This document package contains electrical design specifications and drawings for a Joint Maritime Facility project prepared by Naval Facilities Engineering Systems Command - Atlantic. The specifications establish comprehensive requirements for all electrical installations to comply with the Canadian Electrical Code (CEC C22.x).
The lighting design includes multiple luminaire types with specific applications: Type B1 luminaires in wet locations such as showers, direct/indirect LED luminaires, fixed recessed downlights, LED undercabinet lights, LED industrial lights, emergency lighting units, LED area luminaires, LED exterior decorative wall sconces, LED exit signs, decorative wall sconces, LED wall packs, and LED round ceiling surface mounts. Lighting control utilizes motion sensors with vacancy mode for most occupied spaces, manual on/off switches for mechanical and electrical rooms, and photocell with astronomical timeswitch control for exterior lighting. Target illuminance levels range from 50 lux for exterior perimeter fence to 500 lux for operations equipment room 116 and commercial telecom spaces. The electrical power system comprises two 750 kW standby-rated diesel generators, two 400 kW uninterruptible power systems (UPS A and UPS B), three air-cooled chillers, multiple HVAC split systems and fan coil units, transformers for voltage conversion (TP1 at 45 kVA and TM1 at 75 kVA), and distribution switchboards ES1 and GS1 rated at 1600A, 480Y/277V, three-phase, four-wire service with 65 kAIC minimum capacity. Power distribution includes multiple panelboards (LR118, L118, LR109, T110, GL115, and UPS panels A and B) with detailed circuit schedules. All electrical installations require surface mounting of conduit in prohibited EMT areas, with conduit types specified as IMC or GRS. The facility includes emergency systems with fire alarm control panels, fire suppression control panels, portable generator quick connect enclosures, and emergency pushbuttons for UPS shutdown in operations room 116.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE (CEC C22.x).
B. SEE LUMINAIRE SCHEDULE ON SHEET E-604 FOR DESCRIPTION OF
LUMINAIRE TYPES.
C. SEE LIGHTING CONTROL TABLE ON SHEET EL601 FOR DESCRIPTION OF
LIGHTING CONTROL IN EACH SPACE
1. PROVIDE TYPE B1 LUMINAIRE IN SHOWER WITH LENS AND WET LOCATION
RATING.
2. CONFIGURE LIGHTING FOR ROOM 116 TO SWITCH THREE EQUIVALENTLY
LOADED CIRCUITS AS DEPICTED WITH SUBSCRIPTS. CONNECT EMERGENCY
EGRESS LIGHTING TO ASSOCIATED CIRCUIT AHEAD OF LOCAL SWITCHING.
SEE LIGHTING CONTROL TABLE ON SHEET EL601.
3. EMT INSTALLATION IS PROHIBITED IN THIS ROOM.
4. VIA PHOTOCELL AND ASTRONOMICAL TIMESWITCH FOR CONTROL. INSTALL
PHOTOCELL ON ROOF AND ORIENT NORTHWARD.
5. SURFACE-MOUNT LUMINAIRES ON CONCRETE CEILING THIS ROOM. EMT
INSTALLATION IS PROHIBITED.
6. INSTALL LUMINAIRE AT 2050 AFF TO CENTER.
7. CONNECT TO RECEPTACLE BRANCH CIRCUIT THIS ROOM. SEE SHEET EP101.
8. PROVIDE WALL SWITCHES IN SEPARATE BACKBOXES FOR 120V AND 277V
LIGHTING CIRCUITS.
GRAPHIC SCALE
SHEET KEYNOTES
GENERAL SHEET NOTES
EL101
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:
ELECTRICAL LIGHTING PLAN
1:100
107108
C
A
A
C
C
C
C
C
C
C
C
K
A
A
B
B
D
H
1, TYPICAL THIS ROOM
L L
K
LR109
L118-9,11,13
L118
2 B 2 B 2
B 2 B 2
B 2
C 2
B 1
B 1
L118-8
L118-2,4,6
L118-5,7
MMMMM
L118-1,3
3N
M
M
M M
M
M
MMMM
B 2
F
A
A
A 2
S3D
S S
S
SS
3 3
S
S
S
S S
S S
S
S
S S
O
O
O
O
O O
O
O
O
O
O
O
O O
S 3
S
S
S
S3
S3
S3S3
S3
S 3
S4 a
O
S S O
S
S b c
O
O O
O O
O O
O O
O O a b c b ca a a a a a a a a a a a a a a a a a a b b b bbb b b b b bbbb b b b b b b ba a a c c c c c c cccc c c c c c c c c c c c
