The federal contract opportunity is for the renovation of Building 1 in Biloxi, MS, including selective demolition, exterior building envelope alterations, and interior renovation of the 3rd, 4th, and 5th floors, as well as the crawl spaces and attic. The work will involve upgrades to the interior utilities and building systems, such as HVAC, plumbing, electrical, telecommunications, chilled water, and fire protection systems. There will also be limited structural, mechanical, and electrical work related to the underside of the 3rd floor structure within the occupied areas of the 2nd floor, with site restoration after the project is complete. The awardee will be responsible for monitoring the existing Building 1 foundation system throughout the project. The period of performance is 912 calendar days from the receipt of the Notice to Proceed, and the project magnitude is between $50 million and $100 million. Wage Rate Requirements (Construction) apply.
View the file
Other files
Show 40 more
Latest 50 of 64 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
LO
O R
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
3. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN A SEPARATE
RACEWAY FROM ALL OTHER CIRCUITS.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. INSTALL ALL
RECEPTACLES WITH GROUND PRONG ORIENTED UP.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX
CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN
GRILLE.
11. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
12. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
14. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
15. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE
EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH
IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
16. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF
WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH HIS/HER WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. REFER TO APPENDIX OF PREVIOUS PROJECT AS BUILT DOCUMENTS FOR LOCATIONS OF
ELECTRICAL WORK THAT HAS BEEN INSTALLED.
9. CONTRACTOR SHALL REMOVE ANY AND ALL ABANDONED CONDUIT BACK TO THE SOURCE.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:4
P M
E001
LEGENDS - ELECTRICAL RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
204 238
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED FLOOR) FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
GENERAL NOTES:
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE FAULT
CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMBOR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
ELECTRICAL ABBREVIATIONS
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GOR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUTOR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
ELECTRICAL SYMBOLS - POWER PLAN
JUNCTION BOX
TRANSFORMER, PLAN
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
WYE CONNECTION
EARTH GROUND
LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF CIRCUITS,
NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE SEPARATE GREEN
GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN;
NOT SHOWN
PULL BOX
WIREWAY
RIGID CONDUIT LINE = RC
SUBSTATION
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, SPECIAL PURPOSE
BLANK = 120V, 20A, 1 PHASE, 1-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 1-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
DIRECT BURIAL CABLE = DB
POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
DP#__
LP
T
PB
S
HVS
LVS
P T
TIME CLOCK
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &
RECEPTACLE.
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
RECEPTACLE, SWITCHED DUPLEX
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
ELECTRICAL SYMBOLS - POWER PLAN
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
VARIABLE FREQUENCY DRIVE
TC
S
R
VFD
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
S
A
B
C
A
B
C
D
E
E
SWITCH, CEILING MOUNTED PULL
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED
RECESSED DOWNLIGHT FIXTURE, LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 610x1220mm (2'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 305x1220mm (1'x4');
LETTER INDICATES TYPE.
ELECTRICAL SYMBOLS - LIGHTING PLAN
LIGHT FIXTURE, RECESSED, 305x2439mm (1'x8'); LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 610x1220mm (2'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 305x1220mm (1'x4'); LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED,
305x2439mm (1'x8'); LETTER INDICATES TYPE.
LIGHT FIXTURE, EMERGENCY;
LETTER INDICATES TYPE.
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN
LIGHT FIXTURE, RECESSED, 610x610mm (2'x2');
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 2'x2' [610x610mm]; LETTER INDICATES TYPE.
LIGHT TRACK WITH HEADS AS SHOWN
LIGHT FIXTURE, STRIP/INDUSTRIAL; LETTER INDICATES TYPE.
LIGHT FIXTURE, WALL MOUNTED
LIGHT FIXTURE, DIRECTIONAL
S
0-10v DIMMER FOR LED, VERIFY
COMPATABILITY WITH LIGHT
FIXTURE DRIVER MANF'R.
Sd10=
SEE SHEET E153 FOR LIGHTING CONTROLS SCHEDULE.
RECEPTACLE, DUPLEX
T
RECEPTACLE, DUPLEX TAMPER RESISTANT
RECEPTACLE, ABOVE COUNTER, 42" AFF-COORDINATE WITH BACKSPLASH.
FLOOR BOX FLUSH MOUNT, DUAL COMPARTMENT: POWER AND DATA
GFI
COMMUNICATIONS
TELEPHONE AND DATA OUTLET,ABOVE COUNTER 2 DATA/2VOICE, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
TELEPHONE/DATA OUTLET IN FLOOR BOX, 2 DATA/2VOICE, 1"C TO NEAREST WALL THEN UP TO ACCESSIBLE CEILING SPACE.
MONITOR WALL MOUNTED
TELEVISION TERMINAL CABINET, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
INTERCOM PHONE & CALL IN SWITCH, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
INTERCOM STAFF STATION, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
FLOOR MOUNTED INTERCOM STAFF STATION, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
PUBLIC ADDRESS HEAD END EQUIPMENT RACK
TELEPHONE BACKBOARD/TBB, 4'x8'x3/4"
CALL SWITCH, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
VOLUME CONTROL, 3/4" EC UP TO ACCESSIBLE CEILING SPACE.
ICTC INTERCOM TERMINAL CABINET
TV OUTLET WALL MOUNTED
INTERCOM MASTER
IC
PA
S
TVTC
IM
IC
IC
CS
S
WALL MOUNTED SPEAKER
PAGING HORN
MUSIC & PAGING RACK
PROGRAM BELL
CEILING SPEAKER
F
MPR
S
V
TBB
M
PB
S
0 W
SEE DETAIL
SEE SPECS
SEE SPECS
SEE DETAIL
46"
88"
46"
46"
SEE SPECS
SEE DETAIL
84"
84"
46"
80"
SEE SPECS
FLOOR BOX
FLOOR BOX
FLOOR BOX
FLOOR BOX
18"
46"
46"
18"
46"
46"
S
TV
SECURITY
MAGNETIC LOCK STRIKEMDL
CARD READER 46"CR
PB REQUEST TO EXIT SENSOR/BUTTON
C FIXED CAMERA, CEILING MOUNT UON
TELEMETRY
TELEMETRY CENTRAL SERVER -TCS
TELEMETRY DISPLAYTDM
TELEMETRY ANTENNAT
MS MOTION SENSOR
WIRELESS ACCESS POINT, 2 DATA DROPS EACH LOCATION. 3/4"C. EACH DROP BACK TO MDF/IDF ON SAME FLOOR.WAP AB. CEILING
1" EC TO ACCESSIBLE CEILING SPACE, AS REQ'D.
MIC MICROPHONE, 1" EC UP TO ACCESSIBLE CEILING SPACE OR AS REQUIRED.
CAMERA, PTZ OPTICAL, CEILING MOUNTED. C OPT
CAMERA, PTZ DIGITAL, CEILING MOUNTED. C DIG
TELEPHONE OUTLET,ABOVE COUNTER 2VOICE, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
DATA OUTLET,ABOVE COUNTER 2 DATA, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
TELEPHONE AND DATA OUTLET, 2 DATA/2VOICE, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
TELEPHONE OUTLET, 2VOICE, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
DATA OUTLET, 2 DATA, 1"C TO ACCESSIBLE CEILING SPACE, BACKBOARD, OR TERMINAL AS REQ'D.
DATA OUTLET IN FLOOR BOX, 2 DATA, 1"C TO NEAREST WALL THEN UP TO ACCESSIBLE CEILING SPACE.
INTERCOM IN FLOOR BOX, 2VOICE, 1"C TO NEAREST WALL THEN UP TO ACCESSIBLE CEILING SPACE.
TELEPHONE OUTLET IN FLOOR BOX, 2VOICE, 1"C TO NEAREST WALL THEN UP TO ACCESSIBLE CEILING SPACE.
J
DIGITAL POWER METERDPM
A. REFER TO FA201 FOR FIRE ALARM SYMBOLS.
B. REFER TO M-E100 FOR 2ND FLOOR ELECTRICAL WORK.
C. WHERE COVERPLATES CONFLICT WITH CASEWORK OR MILLWORK,
SLIGHTLY ADJUST THE MOUNTING HEIGHTS OF THE WIRING
DEVICES TO MAKE THE COVERPLATES CLEAR THE COUNTERTOP OR
BACKSPLASH BY 1/2".
D. ADDITIONAL SYMBOLS MAY BE SHOWN OR DENOTED ON OTHER
SHEETS.
