Pre-Renovation Asbestos Inspection
Salt Lake City Veteran Affairs Medical Center
500 Foothill Drive
Salt Lake City, Utah
October 18, 2019
Terracon Project No. 61197461
Prepared for:
Apogee Consulting Group
Cary, North Carolina
Prepared by:
Terracon Consultants, Inc.
Midvale, Utah
Terracon Consultants, Inc. 6949 South H igh Tech Dr ive M idvale, U tah 84047
P [801] 545-8500 F [801] 545-8600 terracon.com
Apogee Consulting Group 1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511
Attn: Mr. Scott Simmons, PLA Landscape Architecture Department Manager P: 919-535-3840 E: ssimmons@acg-pa.com
Re: Pre-renovation Asbestos Inspection Salt Lake City Veterans Affairs Medical Center Expand Linen Distribution Center 500 Foothill Drive
Salt Lake City, Utah 84148
Dear Mr. Simmons:
The purpose of this report is to present the results of the pre-renovation asbestos inspection performed on September 26, 2019, at the Salt Lake City Veterans Affairs Medical Center in Salt Lake City, Utah. This inspection was conducted in accordance with our Proposal Number P61197461, dated September 23, 2019. We understand that this inspection and sampling were requested due to the planned renovation of Buildings 1, 7, and 14.
Asbestos was not identified in any of the building material samples collected. Please refer to the attached report for details.
Terracon appreciates the opportunity to provide this service to Apogee Consulting Group. If you have any questions regarding this report, please contact me at (801) 545-8500.
Sincerely, Terracon Consultants, Inc.
Chase Maeser J. Rush Bowers, CIH, CSP Project Manager Senior Industrial Hygiene Consultant State of Utah Inspector Certification No. ASB-6732 Company Certification No. 289
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Project Objective
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Visual Assessment
3.2 Physical Assessment
3.3 Sample Collection
3.4 Sample Analysis
4.0 REGULATORY OVERVIEW
5.0 FINDINGS AND RECOMMENDATIONS
6.0 GENERAL COMMENTS ..4
APPENDICES
Appendix A Asbestos Inspection Sample Location Summary
Appendix B Asbestos Laboratory Analytical Report
Appendix C Photographs
Appendix D Certifications
Appendix E Asbestos Sample Location Drawing
PRE-RENOVATION ASBESTOS INSPECTION
Salt Lake City Veterans Affairs Medical Center
Buildings 1, 7, and 14
Salt Lake City, Utah 84148
1.0 INTRODUCTION
Terracon conducted a pre-renovation asbestos inspection of Buildings 1, 7, and 14 of the Salt Lake City Veterans Affairs Medical Center located at 500 Foothill Drive, Salt Lake City, Utah. The inspection was conducted on September 26, 2019, by State of Utah-certified asbestos inspectors in accordance with Terracon Proposal No. P61197461, dated September 23, 2019. Interior building components that were anticipated to be impacted by construction activities were inspected and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to inspection accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Suspect ACM samples were collected in accordance with the sampling protocols outlined in Environmental Protection Agency (EPA) regulation 40 CFR 763 Asbestos Hazard Emergency Response Act (AHERA), and the State of Utah, Division of Air Quality (DAQ), Utah Administrative Code R307-801 Asbestos Rule. Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM).
1.1 Project Objective
We understand the asbestos inspection was requested due to the planned renovation of areas of Buildings 1, 7, and 14 at the . EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP and the State of Utah Division of Air Quality (DAQ) require that potentially regulated asbestos-containing materials be identified, classified and quantified prior to planned disturbances or demolition activities. The scope of work was limited to areas that are to be impacted by construction activities as detailed by the renovation plans provided by Apogee Consulting Group.
2.0 BUILDING DESCRIPTION
The renovation area consists of the soiled linen room in Building 1, the laundry room and mechanical room of Building 7, and the linen room in Building 14. Interior finishes consists of acoustical ceiling tiles, carpet, vinyl sheet flooring, rubberized flooring, vinyl floor tile, block filler, gypsum wallboard, plaster, covebase, fireproofing, and duct sealants. At the time of the inspection Terracon was requested to not sample the roof in order to retain the warranty.