TS
O
O
O
A 2
EL501
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
A 1,2 B 1
B 2
D H
C 1,2,3 E J
EL502
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
G L
M K
N
EL601
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
A
LUMINAIRE SCHEDULE
TYPE LUMINAIRE DESCRIPTION LIGHT SOURCE VOLTAGE MOUNTING NOTES LUMEN OUTPUT WATTAGE
600x1200 DIRECT/INDIRECT TROFFER LED 277 RECESSED IN CEILING 1, 2, 3, 4, 5 4000 47
600x600 DIRECT/INDIRECT TROFFER LED 277 RECESSED IN CEILING 2, 3, 4, 5 2000 25
INTERIOR RECESSED DOWNLIGHT LED 277 RECESSED IN CEILING 4, 9 1000 15
EXTERIOR RECESSED DOWNLIGHT LED 277 RECESSED IN SOFFITT 4, 6, 7, 8 2000 21
INDUSTRIAL STRIP LED 277 PENDANT AT 2400 AFF 4, 10 4000 30
INDUSTRIAL STRIP LED 277 PENDANT AT 2400 AFF 4, 10 3000 25
INDUSTRIAL STRIP LED 277 PENDANT AT 2400 AFF 4, 10 6000 48
LINEAR UNDERCABINET LED 277 UNDERSIDE OF WALL CABINET 4, 11 1000 11
EMERGENCY LIGHTING UNIT LED 277 SURFACE - 300 BELOW CEILING 12, 13, 16 n/a 2
WALL-MOUNTED VANITY LED 277 SURFACE, ABOVE MIRROR 4, 11, 13, 14, 15 1300 10
EXIT SIGN LED 277 SURFACE CEILING OR WALL 13, 16 n/a 5
EXTERIOR WALL SCONCE LED 277 SURFACE WALL AT 3000 AFG 16, 17, 18, 24 3000 36
POLE-MOUNTED EXTERIOR AREA LED 277 POLE ARM 18, 19, 20 11130 72
ROUND SURFACE CEILING LED 277 SURFACE CEILING 21 2500 24
DECORATIVE WALL SCONCE LED 120 SURFACE WALL AT 1200 AFF 22 800 10
EXTERIOR WALL PACK LED 277 SURFACE WALL AT 4300 AFG 18, 23, 24 5500 41
DIRECT WALL-MOUNT LINEAR LED 277 SURFACE WALL AT 2150 AFF 4, 13 1600 32
1. PROVIDE 700 LUMEN BATTERY PACK WHERE INDICATED ON DRAWINGS.
2. PROVIDE IN STATIC CONFIGURATION; NO RETURN AIR FUNCTION.
3. PROVIDE ACRYLIC DIFFUSER WITH LINEAR PRISMATIC LENS.
4. PROVIDE WITH 3500 K COLOR TEMPERATURE.
5. PROVIDE 0-10V DIMMING DRIVER TO 10% OUTPUT.
6. PROVIDE 10 WATT BATTERY PACK WHERE INDICATED ON DRAWINGS.
7. WET LOCATION, COVERED CEILING LISTED.
8. PROVIDE WITH TEMPERED GLASS LENS.
9. PROVIDE OPEN REFLECTOR TYPE CONFIGURATION.
10. PROVIDE WITH FROSTED, RIBBED, IMPACT-RESISTANT ACRYLIC DROP LENS COVER.
11. PROVIDE IN LENGTH = 600 mm.
12. PROVIDE WITH CAPACITY FOR 2 SINGLE REMOTE HEADS WHERE SHOWN ON DRAWINGS.
13. PROVIDE HOUSING WHITE IN COLOR.
14. PROVIDE WITH FROSTED, HIGH-IMPACT ACRYLIC LENS.
15. PROVIDE 90 CRI RATING.
16. PROVIDE WITH MINIMUM 90 MINUTES BATTERY BACK-UP.
17. PROVIDE HOUSING IN DARK BRONZE FINISH, PRISMATIC TEMPERED GLASS LENS, AND FORWARD
THROW DISTRIBUTION OPTICS.
18. PROVIDE WITH 4000 K COLOR TEMPERATURE.
19. PROVIDE HOUSING IN DARK BRONZE FINISH, TYPE 4 WIDE DISTRIBUTION OPTICS, TWIST-LOCK
PHOTOCELL, AND 10kV SURGE PROTECTION.
20. PROVIDE WITH 6.1 M TALL ANCHOR-BASE ALUMINUM POLE (XL-19B), ANCHOR BASE CONCRETE POLE
FOUNDATION (XL-21), AND ROUND POLE SINGLE ARM MOUNTING ADAPTER (XL-23).
21. PROVIDE IN 600 mm DIAMETER, WITH 2700 K COLOR TEMPERATURE.
22. WIRE FOR CONTROL BY WALL-MOUNTED LIGHT SWITCH NEAR DOOR.
23. PROVIDE HOUSING IN DARK BRONZE FINISH WITH TYPE III MEDIUM DISTRIBUTION OPTICS.
24. PROVIDE LUMINAIRES H AND M FROM SAME MANUFACTURER "FAMILY" FOR SIMILAR STYLING.
LUMINAIRE SCHEDULE NOTES
LIGHTING CONTROL TABLE
ROOM NO. - NAME LIGHTING CONTROL SCHEME TARGET CALCULATED
ILLUMINANCE (LUX) ILLUMINANCE (LUX)
100 - SECURE VESTIBULE AUTOMATIC ON/OFF WITH MOTION SENSOR 150 150
101 - OPEN OFFICE MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE); 300 350
FULL RANGE DIMMING
102 - UNSECURE CORRIDOR AUTOMATIC ON/OFF WITH MOTION SENSOR 150 135
103 - SHOWER MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 150 195
104 - TOILET MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 150 135
105 - BREAK MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 250 232
106 - JANITOR AUTOMATIC ON/OFF WITH MOTION SENSOR 100 114
107 - BUNK MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 50 88
108 - BUNK MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 50 88
109 - STAGING AREA MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 250 250
110 - COMMERCIAL TELECOM MANUAL ON/OFF SWITCH 500 461
111 - CORRIDOR AUTOMATIC ON/OFF WITH MOTION SENSOR 150 150
112 - MECHANICAL MANUAL ON/OFF SWITCH 200 220
113 - FIRE PUMP MANUAL ON/OFF SWITCH 250 260
114 - GENERATOR FUEL ROOM MANUAL ON/OFF SWITCH 200 170
115 - GENERATOR ROOM MANUAL ON/OFF SWITCH 200 215
116 - OPS EQUIPMENT MANUAL ON WITH WALL SWITCH; AUTOMATIC OFF WITH MOTION SENSOR (VACANCY MODE) 500 500
117 - UPS A MANUAL ON/OFF SWITCH 200 240
118 - ELECTRICAL MANUAL ON/OFF SWITCH 200 270
119 - UPS B MANUAL ON/OFF SWITCH 200 260
BUILDING EXTERIOR ON PER PHOTOCELL, OFF BY ASTRONOMICAL TIMESWITCH 50 45
EXTERIOR PERIMETER FENCE ON PER PHOTOCELL, OFF BY ASTRONOMICAL TIMESWITCH 50 45
A
B
B
C
C
C
D
E
F
G
H
J
K
L
M
N
1. TARGET AND CALCULATED ILLUMINANCE VALUES IN LUX ARE AVERAGE VALUES.
LIGHTING CONTROL TABLE NOTES
A. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE (CAN/CSA-C22.3).
