Attachment 10 - DWG - 06 - M.pdf
PDF 15 MB Posted
- Attached to
- Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
- Solicitation number
- 36C77625B0035
About this file
The file is a set of mechanical engineering drawings for the VA Medical Center Sleep Disorder Clinic renovation project in Murfreesboro, Tennessee. The drawings comprehensively detail mechanical systems including ductwork, piping, equipment layouts, control sequences, and demolition plans across multiple building levels (basement, first floor, crawl space). Key technical elements include new HVAC equipment such as air handling units (AHUs), fan coil units, exhaust fans, variable air volume (VAV) terminal units, and associated control systems. The drawings specify detailed installation requirements for mechanical systems, including ductwork routing, piping connections, equipment mounting, and integration with the existing building infrastructure.
The mechanical design focuses on creating a comprehensive HVAC system for the Sleep Disorder Clinic, with specific attention to control strategies, air distribution, and system zoning. The design incorporates BACnet-compatible direct digital controls (DDC) that will integrate with the existing VA facility control system, allowing for remote monitoring and precise temperature and airflow management. The mechanical systems are designed to support the specialized clinical spaces, with considerations for air quality, temperature control, and energy efficiency. The project involves both new equipment installation and selective demolition of existing mechanical systems to accommodate the clinic renovation.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
BD
P
M
TS
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION
SYMBOL DESCRIPTION
200A
RHC-1-1
AHU-1
VTU-1-1
-PACKAGED TERMINAL AIR CONDITIONER
(PTAC)
-HYDRONIC REHEAT COIL
-NEW FLAT OVAL DUCT
-ELECTRIC DUCT HEATER
(W/ PANEL CLEARANCE)
-FLEXIBLE CONNECTION
-ACCESS DOORS, VERTICAL OR HORIZONTAL
-INLINE CENTRIFUGAL FAN
-STAINLESS STEEL DUCTWORK
-DOOR GRILLE
-UNDERCUT DOOR
-SPIN-IN TAKE-OFF
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE -RECTANGLE-TO-ROUND TAKE-OFF
DNUP
-TRANSITION, SQUARE TO ROUND
UP W/IN FLOORDOWN
-CEILING EXHAUST
-CEILING RETURN
24x12
-STANDARD BRANCH TAKE-OFF
-RADIUS ELBOW
-TRANSITION, ECCENTRIC
-FLEXIBLE DUCT
-CHANGE OF ELEVATION
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
-DUCT ELBOW, EXHAUST
DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
-TRANSITION, CONCENTRIC
-SQUARE THROAT ELBOW
W/TURNING VANES
-RECTANGULAR/ROUND BRANCH TAKE-OFF
OR ROUND/ROUND BRANCH TAKE-OFF
-SQUARE THROAT TEE
-RADIUS TEE
-ROUND DIFFUSER
-SUPPLY REGISTER OR GRILLE
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
(VERTICAL MOUNT, SIDEWALL)
-EXISTING DUCTWORK TO REMAIN
-EXISTING DUCTWORK TO BE REMOVED
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
-CEILING DIFFUSER, ROUND NECK
-CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4-WAY THROW UNO)
M-1
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-HUMIDISTAT/HUMIDITY SENSOR
-THERMOSTAT/TEMPERATURE SENSOR
-REVISION REFERENCE
-DETAIL REFERENCE: TOP-DETAIL#,
BOTTOM-DRAWING# SHOWN ON
-PRESSURE SENSOR
-DUCT SMOKE DETECTOR
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED
FF -FINAL FILTERS
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
P -CHANGE IN PRESSURE
CV -CONSTANT AIR VOLUME
-ROOFTOP AIR HANDLING UNITRTU
RS/L -REFRIGERANT SUCTION & LIQUID LINES
CL
-OUTSIDE AIR LOUVEROAL
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-ROOFTOP HEAT PUMPRHP
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-OUTSIDE AIROA
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-LINEAR DIFFUSERLD
-LEAVING WATER TEMPERATURELWT
-LEAVING AIR TEMPERATURELAT
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-FIRE DAMPER
-FAN COIL UNIT
-ENTERING WATER TEMPERATURE
-ENTERING AIR TEMPERATURE
-DOWN
-CONDENSING UNIT
-CUBIC FEET PER MINUTE
-CHANGE IN TEMPERATURE
-COOLING TOWER
-CEILING DIFFUSER
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ACCESS PANEL
-ABOVE FINISHED FLOOR
FPM
FD
FCU
EWT
EAT
DN
CU
CFM
T
CT
CD
BTU
BOP
BHP
AP
AFF
-AIR HANDLING UNITAHU
MBH -THOUSAND BTUs PER HOUR
AFD -ADJUSTABLE FREQUENCY DRIVE
ESP -EXTERNAL STATIC PRESSURE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
UNO
TSP -TOTAL STATIC PRESSURE
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-UNLESS NOTED OTHERWISE
FLA -FULL LOAD AMPS
-CONTROL VALVE
-45° PIPE RISE (R) / DROP (D)
-CONDENSER WATER SUPPLY
-CONDENSER WATER RETURN
-CHILLED WATER SUPPLY
-CHILLED WATER RETURN
-CONDENSATE
-HOT WATER RETURN
-HOT WATER SUPPLY
-REFRIGERANT LIQUID
-REFRIGERANT SUCTION
-VALVE ON RISER
-CAP
-CONNECTION, BOTTOM
-CONNECTION, TOP
-COUPLING
-ELBOW, 90°
-ELBOW, 45°
-ELBOW, TURNED DOWN
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
-TEE, OUTLET UP
CWS
CWR
CHWS
CHWR
RL
RS
-FLOW SWITCH
-CHECK VALVE
-PSI REG.
-SOLENOID VALVE
-STRAINER
-GAS COCK
-BUTTERFLY VALVE
-CALIBRATING BALANCING VALVE
-BALL VALVE
-GATE VALVE
-UNION
PC -PUMPED CONDENSATE
DD
-HIGH PRESSURE STEAM SUPPLY
-LOW PRESSURE STEAM SUPPLY
-MEDIUM PRESSURE STEAM SUPPLY
CR -CONDENSATE RETURN
-SLOPE DIRECTION (DOWN)
-FLEX CONNECTION
-O.S.&Y. GATE VALVE
-THREE-WAY CONTROL VALVE
-THERMOMETER
- P-TRAP
-TWO-WAY CHECK VALVE
EQUIP.
-MANUAL VENT
-PRESSURE GAUGE
-RELIEF VALVE
-FLOW METER
-WATER METER
-INLINE PUMP
-INLINE PUMP
CTU - CONSTANT TERMINAL UNIT
VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS
VTU - VARIABLE TERMINAL UNIT
PTU - PARALLEL TERMINAL UNIT
STU - SERIES TERMINAL UNIT
-AIR HANDLING UNIT
-REHEAT COIL
-AIR DISTRIBUTION DEVICE
-NEGATIVE RELATIVE PRESSURE
-POSITIVE RELATIVE PRESSURE
-NEUTRAL RELATIVE PRESSURE
-HIGH PRESSURE STEAM RETURN
-LOW PRESSURE STEAM RETURN
-MEDIUM PRESSURE STEAM RETURN
-BACKDRAFT DAMPER
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-PACKAGED TERMINAL AIR CONDITIONERPTAC
-PIPE ANCHORS
-CONCENTRIC REDUCER
-ECCENTRIC REDUCER
-STEAM TRAP
-FLOW DIRECTION
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-SHEET NOTE CALLOUT
-EXHAUST DUCT UP THROUGH SLAB W/
-EXHAUST FAN ON ROOF W/ DUCT DOWN
THROUGH ROOF
-CEILING MOUNTED ACCESS DOOR
-RECTANGULAR DUCT SECTION UP, EXHAUST
-RECTANGULAR DUCT SECTION UP,
-RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE,
-ROUND DUCT SECTION UP
-FLAT OVAL DUCT SECTION UP
SUPPLY OR OUTSIDE AIR
NEGATIVE PRESSURE, RETURN
FAN ON ROOF ABOVE
-ABOVE FINISHED ROOFAFR
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
VOLUME WITH ELECTRIC HEAT
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
VOLUME, FAN POWERED
VOLUME, FAN POWERED, WITH ELECTRIC
HEAT
-TERMINAL UNIT, VARIABLE/CONSTANT AIR
12 / 8
HVAC GENERAL NOTESHVAC ABBREVIATIONSHVAC SYMBOL LEGEND
HVAC EQUIPMENT TAGSHVAC PIPING SYMBOL LEGEND
8"10x8
24x12
12x8
HPS
MPS
LPS
CD
HWR
HWS
HPR
MPR
LPR
H
VOLUME WITH ELECTRIC HEAT
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL
BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER
PIPING, LIGHTS, PLUMBING, AND ELECTRICAL CONDUIT.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC DUCT CONSTRUCTION STANDARD.
