(Attachment 65) SABER Seed SOO Honor Guard Building 10250 Attachment 12 - Mech. Room Report.pdf

PDF 673 KB Posted

Attached to
SABER IDIQ
Solicitation number
FA486125R0003
Issued by

About this file

This document is an Asbestos Hazard Inspection Report for Building 10250 at Nellis Air Force Base, prepared by Macrotec Consulting, LLC on August 4, 2016. The inspection, conducted by certified asbestos inspector Dustin R McAllister, focused on identifying the presence of asbestos-containing Thermal System Insulation (TSI) and Surfacing Material in the building's mechanical room and mechanical yard. Laboratory testing of two samples (black pipe wrap and mud on HVAC ducts) by Triangle Environmental Service Center revealed No Asbestos Detected (NAD), with one sample containing 20% fiberglass and the other 100% non-fibrous materials.

The report emphasizes that while no asbestos-containing materials were found in the mechanical room and yard, additional suspect asbestos-containing materials may exist in other areas of the building. The inspection was not a comprehensive NESHAP (National Emission Standards for Hazardous Air Pollutants) assessment for renovation purposes, but rather a targeted examination of specific mechanical areas. Photographic documentation was included to show the inspected areas, which consisted of one mechanical room with a black pipe wrap and one mechanical yard with bare pipes and HVAC ducts.

View the file

Other files

File Type Posted
Solicitation Amendment FA486125R00030017 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030017.pdf PDF
Atch 80_ RFI Response Log_General Solicitation 9 March 2026.xlsx XLSX spreadsheet
Solicitation Amendment FA486125R00030016 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030016.pdf PDF
Solicitation Amendment - FA486125R00030015.pdf PDF
Solicitation Amendment FA486125R00030015 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030014.pdf PDF
3 - Self Scoring Matrix 17 Feb 26.xlsx XLSX spreadsheet
Solicitation Amendment FA486125R00030014 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030013.pdf PDF
Solicitation Amendment FA486125R00030013 SF 30.pdf PDF
Attach 79 RFI Log SABER Seed 29 Jan 2026_.xlsx XLSX spreadsheet
Att 78 RFI Log Additional Responses General Solicitation 27 Jan 2026_.xlsx XLSX spreadsheet
Att 3 -Self Scoring Matrix 3_Feb_2026.xlsx XLSX spreadsheet
44- SABER SOO RKMF240010 Renovate Honor Guard 99 FSS B10250_28January2026 (003).pdf PDF
Solicitation Amendment FA486125R00030012 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030012.pdf PDF
Solicitation Amendment FA486125R00030011 SF 30 .pdf PDF
1 - SABER SOW 7 Jan 2026.pdf PDF
Solicitation Amendment - FA486125R00030011.pdf PDF
2 - Price Schedule _13 Jan 2026.xlsx XLSX spreadsheet
3 - Self Scoring Matrix 7_Jan 26.xlsx XLSX spreadsheet
77 - RFI Response Log SABER Seed Related _ 13_Jan 2026.xlsx XLSX spreadsheet
Solicitation Amendment - FA486125R00030010.pdf PDF
44 -Statement of Objectives (SOO) for RKMF 240010 20 Nov 25.pdf PDF
Attach 75 SABER Seed Attachment 19 - B10250 comm room.pdf PDF
Attach 74 SABER Seed Attachment 18 - Knox Box Location.pdf PDF
73 - Task Order Pricing Letter _ Gordian System Licens Fees 5 percent and 1.95 percent.pdf PDF
1- SABER SOW 7 Jan 2025 .pdf PDF
76 - RFI Response Log General Solicitation 13_Jan 26.xlsx XLSX spreadsheet
Solicitation Amendment FA486125R00030010 SF 30.pdf PDF
Solicitation Amendment - FA486125R00030009.pdf PDF
Solicitation Amendment FA486125R00030009_SF 30.pdf PDF
Solicitation Amendment FA486125R00030007 SF 30.pdf PDF
Solicitation Amendment FA486125R00030006 SF 30.pdf PDF
(Attachment 66) SABER Seed SOO Honor Guard Building 10250 Attachment 13 - Asbestos and Lead testing building history.xlsx XLSX spreadsheet
Solicitation Amendment - FA486125R00030006.pdf PDF
Attachment 72 SABER IDIQ Preproposal Sign In Sheet 29 October 2025 FA486125R0003.pdf PDF
(Attachment 63) SABER Seed SOO Honor Guard Building 10250 Attachment 10 - Asbestos and Lead testing dated 24 February 2014.pdf PDF
(Attachment 68) SABER Seed SOO Honor Guard Building 10250 Attachment 15 - B10250 room numbers.pdf PDF
(Attachment 55) SABER Seed SOO Honor Guard Building 10250 Attachment 1 - HAZMAT Results 10250 Restrooms Part 1.pdf PDF
(Attachment 58) SABER Seed SOO Honor Guard Building 10250 Attachment 5 - Attachment 5 AFGIMS Utilities Snapshot.pdf PDF
(Attachment 69) SABER Seed SOO Honor Guard Building 10250 Attachment 16 - 10250 BFP Device replacement.png PNG image
(Attachment 57) SABER Seed SOO Honor Guard Building 10250 Attachment 3 - As-Builts 65 LOCATION and GRADING.pdf PDF
(Attachment 70) SABER Seed SOO Honor Guard Building 10250 Attachment 17 - Double Check Valve Assembly.pdf PDF
(Attachment 60) SABER Seed SOO Honor Guard Building 10250 Attachment 7 - Sewer Line with Measurements and Pictures.pdf PDF
Attachment 71 SABER IDIQ Preproposal Conference Slides 29 October 2025 FA486125R0003.pptx PPTX presentation
(Attachment 61) SABER Seed SOO Honor Guard Building 10250 Attachment 8 - Asbestos and Lead testing of entire building dated 7 July 2007.pdf PDF
(Attachment 59) SABER Seed SOO Honor Guard Building 10250 Attachment 6 - Floorplan Conceptual.pdf PDF
Show 40 more

Latest 50 of 126 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Nellis Air Force Base Asbestos Hazard Inspection Report

Building Number: 10250

The information contained in this report pertains only to the specific rooms identified.