E. ALL SYMBOLS, NOTES, AND ABBREVIATIONS SHOWN ON THE
LEGEND ARE NOT NECESSARILY USED IN THIS SET OF CONTRACT
DOCUMENTS.
F. NO SPLICING OF CONDUCTORS/CABLES ALLOWED IN THIS PROJECT.
G. NO EXCEPTIONS, ALL CABLES AND CONDUCTORS MUST BE IN
CONDUIT OR CABLE TRAY AND ALL CABLES AND CONDUCTORS IN
CABLE TRAY ARE TO BE SEPARATED BY FUNCTION.
GROUND BARGB
AV 18"AV ROUGH-IN, 1-1/2"C TO ACCESSIBLE CEILING SPACE.
A
OR
E-CONNECTIONE
Revisions: Date:
"P V C
"P V C
6"PVC
6"PVC
8"PVC
"P V C
8"PVC
6"PVC
"P V C
6"PVC
6"PVC
"P V C
"P V C
"P V C
"P V C
8"PVC
6"PVC
"P V C
"P V C
10"PVC
RETAININGWALL
CONC
F
LU
M E
A/C
WALK
T-4
D
U G
U G
U G
P P
P
P P
U G
FOE FOEEXISTING FIBER OPTIC PATHWAY
LINETYPE LEGEND:
EP100
EXISTING
GENERATOR
ES101
Sim
EP100
B
LD
G
M D F
FO
E
P U
LL
B O X
LO
C A
TIO
N
EXISTING
MANHOLE
PULL BOX
LOCATION
FO
E
FOE FOE
FO
E
FO
E
FO
E
FOE
FOE
FOE
BLDG 1
MDF
EXISTING
GENERATOR
U G
U G
U G
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:5
P M
ES101
SITE PLAN - ELECTRICAL RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
205 238
1" = 40'-0"ES101
1 SITE PLAN - ELECTRICAL
KEYED NOTES:
1. 12 - 3" UNDERGROUND CONDUITS FOR POWER.
2. 4 - 3" UNDERGROUND CONDUITS FOR POWER.
3. 12 - 3" CONDUITS FOR POWER. ROUTE IN CRAWLSPACE.
4. 4 - 3" CONDUITS FOR POWER. ROUTE IN CRAWLSPACE.
5. NOT USED.
6. NEW LIGHTNING PROTECTION SYSTEM FOR BUILDING 1,
SEE SPECIFICATIONS.
7. REFER TO EP100 FOR ELECTRICAL WORK TO INSTALL 1-
BP1 IN BUILDING 1 BASEMENT. PROVIDE NEW FEED FROM
EXISITNG PANEL AS INDICATED.
8. CONNECT TO EXISTING 1200 AMP GENERATOR OUTPUT
BREAKER TO FEED PANEL EDP IN ATTIC.
9. DEMO ELECTRICAL CONNECTIONS FOR EXISTING PUMPS
REFER TO MS101. INSTALL ELECTRICAL CONNNECTIONS
AND VFDS FOR NEW PUMPS SCHWP-1 & SCHWP-2.
INSTALL TWO NEW 200A CIRCUIT BREAKERS IN PANEL
MDP TO FEED SCHWP-1 & SCHWP-2. UTILIZE CIRCUIT
MDP-1,3,5 FOR THE VFD AND PUMP SCHWP-1, AND
CIRCUIT MDP-2,4,6 FOR THE VFD AND PUMP SCHWP-2.
REFER TO E401 POWER CONNECTION SCHEDULE ID #18.
CONTRACTOR SHALL FIELD VERIFY LOCATION,
EQUIPMENT, AND WORK REQUIRED PRIOR TO BID.
CONTRACTOR SHALL NOTIFY R.E. AND ENGINEER OF ANY
CONCERNS.
1/8" = 1'-0"ES101 ES101
SITE PLAN - LARGE SCALE GENERATOR BUILDING
PLAN
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
INSTALLATION NOTES.
PATIENT ROOM 1
3B114
PATIENT ROOM 2
3B116
PATIENT ROOM 3
3B118
PATIENT ROOM 4
3B119
CLEAN EQUIPMENT STORAGE
3B121
MD DICTATION
3B122
PATIENT ROOM 5
3B123 PATIENT ROOM 6
3B124
WHEELCHAIR ALCOVE
3B102
ELECTRICAL ROOM
3B101
PATIENT CENTERED CARE
3B103
MEDICAL GAS STORAGE
3B104
CRASH CART
3B105
HAC
3B106
CLEAN UTILITY
3B107
CLEAN LINEN
3B108
KINESIOTHERAPY
3B109
WEST STAIR
3B110
PATIENT ROOM 7 - NEGATIVE
PRESSURE
3B111
UNASSIGNED
3B113
PATIENT BATHROOM
3B111A
ANTE ROOM
3B111B
PATIENT BATHROOM
3B114A
PATIENT BATHROOM
3B118A
PATIENT BATHROOM
3B119A
PATIENT BATHROOM
3B123A
PATIENT BATHROOM
3B124A
CORRIDOR
C3-104
CENTRAL STAIR
3A101
MALE TOILET
3A102
FEMALE TOILET
3A103
FAMILY TOILET
3A104
WAITING / LOUNGE
3A105FAMILY CONSULTATION
3A106
MECHANICAL SHAFT
3A107
SOILED LINEN
3A110
ENGINEERING
3A111
HEAD NURSE / ASSISTANT MANAGER
3A112
MEDICATION ROOM
3A114
NOURISHMENT STATION
3A115
PATIENT ROOM 8
3A117
PATIENT ROOM 9
3A118
MD DICTATION
3A120
IMD SUPPLY STORAGE
3A121
PATIENT ROOM 10
3A122
PATIENT ROOM 11
3A123
BARIATRIC PATIENT ROOM 12
3A125
CONFERENCE / REPORT ROOM
3A128
PATIENT BATHROOM
3A117A PATIENT BATHROOM
3A118A
PATIENT BATHROOM
3A122A PATIENT BATHROOM
3A123A
BARIATRIC PATIENT BATHROOM
3A125A
HAC
3A127
TELEMETRY
3A130
BARIATRIC PATIENT BATHROOM
3A131A
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
3A131
ANTE ROOM
3A131B
EAST STAIR
3A133
PHARMACY CUBICLES
3A134
MALE LOCKERS
3A137
STAFF TOILET
3A136
STAFF SHOWER
3A135
CORRIDOR
3A141
STAFF LOUNGE
3A138
FEMALE LOCKERS
3A139
TELECOMM
3A140
SOILED UTILITY
3A142
NURSE STATION
3A109A
CORRIDOR
C3-105
CORRIDOR
C3-103
NURSE SERVER
3A124
CORRIDOR
C3-109
NURSE SERVER
3A132
CORRIDOR
C3-101
NURSE SERVER
3B112
NURSE SERVER
3B125
CORRIDOR
C3-107
NURSE SERVER
3A126NURSE SERVER
3A119
NURSE SERVER
3B120NURSE SERVER
3B117
NURSE SERVER
3B115
NURSE STATION
3A109
PATIENT BATHROOM
3B116A
TYP
TYP
REV
ALIGN ALIGN
FEC
FEC
FEC
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
NOTE: SEE SHEET "IN101" FOR INTERIOR ELEVATION REFERENCE