4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK.
5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT FURNISHED.
7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND EQUIPMENT OF ALL
TRADES.
8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48" TO 54" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER EQUIPMENT, FURNITURE, LIGHT SWITCHES, AND DOOR SWINGS.
9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS
REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT BLACK.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR PROPER DRAINAGE TO SUIT EQUIPMENT
FURNISHED.
14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR MAINTENANCE OF
ALL MECHANICAL EQUIPMENT.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO SPECIFICATIONS FOR DETAILED
REQUIREMENTS.
17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION
DEVICES.
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR HANDLING UNITS, AND FAN COIL UNITS.
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE CONNECTED.
20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD
AS BRIEF AS POSSIBLE.
21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL BE DISPOSED OF LEGALLY.
22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE
RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25' CLEAR FROM ALL PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST PLUMBING
DRAIN.
27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN
CHILLED WATER AND HOT WATER PIPING.
28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH
AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26
S
MV
FM
M
T
UC
TAG
CFM
AHU NUMBER
AHU NUMBER COIL NUMBER
AHU NUMBER
TERMINAL NUMBER
TERMINAL UNIT TYPE
CFMM
FM
-MANUAL BALANCING DAMPER
-AIR FLOW MEASURING STATION
-MOTOR OPERATED CONTROL DAMPER (MOD)
-COMBINATION FIRE & SMOKE DAMPER (WITH ACCESS PANEL)
-FIRE DAMPER (WITH ACCESS PANEL)
SA-1 -SOUND ATTENUATOR
-SMOKE DAMPER (WITH ACCESS PANEL)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:1
P
M
M-MK-01
MECHANICAL SYMBOLS, LEGEND,
NOTES AND INDEX
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
MECHANICAL DRAWING INDEX
SHEET DESCRIPTION
M-MK-01 MECHANICAL SYMBOLS, LEGEND, NOTES AND INDEX
M-MK-02 MECHANICAL SCHEDULES
M-MK-03 MECHANICAL SCHEDULES
M-MK-04 MECHANICAL SCHEDULES
M-MK-05 MECHANICAL SCHEDULES
M-MD-01 OVERALL CRAWLSPACE LEVEL DEMO - MECHANICAL
M-MD-02 OVERALL BASEMENT FLOOR DEMO - MECHANICAL
M-MD-05 OVERALL FIRST FLOOR DEMO - MECHANICAL
M-MH-02.01 OVERALL BASEMENT FLOOR NEW WORK - DUCTWORK
M-MH-03.01A BASEMENT FLOOR AREA A & B - DUCTWORK
M-MH-04.01B BASEMENT FLOOR AREA C - DUCTWORK
M-MH-05.01C BASEMENT FLOOR AREA D & E - DUCTWORK
M-MH-06.01D BASEMENT FLOOR AREA F - DUCTWORK
M-MH-07 DUCT RISERS
M-MH-08.01 OVERALL FIRST FLOOR NEW WORK- DUCTWORK
M-MP-01.01 OVERALL CRAWLSPACE LEVEL NEW WORK - PIPING
M-MP-02.01 OVERALL BASEMENT FLOOR NEW WORK - PIPING
M-MP-03.01A BASEMENT FLOOR AREA A & B - PIPING
M-MP-04.01B BASEMENT FLOOR AREA C - PIPING
M-MP-05.01C BASEMENT FLOOR AREA D & E - PIPING
M-MP-06.01D BASEMENT FLOOR AREA F - PIPING
M-MJ-01 MECHANICAL DETAILS
M-MJ-02 MECHANICAL DETAILS
M-MJ-03 MECHANICAL DETAILS
M-MJ-04 MECHANICAL DETAILS
M-MI-01 MECHANICAL CONTROLS
M-MI-02 MECHANICAL CONTROLS
M-MI-03 MECHANICAL CONTROLS
M-MI-04 MECHANICAL CONTROLS
Revisions: Date:
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:2
P
M
M-MK-04
MECHANICAL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:1
P
M
M-MK-02
MECHANICAL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:2
P
M
M-MK-03
MECHANICAL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:3
P
M
M-MK-05
MECHANICAL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
PRE-DEMOLITION TAB REPORT
UP
A
B
C
D
G
I
J
K
L
M N
O P
Q R
S
T
U
4E4
E5
6 7 8 9 10 11 12 13
16 18
25 E28 E29 2829
F
E
26 27E-LL
H
REMOVE EXISTING PNEUMATIC STEAM
VALVE SERVING WATER HEATER AND
REPLACE WITH NEW DDC CONTROL
VALVE
EXISTING WATER HEATER,
SEE PHOTO # 1
HWP-6B
HWP-6A CHWP-6A
CHWP-6B
6"CHWS
6"CHWR
6"CHWS
4"CHWR
4"CHWS
FROM CAMPUS LOOP
SEE PHOTO # 2 FOR
EXISTING PLAN OF PUMPS
SEE PHOTO # 4 FOR
PHOTO OF HOT WATER
PUMPS
SEE PHOTO # 3 FOR
PHOTO OF CHILLED
WATER PUMPS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:2
P
M
M-MD-01
OVERALL CRAWLSPACE LEVEL
DEMO - MECHANICAL
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8" = 1'-0"
1 CRAWLSPACE LEVEL DEMO - MECHANICAL
PHOTO # 1
PHOTO # 2
EXISTING PARTIAL PLAN OF BASEMENT MECHANICAL ROOM FROM
EXISTING DRAWINGS DATED 2012
PHOTO # 3
PHOTO # 4
EXISTING HOT WATER PUMPS
EXISTING CHILLED
WATER PUMPS
ELECTMECHSTAIR
ELECT ELEVATOR
ELEVATOR
ELEVATOR
SUPPORT
ELECT
STAIR
COMM
OFFICE OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HR
CORR.
SERVER
HAC TELE
HR MULTI
PURPOSE
CORRIDOR
ENTRY
OFFICE
HR
CORR.
MECH
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
OFFICE OFFICE
OFFICE OFFICE
OFFICE
STOR
OFFICE OFFICE
OFFICE
ELEVATOR
LOBBY
CORRIDOR
TOILET
TOILET
TOILET
TOILET
PROSTHETIC
WHEELCHAIR
CLINIC
PROS
STORAGE
MRSA
OFFICE
INFECTION
CONTROL
NURSE IRM
PH/DATA
STORAGE
CORRIDOR
ISO
ENGINEERING
LOCKSMITH
VISN
LEAD
EEO
MGR
DRUG
CONTROL
PHARMACIST
CMOP
PROGRAM
MGR
TELE
CARE
TECHS
TOILET
STOR.
PHARM.
