Attachment 9 - DWG - 05 - S.pdf
PDF 961 KB Posted
- Attached to
- Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
- Solicitation number
- 36C77625B0035
About this file
These are structural engineering drawings for the construction of a Sleep Disorder Clinic and Specialty Clinic at the VA Medical Center in Murfreesboro, Tennessee. The structural documents include detailed plans for a connector building and a canopy, with specifications for foundation design, roof framing, steel column base plates, and concrete slab construction. Key technical details include:
Structural specifications cover seismic design parameters (Seismic Design Category B), wind loads of 115 MPH, and concrete compressive strength requirements of 3,500-4,000 PSI. The project uses structural steel conforming to ASTM standards, with W-shapes, HSS sections, and anchor bolts specified. The foundation design is based on a Terracon soils report, with an allowable soil bearing pressure of 2,000 PSF, and requires removal of existing undocumented fill to a depth of 3-4 feet and replacement with compacted engineered fill. The structural system includes cantilevered column systems, ordinary steel moment frames, and detailed requirements for concrete reinforcement, welding, and steel connections.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CODES AND STANDARDS:
1. 2012 AND 2018 INTERNATIONAL BUILDING CODE
2. AMERICAN CONCRETE INSTITUTE, "BUILDING CODE REQUIREMENTS FOR REINFORCED
CONCRETE" (ACI 318)
3. AMERICAN CONCRETE INSTITUTE, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR
BUILDINGS" (ACI 301) LATEST ADOPTED EDITION.
4. AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "SPECIFICATIONS FOR THE DESIGN,
FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS" 13TH EDITION.
5. STEEL DECK INSTITUTE, "DESIGN MANUAL FOR COMPOSITE DECKS, FORM
DECKS, AND ROOF DECKS."
6. AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING CODE AWS D1.1."
7. MASONRY STANDARDS JOINT COMMITTEE,"BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES" (ACI 530/ASCE 5/TMS 402)
DESIGN LIVE LOADS:
1. ROOF GRAVITY LOAD_____________________20 PSF
2. WIND LOAD______________________________115 MPH (3-SEC. GUST)
SEISMIC DESIGN DATA:
Ss = 0.246 Fa = 1.30 Sds = 0.213 S1 = 0.124 Fv = 1.50 Sd1 = 0.124
SITE CLASSIFICATION = C
OCCUPANCY CATEGORY = II
SEISMIC DESIGN CATEGORY = B
BASIC STRUCTURAL SYSTEM = CANTILEVERED COLUMN SYSTEM
SEISMIC RESISTING SYSTEMS = ORDINARY STEEL MOMENT FRAME
RESPONSE MODIFICATION FACTOR R = 1.25
DEFLECTION AMPLIFICATION FACTOR Cd = 1.25
FOUNDATIONS:
1. FOUNDATION DESIGN IS BASED ON RECOMMENDATIONS CONTAINED IN THE SOILS REPORT
BY TERRACON, PROJECT NUMBER 18235258, DATED DEC 1, 2023. THE DESIGN PARAMETERS
ARE:
A. ALLOWABLE SOIL BEARING PRESSURE FOR SPREAD/STRIP FOOTINGS_______2,000 PSF
B. SITE GRADING:
a. ALL ORGANIC MATERIAL SHALL BE STRIPPED
b. EXPOSED SUBGRADE SHALL BE PROOFROLLED TO DETECT SOFT AREAS
c. PROOFROLLING SHALL BE DONE WITH A HEAVILY LOADED DOUBLE AXLE
DUMPTRUCK AND OBSERVED BY A GEOTECHNICAL ENGINEER
d. WHERE SOFT AREAS, ORGANIC MATERIAL, OR HIGHLY PLASTIC CLAYS ARE
ENCOUNTERED DURING THE PROOFROLLING, THE AREA SHALL BE UNDERCUT AND
REPLACED WITH COMPACTED ENGINEERED FILL PLACED IN LAYERS NOT TO EXCEED
8". THIS FILL SHALL BE COMPACTED TO A MINIMUM OF 98% STANDARD PROCTOR
DENSITY (ASTM D-698)
e. THE CONNECTOR BUILDING ADDITIONS ARE EXPECTED TO HAVE 3 TO 4 FEET OF
EXISTING UNDOCUMENTED FILL IN THE EXISTING SUBGRADE. THIS FILL IS TO BE
REMOVED AND REPLACED WITH ENGINEERED COMPACTED FILL FOR FOUNDATION
AND SLAB BEARING. ON-SITE GEOTECH SHOULD EVALUATE EXCAVATIONS TO
ENSURE ALL UNDOCUMENTED FILL HAS BEEN REMOVE AND EXPOSED SUBGRADE IS
READY FOR ENGINEERED.
2. THE FOOTING EXCAVATIONS SHALL BE MADE IN NEAT LINES AND SHALL BE FREE OF LOOSE
OR WET MATERIALS. CONCRETE MAY BE PLACED DIRECTLY AGAINST THE SOIL WITHOUT
FORMING.
3. FOOTINGS SHALL BE INSPECTED BY A SOILS ENGINEER PRIOR TO PLACING CONCRETE IN
ORDER TO ENSURE THAT THE BEARING SURFACES ARE CONSISTENT WITH DESIGN
RECOMMENDATIONS.
4. WHERE SOFT AREAS ARE ENCOUNTERED, THE AREA SHALL BE UNDERCUT AS REQUIRED
AND REPLACED WITH COMPACTED FILL OR CONCRETE. THE FILL SHALL BE PLACED IN
LAYERS NOT TO EXCEED 8" AND SHALL BE COMPACTED TO A MINIMUM OF 98% STANDARD
PROCTOR DENSITY (ASTM D-698).
5. FOOTINGS TO BEAR ON FIRM UNDISTURBED EARTH OR ON ENGINEERED FILL COMPACTED
TO 98% STANDARD PROCTOR, NOT ON DEBRIS OR TOPSOIL.
6. FLOOR DRAINS HAVE NOT BEEN SHOWN ON THE FOUNDATION PLAN. FLOORS SHALL BE
SLOPED TO DRAINS IN ACCORDANCE WITH THE REQUIREMENTS OF THE ARCHITECTURAL
AND PLUMBING DRAWINGS.
7. DEPTH OF PIERS SHOWN IS FOR BIDDING PURPOSES ONLY AND MAY VARY ACCORDING TO
THE ACTUAL FIELD CONDITIONS.
8. THE CONTRACTOR SHALL VERIFY DEPTHS OF PIERS BEFORE PIER STEEL IS CUT. PIER STEEL
SHALL BE DELIVERED TO THE JOB SITE IN STOCK LENGTHS
AND CUT AS REQUIRED.
9. BEARING STRATA SHOWN ON THE PIER DETAIL IS WEATHERED ROCK.
10. MINIMUM PENETRATION INTO THE BEARING STRATA SHALL BE 2'-0".
11. DUE TO THE PRESENCE OF GROUND WATER AND/OR CAVING SOILS, CASING OF SOILS MAY
BE REQUIRED.
12. CONCRETING OF INDIVIDUAL PIERS SHALL BE COMPLETED WITHIN 8 HOURS OF DRILLING.
13. THE CONTRACTOR SHALL MAKE ACCURATE MEASUREMENTS OF THE DEPTH OF
PENETRATION INTO THE BEARING STRATA TO BE ASSURED OF CONFORMANCE WITH THE
DEPTH OF PENETRATION REQUIRED AND SUBMIT A REPORT OF THE DEPTH OF
PENETRATION DRILLED TO THE ENGINEER.
14. GEOTECHNICAL ENGINEER SHALL INSPECT AND TEST EACH DRILLED PIER BOTTOM BY
DRILLING AND PROBING A MINIMUM OF ONE PERCUSSION HOLE (2" DIA.x 6'-0" DEEP) PER
DRILLED PIER TO CONFIRM BEARING MEDIUM MEETS OR EXCEEDS DESIGN PARAMETERS.