Limited Asbestos Inspection Expanded Linen Distribution Center Salt Lake City, Utah October 18, 2019 Terracon No. 61197461
Responsive Resourceful Reliable 2
3.0 FIELD ACTIVITIES
The inspection was conducted by Roy McDonald and Chase Maeser, both State of Utah-certified asbestos inspectors. Copies of Mr. McDonalds asbestos inspector certification cards are attached in Appendix D. The inspection was conducted in accordance with the sample collection protocols established in EPA regulation 40 CFR 763, AHERA. A summary of inspection activities is provided below.
3.1 Visual Assessment
Our inspection activities began with visual observation of the interior of the structure to identify homogeneous areas of suspect ACM in the path of construction. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture, and date of application.
Interior assessment was conducted throughout visually accessible areas of the building, excluding the roof. Building materials identified as glass, wood, metal, or rubber were not considered suspect ACM and were not sampled during this inspection.
3.2 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM were collected in accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. The inspector collected bulk samples using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Terracon collected 93 bulk samples from 30 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the inspection is included as Appendix A.
3.4 Sample Analysis
Samples of suspect ACM were delivered under standard chain-of-custody protocol to EMLab P&K (NVLAP #500031-0) in Phoenix, Arizona, for analysis by PLM, using EPA Method 600/R-93/116.
The percentage of asbestos, where applicable, was determined by microscopic visual estimation.
October 18, 2019 Terracon No. 61197461
Responsive Resourceful Reliable 3
4.0 REGULATORY OVERVIEW
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to demolition or renovation activity. Under NESHAP, asbestos-containing building materials are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I non-friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than 1% asbestos. Category II non-friable ACM are any materials other than Category I materials that contain more than 1% asbestos.
Friable ACM, Category I and Category II non-friable ACM that is in poor condition and has become friable or which will be subjected to drilling, sanding, grinding, cutting or abrading and that could be crushed or pulverized during anticipated renovation or demolition activities are considered regulated ACM (RACM). In the State of Utah, asbestos activities are regulated by the Utah Department of Environmental Quality (UDEQ), Utah Division of Air Quality (UDAQ) under Administrative Code R307-801 Asbestos Rule. R307-801 requires that any asbestos-related activities conducted in the State of Utah, where more than three square feet or three linear feet of RACM will be disturbed, be conducted by personnel certified by the UDAQ. RACM must be removed prior to renovation or demolition activities that will disturb the materials. If the amount of RACM exceeds 260 linear feet (lf) of pipe insulation, more than 160 square feet (ft2) on other building components, or will generate more than one 55-gallon drum of waste, the owner or operator must provide the UDAQ with written notification of planned removal activities at least 10 working days prior to the commencement of asbestos abatement activities. Removal of RACM must be conducted by a State of Utah-certified asbestos abatement contractor. Management Plans developed for the in-place management of asbestos-containing materials in AHERA-regulated facilities must be developed by a UDAQ-certified Management Planner.
The Occupational Safety and Health Administration (OSHA) Asbestos Standard for Construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc). The OSHA standard classifies construction and maintenance activities that could disturb ACM, and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also establishes requirements for handling materials containing less than or equal to 1% asbestos. The State of Utah Division of Occupational Safety and Health has adopted the Federal OSHA regulations by reference.
5.0 FINDINGS AND RECOMMENDATIONS
Asbestos was not identified in any of the samples collected and analyzed. A sample summary is presented in Appendix A. Laboratory analytical results are presented in Appendix B.
October 18, 2019 Terracon No. 61197461
Responsive Resourceful Reliable 4
During the inspection Terracon was requested to not sample the roof in order to maintain the warranty. Since planned renovations will impact the roof this material should be assumed to contain asbestos or sampled to determine asbestos content prior to any work that may disturb it.
