B08_Attach_10_HazMat_Report.pdf

PDF 4 MB Posted

Attached to
ACAD 312255 - Rehabilitate Schoodic Water System
Solicitation number
140P2022R0043
Issued by

About this file

This document contains the results of an asbestos inspection and lead paint testing report for the ACAD - Rehabilitate Schoodic Water and Wastewater Systems project located at the Schoodic Institute in Acadia National Park, Winter Harbor, Maine. Samples were collected from the standalone pumphouse building and bomb shelter and pump room areas within Eliot Hall basement and analyzed for asbestos and lead content. Asbestos was not detected in any of the samples analyzed. Lead was detected in paint samples from metal pipes, CMU walls, and a metal door at levels between 0.94% and 3.6% by weight. The report provides findings and regulatory guidance on asbestos and lead for the referenced project locations.

Additionally, the solicitation is for the ACAD 312255 - Rehabilitate Schoodic Water System project at Acadia National Park in Winter Harbor, Maine. The solicitation was issued by the National Park Service National Office within the Department of the Interior. No other details are provided about requirements, pricing, response dates, or other terms.

View the file

Other files

File Type Posted
B09_Attach_31_General_Refs_0005.doc DOC document
Sol_140P2022R0043_Amd_0005.pdf PDF
B09_Attach_22_Request_for_Information_0005.pdf PDF
B09_Attach_29_O_M_0004.pdf PDF
B09_Attach_30_Photo_0004.pdf PDF
B09_Attach_22_Request_for_Information_0004.pdf PDF
Sol_140P2022R0043_Amd_0004.pdf PDF
B09_Amend_04_RFIs_updated_0004.pdf PDF
B09_Attach_28_Well_Pump_Calcs_0003.pdf PDF
Sol_140P2022R0043_Amd_0003.pdf PDF
B09_Attach_25_Plans_Update_0003.pdf PDF
B09_Attach_24_Spec_Updates_0003.pdf PDF
B09_Attach_23_Addendum_Summary_0003.pdf PDF
B09_Attach_22_Request_for_Information_0003.pdf PDF
B09_Amend_03_Updates_0003.pdf PDF
B09_Attach_26_Generator_Calculation_0003.pdf PDF
B09_Attach_27_Sewer_Tables_0003.pdf PDF
Sol_140P2022R0043_Amd_0002.pdf PDF
B09_Amend_02_Sign_in_Sheet_0002.pdf PDF
Sol_140P2022R0043_Amd_0001.pdf PDF
Amendment_01_Site_Visit_0001.pdf PDF
B08_Attach_12_Permit_Plan.pdf PDF
B08_Attach_05_Vaccination_Certification_Notification_.pdf PDF
B08_Attach_11_Radio_Path_Study.pdf PDF
B08_Attach_04_Certification_of_Vaccination_Form.pdf PDF
B08_Attach_14_PSP.pdf PDF
B08_Attach_03_Davis_Bacon.pdf PDF
B08_Attach_18_Product_Data_basis_of_estimate.pdf PDF
B08_Attach_15_JOFOC_SCADA_Software.pdf PDF
B08_Attach_08_Structural_Tests___Special_Inspections.pdf PDF
B08_Attach_01_Specs.pdf PDF
Sol_140P2022R0043.pdf PDF
B08_Attach_17_O_M_Requirements.xlsx XLSX spreadsheet
B08_Attach_02_Drawings.pdf PDF
B08_RFP_140P2022R0043.pdf PDF
B08_Attach_09_Calculations.pdf PDF
B08_Attach_07__Sewer_Inspection.pdf PDF
B08_Attach_19_ConstructabilityChecklist.xlsx XLSX spreadsheet
B08_Attach_16_SubmittalList_Estimate.xlsx XLSX spreadsheet
B08_Attach_13_LmtOnSubconRpt.xlsx XLSX spreadsheet
B08_Attach_06_Geotechnical_Report.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asbestos Inspection &

Lead Paint Testing Report Acadia National Park

Schoodic Institute

Winter Harbor, Maine 04693

Project: ACAD - Rehabilitate Schoodic

Water and Wastewater Systems April 11, 2022

Terracon Project J1215067

Prepared for:

VHB, Inc.

Watertown, Massachusetts

Prepared by:

Terracon Consultants, Inc.

Manchester, New Hampshire

Terracon Consultants, Inc. 77 Sundial Ave Suite #401w Manchester, NH 03103

P [603] 647 9700 terracon.com

April 11, 2022

VHB, Inc.