CORRIDOR
C3-100
CORRIDOR
C3-102
CORRIDOR
C3-102A
CORRIDOR
C3-106
CORRIDOR
C3-107A
CORRIDOR
C3-108
41R 41R 41R 41R 41R 41R 31R 31R 31R 31R 31R
31R
41R
41R 31R
11W
11W
11W
11W
11W 11W
11W
11W 11W 11W
11W 11W
11W 11W
11W 11W
31R
31R
41R 41R
41R
27R
27R 27R
27R
27R
27R
27R
27R
27R
34R
34R
2X
2X
2X
11W
5S 5S
5S
5S
31R22
31R22
32R 28R
5S
31R
31R
41R
28R 28R
5S 5S
31R
31R 31R
27R
31R
31R
41R
41R
31R
31R
31R
31R
31R
41R
41R
31R22 31R22
41R
41R
31R
31R
31R
31R
32R
41R22
41R22
34R 34R
34R
27R
27R
27R
27R 27R
34R
222019181716151413121110987654321 21
A
B
C
D
E
F
G
27R
27R
27R
27R
27R 34R
27R
27R 27R
27R
27R
27R
34R
34R
31R
31R
31R
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
NLT
41R41R
41R
41R
41R
P
31R
31R
P
P P
P
PW
P
DW
DW
DW
P
P P
P
DWDW
P
P
PP
DW
P
P
DW
a b
P
L
41R
3NA
3NB
3C1
3LS1
c d
P
P
P
H
H
LS
LS
P
LSLS
P
LS
P
LS
D
D
D
D
D D
DDDDDD
DDD
D D
D
D
D
D D
DD
D
D
5S
1a
1b
2W
2W
2W
2W
5S
5S 5S
U C
UC4
UC2
U C
U
C
UC3 UC3
U C
27R
27R
27R
27R27R
34R
NLT
NLT
2W
NLT
27R 27R
27R
27R
27R
34R
2W
27R 27R
27R
27R
27R
2W
34R
NLT
NLT
NLT
NLT
NLT
NLT
27R27R
27R
27R
27R 34R
2W
27R27R
27R
27R
27R
2W
34R
NLT
NLT
NLT
NLT
27R 27R
27R
27R
27R 34R
2W
27R 27R
27R
27R
27R
2W
34R
NLT
NLT
NLT
NLT
NLTNLT
NLTNLT
NLT
27R
27R
NLT
34R
27R
27R 27R
27R
27R
31R22
31R22
NLT
NLT
NLT
2W
1X d10
28R 28R 28R28R
28R28R
28R
28R 28R 28R28R
41R
41R
D
DDD
31R31R
31R 31R
31R
IC
IC
32R
32R
32R d10
D W
D d10
3NA-40
,1-#12, 1-#12, 1-#12
3NA-41
,1-#10, 1-#10, 1-#10
3NA-43
,1-#12, 1-#12, 1-#12
3NA-49
,1-#10, 1-#10, 1-#10
3NB-28
,1-#12, 1-#12, 1-#12
3NB-29
,1-#12, 1-#12, 1-#12
3NB-32
,1-#12, 1-#12, 1-#12
3NB-33
,1-#10, 1-#10, 1-#10 b
3LS1-10
,1-#10, 1-#10, 1-#10
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
3C1-41 ,1-#10, 1-#10, 1-#103C1-42 ,1-#10, 1-#10, 1-#10 3C1-43 ,1-#12, 1-#12, 1-#12
3C1-45 ,1-#12, 1-#12, 1-#12
3C1-47 ,1-#10, 1-#10, 1-#10
3C1-48 ,1-#12, 1-#12, 1-#12
3C1-49 ,1-#10, 1-#10, 1-#10
3C1-50 ,1-#8, 1-#8, 1-#8
3C1-53 ,1-#12, 1-#12, 1-#12
3C1-54 ,1-#12, 1-#12, 1-#12
3C1-55 ,1-#12, 1-#12, 1-#12
1X
32R22
32R22 32R22
32R22
32R22
32R22
32R22
32R22
32R22 32R22
32R22
3NB-26
,1-#8, 1-#8, 1-#8
3NB-26
,1-#8, 1-#8, 1-#8
3NA-44
,1-#10, 1-#10, 1-#10
28R
31R 31R 31R
3C1-51,3NA-45
,2-#10, 1-#10, 1-#10
2-#10, 1-#10, 1-#10
P
3LS1-9
,1-#12, 1-#12, 1-#12
C1
C1
C1 C1 C1
C1
C1 C1 C1 C1
C1 C1 C1 C1
C1
C1 C1
C1 C1 C1
C1
C1 C1 C1
C1 C1 C1
C1 C1
C1
C1
C1 C1
C1 C1
C1 C1
3LS1-12
,1-#12, 1-#12, 1-#12 C1
C1
C1
C1 C1
C1 C1C1
C1
C1 C1
C1
C1 C1
C1 C1
C1
C1
C1C1 C1
3LS1-11
,1-#12, 1-#12, 1-#12
28R
28R
28R
28R
28R
28R
3NA-39
,1-#10, 1-#10, 1-#10
3C1-46 ,1-#10, 1-#10, 1-#10
28R
3NB-27
,1-#10, 1-#10, 1-#10
28R 3C1-44 ,1-#10, 1-#10, 1-#10
28R 28R
28R 28R
28R
C1
28R
3NA-47
,1-#12, 1-#12, 1-#12
3NA-42
,1-#12, 1-#12, 1-#12 d c a b d c a b
1a
1b dc a b
1a
1b d c1 1
1a
1b a b c d a b
1a
1b d c a b
1a
1b
1 c d1 d c a b
1a
1b a b
1a
1b c d1 d c
1a
1b
1a
1b a b a b
3NA-46
,1-#12, 1-#12, 1-#12
3C1-52 ,1-#12, 1-#12, 1-#12 d c a b
2W
1a
1b d c a b1a
1b c d a b
1a
1b d10 d10
P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:1
P M
EL101
3RD FLOOR - LIGHTING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
206 238
1/8" = 1'-0"EL101
1 3RD FLOOR - LIGHTING
KEYED NOTES:
1. TYPICAL LIGHTING CONTROL, LIGHTING FOR ALL PATIENT
ROOMS:
CONTROLLER a - PATIENT EXAM LIGHT, ON HEADWALL.
CONTROLLER b -PATIENT READING LIGHT, ON
HEADWALL.
CONTROLLER c - PATIENT ROOM DOWNLIGHTS.
CONTROLLER d - PATIENT ROOM NIGHT LIGHTS.
1a. CONTROLLER IN PATIENT HEADWALL WILL BE
LABELED "OVERBED LIGHT" IN 1/2" TALL ENGRAVED
LETTERS.
1b. PROVIDE A RELAY AT HEADWALL FOR CONTROL OF
PATIENT ROOM LIGHTING FROM PILLOW HANDSET.
2. SWITCH "a","b", "L" FOR LIGHTING ONLY IN CORRIDORS A, B AND LOBBY/LOUNGE. SWITCH "a" CONTROLS CORRIDOR A, SWITCH "b" CONTROL CORRIDOR B, SWITCH "L" CONTROLS THE LOBBY/LOUNGE LIGHTING.
ALL OF THESE SWITCHES ARE TO BE 0/10V DIMMERS-
LIGHTS SUPPLIED WITH 0/10V DIMMABLE DRIVERS.
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
INSTALLATION NOTES.
2. REFER TO 2/E301 FOR OCCUPANCY SENSOR DETAIL,
3/E301 FOR LAY IN CEILING LUMINAIRE MOUNTING DETAIL,
AND 4/E302 FOR LIGHTING CONTROL PANEL DIAGRAM.
3. REFER TO E401 FOR LIGHTING SYMBOLS AND
SCHEDULES.
4. ALL CABLE SHALL BE IN CONDUIT. INCLUDING LOW
VOLTAGE CABLING. NO J-HOOKS SHALL BE ALLOWED.
