B09_Attach_26_Generator_Calculation_0003.pdf

PDF 221 KB Posted

Attached to
ACAD 312255 - Rehabilitate Schoodic Water System
Solicitation number
140P2022R0043
Issued by

About this file

This document contains a generator sizing analysis and recommendation for a federal contract opportunity to rehabilitate water and wastewater systems at Acadia National Park in Winter Harbor, Maine. The analysis evaluates a load consisting of a 3.5 kW resistive load and a 5 HP motor load, and recommends a 25 kW LP vapor generator model RG25 to meet the total peak load of 21.9 kW. The generator is rated at 23 kW with a 1.5L engine and standard RG025 alternator. The analysis confirms the generator selection can handle the starting transients and running loads within specified voltage and frequency distortion limits.

View the file

Other files

File Type Posted
B09_Attach_31_General_Refs_0005.doc DOC document
Sol_140P2022R0043_Amd_0005.pdf PDF
B09_Attach_22_Request_for_Information_0005.pdf PDF
B09_Attach_29_O_M_0004.pdf PDF
B09_Attach_30_Photo_0004.pdf PDF
B09_Attach_22_Request_for_Information_0004.pdf PDF
Sol_140P2022R0043_Amd_0004.pdf PDF
B09_Amend_04_RFIs_updated_0004.pdf PDF
B09_Attach_28_Well_Pump_Calcs_0003.pdf PDF
Sol_140P2022R0043_Amd_0003.pdf PDF
B09_Attach_25_Plans_Update_0003.pdf PDF
B09_Attach_24_Spec_Updates_0003.pdf PDF
B09_Attach_23_Addendum_Summary_0003.pdf PDF
B09_Attach_22_Request_for_Information_0003.pdf PDF
B09_Amend_03_Updates_0003.pdf PDF
B09_Attach_27_Sewer_Tables_0003.pdf PDF
Sol_140P2022R0043_Amd_0002.pdf PDF
B09_Amend_02_Sign_in_Sheet_0002.pdf PDF
Sol_140P2022R0043_Amd_0001.pdf PDF
Amendment_01_Site_Visit_0001.pdf PDF
B08_Attach_12_Permit_Plan.pdf PDF
B08_Attach_05_Vaccination_Certification_Notification_.pdf PDF
B08_Attach_11_Radio_Path_Study.pdf PDF
B08_Attach_04_Certification_of_Vaccination_Form.pdf PDF
B08_Attach_14_PSP.pdf PDF
B08_Attach_03_Davis_Bacon.pdf PDF
B08_Attach_18_Product_Data_basis_of_estimate.pdf PDF
B08_Attach_15_JOFOC_SCADA_Software.pdf PDF
B08_Attach_08_Structural_Tests___Special_Inspections.pdf PDF
B08_Attach_01_Specs.pdf PDF
Sol_140P2022R0043.pdf PDF
B08_Attach_17_O_M_Requirements.xlsx XLSX spreadsheet
B08_Attach_02_Drawings.pdf PDF
B08_RFP_140P2022R0043.pdf PDF
B08_Attach_10_HazMat_Report.pdf PDF
B08_Attach_09_Calculations.pdf PDF
B08_Attach_07__Sewer_Inspection.pdf PDF
B08_Attach_19_ConstructabilityChecklist.xlsx XLSX spreadsheet
B08_Attach_16_SubmittalList_Estimate.xlsx XLSX spreadsheet
B08_Attach_13_LmtOnSubconRpt.xlsx XLSX spreadsheet
B08_Attach_06_Geotechnical_Report.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CentriPro

Note: Always consult the generator manufacturer whenever questions arise.

These sizing charts are recommendations based on motor service factor loading for typical continuous duty generators. If you need to call the generator manufacturer, be prepared to tell them the motor KVA code, the service factor amperage, locked rotor amperage, phase, Hz, motor type, etc. This information can all be found in this manual.

Please note that the 2-wire chart is only for PSC (permanent split capacitor) type, 2-wire motors and should not be used for split-phase, 2-wire motors. If using split-phase, 2-wire motors the generator should be 50% larger than that listed for a 3-wire motor.

You must know which type generator you have before using the charts as the required generator size varies by type. Internally regulated generators are also called self-excited. Externally regulated generators are the most common. In addition to the Kw/KVA rating, the generator frequency (Hz, typically 60 Hz in USA) is very important when operating pumping equipment because frequency variations affect pump output in direct relation to the pump Affinity Laws.

Operating under 60 Hz will reduce flow and head while operating over 60 Hz will increase flow, head, HP and amp draw and could overload the motor.

The generator should always be started before the pump/motor is started and always stop the pump/ motor before shutting down the generator. Operating generators at higher elevations or using natural gas a fuel can affect performance, consult the generator manufacturer for their recommendations in these instances.

