Drawings - Mechanical - 1.pdf
PDF 10 MB Posted
- Solicitation number
- QSE--36C10F24R50025
About this file
This document appears to be mechanical drawings for the Biloxi Building 1 Renovation project, which is the subject of a federal solicitation issued by the Department of Veterans Affairs Office of Construction and Facilities Management.
The solicitation (Solicitation Number: QSE--36C10F24R50025) is for the renovation of Building 1 in Biloxi, Mississippi. The work includes selective demolition, exterior building envelope alterations, and interior renovation of areas within the building. It also involves upgrades to the interior utilities and building systems such as HVAC, plumbing, electrical, telecommunications, and fire protection. The period of performance is 912 calendar days from the receipt of the Notice to Proceed, and the project magnitude is between $50M to $100M. The contract will be subject to Wage Rate Requirements (Construction). The solicitation requires the contractor to monitor the existing Building 1 foundation system throughout the project duration.
View the file
Other files
Show 40 more
Latest 50 of 64 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
UPUP
UP
1 2 3 4 5 6 7 8 9
11 12
14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
CENTRAL STAIR
2A101
WEST STAIR
2B110
EAST STAIR
2A133
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
ENG. SHOP STORAGE
OFFICE
STOR.
OFFICE
OFFICE
STOR.
STOR.
OFFICE
HAC
STOR.
STOR.
STOR.
OFFICE
OFFICE
OFFICE
OFFICE
STOR.
STOR.
OFFICE
OFFICE
ELEC TELE
OFFICE
OFFICE
OFFICE
EXAM EXAM
OFFICE
TOILET
HAC
ELEC
STOR.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CONF. ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
OFFICEOFFICE
OFFICE
STARBUCKS
TOILET
1 2 3 1 3
3 4
3 4 5
1 2 4
1 4 7
1 2 1 2
3 5
1 4 5
1 2 4
1 3
1 3 4
1 3 5
1 3 5
1 2 3
1 2 4 5
7 6
2 3 3
2 3
1. WHERE DUCTS, CABLE TRAYS, PIPING, ETC. PENETRATIVE PARTITIONS ABOVE CEILINGS, CAULK AND/OR PACK JOINT WITH FIRESTOPPING MATERIALS TO RETAIN FIRE RATING. AT SMOKE RESISTIVE PARTITIONS, PREVENT PASSAGE OF SMOKE AT ALL PENETRATIONS. ALSO PREVENT TRANSMISSION OF SOUND THROUGH
PENETRATION OF WALL DUCTS, PIPES, CONDUITS, ETC.
2. REROUTE/RELOCATE EXISTING EQUIPMENT, CHILLED AND HOT WATER PIPING, DUCTWORK, DOMESTIC COLD AND HOT WATER PIPING, ELECTRICAL CONDUIT, ELECTRICAL DEVICES AND CABLING AS REQUIRED TO ALLOW FOR STRUCTURAL MODIFICATIONS. DO NOT REINSTALL ANCHOR, HANGERS OR SUPPORTS FROM
BEAMS BEING MODIFIED.
3. COORDINATE DOWNTIME WITH OWNER PRIOR TO WORK.
4. REFER TO DRAWING AE102 FOR INFORMATION REGARDING PHASING OF WORK ON THE SECOND FLOOR.
GENERAL SHEET NOTES
RELOCATE EXISTING DUCT AND ASSOCIATED HANGERS TO ALLOW FOR
STRUCTURAL MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM
AWAY FROM STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH
OWNER PRIOR TO WORK
RELOCATE EXISTING PIPING AND ASSOCIATED HANGERS TO ALLOW FOR
STRUCTURAL MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM
AWAY FROM STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH
OWNER PRIOR TO WORK
RELOCATE EXISTING METAL CONDUIT TO ALLOW FOR STRUCTURAL
MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM AWAY FROM
STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH OWNER PRIOR TO
WORK
REMOVE EXISTING METAL ALL-THREAD HANGER RODS TO ALLOW FOR
STRUCTURAL MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM
AWAY FROM STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH
OWNER PRIOR TO WORK
TEMPORARLY REMOVE EXISTING CABLING TO ALLOW FOR STRUCTURAL
MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM AWAY FROM
STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH OWNER PRIOR TO
WORK
RELOCATE EXISTING SPRINKLER PIPING TO ALLOW FOR STRUCTURAL
MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM AWAY FROM
STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH OWNER PRIOR TO
WORK
REMOVE EXISTING WIRE HANGERS TO ALLOW FOR STRUCTURAL
MODIFICATIONS. RELOCATE HANGERS TO EITHER SIDE OF BEAM AWAY FROM
STRUCTURAL MODIFICATIONS. COORDINATE DOWNTIME WITH OWNER PRIOR TO
WORK
SPECIFIC NOTES SHEET ME100
STRUCTURAL REPAIRS LEGEND
LOCATION OF SIKA FRP STRIPS AROUND BEAM
ESTIMATED WORK AREA. ACOUSTICAL CEILING OR GYP BOARD CEILING TO
BE REMOVED TO ACCOMPLISH WORK MAY BE MORE EXTENSIVE DUE TO
REMOVAL AND REPLACEMENT OF EXISTING UTILITIES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:4
P M
ME100
2ND FLOOR ABOVE CEILING
STRUCTURAL FIXES
RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
172 238
1/8" = 1'-0"ME100
1 FLOOR PLAN - LEVEL 2 MP&E
N O
R T
H
Revisions: Date:
- STRUCTURAL UPGRADES 4-3-2017
S
S S
S
S S
S
S S
S
S S SS
S S
S
S
S
S S
S S
S
S S
S S
SS S
S
S
S S
S
S
SS S
S
S
S
S
S S
S S
S S
S
S
S
S S
S
S S
S
SS SS
S S
S S
S
S S
S S
S S
S S
S
S
S
S
S
S
S S
S
S
S
S S
S S
S
S
S SS
S
S S
S
S
S S
S S
S
S
S
S S
S
S SS S
S S
S
S
S
S
S
S SS S S SS SSS SS
S
S
S SS
S
S
S
S
S
S
S
S S
S
S S S
S
S S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
FEC FEC FEC
SL
RC
SL
RC
EB
SL
RC
SA
EB
SL
EB
SC
SC
RC
RC
RC
SC
SC
RD
SL
EB
SL
EB
SC
SC
EE
RE
SA
RD
ED
RE
SJ
SJ
SL
EB
SL
EB
SJ
SC
SJ
SJ
SJ
SJ
SF
SA
SL
EB
EB
SL
SL
EB
SC
SB
SB
SC
RC
SB
RB
RB
SA
RA
SA
RA
SB
SC
RD
335SL
EB
SB
RB
SA
SA
SA
RA
SA
EB
SL
EB
SA
RF
RF
RD
SA
RA
SK
SK
SK
SK
SK
VAV
5-01
VAV
5-03
VAV
5-04
VAV
5-05
VAV
5-06
VAV
5-08
VAV
5-09
VAV
5-10
VAV
5-11
VAV
5-12
VAV
5-14
VAV
5-15
VAV
5-21
VAV
5-22
VAV
5-23
VAV
5-24
VAV
5-26
VAV
5-27
VAV
5-28
VAV
5-29
VAV
5-25
VAV
5-30
VAV
5-31
VAV
5-32
VAV
5-33
RE
VAV
5-02
42"x14"
"x
"Ө
"x
56"x20"
10"x10"
16"x12"
SC
SC
SC
SC
SC
SC
SC
SC
ED
SC
SC
SC
SC
280SC
SC
SC
SC
SC
SC
SC
SC
SB
SJ
18x14 GENERAL EXHAUST 20x16 GENERAL EXHAUST
16x18 ISOLATION EXHAUST
16x18 ISOLATION EXHAUST
MH301
42"x14" 44"x16"
34"x16"Ө
34"x16"Ө
SL
EB
RB
RA
SD
RC
RE
EA
EA
SL
SL
SL
EA
SL
EA
EB
SL
EA
RC
RC
SC
EA
SL
SL
EA
EA
28"x14"Ө18"x12"Ө 26"x12"Ө
"x
"Ө
20"x12"
"x
"Ө
12"x10" 12"x10"
8"x8"
12"x10"
12"x10" 8"ø
12"ø
10"x8"
24"x10"
10"ø 14"x10"
10"ø
10"ø
14"x10"
14"x14"
14"x12"
10"x8"
16"x10"
14"x14"
14"x12"
12"ø
8"x8"
12"x10" 12"x10"
34"x16"Ө
12"ø
8"ø
12"x10" 14"ø
20"x10"
12"x10" 12"x10" 12"x10" 12"x10"
12"x10"
12"x10"
10"x10"
8"x8"
6"x6"
14"x10"
18"x8"
12"x12"
12"ø
10"ø
12"x12"
14"x8" 12"x10"
10"ø
18"x10"
20"x12"
8"x8"
22"x10"
RC
SC
SC
SC
RA
12"x10"
RE
SC
16"x8"
F S
D
F S
D
VAV
5-18
VAV
5-20
VAV
5-19
VAV
5-17
VAV
5-16
PATIENT ROOM 1
3B114
PATIENT ROOM 2
3B116
PATIENT ROOM 3
3B118
PATIENT ROOM 4
3B119 CLEAN EQUIPMENT STORAGE
3B121
M D
D
IC
TA
TI
O N
3B
PATIENT ROOM 5
3B123
PATIENT ROOM 6
3B124
WHEELCHAIR ALCOVE
3B102
ELECTRICAL ROOM
3B101
PATIENT CENTERED CARE
3B103
MEDICAL GAS STORAGE
3B104
CRASH CART
3B105
HAC
3B106
CLEAN UTILITY
3B107
CLEAN LINEN
3B108
KINESIOTHERAPY
3B109
WEST STAIR
3B110
PATIENT ROOM 7 - NEGATIVE
PRESSURE
3B111
UNASSIGNED
3B113
PATIENT BATHROOM
3B111A
ANTE ROOM
3B111B
PATIENT BATHROOM
3B114A
PATIENT BATHROOM
3B116A
PATIENT BATHROOM
3B118A P
A
TI
E N
T B
A
TH
R O
O M
3B
9A
PATIENT BATHROOM
3B123A
PATIENT BATHROOM
3B124A
C O
R R
ID
O
R
C 3-
CENTRAL STAIR
3A101
MALE TOILET
3A102
FEMALE TOILET
3A103
FAMILY TOILET
3A104
WAITING / LOUNGE
3A105
FAMILY CONSULTATION
3A106
MECHANICAL SHAFT
3A107
SOILED LINEN
3A110
ENGINEERING
3A111
HEAD NURSE / ASSISTANT MANAGER
3A112
M E
D
IC
A
TI
O N
R O
O M
3A
NOURISHMENT STATION
3A115
PATIENT ROOM 8
3A117
PATIENT ROOM 9
3A118
MD DICTATION
3A120
IMD SUPPLY STORAGE
3A121
PATIENT ROOM 10
3A122
PATIENT ROOM 11
3A123
BARIATRIC PATIENT ROOM 12
3A125
CONFERENCE / REPORT ROOM
3A128
PATIENT BATHROOM
3A117A
PATIENT BATHROOM
3A118A
PATIENT BATHROOM
3A122A
PATIENT BATHROOM
3A123A
BARIATRIC PATIENT BATHROOM
3A125A
HAC
3A127
TELEMETRY
3A130
BARIATRIC PATIENT BATHROOM
3A131A
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
3A131
ANTE ROOM
3A131B
EAST STAIR
3A133
PHARMACY CUBICLES
3A134
MALE LOCKERS
3A137
STAFF TOILET
3A136
STAFF SHOWER
3A135
CORRIDOR
3A141
STAFF LOUNGE
3A138
FEMALE LOCKERS
3A139
TELECOMM
3A140
SOILED UTILITY
3A142
NURSE STATION
3A109A
CORRIDOR
C3-105
CORRIDOR
C3-103
NURSE SERVER
3A124
C O
R R
ID
O
R
C 3-
NURSE SERVER
3A132
CORRIDOR
C3-101
NURSE SERVER
3B112
NURSE SERVER
3B125
CORRIDOR
C3-107
NURSE SERVER
3A126
NURSE SERVER
3A119
NURSE SERVER
3B120
NURSE SERVER
3B117
NURSE SERVER
3B115
AFCV-5S2
AFCV-5E2
AFCV-5S1
AFCV-5E1
MH301
EE
VAV
5-35 SAR-1
RAR-1
RF
VAV
5-36
VAV
5-37
VAV
5-38
FSD
FSD FSD
FSD
10"x10"
8"ø 6"ø
VAV
5-40
VAV
5-39
RAR-1
SAR-1
40012"x10"
8"ø
12"x10"
8"ø
18"x12"
"x
14"x10" 18"x10"
8"x8"
10"x10"
8"x8"
10"ø
12"ø
10"ø
8"ø
16"x12"
10"x10"
8"ø
12"x10"
18"x12"
34"x32"
46"x26"Ө
M H
10"ø
8"ø 8"ø
8"ø8"ø8"ø8"ø 6"ø
6"ø 8"ø8"ø6"ø8"ø
8"ø 8"ø8"ø
6"ø
6"ø
6"ø
12"ø
6"ø
6"ø
8"ø 10"ø
8"ø
8"ø
REMOVE EXISTING DUCTWORK FROM 4TH FLOOR DOWN TO SLAB ON
3RD FLOOR. INSTALL NEW FIRE/SMOKE DAMPER AT 3RD FLOOR
LEVEL AND CONNECT TO EXISTING DUCT IN 2ND FLOOR CEILING.
