This document is a Statement of Structural Tests and Special Inspections for the ACAD 312255 project to Rehabilitate the Schoodic Water and Wastewater Systems at Acadia National Park in Winter Harbor, Maine. It requires special inspections for steel construction, concrete construction, and soils. Steel construction verification must be done by an ICC-SSBSI inspector. Concrete construction inspections include reinforcing steel, anchors, mix design, placement, curing, and formwork requiring ACI certifications. Soils inspections include verification of bearing capacity and excavation depth by a PE/GE, as well as fill classification, placement and compaction testing. The related federal contract opportunity is solicitation number 140P2022R0043 from the National Park Service for the rehabilitation work with an estimated value over $25,000.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ACAD 312255 Statement of Structural Tests and Special Inspections Page 1 of 6
Statement of Structural Tests and Special Inspections National Park Service (NPS) - Denver Service Center (DSC) | 6-29-21
Park: Acadia National Parl
Project Management Information System (PMIS) Number: ACAD 312255
Project Name: Rehabilitate Schoodic Water and Wastewater Systems
Structural Engineering Firm: Silman
This Statement of Structural Tests and Special Inspections is being submitted as required by Chapter 17 of the 2021 International Building Code (IBC-21). It includes the following:
1. Seismic requirements
2. Wind requirements
3. Qualification Requirements for Inspectors and Testing Technicians
4. Listing of Required Structural Tests and Special Inspections
The Construction Contractor’s Quality Control Supervisor will provide copies of all special inspection reports and associated documentation to the Contracting Officer (CO). The Construction Contractor will be required to correct all deficiencies discovered in the Special Inspection and Structural Testing program.
Prepared By: _________________Edmund Meade, PE___________ (Type or print name)
Signature: ____________________________________________________ Date: ____June 21, 2022
Stamped by Professional Engineer (PE) or Structural Engineer (SE)
ACAD 312255 Statement of Structural Tests and Special Inspections Page 2 of 6
Seismic and Wind Requirements
Seismic Requirements, IBC-21 Section 1704.3 Description of seismic-force-resisting system and designated seismic systems subject to special inspections:
The foundation component of the seismic-force resisting system is ordinary reinforced concrete shear walls (R=5). The well house system is not within Silman’s scope.
Wind Requirements, IBC-21 Section 1704.3 Description of wind-force-resisting system and designated wind systems subject to special inspections:
The foundation component of the seismic-force resisting system is ordinary reinforced concrete shear walls (R=5). The well house system is not within Silman’s scope.
ACAD 312255 Statement of Structural Tests and Special Inspections Page 3 of 6
Instructions:
1. Under Listing of Required Structural Tests and Special Inspections:
a. Required? - Place an X for all Special Inspections and Tests required for this project.
b. Required Qualifications - Provide qualifications for the special inspector, using the
Qualification Requirements for Inspector and Testing Technicians list below, for all required Structural Tests and Special Inspections.
c. Continuous - If marked with an X, continuous special inspection shall be as defined in Chapter
2, IBC-21.
d. Periodic - If marked with an X, provide the minimum number of tests, i.e. 20% of all field welds, or the amount of work to be inspected (e.g. 10% of all wall surfaces).
2. Attach completed Statement of Structural Tests and Special Inspections to the end of NPS DSC Division 1 Specifications Section 01 40 00 Quality Requirements.