GENERATOR SIZING

GENERATOR RECOMMENDATIONS

Externally Regulated Internally Regulated Motor HP KW KVA KW KVA Minimum Generator Rating

PSC .5 2.5 3.1 1.75 2.2

Type .75 3.5 4.4 2.5 3.1 2-Wire 1 5 6.3 3.2 4 1Ø 1.5 6 7.5 4 5 .5 2 2.5 1.5 1.9 .75 3 3.8 2 2.5 1 4 5 2.5 3.2

1.5 5 6.3 3 3.8 2 7.5 9.4 4 5 3 10 12.5 5 6.3 5 15 18.8 7.5 9.4

7.5 20 25 10 12.5

3-Wire 10 30 37.5 15 18.8

1Ø

15 40 50 20 25 and 20 60 75 25 31

3Ø

25 75 94 30 37.5

Motors 30 100 125 40 50

40 100 125 50 62.5 50 150 188 60 75 60 175 220 75 94 75 250 313 100 125 100 300 375 150 188 125 375 469 175 219 150 450 563 200 250 175 525 656 250 313 200 600 750 275 344

SHEET TAKEN FROM PUMP PRODUCT

DATA. GENERATOR SIZE COMPLIES

WITH RECCOMENDATION. IN ADDITION,

MOTOR STARTING / LOADING

ANALYSIS WAS PERFORMED WITH

GENERACS SIZING SOFTWARE AND IT

CONFIRMED THE RG25 AS

ACCEPTABLE.

Home (/home) / ACAD (/project/71570) / acad 1

ACAD

acad 1

Contact Name Contact Email Prepared By sbuscemi@aeieng.com Company AEI Phone 6082170565 Email sbuscemi@aeieng.com

Recommended Product

Model - RG25 25 kw, LP Vapor Genset -- Site rated 23 kw

1.5 L Engine with Standard (RG025) Alternator

37 % Running kW

2.9 Fdip (Hz)

0.0 % THVD Cont.

95 % Peak kW

19.5 % Vdip (%)

0.0 % THVD Peak

Family Selection Method

Manual

Product Family

Protector/QT

Sizing Method

Manual

Generator

RG25

Quantity

1 Unit

Alternator

RG025

Request for Quote✉

Our website uses cookies so that we can provide you with the best user experience. To read more about the cookies we use, see our privacy policy (http://www.generac.com/privacy-policy). .

https://pdp.powerdesignpro.com/home https://pdp.powerdesignpro.com/project/71570 http://www.generac.com/privacy-policy

Solution Limits

Load Summary Running Transients Harmonics

Add Load (/project/71570/solution/89338/addLoad)

Description / Sequence

Starting Running Harmonic Distortion Limits kW kVA kW kVA Peak Run kVA Vdip Fdip

Group 1 (Non-Concurrent)

Resistive:

Resistive #1 1 X 3.50 kW , @

1.00 PF

Harmonics:

THID =

0.00%

Gro

3.5 3.5 3.5 3.5 0 0 0 35.00

Hertz

(/project/71570/solution/89338/load/14/copyLoad/148791)

(/project/71570/solution/89338/load/14/editLoad/148791)

Motor:

Motor #1 1 X 5.00 HP , Code J (7.5 kVA/Hp) , Across the Line , Rated torque at start running at 100%

Gro

18.38 37.5 5.06 6.1 0 0 0 35.00

Hertz

(/project/71570/solution/89338/load/11/copyLoad/290809)

(/project/71570/solution/89338/load/11/editLoad/290809)

Loads Documentation Gas Piping Exhaust Piping Transient Analysis Harmonic Analysis

Max Loading 80 % Fdip (Hz) 15 THVD Cont. 11 %

Vdip (%) 35 % THVD Peak 13 % kW 8.56 kW (step) 18.38 kVA 0 kVA 9.6 kW (peak) 21.88 THID Cont. 0 %

PF 0.89 kVA (step) 37.5 THID Peak 0 %

Our website uses cookies so that we can provide you with the best user experience. To read more about the cookies we use, see our privacy policy (http://www.generac.com/privacy-policy). .

https://pdp.powerdesignpro.com/project/71570/solution/89338/addLoad https://pdp.powerdesignpro.com/project/71570/solution/89338/load/14/copyLoad/148791 https://pdp.powerdesignpro.com/project/71570/solution/89338/load/14/editLoad/148791 https://pdp.powerdesignpro.com/project/71570/solution/89338/load/11/copyLoad/290809 https://pdp.powerdesignpro.com/project/71570/solution/89338/load/11/editLoad/290809

Description / Sequence

Starting Running Harmonic Distortion Limits kW kVA kW kVA Peak Run kVA Vdip Fdip

All Loads on sequence starting 21.9kW

Sequence Peak

21.9kW Application

Peak

18.38 37.5 8.56 9.6 0 0 0 35 %

Volts

25 %

Hertz

Shed

© 2019 Power Design Pro . All rights reserved.