B. SEE SHEET EP102 FOR POWER CONNECTIONS TO HVAC/MECHANICAL
EQUIPMENT.
1. 457W x 100H UNDERFLOOR CABLE TRAY FOR POWER CABLING. INSTALL
FLUSH WITH LOWER STRUCTURAL CONCRETE FLOOR BELOW.
2. ELECTRICAL SWITCHBOARD "ES1" - 1600A, 480Y/277V, 3 PHASE, 4 WIRE, 65
kAIC. PROVIDE CONCRETE HOUSEKEEPING PAD.
3. ELECTRICAL SWITCHBOARD "GS1" - 1600A, 480Y/277V, 3 PHASE, 4 WIRE, 65
kAIC.
4. UNINTERRUPTIBLE POWER SYSTEM "UPS A" - 400 kW, 480V, 3PH.
5. UNINTERRUPTIBLE POWER SYSTEM "UPS B" - 400 kW, 480V, 3PH.
6. STANDBY-RATED EMERGENCY DIESEL GENERATOR "A" - 750 kW, 480Y/277V, 3
PHASE, 4 WIRE.
7. STANDBY-RATED EMERGENCY DIESEL GENERATOR "B" - 750 kW, 480Y/277V, 3
PHASE, 4 WIRE.
8. DRY-TYPE TRANSFORMER "TP1" - 45 kVA, 480V - 208Y/120V, 3 PHASE, 4 WIRE.
9. DRY-TYPE TRANSFORMER "TM1" - 75 kVA, 480V - 208Y/120V, 3 PHASE, 4 WIRE.
10. PROVIDE ONLY UNDER ADDITIVE BID OPTION NO. 1.
11. GENERATOR RESISTIVE LOAD BANK - 750 Kw, 480V, 3PH.
12. VRLA TYPE BATTERY CABINET FOR "UPS-A".
13. VRLA TYPE BATTERY CABINET FOR "UPS-B".
14. FIRE ALARM CONTROL PANEL - 120V.
15. FIRE SUPPRESSION CONTROL PANEL - 120V.
16. PORTABLE GENERATOR QUICK CONNECT ENCLOSURE - 1200A, 480V, 3P, 100%
NEUTRAL.
17. EMT INSTALLATION IS PROHIBITED IN THIS ROOM. UTILIZE IMC OR GRS TYPE
CONDUIT.
18. MOUNTED UNDER SINK FOR GARBAGE DISPOSAL.
19. PROVIDE JUNCTION BOX TO TRANSITION SECONDARY CIRCUIT FROM
SWITCHBOARD SE1 TO UNDERGROUND CIRCUIT TO GUARD SHACK. SEE
ELECTRICAL SITE PLAN ON SHEET ES102.
20. PRIMARY AND SECONDARY ELECTRICAL FEEDERS TO FIRE PUMP
CONTROLLER. SEE ELECTRICAL SITE PLAN ON SHEET ES102 AND ONE-LINE
DIAGRAM ON SHEET EP601.
21. ELECTRICAL SERVICE ENTRANCE FROM PAD-MOUNTED TRANSFORMER. SEE
ELECTRICAL SITE PLAN ON SHEET ES102 AND ONE-LINE DIAGRAM ON SHEET
EP601.
22. FIRE WATER PUMP WITH FREE-STANDING CONTROLLER - 31 HP, 480V, 3 PH.
23. FIRE WATER PRESSURE MAINTENANCE (JOCKEY) PUMP WITH
WALL-MOUNTED CONTROLLER - 1.5 HP, 480V, 3PH.
24. WALL-MOUNTED EMERGENCY PUSHBUTTON. ACTIVATION TRIPS MAIN
CIRCUIT BREAKER FOR UPS PANELS A1 AND B1, SERVING ALL TECHNICAL
POWER IN OPS RM 116.
25. SINGLE RECEPTACLE FOR WALL-MOUNTED DIGITAL CLOCK AT 2200 AFF.
26. CONNECT RECEPTACLE BRANCH CIRCUIT TO WALL-MOUNTED LUMINAIRE
TYPE L. SEE SHEET EL101.
27. MOUNT RECEPTACLES FOR POWER TO DATA EQUIPMENT RACKS OVERHEAD
AT 2500 AFF. BRACE SECURELY WITH U-SHAPED CHANNEL OR OTHER
SUFFICIENT STRUCTURAL SUPPORT.
28. RAISED STRUCTURAL FLOOR THIS AREA 1200 ABOVE CONCRETE FLOOR. SEE
A-105.
29. GENERATOR AUDIBLE ALARM SIGNAL DEVICE.
30. UPS EMERGENCY PUSHBUTTON. ACTIVATION SHUTS DOWN
CORRESPONDING UPS UNIT.
GRAPHIC SCALE
SHEET KEYNOTES
GENERAL SHEET NOTES
EP101
EL
EC
TR
IC
AL
P
OW
ER
P
LA
N
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:
ELECTRICAL POWER PLAN
1:100
107108
6 7
26 26
GFI
WP WP
T
T
STS-1
PDU-1A
PDU-2A
MISSION CONFIGURABLE
MISSION
COMMS
PFE 1 PFE 2
PFE 4PFE 3
PDU-1B
PDU-2B
PDU-AB
J
J
WC
WC
GFI
J
A
GFI
GFI
GFI
LR109-6,8,10
8,10
LR109-2,4
LR109-5,7,9
ML112-36
LR118-1,3,5
PDU-AB-37,39
LR118
-2
ML112-38,
T110-1
ES1
GS1
UPS A
UPS B
LR118
T110
LR109
ML112
MH112
ES1-3J
ML112A
ES1-3I
L118
B1
A1
TP1
TM1
ES1-3K
T110-4,6
GL115
1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE (CEC C22.x).
2. SEE MECHANICAL SHEETS M-601 THROUGH M-603 FOR MECHANICAL/HVAC
EQUIPMENT SCHEDULES AND ADDITIONAL INFORMATION.
