Attachment F_P1360 DWG_Part 11 of 12.pdf

PDF 10 MB Posted

Attached to
P1360: Joint Maritime Facility, Newfoundland, Canada
Solicitation number
N6247026R0011
Issued by

About this file

This document is a set of electrical design drawings and panelboard schedules for a Joint Maritime Facility under the Naval Facilities Engineering Systems Command - Atlantic. The drawings include detailed electrical panelboard schedules (EP603-EP607), grounding and bonding plans (EG101), lightning protection system plans (EG102, EG201-EG202), lightning protection details (EG501-EG502), telecommunications infrastructure plans (TN101, TN401, TN501, TN601), and specifications for installations.

The electrical infrastructure includes multiple panelboards serving various loads: Panelboard ML112 (225A, 208Y/120V, 3-phase), Panelboard MH112 (100A, 208Y/120V), Panelboard ML112A (100A, 208Y/120V), and multiple Power Distribution Units (PDU-1A, PDU-1B, PDU-2A, PDU-2B, PDU-AB) rated at 400A, 208Y/120V, 3-phase. Key systems include HVAC units (DOAS-1, CRAH units, CHWP), electrical heating units (EUH-1 through EUH-10), and equipment racks for mission configuration and communications equipment. The facility incorporates a comprehensive grounding system with copper counterpoise, signal reference equipotential ground planes embedded in concrete floors, and lightning protection systems with air terminals, down conductors, and ground terminations conforming to NFPA 780 and CAN/CSA standards. Telecommunications infrastructure includes overhead and underfloor cable trays, fiber optic and Category 6 UTP cabling to workstations, network printers, and equipment cabinets in communications and operations rooms, with detailed outlet configurations and grounding connections to secondary bonding busbars.

View the file

Other files

File Type Posted
N6247026R00110005 SF 30.pdf PDF
Solicitation Amendment N6247026R00110005 SF 30.pdf PDF
AMENDMENT 0005.pdf PDF
Attachment K _Moll Point Joint Maritime Facility NL Tech Memo.pdf PDF
Attachment J _ Hazardous Materials Report_2024_Appendix D of SEI.pdf PDF
P1360-Drawings- Amendment 0005.pdf PDF
N6247026R0011 Amendment 0004.pdf PDF
N6247026R0011 Amendment 0003.pdf PDF
Amendment 0003 Revised P1360 Demo-DWGS.pdf PDF
P1360 Site Visit Attendance Log.pdf PDF
AMENDMENT 0003.pdf PDF
Amendment 0003 Revised P1360 DWGS.pdf PDF
Amendment 0003 Revised P1360 Specifications.pdf PDF
Amendment N6247026R0008 0005.pdf PDF
Solicitation Amendment N6247026R0011 (0002).pdf PDF
Solicitation Amendment N6247026R00110001 (0001).pdf PDF
Solicitation - N6247026R0011.pdf PDF
Attachment E_P1360 SPECS_Part 3 of 5.pdf PDF
Attachment E_P1360 SPECS_Part 2 of 5.pdf PDF
Attachment F_P1360 DWG_Part 10 of 12.pdf PDF
Attachment D - Schedule B Price Proposal Form.pdf PDF
Attachment G - Representations and Certifications.pdf PDF
Attachment F_P1360 DWG_Part 8 of 12.pdf PDF
Attachment A - Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment B - Construction Experience Project Data Sheet.pdf PDF
Attachment F_P1360 DWG_Part 6 of 12.pdf PDF
Attachment E_P1360 SPECS_Part 5 of 5.pdf PDF
Attachment F_P1360 DWG_Part 4 of 12.pdf PDF
Attachment E_P1360 SPECS_Part 4 of 5.pdf PDF
Attachment F_P1360 DWG_Part 3 of 12.pdf PDF
Attachment F_P1360 DWG_Part 7 of 12.pdf PDF
Attachment F_P1360 DWG_Part 1 of 12.pdf PDF
Attachment F_P1360 DWG_Part 2 of 12.pdf PDF
Attachment C - Past Performance Questionnaire (PPQ).pdf PDF
Attachment F_P1360 DWG_Part 5 of 12.pdf PDF
Attachment F_P1360 DWG_Part 9 of 12.pdf PDF
Attachment F_P1360 DWG_Part 12 of 12.pdf PDF
Attachment E_P1360 SPECS_Part 1 of 5.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EP603

EL

EC

TR

IC

AL

P

AN

EL

BO

AR

D

SC

HE

DU

LE

S

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

600A MCB, 480Y/277V, 3 PHASE, 4 WIRE, 14 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