101 Walnut Street Watertown, Massachusetts 02471

Attn: Mr. Timothy Bryant, PE

Director of Structural Engineering

P: (773) 336-7922

E: Brosenblum@GWProperties.com

Re: Asbestos Inspection & Lead Paint Testing Report

Project: ACAD - Rehabilitate Schoodic Water and Wastewater Systems

Acadia National Park

Schoodic Institute

Winter Harbor, Maine 04693

Terracon Project No. J1215067

Dear Mr. Bryant:

Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced project to VHB, Inc. (VHB). The purpose of this report is to present the results of an asbestos inspection and lead paint testing which were performed at the project site on February 28, 2022. This scope of services was conducted in accordance with VHB’s Task Order Authorization, dated September 28, 2021.

Lead-containing paint (LCP) was identified as a result sampling and laboratory analysis. Asbestos-containing materials (ACM) were not identified as a result of sampling and laboratory analysis.

Please refer to the attached report for further detail.

We trust this report meets your needs at this time. If you have any questions regarding this report, please feel free to contact us.

Sincerely, Terracon Consultants, Inc.

Adam Frey Joseph Tussey, CHMM

Staff Scientist Authorized Project Reviewer http://terranet.terracon.com/dept/marketing/PublishingImages/ServicesBar13Update.jpg

Responsive ■ Resourceful ■ Reliable

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 Project Objective

2.0 PROJECT/STRUCTURE DESCRIPTION

3.0 FIELD ACTIVITIES

3.1 Asbestos-Containing Materials Inspection

3.1.1 Visual Assessment

3.1.2 Physical Assessment

3.1.3 Sample Collection

3.1.4 Sample Analysis

3.2 Lead-Containing Paint Testing

3.2.1 Lead Paint Sample Collection and Analysis

4.0 REGULATORY OVERVIEW

4.1 Asbestos-Containing Materials

4.2 Lead Paint

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos-Containing Materials

5.2 Lead-Containing Paint

6.0 LIMITATIONS/GENERAL COMMENTS

LIST OF APPENDICES

APPENDIX A ASBESTOS INSPECTION SAMPLE LOCATION SUMMARY

APPENDIX B SAMPLE LOCATION DRAWINGS

APPENDIX C PHOTOGRAPHIC DOCUMENTATION

APPENDIX D LABORATORY ANALYTICAL DATA

APPENDIX E INSPECTOR’S LICENSE

Responsive ■ Resourceful ■ Reliable 1

ASBESTOS INSPECTION &

LEAD PAINT TESTING REPORT

PROJECT: ACAD - REHABILITATE SCHOODIC

WATER AND WASTEWATER SYSTEMS

Acadia National Park

Schoodic Institute

Winter Harbor, Maine 04693 Terracon Project No. J1215067

April 11, 2022

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted an asbestos inspection and lead paint testing for the ACAD: Rehabilitate Schoodic Water and Wastewater Systems project which is located at the Schoodic Institute in Acadia National Park, Winter Harbor, Maine. The purpose of this scope of services was to sample/test, identify, and locate suspect asbestos-containing materials (ACM, and paints containing lead (lead-containing paint {LCP}) pertaining to the stand alone pumphouse building and the bomb shelter and pump room in the basement of Eliot Hall.

The scope of services was conducted at the site on February 28, 2022 by State of Maine

Department of Environmental Protection (ME DEP)-licensed asbestos inspector, Mr. Adam Frey, in accordance with the Client’s Task Order authorization, dated September 28, 2021.

Homogenous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Suspect ACM samples were collected in accordance with the sampling protocols outlined in United States Environmental Protection Agency (USEPA) 40 Code of Federal

Regulations (CFR) Part 763, Subpart E, known as the Asbestos Hazard Emergency Response

Act (AHERA). Samples were delivered to an accredited laboratory for analysis by polarized light microscopy (PLM) and the additional transmission electronic microscopy (TEM) with gravimetric reduction analytical method when applicable for non-friable organically bound (NOB) materials.

In conjunction with the asbestos inspection, Terracon conducted sampling of representative acessible suspect lead-containing paints to identify and assess the condition of accessible painted buiding components that are suspected of containing lead. The sampling was of a limited nature specific to project and accessible areas. Paint samples were analyzed for lead content via EPA

Method SW-846-7000B, Flame Atomic Absorption Spectrophotometry.

1.1 Project Objective

We understand this scope of services was requested to identify, locate and sample suspect ACM for laboratory analysis, sample paints for lead-content laboratory analysis, and provide information regarding materials identified by analysis to contain asbestos and components with

Asbestos Inspection & Lead Paint Testing Report

Acadia National Park - Schoodic Institute ■ Winter Harbor, ME

April 11, 2022 ■ Terracon Project No. J1215067

Responsive ■ Resourceful ■ Reliable 2 lead paint, if any, for the above-referenced pumphouse and basement area. USEPA regulation 40

CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP) and state regulations prohibit the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM be identified, classified and quantified prior to planned disturbances or demolition activities. Regarding paints with lead, the Occupational Safety and Health Administration (OSHA) regulation 29 CFR 1926.62 (Lead in

Construction) requires contractor compliance when disturbing lead.