CONCRETE:
1. DETAILS OF EACH PROPOSED CONCRETE MIX SHALL BE SUBMITTED AND REVIEWED PRIOR
TO PLACING CONCRETE OF THAT MIX IN ACCORDANCE WITH CHAPTER 5 OF ACI 318-89R92
2. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS AS FOLLOWS:
A. FOUNDATIONS__________________________3500 PSI
B. INTERIOR SLAB ON GRADE_______________3500 PSI
C. EXTERIOR CONCRETE___________________4000 PSI
3. ALL REINFORCING STEEL SHALL BE DOMESTIC BILLET STEEL CONFORMING TO ASTM A-615, GRADE 60 (60,000 PSI YIELD POINT) EXCEPT THAT #3 BARS MAY BE ASTM A-615, GRADE 40
(40,000 PSI YIELD POINT).
4. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-1064.
5. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI STANDARD "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE", ACI 318 LATEST REVISION.
6. CONCRETE SHALL BE TESTED IN ACCORDANCE WITH AND AT THE FREQUENCY SPECIFIED IN
ACI 318, LATEST REVISION. ONE SLUMP TEST AND ONE AIR ENTRAINMENT SHALL BE TAKEN
FOR EACH SET OF TEST CYLINDERS TAKEN AS WELL AS THE TEMPERATURE RECORDED.
(NOTE THAT WATER SHALL NOT BE ADDED AT THE JOB SITE ALTERING THE APPROVED MIX
DESIGN)
7. REINFORCING BARS SHALL BE DETAILED AND BAR SUPPORTS AND SPACERS PROVIDED IN
ACCORDANCE WITH THE ACI DETAILING MANUAL (ACI-315) AND MANUAL OF STANDARD
PRACTICE BY THE CONCRETE REINFORCING STEEL INSTITUTE.
8. GRADE BEAM REINFORCEMENT SHALL BE CONTINUOUS WHERE POSSIBLE. SPLICE BOTTOM
BARS AT CENTERLINE OF SUPPORT AND SPLICE TOP BARS AT CENTERLINE OF SPAN.
MINIMUM LAP DIMENSIONS SHALL BE 30 BAR DIAMETERS WITH 2'-0" MINIMUM FOR TOP AND
BOTTOM REINFORCING AT MID-SPAN AND SUPPORT LOCATIONS RESPECTIVELY. ALL OTHER
LAP SPLICES SHALL BE LAP TENSION SPLICES(LTS).
9. PROVIDE CORNER BARS FOR BARS MEETING AT INTERSECTIONS. SIZE AND NUMBER OF
CORNER BARS SHALL BE EQUAL TO THE LARGER OF THE BAR INTERSECTING. MINIMUM LAP
DIMENSIONS SHALL BE 30 BAR DIAMETERS WITH 2'-0" MINIMUM.
10. REFERENCE ARCHITECTURAL AND MECHANICAL PLANS FOR VERIFICATION OF CAST-IN-
PLACE BOLTS, INSERTS, ANCHORS, SLAB LEAVE-OUTS, SLOPES, AND DEPRESSIONS.
11. SHOP DRAWINGS SHALL BE SUBMITTED PRIOR TO FABRICATION. REINFORCING BARS SHALL
BE DETAILED AND BAR SUPPORTS AND SPACERS PROVIDED IN ACCORDANCE WITH THE ACI
DETAILING MANUAL(ACI-315) AND MANUAL OF STANDARD PRACTICE BY THE CONCRETE
REINFORCING STEEL INSTITUTE.
12. MINIMUM LAP DIMENSIONS SHALL BE 48 BAR DIAMETERS WITH 2'-0" MINIMUM UNLESS NOTED
OTHERWISE.
13. CLEAR CONCRETE COVER FOR REINFORCING BARS:
FOOTINGS_____________________2" FORMED EDGES
FOOTINGS_____________________3" CAST AGAINST EARTH
GRADE BEAMS AND PIERS_______2"
BELOW GRADE WALLS__________2" EXTERIOR FACE
BELOW GRADE WALLS__________3/4" INTERIOR FACE
ABOVE GRADE WALLS__________3/4" BOTH FACES
SLABS________________________3/4"
MASONRY WALLS______________CENTER OF WALL (U.N.O.)
14. ALL CONCRETE SHALL BE VIBRATED WITH MECHANICAL VIBRATORS.
STRUCTURAL QUALITY ASSURANCE PLAN:
THIS STRUCTURAL QUALITY ASSURANCE PLAN IDENTIFIES THE RESPONSIBILITIES OF THE
CONTRACTOR AND THE SPECIAL INSPECTOR IN PERFORMING THE TESTING AND INSPECTION
OF THE WORK REQUIRED BY CHAPTER 17 OF THE BUILDING CODE THAT IS WITHIN THE SCOPE
OF THE STRUCTURAL ENGINEERING SERVICES FOR THIS PROJECT. REFER TO OTHER
PORTIONS OF THE CONSTRUCTION DOCUMENTS FOR TESTING AND INSPECTIONS REQUIRED OF
ARCHITECTURAL, MECHANICAL, ELECTRICAL, OR OTHER BUILDING COMPONENTS.
CONTRACTOR RESPONSIBILITIES
THE CONTRACTOR SHALL SUBMIT TO THE BUILDING OFFICIAL AND THE ARCHITECT A WRITTEN
STATEMENT OF RESPONSIBILITY THAT CONTAINS THE FOLLOWING:
1. ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED
WITHIN THIS STRUCTURAL QUALITY ASSURANCE PLAN.
2. ACKNOWLEDGEMENT THAT CONTROL SHALL BE EXERCISED TO OBTAIN CONFORMANCE
WITH THE CONSTRUCTION DOCUMENTS APPROVED BY THE BUILDING OFFICIAL.
3. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S ORGANIZATION, THE
METHOD AND FREQUENCY OF REPORTING, AND THE DISTRIBUTION OF REPORTS.
4. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S) EXERCISING SUCH CONTROL
AND THEIR POSITION(S) IN THE ORGANIZATION.
THE STRUCTURAL TESTING/INSPECTION AGENCY THAT IS TO ACT AS THE SPECIAL INSPECTOR
WILL BE HIRED BY THE CONTRACTOR.
CONTRACTOR SHALL PAY FOR ADDITIONAL STRUCTURAL TESTING/INSPECTION REQUIRED FOR
WORK OR MATERIALS NOT COMPLYING WITH THE CONSTRUCTION DOCUMENTS DUE TO
NEGLIGENCE OR NONCONFORMANCE AND SHALL PAY FOR ADDITIONAL STRUCTURAL
TESTING/INSPECTION REQUIRED FOR HIS CONVENIENCE.
CONTRACTOR IS RESPONSIBLE TO ENSURE THAT THE SPECIAL INSPECTOR IS PRESENT FOR ALL
WORK REQUIRING SPECIAL INSPECTION. ANY WORK THAT REQUIRES SPECIAL INSPECTION AND
IS PERFORMED WITHOUT THE SPECIAL INSPECTOR BEING PRESENT IS SUBJECT TO BEING
DEMOLISHED AND RECONSTRUCTED.
CONTRACTOR HAS THE FOLLOWING RESPONSIBILITIES TO THE SPECIAL INSPECTOR:
1. PROVIDE COPY OF CONSTRUCTION DOCUMENTS TO THE SPECIAL INSPECTOR.
2. NOTIFY THE SPECIAL INSPECTOR SUFFICIENTLY IN ADVANCE OF OPERATIONS TO ALLOW
ASSIGNMENT OF PERSONNEL AND SCHEDULING OF TESTS.
3. COOPERATE WITH SPECIAL INSPECTOR AND PROVIDE ACCESS TO WORK.
4. PROVIDE SAMPLES OF MATERIALS TO BE TESTED IN REQUIRED QUANTITIES.
5. PROVIDE STORAGE SPACE FOR THE SPECIAL INSPECTOR'S EXCLUSIVE USE, SUCH AS FOR
STORING AND CURING CONCRETE TESTING SAMPLES.