TELE
CARE
TECHS
ADPAC
MECH
MULTI
PURPOSE
INTERN
KITCHEN
TELE
CARE
TECHS
TELE
CARE
TECHS
TOILET
DAY CARE
ADMINISTRATOR
STORAGE
FOOD
PREP
TWO
YEAR
OLD
DAY
CARE
INFANT
TELE
STORSIGNAL
TOILET TOILET
CHILD
CARE 3, 4, 5
YEAR OLD
REMOVE EXISTING FAN , SEE
PHOTO #1
EXISTING WALL LOUVER TO BE
REMOVED, PATCH OPENING TO
MATCH EXISTING. SEE PHOTO # 2
EXISTING WALL LOUVERS TO
REMAIN, SEE PHOTO # 3
EXISTING CONDENSING
UNITS TO REMAIN, SEE
PHOTO # 3
EXISTING WALL LOUVER TO BE REMOVED,
SEE PHOTO # 4. PATCH OPENING TO MATCH
EXISTING
REMOVE EXISTING CONDENSING UNIT
WITH ASSOCIATED PIPING AND CONC.
PAD. SEE PHOTO # 4
1. REMOVE EXISTING UNDER WINDOW WALL MOUNTED HEATERS AND STEAM PIPING AND CAP OFF EXISTING PIPING DOWN AT THE SLAB OR AS LOW AS POSSIBLE. STEAM PIPING HAS ASBESTOS SO ALLOW FOR ASBESTOS REMOVAL ON STEAM PIPING ROUTED TO WALL MOUNTED HEATERS. WHERE THE STEAM PIPING IS ROUTED THRU THE BASEMENT LEVEL TO SERVE FLOORS ABOVE, PIPING TO REMAIN BUT ASBESTOS TO BE REMOVED AND REPLACED WITH FIBERGLASS INSULATION, ALLOW APPROXIMATELY 25 FEET OF ASBESTOS REMOVAL AND FIBERGLASS REPLACEMENT PER INSTANCE WHICH INCLUDS 12.5 FEET OF STEAM PIPE AND 12.5 FEET OF CONDENSATE PIPING PER INSTANCE ON STEAM PIPING ROUTED THRU BASEMENT LEVEL TO LEVELS ABOVE. WALLS TO BE PATCHED TO MATCH EXISTING, REFER TO ARCHITECTURAL FOR OTHER REQUIREMENTS REGUARDING WALL PATCHING. NOT ALL UNDER WINDOW HEATERS ARE SHOWN ON THIS PLAN AS ACCESS WAS LIMITED DURING SURVEY AND EXISTING PLANS PROVIDED BY THE VA WERE NOT COMPLETE, IN ADDITION TO THE ONES SHOWN HERE, ADD ANOTHER 20 UNITS FOR PRICING PURPOSES OR SURVEY SITE AND GET A FULL COUNT.
2. THE DEMOLITION PLAN IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. EXISTING EQUIPMENT, STRUCTURE, DUCTWORK, ETC. LOCATED ON DRAWING MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES AND LOCATIONS PRIOR TO ANY DEMOLITION WORK. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT AND ENGINEER PRIOR TO BEGINNING DEMOLITION. START UP OF DEMOLITION SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED
DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.
3. CONTRACTOR SHALL PERFORM A PRE-BID SURVEY TO FIELD-VERIFY AND COORDINATE ALL DIMENSIONS PROIR TO PROCUREMENT OR FABRICATION. FIELD CONDITIONS SHALL GOVERN. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, ELECTRUCAL CONDUIT, AND PNEUMATIC TUBING. THE COST OF REROUTING DUCTWORK OR PIPING DUE TO CONFLICTS WITH EXISTING CONDITIONS SHALL BE PAID BY THE CONTRACTOR.
4. ALL MECHANICAL SYSTEMS SERVING OTHER SPACES OR FLOORS THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE ANY DISRUPTION TO THE OTHER SPACES. ALL MECHANICAL SYSTEMS THAT RUN INTO THE SPACE BUT DO NOT SERVE ANYTHING SHALL BE REMOVED BACK TO WHERE THEY ENTER THE SPACE
TO FREE-UP VALUABLE CLREANCE FOR NEW DUCT AND PIPING.
5. CONTRACTOR SHALL PROVIDE MECHANICAL WORK FOR PHASING AS REQUIRED OR DIRECTED BY THE ARCHITECT, REFER TO ARCHITECTURAL PHASING PLAN, TEMPORARY MECHANICAL SERVICES SHALL BE PROVIDED WHEN NEW WORK AFFECTS
SERVICES NEEDED TO REMAIN ACTIVE.
6. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF.
7. CONTRACTOR SHALL REMOVE EXISTING THERMOSTATS IN RENOVATION SPACE. REMOVED THERMOSTATS SHALL BE
DISPOSED OF.
8. PROPERLY REMOVE AND DISPOSE OF ALL INDICATED EXISTING TO BE REMOVED HVAC DUCTWORK AND AIR DISTRIBUTION
DEVICES.
9. PATCH HOLES LEFT IN WALLS AND FLOORS AFTER REMOVAL OF EXISTING DUCTWORK, THERMOSTATS, CONDUIT, ETC… TO
MATCH NEW OR EXISTING CONSTRUCTION AND FIRE RATING. THIS INCLUDES ANY EXISTING OPENINGS IN RATED WALLS OR
FLOORS.
10. PROVIDE TEMPORARY NEGATIVE AIR MACHINES FOR CONSTRUCTION AREA. MAINTAIN A NEGATIVE PRESSURE IN THE AREA RELATIVE TO THE ADJACENT SPACES AT A MINIMUM OF -0.03” W.C. PROVIDE SHEET ROCK TYPE WALL BARRIER PARTITIONS WITH AIR TIGHT OR LOW LEAKAGE CONSTRUCTION ACCESS. FAN TO BE EQUIVALENT TO HEPA-AIRE PAS1200HC, 800 CFM, ¼ HP, 120 VOLT. PROVIDE AS MANY MACHINES AS NECESSARY TO MAINTAIN NEGATIVE PRESSURE REQUIREMENT IN RENOVATION SPACE. REFERENCE ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION CONCERNING ICRA
11. UPPER FLOORS OF THIS BUILDING MAY REQUIRE EGRESS FROM STAIRS OR ELEVATORS, COORDINATE SUCH PATHWAYS IF
REQUIRED WITH ARCHITECTRUAL PLANS.
12. PROVIDE TEST AND BALANCE FOR THE EXHAUST FANS SERVING THE 2 MAIN CHASES PRIOR TO DEMOLITION. CHECK TOTAL AIR FLOW AT EACH FLOOR AND TOTAL AIR FLOW AT FAN IN ATTIC. AFTER NEW EXHAUST DUCT IS INSTALLED IN BASEMENT, BALANCE EACH FLOOR TO ORIGINAL CFM AND BALANCE EXISTING EXHAUST FAN IN ATTIC TO TOTAL CFM INCLUDING
BASEMENT FLOOR CFM AS INDICATED ON PLANS.
DEMOLITION GENERAL NOTES:
UNDER WINDOW WALL
MOUNTED HEATER, SEE
DEMOLITION GENERAL NOTE # 1,
(TYPICAL).
AIR CURTAIL FAN
1" STEAM TO
REMAIN IF IN
USE
REMOVE HOT
WATER SUPPLY &
RETURN
REMOVE HOT
WATER SUPPLY &
RETURN
EXHAUST VENT OUT WALL
EXHAUST VENT OUT WALL
TO BE REUSED
EXHAUST VENT OUT WALL TO BE
REMOVED, PATCH OPENING TO
MATCH EXISTING
EXHAUST VENT OUT WALL
TO BE REUSED
REMOVE EXHAUST DUCT DOWN FROM
CHASE ABOVE, SEE PHOTO # 7 & 9.
SEE DEMOLOTION NOTE 12 ABOVE.