2.0 PROJECT/STRUCTURE DESCRIPTION

As noted above in Section 1.0, the areas included in our scope of services included the accessible interior and exterior areas of the standalone pumphouse building and the Client-specified bomb shelter and pump room areas within the interior of the Eliot Hall basement.

Eliot Hall is located in Winter Harbor, Maine, and currently operates as an education center on the Schoodic Institute campus. The building is a brick structure with multiple classrooms bathrooms, offices, and a basement. The age of the structure was unknown to Terracon. As previously noted, our scope was limited to the interior of the bomb shelter and pump room in the basement and didn’t include any other areas of Eliot Hall.

The pumphouse building is located on a trail from Mountain Road, approximately three (3) miles from Eliot Hall. The structure contains a well and is enclosed in a wood-framed structure of approximately 65 square feet.

3.0 FIELD ACTIVITIES

3.1 Asbestos-Containing Materials Inspection

The asbestos inspection was conducted by Mr. Adam Frey, a MEDEP-licensed asbestos inspector

(license number AI-0784). A copy of his state asbestos inspector license is attached as Appendix

E. The inspection was conducted in accordance with the sample collection protocols established in USEPA regulation 40 CFR Part 763 (AHERA), Subpart E, Section 763.86 - Sampling. A summary of inspection activities is provided below.

3.1.1 Visual Assessment

The inspection activities were initiated with visual observation of subject project areas to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application. The assessment was conducted in physically accessible areas of the subject areas.

Although reasonable effort was made to assess accessible suspect materials, additional suspect

Responsive ■ Resourceful ■ Reliable 3 but non-sampled materials could be located within walls, ceilings, pipe chases or in other concealed areas. Building materials identified as glass, fiberglass, wood, masonry, metal or rubber were not considered suspect ACM.

3.1.2 Physical Assessment

A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material that can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.1.3 Sample Collection

Based on results of the visual and physical observation, bulk samples of suspect ACM were collected in accordance with EPA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon did not perform sampling requiring demolition or destructive activities such as knocking holes in walls, dismantling of equipment or removal of protective coverings. Electrical/mechanical equipment was not dismantled for interior inspections and materials such as wiring were not sampled due to safety issues.

Terracon collected a total of 30 bulk samples from 10 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the inspection is included as Appendix A.

3.1.4 Sample Analysis

Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of South

Portland, Maine for analysis by polarized light microscopy (PLM) and the additional transmission electronic microscopy (TEM) with gravimetric reduction analytical method when applicable for non-friable organically bound (NOB) materials.

EMSL is a Maine Department of Environmental Protection (MEDEP) Environmental Laboratory

Accreditation Program (ELAP)-accredited laboratory for asbestos bulk sample analysis

(accreditation number 100194). EMSL is also accredited under the National Voluntary Laboratory

Responsive ■ Resourceful ■ Reliable 4

Accreditation Program (NVLAP; accreditation number 101048-0) for asbestos bulk sample analysis.

A summary of sample results is included with the sample summary in Appendix A. Sample location drawings are included in Appendix B. The laboratory analytical report is included in

Appendix D.

3.2 Lead-Containing Paint Testing

In conjunction with the asbestos inspection, Terracon conducted lead paint testing limited to representative components in representative projects areas in an effort to identify paints containing lead. This testing scope was not intended to meet the requirements of the HUD

Guidelines for the Evaluation and Control of Lead-Based Paint Hazards which is applicable for

HUD-funded residential housing.

3.2.1 Lead Paint Sample Collection and Analysis

Sample collection was performed using a clean straight-edge razor to remove paint from designated surfaces at random locations from dominant-type paint coatings. Collected paint samples were placed in new sealable containers and labeled with unique sample numbers using an indelible marker.

The paint chip samples were submitted for lead-content analysis to EMSL of Cinnaminson, New

Jersey. EMSL is accredited by the AIHA® Laboratory Accreditation Programs, LLC under the

Environmental Lead Laboratory Accreditation Program (ELLAP; accreditation number 100194).

Terracon collected from a total of six (6) paint samples (a summary with a description of the collected paint samples and analytical results is provided in Section 5.2, below). Samples were analyzed for lead content via EPA Method SW-846-7000B Flame Atomic Absorption

Spectrophotometry. The laboratory analytical report is included in Appendix C.

4.0 REGULATORY OVERVIEW

4.1 Asbestos-Containing Materials

The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity.

Friable ACM is a material containing more than 1% asbestos that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).

