(Attachment 62)SABER Seed SOO Honor Guard Building 10250Attachment 9 -Asbestos and Lead testing for installing air compressor.pdf
PDF 2 MB Posted
- Attached to
- SABER IDIQ
- Solicitation number
- FA486125R0003
About this file
This is an Asbestos and Lead Based Paint Inspection Report for Nellis Air Force Base, specifically focused on Building 10250. Macrotec Consulting, LLC conducted an inspection on 9/29/2011 with the primary objective of identifying potential asbestos and lead-based paint materials that could be impacted during planned renovation activities. The specific work order scope involves installing an air compressor in room 106 and routing air lines to room 102.
Laboratory analysis of three samples (concrete foundation, cinderblock, and mortar) from room 106's north side and north wall revealed no asbestos or lead-based paint detected. A Base Civil Engineer Work Request dated 10/7/2011 substantiates the air compressor installation, with the justification that compressed air is required to operate several pieces of aircraft flight equipment. The work was requested by MSgt Anthony Doering, with a required completion date of 10/21/2011, and was approved by the Ops Chief on 8/31/2011.
View the file
Other files
Show 40 more
Latest 50 of 126 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Nellis Air Force Base Asbestos and Lead Based Paint Inspection Report
Work Order Scope of Work:
Install air compressor in room 106.
Note: The interior and adjacent exterior walls of room 102 were found to have no asbestos or lead based paint issues in a report dated July 25, 2007.
Building Number: 10250
Inspection Date: 9/29/2011
Nellis Work Order: 18080
Macrotec Job Number: 11870
The information contained in this report pertains only to the specific area defined in the above scope of work. This summarized report is for reference purposes, only. A detailed generic report is on file with Nellis Air Force Base Civil Engineering. Only proper personnel should interpret this report to determine whether the information herein can be utilized for current and future renovation activities within the building
Macrotec Consulting, LLC. performed an inspection for Asbestos Containing Building Materials and Lead Based Paint. The intent of this inspection was to identify materials containing asbestos and lead, within the subject site, that may be impacted during planned renovation activities.
Introduction:
Report Limitations:
9724 Mild Weather Ct., Las Vegas, NV 89148 Phone: (702) 338-8213 Fax: (702) 629-5677
Macrotec Consulting, LLC.
Appendix A - Asbestos Assessment
Macrotec Job #11870 - Bldg. 10250 ; WO #18080
The following table lists each of the materials suspected to contain asbestos at the subject site. For each material the sample number, location and laboratory result are listed. If the material was found to contain asbestos, the friablity and NESHAP classification is identified.
1 Concrete Foundation No Asbestos Detected
AB1 Room 106 - N side None Detected
2 Cinderblock No Asbestos Detected
AB2 Room 106 - N wall None Detected
3 Mortar No Asbestos Detected
AB3 Room 106 - N wall None Detected
Asbestos Survey
Bldg. 10250
Macrotec Job #11870
Macrotec Consulting, LLC.
Appendix B - Lead Assessment
Macrotec Job #11870 - Bldg. 10250 ; WO #18080
No suspect lead paint was identified during this investigation, based on the specific scope of work for the project. If suspect materials are found during renovation activities outside what was identified in this report, stop work immediately until further testing can be completed.
Lead Paint Survey
Bldg. 10250
Macrotec Job #11870
Asbestos & Lead Based Paint Survey
Nellis AFB, Bldg. 10250
Macrotec Project # 11870
Appendix C
* Diagram Not Drawn To Scale
Sample Location Diagram
N
AB3AB1 AB2
Macrotec Consulting
TRIANGLE ENVIRONMENTAL SERVICE CENTER, INC.
13509 East Boundary Road, Suite B, Midlothian, VA 23112
804-739-1751 • fax: 804-739-1753
BULK ASBESTOS SAMPLE ANALYSIS SUMMARY
9724 Mild Weather Ct.
Las Vegas, NV 89148
11870
Bldg 10250
110930AN
9/30/2011
10/1/2011
10/2/2011
F. JiangJOB SITE:
TESC LOGIN #:
DATE OF RECEIPT:
DATE OF ANALYSIS:
DATE OF REPORT:
ANALYST:
TESC
SAMPLE #
CLIENT SAMPLE ID
& GROSS DESCRIPTION
ESTIMATED
% ASBESTOS
NON ASBESTOS
% FIBERS
NON FIBROUS
% MATERIALS
CLIENT:
CLIENT JOB/ #:
1 AB1 / Gray granular NAD 100%
2 AB2 / Gray granular NAD 100%
3 AB3 / Gray granular NAD 100%
Total Samples/Layers Analyzed: 3
Sunday, October 02, 2011 Page 1 of 1
Samples are analyzed in accordance with “Interim Method for the Determination of Asbestos in Bulk Insulation Samples”, EPA/600/R-93-116, July 1993
(EPA-600/M4-82-020, Dec 1982), or the current US EPA method for the analysis of asbestos in building material. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or
Transmission Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report must not be reproduced except in full with approval of Triangle Environmental Service Center, Inc. This test report relates only to the item(s) tested.
NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound] [
Reviewed By Authorized Signatory:
Feng Jiang, MS Senior Geologist, Laboratory Director
Yuedong Fang, Senior Geologist
| 110930an |
| CCF01022011_00013 |