PATIENT ROOM 1
4B114
PATIENT ROOM 2
4B116
PATIENT BATHROOM
4B116A
PATIENT BATHROOM
4B114A
PATIENT BATHROOM
4B118A
PATIENT BATHROOM
4B119A
PATIENT ROOM 3
4B118
PATIENT ROOM 4
4B119
CLEAN EQUIPMENT STORAGE
4B121
MD DICTATION
4B122
PATIENT ROOM 5
4B123
PATIENT BATHROOM
4B123A
PATIENT BATHROOM
4B124A
PATIENT ROOM 6
4B124 ENGINEERING
4A111
SOILED LINEN
4A110
STAFF EDUCATION
4A112
MEDICATION ROOM
4A114
NOURISHMENT STATION
4A115
PATIENT ROOM 8
4A117
PATIENT BATHROOM
4A117A
PATIENT BATHROOM
4A118A
PATIENT ROOM 9
4A118
IMD SUPPLY STORAGE
4A121
MD DICTATION
4A120
PATIENT ROOM 10
4A122
PATIENT BATHROOM
4A122A
PATIENT BATHROOM
4A123A
PATIENT ROOM 11
4A123
BARIATRIC PATIENT ROOM 12
4A125
BARIATRIC PATIENT BATHROOM
4A125A
CONFERENCE / REPORT ROOM
4A128
BED STORAGE
4A130BARIATRIC PATIENT BATHROOM
4A131A
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
4A131
M.O.D. ROOM
4A134
EAST STAIR
4A133
STAFF TOILET
4A136
STAFF SHOWER
4A135
MALE LOCKERS
4A137
STAFF LOUNGE
4A138
FEMALE LOCKERS
4A139
TELECOMM
4A140
SOILED UTILITY
4A142
CORRIDOR
4A141
ANTE ROOM
4A131B
CENTRAL STAIR
4A101
MALE TOILET
4A102
FEMALE TOILET
4A103
FAMILY TOILET
4A104
FAMILY CONSULTATION
4A106
MECHANICAL SHAFT
4A107
CORRIDOR
C4-104
WAITING / LOUNGE
4A105
ELECTRICAL ROOM
4B101
PATIENT CENTERED CARE
4B103
MEDICAL GAS STORAGE
4B104
CRASH CART
4B105
HAC
4B106
CLEAN UTILITY
4B107
CLEAN LINEN
4B108
KINESIOTHERAPY
4B109
WHEELCHAIR ALCOVE
4B102
WEST STAIR
4B110
PATIENT ROOM 7 - NEGATIVE
PRESSURE
4B111
PATIENT BATHROOM
4B111A
UNASSIGNED
4B113
ANTE ROOM
4B111B
CORRIDOR
C4-103
NURSE STATION
4A109A
CORRIDOR
C4-105
CORRIDOR
C4-101
CORRIDOR
C4-107
NURSE SERVER
4B120
NURSE SERVER
4B125
NURSE SERVER
4A119
NURSE SERVER
4A124
NURSE SERVER
4A132
NURSE SERVER
4B112
HAC
4A127
NURSE SERVER
4B115
NURSE SERVER
4B117
NURSE SERVER
4A126
M.O.D. BATHROOM
4A134A
CORRIDOR
C4-109
NURSE STATION
4A109
DENTAL VAC CLOSET
4B100A
SIM
TYP
FEC
FEC FEC
NOTE: SEE SHEET "IN102" FOR INTERIOR ELEVATION REFERENCE
CORRIDOR
C4-100
CORRIDOR
C4-102
CORRIDOR
C4-102A
CORRIDOR
C4-106
CORRIDOR
C4-107A
CORRIDOR
C4-108
222019181716151413121110987654321 21
A
B
C
D
E
F
G
41R 41R 41R 41R 41R 41R 31R 31R 31R 31R 31R 31R 41R 41R
11W
11W 11W
11W
11W 11W 11W 11W
11W
11W 11W
11W 11W
11W 11W
31R
31R
2X
11W
5S 5S
5S
5S
5S
31R22
31R22
32R 28R
5S
41R
28R 28R
5S
5S
31R
31R
31R
27R
31R
41R
41R
41R
41R
41R
41R
31R
31R
32R
31R
31R
32R
28R
41R22
41R22
34R 34R
34R
27R
27R
27R
27R
27R
34R
27R
NLT
NLT
NLT
NLT
41R41R
41R 41R
41R
P
31R
31R
P
P P
P
PW
P
DW
DW
DW
P
P P P
DWDW
P
PP
DW
P
P
DW
a b
P
L
41R c d
P
LSLS
LS
PP
DD
2W
5S 5S
5S 5S
U C
UC4
UC2
U C
U
C
UC3 UC3
LS
U C
11W
27R
27R 27R
27R
27R
27R
27R
27R
27R
34R
34R
27R
27R
27R
27R 27R
34R1
NLT
NLT
NLT
NLT
NLT
NLT
NLT
1a
1b
1a
1b
2W
2W
2W
27R
27R
27R
27R27R
34R
NLT
NLT
2W
NLT
NLT
27R
27R
NLT
27R 27R
27R
27R
27R 34R
2W
27R 27R
27R
27R
27R
2W
34R
NLT
NLT
NLT
NLT
NLT
NLT
27R27R
27R
27R
27R
34R 2W
27R 27R
27R
27R
27R
2W 34R
NLT
NLT
NLT
NLT
NLT
NLT
31R
31R
31R
31R
31R
P
LS27R 27R
27R
27R
27R
34R
2W
27R 27R
27R
27R
27R
2W
34R
NLT
NLT
NLT
NLT
NLTNLT
34R
27R
27R
27R
27R27R
NLT
NLT
NLT
2W
31R22
31R22
P
27R
27R
27R
27R
27R 34R
27R
NLT
NLT
NLT
NLT
2W
32R d10 31R
31R
31R
D
D31R31R
IC
IC
32R
D
D
D
D
D d10
D W
41R 41R41R
P
41R41R
D D
D D
D
DDDDDD
D D D D D D
31R22
31R22
31R31R
31R 31R
28R 28R 28R
28R 28R28R 28R28R
28R28R
LS
P
4NA
4NB
4C1
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R22
32R2232R2232R22
32R22
32R22 32R22
32R22
32R22 32R22
32R22
32R22
4NA-38
,1-#12, 1-#12, 1-#12
4NA-40
,1-#10, 1-#10, 1-#10
4NA-41
,1-#10, 1-#10, 1-#10
4NA-42
,1-#12, 1-#12, 1-#12
4NA-45
,1-#12, 1-#12, 1-#12
4NA-49
,1-#10, 1-#10, 1-#10
4NB-26
,1-#8, 1-#8, 1-#8
4NB-29
,1-#10, 1-#10, 1-#10
4NB-30
,1-#12, 1-#12, 1-#12
4NB-31
,1-#12, 1-#12, 1-#12
4NB-32
,1-#12, 1-#12, 1-#12
4C1-31 ,1-#12, 1-#12, 1-#12 4C1-32 ,1-#12, 1-#12, 1-#12
4C1-33 ,1-#10, 1-#10, 1-#10
4NB-33
,1-#10, 1-#10, 1-#10 b
4C1-35 ,1-#8, 1-#8, 1-#8
4C1-35,4C1-36 ,1-#10, 1-#8, 1-#8, 1-#8
4C1-38 ,1-#12, 1-#12, 1-#12
4C1-39 ,1-#10, 1-#10, 1-#10
4C1-40 ,1-#10, 1-#10, 1-#10
4C1-42 ,1-#12, 1-#12, 1-#12
4C1-43 ,1-#12, 1-#12, 1-#12
4C1-45 ,1-#10, 1-#10, 1-#10
3LS1-16
,1-#10, 1-#10, 1-#10
4C1-41 ,1-#8, 1-#8, 1-#8
31R
31R
2X 2X
<unnamed>
P
P
31R
1X
31R
34R
34R
4EQ1
3LS1-15
,1-#10, 1-#10, 1-#10
1X
C1
C1
C1
C1 C1 C1 C1
C1
C1
C1
C1
3LS1-13
,1-#12, 1-#12, 1-#12
C1 C1
C1
C1
C1 C1C1
C1C1 C1
C1
3LS1-14
,1-#10, 1-#10, 1-#10
C1
C1C1C1C1 C1
C1C1C1C1C1C1C1
4NA-44
,1-#8, 1-#8, 1-#8
4NB-26
,1-#8, 1-#8, 1-#8
C1
C1
C1 C1 C1 C1
C1
C1
C1 C1 C1 C1
C1 C1
C1
C1
C1
C1
28R
28R
28R
C1
C1 28R
28R
28R
C1
C1
28R 28R
4C1-44 ,1-#10, 1-#10, 1-#10
28R
28R
28R
C1
4NA-46
,1-#12, 1-#12, 1-#12
4NA-47
,1-#12, 1-#12, 1-#12
28R
4C1-35 ,1-#8, 1-#8, 1-#8
28R
28R
28R cd a b cd b a c d b a
1a
1b cd a b
1a
1b c d b a
1a
1b cd a b
1a
1b c d b a
1a
1b cd a b
1a
1b c d b a
1a
1b c d a b
1a
1b c d a b
1a
1b d c a b
1a
1b d c a b
1a
1bd10d10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:3
P M
EL102
4TH FLOOR - LIGHTING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
207 238
1/8" = 1'-0"EL102
1 4TH FLOOR - LIGHTING
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
INSTALLATION NOTES.
2. REFER TO 2/E301 FOR OCCUPANCY SENSOR DETAIL,
3/E301 FOR LAY IN CEILING LUMINAIRE MOUNTING DETAIL,
AND 4/E302 FOR LIGHTING CONTROL PANEL DIAGRAM.
3. REFER TO E401 FOR LIGHTING SYMBOLS AND
SCHEDULES.
4. ALL CABLE SHALL BE IN CONDUIT. INCLUDING LOW
VOLTAGE CABLING. NO J-HOOKS SHALL BE ALLOWED.