Responsive ■ Resourceful ■ Reliable 5

The NESHAP regulation classifies ACM as RACM, Category I non-friable ACM or Category II non-friable ACM. RACM includes all friable ACM, along with Category I and Category II non-friable ACMs that have become friable or will be or have been subjected to sanding, grinding, cutting or abrading; or that have a high probability of becoming or have become crumbled, pulverized or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACMs are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics and asphalt roofing products that contain more than 1% asbestos.

Category II non-friable ACMs are all other non-friable materials other than Category I non-friable

ACMs that contain more than 1% asbestos.

The Maine Department of Environmental Protection (DEP) enforces state asbestos regulations. Prior to demolition or renovation of a building, the owner must ensure that the work will not disturb more than three (3) square feet or three (3) linear feet of

ACM. Owners of buildings, other than residential buildings with less than 5 units, must have a DEP-licensed Asbestos Consultant inspect the building (or area) for asbestos. If

ACM is identified in a building that will be demolished, or any building materials are assumed to be ACM, these materials must be removed by a DEP-licensed Asbestos

Abatement Contractor before the demolition. Similarly, if any ACM is identified or assumed in areas of a building that will undergo renovation, the ACM must be removed by a DEP-licensed Asbestos Abatement Contractor before the renovation occurs. Intact asbestos-containing flooring and roofing may be left in place during demolition of a building if the demolition is performed by a DEP-licensed Asbestos Abatement Contractor using large equipment in accordance with the Maine “Asbestos Management

Regulations”. State regulations require that building owners notify the DEP at least five

(5) working days prior to demolition of a building (other than single-family residences). This notification is required even if no asbestos is identified in the building. Forms are available from DEP and local code enforcement offices.

4.2 Lead Paint

Lead is regulated by the USEPA, Maine DEP, and OSHA. The US HUD also has guidelines for the inspection, assessment, and abatement for defined lead-based paint (LBP) in residential settings under HUD funding. The USEPA and Maine DEP regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The USEPA and US HUD define LBP as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 milligram per square centimeter (mg/cm2) as determined by laboratory analysis for bulk samples.

For the purpose of the OSHA lead standard, lead includes metallic lead, all inorganic lead compounds, and organic lead soaps. Lead containing paint (LCP), is paint with any detectable

Responsive ■ Resourceful ■ Reliable 6 levels of lead (levels above the analytical method’s reporting limit). A synopsis of the OSHA regulation (29 CFR 1926.62) and the applicability are as follows:

The OSHA Lead in Construction standard (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead (regardless of the lead concentration).

All work related to construction, alteration, or repair (including painting and decorating) is included.

The lead standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard, construction includes, but is not limited to, the following:

◼ Demolition or salvage of structures where lead or materials containing lead are present.

◼ Removal or encapsulation of materials containing lead.

◼ New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead.

◼ Installation of products containing lead.

◼ Lead contamination/emergency clean-up.

◼ Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed.

◼ Maintenance operations associated with construction activities described above.

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos-Containing Materials

Asbestos was not identified in the samples collected and analyzed with respect the scope of this project-specific inspection. Please note that if a structure will be demolished, even if no ACM was identified as result of the inspection, state regulations require a five (5) working day notice to the

Maine DEP prior to demolition. For more information and notifications, please visit Maine’s DEP asbestos webpage at https://www.maine.gov/dep/waste/asbestos/index.html.

A sample and results summary table is included in Appendix A. Sample location drawings are included in Appendix B. The laboratory analytical report is included in Appendix D.

If additional but unsampled suspect materials (not listed in Appendix A) are discovered during the course of demolition or renovation activates, those materials should be assumed as asbestos-containing until sampled by an accredited inspector and laboratory analysis refutes the positive assumption.

https://www.maine.gov/dep/waste/asbestos/index.html

Responsive ■ Resourceful ■ Reliable 7

5.2 Lead-Containing Paint

A summary of the paint chip analysis results is presented in the following table. Data in bold indicates paints containing lead. A copy of the laboratory report for the paint chip samples is attached in Appendix B. Sample locations are shown on the diagram included in Appendix E.

Summary of Paint Samples and Analytical Results

Sample ID Color Substrate Component Sample Location Analytical

Result (% wt.)

PC-1 Blue Metal Pump

Coolers

Eliot Hall Basement, Pump Room

0.94 %

PC-2 Black/Red Metal Pipes Eliot Hall Basement, Pump Room

3.6 %

PC-3

Light

Yellow CMU Walls

Eliot Hall Basement, Outside Pump

Room

2.2 %

PC-4 White CMU Walls Eliot Hall Basement, Bomb Shelter

0.14 %

PC-5 Gray Metal Door Well House, Door <0.034 %

PC-6 Black Wood Wall Well House, Behind

Electric Panel <0.0080%

< = lead not detected above the analytical method’s reporting limit.

