B09_Attach_27_Sewer_Tables_0003.pdf

PDF 229 KB Posted

Attached to
ACAD 312255 - Rehabilitate Schoodic Water System
Solicitation number
140P2022R0043
Issued by

About this file

This document contains tables summarizing the condition and specifications of sewer pipe sections and rehabilitation requirements for the ACAD 312255 solicitation to rehabilitate the Schoodic water and wastewater systems at Acadia National Park in Winter Harbor, Maine. The tables list approximately 4,163 linear feet of sewer pipe in various diameters and materials that will be rehabilitated using cured-in-place pipe lining or replaced with new PVC pipe. The rehabilitation and replacement work includes sections serving buildings, manholes, grease traps, and other infrastructure throughout the park. The solicitation was issued by the National Park Service National Office within the Department of the Interior to solicit bids for the rehabilitation and replacement work on the sewer systems detailed in the tables.

View the file

Other files

File Type Posted
B09_Attach_31_General_Refs_0005.doc DOC document
Sol_140P2022R0043_Amd_0005.pdf PDF
B09_Attach_22_Request_for_Information_0005.pdf PDF
B09_Attach_29_O_M_0004.pdf PDF
B09_Attach_30_Photo_0004.pdf PDF
B09_Attach_22_Request_for_Information_0004.pdf PDF
Sol_140P2022R0043_Amd_0004.pdf PDF
B09_Amend_04_RFIs_updated_0004.pdf PDF
B09_Attach_28_Well_Pump_Calcs_0003.pdf PDF
Sol_140P2022R0043_Amd_0003.pdf PDF
B09_Attach_25_Plans_Update_0003.pdf PDF
B09_Attach_24_Spec_Updates_0003.pdf PDF
B09_Attach_23_Addendum_Summary_0003.pdf PDF
B09_Attach_22_Request_for_Information_0003.pdf PDF
B09_Amend_03_Updates_0003.pdf PDF
B09_Attach_26_Generator_Calculation_0003.pdf PDF
Sol_140P2022R0043_Amd_0002.pdf PDF
B09_Amend_02_Sign_in_Sheet_0002.pdf PDF
Sol_140P2022R0043_Amd_0001.pdf PDF
Amendment_01_Site_Visit_0001.pdf PDF
B08_Attach_12_Permit_Plan.pdf PDF
B08_Attach_05_Vaccination_Certification_Notification_.pdf PDF
B08_Attach_11_Radio_Path_Study.pdf PDF
B08_Attach_04_Certification_of_Vaccination_Form.pdf PDF
B08_Attach_14_PSP.pdf PDF
B08_Attach_03_Davis_Bacon.pdf PDF
B08_Attach_18_Product_Data_basis_of_estimate.pdf PDF
B08_Attach_15_JOFOC_SCADA_Software.pdf PDF
B08_Attach_08_Structural_Tests___Special_Inspections.pdf PDF
B08_Attach_01_Specs.pdf PDF
Sol_140P2022R0043.pdf PDF
B08_Attach_17_O_M_Requirements.xlsx XLSX spreadsheet
B08_Attach_02_Drawings.pdf PDF
B08_RFP_140P2022R0043.pdf PDF
B08_Attach_10_HazMat_Report.pdf PDF
B08_Attach_09_Calculations.pdf PDF
B08_Attach_07__Sewer_Inspection.pdf PDF
B08_Attach_19_ConstructabilityChecklist.xlsx XLSX spreadsheet
B08_Attach_16_SubmittalList_Estimate.xlsx XLSX spreadsheet
B08_Attach_13_LmtOnSubconRpt.xlsx XLSX spreadsheet
B08_Attach_06_Geotechnical_Report.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CIPP Sections

Pipe Section Length*

(ft)

Diameter

(in)