REFRIGERANT PIPING
INDOOR AC UNIT
PHOTO # 9
EXHAUST DUCT IN CHASE
RETURN UP FROM
BASEMENT FLOOR BELOW
REMOVE RETURN DUCT DOWN FROM
CHASE ABOVE, SEE PHOTO # 9
REMOVE SUPPLY DUCT DOWN FROM
CHASE ABOVE, SEE SHEET M-MH-07
REMOVE EXHAUST DUCT DOWN FROM
CHASE ABOVE, SEE PHOTO # 10. SEE
DEMOLITION NOTE 12 ABOVE.
REMOVE RETURN DUCT DOWN FROM
CHASE ABOVE, SEE PHOTO # 10
REMOVE SUPPLY DUCT DOWN FROM
CHASE ABOVE, SEE SHEET M-MH-07
PHOTO # 10
RETURN OPENING
EXHAUST DUCT
REMOVE EXISTING HOT WATER
SUPPLY AND RETURN BACK TO MAIN
REMOVE EXISTING HOT WATER
SUPPLY AND RETURN BACK TO MAIN
ACCESS TO ELEVATORS TO BE MAINTAINED DURING
RENOVATION, COORDINATE PHASING WITH
ARCHITECTURAL PLANS
CORRIDOR
1 / AD 01.02
A
D
.0
A
D
.0
/ A
D
.0
A
D
.0
7 / AD 01.02
/ A
D
.0
REMOVE EXISTING AIR CURTAIN FAN
SEE PHOTO # 5
REMOVE EXISTING CABINET HEATER
SEE PHOTO # 5
REMOVE EXISTING AIR CURTAIN FAN
SEE PHOTO # 6
REMOVE EXISTING CABINET HEATER
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:4
P
M
M-MD-02
OVERALL BASEMENT FLOOR
DEMO - MECHANICAL
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"
1 BASEMENT OVERALL DEMO PLAN - MECHANICAL
0 4' 8' 12'
1/8" = 1'-0"
2 ENTRANCE CORR DEMO - MECHANICAL
0 4' 8' 12'
PHOTO # 1
PHOTO # 2
PHOTO # 3
PHOTO # 4
PHOTO # 5
PHOTO # 6
CABINET HEATER
AIR CURTAIN FAN
PHOTO # 7
EXHAUST DOWN TO FIRST FLOOR AND BASEMENT LEVEL
EXISTING GRATE LOCATED INSIDE CHASE ON 2ND FLOOR FOR RETURN AIR FROM
FLOORS BELOW. AN INLINE RETURN FAN WILL BE LOCATED ON FIRST FLOOR WITH
DISCHARGE POINTED UP SO BASEMENT LEVEL WILL HAVE FULLY DUCTED RETURN
TO THE CAHSE.
PHOTO # 8
ONE OF THE RETURN
OPENINGS INTO CHASE FROM
UPPER FLOOR
EXHAUST DUCT IN CHASE
INTERIOR OF CHASE ON UPPER FLOOR LEVEL
132 133
134A 135 136 137
138 140
144 145 146 146A
149148
153 152
156 155
171A
101A
#1
#2
104105105A
107A
124123
129 128
TOILET
OFFICE
HR/CREDENTIALING
CORRIDOR
CORRIDOR
IRM
STORAGE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
OFFICE HR
SPECIALIST
SIGNAL TOILET
OFFICE HR
SPECIALIST
STAIRS HAC
OFFICE
RESOLUTION
MGMT KITCHEN
COPY/FAX
MULTI-PUR
HR RECEPTION
HR WAITING
CORRIDOR
SOIL UTILITY
HR
OFFICE
OFFICE FINGER
PRINTING
BACKGROUND INVEST. POLICE HAC STAIRS
LOGISTICS
SVC
SIGNALTOILET
STORAGE
IRM
STORAGE
STORAGE TOILET
STORAGE
STORAGE TOILET
TOILET
ENGG
ENGG
TOILET
STORAGE
STORAGE
TOILET
STORAGE
TOILET
TOILET
STORAGE
MECHIRM
CLOSET
EMPL
ASSOC.
STORAGE
TOILET
OFFICE
RESOLUTION
MGMT
OFFICE
RESOLUTION
MGMT
OFFICE
TOILET
TOILET
ELEVATOR
ELEVATOR
ELEVATOR
LOBBY
VISITOR
LOUNGE
EEO
LOCKER RM
TOILETMEDCHUTE
OFFICE HR
SPECIALIST
ANTE
OFFICE NURSE
RECRUITER
SHOWER
SPD
CLEAN
LINEN
MECH
OFFICE
HR ASST
TOILET
TOILET
HR CONFERENCE RM
TOILET
OFFICE
HR ASST
TOILET
CONGREGATE BATH
OFFICE HR
SPECIALIST
TOILET
OFFICE SUPV
HR SPECIALIST
OFFICE
STAFFING
SUPV
STORAGETOILET
STORAGE
TOILET
OFFICE HR
SPECIALIST
TOILET STORAGE
OFFICE HR
PROCESSING
4 E5 6
16 18
26 27
E-JJ
E-LL
REMOVE SECTIONS OF DUCTWORK IN CHASE,
SEE DUCT RISERS SHEET M-MH-07
REMOVE SECTIONS OF DUCTWORK IN CHASE,
SEE DUCT RISERS SHEET M-MH-07
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:5
P
M
M-MD-05
OVERALL FIRST FLOOR DEMO -
MECHANICAL
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8" = 1'-0"
1 FIRST FLOOR OVERALL DEMO - MECHANICAL
T
T
T
T
T
T
T
T
T
T
T
T
T T
T T
T T
T T
T
T
T
T
T
T
T
T
T
T T T T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
H H
T
T
T
T
T
T
T
T
A
B
C
D
G
I
J
K
L
MN
O P
Q R
S
T
U
4 E4 E5 5 6
8 10
16 18
19 21 23
25 E28 E29 28 29
F
E
26 27
E-JJ
E-LL
H
BREAKROOM
G18
FITTING
G15
RECEPTION, OPTHA
G13
TOILET
G16
PULM/SLEEP STUDY
G23C
TOILET/SHOWER
G23E
PULM FUNCT, SLEEP STUDY
G23F
SOILED
G23B
CLEAN LINEN
G23A
TOILET
G23L
TELEHEALTH/ MONITORING
G23H
EXAM
G23K
EXAM
G23J
EXAM
G23I
EQUIP STOR
G24
RECEP/CHECK IN
G25
COPY/PRINT
G25A
EXAM/CPAP
G26
EXAM/CPAP
G28
TOILET
G30
EXAM/CPAP
G31
WORK
G-006G
WORK
G-006F
WORK
G-006H
WORK
G-006J
WORK
G-006E
WORK
G-006D
WORK
G-006C
WORK
G-006B
SUPPLY
G-006A
COPY/FAX
G-006K
SUITE
G29
SLEEP LAB WAITING
G-011
STORAGE
G17A
CONFERENCE
G17
NURSE MANAGER
G21
OFFICE
G22
HAC
G01B
TELECOM
G03B
IT/DATA
G03A
ASST CHIEF
G05
STERILE SUPPLY
G04
RME
G02A
CLEAN UTILITY
G02
EXAM
G07F
PHOTOCOAG LASER
G07D
SPEC TESTING
G07C
VISUAL FIELDS
G07B
ULTRASOUND
G07A
CLINIC MANAGER
G07E
YAG LASER
G07G
TOMOGRAPHY/ CAMERA
G07H
MEDS
G07I
TOILET
G07J
SOILED
G08A
RECEIVING
G08
EXAM
G09E
EXAM
G09D
EXAM
G09B
EXAM
G09A
EXAM
G09G
EXAM
G09H
EXAM
G09I
EXAM
G09J
EXAM
G09K
FAMILY TOILET
G08B
SUB WAITING
G09
WORK
G-074C
WORK
G-074D
WORK
G-074E
WORK
G-074F
WORK
G-074G
WORK
G-074B COPY/FAX