6. PROVIDE LABOR TO ASSIST THE SPECIAL INSPECTOR IN PERFORMING TESTS/INSPECTIONS.
SPECIAL INSPECTOR RESPONSIBILITIES
SPECIAL INSPECTOR SHALL MAINTAIN RECORDS OF INSPECTIONS IN ACCORDANCE WITH
CHAPTER 17 OF THE BUILDING CODE AND SHALL DISTRIBUTE THESE RECORDS TO THE
BUILDING OFFICIAL, ARCHITECT, AND STRUCTURAL ENGINEER ON A WEEKLY BASIS. AT THE
CONCLUSION OF THE PROJECT THE SPECIAL INSPECTOR SHALL SUBMIT A WRITTEN STATEMENT
THAT THE SPECIAL INSPECTIONS DURING CONSTRUCTION HAVE COMPLIED WITH THIS
STRUCTURAL QUALITY ASSURANCE PLAN AND THAT ANY DISCREPANCIES NOTED DURING
CONSTRUCTION HAVE BEEN CORRECTED.
NON-SHRINK GROUT UNDER STEEL BASE PLATES
SPECIAL INSPECTOR SHALL PERFORM THE FOLLOWING:
1. COMPRESSIVE STRENGTH TESTS PER ASTM C109.
2. NUMBER OF TESTS: ONE TEST FOR EACH TEN BAGS OF GROUT USED OR MINIMUM OF ONE
TEST FOR EACH DAY OF GROUTING.
3. CUBE SIZE: 2-INCH X 2-INCH.
4. TEST SCHEDULE: ONE CUBE AT 3 DAYS, TWO CUBES AT 7 DAYS, THREE CUBES AT 28 DAYS.
STRUCTURAL STEEL
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. SUBMIT CERTIFICATION THAT THE FABRICATOR IS REGISTERED AND APPROVED BY THE
BUILDING OFFICIAL TO PERFORM REQUIRED WORK WITHOUT SPECIAL INSPECTIONS.
2. IF FABRICATOR IS NOT REGISTERED AND APPROVED, SPECIAL INSPECTION OF THE
FABRICATED ITEMS SHALL BE REQUIRED. SPECIAL INSPECTOR SHALL VERIFY THAT THE
FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES
THAT PROVIDE A BASIS FOR INSPECTION CONTROL OF THE WORKMANSHIP AND THE
FABRICATOR'S ABILITY TO CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND
REFERENCED STANDARDS. SPECIAL INSPECTOR SHALL REVIEW THE PROCEDURES FOR
COMPLETENESS AND ADEQUACY RELATIVE TO THE CODE REQUIREMENTS FOR THE
FABRICATOR'S SCOPE OF WORK.
3. SUBMIT CERTIFIED MILL TEST REPORTS FOR STRUCTURAL STEEL.
4. SUBMIT MANUFACTURER'S CERTIFICATE OF COMPLIANCE FOR HIGH-STRENGTH BOLTING
AND WELD FILLER MATERIALS.
SPECIAL INSPECTOR SHALL PERFORM THE FOLLOWING:
1. INSPECTION OF THE STEEL FRAME TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON
THE APPROVED CONSTRUCTION DOCUMENTS INCLUDING MEMBER LOCATIONS, BRACING,
CONNECTION DETAILS, ETC.
2. PROVIDE CONTINUOUS INSPECTION TO VERIFY COMPLIANCE OF THE FOLLOWING:
A. COMPLETE AND PARTIAL PENETRATION GROOVE WELDS. ULTRASONICALLY INSPECT
100% OF THE COMPLETE PENETRATION WELDS.
B. MULTI-PASS FILLET WELDS AND SINGLE-PASS FILLET WELDS GREATER THAN 5/16".
3. PROVIDE PERIODIC INSPECTION TO VERIFY COMPLIANCE OF THE FOLLOWING:
A. MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS, AND WASHERS.
B. MATERIAL VERIFICATION OF WELD FILLER MATERIAL.
C. VERIFICATION OF ANCHOR ROD SIZE, CONFIGURATION, AND EMBEDMENT PRIOR TO
PLACEMENT OF CONCRETE.
D. VISUALLY INSPECT ALL BOLTED CONNECTIONS IN ACCORDANCE WITH AISC
SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS. PRIOR TO
VISUAL AND PHYSICAL TESTING, TENSION TESTING USING A CALIBRATION DEVICE
(SKIDMORE-WILHELM) MUST INDICATE TENSIONS AT LEAST 5% IN EXCESS OF THE AISC
MINIMUM. STRUCTURAL STEEL ERECTOR SHALL SUPPLY THE TENSION CALIBRATION
DEVICE. TEST A MINIMUM OF 10% OF THE BOLTED CONNECTIONS.
E. VISUALLY INSPECT ALL FIELD-WELDED CONNECTIONS. VISUAL INSPECTION OF WELDED
JOINTS INCLUDES PERIODIC EXAMINATION OF FITUP.
F. VERIFY STUD SHEAR CONNECTOR SPACING AND LOCATIONS. VISUALLY INSPECT
WELDING OF STUD SHEAR CONNECTORS.
4. WELD INSPECTIONS TO INCLUDE THE FOLLOWING:
A. WELD INSPECTIONS SHALL BE IN ACCORDANCE WITH AWS D1.1.
B. REVIEW AND VERIFY COMPLIANCE OF WRITTEN WELDING PROCEDURES WITH AWS
REQUIREMENTS.
C. VERIFY THAT WELDING PROCEDURES ARE BEING ADHERED TO DURING FIELD WELDING.
D. VERIFY WELDER QUALIFICATIONS.
E. USE ALL MEANS NECESSARY TO DETERMINE THE QUALITY OF WELDS. THE INSPECTOR
MAY USE GAMMA RAY, MAGNAFLUX, TREPANNING, SONICS OR ANY OTHER AID TO VISUAL
INSPECTION THAT THE SPECIAL INSPECTOR MAY DEEM NECESSARY TO BE ASSURED OF
THE ADEQUACY OF THE WELDING.
F. KEEP A SYSTEMATIC RECORD OF ALL WELDS THAT INCLUDES, IN ADDITION TO OTHER
REQUIRED RECORDS, THE IDENTIFICATION MARKS OF WELDERS, A LIST OF DEFECTIVE
WELDS, AND THE MANNER OF CORRECTING DEFECTS.
5. THE SPECIAL INSPECTOR SHALL FURNISH THE ARCHITECT, STRUCTURAL ENGINEER,
CONTRACTOR, AND THE LOCAL BUILDING AUTHORITY WITH A REPORT THAT ALL WELDING IS
IN CONFORMANCE WITH THE APPROVED STRUCTURAL DOCUMENTS AND HAS BEEN DONE IN
ACCORDANCE WITH AWS D1.1, STRUCTURAL WELDING CODES.
STEEL DECK
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. SUBMIT MILL CERTIFICATION THAT THE SUPPLIED STEEL COMPLIES WITH THE
SPECIFICATIONS.
2. SPECIAL INSPECTOR SHALL PERFORM PERIODIC INSPECTIONS OF THE FOLLOWING:
3. VERIFY GENERAL ALIGNMENT AND DECK LAP.
4. VERIFY WELDS FOR SIZE AND PATTERN.
5. VERIFY SPACING AND TYPE OF SIDELAP ATTACHMENTS.
6. VERIFY INSTALLATION DECK CLOSURES.
SOIL:
SPECIAL INSPECTOR SHALL PERFORM THE FOLLOWING:
1. VERIFY STRUCTURAL FILL COMPLIES WITH THE PROJECT SPECIFICATIONS AND THE
GEOTECHNICAL REPORT.
2. OBSERVE PROOF-ROLLING AND UNDERCUTTING WHERE REQUIRED.
3. OBSERVE AND VERIFY THAT PLACEMENT OF STRUCTURAL FILL COMPLIES WITH THE
PROJECT SPECIFICATIONS AND THE GEOTECHNICAL REPORT.
4. PERFORM FIELD DENSITY TESTS TO VERIFY COMPACTION OF STRUCTURAL FILL. AS A
MINIMUM, PERFORM ONE TEST PER LIFT FOR EVERY 2,500 SQUARE FEET OF FILL PLACED.
5. VERIFY FOUNDATION BEARING CAPACITY.
CAST-IN-PLACE CONCRETE
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. SUBMIT MILL TEST REPORTS.