PROVIDE NEW 22x26 DUCTWORK UP TO 4TH FLOOR. COORDINATE
WORK WITH OWNER AS EXHAUST SYSTEM IS STILL USED ON LOWER
FLOORS. SYSTEM CHANGEOVER TIME MUST BE KEPT TO A MINIMUM.
FSD
FSD
REMOVE EXISTING DUCTWORK FROM 4TH FLOOR DOWN TO SLAB ON
3RD FLOOR. INSTALL NEW FIRE/SMOKE DAMPER AT 3RD FLOOR
LEVEL AND CONNECT TO EXISTING DUCT IN 2ND FLOOR CEILING.
PROVIDE NEW 24X16 DUCTWORK UP TO 4TH FLOOR. COORDINATE
WORK WITH OWNER AS EXHAUST SYSTEM IS STILL USED ON LOWER
FLOORS. SYSTEM CHANGEOVER TIME MUST BE KEPT TO A MINIMUM.
T
T
T
T
T
T
T
T
T
T T T
T
T
T
T
T
TTT
T
TT
T
T
T
TT
T
T
TT
T
T
CO
H
T
T
H T H
T
H
H
T
10"x8"
FSD
FSD
FSD
FSD
EB
8"x8"
8"x8"
6"ø
6"ø
SC
EB
8"x8"
16"x8"
10"x8"
8"x8"
10"x10"
20"x12"
LOCATION FOR FLOOR BAS CONTROL
SYSTEM PANELS. COORDINATE WITH
ELECTRICAL FOR POWER REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:5
P M
MH101
3RD FLOOR - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
173 238
1/8" = 1'-0"MH301 MH101
1 3RD FLOOR - HVAC
N O
R T
H
GENERAL SHEET NOTES:
1. PROVIDE MANUAL VOLUME DAMPERS AT DUCT
TAKE-OFFS AND BRANCHES PER DETAILS.
2. LOCATE ALL EQUIPMENT ABOVE SUSPENDED
CEILINGS OR NEAR A CEILING ACCESS
HATCHES OR PANELS AND MOUNTED AS LOW
TO THE CEILING AS POSSIBLE TO ALLOW FOR
PROPER SERVICING. LOCATE EQUIPMENT TO
PROVIDE ACCESSIBILITY FROM THE CEILING
ACCESS POINT TO AREAS OR PARTS OF THE
EQUIPMENT THAT REQUIRE PERIODIC
MAINTENANCE.
3. BALANCE AIR DEVICES TO CFM VALUES
INDICATED OR HIGHER. VALUES INDICATED
ARE MINIMUM AIRFLOWS. ADJUST VAV BOX
MINIMUMS TO MATCH CFM VALUES SHOWN ON
PLANS.
KEYED NOTES:
1. EXISTING GENERAL AREA EXHAUST FROM 1ST
AND 2ND FLOOR.
2. ROOM PRESSURE MONITOR.
3. UP TO 5TH FLOOR
4. PROVIDE FIRE/SMOKE DAMPER AT FLOOR
PENETRATION.
S
S
S
S S
S
S S
S
S S SS
S S
S
S
S
S S
S S
S
S S
SS S
S
S S
S
S S
S
S
S
S
S S
S S
S S
S
S
S S
S S
S S
S
S S
S S
S
S S
S S
S
S
S
S
S
S SS
S
S S
S S
S S
S
S
S SS
S
S S
S
S
S
S S
S
S
S
S S
S
S SS S
S S
S
S S
S S
S
S
S SS S S
S
S SSS SS S S SS S
S
S
S
S
S S S
S
S
S
S
S
S S
S
S S
S
S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
SL
RC
SL
RC
EB
SL
RC
SA
EB
SL
EB
SC
SC
RC
RC
RC
SC
SC
RD
SL
SL
SC
RE
SA
ED
RE
SJ
SJ
SL
EB
SL
EB
SJ
SJ
SJ
SJ
SJ
150 SJ
SF
SA
EB
SL
EB
EB
SL
SL
EB
SC
SB
SB
SC
RC
SB
RB
RB
SA
RA
RA
SB
RD
SL
EB
SB
RB
SA
RA
SA
EB
SL
EB
SA
RF
RF
SA
RA
SK
SK
SK
SK
SK
VAV
6-01 VAV
6-03
VAV
6-04
VAV
6-05
VAV
6-06
VAV
6-08
VAV
6-09
VAV
6-10
VAV
6-11
VAV
6-12
VAV
6-14
VAV
6-15
VAV
6-21
VAV
6-22
VAV
6-23
VAV
6-24
VAV
6-26
VAV
6-27
VAV
6-28
VAV
6-29
VAV
6-25
VAV
6-30
VAV
6-31
VAV
6-32
VAV
6-33
RE
VAV
6-02
42"x14"
"x
"Ө
"x
50"x22"
10"x10"
16"x12"
SC
SC
SC
SC
SC
SC
SC
ED
SC
SC
SC
SC
265SC
SC
SC
SC
SC
320 SC
SC
SC
SB
SJ
FSD
18X14 GENERAL
EXHAUST DOWN, 22X14
GENERAL EXHAUST UP
16X20 GENERAL EXHAUST DOWN,
26X22 GENERAL EXHAUST UP
18x18 ISOLATION
EXHAUST
16x18 ISOLATION EXHAUST
42"x14" 48"x14"
34"x16"Ө34"x16"Ө
16"x12"
SL
EB
RB
RA
SD
RC
RE
EA
EA
SL
SL
SL
EA
SL
EA
EB
150 EB
SL
EA
SL
EA
RC
RC
SC
EA
SL
SL
EA
EA
28"x14"Ө18"x12"Ө 26"x12"Ө
"x
"Ө
20"x12"
"x
"Ө
12"x10" 12"x10"
8"x8"
12"x10"
12"x10" 8"ø
12"ø10"x8"
24"x10"
10"ø 14"x10"
10"ø
10"ø
14"x10"
14"x12"
10"x8"
16"x10"
14"x14"
14"x12"
12"ø
8"x8"
12"x10" 12"x10"
34"x16"Ө
12"ø
8"ø
12"x10"
14"ø
12"x10" 12"x10" 12"x10" 12"x10"
12"x10"
12"x10"
10"x10"
8"x8"
6"x6"
14"x10"
18"x8"
6"x6"
12"x10"
12"ø
10"ø 12"x12"
14"x8"
12"x10"
10"ø
18"x10"
8"x8"
22"x10"
MH301
EB
EB
18"x12"
RA
SC
SC
RC
SC
RE
VAV
6-16
VAV
6-17
VAV
6-18VAV
6-19
VAV
6-20
12"x10"
12"x12"
10"ø
BARIATRIC PATIENT BATHROOM
4A131A
PATIENT ROOM 1
4B114
PATIENT ROOM 2
4B116
PATIENT ROOM 3
4B118
PATIENT ROOM 4
4B119 CLEAN EQUIPMENT STORAGE
4B121
M D
D
IC
TA
TI
O N
4B
PATIENT ROOM 5
4B123
PATIENT ROOM 6
4B124
WHEELCHAIR ALCOVE
4B102
ELECTRICAL ROOM
4B101
PATIENT CENTERED CARE
4B103
MEDICAL GAS STORAGE
4B104
CRASH CART
4B105
HAC
4B106
CLEAN UTILITY
4B107
CLEAN LINEN
4B108
KINESIOTHERAPY
4B109
WEST STAIR
4B110
PATIENT ROOM 7 - NEGATIVE
PRESSURE
4B111
UNASSIGNED
4B113
PATIENT BATHROOM
4B111A
ANTE ROOM
4B111B
PATIENT BATHROOM
4B114A
PATIENT BATHROOM
4B116A
PATIENT BATHROOM
4B118A P
A
TI
E N
T B
A
TH
R O
O M
4B
9A
PATIENT BATHROOM
4B123A
PATIENT BATHROOM
4B124A
C O
R R
ID
O
R
C 4-
CENTRAL STAIR
4A101
MALE TOILET
4A102
FEMALE TOILET
4A103
FAMILY TOILET
4A104
WAITING / LOUNGE
4A105
FAMILY CONSULTATION
4A106
MECHANICAL SHAFT
4A107
SOILED LINEN
4A110
ENGINEERING
4A111
STAFF EDUCATION
4A112
M E
D
IC
A
TI
O N
R O
O M
4A
NOURISHMENT STATION
4A115
PATIENT ROOM 8
4A117
PATIENT ROOM 9
4A118
MD DICTATION
4A120
IMD SUPPLY STORAGE
4A121
PATIENT ROOM 10
4A122
PATIENT ROOM 11
4A123
BARIATRIC PATIENT ROOM 12
4A125
CONFERENCE / REPORT ROOM
4A128
PATIENT BATHROOM
4A117A
PATIENT BATHROOM
4A118A
PATIENT BATHROOM
4A122A
PATIENT BATHROOM
4A123A
BARIATRIC PATIENT BATHROOM
4A125A
HAC
4A127
BED STORAGE
4A130
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
4A131
ANTE ROOM
4A131B
EAST STAIR
4A133
M.O.D. ROOM
4A134
MALE LOCKERS
4A137
STAFF TOILET
4A136
STAFF SHOWER
4A135
CORRIDOR
4A141
STAFF LOUNGE
4A138
FEMALE LOCKERS
4A139
TELECOMM
4A140
SOILED UTILITY
4A142
NURSE STATION
4A109A
CORRIDOR
C4-105
CORRIDOR
C4-103
NURSE SERVER
4A124
C O
R R
ID
O
R
C 4-
NURSE SERVER
4A132
CORRIDOR
C4-101
NURSE SERVER
4B112
NURSE SERVER
4B125
CORRIDOR
C4-107
NURSE SERVER
4A126
NURSE SERVER
4A119
NURSE SERVER
4B120
NURSE SERVER
4B117
NURSE SERVER
4B115
M.O.D. BATHROOM
4A134A
AFCV-6E1
AFCV-6S1AFCV-6S2
MH301
F S
D
SA
VAV
6-38
VAV
6-37
VAV
6-35 SAR-1
VAV
6-36 RAR-1
400SAR-1
RAR-1
12"x10" 12"x10"
SC
RD
FSD
FSD
FSD
8"ø
6"ø
6"ø
SA
SA
VAV
6-40
VAV
6-39
"x
EE
EE
18"x10"14"x10"
"x
8"x8"
10"x10"
8"x8"
10"x8"
10"x8"
16"x8"
10"x10"
20"x16"
10"x10"
12"x10"
18"x18"
10"ø6"ø
M H
8"ø8"ø8"ø8"ø8"ø 8"ø6"ø
10"ø
6"ø 8"ø8"ø6"ø8"ø8"ø8"ø8"ø
12"ø 6"ø
6"ø
8"ø
12"ø
8"ø 10"ø
8"ø
8"ø
8"ø
8"ø
8"ø
14"x14"
8"x8" AFCV-6E2
REMOVE EXISTING DUCTWORK FROM 5TH
FLOOR DOWN TO SLAB ON 4TH FLOOR.