KEYED NOTES:
1. TYPICAL LIGHTING CONTROL, LIGHTING FOR ALL PATIENT
ROOMS:
CONTROLLER a - PATIENT EXAM LIGHT, ON HEADWALL.
CONTROLLER b -PATIENT READING LIGHT, ON
HEADWALL.
CONTROLLER c - PATIENT ROOM DOWNLIGHTS.
CONTROLLER d - PATIENT ROOM NIGHT LIGHTS.
1a. CONTROLLER IN PATIENT HEADWALL WILL BE
LABELED "OVERBED LIGHT" IN 1/2" TALL ENGRAVED
LETTERS.
1b. PROVIDE A RELAY AT HEADWALL FOR CONTROL OF
PATIENT ROOM LIGHTING FROM PILLOW HANDSET.
2. SWITCH "a","b", "L" FOR LIGHTING ONLY IN CORRIDORS A, B AND LOBBY/LOUNGE. SWITCH "a" CONTROLS CORRIDOR A, SWITCH "b" CONTROL CORRIDOR B, SWITCH "L" CONTROLS THE LOBBY/LOUNGE LIGHTING.
ALL OF THESE SWITCHES ARE TO BE 0/10V DIMMERS-
LIGHTS SUPPLIED WITH 0/10V DIMMABLE DRIVERS.
IMD SUPPLY
5B122 PANORAMIC X-RAY
5B123 STERILE INSTR. STORAGE
5B128
SOILED UTILITY
5B130
EQUIPMENT STORAGE
5B135
UNISEX TOILET
5B136
DENTIST WORKSTATIONS
5B129
OPERATORY TREATMENT GENERAL
AREA
5B131
HAC
5A110
ENGINEERING
5A111
STAFF LOUNGE
5A112
MALE TOILETS / LOCKERS
5A113
FEMALE TOILETS / LOCKERS
5A114SCRUBS DISTRIBUTION
5A108
CRASH CART
5A115
PHYSICIANS CUBICLES
5A117
FILE ROOM
5A118
COPY ROOM
5A119
OFFICE
5A120
SUPPLY STORAGE
5A121
DIRECTORS CONFERENCE ROOM
5A122
MENS TOILET ROOM
5A124
CORRIDOR
C5-109
WOMENS TOILET ROOM
5A126
HAC
5A127EAST STAIR
5A128
STAFF LOUNGE
5A130
OFFICE
5A131
CUBICLES
5A134
OFFICE
5A132
OFFICE
5A133
TELECOMM
5A135
CENTRAL STAIR
5A101
FAMILY TOILET
5A102
MEDICAL CONFERENCE
5A103
DENTAL CONFERENCE
5A105
MECHANICAL SHAFT
5A106
LOBBY / LOUNGE
C5-105
ELECTRICAL ROOM
5B102
WAITING
5B103
RECEPTION / SECRETARY
5B104
COPY ROOM
5B105
DENTAL SERVICE CHIEF OFFICE
5B106
MEDICATION ROOM
5B109
AO OFFICE
5B107
WEST STAIR
5B111
TOILET ROOM
5B112
SOILED UTILITY
5B114
CORRIDOR
C5-104A
CORRIDOR
C5-104
CORRIDOR
C5-107ACORRIDOR
C5-102C
CORRIDOR
C5-106
CORRIDOR
C5-103
OPERATORY TREATMENT GENERAL
AREA
5B115
SHIPPING/ RECEIVING ROOM
5B110
DENTAL TREATMENT ROOM 1
5B116
DENTAL TREATMENT ROOM 2
5B117
DENTAL TREATMENT ROOM 3
5B118
DENTAL TREATMENT ROOM 4
5B119
DENTAL TREATMENT ROOM 6
5B121
DENTAL TREATMENT ROOM 7
5B125
DENTAL TREATMENT ROOM 8
5B126
DENTAL TREATMENT ROOM 10-
SPECIAL NEEDS
5B132
DENTAL TREATMENT ROOM 11
5B133
DENTAL TREATMENT ROOM 12
5B134
DENTAL LAB
5B113
PIPE ACCESS
5A125
DECONTAMINATION AREA
5B115A
TYP TYP
REV
REV
SIM
TYP
TYP
FEC
FEC
SOLID SURFACE
CAP (S-1)
SIM SIM
SIM, REV
NOTE: SEE SHEET "IN103" FOR INTERIOR ELEVATION REFERENCE
CORRIDOR
C5-102A
CORRIDOR
C5-102B
CORRIDOR
C5-102C
DENTAL TREATMENT ROOM 9 -
SPECIAL NEEDS
5B127
DENTAL TREATMENT ROOM 5
5B120
CORRIDOR
C5-102
CORRIDOR
C5-101
CORRIDOR
C5-107
CORRIDOR
C5-108
FEC
DR
DR
DR
DR
DR
DR
31R
31R
31R
31R
31R
31R 31R 31R
31R 31R
27R
27R 27R 27R
27R
27R 27R
27R 27R
27R27R 27R
27R27R
27R
27R 27R
27R 27R
27R
27R
27R
41R22
41R22
41R22 41R22
41R2241R22
31R22 31R22
31R22 31R22
31R22
41R
41R41R
41R
31R
31R
31R 31R31R
31R 31R
31R31R
31R
31R
31R31R31R 31R 31R
31R
31R
31R
31R22 31R22 31R22
31R2231R2231R22
31R
27R 27R
27R 27R
27R 27R
31R
27R 31R
31R
31R
27R
31R 31R
31R
31R
31R22
31R
31R
31R
31R
31R
31R
31R
41R22
41R22
41R22 41R22
222019181716151413121110987654321 21
A
B
C
D
E
F
G
5S
5S
2X
1X
2X
31R
31R
31R31R
31R
31R
31R
31R31R
31R
31R
31R31R
1X
41R41R
31R 31R 31R
31R
31R31R31R31R
28R
27R
28R
28R
28R
1C2
1C2
1C2
1C2
1C2 1C2 1C2 1C2
1C2
1X
5NA
5NB
5C1
5LS1
P
P
P
P P
H
DWDWDW
P
P P
P
P
P
P
P
P
P
P
DW
P
P d d10
P
31R31R
DW
H
H
P
DWDW
P
P
DC
DC
LSLSLSLS
PPPP
LS
LS
PP
P
P
P LS LS LS LS
D
D
D
D D D
D(TYP.