ACCH-1 107 150 2 1 2 2 150 - ACCH-2

107 - 1

107 -

ACCH-3 107 150 2 7 8 4 80 69 DOAS-1

107 69 107 69

CRAH-1 56 75 4 13 14 4 75 56 CRAH-2

56 56

56 56

CRAH-3 1 - 75 4 19 20 4 75 56 CRAH-4

- - 56

- - 56

DWH-1 4 15 12 25 26 12 15 - CHWP-2

4 - 1 4 -

CHWP-1 5 15 12 31 32 - SPACE ONLY

5 -

5 -

PANEL ML112 VIA XFMR TM1 64 125 1 37 38 - SPACE ONLY

58 - 59 -

TOTAL 343 337 338 181 181 181 TOTAL

TOTAL CONNECTED AMPSA: 524 B: 518 C: 519

PANELBOARD MH112 SCHEDULE

225A MCB, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

EUH-1 10 20 12 1 2 12 20 10 EUH-2

10 10

EUH-3 10 20 12 5 6 12 20 10 EUH-4

10 10

EUH-5 10 20 12 9 10 12 20 10 EUH-6

10 10

EUH-7 10 20 12 13 14 12 20 10 EUH-8

10 10

EUH-9 10 20 12 17 18 12 20 7 EUH-10

10 7

EF-3 6 15 12 21 22 12 20 2 EF-1/EF-2

EF-4 6 15 12 23 24 12 20 4 EF-5,6,7,8

HEAT TRACE 5 20 12 25 26 12 20 2 EYEWASH HORN/STROBE

RP-1 1 15 12 27 28 12 20 2 F.O. CONTROL PANEL

WASTEWATER TANK ALARM 2 20 10 29 30 12 20 4 F.O. OVERFLOW PUMP

SPARE 0 20 31 32 12 20 2 F.O. TRANSFER PUMP

SPARE 0 20 33 34 12 20 3 F.O. POLISHING UNIT

SPARE 0 20 35 36 12 20 8 RECEPTS RM 112

PANEL ML112A 62 100 2 37 38 12 20 5 RECEPTS RM 113,114

62 40 12 20 5 RECEPTS RM 115

56 42 20 0 SPARE

TOTAL 107 99 94 46 42 43 TOTAL

TOTAL CONNECTED AMPSA: 153 B: 141 C: 137

PANELBOARD ML112 SCHEDULE

100A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

FCU-1 2.4 15 12 1 2 12 15 2.4 FCU-2

2.4 2.4

2.4 2.4

FCU-3 2.4 15 12 7 8 12 20 11 FCU-4

2.4 11

2.4 11

FCU-5 11 20 12 13 14 12 20 11 FCU-6

11 11

11 11

FCU-7 11 20 12 19 20 12 15 4.6 FCU-8

11 4.6 11 4.6

EUH-11 7 20 25 26 20 0 SPARE

7 28 20 0 SPARE

SPARE 0 20 29 30 20 0 SPARE

SPACE ONLY - 31 32 - SPACE ONLY

SPACE ONLY - 33 34 - SPACE ONLY

SPACE ONLY - 35 36 - SPACE ONLY

SPACE ONLY - 37 38 - SPACE ONLY

SPACE ONLY - 39 40 - SPACE ONLY

SPACE ONLY - 41 42 - SPACE ONLY

TOTAL 33 33 27 29 29 29 TOTAL

TOTAL CONNECTED AMPSA: 62 B: 62 C: 56

PANELBOARD ML112A SCHEDULE

PANELBOARD NOTES:

1 LOAD IS SHOWN DELETED TO ACCOUNT FOR REDUNDANCY OF SIMILAR LOAD CONNECTED.

LOAD WILL NOT BE CONNECTED AT SAME TIME OF OTHER LOADS.

EP604

PD

U-

1A P

AN

EL

BO

AR

D

SC

HE

DU

LE

S

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-1 - INPUT A 25 40 1 2 40 25 PFE-1 - INPUT A

25 25

25 25

PFE-1 - INPUT A 25 40 7 8 40 25 PFE-1 - INPUT A

25 25 25 25

PFE-1 - INPUT A 25 40 13 14 40 25 PFE-1 - INPUT A

25 25

25 25

PFE-1 - INPUT A 25 40 19 20 40 25 PFE-1 - INPUT A

25 25 25 25

PFE-1 - INPUT A 25 40 25 26 40 25 PFE-1 - INPUT A

25 25

25 25

PFE-1 - INPUT A 25 40 31 32 40 25 PFE-1 - INPUT A

25 25 25 25

PFE-1 - INPUT A 25 40 37 38 40 25 PFE-1 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1A TECH POWER A TO PFE-1 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-2 - INPUT A 25 40 1 2 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 7 8 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 13 14 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 19 20 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 25 26 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 31 32 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 37 38 40 25 PFE-2 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1A TECH POWER A TO PFE-2 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-3 - INPUT A 25 40 1 2 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 7 8 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 13 14 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 19 20 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 25 26 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 31 32 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 37 38 40 25 PFE-3 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1A TECH POWER A TO PFE-3 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

EP605

U-

2A A

ND

P

DU

-A

B

PA

NE

LB

OA

RD

S

CH

ED

UL

ES

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-4 - INPUT A 25 40 1 2 40 25 PFE-4 - INPUT A

25 25

25 25

PFE-4 - INPUT A 25 40 7 8 40 25 PFE-4 - INPUT A

25 25 25 25

PFE-4 - INPUT A 25 40 13 14 40 25 PFE-4 - INPUT A

25 25

25 25

PFE-4 - INPUT A 25 40 19 20 40 25 PFE-4 - INPUT A

25 25 25 25

PFE-4 - INPUT A 25 40 25 26 40 25 PFE-4 - INPUT A

25 25

25 25

PFE-4 - INPUT A 25 40 31 32 40 25 PFE-4 - INPUT A

25 25 25 25

PFE-4 - INPUT A 25 40 37 38 40 25 PFE-4 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-2A TECH POWER A TO PFE-4 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

MISSION CONFIG - INPUT A 25 40 1 2 40 25 PFE-1 - INPUT A

25 25

25 25

MISSION CONFIG - INPUT A 25 40 7 8 40 25 PFE-1 - INPUT A

25 25 25 25

MISSION CONFIG - INPUT A 25 40 13 14 40 25 PFE-1 - INPUT A

25 25

25 25

PFE-1 - INPUT A 25 40 19 20 40 25 PFE-1 - INPUT A

25 25 25 25

PFE-1 - INPUT A 25 40 25 26 40 25 PFE-1 - INPUT A

25 25

25 25

PFE-1 - INPUT A 25 40 31 32 40 25 PFE-1 - INPUT A

25 25 25 25

PFE-1 - INPUT A 25 40 37 38 40 25 PFE-1 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 0 B: 0 C: 0

PDU-2A TECH POWER A TO MISSION CONFIG EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

225A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

COMMS EQUIPMENT 20 30 1 2 30 20 COMMS EQUIPMENT

20 20

COMMS EQUIPMENT 20 5 6 30 20 COMMS EQUPMENT

20 30 20

COMMS EQUIPMENT 20 9 10 30 20 COMMS EQUIPMENT

20 20

COMMS EQUIPMENT 20 30 13 14 30 20 COMMS EQUIPMENT

20 20

COMMS EQUIPMENT 20 17 18 30 20 COMMS EQUIPMENT

20 30 20

SPACE ONLY 0 - 21 22 - 0 SPACE ONLY

0 0

SPACE ONLY 0 - 25 26 - 0 SPACE ONLY

0 0

SPACE ONLY 0 - 29 30 - 0 SPACE ONLY

0 0

SPACE ONLY 0 - 33 34 - 0 SPACE ONLY

0 0

RECEPTS RM 116 8 20 12 37 38 - 0 SPACE ONLY

RECEPTS RM 116 8 20 12 39 40 - 0 SPACE ONLY

SPACE ONLY 0 - 41 42 - 0 SPACE ONLY

TOTAL 88 88 80 80 80 80 TOTAL

TOTAL CONNECTED AMPSA: 168 B:168C: 160

PDU-AB TECH POWER TO COMMS EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