Existing

Material

Laterals to be

Reinstated

Observation Sheet

SERC MH-B14 - SERC MH-B13 105 8 PVC 0 Debris present C4.2

SCHOONER COMMONS - GREASE TRAP 115 6 PVC 0 No discrete defects noted C4.3

SERC MH-C5 - CABINS PS 67 6 PVC 0 No discrete defects noted C4.3

CABIN 222 - CABINS PS 132 6 PVC 1 No discrete defects noted C4.3

SERC MH-B13 - SERC MH-B12 165 8 PVC 0 No discrete defects noted C4.4

SERC MH-B12 - SERC MH-B11 247 8 PVC 0 No discrete defects noted C4.4

SERC MH-B9 - SERC MH-B8 61 8 AC 0 Sag present C4.6

SERC MH-H1 - SERC MH-B8 123 8 AC 1 No discrete defects noted C4.6

SERC MH-B8 - SERC MH-B7 97 8 AC 0 No discrete defects noted C4.6

SERC MH-E1 - SERC MH-B7 47 8 AC 0 No discrete defects noted C4.6

SERC MH-B7 - SERC MH-B6 116 8 AC 1 No discrete defects noted C4.6

SERC MH-B6 - SERC MH-B5 78 8 AC 1 Encrustation deposit C4.6

SERC MH-D3 - SERC MH-D2 83 8 AC 0 No discrete defects noted C4.6

SERC MH-D2 - SERC MH-D1 50 8 AC 0 Debris present C4.6

SERC MH-D1 - SERC MH-B5 72 8 AC 0 No discrete defects noted C4.6

SERC SMH-C2 - SERC MH-C1A 130 8 AC 0 No discrete defects noted C4.7

SERC MH-C1 - SERC MH-A10 316 8 PVC 1 Roots and defective lateral present C4.7, C4.8

SERC MH-A10 - SERC MH-A9 58 8 PVC 0 No discrete defects noted C4.8

SERC MH-A9 - SERC MH-A8 77 8 PVC 0 No discrete defects noted C4.8

SERC MH-A8 - SERC MH-A7 93 8 PVC 0 No discrete defects noted C4.8, C4.11

SERC MH-A7 - SERC MH-A6 85 8 AC 0 No discrete defects noted C4.11

ROCKEFELLER HALL - SERC MH-A6 159 6 PVC 1 No discrete defects noted C4.11

SERC MH-A6 - SERC MH-A5 40 8 PVC 0 No discrete defects noted C4.11

SERC MH-A5 - SERC MH-A4 133 8 PVC 0 No discrete defects noted C4.11

Total 2649 LF 6

* Lengths in table are approximate. Lengths from CCTV and lengths from plan do not match exactly. Contractor shall determine lengths based on review of drawings.

Replacement Sections - PVC SDR 21 for all Sections Sheet Notes

Length*

(ft)

Existing

Diameter

(in)