3. SEE PLUMBING SHEETS P-601 AND P-602 FOR PLUMBING EQUIPMENT
SCHEDULES AND ADDITIONAL INFORMATION.
1. DOAS HVAC UNIT - 56.6 kW, 480V, 3 PH.
2. COMPUTER ROOM AIR CONDITIONER UNIT - 46.5 kW, 480V, 3 PH.
3. LOCATE RECEPTACLE ABOVE CEILING FOR RADON EXHAUST FAN. SEE
SHEET M-101 AND P-103.
4. COLD WATER CIRCULATING PUMPS CHWP-1 AND 2 - EACH AT 4.4 kW, 480V, 3
PH.
5. HOT WATER CIRCULATING PUMP RP-1 - 40 W, 120V.
6. AIR COOLED CHILLERS ACCH-1, ACCH-2 AND ACCH-3 - EACH AT 50 kW, 480V, 3
PH.
7. HVAC SPLIT SYSTEM DDIU/DDOU-1 - 9 FLA, 208V, 1 PH.
8. FAN COIL UNIT FCU-1 - 2.4 FLA, 208V, 3 PH.
9. FAN COIL UNIT FCU-2 - 2.4 FLA, 208V, 3 PH.
10. FAN COIL UNIT FCU-3 - 2.4 FLA, 208V, 3 PH.
11. FAN COIL UNIT FCU-4 - 11.2 FLA, 208V, 3 PH.
12. FAN COIL UNIT FCU-5 - 11.2 FLA, 208V, 3 PH.
13. ELECTRIC UNIT HEATER EUH-1 - 2 kW, 208V, 1PH.
14. ELECTRIC UNIT HEATER EUH-2 - 2 kW, 208V, 1PH.
15. ELECTRIC UNIT HEATER EUH-3 - 2 kW, 208V, 1PH.
16. ELECTRIC UNIT HEATER EUH-4 - 2 kW, 208V, 1PH.
17. ELECTRIC UNIT HEATER EUH-5 - 2 kW, 208V, 1PH.
18. ELECTRIC UNIT HEATER EUH-6 - 2 kW, 208V, 1PH.
19. ELECTRIC UNIT HEATER EUH-7 - 2 kW, 208V, 1PH.
20. ELECTRIC UNIT HEATER EUH-8 - 2 kW, 208V, 1PH.
21. ELECTRIC UNIT HEATER EUH-9 - 2 kW, 208V, 1PH.
22. ELECTRIC UNIT HEATER EUH-10 - 1.5 kW, 208V, 1PH.
23. NOT USED.
24. EXHAUST FAN EF-3 - 750 W, 120V.
25. EXHAUST FAN EF-4 - 750 W, 120V.
26. EXHAUST FAN EF-1 - 80W, 120V.
27. EXHAUST FAN EF-2 - 80W, 120V.
28. EMERGENCY EYE WASH STATION HORN/STROBE - 120V.
29. DOMESTIC WATER HEATER DWH-1 - 3kW, 480V, 3PH.
30. FAN COIL UNIT FCU-6 - 11.2 FLA, 208V, 3 PH.
31. FAN COIL UNIT FCU-7 - 11.2 FLA, 208V, 3 PH.
32. HVAC PIPING HEAT TRACE - 120V.
33. GENERATOR FUEL OIL POLISHING UNIT FPU-1 - 120V.
34. GENERATOR FUEL OIL CONTROLLER FLC-1 - 120V.
35. EMT INSTALLATION IS PROHIBITED IN THIS ROOM. UTILIZE IMC OR GRS TYPE
CONDUIT.
36. PROVIDE 16 DIA. EMPTY CONDUIT BACK TO SWITCHBOARD ES1 IN ROOM 118
FOR CONNECTION OF WATER METER TO ELECTRICAL SMART METER.
CABLING PROVIDED BY OTHERS.
37. ELECTRIC UNIT HEATER EUH-11 - 1.5kW, 208V, 1PH.
GRAPHIC SCALE
SHEET KEYNOTES
GENERAL SHEET NOTES
EP102
EL
EC
TR
IC
AL
P
OW
ER
P
LA
N
- M
EC
HA
NI
CA
L E
QU
IP
ME
NT
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:
ELECTRICAL POWER PLAN - MECHANICAL EQUIPMENT
1:100
107108
E E E
VFD VFD
MM
M M M
M
M
M
M
M
M
E
M M M
M
E E
E
E
E
E E
EE
J
E
E
E
E
E E
E
J
J
J
J
J
E
E
E
E
E
J
E
EE
J
J
M
E
CRAC-1
CRAC-2
ACCH-3
MH112-7,MH112-2,MH112-1,
ACCH-2ACCH-1
6 6
MH112-13
(3x4 + 1x8 GND
- 35)
ML112A-8
ML112-25
14 15 16
ML112-23ML112-21
24 25
ML112-27
T110-5
ML112A-13
ML112-22
MH112-26 MH112-31
MH112-8
MH112-25
LR118
T110
LR109
ML112
MH112
NF
3P
NF
3P
(3x2 + 1x6
GND - 41)
(3x2 + 1x6
GND - 41)
(3x2 + 1x6
GND - 41)
3x4 + 1x8 GND - 35
NF
3P 100
NF
3P
NF
3P
MH112-14
(3x4 + 1x8 GND
- 35)
CRAC-3
MH112-19
(3x4 + 1x8 GND
- 35)
NF
3P
CRAC-4
MH112-20
(3x4 + 1x8 GND
- 35)
3R 100
NF
3P 3R 100
NF
3P 3R
NF
3P
ML112-1
ML112-2 ML112-5 ML112-6
ML112-9
ML112-10
ML112-13
ML112-14
ML112-17
ML112A
ML112-18
ML112A-1
ML112A-2
ML112A-7
NF
2P 3R
33 3
ML112-22
ML112A-19ML112A-14
NF
3P
NF
3P30
NF
3P
NF
3P
ML112-26
ML112-28
L118
B1
A1
ML112A-25
GL115
EP201
EL
EC
TR
IC
AL
S
W
IT
CH
BO
AR
D
GS
1 E
LE
VA
TI
ON
A
ND
S
CH
ED
UL
E
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:A1 ELECTRICAL SWITCHBOARD "GS1" FRONT ELEVATION
NONE
2000A MAIN BUS, 480Y/277V, 3 PHASE, 4 WIRE, 100 KAIC MIN, NEMA 1, UL 891
COMPARTMENT NO. DEVICE RATING DESCRIPTION
1 - OPERATOR INTERFACE TERMINAL MASTER CONTROLS
- MASTER CONTROL STATION
- DIGITAL POWER METER