225A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

MISSION RACKS 10 30 1 2 30 10 MISSION RACKS

10 10

10 10

MISSION RACKS 10 30 7 8 30 10 MISSION RACKS

10 10 10 10

MISSION RACKS 7 30 13 14 30 7 MISSION RACKS

MISSION RACKS 7 30 15 16 30 7 MISSION RACKS

MISSION RACKS 7 30 17 18 30 7 MISSION RACKS

SPACE ONLY 0 - 19 20 - 0 SPACE ONLY

0 0 0 0

SPACE ONLY 0 - 25 26 - 0 SPACE ONLY

0 0

0 0

SPACE ONLY 0 - 31 32 - 0 SPACE ONLY

0 0 0 0

SPACE ONLY 0 - 37 38 - 0 SPACE ONLY

0 0

0 0

TOTAL 27 27 27 27 27 27 TOTAL

TOTAL CONNECTED AMPSA: 54 B: 54C: 54

PDU-AB TECH POWER TO MISSION EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

EP606

U-

1B P

AN

EL

BO

AR

D

SC

HE

DU

LE

S

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-1 - INPUT B 25 40 1 2 40 25 PFE-1 - INPUT B

25 25

25 25

PFE-1 - INPUT B 25 40 7 8 40 25 PFE-1 - INPUT B

25 25 25 25

PFE-1 - INPUT B 25 40 13 14 40 25 PFE-1 - INPUT B

25 25

25 25

PFE-1 - INPUT B 25 40 19 20 40 25 PFE-1 - INPUT B

25 25 25 25

PFE-1 - INPUT B 25 40 25 26 40 25 PFE-1 - INPUT B

25 25

25 25

PFE-1 - INPUT B 25 40 31 32 40 25 PFE-1 - INPUT B

25 25 25 25

PFE-1 - INPUT B 25 40 37 38 40 25 PFE-1 - INPUT B

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1B TECH POWER B TO PFE-1 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-2 - INPUT A 25 40 1 2 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 7 8 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 13 14 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 19 20 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 25 26 40 25 PFE-2 - INPUT A

25 25

25 25

PFE-2 - INPUT A 25 40 31 32 40 25 PFE-2 - INPUT A

25 25 25 25

PFE-2 - INPUT A 25 40 37 38 40 25 PFE-2 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1B TECH POWER B TO PFE-2 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-3 - INPUT A 25 40 1 2 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 7 8 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 13 14 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 19 20 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 25 26 40 25 PFE-3 - INPUT A

25 25

25 25

PFE-3 - INPUT A 25 40 31 32 40 25 PFE-3 - INPUT A

25 25 25 25

PFE-3 - INPUT A 25 40 37 38 40 25 PFE-3 - INPUT A

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-1B TECH POWER B TO PFE-3 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

EP607

U-

2B A

ND

G

L1

P

AN

EL

BO

AR

D

SC

HE

DU

LE

S

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

PFE-4 - INPUT B 25 40 1 2 40 25 PFE-4 - INPUT B

25 25

25 25

PFE-4 - INPUT B 25 40 7 8 40 25 PFE-4 - INPUT B

25 25 25 25

PFE-4 - INPUT B 25 40 13 14 40 25 PFE-4 - INPUT B

25 25

25 25

PFE-4 - INPUT B 25 40 19 20 40 25 PFE-4 - INPUT B

25 25 25 25

PFE-4 - INPUT B 25 40 25 26 40 25 PFE-4 - INPUT B

25 25

25 25

PFE-4 - INPUT B 25 40 31 32 40 25 PFE-4 - INPUT B

25 25 25 25

PFE-4 - INPUT B 25 40 37 38 40 25 PFE-4 - INPUT B

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-2B TECH POWER B TO PFE-4 EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

400A MLO, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

MISSION CONFIG - INPUT B 25 40 1 2 40 25 MISSION CONFIG - INPUT B

25 25

25 25

MISSION CONFIG - INPUT B 25 40 7 8 40 25 MISSION CONFIG - INPUT B

25 25 25 25

MISSION CONFIG - INPUT B 25 40 13 14 40 25 MISSION CONFIG - INPUT B

25 25

25 25

MISSION CONFIG - INPUT B 25 40 19 20 40 25 MISSION CONFIG - INPUT B

25 25 25 25

MISSION CONFIG - INPUT B 25 40 25 26 40 25 MISSION CONFIG - INPUT B

25 25

25 25

MISSION CONFIG - INPUT B 25 40 31 32 40 25 MISSION CONFIG - INPUT B

25 25 25 25

MISSION CONFIG - INPUT B 25 40 37 38 40 25 MISSION CONFIG - INPUT B

25 25

25 25

TOTAL 175 175 175 175 175 175 TOTAL

TOTAL CONNECTED AMPSA: 350 B: 350 C: 350

PDU-2B TECH POWER B TO MISSION CONFIG EQUIPMENT

NOTE: LOADS IN AMPERES SHOWN ARE APPROXIMATE FOR EQUIPMENT SIZING PURPOSE ONLY. EQUIPMENT CIRCUITS FROM LOAD SIDE OF CIRCUIT BREAKER

PROVIDED BY OTHERS.

60A MCB, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED

LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED

A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C

GENERATOR AUX. LOADS 5 20 12 1 2 12 20 5 GENERATOR AUX. LOADS

GENERATOR AUX. LOADS 5 20 12 3 4 12 20 5 GENERATOR AUX. LOADS

GENERATOR AUX. LOADS 5 20 12 5 6 12 20 5 GENERATOR AUX. LOADS

SPARE 0 20 7 8 20 0 SPARE

SPARE 0 20 9 10 20 0 SPARE

SPARE 0 20 11 12 20 0 SPARE

SPACE ONLY 0 - 13 14 - 0 SPACE ONLY

SPACE ONLY 0 - 15 16 - 0 SPACE ONLY

SPACE ONLY 0 - 17 18 - 0 SPACE ONLY

TOTAL 5 5 5 5 5 5 TOTAL

TOTAL CONNECTED AMPSA: 10 B: 10 C: 10

PANELBOARD GL115 SCHEDULE

1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE

CANADIAN ELECTRICAL CODE (CAN/CSA C22.x), AS WELL AS ADDITIONAL

REQUIREMENTS LISTED IN THE SPECIFICATIONS.