2. SUBMIT MANUFACTURER'S DATA FOR TENSILE AND COMPRESSIVE SPLICERS.
3. ESTABLISH CONCRETE MIX DESIGN PROPORTIONS PER ACI 318, CHAPTER 5. SUBMIT
THREE COPIES OF THE CONCRETE MIX DESIGNS. INCLUDE THE FOLLOWING:
A. TYPE AND QUANTITIES OF MATERIALS.
B. SLUMP
C. AIR CONTENT
D. FRESH UNIT WEIGHT
E. AGGREGATES SIEVE ANALYSIS
F. DESIGN COMPRESSIVE STRENGTH
G. LOCATION OF PLACEMENT IN STRUCTURE
H. METHOD OF PLACEMENT
I. METHOD OF CURING
J. SEVEN-DAY AND 28-DAY COMPRESSIVE STRENGTHS
4. SUBMIT A CERTIFICATION FROM EACH MANUFACTURER OR SUPPLIER STATING THAT
MATERIALS MEET THE REQUIREMENTS OF THE SPECIFIED ASTM AND ACI STANDARDS.
5. SUBMIT CERTIFICATION THAT THE READY-MIXED CONCRETE PLAN COMPLIES WITH THE
REQUIREMENTS OF THE NATIONAL READY MIX CONCRETE ASSOCIATION.
SPECIAL INSPECTOR SHALL PERFORM THE FOLLOWING:
1. VERIFY GRADE, QUANTITY, LOCATION, AND PLACEMENT OF REINFORCING STEEL PRIOR TO
CONCRETE PLACEMENT.
2. EXAMINE CONCRETE IN TRUCK TO VERIFY THAT CONCRETE APPEARS PROPERLY MIXED.
3. PERFORM A SLUMP TEST AS DEEMED NECESSARY FOR EACH CONCRETE LOAD. RECORD IF
WATER OR ADMIXTURES ARE ADDED TO THE CONCRETE AT THE JOB SITE. PERFORM
ADDITIONAL SLUMP TESTS AFTER JOB SITE ADJUSTMENTS.
4. MOLD FOUR SPECIMENS PER SET FOR COMPRESSIVE STRENGTH TESTING; ONE SET FOR
EACH 75 CUBIC YARDS OF EACH MIX DESIGN PLACED IN ANY ONE DAY. FOR EACH SET
MOLDED, RECORD:
A. SLUMP
B. AIR CONTENT
C. UNIT WEIGHT
D. TEMPERATURE, AMBIENT AND CONCRETE
E. LOCATION OF PLACEMENT
F. ANY PERTINENT INFORMATION, SUCH AS ADDITION OF WATER, ADDITION OF
ADMIXTURES, ETC.
PERFORM ONE 7-DAY AND TWO 28-DAY COMPRESSIVE STRENGTH TESTS. (USE ONE AS
A SPARE TO BE BROKEN AS DIRECTED BY THE STRUCTURAL ENGINEER IF COMPRESSIVE
STRENGTHS DO NOT APPEAR ADEQUATE.
5. REPORTS OF COMPRESSIVE STRENGTH TESTS SHALL CONTAIN THE PROJECT
IDENTIFICATION NAME AND NUMBER, DATE OF CONCRETE PLACEMENT, NAME OF CONCRETE
TESTING AGENCY, CONCRETE DESIGN COMPRESSIVE STRENGTH, LOCATION OF CONCRETE
PLACEMENT IN STRUCTURE, CONCRETE MIX PROPORTIONS AND MATERIALS, COMPRESSIVE
BREAKING STRENGTH AND TYPE OF BREAK.
6. VERIFY THE DRY WEIGHT OF THE LIGHTWEIGHT AGGREGATES AND THE FIVE-DAY
SATURATED WEIGHT OF THE AGGREGATE, AND VERIFY THAT AGGREGATES ARE BEING
PROPERLY PRESOAKED PRIOR TO BATCHING CONCRETE.
7. MONITOR PLACEMENT OF STRUCTURAL LIGHTWEIGHT CONCRETE PLACED BY PUMPING.
CONCRETE MASONRY
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. SUBMIT A CERTIFICATION FROM EACH MANUFACTURER OR SUPPLIER STATING THAT THE
FOLLOWING MATERIALS COMPLY WITH THE SPECIFIED ASTM OR ACI STANDARDS:
A. CONCRETE MASONRY UNITS.
B. MORTAR MATERIALS: PORTLAND CEMENT, HYDRATED LIME, AND AGGREGATES.
C. GROUT MATERIALS: PORTLAND CEMENT AND AGGREGATES.
D. JOINT REINFORCEMENT STEEL.
E. REINFORCING STEEL.
2. FOR REINFORCING STEEL USED IN CONCRETE MASONRY WALLS, SUBMIT CERTIFIED MILL
TEST REPORTS.
SPECIAL INSPECTOR SHALL PERFORM THE FOLLOWING:
1. VERIFY COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS, MORTAR, AND COARSE
GROUT FOR EVERY 5,000 SQ. FT. OF SURFACE AREA AS FOLLOWS:
A. THREE (3) CONCRETE MASONRY UNITS SHALL BE TESTED IN ACCORDANCE WITH ASTM
C140.
B. SIX (6) MORTAR CUBE SPECIMENS SHALL BE TESTED, THREE (3) AT 7-DAYS AND THREE
(3) AT 28-DAYS, IN ACCORDANCE WITH ASTM C780.
C. FOUR (4) COARSE GROUT SPECIMENS SHALL BE TESTED, TWO (2) AT 7-DAYS AND TWO
(2) AT 28 DAYS, IN ACCORDANCE WITH ASTM C1019.
D. IN LIEU OF INDIVIDUAL TESTS OF MASONRY UNITS, MORTAR, AND GROUT, PERFORM ONE
(1) PRISM TEST (WHICH CONSISTS OF THREE PRISMS) IN ACCORDANCE WITH ASTM
C1388.
2. PROVIDE CONTINUOUS INSPECTION TO VERIFY COMPLIANCE OF THE FOLLOWING:
A. CLEANLINESS OF GROUT SPACE PRIOR TO GROUTING.
B. PLACEMENT OF GROUT IN REINFORCED CELLS.
C. PREPARATION OF REQUIRED GROUT AND MORTAR SPECIMENS.
D. TYPE, SIZE AND LOCATION OF ANCHORS.
E. WELDING OF REINFORCING BARS.
3. PROVIDE PERIODIC INSPECTION TO VERIFY COMPLIANCE OF THE FOLLOWING:
A. PROPORTIONS OF SITE-PREPARED MORTAR OR GROUT.
B. CONSTRUCTION OF MORTAR JOINTS.
C. QUANTITY, SIZE, LOCATION, AND SUPPORT OF REINFORCING STEEL.
D. QUANTITY, SIZE, AND PLACEMENT OF HORIZONTAL JOINT REINFORCEMENT.
E. PROTECTION OF MASONRY DURING COLD OR HOT WEATHER.
STRUCTURAL MASONRY:
1. BLOCK UNITS: ASTM C90 LIGHT-WEIGHT UNITS WITH OVEN DRY DENSITY OF 85 TO 105 LBS
PER CUBIC FOOT. PROVIDE CONCRETE MASONRY UNITS WITH A 28-DAY COMPRESSIVE
STRENGTH ON NET AREA OF 1,700 PSI MINIMUM FOR INDIVIDUAL UNITS AND 1,900 FOR THE
AVERAGE OF THREE UNITS. FOLLOW ASTM C140 FOR NET AREA CALCULATIONS.
2. MORTAR SHALL CONFORM TO ASTM C-270 AND C-780 WITH A MINIMUM COMPRESSIVE
STRENGTH OF 1800 PSI UNDER FIELD TEST (ASTM C-780) @ 28 DAYS (TYPE S MORTAR).
3. COARSE GROUT SHALL CONFORM TO ASTM C-476 WITH A MAXIMUM AGGREGATE SIZE OF
3/8" AND A MINIMUM COMPRESSIVE STRENGTH OF 2500 PSI.