- VOLTMETER, AMMETER, WATTMETER,
FREQUENCY METER
- PLC WITH CPU
- ENGINE START MONITOR
- SYNCHROSCOPE
- SYNCH CHECK RELAY
- ALARM STATUS INDICATING PANEL
- OTHER DEVICES AS REQUIRED BY
SPECIFICATION 26 24 13
2A - GENERATOR CONTROL STATION GENERATOR A CONTROLS
- DIGITAL POWER METER
- VOLTMETER, AMMETER, WATTMETER,
FREQUENCY METER
- PLC WITH CPU
- DIGITAL SYNCHRONIZER
- OTHER DEVICES AS REQUIRED BY
SPECIFICATION 26 24 13
2B MOLDED CASE CIRCUIT BREAKER 1600A FRAME GENERATOR A
1200A TRIP
LSIA
3A - GENERATOR CONTROL STATION GENERATOR B CONTROLS
- DIGITAL POWER METER
- VOLTMETER, AMMETER, WATTMETER,
FREQUENCY METER
- PLC WITH CPU
- DIGITAL SYNCHRONIZER
- OTHER DEVICES AS REQUIRED BY
SPECIFICATION 26 24 13
3B MOLDED CASE CIRCUIT BREAKER 1600A FRAME GENERATOR B
1200A TRIP
LSIA
4 1600mm HIGH BUS SECTION DISTRIBUTION
4A MOLDED CASE CIRCUIT BREAKER 150A FRAME FIRE PUMP
150A TRIP
LSI
4B MOLDED CASE CIRCUIT BREAKER 1600A FRAME SWITCHBOARD ES1
1200A TRIP
LSI
5A - ENERGY REDUCTION MAINTENANCE PORTABLE GENERATOR/
- CIRCUIT BREAKER CONTROL SWITCH LOAD BANK CONTROLS
5B MOLDED CASE CIRCUIT BREAKER 1600A FRAME PORTABLE GENERATOR
1200A TRIP
LSIA
5C MOLDED CASE CIRCUIT BREAKER 1600A FRAME LOAD BANK
1200A TRIP
LSIA
SWITCHBOARD GS1 SCHEDULE
100 HIGH HOUSEKEEPING PAD
WITH PERIMETER CHAMFER
NOTE: EQUIPMENT DEPTH
DIMENSION = 1880
2A 3A
660 660
2B 3B
5C
5B
5A
ELEVATION PROVIDED DEPICTS DIMENSIONS FROM MANUFACTURER USED AS BASIS OF DESIGN
FOR EQUIPMENT. FINAL EQUIPMENT SELECTION WILL BE PER APPROVED SHOP DRAWING.
4A
4B
EP202
EC
TR
IC
AL
S
W
IT
CH
BO
AR
D
ES
1 E
LE
VA
TI
ON
A
ND
S
CH
ED
UL
E
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:A1 ELECTRICAL SWITCHBOARD "ES1" FRONT ELEVATION
NONE
2000A MAIN BUS, 480Y/277V, 3 PHASE, 4 WIRE, 100 KAIC MIN, NEMA 1, UL 891
COMPARTMENT NO. DEVICE RATING DESCRIPTION
1A SURGE PROTECTION DEVICE 240 kA PROVIDE WITH SURGE
COUNTER
1B MOLDED CASE 1600A FRAME MAIN UTILITY SERVICE
CIRCUIT BREAKER 1200A TRIP DISCONNECT
1C INCOMING TERMINATIONS CABLING AND LUGS
FROM SERVICE XFMR
2A INCOMING TERMINATIONS CABLING AND LUGS FROM
MIMIC BUS DIAGRAM SWITCHBOARD GS1
2B AUTOMATIC TRANSFER SWITCH 1600A OPEN TRANSITION TYPE,
WITH CONTROLS
3A MOLDED CASE 600A FRAME PANEL MH112
CIRCUIT BREAKER 600A TRIP
3B MOLDED CASE 600A FRAME UPS A
CIRCUIT BREAKER 600A TRIP
3C MOLDED CASE 600A FRAME UPS A BYPASS
CIRCUIT BREAKER 600A TRIP
3D MOLDED CASE 600A FRAME UPS B
CIRCUIT BREAKER 600A TRIP
3E MOLDED CASE 600A FRAME UPS B BYPASS
CIRCUIT BREAKER 600A TRIP
3F - 600A FRAME SPACE ONLY
3G MOLDED CASE 100A FRAME PANEL LR118 VIA XFMR
CIRCUIT BREAKER 80A TRIP TP1
3H MOLDED CASE 100A FRAME PANEL L118
CIRCUIT BREAKER 60A TRIP
3I MOLDED CASE 100A FRAME JOCKEY PUMP
CIRCUIT BREAKER 20A TRIP
3J MOLDED CASE 100A FRAME FIRE ALARM CONTROL
CIRCUIT BREAKER 20A TRIP PANEL
3K MOLDED CASE 100A FRAME FIRE SUPPRESSION
CIRCUIT BREAKER 20A TRIP CONTROL PANEL
3L MOLDED CASE 100A FRAME EXTERIOR GUARD SHACK
CIRCUIT BREAKER 60A TRIP
3M - 100A FRAME SPACE ONLY
SWITCHBOARD ES1 SCHEDULE
SCALE:C1 UPS A & B FRONT ELEVATION
NONE
400 kW, 480Y/277V INPUT - 480Y/277V OUTPUT, 3 PHASE, 4 WIRE, 65 KAIC MIN
COMPARTMENT NO. DEVICE RATING DESCRIPTION
1 MAINTENANCE BYPASS SWITCH WITH KIRK KEY INTERLOCK
2A UPS CONTROL INTERFACE TOUCH SCREEN LCD
2B UPS 400 kW (8 x 50 kW SCALABLE TO 500 kW
MODULES)
3A BATTERY COMPARTMENT VRLA, 15-MINUTE RUN TIME
100 kW
3B BATTERY COMPARTMENT VRLA, 15-MINUTE RUN TIME
100 kW
3C BATTERY COMPARTMENT VRLA, 15-MINUTE RUN TIME
100 kW
3D BATTERY COMPARTMENT VRLA, 15-MINUTE RUN TIME
100 kW
NOTE - UPS A & B ARE IDENTICAL.