PROVIDE NEW 22X26 DUCTWORK UP TO 5TH
FLOOR. COORDINATE WORK WITH OWNER
AS EXHAUST SYSTEM IS STILL USED ON
LOWER FLOORS. SYSTEM CHANGEOVER
TIME MUST BE KEPT TO A MINIMUM.
REMOVE EXISTING DUCTWORK FROM 5TH
FLOOR DOWN TO SLAB ON 4TH FLOOR.
PROVIDE NEW 24X16 DUCTWORK UP TO 5TH
FLOOR. COORDINATE WORK WITH OWNER AS
EXHAUST SYSTEM IS STILL USED ON LOWER
FLOORS. SYSTEM CHANGEOVER TIME MUST
BE KEPT TO A MINIMUM.
8"x8"
"x
"Ө
T
T
T
T
T
T
T
T
T
T T T
T
T
T
T
T
TT
T
T
TT
T
T
T
TT
T
TT
T
T
T
CO
H
T
T
H T H
T
H
H
T
FSD
FSD
FSD
FSD
RD
SC
16"x8" 8"x8"
RD
SC
10"ø
16"x8"
SC
8"x8"
10"x8"
20"x10"
LOCATION FOR BAS ECC AND FLOOR
CONTROL SYSTEM PANELS. COORDINATE
WITH ELECTRICAL FOR POWER
REQUIREMENTS.
10"x10"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:0
P M
MH102
4TH FLOOR - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
174 238
1/8" = 1'-0"MH301 MH102
1 4TH FLOOR - HVAC
N O
R T
H
GENERAL SHEET NOTES:
1. PROVIDE MANUAL VOLUME DAMPERS AT DUCT
TAKE-OFFS AND BRANCHES PER DETAILS.
2. LOCATE ALL EQUIPMENT ABOVE SUSPENDED
CEILINGS OR NEAR A CEILING ACCESS
HATCHES OR PANELS AND MOUNTED AS LOW
TO THE CEILING AS POSSIBLE TO ALLOW FOR
PROPER SERVICING. LOCATE EQUIPMENT TO
PROVIDE ACCESSIBILITY FROM THE CEILING
ACCESS POINT TO AREAS OR PARTS OF THE
EQUIPMENT THAT REQUIRE PERIODIC
MAINTENANCE.
3. BALANCE AIR DEVICES TO CFM VALUES
INDICATED OR HIGHER. VALUES INDICATED
ARE MINIMUM AIRFLOWS. ADJUST VAV BOX
MINIMUMS TO MATCH CFM VALUES SHOWN ON
PLANS.
KEYED NOTES:
1. EXISTING GENERAL AREA EXHAUST FROM 1ST
AND 2ND FLOOR.
2. ROOM PRESSURE MONITOR.
3. UP TO ATTIC.
4. DOWN TO 3RD FLOOR.
STAMP
S SS
S
S
SS S
S S
S
S SS S
S
S S
S
S
S
S
S S
S
S S
S
S
S S
S
SS
SS
S S
S S
S S
S
S
S
S
S S
S S
S SS
S SS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
RE
RE
RF
SB
EB
SA
RB
SA
RB
60 SA
RA
SC
ED
SB
RB
SC
ED
RE
RC
RC
RC
SI
SB
120SB
SB
RE
SC
EC
SB
EC
RC
SL
SI
RB
SJ
SA
RA
SF
EB
SA
SA
SA
SF
EB
SB
SB
RD
SB
SB
SB
SB
RD
SC
SC
120SC
RE
SB
SB
RE
SC
SC
SC
RE
SF
EB
SC
SC
SB
EC
SD
SD
RE
SC
RD
SC
RD
205 SB
EB
SD
SD
RE
SI
SJ
SJ
SJ
RA
SA
SB
RC
SA
SB
RB
SA
RA
SA
SA
SA
EB
EB
SJ
130 SJ
SJ
SB
SB
RD
SB
EB
VAV
10-01
VAV
10-32
VAV
10-07
VAV
10-08
VAV
10-33
VAV
10-11
VAV
10-14
VAV
10-16
VAV
10-18
VAV
10-19
VAV
10-26
42"x18"30"x18"
32"x20"Ө
"x
"x
"Ө
SC
SC
SC
SC
SC
SC
SC
SC
SC
SC
200SC
SB
SB
SB
SB
SC
SC
SC
SC
SC
SC
F S
D
FSD
12X10 UP, TRANSITION TO 10"
HOOD CONNECTION AS
NECESSARY. FAN/HOOD TO BE
BALANCED TO 600 CFM.
26X22 GENERAL EXHAUST DOWN,
26X22 GENERAL EXHAUST UP
18x18 ISOLATION
EXHAUST
16x18 ISOLATION
EXHAUST
32"x20"Ө
14"x12"
24"x14"Ө
18"x14"
12"x12"
30"x30"
RA
SB
SB
SB
EC
RG
RA
34"x18" 20"x16"
"x
SA
"x
22"x12"
30"x18"
"x
20"ø
24"x12"
40"x20"Ө 4 "x
"Ө
"x
16"x10"
"x
"x
"x
14"x14"
14"x14"
"x
12"x12"
10"x10"
14"x12"
10"x12"
12"ø
8"x6"
14"x12" 10"x8"
14"x12"
10"ø 14"x10"Ө
8"ø 8"ø
14"x10"Ө
8"x8"
14"x14"
14"x14"
12"x12"
12"x12" 16"x20"
14"ø 10"ø
22"x14"
"x
20"x10"
12"x10" 12"x10"
14"x10"
14"x10"
10"x10"
8"x8"8"x10"
12"x10"
"x
6"ø10"ø8"ø 6"ø
14"ø
8"ø
8"ø
10"ø
10"x8"
8"x10"
14"x12"
8"ø 12"ø 6"ø
10"x10"
10"ø
14"x12"
10"ø 6"ø 8"ø 6"ø3 "x
"x
18"x8"
8"x8"
10"x12"
14"x14"
10"x10"
10"ø 10"x10"
12"x10"
10"ø
16"ø
12"x12"
IMD SUPPLY
5B122
PANORAMIC X-RAY
5B123
STERILE INSTR. STORAGE
5B128
S O
IL
E
D U
TI
LI
TY
5B
EQUIPMENT STORAGE
5B135
UNISEX TOILET
5B136
DENTIST WORKSTATIONS
5B129 OPERATORY TREATMENT GENERAL
AREA
5B131
HAC
5A110
ENGINEERING
5A111
STAFF LOUNGE
5A112
MALE TOILETS / LOCKERS
5A113
FEMALE TOILETS / LOCKERS
5A114
SCRUBS DISTRIBUTION
5A108
CRASH CART
5A115
PHYSICIANS CUBICLES
5A117
FILE ROOM
5A118
COPY ROOM
5A119
OFFICE
5A120
SUPPLY STORAGE
5A121
DIRECTORS CONFERENCE ROOM
5A122
MENS TOILET ROOM
5A124
PIPE ACCESS
5A125
WOMENS TOILET ROOM
5A126
HAC
5A127
EAST STAIR
5A128
STAFF LOUNGE
5A130OFFICE
5A131
CUBICLES
5A134
OFFICE
5A132
OFFICE
5A133
TELECOMM
5A135
CENTRAL STAIR
5A101
FAMILY TOILET
5A102
MEDICAL CONFERENCE
5A103
DENTAL CONFERENCE
5A105
MECHANICAL SHAFT
5A106
LOBBY / LOUNGE
C5-105
ELECTRICAL ROOM
5B102
WAITING
5B103
RECEPTION / SECRETARY
5B104 C
O P
Y R
O O
M
5B
DENTAL SERVICE CHIEF OFFICE
5B106
MEDICATION ROOM
5B109
AO OFFICE
5B107SHIPPING/ RECEIVING ROOM
5B110
WEST STAIR
5B111
TOILET ROOM
5B112
SOILED UTILITY
5B114
OPERATORY TREATMENT GENERAL
AREA
5B115
C O
R R
ID
O
R
C 5-
4A
CORRIDOR
C5-104
C O
R R
ID
O
R
C 5-
7A
CORRIDOR
C5-109
CORRIDOR
C5-102C
CORRIDOR
C5-106
CORRIDOR
C5-103
CORRIDOR
C5-102
DENTAL TREATMENT ROOM 1
5B116
DENTAL TREATMENT ROOM 2
5B117
DENTAL TREATMENT ROOM 3
5B118
DENTAL TREATMENT ROOM 4
5B119
DENTAL TREATMENT ROOM 5
5B120
DENTAL TREATMENT ROOM 6
5B121
DENTAL TREATMENT ROOM 7
5B125
DENTAL TREATMENT ROOM 8
5B126
DENTAL TREATMENT ROOM 9 -
SPECIAL NEEDS
5B127
DENTAL TREATMENT ROOM 10-
SPECIAL NEEDS
5B132
DENTAL TREATMENT ROOM 11
5B133
DENTAL TREATMENT ROOM 12
5B134
DENTAL LAB
5B113
10"x8" VAV
10-09 VAV
10-06
VAV
10-05
VAV
10-04
VAV
10-02
VAV
10-15
VAV
10-17
VAV
10-34
VAV
10-20
VAV
10-22
VAV
10-21
VAV
10-23
VAV
10-24
VAV
10-12
VAV
10-27
VAV
10-13
14"x12"
12"x12"
MH301
MH301
ACCESS HATCH FSD
20"x12"
18"x10"
RAR-1
SAR-1
14"x8"
VAV
10-29 12"x10"
VAV
10-28
SAR-1
12"x10"
RAR-1
10"x8"
VAV
10-03
VAV
10-10
VAV
10-25
10"x8" 6"ø
VAV
10-30
20"x10"
6"ø
8"x8"
6"x6"
6"ø
VAV
10-31
8"ø6"ø
20"x12"14"x8"
M H
RA
RA
10"ø
8"ø 8"ø6"ø
8"ø 8"ø
10"x8"
10"x10"
6"ø
8"ø
6"ø
12"ø
8"ø
COORDINATE DUCT ROUTING
WITH LOWER VOLTAGE
SYSTEM PANEL PLACEMENT
TO PROVIDE 6'-0" CLEAR
SPACE ABOVE PANELS.