ALL)
5S 5S
5S 5S
XR2XR2XR2XR2XR2
XR2 XR2 XR2
XR2
XR2
UC2
UC3
U C
UC3
U C
UC2
U C
U
C
U C
11W 11W
11W 11W
LS
P
LS P
31R
DW
P
P d d d d10 d10 d10 d10 d10 d10
P d d d d10
D d
P
LSLS
31R 31R
31R D D d10 d
DC
LS
E17
E17
27R27R27R
27R 27R 27R
LSP
d d
E17
E17
27R 27R 27R
27R27R27R
LS P
d d
D W
1C2
1C2
IC4
IC4
1C2
IC4
IC4
1C2
DW
27R
27R
31R
UC3
41R
31R
31R31R31R31R31R31R31R31R31R31R31R
31R
31R
31R
31R
31R2231R22
31R22 31R22
31R22
31R22
31R22
31R22
41R22
41R22
41R2241R22
41R2241R2241R2241R22
31R 31R
27R 27R
41R22 41R22
41R22 41R22
41R22 41R22 41R22 41R22
41R22 41R22
41R22 41R22 41R22 41R22
41R22 41R22 41R22 41R22
41R22 41R22 41R22 41R22
41R22 41R22
41R22 41R22
41R22
41R22
41R22
41R22
41R22
41R22
41R22
41R22
41R22
41R22
31R22
D
27R
27R27R
27R
27R
27R 27R
27R
27R
D D D D
D
D D
D
D
D
D
D
D
DD
D D
41R2241R2241R2241R22
41R22 41R22 41R22
DDDD
D D D D
P
DDD
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
E L C
ELC ELC
1C2 1C2
1C2
1C2 1C2
1C2
1C2
1C2
1C2
41R22
41R22
41R22
41R22 41R22
41R22
D
DR
DR
D
D
D
D
D
DR
DR
DR
DR
DR
D
D
31R31R
DD
D D D D D D
31R 31R 31R 31R 31R 31R
31R
31R
31R
D
D
D
D
D
D
D
DD
D
D
D
31R 31R 31R
31R
31R
31R
31R
31R
DRDR DR DR DR DRDR
DDDD
D
DR DR DR DRDR
DD
5NA-45
1-#8, 1-#8, 1-#8
5NA-46
1-#8, 1-#8, 1-#8
5NA-47
1-#6, 1-#6, 1-#6
5NA-48 1-#10, 1-#10, 1-#10
E L C
ELC
ELC
1-#8, 1-#8, 1-#8
5NA-49
5NA-50
1-#4, 1-#4, 1-#4
1-#6, 1-#6, 1-#6
5NA-51
5NA-52
1-#12, 1-#12, 1-#12
5NA-53
1-#8, 1-#8, 1-#8
3 3 d3 d3
D
D d10
5LS1-6
1-#8, 1-#8, 1-#8
5LS1-11
1-#4, 1-#4, 1-#4
1-#8, 1-#8, 1-#8
5LS1-8
5NA-54
1-#6, 1-#6, 1-#65NB-28
1-#12, 1-#12, 1-#12
5NB-29
1-#12, 1-#12, 1-#12
5NB-31
5NB-30
ELC
5NB-32
ELC
31R
5NB-33
5LS1-9
1-#12, 1-#12, 1-#12
5LS1-10
1-#8, 1-#8, 1-#8
5C1-42
1-#8, 1-#8, 1-#8
1-#12, 1-#12, 1-#12
5C1-43
P
P
P P
P
5C1-43,5C1-44,5LS1-10
2-#6, 1-#8, 1-#6, 1-#6
1-#6, 1-#6, 1-#6
PP
5C1-45 1-#6, 1-#6, 1-#6
5C1-46
1-#8, 1-#8, 1-#8
5C1-47
1-#8, 1-#8, 1-#8
PP
1-#12, 1-#12, 1-#12
D 31R22
2X
2X 1X
1X
1X
1X
1X
LS
P
31R
1X
1X
1C2 1C2 1C2 1C2 1C2 1C2
1C2 1C2 1C2 1C2 1C2 1C2 1C2
3/a
3/b 3/c
3/a
3/c3/b
5S 5S zone b zone c zone a d10 d10
5S
5S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:4
P M
EL103
5TH FLOOR - LIGHTING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
208 238
1/8" = 1'-0"EL103
1 FLOOR 5 - LIGHTING
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
INSTALLATION NOTES.
2. REFER TO 2/E301 FOR OCCUPANCY SENSOR DETAIL,
3/E301 FOR LAY IN CEILING LUMINAIRE MOUNTING DETAIL,
AND 4/E302 FOR LIGHTING CONTROL PANEL DIAGRAM.
3. REFER TO E401 FOR LIGHTING SYMBOLS AND
SCHEDULES.
4. ALL CABLE SHALL BE IN CONDUIT. INCLUDING LOW
VOLTAGE CABLING. NO J-HOOKS SHALL BE ALLOWED.
UP
ELEVATOR EQUIP ROOM
6B102
CENTRAL STAIR
6B103
ELECTRICAL ROOM
6B100A
6B100B
ELECTRICAL ROOM
6B100B
6B
0A
6B103
RADIO ROOM
6B104
ALCOVE
6B105
5.1
J
FE
FE
6B102A
6B104 6B102C
6B102B
S
S R
R
R
R
222019181716151413121110987654321 21
A
B
C
D
E
F
G
EL201
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S/5LS1-7
5S/5NB-38
5S/5NB-38
5S/5NB-38
5S
5LS1-7
5S/5NB-38
E
5LS1-7 1#
10, 1#10, 1#10
5NB-38 1#
10, 1#10, 1#10
X1
5LS1-7
X1
5LS1-7
X1
5LS1-7
X1
5LS1-7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:4
P M
EL104
ATTIC PLAN - LIGHTING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 Checker Author 209 238
1/8" = 1'-0"EL104
1 ATTIC PLAN - LIGHTING
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
INSTALLATION NOTES.
2. REFER TO 2/E301 FOR OCCUPANCY SENSOR DETAIL,
3/E301 FOR LAY IN CEILING LUMINAIRE MOUNTING DETAIL,
AND 4/E302 FOR LIGHTING CONTROL PANEL DIAGRAM.
3. REFER TO E401 FOR LIGHTING SYMBOLS AND
SCHEDULES.
SS
S
S
S
S
S S
S S
S
S
S
S
S S
S
S
S
S S S
S
S
S S
S
S S
S
S
S
S
S
S SS S
S
PATIENT ROOM 2
3B116
PATIENT BATHROOM
3B116A
FEC
34R
27R
27R
27R
27R
27R
E
F
G
11W
NLT
NLT
2W
2W
34R
NLT
2W
NLT
27R
28R
32R22
32R22 cd a b
PATIENT ROOM 3
3B118
PATIENT BATHROOM
3B118A
NURSE SERVER
3B120
E
F
27R
27R
27R
27R 27R
34R
11W
NLT
NLT
NLT
NLT
NLT
NLT
2W
28R
32R22
32R22 a b c d a b
PATIENT ROOM 7 - NEGATIVE
PRESSURE
3B111
PATIENT BATHROOM
3B111A
ANTE ROOM
3B111B
B
C
34R
34R
27R
27R
27R
27R
27R
NLT
NLT
NLT
NLT
2W
28R
32R22
32R22 cd b a
BARIATRIC PATIENT BATHROOM
3A131A
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
3A131
ANTE ROOM
3A131B
20 21
B
C
1 27R
34R
27R
27R
27R
27R
27R
NLT
NLT
32R22
32R22 b a
BARIATRIC PATIENT ROOM 12
3A125
HAC
3A127
NURSE SERVER
3A126
FEC
3RD
FLOOR
CORRIDOR
C3-108
11W
E
F
G
31R22
NLT
NLT
2W
34R
27R
27R
27R
27R27R
NLT
NLT
NLT
2W
32R22
32R22
SOILED UTILITY
5B114
DENTAL LAB
5B113
B
C
31R
31R
31R
31R
31R
31R 31R
31R
31R31R 31R31R
31R
ELC33
1C2
1C2
1C2
31R
31R
P
1C2 1C2 1C2
1C2
1C2
5NB-32
5C1-42
131211
A
B
5LS1-7
,1-#10, 1-#10, 1-#10
5NB-38
,1-#8, 1-#8, 1-#8
5S5S
5S 5S5S
ELC
5S
ELC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:5
P M
EL201
ENLARGED PLANS - LIGHTING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
210 238
1/4" = 1'-0"EL201
1 3RD FLOOR - PATIENT ROOM 2
1/4" = 1'-0"EL201
2 3RD FLOOR - PATIENT ROOM 3
1/4" = 1'-0"EL201
3RD FLOOR - PATIENT ROOM 7 - BARIATRIC NEG.
PRESS.
1/4" = 1'-0"EL201
4 3RD FLOOR - PATIENT ROOM 13 - NEG. PRESS.
1/4" = 1'-0"EL201
5 3RD FLOOR - PATIENT ROOM 12 - BARIATRIC
1/4" = 1'-0"EL201
6 DENTAL LAB PLAN
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL
SYMBOLS, GENERAL NOTES, RENOVATION
NOTES, AND INSTALLATION NOTES.
1/4" = 1'-0"EL104 EL201
7 ATTIC - ELECTRICAL ROOM PLAN - LIGHTING
KEYED NOTES:
1. TYPICAL LIGHTING CONTROL, LIGHTING FOR ALL
PATIENT ROOMS:
CONTROLLER a - PATIENT EXAM LIGHT, ON
HEADWALL.
CONTROLLER b - PATIENT READING LIGHT, ON
HEADWALL.
CONTROLLER c - PATIENT ROOM DOWNLIGHTS.
CONTROLLER d - PATIENT ROOM NIGHT LIGHTS.
1a. CONTROLLER IN PATIENT HEADWALL WILL BE
LABELED "OVERBED LIGHT" IN 1/2" TALL
ENGRAVED LETTERS.
1b. PROVIDE A RELAY AT HEADWALL FOR
CONTROL OF PATIENT ROOM LIGHTING FROM
PILLOW HANDSET.
J
1 2 3 4 5 6 7 8 9
11 12
14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
E P
2 ELEVTR
EXIST. 30KVA
EDP3(EXISTING)DP1
ATSD
ATS4
WELL PUMP
ATS1
ATS2
EDP2AB(EXISTING)
LPQ
DP2
ATS
EDP5
EP100
PULL BOX
NORMAL
8 - 3"C.
4 - 3"C.
4 - 3"C.