UPS A & B SCHEDULE
100 HIGH HOUSEKEEPING PAD
WITH PERIMETER CHAMFER
NOTE: EQUIPMENT DEPTH
DIMENSION = 1220
1A
1B
2A 2B
3A
3G3B
3C
3D
3E
3H 3I 3J 3K 3L 3M
1C
914 1219 1219
3F
PROVIDE LOCK-ON MECHANISM
AND RED NAMEPLATE INDICATING
"FIRE ALARM - DO NOT TURN OFF"
FOR CIRCUIT BREAKERS 3J AND
3K.
M
NEXUS 1272
AMI METER
ELEVATION PROVIDED DEPICTS DIMENSIONS FROM MANUFACTURER USED AS BASIS OF DESIGN
FOR EQUIPMENT. FINAL EQUIPMENT SELECTION WILL BE PER APPROVED SHOP DRAWING.
ELEVATIONS PROVIDED DEPICTS DIMENSIONS FROM MANUFACTURER USED AS BASIS OF DESIGN
FOR EQUIPMENT. FINAL EQUIPMENT SELECTION WILL BE PER APPROVED SHOP DRAWING.
100 HIGH HOUSEKEEPING PAD
WITH PERIMETER CHAMFER
1 2B
2A
3A 3B 3C 3D
EQUIP. DEPTH
DIM. = 838
EQUIP. DEPTH
DIM. = 915
EQUIP. DEPTH
DIM. = 787
EP601
EC
TR
IC
AL
O
NE
-L
IN
E
DI
AG
RA
M
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
SCALE:A1 ELECTRICAL ONE-LINE DIAGRAM
NONE
GM
DIESEL GENERATOR A - 800 kW, 480Y/277V, 3PH, 4W, 60 Hz
GENERATOR
LOAD BANK
750 kW
MAINT.
BYPASS
A
MAINT.
BYPASS
B
PAD-MOUNTED TRANSFORMER - 750
kVA, 12.47 kV - 480Y/277V, 3PH, 4W, 903 FLA
PROVIDE ADDITIONAL LUGS AND
TAP TRANSFORMER SECONDARY
FOR FIRE PUMP FEEDER
1200/3
225 kVA
POWER
DISTRIBUTION
UNIT
PDU-1A
PROVIDE MANUAL SHUNT
TRIP CONTROL FROM EPO
PUSHBUTTON IN OPS RM
116FIRE
PUMP
CONTROLLER
WITH
INTERNAL
TRANSFER
31 HP
SP
AC
E
ON
LY
INTEGRAL 480V-208Y/120V
XFMR/PDU IN 116 OPS
EQUIPMENT RM, TYPICAL OF 5
350/3
XFMR TM1 - 75
kVA, 480V, 3PH PRI -
208Y/120V, 3PH, 4W SEC.
XFMR TP1 - 45
kVA, 480V, 3PH PRI -
208Y/120V, 3PH, 4W SEC.
60/3600/3
LSI
F12
F10
F9
F13
F3 F2
F7
F6
F6
F1
F16
F3 F3 F3 F3
F3F3
F14 F15 F14
F1 (4) 4 x 350 kCMIL+ 1 x #3/0 GND - 103 F2 3 x #4 + 1 x #8 GND - 35 F3 (2) 4 x 350 kCMIL+ 1 x #1 GND - 78 F4 3 x #12 + 1 x #12 GND - 16 F5 3 x #12 - 16 F6 3 x #1/0 + 1 x #6 GND - 53 F7 3 x #1/0 - 53 F8 4 x #2 + 1 x #8 GND - 41 F9 4 x #4/0 + 1 x #6 GND - 63 F10 3 x #2 + 1 x #6 GND - 41
F11 PROVIDED BY OTHERS; NOT IN SCOPE
F12 4 x #6 + 1 x #10 GND - 27 F13 4 x #1/0 + 1 x #6 GND - 53 F14 3 x 500 kCMIL + 1 x 3 GND - 91 F15 3 x #4/0 + 1 x #4 GND - 63 F16 3 x #4/0 (8kV) - 100
GM
DIESEL GENERATOR B - 800 kW, 480Y/277V, 3PH, 4W, 60 Hz
1200/3
1200/3
F1F1
F1
F1
F1
1600A, 480Y/277V, 3PH, 4W
GENERATOR SWITCHBOARD GS1
PORTABLE GENERATOR QUICK
DISCONNECT ENCLOSURE - 750 kW, 480Y/277V, 3PH, 4W
ONE-LINE DIAGRAM FEEDER SCHEDULE
ONE-LINE DIAGRAM NOTES
1 PROVIDE DIESEL GENERATOR B, WITH FEEDER AND CIRCUIT
BREAKER AS PART OF ADDITIVE BID OPTION NO. 1.
2 PROVIDE MINIMUM 20mm CONCRETE SURROUNDING FEEDER
CONDUIT.
3 SEE SWITCHBOARD ELEVATION AND SCHEDULE ON SHEET EP201.
ONE-LINE DIAGRAM IS DIAGRAMMATIC AND IS NOT INTENDED TO
INDICATE CIRCUIT BREAKERS IN INDIVIDUAL SECTIONS OF
SWITCHBOARD.