G-074A
FILES
G-074H
CORRIDOR
G09L
ELEVATOR SUPPORT
G01A
ELEVATOR
G-X05
ELEVATOR
G-X04
WORK
G-026C
WORK
G-026D
WORK
G-026E
WORK
G-026F
WORK
G-026G
WORK
G-026H
WORK
G-026A
WORK
G-026B
COPY/PRINT
G13A
SUPPLY STO
G-026J
TOILET/SHOWER
G23D
ELECT
G03
ELECT
G12
COMM
G33
MECH
G11
MECH
G06
ELECT
G19
STAIR
G10
STAIR
G20
CORRIDOR
G07
CORRIDOR
G32
EXAM
G23M
EXAM
G09C
WAITING
G14
WORK STATIONS
G23G
CORRIDOR
G23
WORKSTATIONS
G09F
CORRIDOR
G37
AC-1
AC-2
CU-1 CU-2
A 205
A 150
A 175
A 150
A 30
A 165
A 165
A 150
A 150 A 75
A 175
A 50
A 90
A 30
A 205
A 205
A 205
A 205
B 150
B 120
B 1,025
B 150
B 150
B 105
B 165
B 165
B 90
B 75
B 130
B 100
EF-3
EF-2
A 210 A 210
A 210
A 210 A 210 x1
S
A
A 190A 30
A 150
/8
S A
A 190
A 145
A 220
A 295
A 170
/1
S
A
B 190
B 190
EF-1
B 100
B 150
B 1,050
B 1,250
/1
S
A x1
R
A
/1
S
A
/1
S A x1
R
A x1
R A
/1
S
A
B 170 x1
R
A x1
R
A x1
R
A8x
E A
A 210
A 210
A 210
A 210A 120 A 240 A 210 A 210
A 210
A 30
A 120
A 160
A 160
A 105
A 110
A 50
A 220
A 140 ø
S A
23/10 SA 30/10 SA 34/10 SA
x1
S
A x1
S
A x1
S A x1
S
A x1
S
A x1
S
A
B 100
B 100
B 120
B 630
B 630
B 320 B 105 B 110
B 1,200
30x12 RA
30x20 RA 44x10 RA
A 215
A 215 A 215
A 215
A 185 A 190
A 185 A 190
A 185
A 190 A 185
A 185
A 185
A 185
A 185
A 30
A 100
A 200
A 200
A 200
A 200
A 200
A 200 A 110
A 125
A 185
A 130
A 50
A 60
B 185
B 185
B 185
B 185
B 185
B 860 x1
R
A x1
R
A
/1
S
A
/1
S A x1
R
A x1
S
A
B 185
B 200
B 200
B 125
B 200
B 125
B 110
B 225
B 200
B 100
A 150
A 160A 110
B 110 B 850
B 100
B 100
10x6 EA
B 50 x1
R
A
14x10 RA 16x10 RA x1
R
A
20x10 RA
VAV-17-1
VAV-17-2
VAV-17-3
VAV-17-4
VAV-17-6
VAV-17-5
VAV-17-7
VAV-17-8
VAV-17-9 VAV-17-10
VAV-17-11
VAV-17-12
VAV-17-13
VAV-17-15
VAV-17-16
VAV-17-17
VAV-17-18
VAV-17-19
VAV-17-20
VAV-17-22
VAV-17-21
VAV-17-23
VAV-18-3
VAV-18-4
VAV-18-5
VAV-18-6
VAV-18-7
VAV-18-8
VAV-18-1 VAV-18-2
VAV-18-9
VAV-18-10
VAV-18-11
VAV-18-12
VAV-18-13
VAV-18-14
VAV-18-15
B 145
VAV-18-16VAV-18-17
VAV-18-18
VAV-18-19
VAV-18-20
VAV-18-23
VAV-18-25
VAV-18-24
VAV-18-21
VAV-18-22
32x32 RA26x26 RA
CF-4
CF-3
12x6 SA
B 120
42x14 SA
10x10 EA
A 200
B 200
A 150
E 300
B 550
B 350
CF-2
B 350
20x10 SA
A 200
CF-1
DUCTS TO RISE UP OVER CEILING POP UP
DUCTS TO DROP BACK DOWN FROM CEILING POP UP
B 190
B 190
B 190
B 185
30x10 SA
18x10 SA
48x10 SA
24x14 RA x1
R
A x1
R A
12x6 EA 10x10 EA
18x14 SA
24x14 SA
16x14 SA
16x14 SA
32x14 SA
34/10 SA
/1
S
A
24x12 RA
16x10 RA
12x12 PRICE 510Z SIDE WALL
EXHAUST GRILLE, 500 CFM
x1
R
A
EXISTING CONDENSING UNITS
FOR DX UNITS SERVING
ELECT G12 AND G03
VAV-18-26
x8
E A
16x10 SA
6x10 SA
10x10 SA
6x8 SA
GENERAL NOTES:
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED
CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH
MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
4. FOR TYPICAL WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD EQUIPMENT
DETAILS.
5. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE CFM's, REFER TO AIR
DISTRIBUTION DEVICE SCHEDULE FOR ADDITIONAL INFORMATION .
6. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING
DIFFUSERS, REGISTERS, AND GRILLES.
8. COORDINATE EXISTING CONDITIONS WITH NEW DUCT AND PIPE LAYOUT. CONDITIONS SUCH
AS PIPING FROM PLUMBING DEVICES ON THE FLOOR ABOVE AND EXISTING CONCRETE BEAMS
WERE NOT MODELED IN THE PROJECT DUE TO LACK OF EXISTING AS-BUILTS. CONTRACTOR
SHALL ASSUME AT LEAST 1 OFFSET FOR EVERY 30 FEET OF DUCT AND PIPE. CONDITIONS
WILL NOT BE VISIBLE UNTIL CEILINGS ARE REMOVED AND OBSTRUCTIONS CAN BE
DETERMINED.
/1
S
A
/1
S A
CONNECT TO EXISTING VENT IF IN GOOD
CONDITION, INSTALL NEW VENT IF EXISTING
IS IN POOR CONDITION (TYP.)
/1
S
A
10x8 EA
PAINT EXPOSED AREAS OF LINEAR DIFFUSER TO
MATCH CEILING IN THIS AREA, (TYPICAL ALL LINEAR
DIFFUSERS MOUNTED IN WOOD SLAT TYPE CEILING).
/1
S
A x1
R
A x1
R A x1
R
A x1
R A
8x
R A x1
R
A x1
R A x1
R
A x1
R A x1
R
A
/8
S A ø
S A
D 500
EF-4
VAV-18-27
VAV-18-28
10x8 SA
A 160
8x10 SA x1
S
A
VAV-17-14
VAV-17-24
/1
S
A
A 150
A 150
VAV-18-29
20x10 EA
32x14 SA
CORRIDOR
G00
ELEVATOR LOBBY
G01
A 210 A 210
A 210
A 210
10x10 SA
A 210
C 50 D 160
10x6 EA
ENTRY
G34
FAMILY TOILET
G34A
MENS
G35
WOMENS
G36CORRIDOR
G-003
A 175 A 175
B 200
FCU-1
FCU-3
FCU-2A 275 A 275
B 550
B 550 12x12 SA
12x12 SA
A1 150
A 125
A 300
A 275 A 275
DOAS-1
A 125
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:1
P
M
M-MH-02.01
OVERALL BASEMENT FLOOR NEW
WORK - DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"
1 BASEMENT OVERALL NEW WORK - DUCTWORK
0 4' 8' 12'
T
T T
T T
T T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
COPIER
MED LOCK BOX.