UL-Rated fire doors and door frames were observed in the renovation areas. Fire doors and door frames were not sampled to maintain their fire-rating. These materials should be assumed to contain asbestos or sampled to determine asbestos content prior to any work that may disturb it.
6.0 GENERAL COMMENTS
This pre-renovation asbestos inspection was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our inspection of the building. The information contained in this report is relevant to the date on which this inspection was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Apogee Consulting Group for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
APPENDIX A
ASBESTOS SURVEY SAMPLE LOCATION SUMMARY
Bulk Asbestos Sample Log Salt Lake City Veterans Affairs Medical Center
Salt Lake City, Utah
Homogeneous Area
Sample No.
Description Sample Location Quantity Lab
Results
Building 7
7-1-1
Green duct sealant 1st floor fuse room
200 SF
None detected 7-1-2 Basement near entry to big room 7-1-3 Basement on north duct
7-2-4 -in ceiling panel, small fissures and pinholes
Hallway across bathroom
798 SF
None detected
7-2-5 SE office 7-2-6 N end hallway
7-3-7 base and mastic
South storage
300 LF
None detected
7-3-8 South end on north hallway 7-3-9 North end hallway
7-4-10 base and mastic
SE near door
550 LF
None detected
7-4-11 NE dock 7-4-12 West main room hallway
7-5-13 Off-white sheet vinyl with blue and brown specks
North hallway NEC
7,500 SF
None detected
7-5-14 South office NEC 7-5-15 Breakroom SWC
7-6-16
Gypsum wallboard system
NE of breakroom
6,500 SF
None detected
7-6-17 West side of north hall 7-6-18 East middle hall
7-7-19 Off-floor tile square pattern with mastic
Laundry south storage door
7,500 SF
None detected
7-7-20 Laundry north wall center column 7-7-21 Receiving north wall columns
7-8-22
Carpet mastic Supervisors office NWC
300 SF
None detected 7-8-23 Supervisors office NEC
7-9-24
Plaster skim coat
Supervisors office SEC
5,500 SF
None detected
7-9-25 North wall of laundry 7-9-26 West wall of laundry 7-9-27 East wall of laundry 7-9-28 NE wall of laundry 7-9-29 NW wall of laundry 7-9-30 South storage of laundry
7-10-31
Block filler Receiving north wall
2,800 SF
None detected 7-10-32 North hallway north wall 7-10-33 Laundry SEC
7-11-34
Red fire putty Basement hallway
20 SF
None detected 7-11-35 Basement hallway 7-11-36 Pipe area
7-12-37
Green fire putty Basement hallway
15 SF
None detected 7-12-38 Basement hallway 7-12-39 Pipe area
Sample No.