2. SEE LIGHTNING PROTECTION SYSTEM ROOF PLAN ON SHEET EG102 FOR

ADDITIONAL LPS, GROUNDING, AND BONDING COORDINATION.

3. THIS PLAN IS PROVIDED TO DEPICT AN OVERALL VIEW OF THE EXTENT OF

THE FACILITY GROUNDING AND BONDING REQUIREMENTS. IT IS NOT

INTENDED TO INDICATE EVERY REQUIREMENT FOR GROUNDING AND

BONDING OF ELECTRICAL AND TELECOMMUNICATIONS SYSTEMS PER THE

LOCAL CODES AND STANDARDS.

1. GROUNDING COUNTERPOISE TEST WELL/HAND HOLE, TYPICAL.

2. LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR FROM ROOF,

TYPICAL. SEE SHEET EG102 LIGHTNING PROTECTION SYSTEM PLAN.

3. DIRECT-BURIED #4/0 BARE COPPER GROUNDING COUNTERPOISE.

4. SIGNAL REFERENCE EQUIPOTENTIAL GROUND PLANE - PROVIDE 100mm X 100mm GRID OF COPPER-CLAD STEEL MESH EMBEDDED IN CONCRETE

SLAB THROUGHOUT ENTIRE FOOTPRINT OF THIS ROOM.

5. PROVIDE SIGNAL REFERENCE GROUND LUG FLUSH IN CONCRETE FLOOR,

CONNECTED TO EMBEDDED GROUND MESH. GROUND ALL

TELECOMMUNICATION EQUIPMENT THIS ROOM TO GROUND LUGS USING

SHORTEST PATH POSSIBLE.

6. PROVIDE CONNECTION FROM EACH INCOMING CABLE ENCLOSURE TO

NEAREST TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

7. ELECTRICAL SERVICE PAD-MOUNT TRANSFORMER. SEE DETAIL ON ES501

FOR GROUNDING REQUIREMENTS.

GRAPHIC SCALE

SHEET KEYNOTES

GENERAL SHEET NOTES

EG101

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE:

ELECTRICAL GROUNDING PLAN

1:100

GC

GC

GC

GC

GC

PBB

SBB

SBB

SB

B

SB

B

ME

GB

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G T

G T

G T

G T

G

GG

G

GG

SEGB

SE

GB

SE

GB

T

SEGB

SEGB

SE

GB

GC

GC GC

GCGC

EG

C

EGC

EGC

EG

C

EGC

EGCEGC

EGC

EG

C

EGC

EG

C

EG

C

EG

C

EG

C

EGC

EGC

EGC

EGC

EGC

EG

C

EGCEGC

EGC

EGC

G

T

T

SE

GB

EGC

107108

LR118

T110

LR109

ML112

MH112

ML112A

L118

B1

A1

TP1

TM1

GL115

1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE

CANADIAN INSTALLATION CODE FOR LIGHTNING PROTECTION SYSTEMS

(CAN/CSA B72), AS WELL AS ADDITIONAL REQUIREMENTS LISTED IN THE

SPECIFICATIONS.

2. SEE EXTERIOR LPS ELEVATIONS ON SHEETS EG201 AND EG202 FOR

ADDITIONAL EXTERIOR VIEWS OF LIGHTNING PROTECTION SYSTEM.

1. LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR. SEE SHEET EG101

ELECTRICAL GROUNDING PLAN FOR CONTINUATION.

2. ROOF-MOUNTED LIGHTNING PROTECTION SYSTEM AIR TERMINAL, TYPICAL.

3. LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR, TYPICAL.

GRAPHIC SCALE

SHEET KEYNOTES

GENERAL SHEET NOTES

EG102

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE:

LIGHTNING PROTECTION SYSTEM ROOF PLAN

1:100

LRC

LR

C

LRCLRC

LR

C

LR

C

LR

C

LR

C

LR

C

LR

C

LR

C

LPCLPCLPC

LRC

LRCLRCLRC

LR

C

LR

C

LR

C

LR

C

LRC

LR

C

LR

C

LRC LRCLRCLRCLRC

LR

C

LR

C

LR

C

LR

C

LR

C

LR

C

LRC

LR

C

1 1

1. LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR, TYPICAL. SEE SHEET

EG101 ELECTRICAL GROUNDING PLAN FOR CONTINUATION.

2. ROOF-MOUNTED LIGHTNING PROTECTION SYSTEM AIR TERMINAL, TYPICAL.

3. GROUND ROD, CONNECTED TO COUNTERPOISE WITH EXOTHERMIC WELD.

4. GROUND ROD WITH ACCESSIBLE TEST WELL HANDHOLE, CONNECTED TO

COUNTERPOISE WITH EXOTHERMIC WELD.

5. ROOF-MOUNTED LIGHTNING PROTECTION SYSTEM CONDUCTOR, TYPICAL.

GRAPHIC SCALE

SHEET KEYNOTES

GENERAL SHEET NOTES

EG201

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE: SOUTH ELEVATION - LIGHTNING PROTECTION SYSTEM

1:100

SCALE: NORTH ELEVATION - LIGHTNING PROTECTION SYSTEM

1:100

1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE

CANADIAN INSTALLATION CODE FOR LIGHTNING PROTECTION SYSTEMS

(CAN/CSA B72), AS WELL AS ADDITIONAL REQUIREMENTS LISTED IN THE

SPECIFICATIONS.

TT 4

T TT

2 5

GRAPHIC SCALE

SHEET KEYNOTES

GENERAL SHEET NOTES

EG202

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE: WEST ELEVATION - LIGHTNING PROTECTION SYSTEM

1:100

SCALE: EAST ELEVATION - LIGHTNING PROTECTION SYSTEM

1:100

1. LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR, TYPICAL. SEE SHEET

EG101 ELECTRICAL GROUNDING PLAN FOR CONTINUATION.

2. ROOF-MOUNTED LIGHTNING PROTECTION SYSTEM AIR TERMINAL, TYPICAL.

3. GROUND ROD, CONNECTED TO COUNTERPOISE WITH EXOTHERMIC WELD.

4. GROUND ROD WITH ACCESSIBLE TEST WELL HANDHOLE, CONNECTED TO

COUNTERPOISE WITH EXOTHERMIC WELD.