L
N
P
R
S
T
U
2 4 E4 E5 5 6
E-JJ
EXAM
G09E
EXAM
G09D
EXAM
G09B
EXAM
G09A
EXAM
G09G
EXAM
G09H
EXAM
G09I
EXAM
G09J
EXAM
G09K
FAMILY TOILET
G08B
SUB WAITING
G09
WORK
G-074C
WORK
G-074D
WORK
G-074E
WORK
G-074F
WORK
G-074GWORK
G-074B COPY/FAX
G-074A
FILES
G-074H
CORRIDOR
G09L
STAIR
G10
EXAM
G09C
WORKSTATIONS
G09F
A 185
VAV-17-3
VAV-17-4
A 185
B 185
30x10 RA B 185
B 185
VAV-17-6
A 185
A 185
B 185
VAV-17-5
VAV-17-7A 185
B 185
A 185
VAV-17-8
A 190
B 190
A 185
VAV-17-9
B 190
A 190
VAV-17-10
B 190
VAV-17-11
A 185
A 190
VAV-17-12
B 185
VAV-17-13
A 215
A 215
A 215 A 215 x1
S
A
B 860
B 185
A 60
B 100 x1
R
A
6x10 SA
6x10 SA
6x10 SA
6x10 SA
/1
S
A
/1
S A
/1
S
A x1
R
A x1
R A x1
R
A
18x10 RA x1
R
A
8x8 RA x1
R
A x1
R A x1
R
A x1
R A
10x10 SA
6x10 SA
6x10 SA
6x10 SA
6x10 SA
6x10 SA
VAV-17-14
/1
S
A
/1
S A
A
B
C
D
G
I
J
K
L
1 2
E4 E5 6
E-JJ
H
ASST CHIEF
G05
EXAM
G07F
PHOTOCOAG LASER
G07D
SPEC TESTING
G07C
VISUAL FIELDS
G07B
ULTRASOUND
G07A
CLINIC MANAGER
G07E
YAG LASER
G07G
TOMOGRAPHY/ CAMERA
G07H
MEDS
G07I
TOILET
G07J
SOILED
G08A
RECEIVING
G08
EXAM
G09A
FAMILY TOILET
G08B
SUB WAITING
G09
MECH
G06
STAIR
G10
CORRIDOR
G07
A 60
B 100 20 x1
R
A
30x10 RA32x10 RA
A 185
CF-4
A 50
A 130
VAV-17-24
B 100
B 850
30x10 SA
18x10 SA
48x10 SA
32x10 RA A 150
B 110
A 110
VAV-17-1
26x26 RA
B 100 A 30
10x6 EA
6x
E A
6x
E A
/1
S
A
B 50
VAV-17-15
A 100
6x8 SA
B 200
A 200
B 200
VAV-17-16
B 200
A 200
6x10 SA
6x10 SA
A 200
VAV-17-18
VAV-17-17
VAV-17-19
VAV-17-20
6x10 SA
6x10 SA x1
R
A
/1
S
A
A 200
B 125
B 200
A 200
12x6 RA
VAV-17-21
10x10 SA
VAV-17-22
A 200
B 110
B 125
VAV-17-23
A 125
/1
S
A
14x10 RA x8
R A
A 110 x1
R
A
16x10 RA
12x6 RA
12x6 RA
6x
R A
10ø SA x8
S A
6ø SA
6x6 RA
20x10 RA
CF-3
24x14 RA
24x12 RA
24x14 RA x1
R
A
12x6 EA
10x10 EA
B 225
A 150
A 150
8x
S A
SEE "AHU-17 RISER - NEW" ON SHEET M-
MH-07, SINGLE RETURN OPENING IN SLAB
MAY HAVE TO BE MODIFIED TO 2 OPENINGS
DUE TO EXISTING STRUCTURAL
CONDITIONS, CONTRACTOR TO FIELD
COORDINATE.
6x10 SA
8x
R A
6x
S A x1
R
A x1
R A
8ø SA
A 160
VAV-17-14
x1
S
A 8x
S
A
/1
S
A
/1
S A
DDC
12x6 SA
EXISTING VETRICAL PIPES ARE LOCATRED IN
THIS AREA, COORDINATE WITH EXISTING
PIPE LOCATIONS.
x1
S
A
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:3
P
M
M-MH-03.01A
BASEMENT FLOOR AREA A & B -
DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
1 BASEMENT FLOOR AREA A NEW WORK - DUCTWORK
1/4" = 1'-0"
2 BASEMENT FLOOR AREA B NEW WORK - DUCTWORK
0 2' 4' 6'
0 2' 4' 6'
0 2' 4' 6'