UP TO
ATTIC
8 - 3"C.
UP TO
ATTIC
TO
SWITCHGEAR.
SEE SHEET
ES101.
PULL BOX
EMERGENCY
EP100
B A
S E
M E
N T
E L E
V A
T
IO
N A
P
U L L B
O X
E S
1 2 3 4 5 6 7 8 9
11 12
14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
ATSD
DP1EDP3(EXISTING)
EXIST. 30KVA
ELEVTR
EP12
EDP5
ATS
DP2
LPQ
EDP2AB(EXISTING)
ATS2
ATS1
ATS4
WELL PUMP
ALL EQUIPMENT
IN THIS ROOM IS
EXISTING.
PROVIDE POWER CONNECTION FOR
1-BP1 LOCATED IN BUILDING 1 BASEMENT
ROOM BC109. INSTALL A 3-POLE 45A
CIRCUIT BREAKER INTO EXISTING PANEL
EDP5 AND UTILIZE 4#6 & 1#10 GND IN 1"
CONDUIT. REFER TO PL101 FOR
APPROXIMATE LOCATION FOR 1-BP1.
PROVIDE POWER CONNECTION FOR
WATER MONITORING SYSTEM IN
BASEMENT ROOM BC109. INSTALL A
SINGLE POLE 20A CIRCUIT BREAKER INTO
EXISTING PANEL EDP5 AND UTILIZE 2#12
& 1#12 GND IN 3/4" CONDUIT. REFER TO
PL101 FOR APPROXIMATE LOCATION.
COORDINATE INSTALLATION WITH
PLUMBING CONTRACTOR, PROVIDE ALL
NECESSARY ELECTRICAL CONNECTIONS
FOR A COMPLETE OPERATION SYSTEM.
EX_53HWP-2
EX_53HWP-1
ET-1
EXIST. AC
EXIST. NP
EXIST. P
MDP BLDG 53
EXIST. L1C
REFER TO ES101 FOR WORK
ASSOCIATED WITH PANEL
MDP
FIRST FLOOR
13' - 0"
GROUND FLOOR
0' - 0"
T.O.F
-6' - 0"
A B C
42" W X 42" H X
42" DEEP
PULL BOX
FOR NORMAL
28" W X 28" H X
28" DEEP
PULL BOX
FOR
EMERGENCY 1st FLOOR
0' - 0"
2nd Floor 13' - 0"
Foundation -6' - 0"
CBA B.4 B.7
10 11 12 13
D
C
B
A
CENTRAL STAIR
1A101
B.4
B.7
D.2
B.8
B.2
10.8 12.2
FACP
3LS1-5
11 12
D
C
B
A
B.4
B.7
D.2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of fi le s \C o rp o ra te \T e a m s \C
S L
E G
\B
IM
D o c u m e n ts \1
.0
\R e v it \I C
T
B
L D
G
E le c tr ic a l C
D S
.r v t
/1 /2
:1
:5
P M
EP100
BASEMENT PLAN - POWER RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 IMEG STEWIE
211 238
1/8" = 1'-0"EP100
1 EXISTING FOUNDATION PLAN - ELECTRICAL
1/4" = 1'-0"EP100 EP100
EXISTING FOUNDATION PLAN - ELECTRICAL - LARGE
SCALE PLAN
1/8" = 1'-0"ES101 EP100
3 BUILDING 53 - ELECTRICAL
1/8" = 1'-0"EP100 EP100
4 BASEMENT ELEVATION A - PULL BOXES
1/8" = 1'-0"EP100
5 1ST FLOOR PARTIAL PLAN - POWER
KEYED NOTES:
GENERAL NOTES:
1. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS,
GENERAL NOTES, RENOVATION NOTES, AND
J J
JJ
J
J J
J
J J J
J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J
J J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
JJ
J
J
J
E
E
E E
E E
E E
E
EE
E
E
S
J
S S
S S
S
PATIENT ROOM 1
3B114
PATIENT ROOM 2
3B116
PATIENT ROOM 3
3B118
PATIENT ROOM 4
3B119
CLEAN EQUIPMENT STORAGE
3B121
MD DICTATION
3B122
PATIENT ROOM 5
3B123 PATIENT ROOM 6
3B124
WHEELCHAIR ALCOVE
3B102
ELECTRICAL ROOM
3B101
PATIENT CENTERED CARE
3B103
MEDICAL GAS STORAGE
3B104
CRASH CART
3B105
HAC
3B106
CLEAN UTILITY
3B107
CLEAN LINEN
3B108
KINESIOTHERAPY
3B109
WEST STAIR
3B110
PATIENT ROOM 7 - NEGATIVE
PRESSURE
3B111
UNASSIGNED
3B113
PATIENT BATHROOM
3B111A
ANTE ROOM
3B111B
PATIENT BATHROOM
3B114A
PATIENT BATHROOM
3B118A
PATIENT BATHROOM
3B119A
PATIENT BATHROOM
3B123A
PATIENT BATHROOM
3B124A
CORRIDOR
C3-104
CENTRAL STAIR
3A101
MALE TOILET
3A102
FEMALE TOILET
3A103
FAMILY TOILET
3A104
WAITING / LOUNGE
3A105FAMILY CONSULTATION
3A106
MECHANICAL SHAFT
3A107
SOILED LINEN
3A110
ENGINEERING
3A111
HEAD NURSE / ASSISTANT MANAGER
3A112
MEDICATION ROOM
3A114
NOURISHMENT STATION
3A115
PATIENT ROOM 8
3A117
PATIENT ROOM 9
3A118
MD DICTATION
3A120
IMD SUPPLY STORAGE
3A121
PATIENT ROOM 10
3A122
PATIENT ROOM 11
3A123
BARIATRIC PATIENT ROOM 12
3A125
CONFERENCE / REPORT ROOM
3A128
PATIENT BATHROOM
3A117A PATIENT BATHROOM
3A118A
PATIENT BATHROOM
3A122A PATIENT BATHROOM
3A123A
BARIATRIC PATIENT BATHROOM
3A125A
HAC
3A127
TELEMETRY
3A130
BARIATRIC PATIENT BATHROOM
3A131A
BARIATRIC PATIENT ROOM 13 - NEG.
PRESS.
3A131
ANTE ROOM
3A131B
EAST STAIR
3A133
PHARMACY CUBICLES
3A134
MALE LOCKERS
3A137
STAFF TOILET
3A136
STAFF SHOWER
3A135
CORRIDOR
3A141
STAFF LOUNGE
3A138
FEMALE LOCKERS
3A139
TELECOMM
3A140
SOILED UTILITY
3A142
NURSE STATION
3A109A
CORRIDOR
C3-105
CORRIDOR
C3-103
NURSE SERVER
3A124
CORRIDOR
C3-109
NURSE SERVER
3A132
CORRIDOR
C3-101
NURSE SERVER
3B112
NURSE SERVER
3B125
CORRIDOR
C3-107
NURSE SERVER
3A126NURSE SERVER
3A119
NURSE SERVER
3B120NURSE SERVER
3B117
NURSE SERVER
3B115
NURSE STATION
3A109
PATIENT BATHROOM
3B116A
TYP
TYP
REV
ALIGN ALIGN
FEC
FEC
FEC
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
3RD
FLOOR
2ND
FLOOR
1ST
FLOOR
NOTE: SEE SHEET "IN101" FOR INTERIOR ELEVATION REFERENCE
CORRIDOR
C3-100
CORRIDOR
C3-102
CORRIDOR
C3-102A
CORRIDOR
C3-106
CORRIDOR
C3-107A
CORRIDOR
C3-108
T
T
GFI
GFI
GFI
GFI
GFI
E
GFI
ICE
MGA
GFI
E
REFR.
GFI
GFI
GFIGFI
E
DR
HLDR
3NA
3NB
3C1
E
3LS1
222019181716151413121110987654321 21
A
B
C
D
E
F
G
E
TV
72"
GFI
GFI
E
TV
72"
E72"
TV TV
TV
E E E E
TVTV E
E
E
TV
E
EP101
E
E
TV
COPY
72"
MICR.
72"
TV
COPY
EP101
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI
GFI
4 - 3"C. UP
TO ATTIC
8 - 3"C.
UP TO
ATTIC
TV
72"
3NB-1 ,1-#3,
1-#3, 1-#3
3NB-2
,1-#12, 1-#12, 1-#12
3C1-9 ,1-#10, 1-#10, 1-#10
E
EE
E
E
E E
E
E
GFI
E
EE
E
E
E
E
REFR.