4 DISTRIBUTION PANELBOARD IN SECONDARY COMPARTMENT OF
POWER DISTRIBUTION UNIT (PDU), TYPICAL.
5 PORTION OF FEEDER RUN UNDERGROUND ON EXTERIOR OF
BUILDING IS SHOWN ON SITE PLAN AS UTILIZING 100 DIA DUCT.
6 1600A, 4P, SERVICE ENTRANCE-RATED, OPEN-TRANSITION
AUTOMATIC TRANSFER SWITCH.
7 PROVIDE RISER AT EXISTING UNLABELED UTILITY POLE AND
FUSED CUTOUTS AND TERMINATIONS NECESSARY TO CONNECT
TO EXISTING OVERHEAD 12.47 kV, 3PH PRIMARY CIRCUIT.
8 PROVIDE SHUNT TRIP TYPE CIRCUIT BREAKER.
9 LOCAL EMERGENCY SHUNT TRIP PUSHBUTTON FOR UPS
EQUIPMENT ROOM A OR B RESPECTIVELY.
PRESSURE
MAINTENANCE
(JOCKEY)
PUMP
CONTROLLER
1.5 HP
F5
F4
150 kVA
POWER
DISTRIBUTION
UNIT
PDU-2A
225 kVA
POWER
DISTRIBUTION
UNIT
PDU-1B
150 kVA
POWER
DISTRIBUTION
UNIT
PDU-2B
F15
TECH POWER A TO PFE 1
TECH POWER A TO PFE 2
TECH POWER A TO PFE 3
TECH POWER A TO PFE 4
TECH POWER A TO
MISSION CONFIGURABLE
TECH POWER B TO PFE 1
TECH POWER B TO PFE 2
TECH POWER B TO PFE 3
TECH POWER B TO PFE 4
TECH POWER B TO
MISSION CONFIGURABLE
75 kVA
POWER
DISTRIBUTION
UNIT
PDU-AB
100A
STATIC
TRANSFER
SWITCH
STS-1
COMMS
MISSION
208Y/120V
ML112A
100A MLO
RM 112
F8
ML112
225A MCB
RM 112
MH112
600A MCB
RM 112
F12
LR109
60A MCB
RM 109
T110
60A MCB
RM 110
LR118
150A MCB
RM 118
L118
60A MCB
RM 118
F12
SP
AC
E
ON
LY
SP
AC
E
ON
LY
F11F11F11F11
F11
F10F10
208Y/120V208Y/120V 208Y/120V 208Y/120V
4 4
4 4
600/3 600/3
F10
480v480v
480v
480v480v
SPD
1200/3
LSIG 6
20/3 70/3 600/3
LSI
600/3
LSI
600/3
LSI
600/3
LSI
1200/3
LSIG
150/3
1200/3
LSIG
1200/3
LSIG
1200/3
LSIG
1200/3
LSIG
UPS PANEL A1 - 600A MCB,
480Y/277V, 3PH, 4W
UPS PANEL B1 - 600A MCB,
480Y/277V, 3PH, 4W
1600A MCB, 480Y/277V, 3PH, 4W SERVICE ENTRANCE SWITCHBOARD ES1
8 8
C
60/3
EXISTING
PANEL
AT GATE
HOUSE
600A MCB
350/3250/3 250/3100/3100/3
UPS A
400 KVA
480Y/277V
RM 117
UPS B
400 KVA
480Y/277V
RM 119
F12
12.47
F12
LR109
60A MCB
RM 109
CC
EP602
EC
TR
IC
AL
P
AN
EL
BO
AR
D
SC
HE
DU
LE
S
JO
IN
T M
A R
IT
IM
E F
A C
IL
IT
Y
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M S
C O
M M
A N
D
A
TL
A N
TI
C
150A MCB, 208Y/120V, 3 PHASE, 4 WIRE, 14 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
RECEPTACLES RM 118 9 20 12 1 2 12 20 10 RECEPTACLES CORR 111
RECEPTACLES RM 117 9 20 12 3 4 20 0 SPARE
RECEPTACLES RM 119 9 20 12 5 6 20 0 SPARE
SPARE 0 20 7 8 20 0 SPARE
SPARE 0 20 9 10 20 0 SPARE
SPARE 0 20 11 12 20 0 SPARE
SPARE 0 20 13 14 20 0 SPARE
SPARE 0 20 15 16 20 0 SPARE
SPARE 0 20 17 18 20 0 SPARE
SPACE ONLY 0 - 19 20 6 60 10 PANEL GL115
SPACE ONLY 0 - 21 10 SPACE ONLY
SPACE ONLY 0 - 23 10 SPACE ONLY
PANEL T110 22 60 6 25 26 6 60 22 PANEL LR109
8 29 16 18
TOTAL 31 17 25 32 29 18 TOTAL
TOTAL CONNECTED AMPSA:73 B: 46 C: 53
PANELBOARD LR118 SCHEDULE
60A MCB, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
SPARE 0 20 1 2 12 20 8 RECEPTACLES RM 107,8
SPARE 0 20 3 4 12 20 12 RECEPTACLES RM 100,2
RECEPTACLES RM 105 6 20 12 5 6 12 20 12 RECEPTACLES RM 109
RECEPTACLES RMS 103,4,5 6 20 12 7 8 12 20 8 RECEPTACLES RM 101
RECEPTACLES RM 105 9 20 12 9 10 12 20 8 RECEPTACLES RM 101
SPARE 0 20 11 12 20 0 SPARE
SPARE 0 20 13 14 20 0 SPARE
SPARE 0 20 15 16 20 0 SPARE
SPARE 0 20 17 18 20 0 SPARE
SPACE ONLY 0 - 19 20 - 0 SPACE ONLY
SPACE ONLY 0 - 21 22 - 0 SPACE ONLY
SPACE ONLY 0 - 23 24 - 0 SPACE ONLY
SPACE ONLY 0 - 25 26 - 0 SPACE ONLY
SPACE ONLY 0 - 27 28 - 0 SPACE ONLY
SPACE ONLY 0 - 29 30 - 0 SPACE ONLY