T
T
T
T
T T T
T
T
T
H H
T
G
I
J
K
L
M
O
Q
11 12
16 18
19 20
F
E
H
BREAKROOM
G18
FITTING
G15
RECEPTION, OPTHA
G13
TOILET
G16
STORAGE
G17A
CONFERENCE
G17
NURSE MANAGER
G21
HAC
G01B
TELECOM
G03B
IT/DATA
G03A
ASST CHIEF
G05
STERILE SUPPLY
G04
RME
G02A
CLEAN UTILITY
G02
ELEVATOR SUPPORT
G01A
ELEVATOR
G-X05
ELEVATOR
G-X04
COPY/PRINT
G13A
ELECT
G03
ELECT
G12
MECH
G11
WAITING
G14
A 150
VAV-17-2B 110
A 110
A 160
AC-1 AC-2
A 50
CU-1 CU-2
B 120
A 120
A 210
A 210 A 210 x1
S
A
B 630 x1
R
A
VAV-18-25
ø
S A x1
S
A
VAV-18-24
x1
S
A
A 210 x1
S
A
VAV-18-20
VAV-18-23
10x10 SA
16x10 RA
23/10 SA 30/10 SA
8x6 EA 10x6 EA
24x10 RA
B 630
A 210 A 210 A 210 x1
S
A
VAV-18-18
34/10 SA
B 320 B 105
A 160
VAV-18-19
x1
S
A
A 160
A 30
B 100
B 120 x8
E A
10x8 EA
30x12 RA24x12 RA A 120
VAV-18-22
A 220
VAV-18-21
8x
E A
A 140
B 100 12x12 PRICE 510Z SIDE
WALL EXHAUST, 500 CFM
x1
R
A
CONTRACTOR TO VERIFY EXISTING
DUCT AND GRILLE ARE HERE. IF NOT,
INSTALL NEW 12x10 SUPPLY DUCT AND
475 CFM SUPPLY GRILLE.
A 240
/1
S
A
8x6 RA
VAV-18-27
VAV-18-28
8ø S
A
A 210 A 210
A 210 A 210
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
C
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:4
P
M
M-MH-04.01B
BASEMENT FLOOR AREA C -
DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
1 BASEMENT FLOOR AREA C NEW WORK - DUCTWORK
0 2' 4' 6'
T
T
T
T
T
T
T
T
T
UP
T
T
T
T
T
T
T
T
T
T
L
N
P
R
S
T
U
E28 E29
26 27
E-LL
BREAKROOM
G18
PULM/SLEEP STUDY
G23C
TOILET/SHOWER
G23E
PULM FUNCT, SLEEP STUDY
G23F
SOILED
G23B
CLEAN LINEN
G23A
TOILET
G23L
TELEHEALTH/ MONITORING
G23H
EXAM
G23K
EXAM
G23J
EXAM
G23I
EQUIP STOR
G24
WORK
G-026C
WORK
G-026D
WORK
G-026E
WORK
G-026F
WORK
G-026G
WORK
G-026H
WORK
G-026A
WORK
G-026B
SUPPLY STO
G-026J
TOILET/SHOWER
G23D
STAIR
G20
EXAM
G23M
WORK STATIONS
G23G
CORRIDOR
G23
A 205
A 205 A 205 x1
S
A
A 205
A 205
VAV-18-9
B 1,025 x1
R
A
B 150
VAV-18-8
A 150
6x10 SA
/1
S
A
/1
S A
A 175
B 105
B 150B 100
A 30 8x10 SA
VAV-18-7
A 150
VAV-18-6
x1
R
A
EF-3
10x8 EA x1
E
AB 130
B 165
A 165
6x10 SA
VAV-18-5
A 75
10x10 SA
VAV-18-4
A 150
B 165
A 165
6x10 SA
VAV-18-3
A 175
/1
S
A x1
R
A
B 120
A 30 B 75
EF-2
6x10 SA
A 150
VAV-18-2
A 90
A 50B 90
VAV-18-1
/1
S
A
B 150 x1
R
A
A 210
A 170
6x10 SA
VAV-18-29
6x
E A
A
B
C
D
G
I
J
K
L
25 E28 E29 28 29 30
BREAKROOM
G18
EQUIP STOR
G24
RECEP/CHECK IN
G25
COPY/PRINT
G25A
EXAM/CPAP
G26
EXAM/CPAP
G28
TOILET
G30
EXAM/CPAP
G31
WORK
G-006G
WORK
G-006F
WORK
G-006H
WORK
G-006J
WORK
G-006E WORK
G-006D
WORK
G-006C
WORK
G-006B
SUPPLY
G-006A
COPY/FAX
G-006K
SUITE
G29
SLEEP LAB WAITING
G-011
NURSE MANAGER
G21
OFFICE
G22
COMM
G33
ELECT
G19
STAIR
G20
CORRIDOR
G32
/1
S
A x1
R
A
B 150 6x6 EA
A 210
34/10 SA
18x14 SA 24x14 SA
32x14 SA
16x14 SA
16x14 SA x1
S
A
VAV-18-17
VAV-18-16
B 110
6x
S A
A 110 A 105
B 105
6x
S A
30x12 RA
10x8 EA
30x14 RA 30x20 RA
/1
S
A
VAV-18-10
A 220
A 295
16x10 SA
A 145
B 145 x8
E A
B 1,200
VAV-18-12
10x10 SA
B 150
B 190
A 190
VAV-18-11
6x10 SA
A 150
VAV-18-13
/8
S A
B 190
6x10 SA
A 190
VAV-18-14
8x
R A
B 100
A 30
A 210
B 1,050 x1
R
A
VAV-18-15
A 210
EF-1
x1
S
A
A 210
A 210 A 210 x8
E A
/8
S A x1
R
A
6x10 SA
44x10 RA
10x10 RA x1
R
A
B 1,250
10x10 EA
B 170
A 170
24x14 SA18x14 SA
/1
S
A x1
R
A
32x32 RA
8x
E A
EXISTING EXHAUST VENT, SEE
PHOTO # 1 THIS SHEET
VAV-18-26
SEE AHU-18 RISER-NEW ON SHEET M-MH-07
C 50
D 160 ø
S A
VERTICAL PIPING IS LOCATED IN THIS
AREA, COORDINATE WITH EXISTING
PIPING, SEE PHOTO # 2 THIS SHEET
WHICH WAS TAKEN ON THE FLOOR
ABOVE.
A 175
A 175
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
D
E
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:0
P
M
M-MH-05.01C
BASEMENT FLOOR AREA D & E -
DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
1 BASEMENT FLOOR AREA D NEW WORK - DUCTWORK
1/4" = 1'-0"
2 BASEMENT FLOOR AREA E NEW WORK - DUCTWORK
0 2' 4' 6' 0 2' 4' 6'
PHOTO # 1
EXISTING EXHAUST VENT
PHOTO # 2
EXISTING SUPPLY DUCTEXISTING PIPING
T
T
T
T
M4705
M4705
F3200
A5090
A5145
A5145
A5145
F2010
F0305
F0305
F0305
F0305
F2000
A5145
A5090
F2015F2015
ENTRY
G34
FAMILY TOILET
G34A
CORRIDOR
G37
WOMENS
G36
CORRIDOR
G-003
MENS
G35
A5090
G
I
K
L
B 200
A 150
E 300
A 200 A 200
10x8 SA
10x8 SA
8x6 SA
8x6 RA
14x6 RA
B 550
B 350 B 350
CF-2
CF-1
CONCRETE PAD
DUCTS TO RISE UP OVER CEILING POP UP
DUCTS TO DROP BACK DOWN FROM CEILING POP UP
SLEEVE DUCTS THRU BRICK WALL AND LEAVE
SPACE IN SLEEVES TO ACCOMODATE
INSULATION ON SUPPLY DUCTS.
SLEEVE DUCTS THRU BRICK WALL
CONNECTION SIZE RETURN
CEILING POPS UP IN THE CENTER AREA, SEE ARCHITECTURAL PLANS
SEE DUCT EXPOSED TO WEATHER
DETAIL ON SHEET M-MJ-03
PROVIDE SHEET METAL COVER OVER VERTICAL
DUCTS MOUNTED TO WALL, SHEET METAL TO BE
ALUMINUM, MINIMUM 22 GAGE, SECURE COVER
TO WALL WITH ANCHOR SCREWS AND RUBBER
COATED STAINLESS WASHERS.
8x6 RA
20x10 SA
DO NOT GROUP DUCTS TOGETHER TO AVOID
ONE LONG BRICK WALL PENETRATION. LEAVE
SPACE BETWEEN DUCTS FOR STRUCTURAL
SUPPORT, COORDINATE WITH STRUCTURAL
SUPPLY DUCT CONNECTS TO SIDE OF UNIT, EXHAUST
DUCT IS ROUTED UNDER SUPPLY DUCT AND GOES
THRU SIDE OF CURB AND IS ROUTED UNDER UNIT TO
BOTTOM CONNECTION OF UNIT, COORDINATE WITH
UNIT MANUFACTURER AND UNIT SUPPORT CURB. KEEP
BOTTOM OF DUCT ABOVE GRADE MINIMUM 1 FOOT OR
MORE.
A 125
A 125
10x6 SA
8x6 SA
8x
S A
COORDINATE THIS DIFFUSER WITH
ARCHITECTURAL CEILING, PAINT EXPOSED PARTS
OF THIS DIFFUSER TO MATCH CEILING
DSD
DSD
20x10 EA
A1 150
12x10 SA
A 275 A 275
A 275 A 275
B 550
B 550
DOAS-1
FCU-1
FCU-2
FCU-3
A 300
PREFABRICATED DOUBLE WALL ENCLOSURE TO
ENCLOSE PIPING AND RECIRC PUMP P-DOAS-1,
MOUNT ON SLAB AND PROVIDE SECURE SEAL TO
DOAS UNIT, ENCLOSURE TO HAVE HINGED
SERVICE ACCESS DOOR WITH LATCHES.