5. ROOF-MOUNTED LIGHTNING PROTECTION SYSTEM CONDUCTOR, TYPICAL.

1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE

CANADIAN INSTALLATION CODE FOR LIGHTNING PROTECTION SYSTEMS

(CAN/CSA B72), AS WELL AS ADDITIONAL REQUIREMENTS LISTED IN THE

SPECIFICATIONS.

TT 4

TT 4

EG501

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

REVISED: JUNE 2011 LIGHTNING PLATE:

NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

FASTEN COPPER CONDUCTORS WITH

COPPER CABLE LOOPS. FASTEN ALUMINUM

CONDUCTORS WITH ALUMINUM CABLE

LOOPS. LIGHTNING PROTECTION

CONDUCTORS SHALL BE FASTENED AT

INTERVALS NOT MORE THAN 915mm ON

CENTER.

MOUNT AIR TERMINAL BASE WITH (2) SELF

TAPPING STAINLESS STEEL SCREWS.

SIDE MOUNT AIR TERMINAL BASE.

AIR TERMINAL:

COPPER CLASS 1 OR 2 - AS REQUIRED

FOR SURFACES NOT COMPATIBLE WITH

COPPER:

ALUMINUM CLASS 1 OR 2 - AS REQUIRED

600mm MAX.

250mm MIN.

PARAPET AIR TERMINAL DETAIL

LP-1

ADHESIVE AIR TERMINAL BASE.

MOUNT ADHESIVE FITTINGS WITH ROOF

SYSTEM MANUFACTURER APPROVED

ADHESIVE. ALL REQUIRED SLIP SHEETS,

BATTEN STRIPS, PAVERS, AND SPECIAL

REQUIREMENTS OF THE ROOFING SYSTEM

MANUFACTURER SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR.

FASTEN COPPER CONDUCTORS WITH ADHESIVE

COPPER CABLE HOLDERS. FASTEN ALUMINUM

CONDUCTORS WITH ADHESIVE ALUMINUM

CABLE HOLDERS. LIGHTNING PROTECTION

CONDUCTORS SHALL BE FASTENED AT

INTERVALS NOT MORE THAN 915mm ON

CENTER.

MID ROOF AIR TERMINAL

AIR TERMINAL:

COPPER CLASS 1 OR 2 - AS REQUIRED

FOR SURFACES NOT COMPATIBLE WITH

COPPER:

ALUMINUM CLASS 1 OR 2 - AS REQUIRED

REVISED: JUNE 2011 LIGHTNING PLATE: LP-2

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

COPPER RIDGE AIR TERMINAL BASE.

FOR SURFACES NOT COMPATIBLE WITH COPPER

USE ALUMINUM RIDGE AIR TERMINAL BASE. MOUNT

AIR TERMINAL BASE WITH (4) SELF TAPPING

STAINLESS STEEL SCREWS.

RIDGE AIR TERMINAL DETAIL

REVISED: JUNE 2011 LIGHTNING PLATE: LP-5

AIR TERMINAL:

COPPER CLASS 1 OR 2 - AS REQUIRED

FOR SURFACES NOT COMPATIBLE WITH

COPPER:

ALUMINUM CLASS 1 OR 2 - AS REQUIRED

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

FASTEN COPPER CONDUCTORS WITH

COPPER CABLE LOOPS. FASTEN

ALUMINUM CONDUCTORS WITH ALUMINUM

CABLE LOOPS. LIGHTNING PROTECTION

CONDUCTORS SHALL BE FASTENED AT

INTERVALS NOT MORE THAN 915mm ON

CENTER.

NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

FASTEN COPPER CONDUCTORS WITH COPPER STANDING SEAM

METAL ROOF FASTENER. FASTEN ALUMINUM CONDUCTORS

WITH ALUMINUM STANDING SEAM METAL ROOF FASTENER.

LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED AT

INTERVALS NOT MORE THAN 915mm ON CENTER.

EXTRUDED COPPER STANDING SEAM METAL

ROOF AIR TERMINAL BASE. FOR SURFACES

NOT COMPATIBLE WITH COPPER USE

EXTRUDED ALUMINUM STANDING SEAM METAL

ROOF AIR TERMINAL BASE.

STANDING SEAM ROOF AIR TERMINAL DETAIL

REVISED: JUNE 2011 LIGHTNING PLATE: LP-6

NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

AIR TERMINAL:

COPPER CLASS 1 OR 2 - AS REQUIRED

FOR SURFACES NOT COMPATIBLE WITH

COPPER:

ALUMINUM CLASS 1 OR 2 - AS REQUIRED

REVISED: JUNE 2011 LIGHTNING PLATE:

STRUCTURAL BONDING DETAIL

LP-22

200mm SQUARE BONDING CLAMP. ATTACH

CLAMP TO CLEANED BARE METAL SURFACE.

200MM SQUARE BONDING PLATE. FASTEN TO

CLEANED BARE METAL SURFACE WITH 2

STAINLESS STEEL FASTENERS

NOTES:

1. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780.

2. BONDING DISTANCES SHALL COMPLY WITH NFPA 780 & UL96A

REQUIREMENTS.

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

REVISED: JUNE 2011 LIGHTNING PLATE:

CONDUCTOR SPLICES

LP-9

NOTES:

1. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 .

2. NO BEND OF CONDUCTOR SHALL FORM A FINAL INCLUDED ANGLE OF

LESS THAN 90° NOR SHALL THERE BE A BEND RADIUS LESS THAN 200mm .

PARALLEL CABLE SPLICER

CABLE TO CABLE END SPLICER

90° MIN.

MINIMUM 200mm

RADIUS

COPPER LIGHTNING PROTECTION

CONDUCTORS

ALUMINUM LIGHTNING PROTECTION

CONDUCTORS

MAKE COPPER TO ALUMINUM CONDUCTOR

CONNECTIONS WITH A BIMETALLIC

CONNECTOR

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

LIGHTNING PROTECTION CONDUCTORS:

USE COPPER CONDUCTOR CLASS 1 OR 2 - AS

REQUIRED.

FOR SURFACES NOT COMPATIBLE WITH

COPPER: USE ALUMINUM CONDUCTOR

CLASS 1 OR 2 AS REQUIRED.