4. VERTICAL BARS SHALL BE HELD IN POSITION AT TOP AND BOTTOM AT INTERVALS NOT
EXCEEDING 8'-0" WITH A MINIMUM CLEARANCE OF 1/4" FROM THE MASONRY, AND NOT LESS
THAN ONE BAR DIAMETER BETWEEN BARS.
5. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL CORE, IT SHALL NOT BE
SLOPED MORE THAN ONE HORIZONTAL TO SIX VERTICAL. DOWELS SHALL BE GROUTED INTO
A CORE IN VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN ADJACENT CELL TO THE
VERTICAL WALL REINFORCING.
6. HORIZONTAL REINFORCING BARS SHALL BE PLACED IN THE CONTINUOUS MASONRY
COURSES CONSISTING OF BOND BEAM UNITS AND SHALL BE SOLIDLY GROUTED IN PLACE.
7. REINFORCING BARS SHALL BE STRAIGHT EXCEPT FOR BENDS AROUND CORNERS AND
WHERE BENDS AND HOOKS ARE DETAILED ON THE PLANS.
8. REINFORCING STEEL SHALL BE LAPPED 48 BAR DIAMETERS WITH 2'-0" MINIMUM WHERE
SPLICED AND SHALL BE WIRED TOGETHER.
9. HORIZONTAL WALL REINFORCEMENT SHALL BE LAPPED AT LEAST 6" AT SPLICES AND SHALL
CONTAIN AT LEAST ONE CROSS WIRE FOR EACH PIECE OF REINFORCEMENT IN THE LAPPED
DISTANCE.
10. WHERE CMU WALLS ABUT CONCRETE COLUMNS OR WALLS, DOVETAIL SLOTS SHALL BE
CAST INTO CONCRETE TO RECEIVE TRIANGULAR WEB TIES IN THE CMU BED JOINTS AT 8" ON
CENTER.
11. VERTICAL REINFORCING BARS MAY BE SPLICED IN 6'-0" TO 8'-0" LENGTHS PROVIDED THE
SPLICES IN ADJACENT BARS ARE STAGGERED AND ARRANGED SO NOT MORE THAN 1/3 OF
THE TOTAL NUMBER OF BARS ARE SPLICED AT ANY LOCATION AT MID-HEIGHT OF THE WALL
OR PILASTER (BETWEEN POINTS OF LATERAL BRACING). MINIMUM LAP AT SPLICES SHALL BE
48 BAR DIAMETERS. ALL BARS SHALL BE TIED AT SPLICES.
12. VERTICAL FOUNDATION DOWELS SHALL BE PROVIDED AT EACH PILASTER LOCATION AND
OTHER LOCATIONS WHERE VERTICAL REINFORCING IS SPLICED AND PROJECT 48 BAR
DIAMETERS OUT OF THE FOUNDATION. THESE DOWELS SHALL BE EQUAL IN NUMBER AND
SIZE TO THE SPECIFIED REINFORCEMENT.
13. MORTAR AND GROUT FOR MASONRY SHALL BE MIXED TO THE EXACT PROPORTIONS
ESTABLISHED BY THE MIX DESIGN. MASONRY CONTRACTOR SHALL PROVIDE CONTAINERS
CONSTRUCTED TO THE REQUIRED SIZES FOR EACH INGREDIENT.
14. VERTICAL REINFORCING SHALL BE #5 BARS AT A MAXIMUM SPACING OF 48" O.C. UNLESS
NOTED OTHERWISE ON DRAWINGS. THE FIRST CELL AT CORNERS AND ENDS OF WALLS
SHALL BE REINFORCED WITH 1-#5 AND GROUTED. 1-#5 (EXTENDING 2'-0" BEYOND CORNERS)
SHALL BE PLACED ON ALL SIDES OF WALL OPENINGS.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL W-SHAPES SHALL CONFORM TO ASTM A-992. STRUCTURAL STEEL M, S,
AND CHANNEL SHAPES SHALL CONFORM TO ASTM A572 GRADE 50 STRUCTURAL STEEL
ANGLES AND MISCELLANEOUS PLATES, ETC. SHALL CONFORM TO ASTM A-36 UNLESS NOTED
OTHERWISE ON THE PLANS. ANCHOR BOLTS SHALL BE ASTM F1554, GRADE 36 UNLESS
NOTED OTHERWISE ON THE PLANS.
2. HOLLOW STEEL SECTIONS (HSS) SHALL CONFORM TO ASTM A-500, GRADE B.
3. STRUCTURAL STEEL SHALL CONFORM TO AISC "SPECIFICATIONS FOR THE DESIGN,
FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS" 13TH EDITION.
4. WELDED CONNECTIONS SHALL CONFORM TO THE AMERICAN WELDING SOCIETY
SPECIFICATIONS AND REQUIREMENTS, LATEST REVISIONS, E70XX ELECTRODES. ALL
WELDING SHALL COMPLY WITH THE "STRUCTURAL WELDING CODE" OF THE AWS D1.1.
5. STRUCTURAL BOLTS, NUTS, AND CIRCULAR WASHERS AND JOINTS SHALL CONFORM TO
ASTM A325. USE BEARING-TYPE BOLTS WITH THREAD ALLOWED ACROSS THE SHEAR PLANE.
6. PLATE SIZES, ANGLE SIZES, NUMBER AND SIZE OF BOLTS AND OR WELDS FOR
CONNECTIONS SHALL BE DESIGNED BY THE CONTRACTOR IN ACCORDANCE WITH THE
REQUIREMENTS OF PART 10 OF THE 13TH EDITION OF THE AISC MANUAL FOR THE SHEAR.
USE 55% OF THE TOTAL LOAD SHOWN IN THE BEAM TABLES IN PART 3 OF THE 13TH EDITION
OF THE AISC CODE FOR THE GIVEN BEAM SPAN AND STEEL GRADE FOR NON-COMPOSITE
BEAMS. USE THE REACTIONS AS SPECIFIED ON THE DRAWINGS FOR COMPOSITE BEAMS.
7. ALL STEEL EXPOSED TO EXTERIOR ELEMENTS SHALL BE GALVANIZED.
8. NO SHOP OR FIELD SPLICES SHALL BE ALLOWED IN ANY BEAMS, GIRDERS, OR COLUMNS AT
LOCATIONS OTHER THAN THOSE SHOWN ON THE DRAWINGS.
9. VERIFY EXACT SIZE AND LOCATION OF MECHANICAL OPENINGS WITH EQUIPMENT TO BE
USED.
10. ANY DEVIATION FROM, ADDITION TO, SUBSTITUTION FOR, OR MODIFICATION TO THE
STRUCTURE OR ANY PART OF THE STRUCTURE DETAILED ON THESE CONTRACT
DOCUMENTS SHALL BE SUBMITTED, IN WRITING, TO THE ENGINEER FOR HIS REVIEW. SHOP
DRAWINGS THAT ARE SUBMITTED TO THE ENGINEER FOR HIS REVIEW DO NOT CONSTITUTE
"IN WRITING" UNLESS IT IS BROUGHT TO THE ATTENTION OF THE ENGINEER THAT SPECIFIC
CHANGES ARE BEING SUGGESTED.
11. SEE SERIES OF SHEETS LABELED S4 FOR TYPICAL DETAILS LABELED AS SUCH AND NOT
REFERRED TO EXCEPT HEREIN. OBSERVE ALL THE REQUIREMENTS OF THESE DETAILS TO
THE SAME EXTENT AS THAT GIVEN TO ALL OTHER DETAILS.
12. UNLESS NOTED OTHERWISE, STEEL BEAMS SHALL BEAR 16" ON MASONRY AND BE
ANCHORED WITH 2- 3/4" DIAMETER ROUND ANCHOR BOLTS.
13. ALL EPOXY ANCHORS INTO CMU OR CONCRETE SHALL BE HILTI HIT HY 200 ADHESIVE
ANCHORS (OR EQUAL) UNLESS SPECIFICALLY NOTED OTHERWISE ON THE STRUCTURAL
DRAWINGS. NOTE THAT ANCHORS INTO CMU SHALL BE LOCATED AT EITHER VERTICALLY
GROUTED CELLS OR AT HORIZONTAL BOND BEAMS. ADHESIVE ANCHOR INSTALLERS SHALL
BE CERTIFIED BY THE ACI/CRSI CERTIFICATION PROGRAM.