THIS IMAGE SHOWS HOW THE DUCTS AND PIPES
HAVE TO RISE UP OVER THE HIGH CEILING IN THE
CORRIDOR AND DROP BACK DOWN ON THE OTHER
SIDE. THE ARCHITECT HAS PROVIDED A FUROUT
SPACE ON EITHER SIDE FOR THE HVAC TO FIT IN.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:1
P
M
M-MH-06.01D
BASEMENT FLOOR AREA F -
DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
1 BASEMENT FLOOR AREA F NEW WORK - DUCTWORK
0 2' 4' 6'
NOT TO SCALE
2 DUCT ABOVE CONNECTOR CEILING
FD
42" 42"
10"x32"
12"x34"
10"x32"
28"
"x
"x
"x
28"x8"
36"x14"
FD
FD
FD
FDFDFD
14"x8"
CRAWL SPACE
BASEMENT FLOOR
1ST FLOOR
2ND FLOOR
ATTIC
48"x14"
AHU - 17 RISER - NEW
FD
42"42"
10"x38"
14"x42"
36"
"x
"x
23"x8"
28"x14"
FD
FD FD
13"x8"
CRAWL SPACE
BASEMENT FLOOR
1ST FLOOR
2ND FLOOR
ATTIC
AHU - 18 RISER - NEW
10"x38"FD
PROVIDE NEW AIR
MEASURING DEVICE
10"x10"
32"
SHEET
METAL
CAP CHASE
EXTENSION
MECHANICAL NEW
(NOT TO SCALE)
MECHANICAL NEW
(NOT TO SCALE)
TAPED INTO SIDE OF
RETURN PLENUM
TAPED INTO TOP OF
RETURN PLENUM
FD
42" 42"
10"x32"
12"x34"
14"x32"
28"
"x
28"x8"
36"x14"
FD
FD
FD
FD
FDFD
14"x8"
CRAWL SPACE
BASEMENT FLOOR
1ST FLOOR
2ND FLOOR
ATTIC
26"x26"
AHU - 17 RISER - DEMO
FD
42"42"
10"x38"
10"x32"
28"
"x
"x
"x
23"x8"
28"x14"
FD
FD FD
13"x8"
CRAWL SPACE
BASEMENT FLOOR
1ST FLOOR
2ND FLOOR
ATTIC
58"x14"
AHU - 18 RISER - DEMO
10"x38"FD
REMOVE EXISTING
AIR MEASURING
DEVICE
26"x10"
FD
TAPED INTO SIDE OF
RETURN PLENUM 32"
TAPED INTO TOP OF
RETURN PLENUM SHEET
METAL
CAP CHASE
EXTENSION
MECHANICAL EXISTING
(NOT TO SCALE)
MECHANICAL EXISTING
(NOT TO SCALE)
10"x10" 6"x12"
RF-17
S-17
FD
32"x32"
RF-18
S-18
PROVIDE NEW
AIR MEASURING
DEVICE
REMOVE SUPPLY DUCT
REMOVE RETURN DUCT, SEE
PHOTO # 1 THIS SHEET
REMOVE SUPPLY DUCT
REMOVE RETURN DUCT
REMOVE EXHAUST
DUCT
REMOVE EXHAUST
DUCT
DUCT TO BE REMOVED (TYP)
ACCESS DOOR TO BE REPLACED WITH LARGER
DOOR TO ALLOW FOR INSTALLATION OF FAN AND
SILENCER, CONTRACTOR TO VERIFY EQUIPMENT
WILL FIT THRU DOOR
FDFD
IF RETURN DUCT CAN NOT BE ROUTED THRU
SLAB AS A SINGLE 26x26 DUE TO RIBS IN SLAB, CONTRACTOR MAY HAVE TO SPLIT DUCT AND
ROUTE ON EITHER SIDE OF RIB AS SHOWN
ABOVE. FIELD VERIFY AND COORDINATE WITH
STRUCTURAL.
14"x34" 14"x34"
36"x34"RIB IN SLAB
OFFSET DUCT
REMOVE EXHAUST
DUCT
FDFD
IF RETURN DUCT CAN NOT BE ROUTED THRU
SLAB AS A SINGLE 32x32 DUE TO RIBS IN SLAB, CONTRACTOR MAY HAVE TO SPLIT DUCT AND
ROUTE ON EITHER SIDE OF RIB AS SHOWN
ABOVE. FIELD VERIFY AND COORDINATE WITH
STRUCTURAL.
16"x40" 16"x40"
40"x40"RIB IN SLAB
EXISTING DUCT TO REMAIN (TYP)
EXISTING DUCT TO REMAIN (TYP)
NEW DUCT TO BE INSTALLED (TYP)
VFD-17
VFD-18
RF-17
S-17
RF-18
S-18
REMOVE EXISTING
AIR MEASURING
DEVICE, SEE
PHOTO # 4
SEE PHOTO # 2
SEE PHOTO # 3
GRATE GRATE
PANTS LEG TYPE
DUCT SPLIT TO
AVOID RIB IN SLAB PANTS LEG TYPE
DUCT SPLIT TO
AVOID RIB IN SLAB
ACCESS DOOR (TYP)
THREADED ROD WITH SPRING HANGERS (TYP.)
ALTERNATE RETURN DUCT
SLAB PENETRATION
MECHANICAL NEW
(NOT TO SCALE)
ALTERNATE RETURN DUCT
SLAB PENETRATION
MECHANICAL NEW
(NOT TO SCALE)
EXISTING GRATE
BEFORE DEMOLITION, MEASURE
EXHAUST CFM AT EACH FLOOR
AND AT FAN IN ATTIC. AFTER NEW
DUCT IS INSTALLED IN BASEMENT,
RESET UPPER FLOORS TO
ORIGINAL EXHAUST CFM AND
BALANCE EXHAUST FAN IN ATTIC
AS NEEDED. SEE DEMO NOTE 12 ON
SHEET M-MD-02
FLEX
FLEX
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:1
P
M
M-MH-07
DUCT RISERS CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
PHOTO # 1
RETURN DUCT UP THRU FIRST FLOOR
EXHAUST DUCT
PHOTO # 2
AHU-18 SUPPLY DUCT
PHOTO # 3
EXISTING RETURN OPENING FROM BASEMENT
FLOOR BELOW
REWORK EXHAUST DUCT UP IN
AHU-18 RISER TO MAKE ROOM FOR
RETURN FAN
PHOTO # 4 AHU-17 SUPPLY DUCT
132 133
134A 135 136 137
138 140
144 145 146 146A
149148
153 152
156 155
171A
101A
#1
#2
104105105A
107A
110A
124123
129 128
TOILET
OFFICE
HR/CREDENTIALING
CORRIDOR
CORRIDOR
IRM
STORAGE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
OFFICE HR
SPECIALIST
SIGNAL TOILET
OFFICE HR
SPECIALIST
STAIRS HAC
OFFICE
RESOLUTION
MGMT KITCHEN
COPY/FAX
MULTI-PUR
HR RECEPTION
HR WAITING
CORRIDOR
SOIL UTILITY
HR
OFFICE
OFFICE FINGER
PRINTING
BACKGROUND INVEST. POLICE HAC STAIRS
LOGISTICS
SVC
SIGNALTOILET
STORAGE
IRM
STORAGE
STORAGE TOILET
STORAGE
STORAGE TOILET
TOILET
ENGG
ENGG
TOILET
STORAGE
STORAGE
TOILET
STORAGE
TOILET
TOILET
STORAGE
MECHIRM
CLOSET
EMPL
ASSOC.
STORAGE
TOILET
OFFICE
RESOLUTION
MGMT
OFFICE
RESOLUTION
MGMT
OFFICE
TOILET
TOILET
ELEVATOR
ELEVATOR
ELEVATOR
LOBBY
VISITOR
LOUNGE
EEO
LOCKER RM
TOILETMEDCHUTE
OFFICE HR
SPECIALIST
ANTE
OFFICE NURSE
RECRUITER
SHOWER
SPD
CLEAN
LINEN
MECH
OFFICE
HR ASST
TOILET
TOILET
HR CONFERENCE RM
TOILET
OFFICE
HR ASST
TOILET
CONGREGATE BATH
OFFICE HR
SPECIALIST
TOILET
OFFICE SUPV
HR SPECIALIST
OFFICE
STAFFING
SUPV
STORAGETOILET
STORAGE
TOILET
OFFICE HR
SPECIALIST
TOILET STORAGE
OFFICE HR
PROCESSING
4E4 E55 6
16 18
25 E28 E29 2829
26 27
E-JJ
E-LL
14x32 SA
26x26 RA
10x10 EA
42x14 SA
32x32 RA
10x10 EA
FD AT SLAB WITH ACCESS
DOOR, SEE SHEET M-MH-07
FD AT SLAB WITH ACCESS
DOOR, SEE SHEET M-MH-07
RF-18RF-17
VFD-17
VFD-18
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T V
H S
A C
Y V
A M
C S le e p
L a b
M
R
.r v t
/1
/2
:1
:2
P
M
M-MH-08.01
OVERALL FIRST FLOOR NEW
WORK- DUCTWORK
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SK07/10/2024
626A4-21-101
JE
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8"…