CONDUCTOR BEND REQUIREMENTS

REVISED: JUNE 2011 LIGHTNING PLATE: LP-12

90°

MINIMUM 200mm

RADIUS

135°

MINIMUM 200mm

RADIUS

LESS THAN 90°

LESS THAN 8

INCH RADIUS

MINIMUM 200mm

RADIUS

135°

TO GROUND

TO GROUND

TO GROUND

ACCEPTABLE

ACCEPTABLE

ACCEPTABLE

NOT

ACCEPTABLE

TO GROUND

CONDUCTOR

CONDUIT

CONDUIT

CONDUCTOR

CONDUIT

CONDUCTOR

DOWN CONDUCTOR DETAIL

REVISED: JUNE 2011 LIGHTNING PLATE: LP-13

LIGHTNING

CONDUCTOR

LIGHTNING CONDUCTOR

45 DEGREE 27mm PVC ELBOW

27mm SCH 40 PVC CONDUIT

2 HOLE STRAP FOR 27mm

PVC CONDUIT

CONNECTOR FOR 27mm PVC

27mm SCH 40 PVC CONDUIT

27mm SCH 40 PVC CONDUIT

2 HOLE STRAP FOR 27mm

PVC CONDUIT

45 DEGREE 27mm PVC ELBOW

TO GROUND

EG502

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

GROUND ROD

REVISED: JUNE 2011 LIGHTNING PLATE: LP-14

LPS DOWN

CONDUCTOR

GROUNDING SYSTEM

COUNTERPOISE

EXOTHERMICALLY

WELD CONDUCTORS

TO GROUND ROD

COPPER-COATED

STEEL GROUND ROD

REVISED: JUNE 2011 LIGHTNING PLATE:

GROUND TERMINATION DETAIL

LP-15

LIGHTNING PROTECTION COPPER DOWN

CONDUCTOR

COPPER GROUND LOOP

COPPER HIGH COMPRESSION FITTING

HIGH COMPRESSION FITTING (WHEN GROUND

LOOP IS USED)

20mm X 3m COPPER-CLAD GROUND ROD.

NOTES:

1. ALUMINUM LIGHTNING PROTECTION CONDUCTORS SHALL NOT COME INTO DIRECT

CONTACT WITH EARTH.

2. WHERE MATERIAL COMPATIBILITY REQUIRES THE USE OF ALUMINUM DOWN

CONDUCTORS THEY SHALL BE TERMINATED AT A UL LISTED BIMETALLIC FITTING A

MINIMUM OF 450mm ABOVE GRADE. A COPPER CONDUCTOR SHALL BE UTILIZED

BETWEEN THE BIMETALLIC FITTING AND THE GROUND SYSTEM CONNECTION.

STRUCTURAL STEEL GROUNDING

REVISED: JUNE 2011 LIGHTNING PLATE: LP-17

PERIMETER STEEL COLUMN.

200mm SQUARE BONDING PLATE.

FASTEN BOND PLATE TO CLEANED BARE METAL

SURFACE OF STEEL COLUMN WITH (2)

STAINLESS STEEL SELF TAPPING SCREWS.

COPPER GROUND CONDUCTOR

27MM SCH 40 PVC SLEEVE THROUGH FLOOR

FOR CONNECTION OF PERIMETER STEEL

COLUMN GROUND. SEAL SLEEVE AS REQUIRED

AFTER INSTALLATION OF GROUND CONDUCTOR.

COPPER HIGH COMPRESSION CONNECTOR.

GROUND LOOP CONDUCTOR

COPPER HIGH COMPRESSION CONNECTOR

(WHERE GROUND LOOP IS USED).

20mm X 3m COPPER GROUND ROD. THE

CONNECTION TO THE GROUND ROD SHALL BE

MADE AT A POINT NOT LESS THAN 610mm BELOW GRADE AND A MINIMUM OF 610mm

AWAY FROM FOOTINGS OR FOUNDATION

WALLS.

POTENTIAL EQUALIZATION BONDING

REVISED: JUNE 2011 LIGHTNING PLATE: LP-21

30mm WIDE STEEL WALL MOUNTING

BRACKET (TYPICAL OF 2)INSULATOR (TYP OF 2)

15mm STAINLESS STEEL HEX HEAD BOLT

W/ HELICAL SPLIT LOCK WASHER (TYPICAL

OF 2).

COPPER BUS BAR

8mm X 25mm STAINLESS STEEL HEX HEAD

BOLT EACH WITH (1) STAINLESS STEEL

HEX HEAD NUT AND (2) #1369S STAINLESS

STEEL HELICAL SPLIT LOCK WASHER.

HIGH COMPRESSION GROUNDING

TERMINAL.

TO CONNECTION WITH ELECTRICAL

SERVICE GROUND

TO CONNECTION WITH TELEPHONE

SERVICE

TO CONNECTION WITH COLD WATER

TO CONNECTION WITH BUILDING STEEL

(WHERE APPLICABLE)

TO CONNECTION WITH GROUND SYSTEM

SCALE:C1 SIGNAL REFERENCE GROUND CONNECTOR IN CONCRETE FLOOR

NONE

CAST BRASS GROUNDING PLATE WITH

4 - 13mm THREADED HOLES FOR

SECURING GROUNDING CABLE LUGS

GROUNDING MESH EMBEDDED IN

CONCRETE FLOOR

COMPRESSION OR EXOTHERMIC

WELDED CONNECTION TO GROUNDING

MESH IN CONCRETE FLOOR

GRAPHIC SCALE

GENERAL SHEET NOTES

TN101

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE:

TELECOMMUNICATIONS AND OVERHEAD CABLE TRAY PLAN

1:100

A. PROVIDE ALL TELECOMMUNICATIONS INSTALLATIONS IN ACCORDANCE

WITH THE CANADIAN CSA GROUP (CAN/CSA-T527, 528, 529 AND 530), AS

WELL AS ADDITIONAL REQUIREMENTS LISTED IN THE SPECIFICATIONS.

B. SEE SHEETS E-501 FOR TYPICAL WORKSTATION AND PRINTER OUTLET

DETAILS AND CONFIGURATIONS.

1. SEE "OPS EQUIPMENT ROOM 116 UNDERFLOOR CABLE TRAY PLAN" ON SHEET

TN401.

2. SEE "ENLARGED OUTSIDE CABLING ENTRANCE DETAIL" ON SHEET TN401 FOR

ADDITIONAL WORK THIS AREA.

