 3 - EXECUTION

3.1 INSTALLATION

Underground installation shall conform to CEI 11-17 CEI 11-18 except as otherwise specified or indicated.

3.1.1 Contractor Damage

The Contractor shall promptly repair any indicated utility lines or systems damaged by Contractor operations. Damage to lines or systems not indicated, which are caused by Contractor operations, shall be treated as "changes" under the terms of the General Provisions of the contract. If the contractor is advised in writing of the location of a non-indicated line or system, such notice shall provide that portion of the line or system with "indicated" status in determining liability for damages.

In any event, the Contractor shall immediately notify the Contracting Officer’s Technical Representative of any such damage.

3.1.2 Underground Duct with Concrete Encasement

Shall be constructed of individual conduits encased in concrete. The type of conduit used shall not be mixed in any duct bank. Ducts shall be a minimum of 110 mm in diameter unless otherwise indicated. The concrete encasement surrounding the bank shall be rectangular in cross-section and shall provide at least 75 mm of concrete cover for ducts. Separate conduits by a minimum concrete thickness of 50 mm, except separate light and power conduits from control, signal, and telephone conduits by a minimum concrete thickness of 75 mm.

3.1.2.1 The top of the concrete envelope shall be a minimum of 500 mm below grade, except under roads and pavement, concrete envelope shall be a minimum of 600 mm below grade.

Section 16303/R 149

3.1.2.2 Duct banks shall have a continuous slope downward toward underground structures and away from buildings with a minimum pitch of 75 mm in 30 meters. Except at conduit risers, changes in direction of runs exceeding a total of 10 degrees, either vertical or horizontal, shall be accomplished by long sweep bends having a minimum radius of curvature of 7.5 meters; sweep bends may be composed of one or more curved or straight sections or combinations thereof.

Manufactured bends shall have a minimum radius of 50 cm for use with conduits of less than 80 mm in diameter and a minimum radius of 1.5 meters for ducts of 80 mm in diameter and larger.

Excavate trenches along straight lines from structure to structure before ducts are laid or structure constructed so the elevation can be adjusted, if necessary, to avoid unseen obstructions.

3.1.2.3 Terminate conduits in end-bells where ducts enter underground structures. Stagger the joints of the conduits by rows and layers to strengthen the duct bank. Provide plastic duct spacers that interlock vertically and horizontally. Spacer assembly shall consist of base spacers, intermediate spacers, and top spacers to provide a completely enclosed and locked-in duct bank. Install spacers as per manufacturer's instructions, but provide a minimum of two spacer assemblies for each 3 meters of duct bank. Before pouring concrete, anchor duct bank assemblies to prevent the assemblies from floating during concrete pouring. Anchoring shall be done by driving reinforcing rods adjacent to every other duct spacer assembly and attaching to rod to the spacer assembly.

3.1.2.4 As each section of a duct bank is completed from structure to structure, a testing mandrel not less than 30 cm long with a diameter 6 mm less than the inside diameter of the conduit shall be drawn through each conduit, after which a stiff-bristled brush, having the diameter of the conduit, shall be drawn through until the conduit is clear of earth, sand, and gravel particles. Conduit plugs shall then be immediately installed.

3.1.2.5 New conduit indicated as being unused or empty shall be provided with plugs on each end.

Plugs shall contain a weephole or screen to allow water drainage. Provide a plastic pull rope having 1 meter of slack at each end of unused or empty conduits.

3.1.2.6 Connections to Manholes

Duct bank envelopes connecting to underground structures shall be flared to have an enlarged cross-section at the manhole entrance to provide additional shear strength. The dimensions of the flared cross-section shall be larger than the corresponding manhole opening dimensions by no less than 30 cm in each direction. The perimeter of the duct bank opening in the underground structures shall be flared toward the inside or keyed to provide for a positive interlock between the duct bank and the wall of the structure. Vibrators shall be used when this portion of the envelope is poured to ensure a seal between the envelope and the wall of the structure.

3.1.2.7 Partially Completed Duct Banks

During construction wherever a construction joint is necessary in a duct bank, prevent debris such as mud, sand, and dirt from entering ducts by providing suitable conduit plugs. Fit concrete envelope of a partially completed duct bank with reinforcing steel extending a minimum of 60 cm back into the envelope and a minimum of 60 cm beyond the end of the envelope. Provide one Ø10 mm bar in each corner, 75 mm from the edge of the envelope. Secure corner bars with two DN 10 mm ties, spaced approximately 30 cm apart. Restrain reinforcing assembly from moving during concrete pouring.

3.1.3 Underground Conduits for Service Conductors Into Buildings

Shall be rigid steel conduits from the service equipment to a point 1.5 meter beyond the building and projections thereof. Protect the ends of the conduit by caps or bushings. Clean and plug conduit until conductors are installed. Encase the underground portion of the conduit in a concrete envelope and bury as specified for underground duct with concrete encasement.

3.1.4 Concrete for Electrical…