COORDINATE 14X12 DUCT
ROUTE AROUND ACCESS
HATCH OPENING.
REMOVE EXISTING DUCTWORK FROM APPROXIMATELY
12" BELOW ATTIC SLAB DOWN TO 5TH FLOOR SLAB.
PROVIDE NEW 22X26 DUCTWORK UP TO EXISTING 32X44
DUCT. COORDINATE WORK WITH OWNER AS EXHAUST
SYSTEM IS STILL USED ON LOWER FLOORS. SYSTEM
CHANGEOVER TIME MUST BE KEPT TO A MINIMUM.
PROVIDE OFFSETS AS NECESSARY FOR NEW DUCT
SHAFT.
REMOVE EXISTING DUCTWORK FROM
APPROXIMATELY 12" BELOW ATTIC SLAB DOWN TO
5TH FLOOR SLAB. PROVIDE NEW 24X16 DUCTWORK
UP TO EXISTING 30X40 DUCT. COORDINATE WORK
WITH OWNER AS EXHAUST SYSTEM IS STILL USED
ON LOWER FLOORS. SYSTEM CHANGEOVER TIME
MUST BE KEPT TO A MINIMUM.
T
T
T
T
T
T
T
T
T T T
T
T
T
T T
T T
T
T T T
T
T
T
T
T CO
CO
CO
CO
H
T
TS
TS
T
T
T
TS
TS
H
CO CO
SA-R-1
SA-D-1
10"x6"
"x
EC
10"x8"
22X14 GENERAL EXHAUST
DOWN, 24X20 GENERAL
EXHAUST UP
16"x10"
20"x10"
10"x10"
19"ø 20"ø
12"x12"
10"x8"
T
LOCATION FOR FLOOR BAS CONTROL
SYSTEM PANELS. COORDINATE WITH
ELECTRICAL FOR POWER REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:1
P M
MH103
5TH FLOOR - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
175 238
1/8" = 1'-0"MH301 MH103
1 5TH FLOOR - HVAC
N O
R T
H
SPECIAL CONDITION NOTES:
1. DUCTWORK HAS BEEN FABRICATED FOR THIS FLOOR
AND IS ON SITE. ALL HANGERS HAVE BEEN INSERTED
ON THIS FLOOR. CONTRACTOR SHALL INSTALL, TEST,
AND INSULATE ALL DUCTWORK AS PART OF THIS
CONTRACT. CONTRACTOR IS RESPONSIBLE FOR ANY
AND ALL ADJUSTMENTS NECESSARY FOR
COORDINATION AND INSTALLATION.
2. REFER TO AS BUILT DRAWINGS IN APPENDIX FOR
MORE INFORMATION INCLUDING DRAWINGS
INDICATING WHICH DUCTWORK HAS BEEN
INSTALLED.
3. CONTRACTOR SHALL FIELD VERIFY ON SITE
DUCTWORK PRIOR TO SUBMITTING BIDS.
4. CONTRACTOR SHALL NOTIFY THE OWNER OF ANY
DISCREPANCIES WITH ITEMS ON SITE.
GENERAL SHEET NOTES:
1. PROVIDE MANUAL VOLUME DAMPERS AT DUCT TAKE-OFFS
AND BRANCHES PER DETAILS.
2. LOCATE ALL EQUIPMENT ABOVE SUSPENDED CEILINGS OR
NEAR A CEILING ACCESS HATCHES OR PANELS AND
MOUNTED AS LOW TO THE CEILING AS POSSIBLE TO
ALLOW FOR PROPER SERVICING. LOCATE EQUIPMENT TO
PROVIDE ACCESSIBILITY FROM THE CEILING ACCESS POINT
TO AREAS OR PARTS OF THE EQUIPMENT THAT REQUIRE
PERIODIC MAINTENANCE.
3. BALANCE AIR DEVICES TO CFM VALUES INDICATED OR
HIGHER. VALUES INDICATED ARE MINIMUM AIRFLOWS.
ADJUST VAV BOX MINIMUMS TO MATCH CFM VALUES
SHOWN ON PLANS.
KEYED NOTES:
1. 40x24 OVAL UP TO AHU-10 IN ATTIC
2. 48x24 UP TO AHU-10 IN ATTIC
3. UP TO ATTIC
4. EXISTING GENERAL AREA EXHAUST FROM 1ST AND 2ND
FLOOR
5. DOWN TO 3RD FLOOR.
6. PROVIDE DUCT SILENCER. REFER TO MH603.
7. PROVIDE 430 STAINLESS STEEL TYPE II EXHAUST HOOD 42"
WIDE, 36" DEEP, AND 24" TALL WITH LIGHTS AND 6" HIGH
WRAP. COORDINATE INSTALLATION LOCATION WITH
DENTAL EQUIPMENT. UNIT TO BE MOUNTED
APPROXIMATELY 80" AFF. PROVIDE ALL BRACKETS,
HANGERS, WIRING, AND ACCESSORIES FOR A COMPLETE
INSTALLATION. COORDINATE POWER REQUIREMENTS WITH
ELECTRICAL.UNIT SHALL REQUIRE 600 CFM WITH 0.09"
STATIC PRESSURE DROP. EXHAUST PLENUM ON HOOD
SHALL BE 4" TALL WITH 10" DIAMETER CONNECTION.
UP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
ELEVATOR EQUIP ROOM
6B102
CENTRAL STAIR
6B103
ELECTRICAL ROOM
6B100A
ELECTRICAL ROOM
6B100B
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
RADIO ROOM
6B104
ALCOVE
6B105
56"x22"
DN. TO 5TH FLOOR
DN. IN EXISTING CHASE
DN. TO 5TH FLOOR
18x18 UP TO ROOF CAP
18"x18"
18"x18" 26"x26"18"x16"
18"x16"
VFD-EF-1
VFD-EF-2
24"x24"
MH302
MH302
MH302
TRANSITION UP
TO ROOF CAP
CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS TO
LOUVER CONNECTION.
AHU-6
HEPA FILTER RACK
(BAG IN BAG OUT)
HEPA FILTER RACK
(BAG IN BAG OUT)
F S
D
1 1
VAV
6-34
VAV
5-34
2 2
24"x24"
28"x28"
24"x24"
24"x24"
46"x24"Ө
34"x32"
28"x28"
28"x28"
28"x28"
AHU-10
AHU-5
UP TO ROOF CAP
DN. TO 5TH FLOOR
UP TO ROOF CAP
UP TO ROOF CAP
EX-EF-3
VFD
EXISTING EHAUST
FAN TO REMAIN
EX-EF-1
VFD
28"x28"
34"x36"
28"x28"
48"x28"2 "x
"x
46"x26"Ө
"x
"Ө
OAOA
OAOA
RETN
SUPL
S U
P L
OA OA
OA OA
R E
T N
EXISTING
EXHAUST
FAN TO
REMAIN
24"x24"
24"x24"
20"x24"
MH302
RAR 16x10
RAR 16x10
MH302
MH302
FSD
L-4
CONNECT TO NEW LOUVER
AT EXISTING DORMER.
SHEETMETAL SHALL BE
CONTINUOUS TO LOUVER
CONNECTION.
L-3
CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS
TO LOUVER
CONNECTION.
L-1
CONNECT TO NEW
LOUVER AT EXISTING
DORMER.
SHEETMETAL SHALL
BE CONTINUOUS TO
LOUVER CONNECTION.
L-2 CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS
TO LOUVER
CONNECTION.
L-5
CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS
TO LOUVER
CONNECTION.
L-6
CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS
TO LOUVER
CONNECTION.
L-8
CONNECT TO NEW
LOUVER AT EXISTING
DORMER. SHEETMETAL
SHALL BE CONTINUOUS
TO LOUVER CONNECTION.
L-7
VFD-EF-4
6 6
66 6
ACCESS HATCH
VFD-AHU-5S
VFD-AHU-10S
VFD-AHU-6S
VFD-AHU-10R
VFD-AHU-5R
VFD-AHU-6R
M H
VAV
6-43
SAR-1
VAV
6-42
VAV
6-41RAR-1
RAR-1
14"x8"
SAR-1
RAR-1
VAV
6-44SAR-1
SAR-1
RAR-1
EXISTING ELEV.