MECHANICAL, ELECTRICAL AND PLUMBING:
1. THE STRUCTURAL FRAMING HAS BEEN DESIGNED TO ACCOMMODATE 5 PSF HANGING
LOADS. THIS INCLUDES ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT,
DUCTWORK, PIPING, ETC. UNLESS NOTED OTHERWISE ON THE DRAWINGS. SINCE THE
MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS ARE DIAGRAMATIC, THE
CONTRACTOR SHALL ENSURE THAT THIS LOADING RESTRICTION IS ACCOMMODATED IN THE
MEP LAYOUT AND ROUTING.
2. THE HANGING LOAD RESTRICTION APPLIES TO EACH HANGER CONNECTION FOR THE
TRIBUTARY AREA OF THE FRAMING MEMBER
3. HANGERS NOT SPECIFIED IN THE MEP DRAWINGS AND SPECS. SHALL BE ACQUIRED FROM
THE MANUFACTURER AND RATED FOR THE APPLICATION OR THE DESIGN OF SUCH HANGER
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
4. THE ABOVE RESTRICTIONS SHALL BE CONSIDERED AND INCLUDED BY THE CONTRACTOR IN
THEIR BID.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
703 MAIN AVENUE SW
HICKORY, NC 28602
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /S tr u c tu ra l R e v it
.r v t
/2
/2
:2
:0
P
M
S1.00
STRUCTURAL NOTES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
BFC07/10/2024
626A4-21-101
BFC
100% CONSTRUCTION
DOCUMENTS
S T R U C T U R A L N O T E S Q U A L I T Y A S S U R A N C E
Revisions: Date:
A U
T O
D O
O R
A U
T O
D O
O R
A B
28'-9 3/4"
E O
S 1'
-0
T O
'-3
/8
3'
-0
'-1
1/
4" 3'
-0
'-1
1/
2" (U
.N .O
1'
-0
T O
E O
S
T O
E O
S 1'
-0
G R
ID
H
SS
8X 8X
3/
H
SS
8X 8X
3/
H S S 8X8X3/8
H
SS
8X 8X
3/
H S S 8X8X3/8
H S S 8X8X3/8
H S S 8X8X3/8H
S S 8X
8X 3/
TO EOS
1'-0" GRID
TO EOS
1'-0" GRID
TO EOS
1'-0" GRID
TO EOS
1'-0"
TO EOS
1'-0" GRID
T O
E O
S 1'
-0
T O
E O
S 1'
-2
/2
G R
ID
TYP. SLAB ON GRADE NOTE:
4" CONC. SLAB ON GRADE REINFORCED WITH
6x6-W2.9xW2.9 W.W.F. OVER 15 MIL VAPOR
BARRIER AND MIN. 4" COMPACTED DRAINAGE FILL
(TYP. U.N.O.)
TYP. SLAB ON GRADE NOTE:
4" CONC. SLAB ON GRADE REINFORCED WITH
6x6-W2.9xW2.9 W.W.F. OVER 15 MIL VAPOR
BARRIER AND MIN. 4" COMPACTED DRAINAGE FILL
(TYP. U.N.O.)3
S4.01
S4.01
F8/6 (-1'-4")
F7 1' -4
WF2.0WF2.0
WF2.0
W F
2.
W F
2.
W F
2.
W F
2.
WF2.0
EXTEND SLAB ON GRADE INTO EXISTING STOREFRONT OPENING TO ABUT
EXISTING BLDG SLAB. TURN SLAB DOWN ATOP EXISTING STRIP FOOTING
(IF EXISTING FTG OR STEM WALL IS NOT AVAILABLE FOR SLAB BEARING,
DRILL AND EPOXY #4x24" LONG DOWELS INTO EXISTING WITH 6" EMBED.)
S4.01
S4.01
S4.01
S4.01
S4.01
W F
2.
W F
2.
T O
E O
S 1'
-0
G R
ID
F7 1' -4
F7 1' -4
F7 (-1'-4")
10'-9 3/4" 7'-2 1/4" 10'-9 3/4"
3' -9
EQUAL REF. ARCH. EQUAL
F8/6 (-1'-4")
F8/
(-1 '-4
F8/6 (-1'-4")
A B
W X
W X
W16X40
W X
W X
W14X22
W14X22
W14X22
W14X22
W14X22
W14X22
ROOF DECK NOTE:
22 GA. 1-1/2" DEEP, TYPE "B" ROOF DECK
(GALVANIZED) WITH STEEL SUPPORTS
EQUALLY SPACED AS SHOWN WITH
6'-0" MAXIMUM SPACING
ROOF DECK NOTE:
22 GA. 1-1/2" DEEP, TYPE "B" ROOF DECK
(GALVANIZED) WITH STEEL SUPPORTS
EQUALLY SPACED AS SHOWN WITH
6'-0" MAXIMUM SPACING
T.O.S. ELEV. = 13'-0" A.F.F.
T.O.S. ELEV. = 13'-0" A.F.F.
1-1/2" EXPANSION JOINT
BETWEEN NEW AND EXIST.
(VERIFY DIMENSIONS)
28'-9 3/4"
'-3
/8
'-1
1/ 4"
'-1
1/
2"
PROVIDE HANGERS AND
KICKERS FOR SUPPORT OF
PRE-ENGINEERED CANOPY
4"
JO
IN
T
1/
2" E
X P
JO
IN
T
1/ 2"
E X
P
4"
F
IE
LD
V
E R
IF
Y F
IE
LD
V E
R
IF
Y
W14X22
W14X22
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
5 1/2"
1/
2"
5 1/2"
5 1/2" 5 1/2"
1/
2"
S4.51
S4.51
S4.51
S4.51
S4.51
S4.51
S4.51
W16X40
AT
RECESS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
703 MAIN AVENUE SW
HICKORY, NC 28602
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /S tr u c tu ra l R e v it
.r v t
/2
/2
:2
:0
P
M
S1.01
CONNECTOR FOUNDATION AND
ROOF FRAMING PLAN
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
BFC07/10/2024
626A4-21-101
BFC
100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"
CONNECTOR FOUNDATION PLAN
1/8" = 1'-0"
CONNECTOR ROOF FRAMING PLAN
EXISTING SUBGRADE PREP:
EXISTING UNDOCUMENTED SUBGRADE FILL MATERIALS
BENEATH THE PROPOSED NEW BUILDING ADDITIONS
SHALL BE REMOVED AND REPLACED WITH COMPACTED
ENGINEERED FILL. EXISTING FILL DPETHS ARE
EXPECTED TO BE 3 TO 4 FEET DEEP.
C D E
23'-0" 23'-0"
W
X74
W
X74
W
X74 F10 F10 F10
S4.01
C D E
W10X15
W10X15
W10X15
W10X15
W10X15
W10X15
W10X15
W X
W X
W X
23'-0" 23'-0"
STRUCTURAL ROOF DECK NOTE:
22 GA. 1-1/2" DEEP, TYPE "B" ROOF DECK
(GALVANIZED) WITH STEEL SUPPORTS
EQUALLY SPACED AS SHOWN WITH
6'-0" MAXIMUM SPACING
(REF. ARCH FOR DECK OVER TOP OF
STRUCTURAL DECKING)
1/ 2"
:1 2"
S
LO
P E
TOP OF STEEL BEAM ELEV = 14'-10" MIN
ABOVE ROADWAY THIS SIDE
E Q
E Q
E Q
6"
'-8
1' -0
11"
11"
TOP OF STEEL BEAM ELEV = 15'-6 3/8" MIN
ABOVE ROADWAY THIS SIDE
W10X15
VERTICAL FACE
OF BENT PLATE,
REF. DETAIL
S4.51
S4.51
S4.51
S4.51
DENOTED FULL PENETRATION
WELDED MOMENT CONNECTION
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
703 MAIN AVENUE SW
HICKORY, NC 28602
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /S tr u c tu ra l R e v it
.r v t
/2
/2
:2
:1
P
M
S1.02
CANOPY FOUNDATION AND ROOF
FRAMING PLAN
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
BFC07/10/2024
626A4-21-101
BFC
100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"
CANOPY FOUNDATION PLAN
1/8" = 1'-0"
CANOPY ROOF FRAMING PLAN
TYP. FORMED CONSTRUCTION JOINT
TYP. SAWN CONTROL JOINT
SMOOTH DOWEL SCHEDULE
"D
"D
P
LA
N S
E E
SMOOTH DOWELS
REF. SCHEDULE
SLAB REINFORCING
NOT CONTINUOUS
SLAB REINFORCING
CONTINUOUS
FILL JOINT WITH SEALANT.