Description Sample Location Quantity Lab Results
7-13-40
Gray duct sealant Basement air handler SWC
500 SF None detected 7-13-41 Basement air handler CTR 7-13-42 Basement air handler SEC
7-14-43
TSI sealed end caps Basement
100 EA None detected 7-14-44 Laundry east wall 7-14-45 Receiving south area
7-15-46
Silver steam line with mag block
Basement 215 LF None detected 7-15-47 1st floor pipe
7-15-48 1st floor pipe FD NC Fire doors None collected NQ Assumed
Building 14
14-16-49
Beige block filler Equipment storage SW
820 SF None detected 14-16-50 Equipment storage NW 14-16-51 Equipment storage NW
14-17-52
Gray cove base S. equipment room
160 LF None detected 14-17-53 W. equipment room 14-17-54 E. pharmacy
14-18-55
Red fire caulk Storage room E. wall
10 SF None detected 14-18-56 Large we room S. wall 14-18-57 Equipment E. wall
14-19-58
Green duct sealant Small wet room SWC
5 SF None detected 14-19-59 Large wet room W.
14-19-60 Large wet room middle
14-20-61
Gray spray on fire proofing
S. end equipment storage
~800 SF None detected 14-20-62 N. end equipment storage 14-20-63 N. end large wet room 14-20-64 Small wet room 14-20-65 Pharmacy storage E. wall
14-21-66
White wall insulation Large wet room SWC
220 SF None detected 14-21-67 Pharmacy storage E. wall 14-21-68 Equipment storage
14-22-69
Gypsum board wall system
Equipment storage E. wall ~150 SF None detected 14-22-70 Small wet room wall
14-22-71 Small wet room wall
14-23-72 -in ceiling panel with small fissure and pinholes
SE. pharmacy 300 SF None detected 14-23-73 W. pharmacy
14-23-74 NW. pharmacy
14-24-75 with black specks
Equipment storage entry ~20 SF None detected 14-24-76 Large wet room entry
14-24-77 Small wet room entry
14-25-78
Sealed end caps;
piping
Equipment storage 8 ea. None detected 14-25-79 Equipment storage
14-25-80 Equipment storage
Building 1
1-26-81
Block filler E. wall N. of door
750 SF None detected 1-26-82 S. wall W. end 1-26-83 W. wall N. end
Key:
SF = square feet LF = linear feet ea. = each
Sample No.
Description Sample Location Quantity Lab Results
1-27-84
Fire proofing E. end
~200 SF None detected 1-27-85 Middle 1-27-86 W. end
1-28-87
Green fire putty E. wall
10 SF None detected 1-28-88 E. wall 1-28-89 S. wall
1-29-90
Gypsum board wall system
N. wall E. of chute 100 SF None detected 1-29-91 N. wall E. of chute
1-29-92 Ceiling E. of chute 30 1-30-93 Red fire putty N. wall <1 SF None detected
APPENDIX B
ASBESTOS LABORATORY ANALYTICAL REPORTS
Approved by:
Approved Signatory Renee Luna-Trepczynski
Report for:
Chase Maeser Terracon Consultants, Inc. - Utah 6949 S. High Tech Drive, Suite 100 Midvale, UT 84047
Regarding: Project: 61197461; VA Linen Distribution Ctr
EML ID: 2264953
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 10-03-2019
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267)
EMLab ID: 2264953, Page 1 of 25Aerotech Laboratories, Inc
Eurofins EMLab P&K 1501 West Knudsen Drive, Phoenix, AZ 85027
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Total Samples Submitted: 93 Total Samples Analyzed: 93
Total Samples with Layer Asbestos Content > 1%: 0
Location: 7-1-1, Green Duct Sealant Lab ID-Version‡: 10771006-1
Sample Layers Asbestos Content Green Sealant ND
Sample Composite Homogeneity: Good
Location: 7-1-2, Green Duct Sealant Lab ID-Version‡: 10771007-1
Sample Layers Asbestos Content Green Sealant ND
Sample Composite Homogeneity: Good
Location: 7-1-3, Green Duct Sealant Lab ID-Version‡: 10771008-1
Sample Layers Asbestos Content Green Sealant ND
Sample Composite Homogeneity: Good
Location: 7-2-4, White 2'x2' Lay-In Ceiling Panel, Small Fissures and Pinholes Lab ID-Version‡: 10771009-1
Sample Layers Asbestos Content White Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 50% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 2 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-2-5, White 2'x2' Lay-In Ceiling Panel, Small Fissures and Pinholes Lab ID-Version‡: 10771010-1