MIC.
E
GFI
E
TV
E
E E E E
GFI
E
E
EE
E
TV
E
TV
E E E E E E E E
E E
GFI
T T
3C1-3 ,1-#6, 1-#6, 1-#6
3C1-4 ,1-#10, 1-#10, 1-#10
3NA-2 ,1-#4,
1-#4, 1-#4
3C1-1 ,1-#12, 1-#12, 1-#12
3NB-5
,1-#12, 1-#12, 1-#12
72" 72"
72" 72" 72"
72"
72"
40"
3NB-6 ,1-#6,
1-#6, 1-#6
3NB-7
,1-#10, 1-#10, 1-#10
3NB-8
,1-#12, 1-#12, 1-#12
3NB-9
,1-#12, 1-#12, 1-#12
3NB-10
,1-#12, 1-#12, 1-#12
3NB-11
,1-#10, 1-#10, 1-#10
3NB-25
,1-#12, 1-#12, 1-#12
3NB-14
,1-#8, 1-#8, 1-#8
3NB-15
,1-#8, 1-#8, 1-#8
3NA-3
,1-#12, 1-#12, 1-#12
3NA-4
,1-#12, 1-#12, 1-#12
3NA-5
,1-#10, 1-#10, 1-#10
3NA-6
,1-#10, 1-#10, 1-#10
3NA-7
,1-#12, 1-#12, 1-#12
3NA-8
,1-#10, 1-#10, 1-#10
3NA-9 ,1-#6,
1-#6, 1-#6
3NA-10
,1-#12, 1-#12, 1-#12
3NA-11
,1-#10, 1-#10, 1-#10
3C1-69 ,1-#10, 1-#10, 1-#10
3NA-13
,1-#12, 1-#12, 1-#12
3NA-14
,1-#8, 1-#8, 1-#8
3NA-15
,1-#10, 1-#10, 1-#10
3NA-16
,1-#10, 1-#10, 1-#10
3NA-17
,1-#12, 1-#12, 1-#12
3NA-18
,1-#12, 1-#12, 1-#12
3NA-19
,1-#12, 1-#12, 1-#12
E
E
3NA-20
,1-#10, 1-#10, 1-#10
E
E
E
E E
E
3NA-21
,1-#8, 1-#8, 1-#8
3NA-22
,1-#6, 1-#6, 1-#6
3NA-25
,1-#10, 1-#10, 1-#10
3NA-26
,1-#12, 1-#12, 1-#12
3NA-27
,1-#12, 1-#12, 1-#12
3C1-11 ,1-#10, 1-#10, 1-#10
3C1-12 ,1-#10, 1-#10, 1-#10
3C1-13 ,1-#10, 1-#10, 1-#10
3C1-6 ,1-#10, 1-#10, 1-#10
3C1-14 ,1-#8, 1-#8, 1-#8
3C1-15 ,1-#8, 1-#8, 1-#8
3C1-16 ,1-#8, 1-#8, 1-#8
3C1-17 ,1-#10, 1-#10, 1-#10
3C1-18 ,1-#12, 1-#12, 1-#12
3C1-20 ,1-#10, 1-#10, 1-#10
3C1-19 ,1-#10, 1-#10, 1-#10
3C1-21 ,1-#12, 1-#12, 1-#12
3C1-22 ,1-#12, 1-#12, 1-#12
3C1-23 ,1-#12, 1-#12, 1-#12
3C1-24 ,1-#10, 1-#10, 1-#10
3C1-25 ,1-#10, 1-#10, 1-#10
E
3C1-26 ,1-#6, 1-#6, 1-#6
3C1-27 ,1-#12, 1-#12, 1-#12
3C1-28 ,1-#12, 1-#12, 1-#123C1-29 ,1-#12, 1-#12, 1-#12
3C1-30 ,1-#10, 1-#10, 1-#10
3C1-31 ,1-#12, 1-#12, 1-#12
3C1-2 ,1-#12, 1-#12, 1-#12
3C1-32 ,1-#10, 1-#10, 1-#10
3C1-33 ,1-#12, 1-#12, 1-#12
3C1-34 ,1-#12, 1-#12, 1-#12
3NA-28
,1-#10, 1-#10, 1-#10
3LS1-1
,1-#12, 1-#12, 1-#12
3NA-1
,1-#10, 1-#10, 1-#10
3NA-29
,1-#10, 1-#10, 1-#10
3NA-30
,1-#6, 1-#6, 1-#6
3NA-31
,1-#10, 1-#10, 1-#10
3NA-32
,1-#6, 1-#6, 1-#6
3NA-33
,1-#12, 1-#12, 1-#12
3NA-34
,1-#8, 1-#8, 1-#8
3NA-35
,1-#12, 1-#12, 1-#12
3NA-36
,1-#8, 1-#8, 1-#8
3NA-37
,1-#12, 1-#12, 1-#12
3NA-38
,1-#10, 1-#10, 1-#10
3NB-16
,1-#12, 1-#12, 1-#12
3NB-17
,1-#10, 1-#10, 1-#10
3NB-18
,1-#12, 1-#12, 1-#12
3NB-19
,1-#10, 1-#10, 1-#10
3NB-21
,1-#12, 1-#12, 1-#12
3NB-20
,1-#10, 1-#10, 1-#10
3NB-3
,1-#12, 1-#12, 1-#12
3NB-22,3NB-23
,1-#12, 1-#6, 1-#6, 1-#6
3NB-24
,1-#12, 1-#12, 1-#12
3NB-12
,1-#12, 1-#12, 1-#12
3NB-13
,1-#10, 1-#10, 1-#10
LIFT
E
3C1-35 ,1-#8, 1-#8, 1-#8
E
LIFT
E
LIFT
E
LIFT
3C1-35 ,1-#8, 1-#8, 1-#8
E LIFT
3C1-35 ,1-#8, 1-#8, 1-#8
E
E
LIFT
LIFT
E
EE
E
LIFT LIFT
LIFTLIFT
3C1-36 ,1-#6, 1-#6, 1-#6
E
E
LIFT
LIFT
3C1-37 ,1-#12, 1-#12, 1-#12
E
E
LIFT
LIFT
3C1-38 ,1-#12, 1-#12, 1-#12
E
E
LIFT
LIFT
LIFTLIFT
LIFT
E
E LIFT
LIFTLIFT
LIFT LIFT
3C1-40 ,1-#6, 1-#6, 1-#6
3C1-39 ,1-#8, 1-#8, 1-#8
(TYP.)
(TYP.)
(TYP.)
FABPS
3LS1-7
,1-#12, 1-#12, 1-#12
4EQ1-5
,1-#10, 1-#10, 1-#10
4EQ1-5
,1-#10, 1-#10, 1-#10
4EQ1-5
,1-#10, 1-#10, 1-#10
4EQ1-5
,1-#10, 1-#10, 1-#10
4EQ1-5
,1-#10, 1-#10, 1-#10
3NB-34
,1-#12, 1-#12, 1-#12
3NB-34
,1-#12, 1-#12, 1-#12
4EQ1-3
,1-#8, 1-#8, 1-#8
4EQ1-3
,1-#8, 1-#8, 1-#8
4EQ1-3
,1-#8, 1-#8, 1-#8
4EQ1-1
,1-#12, 1-#12, 1-#12
3NA-50
,1-#12, 1-#12, 1-#12
3NA-51
,1-#10, 1-#10, 1-#10
4EQ1-5
,1-#10, 1-#10, 1-#10
4EQ1-3
,1-#8, 1-#8, 1-#8
3LS1-2
,1-#12, 1-#12, 1-#12
4EQ1-5
,1-#10, 1-#10, 1-#10
GFI
GFI
E
MOT
BARS
3C1-56 ,1-#12, 1-#12, 1-#12
E
MOT
BARS
3C1-57 ,1-#12, 1-#12, 1-#12
GFI
GFI
GFI
GFI
E E
E E E
E E
E
EE
EE
3C1-58 ,1-#8, 1-#8, 1-#8
3C1-58 ,1-#8, 1-#8, 1-#8
3C1-58 ,1-#8, 1-#8, 1-#8 3C1-58
,1-#8, 1-#8, 1-#8
3C1-58 ,1-#8, 1-#8, 1-#8
3C1-58 ,1-#8, 1-#8, 1-#8
3C1-60 ,1-#8, 1-#8, 1-#8
3C1-60 ,1-#8, 1-#8,…