Replaced

Diameter

Existing

Material

CAMPSITE 9 - SERC MH-B19 26 4 4 PVC C4.1 Bid Option 1

SERC MH-B19 - SERC MH-B18 196 6 6 PVC C4.1 Bid Option 1

CAMPSITE 6 - B MAIN LINE 63 4 4 PVC C4.1 Bid Option 1

CAMPSITE 5 - B MAIN LINE 57 4 4 PVC C4.1 Bid Option 1

CAMPSITE 4 - SERC MH-B18 56 4 4 PVC C4.1 Bid Option 1

SERC MH-B18 - SERC MH-B17 247 6 6 PVC C4.1 Bid Option 1

CAMPSITE 3 - B MAIN LINE 51 4 4 PVC C4.1 Bid Option 1

CAMPSITE 2 - B MAIN LINE 44 4 4 PVC C4.1 Bid Option 1

CAMPSITE 1 - SERC MH-B17 44 4 4 PVC C4.1 Bid Option 1

SERC MH-B17 - SERC MH-B16 88 6 6 PVC C4.1 Bid Option 1

Subtotal Bid Option 1 872

SERC MH-B16 - CAMPGROUNDS PS 86 6 6 PVC C4.1

HOST - B MAIN LINE 26 4 4 PVC C4.1

TRAILER 1 - CAMPGROUNDS PS 163 4 4 PVC C4.1

TRAILER 2 - TRAILER 1 LINE 36 4 4 PVC C4.1

NORTH FIELD TOILET - SERC MH-G2 62 4 4 PVC C4.1

WTP - SERC MH-G2 72 4 4 PVC C4.1

SERC MH-G2 - SERC MH-G1 137 8 8 PVC C4.1

SERC MH-G1 - CAMPGROUNDS PS 59 8 8 PVC C4.1

GREASE TRAP - SERC MH-C5 56 6 6 PVC C4.3

CABIN 220 - SERC MH-C5 29 6 6 PVC C4.3

CABIN 221 - CABIN 222 LINE 29 6 6 PVC C4.3

BLDG. 1192 - SERC MH-B11 87 6 6 PVC C4.4

SERC MH-B11 - SERC MH-B10 28 8 8 PVC C4.6

SERC MH-B10 - SERC MH-B9 38 8 8 PVC C4.6

BLDG. 186(1) - SERC MH-B9 27 6 6 PVC C4.6

BLDG. 186(2) - SERC MH-B9 28 6 6 PVC C4.6

BLDG. 197 - H MAIN LINE 21 6 6 AC C4.7

BLDG. 189 - SERC MH-E1 23 6 6 AC C4.6

BLDG. 186 - SERC MH-D3 51 6 6 AC C4.6

BLDG. 184 - SERC MH-D2 60 6 6 AC C4.6

SERC MH-B5 - SERC MH-B4 260 8 8 AC C4.6, C4.8, C4.9

BLDG. 164(1) - SERC MH-C2 31 6 6 AC C4.7

BLDG. 164(2) - SERC MH-C2 40 6 6 AC C4.7

ELIOT HALL - SERC MH-C1D 8 6 6 N/A C4.7

SERC MH-C1D - SERC MH-C1C 40 6 6 N/A C4.7

SERC MH-C1C - SERC MH-C1B 83 6 6 N/A C4.7

ELIOT HALL - SERC MH-C1B 29 6 6 AC C4.7

SERC MH-C1B - SERC MH-C1A 121 8 8 N/A C4.7

SERC MH-C1A - SERC MH-C1 132 8 8 AC C4.7

SERC MH-A12 - SERC MH-A11 247 6 6 PVC C4.8, C4.10

SERC MH-A11 - A MAIN LINE 13 6 6 PVC C4.8

BLDG. 148 - SERC MH-A9 206 6 6 PVC C4.8

SERC MH-B4 - SERC MH-B3 64 8 8 AC C4.9

SERC MH-B3 - SERC MH-B2 34 8 8 AC C4.9

SERC MH-B2 - SERC MH-B1 28 8 8 AC C4.9

BLDG. 137 - SERC MH-B1 13 4 4 AC C4.9

SERC MH-B1 - SERC MH-A1 44 8 8 AC C4.9

Replacement Sections - PVC SDR 21 for all Sections Sheet Notes

Length*

(ft)

Existing

Diameter

(in)

Replaced

Diameter

Existing

Material

SERC MH-A1 - WWTF 12 8 8 AC C4.9

SERC MH-A3 - SERC MH-A1 102 10 10 AC C4.9, C4.11

BLDG. 39 - SERC MH-A14 41 4 4 PVC C4.10

SERC MH-A14 - SERC MH-A13 116 8 8 PVC C4.10

SERC MH-A13 - SERC MH-A12 238 8 8 PVC C4.10

BLDG. 216 - SERC MH-A12 271 6 6 PVC C4.10

Subtotal Base Bid 3291

Total 4163 LF

* Lengths in table are approximate. Lengths from CCTV and lengths from plan do not match exactly. Contractor shall determine lengths based on review of drawings.

SewerSummary-CIPP-22-07-29
SewerSummary-Replace-22-07-29