Sample Layers Asbestos Content White Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 50% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 3 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-2-6, White 2'x2' Lay-In Ceiling Panel, Small Fissures and Pinholes Lab ID-Version‡: 10771011-1
Sample Layers Asbestos Content White Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 50% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Good
Location: 7-3-7, Tan 6" Cove Base Mastic Lab ID-Version‡: 10771012-1
Sample Layers Asbestos Content Tan Baseboard ND White Mastic ND
Sample Composite Homogeneity: Moderate
Location: 7-3-8, Tan 6" Cove Base Mastic Lab ID-Version‡: 10771013-1
Sample Layers Asbestos Content Tan Baseboard ND White Mastic ND
White Compound ND Sample Composite Homogeneity: Poor
Location: 7-3-9, Tan 6" Cove Base Mastic Lab ID-Version‡: 10771014-1
Sample Layers Asbestos Content Tan Baseboard ND White Mastic ND
White Compound ND Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 4 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-4-10, Blue 6" Cove Base Mastic Lab ID-Version‡: 10771015-1
Sample Layers Asbestos Content Blue Baseboard ND White Mastic ND
White Compound ND Sample Composite Homogeneity: Poor
Location: 7-4-11, Blue 6" Cove Base Mastic Lab ID-Version‡: 10771016-1
Sample Layers Asbestos Content Blue Baseboard ND White Mastic ND
Sample Composite Homogeneity: Moderate
Location: 7-4-12, Blue 6" Cove Base Mastic Lab ID-Version‡: 10771017-1
Sample Layers Asbestos Content Blue Baseboard ND White Mastic ND
Sample Composite Homogeneity: Moderate
Location: 7-5-13, Off White Sheet Vinyl with Blue and Brown Specks Lab ID-Version‡: 10771018-1
Sample Layers Asbestos Content Off-White Sheet Flooring ND
Yellow Mastic ND Gray Cementitious Material ND
Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 5 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-5-14, Off White Sheet Vinyl with Blue and Brown Specks Lab ID-Version‡: 10771019-1
Sample Layers Asbestos Content Off-White Sheet Flooring ND
Green Mastic ND White Compound ND
Sample Composite Homogeneity: Poor
Location: 7-5-15, Off White Sheet Vinyl with Blue and Brown Specks Lab ID-Version‡: 10771020-1
Sample Layers Asbestos Content Off-White Sheet Flooring ND
Yellow Mastic with White Paint ND Sample Composite Homogeneity: Moderate
Location: 7-6-16, Gypsum Wallboard System Lab ID-Version‡: 10771021-1
Sample Layers Asbestos Content White Compound with White Paint ND
Cream Tape ND White Joint Compound ND
White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor
Location: 7-6-17, Gypsum Wallboard System Lab ID-Version‡: 10771022-1
Sample Layers Asbestos Content White Compound with Gray Paint ND
Cream Tape ND White Joint Compound ND
White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 6 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-6-18, Gypsum Wallboard System Lab ID-Version‡: 10771023-1
Sample Layers Asbestos Content White Compound with Gray Paint ND
Cream Tape ND White Joint Compound ND
White Drywall with Brown Paper ND Composite Non-Asbestos Content: 15% Cellulose Sample Composite Homogeneity: Poor
Location: 7-7-19, Off White 2'x2' Rubber Floor Tile Square Pattern Mastic Lab ID-Version‡: 10771024-1
Sample Layers Asbestos Content Off-White Floor Tile ND
Yellow Mastic ND Sample Composite Homogeneity: Moderate
Location: 7-7-20, Off White 2'x2' Rubber Floor Tile Square Pattern Mastic Lab ID-Version‡: 10771025-1
Sample Layers Asbestos Content Off-White Floor Tile ND
Yellow Mastic ND Sample Composite Homogeneity: Moderate
Location: 7-7-21, Off White 2'x2' Rubber Floor Tile Square Pattern Mastic Lab ID-Version‡: 10771026-1
Sample Layers Asbestos Content Off-White Floor Tile ND
Yellow Mastic ND Gray Cementitious Material ND
Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 7 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-8-22, Carpet Mastic Lab ID-Version‡: 10771027-1
Sample Layers Asbestos Content Multicolored Carpet ND
Yellow Mastic ND Composite Non-Asbestos Content: 35% Synthetic Fibers Sample Composite Homogeneity: Moderate