CONTRACTOR TO GRIND
EDGES SMOOTH & STRAIGHT
PRIOR TO SEALING
FILL JOINT WITH SEALANT.
CONTRACTOR TO GRIND
EDGES SMOOTH & STRAIGHT
PRIOR TO SEALING
1/8" to 1/4" (BLADE THICKNESS)
SLAB DEPTH
(INCHES)
4 TO 6
7 TO 8
9 TO 11
DOWEL DIAMETER
(INCHES)
3/4
1 1/4
TOTAL DOWEL LENGTH
(INCHES)
DOWEL SPACING
ON CENTERS (IN.)
(4)-#5 BARSxCONT.
PLACE DOWELS AT MID-DEPTH OF THICKENED PORTION OF SLAB AND
HOLD IN PLACE WITH DOWEL BASKETS
NOTE: CONTROL JOINTS SHALL BE SPACED AT INTERVALS NOT TO EXCEED 12'-0" O.C. EACH
DIRECTION, WITH ENCLOSED AREA NOT TO EXCEED 144 SF. WHERE APPLICABLE , JOINTS
SHOULD BE LOCATED ON COLUMN CENTERLINES AND AT SLAB RE-ENTRANT CORNERS.
LENGTH TO WIDTH PROPORTIONS OF JOINT PATTERN SHALL NOT EXCEED 1.35:1. (TYPICAL
FOR ALL CONCRETE SLABS ON GRADE UNLESS NOTED OTHERWISE ON PLANS).
CONTRACTOR SHALL SUBMIT A SHOP DRAWING OF ANTICIPATED CONTROL JOINT
LOCATIONS FOR RECORD.
COORDINATE LOCATIONS OF CONST./CONTROL JOINTS WITH
ARCHITECTURAL FINISH SUCH AS TILE FLOORING.
4" M
IN
P
LA
N
R E
F
1'-4" 1'-4"
COLUMN
1/2" FIBER JOINT
MATERIAL (TYP.)
EXTERIOR FINISH
CONSTRUCTION JOINT
OR CONTROL JOINT
INTERIOREXTERIOR
M
IN
6"
M A
X
APPROX.
FIN. GRADE
FINISHED SLAB,
REF. FOUNDATION PLAN
FOR TYP. REINF.
METAL STUD WALL,
REF. ARCH.
#4 BARS AT 12" O.C.
(2)-#5xCONT.
COMPACTED
DRAINAGE FILL
GROUT VOID SOLID
BELOW GRADE (TYP.)
36"
BRICK, REF. ARCH.
REF. PLAN
2"
REF. SCHEDULE
S C
H E
D U
LE
R E
F
(U .N
.O
1' -4
M
IN
CENTER
OF FTG
M
IN
1' -4
M
IN
6"
M A
X
APPROX.
FIN. GRADE
FINISHED SLAB,
REF. FOUNDATION PLAN
FOR TYP. REINF.
METAL STUD WALL,
REF. ARCH.
(2)-#5xCONT.
COMPACTED
DRAINAGE FILL
REF. SCHEDULE
S C
H E
D
R E
F
CENTERLINE FOOTING AND COL.
STEEL COLUMN
REF. PLAN FOR SIZE
AND ORIENTATION
CONC. FOOTING, REF. PLAN
AND SCHEDULE
WALL FTG
BEYOND
GROUT VOID SOLID
BELOW GRADE (TYP.)
REF. PLAN
COLUMN BASE PLATE AND ANCHOR BOLT SCHEDULE
BASE PLATE
COLUMN
("A" x "B" x THICKNESS)
BASE PLATE SIZE
"C" GRADE/YIELD"D" DIAMETER
HSS8x8x3/8" 16" x 16" x 1-1/4" 6" 6" 36 1-1/4" F1554 GR 36 15"
W14x74 20" x 24" x 2" 7 1/2" 9 1/2" 50 1-3/4" F1554 GR 50 20"
COLUMN BASE PLATE ELEVATION
LE
N
G T
H
P R
O J.
**NOTE: USE 2 1/2" GROUT AT ANCHOR BOLTS > 1" DIA.
USE 3" GROUT AT ANCHOR BOLTS > 1 1/2" DIA
E M
B E
D
HEADED ANCHOR
BOLTS
C O
N C
BASE PLATE
LEVELING NUT
STEEL COL.
SEE FOUNDATION PLAN
2" N
O N
-S H
R
IN
K G
R O
U T
M
IL
L
T H
IC
K
N E
S S
BOLT HOLE SIZE AND PLATE WASHER THICKNESS
BOLT DIA. HOLE OVERSIZE (MAX.) PLATE WASHER (MIN.) THICKNESS
3/4" TO 1" 5/16" OVERSIZED HOLE 1/4"
1" TO 2" 1/2" OVERSIZED HOLE 1/2"
OVER 2" 1" OVERSIZED HOLE 3/4"
ANCHOR BOLTS
EMBEDMENTGRADE
HSS COLUMN BASE PLATE WF COLUMN BASE PLATE
PLAN VIEW PLAN VIEW
"D
"B
"C""C"
"A"
"D
"B
"D
"A"
"C""C"
"D
STEEL COLUMN,
REF. FOUNDATION PLAN BASE PLATE,
REF. SCHEDULE
TYP.
1/16" LESS THAN
COL'N THICKNESS
STEEL COLUMN,
SEE FOUNDATION PLAN
TYP.
ANCHOR BOLTS,
REF. SCHEDULE
75% OF FLANGE
AND WEB THICKNESS
AT WF COLUMN
BASE PLATE,
REF. SCHEDULE
ANCHOR BOLTS,
REF. SCHEDULE
FINISHED SLAB,
REF. CIVIL DWGS
8" CMU GROUTED SOLID,
REF. ARCH.
COMPACTED
DRAINAGE FILL
REF. SCHEDULE
S C
H E
D
R E
F
2' -0
CENTERLINE FOOTING AND COL.
STEEL COLUMN
REF. PLAN FOR SIZE
CONC. FOOTING, REF. PLAN
AND SCHEDULE
BRICK VENEER,
REF. ARCH.
GROUT VOID SOLID
WITH GROUT
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
703 MAIN AVENUE SW
HICKORY, NC 28602
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /S tr u c tu ra l R e v it
.r v t
/2
/2
:2
:1
P
M
S4.01
SECTIONS AND DETAILS CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
BFC07/10/2024
626A4-21-101
BFC
100% CONSTRUCTION
DOCUMENTS
3/4" = 1'-0"
TYP. SLAB CONSTRUCTION/CONTROL JOINT DETAIL
3/4" = 1'-0"
TYP. COLUMN ISOLATION JOINTS
3/4" = 1'-0"
TYP. EXTERIOR TURNDOWN AT STUD/BRICK
3/4" = 1'-0"
TYP. EXTERIOR COLUMN FOOTING
FOOTING SCHEDULE
MARK
SIZE SIZE
THICKNESS REINFORCING COMMENTSWIDTH LENGTH
F7 7'-0" 7'-0" 1'-6" (7)-#7 BARS EACH WAY - TOP AND BOTTOM
F8/6 8'-0" 6'-0" 1'-6" (8)-#7 TOP AND BOTTOM (SHORT WAY) AND (6)-#7 TOP AND BOTTOM (LONG WAY)
F10 10'-0" 10'-0" 2'-0" (10)-#9 BARS EACH WAY, TOP AND BOTTOM
WF2.0 2'-0" CONT. 1'-0" (3)-#5 BARS x CONT. AND #4 TRANSVERSE BARS AT 16" O.C.