TOTAL 6 9 6 16 20 12 TOTAL
TOTAL CONNECTED AMPSA: 22 B: 29 C: 18
PANELBOARD LR109 SCHEDULE
60A MCB, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
RECEPTACLES RM 110 6 20 12 1 2 20 SPARE
SPARE 0 20 3 4 12 20 8 COMM CABINET 2
HVAC SPLIT SYSTEM 8 20 12 5 6 12 20 8 COMM CABINET 3
8 8 20 0 SPARE
SPARE 0 20 9 10 20 0 SPARE
SPARE 0 20 11 12 20 0 SPARE
SPACE ONLY 0 - 13 14 - 0 SPACE ONLY
SPACE ONLY 0 - 15 16 - 0 SPACE ONLY
SPACE ONLY 0 - 17 18 - 0 SPACE ONLY
TOTAL 14 0 8 0 8 8 TOTAL
TOTAL CONNECTED AMPSA: 14 B: 8 C: 16
PANELBOARD T110 SCHEDULE
60A MCB, 480Y/277, 3 PHASE, 4 WIRE, 22 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
LIGHTS - RMS 117,118,119 5 20 12 1 2 12 20 5 LIGHTS - RM 116
LIGHTS - RMS 112,113,114,115 4 20 12 3 4 12 20 5 LIGHTS - RM 116
LIGHTS - EXTERIOR WALL 3 20 12 5 6 12 20 5 LIGHTS - RM 116
LIGHTS - EXTERIOR WALL EAST 3 20 12 7 8 12 20 3 LIGHTS - RM 111
LIGHTS - RMS 1001,101 2 20 12 9 10 20 0 SPARE
LIGHTS - RMS 102,3,4,5,6,7,8 4 20 12 11 12 20 0 SPARE
LIGHTS - RMS 109, 110 4 20 12 13 14 20 0 SPARE
SPARE 0 20 15 16 20 0 SPARE
SPARE 0 20 17 18 20 0 SPARE
SPACE ONLY 0 - 19 20 - 0 SPACE ONLY
SPACE ONLY 0 - 21 22 - 0 SPACE ONLY
SPACE ONLY 0 - 23 24 - 0 SPACE ONLY
TOTAL 12 6 7 8 5 5 TOTAL
TOTAL CONNECTED AMPSA: 20 B: 11C: 12
PANELBOARD L118 SCHEDULE
600A MCB, 480Y/277V, 3 PHASE, 4 WIRE, 14 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
PDU-1A 271 350 500 1 2 4/0 250 181 PDU-2A
271 181
271 181
PDU-AB 90 125 2 7 8 0 SPACE ONLY
90 0 90 0
SPACE ONLY 0 - 13 14 - 0 SPACE ONLY
SPACE ONLY 0 - 15 16 - 0 SPACE ONLY
SPACE ONLY 0 - 17 18 - 0 SPACE ONLY
TOTAL 361 361 361 181 181 181 TOTAL
TOTAL CONNECTED AMPSA: 542 B: 542 C: 542
UPS PANELBOARD A SCHEDULE
600A MCB, 480Y/277V, 3 PHASE, 4 WIRE, 14 KAIC MINIMUM, SURFACE MOUNTED
LOAD SERVED LOAD (AMPS) BRKR WIRE CKT PHASE CKT WIRE BRKR LOAD (AMPS) LOAD SERVED
A B C TRIP SIZE NO. A B C NO. SIZE TRIP A B C
PDU-1B 271 350 500 1 2 4/0 250 181 PDU-2B
271 181
271 181
PDU-AB 90 125 2 7 8 0 SPARE
90 0 90 0
SPACE ONLY 0 - 13 14 - 0 SPACE ONLY
SPACE ONLY 0 - 15 16 - 0 SPACE ONLY
SPACE ONLY 0 - 17 18 - 0 SPACE ONLY
TOTAL 361 361 361 181 181 181 TOTAL
TOTAL CONNECTED AMPSA: 542 B: 542 C: 542
UPS PANELBOARD B SCHEDULE
PANELBOARD NOTES:
1 PROVIDE SHUNT TRIP CONTROL VIA ACTIVATION FROM EPO
PUSHBUTTON IN OPS RM 116.
2 POWER TO ONLY FLOW THROUGH ONE UPS PANEL AT A TIME, NOT
BOTH.
PANELBOARD NOTES:
1 PROVIDE SHUNT TRIP CONTROL VIA ACTIVATION FROM EPO
PUSHBUTTON IN OPS RM 116.
2 POWER TO ONLY FLOW THROUGH ONE UPS PANEL AT A TIME, NOT
BOTH.
11 2 2
| EL101 ELECTRICAL LIGHTING PLAN |
| EL501 LUMINAIRE DETAILS |
| EL502 LUMINAIRE DETAILS |
| EL601 LUMINAIRE SCHEDULE AND CONTROL TABLE |
| EP101 ELECTRICAL POWER PLAN |
| EP102 ELECTRICAL POWER PLAN - MECHANICAL EQUIPMENT |
| EP201 ELECTRICAL SWITCHBOARD GS1 ELEVATION AND SCHEDULE |
| EP202 ELECTRICAL SWITCHBOARD ES1 ELEVATION AND SCHEDULE |
| EP601 ELECTRICAL ONE-LINE DIAGRAM |
| EP602 ELECTRICAL PANELBOARD SCHEDULES |
| EP603 ELECTRICAL PANELBOARD SCHEDULES |
| EP604 PDU-1A PANELBOARD SCHEDULES |
| EP605 PDU-2A AND PDU-AB PANELBOARD SCHEDULES |
| 2026-01-28T16:59:54-0500 | |
| signature |
| 2026-01-28T16:59:54-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
| 2026-01-28T16:59:55-0500 | |
| signature |
File details come from the government source that posted it. Updated .