OSHA construction rules do not specify acceptable levels of lead within paints or other surface coatings for the purposes of occupational exposures. Construction work involving lead-containing paint must be completed in accordance with OSHA regulations, not limited to the lead standard, 29 CFR 1926.62 (Lead in Construction). Contractors completing work in areas found to contain lead, or where it is reasonable to assume lead may be present, should be notified of the presence

(and potential presence) of lead and proper work protocols should be used in accordance with 29

CFR 1926.62. Additionally, contractors must comply with applicable Owner project specifications when disturbing any paints confirmed or assumed (untested; not listed in the table above) to contain lead.

The lead paint testing was limited to dominant type painted surfaces described herein, and the scope of work outlined in our proposal. It should be understood that this limited lead paint sampling is not considered to be comprehensive in nature, and the results are not intended to be used to determine lead hazards, develop abatement plans, or prepare detailed cost estimates for abatement. Any untested paints should be assumed as lead-containing.

Responsive ■ Resourceful ■ Reliable 8

6.0 LIMITATIONS/GENERAL COMMENTS

In addition to limitations indicated in other sections of this report, if any, Terracon did not perform sampling which required demolition or destructive activities such as knocking large holes in walls, dismantling of equipment or removal of protective coverings. Electrical equipment, electrical lines, and active equipment such as inside of boilers, HVAC units, and elevator shafts were not included in this scope of services as such item present a safety hazard to the inspectors. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas which may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.

The scope of services was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our inspection/testing pertaining to the authorized scope of services. The information contained in this report is relevant to the date on which the site visit was performed and may not represent conditions at a later date (especially if new materials are later installed). This report has been prepared on behalf of and exclusively for use by the Client for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding any quantities listed, further investigation, or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

APPENDIX A

ASBESTOS INSPECTION SAMPLE LOCATION SUMMARY

Responsive ■ Resourceful ■ Reliable B-1

APPENDIX A

PROJECT: ACAD - REHABILITATE SCHOODIC

WATER AND WASTEWATER SYSTEMS

Acadia National Park

Schoodic Institute

Winter Harbor, Maine 04693

Asbestos Inspection Sample Location Summary

HA No. Sample Number Material Description Sample Location

Lab Results

PLM

TEM Gravimetric Reduction (for non-friable organically bound

(NOB) material samples)

1A Black Pipe Gasket Eliot Hall Basement, Pump

Room None Detected None Detected

1B Black Pipe Gasket Eliot Hall Basement, Pump

Room None Detected None Detected

1C Black Pipe Gasket Eliot Hall Basement, Pump

Room None Detected None Detected

2A Patch Cement Eliot Hall Basement, Pump

Room, Between Brick and Pipe None Detected Not Applicable

2B Patch Cement Eliot Hall Basement, Pump

Room, Between Brick and Pipe None Detected Not Applicable

2C Patch Cement Eliot Hall Basement, Pump

Room, Between Brick and Pipe None Detected Not Applicable

3A Smooth Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

3B Smooth Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

Responsive ■ Resourceful ■ Reliable B-2

Lab Results

PLM

TEM Gravimetric Reduction (for non-friable organically bound

(NOB) material samples)

3C Smooth Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

4A Rough Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

4B Rough Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

4C Rough Penetration

Cement

Eliot Hall Basement, Pump

Room, North Wall None Detected Not Applicable

5A Penetration Cement Eliot Hall Basement, Outside

Pump Room, South Wall None Detected Not Applicable

5B Penetration Cement Eliot Hall Basement, Outside

Pump Room, South Wall None Detected Not Applicable

5C Penetration Cement Eliot Hall Basement, Outside

Pump Room, South Wall None Detected Not Applicable

6A Brown Grease Eliot Hall Basement, Pump

Room, Inside Blue Pipe Cooler None Detected None Detected

6B Brown Grease Eliot Hall Basement, Pump

Room, Inside Blue Pipe Cooler None Detected None Detected

6C Brown Grease Eliot Hall Basement, Pump

Room, Inside Blue Pipe Cooler None Detected None Detected

7A Bomb Shelter

Cement

Eliot Hall Basement, Bomb

Shelter Room None Detected Not Applicable

7B Bomb Shelter

Cement

Eliot Hall Basement, Bomb

Shelter Room None Detected Not Applicable

7C Bomb Shelter

Cement

Eliot Hall Basement, Bomb

Shelter Room None Detected Not Applicable

08 8A Black Rope Eliot Hall Basement, Pump

Room None Detected Not Applicable

Responsive ■ Resourceful ■ Reliable B-3

Lab Results

PLM

TEM Gravimetric Reduction (for non-friable organically bound

(NOB) material samples)