Qualification Requirements for Inspectors and Testing Technicians
PE/SE Structural Engineer – licensed PE or SE specializing in the design of buildings and structures PE/GE Geotechnical Engineer – licensed PE specializing in soil mechanics and foundations EIT Engineer-In-Training – graduate engineer who has passed the Fundamentals of engineering examination
American Concrete Institute (ACI) Certification ACI-CCSI Concrete Construction Special Inspector ACI-LTT Concrete Laboratory Testing Technician Level 1 or 2 ACI-STT Concrete Strength Testing Technician ACI-FTT Concrete Field Testing Technician – Grade I
American Society of Non-Destructive Testing (ASNT) Certification Non-Destructive Testing Technician – Level II or III
American Welding Society (AWS) Certification AWS-CWI Certified Welding Inspector
Exterior Design Institute (EDI) Certification EDI-EIFS Certified EIFS inspector
International Code Council (ICC) Certification ICC-PCSI Prestressed Concrete Special Inspector ICC-RCSI Reinforced Concrete Special Inspector ICC-SSI Soils Special Inspector ICC-SFSI Spray-applied Fireproofing Special Inspector ICC-SMSI Structural Masonry Special Inspector ICC-SSBSI Structural Steel and Bolting Special Inspector ICC-SWSI Structural Welding Special Inspector
National Institute for Certification in Engineering Technologies (NICET) Certification NICET-CT Concrete Technician – Levels I, II, III and IV NICET-GET Geotechnical Engineering Technician - Levels I, II, III and IV NICET-ST Soils Technician - Levels I, II, III and IV
ACAD 312255 Statement of Structural Tests and Special Inspections Page 4 of 6
Other
ACAD 312255 Statement of Structural Tests and Special Inspections Page 5 of 6
Listing of Required Structural Tests and Special Inspections R eq ui re d?
Structural Test or Special Inspection Required Qualifications
C on tin uo us
P er io di c Frequency of Periodic Test or Inspection
Steel Construction (IBC-21 Section 1705.2; American Institute of Steel Construction: AISC 360-16 Chapter N, AISC 341- 16 Chapter J)
Other Inspection Tasks (AISC 360-16 Section N5.7)
X 1. Verify compliance of fabricated steel with the details shown on the approved shop drawings.
ICC-SSBSI X
Concrete Construction (IBC-21 Section 1705.3)
X 1. Inspect reinforcing steel ACI-FTT X
X 2. Inspection of anchors post-installed in hardened concrete members.
X a. Mechanical anchors and adhesive anchors ACI-FTT X
X 3. Verify use of approved design mix. ACI-FTT X Each truck
X
4. Prior to placement fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete.
ACI-FTT
X
Each truck
X 5. Inspect concrete placement for proper application techniques.
ACI-FTT X Each pour
X 6. Inspect for maintenance of specified curing temperature and techniques.
ACI-FTT X Each pour
X
7. Inspection formwork for shape, location and dimensions of the concrete member being formed.
ACI-FTT
X
Each member/element
Soils (IBC-21 Section 1705.6)
X
1. Verify materials below shallow foundations are adequate to achieve the required bearing capacity.
PE/GE
X
Min 1 soil/rock test per foundation to confirm bearing capacity
ACAD 312255 Statement of Structural Tests and Special Inspections Page 6 of 6
R eq ui re d?
Structural Test or Special Inspection Required Qualifications
C on tin uo us
P er io di c Frequency of Periodic Test or Inspection
X 2. Verify excavations are extended to proper depth and have reached proper material.
CI X Each excavation
X 3. Perform classification and testing of compacted fill materials.
PE/GE X
X
4. During fill placement, verify use of proper materials and procedure in accordance with the provisions of the approved geotechnical report.
Verify densities and lift thicknesses during placement and compaction of compacted fill.
PE/GE
X
X
5. Prior to placement of compacted fill, inspect subgrade and verify that site has been prepared properly.
PE/GE
X
| Seismic and Wind Requirements |
| Seismic Requirements, IBC-21 Section 1704.3 |
| Wind Requirements, IBC-21 Section 1704.3 |
| Instructions: |
| Qualification Requirements for Inspectors and Testing Technicians |
| American Concrete Institute (ACI) Certification |
| American Society of Non-Destructive Testing (ASNT) Certification |
| American Welding Society (AWS) Certification |
| Exterior Design Institute (EDI) Certification |
| International Code Council (ICC) Certification |
| National Institute for Certification in Engineering Technologies (NICET) Certification |
| Other |
Listing of Required Structural Tests and Special Inspections