VENT DUCT
MH306
8"ø
8"ø 8"ø
8"ø
14"x8"
12"ø
12"ø
EXISTING TRASH
CHUTE TO
BE REMOVED
EXISTING LAUNDRY
CHUTE
BCU-1
BCU-3
BCU-2
24"x20"
FSD
FSD
INSTALL NEW FIRE/SMOKE DAMPER AT ATTIC
FLOOR IN EXISTING DUCTWORK. CONTRACTOR
SHALL FIELD VERIFY DUCT SIZE PRIOR TO
ORDERING DAMPER. COORDINATE WORK WITH
OWNER AS EXHAUST SYSTEM IS STILL USED
ON LOWER FLOORS. SYSTEM CHANGEOVER
TIME MUST BE KEPT TO A MINIMUM.
1 FSD
UP TO EXISTING
ROOF CAP
FSD
FSD
FSD
INSTALL NEW FIRE/SMOKE DAMPER AT
ATTIC FLOOR IN EXISTING DUCTWORK.
CONTRACTOR SHALL FIELD VERIFY DUCT
SIZE PRIOR TO ORDERING DAMPER.
COORDINATE WORK WITH OWNER AS
EXHAUST SYSTEM IS STILL USED ON
LOWER FLOORS. SYSTEM CHANGEOVER
TIME MUST BE KEPT TO A MINIMUM.
OFFSET DUCTWORK AS REQUIRED FOR
NEW CHASE LOCATION.
FSD
26"x26"
T
T
T
T
T T
T H
T H
T H
REMOVE EXISTING
DUCTWORK WHICH IS
ABANDONED IN ATTIC
SPACE.
REMOVE EXISTING
DUCTWORK WHICH IS
ABANDONED IN ELEVATOR
MACHINE ROOM. REMOVE EXISTING
DUCTWORK WHICH IS
ABANDONED IN ATTIC
SPACES AND ABOVE
RADIO ROOM.
REMOVE EXISTING
DUCTWORK WHICH IS
ABANDONED IN ATTIC
SPACE.
FSD
12"x10" DN
FSDFSD
PROVIDE STAINLESS STEEL
DUCTWORK, FITTINGS, AND
ACCESSORIES FOR EH-5 SYSTEM
12"x10" 42"x30"
56"x22"
PROVIDE STAINLESS STEEL
SILENCER, SA-E-1. REFER TO
MH-603 FOR MORE INFORMATION.
PROVIDE ACOUSTICAL LAGGING AROUND
DUCTWORK FROM SILENCER AND DOWN
THROUGH ATTIC FLOOR. PROVIDE ABILITY TO
ACCESS FSD AS NECESSARY. PRIMARY ACCESS
FOR FSD CAN BE FROM ABOVE CEILING OF 5TH
FLOOR.
ROUTE ATTIC DUCTWORK AS HIGH AS
POSSIBLE. COORDINATE ACCESS TO ALL
EQUIPMENT AND SPACES WITH DUCTWORK.
REVIEW AREAS WITH LIMITED HEADSPACE WITH
RESIDENT ENGINEER PRIOR TO FABRICATION.
FSD
FSD
26X22 DOWN
32x32 UP TO ROOF CAP
EF-5
EF-7
EF-3
EF-4
EF-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:1
P M
MH104
ATTIC - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
176 238
1/8" = 1'-0"MH301 MH104
1 ATTIC - HVAC
N O
R T
H
SPECIAL CONDITION NOTES:
1. CONTRACTOR TO COORDINATE WITH THE OWNER
FOR EXISTING EXHAUST SYSTEM WORK. SYSTEM
SERVES LOWER LEVELS OF THE HOSPITAL AND
MUST HAVE MINIMAL DOWNTIME.
2. COORDINATE WITH PLUMBING CONTRACTOR FOR
EXISTING PLUMBING VENT PIPING ADJUSTMENTS
FOR NEW HVAC INSTALLATION.
KEYED NOTES:
1. PROVIDE FIRE/SMOKE DAMPER AT FLOOR
PENETRATION.
2. 3,750 CFM 4.64 SQ.FT. MIN. FREE AREA
OUTSIDE AIR LOUVER (TYPICAL 4 LOCATIONS)
3. 15,400 CFM OUTSIDE AIR DUCTED FROM
INTAKE ROOF HOOD.
4. PROVIDE DRIP PAN UNDERNEATH RELIEF
HOODS.
5. 3,825 CFM 4.64 SQ.FT. MIN. FREE AREA
OUTSIDE AIR LOUVER (TYPICAL 4 LOCATIONS)
6. PROVIDE ACCESS DOORS TO ACCESS LOUVER
FROM INSIDE ATTIC SPACE.
- WATER INTRUSION FIX 2017 02 15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
IH-10
RH-6
EH-2
EH-4
EH-1
RH-5
HATCHING INDICATES POSSIBLE AREA OF
ROOF WORK REQUIRED FOR NEW
EQUIPMENT INSTALLATION. REFER TO
ARCHITECTURAL FOR MORE INFORMATION.
(TYPICAL)
RH-10
EH-5
PROVIDE NEW CAP FOR
EXISTING ROOF HOOD.
REPAIR EXISTING HOOD
IN PLACE.
EXISTING ROOF HOOD
TO REMAIN.
EH-3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:1
P M
MH105
ROOF PLAN - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
177 238
1/8" = 1'-0"MH302 MH105
1 ROOF PLAN - HVAC
N O
R T
H
F E D CF.8 F.3 B.4B.7D.8 D.2 B.8
5TH FLOOR
52' - 0 9/32"
ATTIC
66' - 0"
5TH FLOOR
52' - 0 9/32"
Level 6 66' - 0"
5TH FLOOR
52' - 0 9/32"
ATTIC
66' - 0"
18"x14"
SUPL
12"x34"
RETN
24"x14"Ө SUPL 14"x12"
SUPL
12"x24"
RETN
10"x10"
SUPL
10"x10"
RETN
1/2" HWR
1/2" HWS
1" HWR
1" HWS
CABLE TRAY
8"x8"
EXHS
CONDUIT
FILE ROOM
5A118
PHYSICIANS CUBICLES
5A117
CUBICLES
5A134
OFFICE
5A133
RC
SC
12"x34"
RETN
34"x18"
RETN
10"x10"
SUPL
F E D CF.8 F.3 B.4B.7D.8 D.2 B.8
5TH FLOOR
52' - 0 9/32"
ATTIC
66' - 0"
32"x34"
RETN
32"x34"
RETN
32"x20"Ө
SUPL
8"x22"
RETN
VAV
10-15
1/2" HWR
1/2" HWS
22"x8"
RETN
14"ø
SUPL
VAV
10-23
12"x14"
SUPL
22"x12"
RETN
12"x12"
SUPL
30"x18"
RETN 4" SV
1 1/4" HWR
1 1/4" HWS
RE
RE
SD
1 1/2" DA
CONDUITSCONDUITS
1" HW
1" HW
3/4" CW
2" SS
WAITING
5B103
RECEPTION / SECRETARY
5B104
CORRIDOR
C5-102
OPERATORY TREATMENT GENERAL
AREA
5B131
DENTAL TREATMENT ROOM 10-
SPECIAL NEEDS
5B132
18"x10"
EXHS
SC
RA
2" SV
2" SV
2" SV
1 1/2" LA
3/4" O
F E D CF.8 F.3 B.4B.7D.8 D.2 B.8 B.2
3RD FLOOR
26' - 0"
4TH FLOOR
39' - 0"
5TH FLOOR
52' - 0 9/32"
RF
RA
SA
RA
28"x14"Ө
SUPL
6"x6"
RETN
1/2" HWR 1/2" HWS
42"x14"
RETN
10"x24"
RETN
8"x8"
EXHS
1 1/2" SS
14"x10"
SUPL
VAV
6-28
6"ø
SUPL
1/2" O
3/4" MV
1/2" MA
1 1/2" MV
3/4" MA
3/4" O
CLEAN UTILITY
4B107
CORRIDOR
C4-101
MD DICTATION
4B122
CLEAN EQUIPMENT STORAGE
4B121
28"x14"Ө
SUPL
VAV
5-28
1/2" O
1/2" MA
3/4" MV
4" SV
10"x8"
EXHS
6"x6"
RETN
42"x14"
RETN
10"x24"
RETN
14"x10"
SUPL
3/4" O
3/4" MA
1 1/2" MV
1/2" HWR
1/2" HWS
8"x8"
EXHS
RA
SA
RA
SA
RF
CLEAN UTILITY
3B107
CORRIDOR
C3-101
MD DICTATION
3B122
CLEAN EQUIPMENT STORAGE
3B121
SA
1 1/2" SS
3" SS
1 1/2" LA
VAV
5-39
VAV
6-40
1" HWS
1" HWR
1" HWS
1" HWR
10 11 12 1310.8 12.2
3RD FLOOR
26' - 0"
4TH FLOOR
39' - 0"
5TH FLOOR
52' - 0 9/32"
50"x22" RETN 14"x48"
RETN
14"ø
SUPL
VAV
6-21
10"x20"
SUPL
12"ø
SUPL
10"x22"
SUPL
VAV
6-33
14"x42"
RETN
14"x42"
RETN
10"x22"
SUPL
VAV
5-33
56"x20" RETN 16"x44"
RETN
14"ø
SUPL
VAV
5-21
10"x20"
SUPL
RE
RE
SJ
SJ
SK
SK
1 1/4" O
1 1/2" MA
2" MV
1 1/4" O
1 1/2" MA
2" MV
CABLE TRAY
CABLE TRAY
CORRIDOR
C3-104
CORRIDOR
C4-104
46"x20"Ө
SUPL
46"x20"Ө
SUPL
2" MV1 1/2" MA1 1/4" O 1 1/2" MV
3/4" MA
3/4" O
1 1/2" MV
3/4" MA
3/4" O
1 1/2" MA
1 1/4" O
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:2
P M
MH301
BUILDING SECTIONS - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
178 238
1/4" = 1'-0"MH103 MH301
1 Section 1 (5TH FLOOR)
1/4" = 1'-0"MH103 MH301
2 Section 2 (5TH FLOOR)
1/4" = 1'-0"MH101 MH301
3 Section 3 (3RD & 4TH FLOOR)
1/4" = 1'-0"MH101 MH301
4 Section 4 (3RD & 4TH FLOOR)
14 15 16
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
FAN SECTION
MIXING BOX
FILTER SECTION
COOLING COIL
ACCESS SECTION
DISCHARGE PLENUM
FINAL FILTER SECTION
FAN SECTION
28"x28"
34"x36" 24"x46"Ө
SUPL
OA
AHU-6
3" CHWS
12"ø
SUPL
VFD-AHU-6S
VFD-AHU-6R
8 9
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
FAN SECTION
MIXING BOX
FILTER SECTION
COOLING COIL
ACCESS SECTION
DISCHARGE PLENUM
FINAL FILTER SECTION
FAN SECTION
26"x46"Ө 28"x28"
34"x34"
RETURN
PLENUM
AHU-5
OA
RETN SUPL
3" CHWR3" CHWS
VFD-AHU-5R
VFD-AHU-5S
12"ø
11 1210.8 12.2
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
FAN SECTION
MIXING BOX
FILTER SECTION
COOLING COIL
DISCHARGE PLENUM
FINAL FILTER SECTION
FAN SECTION
48"x24"
28"x48" 24"x46"Ө
RETURN
PLENUM
OA
RETN
AHU-10
A C C E S S
MH302
VFD-AHU-10R VFD-AHU-10S
4" CHWR4" CHWS3" CHWR3" CHWS