Macrotec made an effort to identify and inspect each of the building's mechanical rooms, however there may be instances where they may have not been identified or been in high security rooms, etc. Building diagrams were not always provided and when they were, were sometimes out of date. Macrotec also noted if there are suspicions of, or visual evidence of suspect TSI or Surfacing Materials in areas other than the mechanical room, however, Macrotec cannot warrant that there are not additional suspect materials outside of the mechanical rooms identified. Only proper personnel should interpret this report to determine whether the information herein can be utilized.

On 8/4/2016, Dustin R McAllister, a certified asbestos inspector for Macrotec Consulting, LLC., performed an inspection to identify the presence or absence of asbestos hazards in the mechanical room(s) of the building. Specifically, Macrotec inspected for the presence of asbestos containing Thermal System Insulation (TSI) and Surfacing Material and made a determination of the condition of these materials, if present. Note that this inspection is not a NESHAP inspection that would identify asbestos containing building materials for the purpose of renovating the rooms or components in the rooms.

No asbetos containing TSI or Surfacing Material were found in the mechanical room(s) of building 10250. Please note that these materials and other suspect asbestos containing materials may be present in other areas of the building.

Report Limitations:

Bldg. 10250 has one mechanical room and one mechanical yard. The mechanical room one black pipe wrap that does not contain asbestos. The mechanical yards has bare pipes and mud on HVAC ducts that was tested and found to not contain asbestos.

Building 10250 Inspection Details:

Introduction:

Office@MacrotecConsulting.com Phone: (702) 949-6225 Fax: (702) 629-5677

Mech. Room Investigation Macrotec Project # 16603 Nellis Air Force Base, Bldg. 10250 Appendix A

Building 10250 has one mechanical room and one exterior mechanical yard. Above is the mechanical room that has one black pipe wrap that was tested and found to not contain asbestos.

The mechanical yard has mud on HVAC duct that was tested and found to not contain asbestos.

Above is the another picture of the mechanical room that has bare ducts an bare pipes

The mechanical yard has bare pipes.

Appendix B - Assessment

Macrotec Job #16603 - Building 10250

Laboratory reports are attached with this report (if samples were collected). Please note that the primary purpose of this inspection was to determine the presence of TSI or Surfacing Material in the mechanical rooms/areas. Additional suspect asbestos containing TSI or Surfacing Material may be present in other rooms/areas of the building.

Mechanical Room

One black pipe wrap

No ACM Present : Samples Collected :

Mechanical Yard

Bare pipes and mud on HVAC ducts

No ACM Present : Samples Collected :

Asbestos Inspection

Building 10250

Macrotec Job #16603 Appendix B

Macrotec Consulting

TRIANGLE ENVIRONMENTAL SERVICE CENTER, INC.

13509 East Boundary Road, Suite B, Midlothian, VA 23112

804-739-1751 • fax: 804-739-1753

BULK ASBESTOS SAMPLE ANALYSIS SUMMARY

9724 Mild Weather Ct.

Las Vegas, NV 89148

16603-10250

WO #28328 - Bldg. 10250

160809X

08/09/2016

08/10/2016

08/10/2016

B.TrimmerJOB SITE:

TESC LOGIN #:

DATE OF RECEIPT:

DATE OF ANALYSIS:

DATE OF REPORT:

ANALYST:

TESC

SAMPLE #

CLIENT SAMPLE ID

& GROSS DESCRIPTION

ESTIMATED

% ASBESTOS

NON ASBESTOS

% FIBERS

NON FIBROUS

% MATERIALS

CLIENT:

CLIENT JOB:

100%AB1 / Black foam NAD1

20% Fiberglass 80%AB2 / Foil, white fibers, gray adhesive NAD2

Total Samples/Layers Analyzed: 2

August 10, 2016 Page 1 of 1

Samples are analyzed in accordance with “Interim Method for the Determination of Asbestos in Bulk Insulation Samples”, EPA 600/M4-82-020, Dec. 1982 and "Method for the Determination of Asbestos in Bulk Building Materials", EPA 600/R-93/116, July 1993. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or Transmission

Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report shall not be reproduced, except in full written approval of Triangle Environmental Service Center, Inc. This report must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. This test report relates only to the item(s) tested.

NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound] [

Reviewed By Authorized Signatory:

Feng Jiang, MS Senior Geologist, Laboratory Director

Yuedong Fang, Senior Geologist

Macrotec Consul , LLC

Client Name Nellis Bulk Sampling Chain of Custody Form

Project Name Bldg' 7O25O

Project Location lrJO #25328 - Bldg. IO2SO Technician _Dus'tin R /llc1llister Laboratorv .rE:;c

Stop at 1st pol;itive?: y / N Composite Wall Substrate?: y / N

Project Number

Collection Date

WO Number

7(;603-70250 a/4/2076 ,28325

Turn Around Time

Method of Analysis

Matrix Eulk

3 DaLl

,PLm

Sample # H # lCount

Sample Description Material Type : Color / Deserinr sampreto,ffi (General : Room : Soecifie\ nE/ nB2

P,'pe l,tttrqp - Black lnterior - //lech Room - N :;ide

Exterior - /llech yard - ld side

Relinquished By:

Relinquished By:

( neceiveo

Received By:

As Lab 10250.pdf