3. PLYWOOD BACKBOARD ON TWO LONG WALLS IN TELECOMM. ROOM, 5450

LONG, FROM 300 AFF TO 2440 AFF.

4. 300 WIDE X 50 DEEP, OVERHEAD, BASKET OR LADDER-TYPE CABLE TRAY.

INSTALL ABOVE LAY-IN CEILING AT 3150 AFF TO BOTTOM.

5. 300 WIDE X 50 DEEP, OVERHEAD, BASKET OR LADDER-TYPE CABLE TRAY.

COORDINATE MOUNTING HEIGHT WITH OTHER CABLE TRAY PROVIDED IN

ROOM UNDER NOTE 1 ABOVE.

6. TRANSITION CABLE TRAY TO CONDUIT WHEN PASSING THROUGH INTERIOR

PARTITION. SEAL OPENING TO MAINTAIN ALL RATINGS OF PARTITION.

7. LOCATE JUNCTION BOX ABOVE LAY-IN CEILING AND ROUTE 25 EMPTY

CONDUIT TO JUST BELOW ROOF FOR INSTALLATION OF ROOF-MOUNTED GPS

ANTENNA CABLING BY OTHERS.

8. SEE "ENLARGED ROOM 110 TELECOMMUNICATIONS PLAN ON SHEET TN401

FOR ADDITIONAL WORK THIS AREA.

A

A A

A

A

A

A

A

A

A B

B

C

B

J

A

A

A

107108

GRAPHIC SCALES

GENERAL SHEET NOTES

TN401

JO

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE:A1 ENLARGED OUTSIDE CABLING ENTRANCE PATHWAY PLAN

1:50 TN101

A. PROVIDE ALL TELECOMMUNICATIONS INSTALLATIONS IN ACCORDANCE

WITH THE CANADIAN CSA GROUP (CAN/CSA-T527, 528, 529 AND 530), AS

WELL AS ADDITIONAL REQUIREMENTS LISTED IN THE SPECIFICATIONS.

B. SEE TELECOMMUNICATIONS AND OVERHEAD CABLE TRAY PLAN ON SHEET

TN101 FOR ADDITIONAL INFORMATION.

1. COMMERCIAL TELECOMMUNICATIONS SERVICE ENTRANCE DUCTBANK. SEE

"ELECTRICAL SITE PLAN" ON SHEET ES102 FOR DESCRIPTION AND

CONTINUATION. TURN UP IN TELECOM ROOM 110 ON INTERIOR SIDE OF

OUTSIDE WALL AS SHOWN.

2. OUTSIDE CABLING MANHOLE UC1A. SEE "ELECTRICAL SITE PLAN" ON SHEET

ES102 FOR CONTINUATION AND "OUTSIDE CABLING MANHOLE UC1A" ON

SHEET ES501 FOR DESCRIPTION.

3. 3 - 100 DIA DUCTS FOR OUTSIDE CABLING ROUTING INTO FACILITY.

TERMINATE AT UNDERSIDE OF ENCLOSURE PROVIDED ON NORTH WALL OF

OPS EQUIPMENT ROOM 116 AS SHOWN. COORDINATE ROUTING AND BURIAL

DEPTH WITH "TYPICAL OPENING AT CONDUIT" DETAIL PROVIDED ON SHEET

S-501.

4. 610 WIDE X 610 TALL X 305 DEEP NEMA 4X CABLE ENCLOSURE WITH HINGED

DOOR AND HANDLE. MOUNT AT 1700 AFF TO CENTER OF ENCLOSURE.

5. 450 WIDE X 50 DEEP, OVERHEAD, RUNWAY-TYPE CABLE TRAY. INSTALL 2610

AFF TO BOTTOM.

6. 42U TALL TELECOM EQUIPMENT CABINET. SEE "TELECOMMUNICATIONS RISER

DIAGRAM" ON SHEET TN601.

7. 450 WIDE X 100 DEEP BASKET-TYPE UNDERFLOOR CABLE TRAY. MOUNT AT

200 FROM BOTTOM OF TRAY TO TOP OF POWER CABLE TRAY MOUNTED FLUSH

AT FLOOR LEVEL. SEE SHEET EP101.

SCALE:C1 ENLARGED ROOM 110 TELECOMMUNICATIONS PLAN

1:50 TN101

SCALE:C2 OPS EQUIPMENT ROOM 116 UNDERFLOOR TELECOMMUNICATIONS CABLE TRAY PLAN

1:100

A

A

TN501

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

A

SCALE:NOT TO SCALE

WORKSTATION OUTLET TYPE 'A' -

SCALE:NOT TO SCALE

NETWORK PRINTER OUTLET TYPE 'C' -C

SCALE:NOT TO SCALE

WALL-MOUNTED HANDSET OUTLET - A2A1

C1 B

SCALE:NOT TO SCALE

WORKSTATION OUTLET TYPE 'B' -C2

SINGLE GANG BACKBOX RECESSED

IN WALL

HIGH-IMPACT THERMOPLASTIC

FACEPLATE; MATCH COLOR TO

ADJACENT RECEPTACLE FACEPLATES.

MOUNTING TABS FOR

WALL-MOUNTING OF TELEPHONE

HANDSET.

21 CONDUIT TO CABLE TRAY WITH ONE CAT 6, 4-PR UTP.

COLOR OUTER JACKET GREY FOR UNCLASSIFIED

VOICE.

VOICE CATEGORY 6 STP, RJ-45 OUTLET.

COLOR CODE GREY FOR

UNCLASSIFIED VOICE.

OUTLET IDENTIFICATION TAG

HOLDER

DATA

DATA

VOICE

102 SQ. X MIN. 54 D BACKBOX

RECESSED IN WALL

CATEGORY 6, RJ-45 OUTLET, TYP. OF 3.

COLOR CODE GREEN FOR

UNCLASSIFIED DATA, GREY FOR

UNCLASSIFIED VOICE.

BACKBOX REDUCER PLATE FOR

SINGLE-GANG OPENING

HIGH-IMPACT THERMOPLASTIC

FACEPLATE; MATCH COLOR TO

ADJACENT RECEPTACLE FACEPLATES.

27 CONDUIT TO CABLE TRAY WITH CAT 6, 4-PR, UTP FOR

EACH WIRED OUTLET. OFFSET ENTRANCE INTO TOP OF

BACKBOX. COLOR OUTER JACKET GREEN FOR

UNCLASSIFIED DATA, GREY FOR UNCLASSIFIED VOICE.