F E DF.3 D.8 D.2
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
CONNECT TO NEW
LOUVER IN EXISTING
DORMER
CONNECT TO NEW
LOUVER IN EXISTING
DORMER
12"ø
28"x28"
28"x28"
3" CHWS
3" CHWR
AHU-634"x36"
28"x28"24"x24"
OA
OA
OA
SUPL
VFD-AHU-6S
OA
F E DF.3 D.8 D.2
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
OA
RETN
SUPL
R E
T N
SUPL
3" CHWR
3" CHWS
6" CHWR6" CHWS
AHU-10
36"x36"
26"x48" 28"x46"Ө
1 1/2" MCD
VFD-AHU-10R
VFD-AHU-10S
VAV
6-43
SAR-1
26"x48"
RETN
10"x16"
EXHS
FED F.3D.8D.2
ATTIC
66' - 0"
PENTHOUSE
72' - 6"
28"x28" 24"x24"
24"x24"
26"x46"Ө
12"ø
32"x34"
32"x34"
3" CHWR
3" CHWS
28"x28" 26"x46"Ө
28"x28"
RETN
OA
OA
SUPL
O A
SUPL
CONNECT TO NEW
LOUVER IN EXISTING
DORMER
CONNECT TO NEW
LOUVER IN EXISTING
DORMER
AHU-5
VFD-AHU-5S
RH-10
MOTORIZED DAMPER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:2
P M
MH302
AHU ELEVATIONS - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
179 238
1/4" = 1'-0"MH104 MH302
1 AHU-6 SECTION
1/4" = 1'-0"MH104 MH302
2 AHU-5 SECTION
1/4" = 1'-0"MH104 MH302
3 AHU-10 SECTION
1/4" = 1'-0"MH104 MH302
4 AHU-6 SECTION 2
1/4" = 1'-0"MH104 MH302
5 AHU-10 SECTION 2
1/4" = 1'-0"MH104 MH302
6 AHU-5 SECTION 2
8" CHWS
8" CHWR
TO BLDG. #53TO BLDG. #53
EXISTING HWS/R NEW 3" CHWS/R
1" CHWS/R VALVE AND CAP
FOR FUTURE
1" CHWS/R VALVE AND CAP
FOR FUTURE
C H
W S
C H
W R
C H
W S
C H
W R
C H
W S
C H
W R
2" HWS/R @ 29.61 GPM TO
5TH FLOOR EQUIPMENT
2" HWS/R @ 34.98 GPM TO
4TH FLOOR EQUIPMENT
4" CHWS
4" CHWR
3" HWR
3" HWS
1" CHWS/R VALVE AND CAP
FOR FUTURE
C H
W S
C H
W R
C H
W S
C H
W R
EXISTING
INCINERATOR
SHAFT
EXISTING HWS/R
FROM BUILDING #3
AHU-6
131 GPM
AHU-10
114 GPM
3" CHWS
3" CHWR
3" CHWS
3" CHWR
6" CHWS
6" CHWR
C H
W S
C H
W R
H W
R
H W
S
H W
R
H W
S
H W
R
H W
S
H W
R
H W
S
8" CHWS
8" CHWR
5" HWR
5" HWS
8" CHWS
8" CHWR
5" HWR
5" HWS
SCHWP-1SCHWP-2EX_53HWP-1 EX_53HWP-2
MECHANICAL ROOM
BUILDING 53 CRAWL SPACE
8" CHWS
8" CHWR
8" CHWS
8" CHWR
5" HWR
5" HWS
TO VAV'S AND
BCU'S IN ATTIC
2" CHWS/R & HWS/R. VALVE
AND CAP FOR FUTURE
CONNECTION TO 1ST FLOOR
EQUIPMENT
2" CHWS/R & HWS/R. VALVE
AND CAP FOR FUTURE
CONNECTION TO 2ND FLOOR
EQUIPMENT
2" HWS/R @ 32.29 GPM TO
3RD FLOOR EQUIPMENT
TO EXISTING 1ST &
2ND FLOOR RISERS
CHILLED / HOT WATER FLOW DIAGRAM
NOT TO SCALE
AHU-5
130 GPM
ROOF
ATTIC
LEVEL 5
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
BUILDING 1 CRAWL SPACE
TO BCU-1
2.1 GPM
TO BCU-3
2.1 GPM
TO BCU-2
2.1 GPM
1" CHWS/R VALVE AND
CAP FOR FUTURE
1" HWS
1" HWR
4" HWS
4" HWR
EXISTING 8" CHWS/R
FROM CAMPUS LOOP
REFER TO PLANS FOR
EXISTING AND NEW PIPING
ROUTES
EXISTING PUMP MECHANICAL ROOM
EX_HWR
EX_HWS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:3
P M
MH303
CHILLED / HOT WATER FLOW
DIAGRAMS - HVAC
RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
180 238Revisions: Date:
EXISTING
INCINERATOR
SHAFT
ROOF
ATTIC
LEVEL 5
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
BUILDING 1 CRAWL SPACE
EX_EF-1
EX_EH-1
EX_EF-3
EX_EH-3
NOT TO SCALE
AIR FLOW DIAGRAM
AHU-10 AHU-6AHU-5 EF-4 EF-2EF-3EF-1
EH-1 EH-3 RH-5 RH-10 IH-10 RH-6 EH-4 EH-2
EF-5
EH-5
NEW LOUVER
IN EXISTING
DORMER
(4 PLACES)
NEW LOUVER
IN EXISTING
DORMER
(4 PLACES)
HEPA FILTER
16235 CFM
BLOCK SELECTION 15400 CFM
BLOCK SELECTION
16160 CFM
BLOCK SELECTION
HEPA FILTER
12x10 DENTAL LAB
HOOD EXHAUST AIR
600 CFM
56x22 RETURN AIR
12,490 CFM
15,475 CFM
46x24 Ø SUPPLY AIR
50x22 RETURN AIR
10,275 CFM
15,870 CFM
46x26 Ø SUPPLY AIR
34x32 RETURN AIR
10,985 CFM
28x28 OUTSIDE AIR
16235 CFM MAX
5994 CFM MIN
28x28 OUTSIDE AIR
16180 CFM MAX
6410 CFM MIN
36x36 OUTSIDE AIR
15400 CFM MAX
4107 CFM MIN
26x22 EXHAUST AIR
5,445 CFM
26x22 EXHAUST AIR
4,315 CFM
16x20 EXHAUST AIR
2,075 CFM
26x26 EXHAUST AIR
5,445 CFM
18x18 EXHAUST AIR
2,085 CFM
16x18 EXHAUST AIR
1045 CFM
24x20 EXHAUST AIR
3,700 CFM
22x14 EXHAUST AIR
1,915 CFM
18x14 EXHAUST AIR
950 CFM
18x16 EXHAUST AIR
1,830 CFM
18x16 EXHAUST AIR
920 CFM
24x20 EXHAUST AIR
3,700 CFM
18x16 EXHAUST AIR
1,830 CFM
48x26 RETURN AIR
12,615 CFM
34x34 RETURN AIR
11,600 CFM
48x28 SUPPLY
16,175 CFM
17,690 CFM
2,215 CFM
TO ATTIC
2,215 CFM
FROM ATTIC
17,690 CFM
46x24 Ø SUPPLY AIR
615 CFM
TO ATTIC
615 CFM
FROM ATTIC
16,485 CFM
46x26 Ø SUPPLY AIR
MMM
GENERAL NOTE:
1. AIRFLOW VALUES ON THIS SHEET ARE BASED ON TOTAL PEAK
AIRFLOW. AHU'S ARE SIZED BASED ON BUILDING BLOCK AIRFLOW.
2. SEE FLOOR PLANS FOR FIRE/SMOKE DAMPER LOCATIONS.
18x18 EXHAUST AIR
2,085 CFM
3. EQUIPMENT TAGS SHALL INCLUDE UNIT NUMBER, FLOORS THE
UNITS SERVE, AND WHERE THE POWER IS FED.
REFER TO EP104 FOR POWER FEED INFORMATION FOR
EQUIPMENT.
4.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:3
P M
MH304
AIR FLOW DIAGRAM - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
181 238Revisions: Date:
ATTIC
LEVEL
5TH LEVEL
4TH LEVEL
3RD LEVEL
2ND LEVEL
1ST LEVEL
CRAWLSPACE
LEVEL
6" CHWS
6" CHWR
4" HWS
4" HWR
2" CHWS
2" CHWR
2" HWS
2" HWR
6" CHWS
6" CHWR
4" HWS
4" HWR2" HWR
2" HWS
1" CHWR
1" CHWS
2" HWR
2" HWS
1" CHWR
1" CHWS
2" HWR
2" HWR
2" HWS
2" CHWR
2" CHWS
VALVE AND
CAP FOR
FUTURE
VALVE AND
CAP FOR
FUTURE
TO 5TH FLR
EQUIPMENT
TO 4TH FLR
EQUIPMENT
TO 3RD FLR
EQUIPMENT
TO ATTIC LEVEL
EQUIPMENT
ATTIC
LEVEL
5TH LEVEL
4TH LEVEL
3RD LEVEL
2ND LEVEL
1ST LEVEL
CRAWLSPACE
LEVEL
TO 5TH FLR
EQUIPMENT
TO 4TH FLR
EQUIPMENT
TO 3RD FLR
EQUIPMENT
FROM ATTIC
LEVEL
EQUIPMENT
46"x24"Ө
SUPL
52"x22"
RETN
46"x26"Ө
SUPL
"x
"Ө
S U
P L
"x
R E
T N
"x
"Ө
S U
P L
50"x22"
RETN
FROM ATTIC
LEVEL
EQUIPMENT
50"x22"
RETN
VAV
6-41
VAV
6-42
14"x12"
RETN
8" CHWR
8" CHWS
5" HWS
EX_53HWP-1
EX_53HWP-2
ET-1
SEE SHEET MS101
FOR CONTINUATION
EXISTING 6" HWS/R
FROM BUILDING #3
SEE SHEET MS101
FOR CONTINUATION
EXISTING AIR SEPARATOR
3" CHWR
3" CHWS
NEW 3"
CHWS/R TO
BUILDING #53
EXISTING
HWS/R TO
BUILDING #53
5" HWR
SEE SHEET MS101
FOR CONTINUATION
SEE SHEET MS101
FOR CONTINUATION
8" CHWR
8" CHWS
8" CHWR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:3
P M
MH305
3D VIEWS - HVAC & PIPING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
182 238
MH305
2 PIPING RISER 3D-2
MH305
1 DUCT RISER 3D-1
MH305
3 BLDG 53 PIPING 3D
18"x18"
EXHS
18"x18"
EXHS
32"x32"
EXHS
24"x24"
OA
24"x24"
OA
24"x24"
OA
24"x24"
OA
AHU-6
EH-2
EH-4
RH-6
IH-10
RH-5
VAV
5-34
VAV
6-34
EH-3
EH-1
24"x24"
OA
34"x32"
RETN
34"x34"
RETN
12"ø
SUPL
46"x26"Ө
SUPL
AHU-5
AHU-10
46"x24"Ө
SUPL
48"x28"
OA
28"x28"
OA
24"x24"
OA
18"x16"
EXHS
18"x16"
EXHS
VFD-EF-1
EX-EF-3
VFD
56"x22"
RETN
46"x24"Ө
SUPL
EX-EF-1
VFD
VFD-EF-2
6" CHWS
6" CHWR
4" HWS
4" HWR
3" CHWR
3" CHWS
12"ø
SUPL
VAV
6-42 VAV
6-41
VAV
6-44
FSDFSD
VAV
6-43
14"x8"
BCU-3
BCU-2
BCU-1
DRAIN ROUTED TO
NEAREST FLOOR DRAIN.