8B Black Rope Eliot Hall Basement, Pump

Room None Detected Not Applicable

8C Black Rope Eliot Hall Basement, Pump

Room None Detected Not Applicable

9A Cement Well House, Foundation None Detected Not Applicable

9B Cement Well House, Foundation None Detected Not Applicable

9C Cement Well House, Foundation None Detected Not Applicable

10A Mortar Well House, Casing Opening None Detected Not Applicable

10B Mortar Well House, Casing Opening None Detected Not Applicable

10C Mortar Well House, Casing Opening None Detected Not Applicable

11A Gypsum Board Well House Walls None Detected Not Applicable

11B Gypsum Board Well House Walls None Detected Not Applicable

11C Gypsum Board Well House Walls None Detected Not Applicable

12A Fiberglass Backing

Paper Well House Walls and Ceiling None Detected Not Applicable

12B Fiberglass Backing

Paper Well House Walls and Ceiling None Detected Not Applicable

12C Fiberglass Backing

Paper Well House Walls and Ceiling None Detected Not Applicable

13A Red Gasket Well House, Lower Pipe, Gray

Flange None Detected None Detected

13B Red Gasket Well House, Lower Pipe, Gray

Flange None Detected None Detected

Responsive ■ Resourceful ■ Reliable B-4

Lab Results

PLM

TEM Gravimetric Reduction (for non-friable organically bound

(NOB) material samples)

13C Red Gasket Well House, Lower Pipe, Gray

Flange None Detected None Detected

14A Gray Pipe Thread

Caulk Well House, Pipe Threads None Detected None Detected

14B Gray Pipe Thread

Caulk Well House, Pipe Threads None Detected None Detected

14C Gray Pipe Thread

Caulk Well House, Pipe Threads None Detected None Detected

15A Red Gasket Well House, Upper Pipe, Hexagonal Flange None Detected None Detected

15B Red Gasket Well House, Upper Pipe, Hexagonal Flange None Detected None Detected

15C Red Gasket Well House, Upper Pipe, Hexagonal Flange None Detected None Detected

16A White Thread Sealant Well House, Upper Pipe, Below

Meter None Detected None Detected

16B White Thread Sealant Well House, Upper Pipe, Below

Meter None Detected None Detected

16C White Thread Sealant Well House, Upper Pipe, Below

Meter None Detected None Detected

17A Roof Shingle Well House Roof None Detected None Detected

17B Roof Shingle Well House Roof None Detected None Detected

17C Roof Shingle Well House Roof None Detected None Detected

18A Vapor Barrier Well House Roof None Detected None Detected

18B Vapor Barrier Well House Roof None Detected None Detected

18C Vapor Barrier Well House Roof None Detected None Detected

APPENDIX B

SAMPLE LOCATION DIAGRAMS

GENERAL BUILDING LAYOUT / SAMPLE LOCATIONS

Eliot Hall - Basement Winter Harbor, Maine B

77 Sundial Ave, Suite #401w Manchester, NH 03103

PH. (603) 647-9700 FAX. (864) 647-4432

J1215067

4/11/22

MAC

ACF

MAC

MAC

N.T.S.

Project Manager:

Drawn by:

Checked by:

Approved by:

Project No.

Scale:

File Name:

Date:

App.

VHB - Acadia

DIAGRAM PROVIDED BY CLIENT AND

ADAPTED FOR PROJECT USE. DRAWING

MAY HAVE NON-TERRACON RELATED

INFORMATION. TERRACON SAMPLE

NUMBERS ARE PROVIDED OVER CLIENT

SUPPLIED DRAWING AND IS FOR GENERAL

LOCATION ONLY.

1A-C

2A-C

6A-C

8A-C 4A-C

3A-C

5A-C

PC-3

7A

7B 7C

PC-1

PC-2

PC-4

Pump Room

Bomb Shelter

GENERAL BUILDING LAYOUT / SAMPLE LOCATIONS

Pumphouse Winter Harbor, Maine B

77 Sundial Ave, Suite #401w Manchester, NH 03103

PH. (603) 647-9700 FAX. (864) 647-4432

J1215067

4/11/22

MAC

ACF

MAC

MAC

N.T.S.

Project Manager:

Drawn by:

Checked by:

Approved by:

Project No.

Scale:

File Name:

Date:

App.

VHB – Acadia

DIAGRAM PROVIDED BY CLIENT AND

ADAPTED FOR PROJECT USE. DRAWING

MAY HAVE NON-TERRACON RELATED

INFORMATION. TERRACON SAMPLE

NUMBERS ARE PROVIDED OVER CLIENT

SUPPLIED DRAWING AND IS FOR GENERAL

LOCATION ONLY.