Location: 7-8-23, Carpet Mastic Lab ID-Version‡: 10771028-1
Sample Layers Asbestos Content Multicolored Carpet ND
Yellow Mastic ND Composite Non-Asbestos Content: 35% Synthetic Fibers Sample Composite Homogeneity: Moderate
Location: 7-9-24, Plaster Skim Coat Lab ID-Version‡: 10771029-1
Sample Layers Asbestos Content White Skim Coat with Cream Paint ND
Sample Composite Homogeneity: Good
Location: 7-9-25, Plaster Skim Coat Lab ID-Version‡: 10771030-1
Sample Layers Asbestos Content White Skim Coat with Multilayered Paint ND
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 8 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-9-26, Plaster Skim Coat Lab ID-Version‡: 10771031-1
Sample Layers Asbestos Content White Skim Coat with Multilayered Paint ND
Sample Composite Homogeneity: Good
Location: 7-9-27, Plaster Skim Coat Lab ID-Version‡: 10771032-1
Sample Layers Asbestos Content White Skim Coat with Multilayered Paint ND
Sample Composite Homogeneity: Good
Location: 7-9-28, Plaster Skim Coat Lab ID-Version‡: 10771033-1
Sample Layers Asbestos Content White Drywall with Brown Paper and Multilayered Paint ND
Composite Non-Asbestos Content: 10% Cellulose Sample Composite Homogeneity: Good
Location: 7-9-29, Plaster Skim Coat Lab ID-Version‡: 10771034-1
Sample Layers Asbestos Content White Drywall with Brown Paper and Multilayered Paint ND
Composite Non-Asbestos Content: 10% Cellulose Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 9 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-9-30, Plaster Skim Coat Lab ID-Version‡: 10771035-1
Sample Layers Asbestos Content White Skim Coat with Multilayered Paint ND
Sample Composite Homogeneity: Good
Location: 7-10-31, Block Filler Lab ID-Version‡: 10771036-1
Sample Layers Asbestos Content White Paint and Filler ND
Gray Block ND Sample Composite Homogeneity: Moderate
Location: 7-10-32, Block Filler Lab ID-Version‡: 10771037-1
Sample Layers Asbestos Content White Paint and Filler ND
Gray Block ND Sample Composite Homogeneity: Moderate
Location: 7-10-33, Block Filler Lab ID-Version‡: 10771038-1
Sample Layers Asbestos Content Multicolored Paint with White Filler ND
Tan Cementitious Material ND Gray Mortar ND Gray Block ND Composite Non-Asbestos Content: < 1% Cellulose
< 1% Glass Fibers Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 10 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-11-34, Red Fire Putty Lab ID-Version‡: 10771039-1
Sample Layers Asbestos Content Red Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: 7-11-35, Red Fire Putty Lab ID-Version‡: 10771040-1
Sample Layers Asbestos Content Red Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: 7-11-36, Red Fire Putty Lab ID-Version‡: 10771041-1
Sample Layers Asbestos Content Red Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: 7-12-37, Green Fire Putty Lab ID-Version‡: 10771042-1
Sample Layers Asbestos Content Green Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 11 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-12-38, Green Fire Putty Lab ID-Version‡: 10771043-1
Sample Layers Asbestos Content Green Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: 7-12-39, Green Fire Putty Lab ID-Version‡: 10771044-1
Sample Layers Asbestos Content Green Putty ND Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: 7-13-40, Gray Duct Sealant Lab ID-Version‡: 10771045-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 7-13-41, Gray Duct Sealant Lab ID-Version‡: 10771046-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 12 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-13-42, Gray Duct Sealant Lab ID-Version‡: 10771047-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 7-14-43, TSI Sealed End Caps Lab ID-Version‡: 10771048-1
Sample Layers Asbestos Content White Sealant ND
Yellow Insulation ND Composite Non-Asbestos Content: 30% Glass Fibers
3% Cellulose Sample Composite Homogeneity: Moderate
Location: 7-14-44, TSI Sealed End Caps Lab ID-Version‡: 10771049-1
