Attachment 2 - Comm Data Drops, Camera Tv Locations, and Rack Elecations
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Comm Data Drops, Camera & TV locations, and Rack Elevations for B1469
Renovation
*Drawings not to scale
Ground Level - Left = CCTV Rack = CCTV Camera= 2 LAN Cables
= 4 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
= AFN Rack
= Television
Ground level - Right = CCTV Rack = CCTV Camera= 2 LAN Cables
= Wall Addition
= Wall Deletion = Plywood Backboard
= Comm Rack = AFN Rack
= 75mm Conduit
Ground level – Ballroom = CCTV Rack = CCTV Camera= 2 LAN Cables
= Wall Addition
= Wall Deletion
= 2 x 75mm Conduit
= Comm Rack
= AFN Rack
= Television
= A/V Rack= 100mm Conduit
Sliding Doors
*Ensure there are sound-rated doors in the three wall openings
*All conduits must have a pull box every 10m.
Stage
Stage
StairsT ec h R o o m
/S ta g e
S ta g e
C o n tr o l
E m er g en cy C o rr id o r
Stairs
Stairs
First Level - Left
Relocate this Cable Tray system
To where the rack will be located.
Will be used for backbone fiber and ground wire only
= 2 LAN Cables
= 4 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
= AFN Rack
= Television
= CCTV Rack = CCTV Camera= 2 LAN
= 4 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
First Level – Right
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
= AFN Rack
= Television
= CCTV Rack = CCTV Camera= 2 LAN Cables
= 4 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
Second Level - Left = CCTV Rack = CCTV Camera= 2 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
= AFN Rack
= Television
Relocate this Cable Tray system
To where the rack will be located.
Will be used for backbone fiber and ground wire only
Second Level - Right = CCTV Rack = CCTV Camera= 2 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
= AFN Rack
New double door
Third Level = CCTV Rack = CCTV Camera= 2 LAN Cables
= Wall Addition
= Wall Deletion
= Plywood Backboard
= Comm Rack
Rack Elevations GL & FL
First Level
12-st FOC MM ISP FODP (1RU)
UPS (2RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
48-port CAT6 Patch Panel (2RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
Cable Management (1RU)
Cable Management (1RU)
Ground Level
24 port CAT6 Patch Panel for CCTV (1RU)
UPS (2RU)
CCTV System (Includes server, recording system, power supply, switches, etc… based on
FSS Tech solution (RUs unspecified)
Cable Management (1RU)
Cable Management (1RU)
This Rack is reserved and should coordinated by the customer and AFN on technical solutions.
Ensure AFN customers are contacted to generate requirements. Solution should include AFN over fiber solutions. Fiber Optic Cabling will be provided by SRM project.
UPS (2RU)
24-st FOC SM OSP FODP (1RU)
UPS (2RU)
1st Lvl 12-st FOC MM ISP FODP (1RU)
3rd Lvl 12-st FOC MM ISP FODP (1RU)
2nd Lvl 12-st FOC MM ISP FODP (1RU)
12-port Fiber Dist. Switch (1RU)
Cable Management (1RU)
Cable Management (1RU)
Cable Management (1RU)
Cable Management (1RU)
48-port CAT6 Patch Panel (2RU)
48-port CAT6 Patch Panel (2RU)
48-port CAT6 Patch Panel (2RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
Cable Management (1RU)
48-port NIPR CAT6 Access Switch (1RU)
Cable Management (1RU)
Rack Elevations SL & TL
Second Level
12-st FOC MM ISP FODP (1RU)
UPS (2RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
48-port CAT6 Patch Panel (2RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
Cable Management (1RU)
Cable Management (1RU)
48-port NIPR CAT6 Access Switch (1RU)
Cable Management (1RU)
Cable Management (1RU)
Third Level
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
UPS (2RU)
12-st FOC MM ISP FODP (1RU)
Cable Management (1RU)
48-port CAT6 Patch Panel (2RU)
Cable Management (1RU)
Example of Wall-mounted quarter server rack.
All Racks except for the quarter rack on the third level shall be
Full-sized with exhaust fans located at the top. Each rack must
Be bolted down to the floor to prevent accidental movement.
Server racks are a must due to the size of UPS and airflow
Required for cooling down network equipment. Use the picture
On the right as an example of a full-sized server rack. Placement
Of all racks must have a clearance of 36” in the front or back
And a 24” clearance on at least one side. If it is wall-mounted, The rack must be able to pivot open to expose the back so access
Is provided for maintenance/new installs. Thus, the front will
Maintain a 36” clearance and both sides must have 24” clearance.
The height of the wall-mounted rack will be 2m and will have on
It reflective warning tape for safety.
All NIPR and Fiber switches and UPS are to be government-furnished
Equipment (GFE). All other hardware are to be supplied and
Installed by the contractor. Customer will create CIPS WO to
Purchase necessary switches and UPS.
Rack Requirements and Equipment
Grounding Requirements
= Telecommunications Main Grounding Busbar (TMGB)
= Telecommunications Room Busbar
= Rack Busbar)
= Two-hole Compression-type Grounding Lug
*All surfaces must be brushed clean/polished
And coated with non-oxidizing compound prior