9A

9B

9C

10A

10B

10C

11A

11B

11C

12A

12B

12C

13A-C 14A-C

16A-C15A-C

17A

17B 17C

18C

18A

18B

PC-5

PC-6

APPENDIX C

PHOTOGRAPHIC DOCUMENTATION

Asbestos and Lead Paint Inspection Schoodic Institute, Acadia National Park Winter Harbor, ME

Photo 1 – Pump Room, Pipes Pictured Photo 2 – Pump Room, Pipes Pictured

Photo 3 – Pump Room, Pipes Pictured Photo 4 – Pump Room, Pipes Pictured

Photo 5 – Bomb Shelter Photo 6 – Outside Pump Room

Asbestos and Lead Paint Inspection Schoodic Institute, Acadia National Park Winter Harbor, ME

Photo 7 – Outside Pump House Photo 8 – Interior of Pipe House – Pipe Junction Pictured

Photo 9 – Interior of Pump House – Pump Hole

Photo 10 – Interior of Pump House, Pipe Gasket

Photo 11 – Interior of Pump House, Pipe Junction

Photo 12 – Roof of Pump House

APPENDIX D

LABORATORY ANALYTICAL DATA

EMSL Analytical, Inc.

161 John Roberts Road South Portland, ME 04106

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Attn:

Proj: ACAD Water and WW System Replacement/J1215067

Phone: (603) 647-9700

Fax: (603) 647-4432

Collected: 2/28/2022

Received: 3/02/2022

Analyzed: 3/09/2022

Adam Frey

Terracon Consultants, Inc.

77 Sundial Avenue

Suite 401-W

Manchester, NH 03103

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00011A

Eliot Hall Basement, pipe room/Black pipe gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00021B

Eliot Hall Basement, pipe room/Black pipe gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00031C

Eliot Hall Basement, pipe room/Black pipe gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00042A

Eliot Hall basement, pipe room, between brick and pipe/Patch cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00052B

Eliot Hall basement, pipe room, between brick and pipe/Patch cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00062C

Eliot Hall basement, pipe room, between brick and pipe/Patch cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00073A

Eliot Hall basement, pipe room, north wall/Smooth penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 1 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00083B

Eliot Hall basement, pipe room, north wall/Smooth penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00093C

Eliot Hall basement, pipe room, north wall/Smooth penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00104A

Eliot Hall basement, pipe room, north wall/Rough penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00114B

Eliot Hall basement, pipe room, north wall/Rough penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00124C

Eliot Hall basement, pipe room, north wall/Rough penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00135A

Eliot Hall basement, outside pipe room, south wall/Penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00145B

Eliot Hall basement, outside pipe room, south wall/Penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00155C

Eliot Hall basement, outside pipe room, south wall/Penetration cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 2 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00166A

Eliot Hall basement, pipe room, inside blue pipe cooler/Brown grease

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBrown

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBrown

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00176B

Eliot Hall basement, pipe room, inside blue pipe cooler/Brown grease

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBrown

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBrown

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00186C

Eliot Hall basement, pipe room, inside blue pipe cooler/Brown grease

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBrown

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBrown

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00197A

Eliot Hall basement, bomb shelter/Bomb shelter cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00207B

Eliot Hall basement, bomb shelter/Bomb shelter cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00217C

Eliot Hall basement, bomb shelter/Bomb shelter cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00228A

Eliot Hall basement, pipe room/Black rope

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00238B

Eliot Hall basement, pipe room/Black rope

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 3 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00248C

Eliot Hall basement, pipe room/Black rope

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00259A

Well house, foundation/Cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00269B

Well house, foundation/Cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-00279C

Well house, foundation/Cement

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-002810A

Well house, mortar casing opening/Mortar

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-002910B

Well house, mortar casing opening/Mortar

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003010C

Well house, mortar casing opening/Mortar

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 0.0% 100.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003111A

Well house walls/Gypsum board

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 5.0% 95.0%PLM Gray None Detected

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 4 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003211B

Well house walls/Gypsum board

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 5.0% 95.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003311C

Well house walls/Gypsum board

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 5.0% 95.0%PLM Gray None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003412A

Well house walls and ceiling/Fiberglass backing paper

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 80.0% 20.0%PLM Black None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003512B

Well house walls and ceiling/Fiberglass backing paper

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 80.0% 20.0%PLM Black None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003612C

Well house walls and ceiling/Fiberglass backing paper

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/07/2022 80.0% 20.0%PLM Black None Detected

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003713A

Well house, lower pipe, gray flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003813B

Well house, lower pipe, gray flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-003913C

Well house, lower pipe, gray flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 5 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004014A