WF3.0 3'-0" CONT. 1'-0" (4)-#5 BARS x CONT. AND #5 TRANSVERSE BARS AT 12" O.C.
3/4" = 1'-0"
BASE PLATE SCHEDULE/DETAILS
Revisions: Date:
3/4" = 1'-0"
TYP CANOPY COLUMN FOOTING
5/8" DIA. PUDDLE WELDS
AT 6" O.C. AT PERIMETER
SUPPORRTS
PERIMETER
SUPPORT
END SUPPORT
SUPPORT
INTERMEDIATE
INTERMEDIATE
SUPPORT
7-5/8" DIA. PUDDLE
WELDS AT END
SUPPORTS
1 1/2" SEAM WELDS
OR #10 TEK SCREWS
AT 24" O.C.
4-5/8" DIA. PUDDLE
WELDS PER SHEET
AFTER INTERMEDIATE
SUPPORTS
BUILDING PERIMETER AREA WELDS:
PROVIDE 5/8" DIA. PUDDLE WELDS AT 6" O.C. AT ALL
SUPPORTS WITHIN 15'-0" OF THE PERIMETER. (THIS
ATTACHMENT SHOULD EXTEND TO THE NEXT
SUPPORT IF 15'-0" FALLS BETWEEN SUPORTS)
TYP. ROOF OPENING FRAME
AT EQUIPMENT UP TO 500# MAX.
CENTERLINE SUPPORT
OPENING
REF. PLAN
L5x5x3/8
TYP.
L 6x4x1/4x0'-5" LLV
(TYPICAL)
CENTERLINE SUPPORT
3/16"
3/16"
TYP.
TYP. ROOF OPENING FRAME
AT EQUIPMENT GREATER THAN 500#
SEE PLAN
OPENING
C6x8.2
(TYP)
CENTERLINE SUPPORT
L 6x4x1/4x0'-5" LLV
(TYPICAL)
CENTERLINE SUPPORT
3/16"
3/16"
TYP.
REF. ARCH
FOR EIFS FINISH
SECTION PERPENDICULAR TO DECKING SECTION PARALLEL TO DECKING
REF. ARCH
FOR EIFS FINISH
METAL STUD PARAPET WALL,
REF. ARCH.
METAL STUD PARAPET WALL,
REF. ARCH.
STEEL BEAM,
REF. PLAN
1/4" BENT PLATE x CONT.
WELDED TO BEAM
METAL DECK,
REF. PLAN
3/8" GUSSET PLATES
AT 48" O.C.
REF. PLAN
STEEL BEAM,
REF. PLAN
1/4" BENT PLATE x CONT.
WELDED TO BEAM
METAL DECK,
REF. PLAN
3/8" GUSSET PLATES
AT 48" O.C.
3/8" GUSSET PLATE AT
EACH CHANNEL HANGER
(4'-0" O.C. MAX)
1/4" BENT PLATE
WELDED TO BEAM
METAL ROOF DECK,
REF. PLAN3/16" 3-12
3/16" 3-12 TYP. - BENT
PLATE TO
BEAM
L3x3x1/4" KICKERS AT
EACH HANGER
STL BM,
REF. PLAN
C6x8.2 HANGERS AT EACH CANOPY HANGER
AND AT 48" MAX. SPACING BETWEEN
(SISTER METAL STUDS TO CHANNELS AND INFILL
WIH STUDS AT 16" O.C.)
REF. PLAN
7"x7"x3/8" BENT PLATE (GALV.)
WELDED TO VERTICAL CHANNELS
FOR BRICK BELOW CANOPY
C6x8.2xCONT. WELDED TO EACH VERTICAL CHANNEL HANGER
(COORD. W/ ARCH AND STOREFRONT FOR USE OF BLOCKING
BETWEEN CHANNEL AND FRAME)
BRICK ROWLOCK COURSE, REF. ARCH.
STOREFRONT, REF. ARCH.
PRE-ENGINEERED CANOPY
BY CANOPY MANUF.
3/8" PLATE (HANGER TAB)
WELDED TO CHANNELS
(VERIFY WITH CANOPY VENDOR)
COORDINATE HOLE SIZE
WITH HANGER ROD
DECORATIVE PLATE
OVER HANGER TAB
ATTACH CANOPY DIRECTLY
TO VERTICAL CHANNELS
REF. ARCH
FOR EIFS FINISH
METAL STUD PARAPET WALL,
REF. ARCH.
STEEL BEAM,
REF. PLAN
1/4" BENT PLATE x CONT.
WELDED TO BEAM
METAL DECK,
REF. PLAN
3/8" GUSSET PLATES
AT 48" O.C.
DOORWAY, REF. ARCH.
BRICK ROWLOCK COURSE, REF. ARCH.
L4x4x3/8" (GALV.) LOOSE LINTEL WITH
12" MIN. BEARING EACH END
L4x4x3/8" (GALV.) LOOSE LINTEL WITH
12" MIN. BEARING EACH END
LIGHT GAGE HEADER AS
REQ'D FOR STUD SUPPORT
LIGHT GAGE HEADER
REF. PLAN
COMPLETE
PENETRATION
(PLT TO BM
FLANGE)
M
COMPLETE
PENETRATION
(TYP.)
M
STIFFENER PLATES TO
COLUMN FLANGE
THICKNESS AND GRADE
(TYP. EACH SIDE)
STEEL COLUMN,
REF. PLAN
REF. PLAN FOR TOP OF STEEL AT 5-LINE
3/8"
3/8" TYPICAL
(PLATE TO BM
WEB)
3 5/8" REF. PLAN
1/4" BENT PLATE
WELDED TO BEAM
AND GUSSET PLATES
REF. ARCH FOR FINISHES
STEEL BEAM,
(REF. PLAN FOR SIZE AND SLOPE)
STRUCTURAL METAL DECK, REF. PLAN
1/4":1' SLOPED STEEL
STEEL COLUMN BEYOND,
REF. PLAN
REF. PLAN FOR TOP
OF STEEL AT 5-LINE
3 5/8" REF. PLAN
1/4" BENT PLATE
WELDED TO BEAM
AND GUSSET PLATES
REF. ARCH
FOR FINISHES
STEEL BEAM BEYOND,
(REF. PLAN FOR SIZE AND SLOPE)
3/8" GUSSET PLATES
AT 32" O.C.
BRACE STUD BACK TO BEAM
WITH STUD FRAMING
1/4" BENT PLATE
WELDED TO BEAM
AND GUSSET PLATES
3/8" GUSSET PLATES
AT 32" O.C.
BRACE STUD BACK TO BEAM
WITH STUD FRAMING
REF. PLAN 3 5/8"
STRUCTURAL METAL DECK, REF. PLAN
3/
4"
STRUCTURAL ROOF DECKING,
REF. PLAN
1/4" BENT PLATE
WELDED TO BEAM
AND GUSSET PLATES
3 5/8" REF. PLAN
3/8" GUSSET PLATES
AT 32" O.C.
BRACE STUD BACK TO BEAM
WITH STUD FRAMING
REF. ARCH FOR FINISHES
REF. ARCH FOR ROOFING
STEEL BEAM,
(REF. PLAN FOR
SIZE AND SLOPE)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
703 MAIN AVENUE SW
HICKORY, NC 28602
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /S tr u c tu ra l R e v it
.r v t
/2
/2
:2
:1
P
M
S4.51
SECTIONS AND DETAILS CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
BFC07/10/2024
626A4-21-101
BFC
100% CONSTRUCTION
DOCUMENTS
3/4" = 1'-0"
TYP. ROOF DECK ATTACHMENT
3/4" = 1'-0"
DETAIL
3/4" = 1'-0"
DETAIL
3/4" = 1'-0"
TYP. SECTION AT ROOF EDGE AT EIFS
3/4" = 1'-0"
SECTION AT PRE-ENGR. CANOPY AT VESTIBULE
3/4" = 1'-0"
SECTION AT RECESSED DOORWAY
Revisions: Date:
3/4" = 1'-0"
SECTION AT CANTILEVERED CANOPY COLUMN
3/4" = 1'-0"
SECTION AT CANTILEVERED CANOPY
3/4" = 1'-0"
CANOPY DETAIL - SIDE OF CANOPY