OUTLET IDENTIFICATION TAG

HOLDER, TYP. OF 2

SAME DESCRIPTION AS ABOVE, ROUTED DOWN IN LIEU

OF UP IN AREAS WITH RAISED FLOORING SYSTEM.

102 SQ. X MIN. 54 D BACKBOX

RECESSED IN WALL

CATEGORY 6 STP, RJ-45 OUTLET.

COLOR CODE GREEN FOR

UNCLASSIFIED DATA.

BACKBOX REDUCER PLATE FOR

SINGLE-GANG OPENING

HIGH-IMPACT THERMOPLASTIC

FACEPLATE; MATCH COLOR TO

ADJACENT RECEPTACLE FACEPLATES.

OUTLET IDENTIFICATION TAG

HOLDER, TYP. OF 2

DATA

BLANK FACEPLATE SPACE

27 CONDUIT TO CABLE TRAY WITH CAT 6, 4-PR, UTP FOR

EACH WIRED OUTLET. OFFSET ENTRANCE INTO TOP OF

BACKBOX. COLOR OUTER JACKET GREEN FOR

UNCLASSIFIED DATA, GREY FOR UNCLASSIFIED VOICE.

SAME DESCRIPTION AS ABOVE, ROUTED DOWN IN LIEU

OF UP IN AREAS WITH RAISED FLOORING SYSTEM.

DATA

DATA

102 SQ. X MIN. 54 D BACKBOX

RECESSED IN WALL

DUPLEX SC, MM FIBER OPTIC

OUTLET, TYP. OF 2. COLOR

CODE RED FOR SECRET DATA

NETWORK.

BACKBOX REDUCER PLATE FOR

SINGLE-GANG OPENING

HIGH-IMPACT THERMOPLASTIC

FACEPLATE; MATCH COLOR TO

ADJACENT RECEPTACLE FACEPLATES.

OUTLET IDENTIFICATION TAG

HOLDER, TYP. OF 2

BLANK FACEPLATE SPACE

27 CONDUIT TO CABLE TRAY WITH 2-FIBER, MM, OM3 FOR

EACH CONNECTED OUTLET. OFFSET ENTRANCE INTO

TOP OF BACKBOX. COLOR OUTER JACKET RED FOR

CLASSIFIED SECRET DATA NETWORK.

SAME DESCRIPTION AS ABOVE, ROUTED DOWN IN LIEU

OF UP IN AREAS WITH RAISED FLOORING SYSTEM.

TN601

IN

T M

A R

IT

IM

E F

A C

IL

IT

Y

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M S

C O

M M

A N

D

A

TL

A N

TI

C

SCALE:A1 TELECOMMUNICATIONS RISER DIAGRAM

NONE

SCALE:C1 TELECOMMUNICATIONS GROUNDING RISER DIAGRAM

NONE

9 11

1 3

COPPER

VOICE

CABINET

100mm EMPTY DUCT

50 PAIR PET FOR

COPPER SERVICE

ENTRANCE CABLING

WALL-MOUNTED FIBER

OPTIC BUILDING

TERMINAL

FIBER OPTIC SERVICE

ENTRANCE CABLING BY

OTHERS

DUCTS TO HAND

HOLE ON SITE. SEE

ES102

TELECOMMUNICATIONS

PRIMARY BONDING

BUSBAR (PBB)

MINIMUM #6 TO MAIN

ELECTRICAL GROUNDING

BUSBAR (MEGB)

#6 CU GND

#6 CU GND

ENCLOSED,

FREE-STANDING,

LOCKABLE CABINET -

TYPICAL OF 2.

12 PORT, DUPLEX LC

FIBER OPTIC PATCH

PANEL

24 PORT, CAT 6 UTP

PATCH PANELS

TYPICAL

UNCLASSIFIED

WORKSTATION

27mm C WITH 2 - CAT 6, 4-PR, UTP, TYPICAL

ROUTE CONDUIT BACK TO CABLE TRAY IN

COMM ROOM 110 AND PROVIDE PLASTIC

BUSHING ON CONDUIT END, TYPICAL

COMM

HORIZONTAL LADDER

TRAY

A

TYPICAL

CLASSIFIED

WORKSTATION

27mm C WITH 2 - 2

STRAND MM FOC,

TYPICAL

ROUTE CONDUIT BACK TO CABLE TRAY IN

OPS ROOM 116 AND PROVIDE PLASTIC

BUSHING ON CONDUIT END, TYPICAL

B

FIBER

DATA

CABINETCOPPER SERVICE

ENTRANCE CABLING BY

OTHERS

COPPER SERVICE

ENTRANCE CABLING BY

OTHERS

FIBER OPTIC SERVICE

ENTRANCE CABLING BY

OTHERS

MINIMUM #6 TO SECONDARY

BONDING BUSBAR (SBB)

PBB SBB MEGBSBB SBB SBB

G G G

EQUIPOTENTIAL GROUND

MESH IN FLOOR SLAB

UNDERFLOOR CABLE

TRAY

TYPICAL

EQUIP.

CABINET

TYPICAL

EQUIP.

CABINET

COPPER SERVICE

ENTRANCE PET

TYPICAL INCOMING CABLE

ENCLOSURE

110 116 118OVERHEAD CABLE TRAY

EP603 ELECTRICAL PANELBOARD SCHEDULES
EP604 PDU-1A PANELBOARD SCHEDULES
EP605 PDU-2A AND PDU-AB PANELBOARD SCHEDULES
EP606 PDU-1B PANELBOARD SCHEDULES
EP607 PDU-2B AND GL115 PANELBOARD SCHEDULES
EG101 ELECTRICAL GROUNDING PLAN
EG102 LIGHTNING PROTECTION SYSTEM ROOF PLAN
EG201 EXTERIOR LPS ELEVATIONS
EG202 EXTERIOR LPS ELEVATIONS
EG501 GROUDING AND LPS DETAILS
EG502 GROUNDING AND LPS DETAILS
TN101 TELECOMMUNICATIONS AND OVERHEAD CABLE TRAY PLAN
TN401 ENLARGED TELECOMMUNICATIONS PLANS
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature
2026-01-28T17:01:05-0500
signature

File details come from the government source that posted it. Updated .