Well house, pipe threads/Gray pipe thread caulk

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedGray

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedGray

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004114B

Well house, pipe threads/Gray pipe thread caulk

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedGray

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedGray

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004214C

Well house, pipe threads/Gray pipe thread caulk

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedGray

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedGray

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004315A

Well house, upper pipe, hexagonal flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004415B

Well house, upper pipe, hexagonal flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004515C

Well house, upper pipe, hexagonal flange/Red gasket

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedRed

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedRed

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004616A

Well house, upper pipe, below meter/White thread sealant

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedWhite

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedWhite

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 6 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004716B

Well house, upper pipe, below meter/White thread sealant

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedWhite

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedWhite

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004816C

Well house, upper pipe, below meter/White thread sealant

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedWhite

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedWhite

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-004917A

Well house roof/Roof shingle

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 15.5% 84.5%PLM Grav. Reduction None DetectedBlack/Green

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack/Green

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-005017B

Well house roof/Roof shingle

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 15.2% 84.8%PLM Grav. Reduction None DetectedBlack/Green

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack/Green

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-005117C

Well house roof/Roof shingle

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 15.7% 84.3%PLM Grav. Reduction None DetectedBlack/Green

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack/Green

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-005218A

Well house roof/Black roof paper/vapor barrier

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-005318B

Well house roof/Black roof paper/vapor barrier

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 7 of 8

Phone/Fax: (207) 517-6921 / (207) 517-6922 http://www.EMSL.com / portlandlab@emsl.com

JAWO50

622200326EMSL Order ID:

Customer ID:

Customer PO:

Project ID:

Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116

Client Sample ID:

Sample Description:

Lab Sample ID: 622200326-005418C

Well house roof/Black roof paper/vapor barrier

DateTEST Non-Fibrous Asbestos CommentColor Fibrous

Non-AsbestosAnalyzed

3/09/2022 0.0% 100%PLM Grav. Reduction None DetectedBlack

3/09/2022 0.0% 100.0%TEM Grav. Reduction None DetectedBlack

PLM: ME CERT #BA-0178

PLM EPA NOB: ME CERT #BA-0197

TEM EPA NOB: ME CERT #BA-0197

Analyst(s):

PLM (30)Stephen Severn

PLM Grav. Reduction (24)

TEM Grav. Reduction (24)

Thomas Stegeman

Samantha Voigt, Laboratory Manager or Other Approved Signatory

Reviewed and approved by:

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S.

Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM alone is not consistently reliable in detecting asbestos in floor coverings and similar NOBs

Samples analyzed by EMSL Analytical, Inc. South Portland, ME NVLAP Lab Code 500094-0, VT AL197271, ME LM-0039, CT PH-0346 Initial report from: 03/09/202214:57:26

Test Report:EPAMultiTests-7.32.2.D Printed: 3/09/2022 02:57PM Page 8 of 8

OrderID: 622200326

OrderID: 622200326

Client Sample Description ConcentrationLab ID Analyzed Weight Lead

Collected

EMSL Analytical, Inc.

200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com

Attn: Adam Frey Terracon Consultants, Inc.

77 Sundial Avenue Suite 401-W Manchester, NH 03103

Received: 3/3/2022 10:30 AM

ACAD Water and WW System Replacement / J1215067

Fax: (603) 647-4432 Phone: (603) 647-9700

Project:

2/28/2022Collected:

Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*

202202356 CustomerID: JAWO50 CustomerPO: J1215067 ProjectID:

EMSL Order:

0.0655 Site: Eliot Hall Basement - Pump Room - Blue Pump Coolers

202202356-0001PC-1 0.94 % wt3/10/2022 g2/28/2022

0.2826 Site: Eliot Hall Basement - Pump Room - Black/Red Pipes

202202356-0002PC-2 3.6 % wt3/10/2022 g2/28/2022

0.2600 Site: Eliot Hall Basement - Outside Pump Room - Light Yellow CMU Walls

202202356-0003PC-3 2.2 % wt3/10/2022 g2/28/2022

0.2517 Site: Eliot Hall Basement - Bomb Shelter - White Walls

202202356-0004PC-4 0.14 % wt3/10/2022 g2/28/2022

0.0591 Site: Well House - Gray Door of Well House

202202356-0005PC-5 <0.034 % wt3/10/2022 g2/28/2022

0.2628 Site: Well House - Electric/Wood Panel

202202356-0006PC-6 <0.0080 % wt3/10/2022 g2/28/2022

Owen Mckenna, Lead Lab Manager or other approved signatory

Test Report ChmSnglePrm/nQC-7.32.3 Printed: 3/11/2022 2:25:08 PM

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.

* Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.

Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01

Initial report from 03/11/2022 14:25:08 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com

OrderID: 202202356

OrderID: 202202356

APPENDIX E

INSPECTOR’S LICENSE