DRAIN ROUTED TO
NEAREST FLOOR DRAIN.
RH-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:3
P M
MH306
3D VIEW ATTIC - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY
183 238
MH306
1 ATTIC LEVEL 3D - HVAC
ALARM
PROCESSING
D U
T Y
C Y
C
LE
F U
N C
T
IO
N
S C
H E
D U
LE
S
T A
R T /S
T O
P
RETURN FAN VSMC ALARM
SUPPLY FAN VSMC ALARM
RETURN FAN STATUS
STATIC PRESSURE HIGH LIMIT
SUPPLY AIR FLOW (CFM)
RETURN LOW PRESSURE
S T A
T U
S
SYSTEM
A
LA
R M
P R
IO
R
IT
Y
/A D
D -A
LT
E
R N
A T E
N O
E
LE
C T R
IC
D
E V
IC
E
S P
E E
D C
O M
M A
N D
P O
IN
T
ID
DISCHARGE STATIC PRESSURE
DISCHARGE AIR HUMIDITY
DISCHARGE AIR TEMPERATURE
MIXED AIR TEMPERATURE
COOILING COIL TEMPERATURE
SYSTEM COMPONENT:
RETURN AIR FLOW (CFM)
RETURN AIR TEMPERATURE
-- O P
E N
/C L O
S E
S T A
R T /S
T O
P -- V
A L V
E P
O S
IT
IO
N
D A
M P
E R
P O
S
IT
IO
N
JOB: 0555.09
VAV AIR HANDLER
BUILDING #1
SYSTEM:
BUILDING:
LEGEND
POINT
BINARY
T E
M P
E R
A T U
R E
T I)
L O
C A
L A
L A
R M
P A
N E
L
M A
S T E
R A
LA
R
M P
A N
E L
A R
E A
A L A
R M
P A
N E
L
H
IG
H S
T A
T
IC
P R
E S
S U
R E
E N
D S
W
IT
C H
P R
E S
S U
R E
F
IR
E A
LA
R
M
L O
W T
E M
P E
R A
T U
R E
P E
R C
E N
T
P R
E S
S U
R E
P O
S
IT
IO
N
F L O
W
H
IG
H L
IM
IT
L O
W L
IM
IT
M A
N U
A L R
E S
E T
A U
T O
R E
S E
T
SYSTEM INPUTS
ANA- BINARY ANALOG
S P
A C
E T
E M
P . C
O N
T R
O L
--S T A
T
IC
P R
E S
S U
R E
R E
S E
T
--D E
M A
N D
L
IM
IT
IN
G
T E
M P
E R
A T U
R E
R E
S E
T
T E
M P
E R
A T U
R E
O V
E R
R
ID
E
E N
T H
A
LP
Y E
C O
N O
M
IZ
E R
T E
M P
E R
A T U
R E
E C
O N
O M
IZ
E
R
F A
IL
U
R E
M O
D E
P R
E S
S U
R E
/V O
LU
M
E C
O N
T R
O L
REMARKS
F U
LL
C
O M
M U
N
IC
A T
IO
N
SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
PAGE:
RETURN AIR HUMIDITY
SUPPLY FAN STATUS
MIXED AIR LOW LIMIT
RETURN AIR DAMPER
RETURN FAN START/STOP
CHILLED WATER VALVE V-1
EXHAUST AIR DAMPER
MINIMUM OUTSIDE AIR DAMPER
SUPPLY FAN VSMC
OUTSIDE AIR DAMPER
RETURN FAN VSMC
S T A
T
IC
P R
E S
S U
R E
C A
R B
O N
D
IO
X
ID
E
H U
M
ID
IT
Y
V A
C U
U M
SUPPLY FAN START/STOP
AI-1
AI-2
AI-3
AI-4
AI-5
AI-6
AI-7
AI-8
AI-9
T R
E N
D
IN
G
BI-1
BI-2
BI-3
BI-4
BI-5
BI-6
BI-7
AO-1
AO-2
AO-3
AO-4
AO-5
AO-6
AO-7
BO-2
BO-3
FULL COMMUNICATION
FULL COMMUNICATION
A B
B R
E V
IA
T
IO
N
TT-RAT
MT-RAH
FT-RAF
TT-MAT
TT-CCT
TT-DAT
SPS-DA
MT-DAH
FT-SAF
PSL
RF-STS
SF-STS
TSL
PSH
SF-ALA
RF-ALA
RF-SPD
SF-SPD
D-OA
D-RA
D-EA
D-MIN
CLG-V1
RF-SST
SF-SST
NTS
ECONOMIZER
POINTS LIST FOR VAV AIR HANDLING UNIT WITH
OUTPUTS
LOG
NTS
VAV AIR HANDLING UNIT WITH ECONOMIZER CONTROL DIAGRAM
EXHAUST AIR
D-EA D-RA
P R
E
F
IL
T E
R
OUTSIDE AIR
D-OA
C O
IL
C
O O
L
IN
G
CHR
CHS
RETURN FAN
SUPPLY FAN
RETURN
AIR
SUPPLY AIR
TO TERMINAL
UNITS
TT TT
MT
F
IN
A L
F
IL
T E
R
TT MT
HSVSMC
HSVSMC
MAT CCT
SD-SA
CURRENT
TRANSMITTER
FOR FAN
STATUS ,TYP.
PSH
SMOKE
DETECTOR, TYP.
VARIABLE SPEED MOTOR
CONTROLLER, TYP.
ZC
ZC
ZC
TT
DAT
SST
PSL
RAT
SST
SD-RA
SPSTSL
ECC
ECC
N.O.
DAH
RAH
1.0 GENERAL
1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT
IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.
WHEN THE UNIT IS "OFF" D-OA AND D-EA SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" ALL
ASSOCIATED SMOKE DAMPERS SHALL BE FULLY OPEN. D-OA, D-RA AND D-EA SHALL MODULATE IN
ACCORDANCE WITH THE FOLLOWING SEQUENCE:
2.0 TEMPERATURE CONTROL
2.1
2.2
2.3
3.0 AIR FLOW CONTROL
3.1
3.2
3.3
3.4
4.0 FREEZE PROTECTION
4.1
6.0 EMERGENCY CONSTANT SPEED OPERATION
6.1
SUPPLY DISCHARGE AIR TEMPERATURE SETPOINT (55.0 DEG F ADJUSTABLE - AS SET BY ECC), SENSED BY SENSOR TT-DAT, SHALL BE MAINTAINED BY MODULATING CLG-V1. COOLING CONTROL
VALVES SHALL BE MODULATED VIA PID CONTROL LOOP TO MAINTAIN THE SUPPLY AIR TEMP.
WHEN THE OUTSIDE AIR DEW POINT TEMPERATURE, AS DETERMINED BY THE CAMPUS WEATHER
STATION SENSORS, IS LOWER THAN 55.0 DEG F (ADJ) AND THE OUTSIDE AIR DRY BULB
TEMPERATURE IS BETWEEN 38.0 - 70.0 DEG F (ADJ), THE UNIT ECONOMIZER MODE SHALL BE
ENABLED. WHEN THE ECONOMIZER IS ENABLED, RELIEF HOOD DAMPER D-RH SHALL FULLY OPEN
AND DAMPERS D-OA, D-RA, AND D-EA SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR
SETPOINT AS SENSED BY THE DISCHARGE AIR SENSOR TT-DAT.
WHEN THE OUTSIDE AIR DEW POINT TEMPERATURE IS GREATER THAN 55.0 DEG F (ADJ) OR THE
OUTSIDE AIR DRY BULB TEMPERATURE IS OUTSIDE OF THE 38.0 - 70.0 DEG F RANGE, THE
ECONOMIZER SHALL BE DISABLED, RELIEF HOOD DAMPER D-RH SHALL CLOSE, DAMPER D-EA SHALL
CLOSE, D-RA SHALL OPEN AND D-OA SHALL MODULATE TO MAINTAIN THE MINIMUM OUTSIDE AIR
CFM SETPOINT.
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE
SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE
(FIELD ADJUSTABLE), SENSED BY SPS-DA. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING
LOAD BY POLLING ALL AIR TERMINAL UNITS EVERY 10 MINUTES (ADJ).
A. IF ONE (OR LESS) TERMINAL UNIT DAMPER IS GREATER THAN 90% OPEN, DECREASE
STATIC PRESSURE SET POINT BY 0.1"
B. IF TWO TERMINAL UNIT DAMPERS ARE GREATER THAN 90% OPEN, STATIC PRESSURE SET
POINT REMAINS THE SAME.
C. IF MORE THAN TWO TERMINAL UNIT DAMPERS ARE GREATER THAN 90% OPEN, INCREASE
STATIC PRESSURE SET POINT BY 0.1"
THE DIGITAL CONTROL PANEL, USING BUILDING PRESSURE SENSORS ON THE FLOOR SERVED BY THE AHU
AND AN OUTDOOR PRESSURE SENSOR, SHALL CONTROL THE SPEED OF THE RETURN AIR
USING HIGH PRESSURE SENSOR PSH LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT
THE SUPPLY FAN FROM DEVELOPING OVER (AHU-5) 5", (AHU-6) 4.75", (AHU-10) 3" OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT PSH DOES EXCEED THE PRESSURE LIMIT THE SUPPLY AIR FAN SHALL STOP.