Sample Layers Asbestos Content White Sealant ND
Yellow Insulation ND Composite Non-Asbestos Content: 60% Glass Fibers
2% Cellulose Sample Composite Homogeneity: Moderate
Location: 7-14-45, TSI Sealed End Caps Lab ID-Version‡: 10771050-1
Sample Layers Asbestos Content White Sealant ND
Yellow Insulation ND Composite Non-Asbestos Content: 60% Glass Fibers
2% Cellulose Sample Composite Homogeneity: Moderate
EMLab ID: 2264953, Page 13 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 7-15-46, Silver Steamline W/ Mag Block Lab ID-Version‡: 10771051-1
Sample Layers Asbestos Content Off-White Powdery Material ND
Composite Non-Asbestos Content: 3% Cellulose < 1% Glass Fibers < 1% Synthetic Fibers
Sample Composite Homogeneity: Good
Location: 7-15-47, Silver Steamline W/ Mag Block Lab ID-Version‡: 10771052-1
Sample Layers Asbestos Content Off-White Powdery Material ND
Composite Non-Asbestos Content: 3% Cellulose < 1% Glass Fibers < 1% Synthetic Fibers
Sample Composite Homogeneity: Good
Location: 7-15-48, Silver Steamline W/ Mag Block Lab ID-Version‡: 10771053-1
Sample Layers Asbestos Content Off-White Powdery Material ND
Composite Non-Asbestos Content: 3% Cellulose < 1% Glass Fibers < 1% Synthetic Fibers
Sample Composite Homogeneity: Good
Location: 14-16-49, Beige Block Filler Lab ID-Version‡: 10771054-1
Sample Layers Asbestos Content Gray Block with Beige Paint ND
White Compound ND White Drywall with Brown Paper ND
Composite Non-Asbestos Content: 2% Cellulose Sample Composite Homogeneity: Poor
EMLab ID: 2264953, Page 14 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 14-16-50, Beige Block Filler Lab ID-Version‡: 10771055-1
Sample Layers Asbestos Content Gray Block with Beige Paint ND
Sample Composite Homogeneity: Good
Location: 14-16-51, Beige Block Filler Lab ID-Version‡: 10771056-1
Sample Layers Asbestos Content Gray Block with Beige Paint ND
Sample Composite Homogeneity: Good
Location: 14-17-52, Gray Cove Base Lab ID-Version‡: 10771057-1
Sample Layers Asbestos Content Gray Baseboard ND Yellow Mastic ND Brown Mastic ND
Sample Composite Homogeneity: Poor
Location: 14-17-53, Gray Cove Base Lab ID-Version‡: 10771058-1
Sample Layers Asbestos Content Gray Baseboard ND Brown Mastic ND
Sample Composite Homogeneity: Moderate
EMLab ID: 2264953, Page 15 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 14-17-54, Gray Cove Base Lab ID-Version‡: 10771059-1
Sample Layers Asbestos Content Gray Baseboard ND Brown Mastic ND
Sample Composite Homogeneity: Moderate
Location: 14-18-55, Red Fire Caulk Lab ID-Version‡: 10771060-1
Sample Layers Asbestos Content Red Caulk ND
Sample Composite Homogeneity: Good
Location: 14-18-56, Red Fire Caulk Lab ID-Version‡: 10771061-1
Sample Layers Asbestos Content Red Caulk ND Composite Non-Asbestos Content: < 1% Glass Fibers Sample Composite Homogeneity: Good
Location: 14-18-57, Red Fire Caulk Lab ID-Version‡: 10771062-1
Sample Layers Asbestos Content Red Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 16 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(800) 651-4802 Fax (623) 780-7695 www.emlab.com Client: Terracon Consultants, Inc. - Utah C/O: Chase Maeser Re: 61197461; VA Linen Distribution Ctr
Date of Receipt: 09-30-2019 Date of Report: 10-03-2019
ASBESTOS PLM REPORT
Location: 14-19-58, Green Duct Sealant Lab ID-Version‡: 10771063-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 14-19-59, Green Duct Sealant Lab ID-Version‡: 10771064-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 14-19-60, Green Duct Sealant Lab ID-Version‡: 10771065-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 14-20-61, Spray on Fireproofing Gray Lab ID-Version‡: 10771066-1
Sample Layers Asbestos Content Gray Fireproofing ND
Composite Non-Asbestos Content: 20% Glass Fibers < 1% Cellulose
Sample Composite Homogeneity: Good
EMLab ID: 2264953, Page 17 of 25Aerotech Laboratories, Inc
The test report shall not be reproduced except in full, without written approval of the laboratory.