PSH SHALL BE HARDWIRED TO THE SUPPLY FAN AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE.
PSH WILL REQUIRE MANUAL RESET AT THE DEVICE.
USING LOW PRESSURE SENSOR PSL LOCATE AT THE RETURN FAN INLET, SHALL PREVENT THE RETURN FAN FROM DEVELOPING OVER - (AHU-5) 3", (AHU-6) 3", (AHU-10) 2" OF NEGATIVE STATIC PRESSURE (FIELD ADJUSTABLE) IF STATIC PRESSURE AT PSL DOES EXCEED THE PRESSURE LIMIT THE RETURN AIR FAN SHALL STOP. PSL SHALL BE HARDWIRED TO THE RETURN FAN AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. PSL WILL REQUIRE MANUAL RESET.
UPON FAILURE OF THE VSMC, THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED
AUTOMATICALLY AT THE DIGITAL CONTROL PANEL OR THE ECC THROUGH THE 3-CONTACT BY-PASS STARTER.
IF THE AIR TEMPERATURE AS SENSED BY TT-MAT FALLS BELOW 45°F (ADJ.), AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC AND THE OUTSIDE AIR DAMPER SHALL CLOSE UNTIL THE AIR TEMPERATURE RISES ABOVE 45°F (ADJ.). IF THIS TEMPERATURE FALLS BELOW 36°F (ADJ.), AS SENSED BY THE TSL THE COOLING COIL SHALL FULLY OPEN, AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL
WILL REQUIRE MANUAL RESET AT THE DEVICE.
5.0 LOSS OF COOLING PROTECTION
5.1 IF THE CHILLED WATER SUPPLY TEMPERATURE RAISES ABOVE 55°F (ADJ.), AN ALARM SIGNAL SHALL
INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE RAISES ABOVE 60°F (ADJ.), THE SUPPLY AND
RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL
CONTROL PANEL AND ECC UNLESS THE ASSOCIATED CHILLERS ARE ON LOW TEMPERATURE
SHUT-DOWN.
SUPPLY SMOKE DETECTOR
EXHAUST FAN STATUS (TYP.)
EXHAUST FAN START/STOP (TYP.)
FIRE ALARM
SMOKE DAMPER (TYP.)
RETURN SMOKE DETECTOR BI-8
BI-9
BI-10
BO-4
BO-5
BI-11
SD-RA
SD-SA
EF-SST
EF-STS
A F
M D
FT
A F
M D
FT
A F
M D
FT
SAF
DA
RAF
OAF
RF-STS
RF
SF-STS
SF
D-RA
D-EA
D-OA
SPD
RF
SPD
SF
ZC
CLG-V1
OUTSIDE AIR FLOW (CFM) AI-10 FT-OAF
CHILLED WATER FLOW (GPM) AI-11 ----- TYP. FOR ALL AHU COILS
N.C.
N.C.
N.O.
BUILDING PRESSURE MONITORS
CO2 MONITORS
AI-12
AI-13
RELIEF HOOD DAMPER BO-1 D-RH
7.0 GENERAL EXHAUST FANS
7.1 GENERAL EXHAUST FANS AND HOOD FAN TO BE ENERGIZED WHEN RESPECTIVE SUPPLY AIR FAN IS ENERGIZED.
CHILLED WATER TEMPERATURE AI-12 TT-CWT
MIXED AIR LOW PRESSURE BI-12 PSL-MA
TYP. FOR ALL AHU COILS
LOCATE SENSOR 2/3
DOWN LONGEST MEDIUM
PRESSURE DUCT MAIN.
PSL-MA
TT
CWT
PRESSURE SWITCH
LOW (NEGATIVE) TO
DISABLE UNIT WHEN
LOW PRESSURE LIMIT
SET POINT IS REACHED
D-RH
ZC
D-RH
N.C.
RELIEF AIR
RELIEF HOOD
3.5 USING LOW PRESSURE SENSOR PSL-MA LOCATE AT THE MIXED AIR SECTION SHALL PREVENT THE UNIT FROM DEVELOPING OVER - (AHU-5) 3", (AHU-6) 3", (AHU-10) 2" OF NEGATIVE STATIC PRESSURE (FIELD ADJUSTABLE) IN THE MIXED AIR SECTION TO PROTECT THE OA DUCT. IF STATIC PRESSURE AT PSL-MA DOES EXCEED THE PRESSURE LIMIT THE SUPPLY FAN SHALL STOP. PSL-MA SHALL BE HARDWIRED TO THE SUPPLY FAN AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. PSL-MA SHALL REQUIRE
MANUAL RESET.
8.0 DEMAND CONTROL VENTILATION. (DCV) - (SEQUENCE APPLIES ONLY TO AHU-10):
8.1 WHENEVER THE AIR HANDLING UNIT IS OPERATING, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN.
THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE LARGER OF THE MINIMUM OUTSIDE AIR FLOW RATE AS MEASURED AT THE OUTSIDE AIRFLOW MEASURING STATION AND THE FLOW RATE NEEDED TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE. THE
MINIMUM OUTSIDE AIR FLOW RATE SHALL BE RESET AS FLOW:
A. DURING UNIT OPERATION THE MINIMUM OA FLOW RATE SHALL NOT FALL BELOW THE AMOUNT
LISTED IN THE AHU SCHEDULE.
B. IF ANY DCV ZONE HAS A CO2 CONCENTRATION ABOVE ITS INDICATED SETPOINT AND THAT ZONE'S
TAB MINIMUM FLOW IS RESET TO ITS MAXIMUM FLOW RATE, THE AHU MINIMUM OA SETPOINT
SHALL INCREASE UNTIL THAT ZONE CO2 SETPOINT IS SATISFIED OR UNTIL THE MAXIMUM OUTSIDE
AIR FLOW ON THE AHU SCHEDULE IS REACHED.
C. IF THE CRITICAL ZONE'S CO2 CONCENTRATION DROPS BELOW THE INDICATED CO2 SETPOINT, THE
AHU MINIMUM OUTSIDE AIR RATE SHALL BE RESET LOWER UNTIL THE CO2 CONCENTRATION
REACHES ITS SETPOINT OR UNTIL THE AHU OUT SIDE AIR FLOW RATE REACHES THE MINIMUM OA
RATE IN AHU SCHEDULE.
CO2-G
GLOBAL CO2 SENSOR
MOUNTED ON NORTH
FACE OF BUILDING.
COORDINATE EXACT
LOCATION WITH OWNER.
PRESSURE SWITCH LOW (NEGATIVE) TO
DISABLE RETURN FAN WHEN SMOKE
DAMPER IN RETURN DUCT CLOSES
PRESSURE SWITCH HIGH
(POSITIVE) TO DISABLE FAN
WHEN HIGH PRESSURE LIMIT
SETPOINT IS REACHED
SEQUENCE OF OPERATION FOR VAV AIR HANDLING UNIT WITH ECONOMIZER
FAN TO MAINTAIN A TARGET PRESSURE DIFFERENTIAL OF 0.01" (ADJUSTABLE). SENSORS TO BE LOCATED ON THE NORTH SIDE OF THE BUILDING. COORDINATE WITH OWNER FOR EXACT LOCATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
C R e v it L o c a l F ile s \I C
T
B L D
G
M e c h a n ic a l C
D S
A a ro n .C
.M e y e r.
rv t
/1
/2
:0
:4
P M
MH401
CONTROLS - HVAC RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
184 238Revisions: Date:
TE
TEMPERATURE ELEMENT
INTERFACE WITH METERING
STATION
TEFE
SUPPLY
OUTLET
FLOW ELEMENT
BACNET
INTERFACE
NOTE:
1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURER
2.
3.
PROVIDE BTU METER FOR CHILLED WATER SERVICES TO BUILDING. PROVIDE FLOW METERS FOR DOMESTIC COLD, HOT, AND HOT WATER RECIRCULATION PIPING. PROVIDE TEMPERATURE SENSORS FOR DOMESTIC COLD, HOT, AND HOT WATER RECIRCULATION PIPING. REFER TO PLUMBING PLANS FOR MORE INFORMATION.
LEGEND
AIR FLOW CONTROL VALVE
PRESSURE INDEPENDENT TYPE
ACV
CORRIDOR
ANTE ROOM
PATIENT
ROOM
TOILET ROOM
ATTIC
EXHAUST BLOWERACV
HS
S/A
REHEAT
COIL
BED
VSMC
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
MAINTAIN THE ATTACHED TOILET, IF ANY, AT NEGATIVE AIR PRESSURE WITH RESPECT TO THE AII ROOM. HOWEVER, THE DESIGN NEED NOT INCLUDE A PRESSURE DIFFERENTIAL SENSOR FOR VERIFICATION.
LOCATE CEILING EXHAUST AIR REGISTER OVER EITHER SIDE OF THE PATIENT BED, AT THE HEAD OF THE BED.
LOCATE THE SUPPLY AIR OUTLET TO BLOW AIR TOWARDS THE OCCUPIED AREA.
PROVIDE A DEDICATED EXHAUST SYSTEM FOR THE AII ROOMS WITHOUT MIXING IT WITH ANY OTHER EXHAUST.
KEYED PRESSURE MONITORS SHALL BE PROVIDED AT THE ANTE ROOM ENTRANCE (FROM CORRIDOR) AND THE AII
PATIENT ROOM ENTRANCE (FROM ANTE ROOM).
DOOR SWITCHES SHALL BE PROVIDED WITH PRESSURE MONITORS TO PREVENT NUISANCE ALARMS.
AII PATIENT ROOM REQUIRES 12 ACPH (MINIMUM). REDUCE TO 6 ACPH (MINIMUM) WHENEVER ROOM IS UTILIZED AS
AN ACUTE CARE PATIENT ROOM. A KEY SWITCH LOCATED ON EACH PRESSURE MONITOR WILL SWITCH THE ROOM
MODE. THE EXHAUST FAN VFD SPEED SHALL BE ADJUSTED UPON KEY SWITCH ACTIVATION.
NTS
ISOLATION ROOM (AII)( WITH ANTE ROOM)
AIR SYSTEM FOR AIRBORNE INFECTION
SA
FROM
AHU
FROM
OTHER
AII ROOMS
SEE NOTE
NEGATIVE PRESSURE
EXHAUST
VARIABLE SPEED
MOTOR CONTROLLER
TOTAL
EXHAUST
EXHAUST FAN
DISCHARGE
SEE
NOTE 1
VSMC
FT
TT
TT
PDT
1. SECONDARY CHILLED WATER PUMP SEQUENCE
1.1
1.2
1.3
1.4
1.5
1.6
PUMPS ARE NORMALLY…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .