Attachment 13 - DWG - 09 - FP.pdf

PDF 14 MB Posted

Attached to
Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
Solicitation number
36C77625B0035
Issued by

About this file

These fire protection drawings (F-FI-01 through F-FX-01.01D) detail the fire sprinkler system design for a VA Sleep Disorder and Specialty Clinic renovation project in Murfreesboro, Tennessee. The comprehensive set of drawings includes fire protection symbols, legends, demolition plans, and new work plans for the basement level, with specific focus on Areas A through F of the facility.

Key technical specifications include a fully sprinklered wet pipe system designed per VA Fire Protection Design Manual and NFPA 13 (2022 Edition), with different hazard classifications (Light Hazard, Ordinary Hazard Group I and II) across various spaces. The design requires Tennessee-registered sprinkler contractors to install new sprinkler heads and piping, coordinate with structural and mechanical systems, and provide detailed shop drawings with hydraulic calculations. Critical notes emphasize maintaining continuous fire protection during construction, using temporary heat detectors, and ensuring sprinkler coverage in all renovated areas, with specific requirements for sprinkler head placement, piping routing, and coordination with existing building systems.

View the file

Other files

File Type Posted
36C77625B0035 Amendment 0004.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
VAAR 852.236-92 NOTICE TO BIDDERS—ADDITIVE OR DEDUCTIVE BID LINE ITEMS APR 2019.docx DOCX document
Attachment 23 - VA Sleep Lab - Civil Specs.pdf PDF
36C77625B0035 Amendment 0003.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
Attachment 19 - Site Layout.pdf PDF
Attachment 20 - 085653 Blast resistant Windows.pdf PDF
Attachment 22 - 102113 Toilet Compartments.pdf PDF
Attachment 18.docx DOCX document
Attachment 21 - 088000 Glazing.pdf PDF
Solicitation section 2.3 and 2.8 revisions.docx DOCX document
Attachment 17 - DWG - 02 - C.pdf PDF
36C77625B0035 Amendment 0002.docx DOCX document
Site Visit Sign-in Sheet - Murfreesboro - 7.16.pdf PDF
36C77625B0035 Amendment 0001.docx DOCX document
Attachment 10 - DWG - 06 - M.pdf PDF
Attachment 6 - DWG - 01 - G.pdf PDF
Attachment 11 - DWG - 07 - P.pdf PDF
Attachment 1 - Wage Rates - Rutherford County 6.6.25 - Murfreesboro.pdf PDF
Attachment 14 - DWG - 10 - T.pdf PDF
Attachment 4 - Specs Vol 1.pdf PDF
Attachment 12 - DWG - 08 - E.pdf PDF
Attachment 2 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - Specs Vol 2.pdf PDF
Attachment 16 - VHA ICRA Sleep Disorder.docx DOCX document
Attachment 15 - VHA PCRA Sleep disorder.docx DOCX document
Attachment 8 - DWG - 04 - I.pdf PDF
Attachment 3 - Site Visit Instructions Murfreesboro.pdf PDF
Attachment 9 - DWG - 05 - S.pdf PDF
Attachment 7 - DWG - 03 - A.pdf PDF
36C77625B0035_1.docx DOCX document
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2 1/2"

2 1/2"

3-0

NOT TO SCALE

METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (1-HR.)

INSTALL PER UL SYSTEM W-L-1054

USE HILTI FS-ONE MAX FIRESTOP SEALANT

METAL PIPE

TYPE MAX. DIA.

STEEL PIPE (SCH. 10

OR HEAVIER)

30"

CAST IRON PIPE 30"

COPPER PIPE 6"

STEEL CONDUIT 6"

EMT 4"

NOT TO SCALE

METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (2-HR.)

INSTALL PER UL SYSTEM W-L-1054

USE HILTI FS-ONE MAX FIRESTOP SEALANT

METAL PIPE

TYPE MAX. DIA.

STEEL PIPE (SCH. 10

OR HEAVIER)

30"

CAST IRON PIPE 30"

COPPER PIPE 6"

STEEL CONDUIT 6"

EMT 4"

FIRE PROTECTION LEGEND

FIRE PROTECTION DESIGN CRITERIA

FIRE PROTECTION FLOW TEST DATA

THERE IS NO FIRE PUMP AT THIS FACILITY.

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

SYMBOL DESCRIPTION

- CONTROL VALVE w/TAMPER SWITCH

- HYDRAULIC REFERENCE NODE

- EXISTING SPRINKLER PIPING

- FIRE VALVE CABINET

- REVISION REFERENCE

OR

- CONNECT TO

- DEMO TO

- DEMOLISHED SPRINKLER PIPING

- NEW SPRINKLER PIPING

- U/G GATE VALVE

# - KEYNOTE

- HYDRAULIC REMOTE AREA

- CONTROL VALVE W/ TAMPER SWITCH

- PIPE SIZE

- 2-1/2" FIRE DEPARTMENT VALVE W/ CAP AND CHAIN

- PIPE SIZE AND LENGTH

1. FIRE PROTECTION DESIGN SHALL COMPLY WITH THE VA FIRE PROTECTION DESIGN MANUAL;

LATEST EDITION.

2. V.A. IS THE ONLY AHJ. SEE LATEST V.A. FIRE PROTECTION DESIGN MANUAL AND NFPA 13, 2022

EDITION.

3. THE FIRE PROTECTION SYSTEMS SHOWN REPRESENT THE DESIGN INTENT OF THE ENGINEER, IN

ACCORDANCE WITH ALL APPLICABLE LOCAL CODES. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO COORDINATE INSTALLATION WITH ALL OTHER TRADES. SUBMIT COMPLETE

SPRINKLER SYSTEM LAYOUT DRAWINGS WITH ANY ADDITIONAL OFFSETS, SPRINKLERS OR SYSTEM

COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM AND TO AVOID CONFLICTS

WITH OTHER TRADES.

4. SPRINKLER SHOP DRAWINGS AND MATERIAL CUT SHEETS SHALL BE SUBMITTED TO THE

ARCHITECT AND LOCAL FIRE MARSHAL FOR APPROVAL PRIOR TO ANY INSTALLATION.

5. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. PROVIDE ALL ADDITIONAL OFFSETS REQUIRED FOR

PROPER INSTALLATION AND COORDINATION WITH OTHER TRADES.

6. INSTALL PIPING IN AREAS WITH EXPOSED STRUCTURE AS HIGH AS POSSIBLE TO ALLOW THE

OWNER MAXIMUM USE OF THE SPACE.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.

8. COORDINATE SPRINKLERS WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND LISTING OF

THE SPRINKLER.

9. CENTER SPRINKLERS IN THE CENTER OF CEILING TILE. PROVIDE ARMOVER OR SWING JOINT AS

REQUIRED.

10. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE

INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF

DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID

SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE

PROOFING.

11. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. PROVIDE FIRESTOP ASSEMBLIES EQUAL TO OR EXCEEDING THE

RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR RATINGS.

12. FURNISH ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES, FOR

INSTALLATION BY GENERAL CONTRACTOR.

13. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN

CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.

14. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND

SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL 2023 EDITION AND NFPA 13, 2022 EDITION. HEADS UNDER DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED. PROVIDE IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL 2023 EDITION. COORDINATE SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND

OBSTRUCTIONS WITH FINAL INSTALLED LOCATIONS.

15. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR

ROOMS, ELEVATOR SHAFTS, STORAGE ROOMS, UTILITY ROOMS AND ON ANY HEADS LESS THAN

7'-0" ABOVE THE FLOOR.

16. PROVIDE HANGERS ON END HEADS IN PENDANT POSITION WITHIN 12" OF END OF LINE, IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2022 EDITION, WHEN SYSTEM

PRESSURE EXCEEDS 100 PSI.

17. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO

ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY

CIRCUMSTANCES. REROUTE ANY PIPING RUN OVER ELECTRICAL EQUIPMENT.

18. ALL DRAIN SYSTEM PIPING AND FITTINGS SHALL BE GALVANIZED BOTH INSIDE AND OUTSIDE.

19. PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES.

20. SLOPE ALL PIPING TO THE SYSTEM MAIN DRAIN AS REQUIRED TO INSURE PROPER DRAINAGE.

INSTALL ADDITIONAL DRAINS AND PLUGS WHERE REQUIRED TO COMPLY WITH THE ABOVE

REFERENCED CODES.

21. SPRINKLER CONTRACTOR TO INDICATE SPRINKLER DESIGN DENSITIES FOR ALL AREAS/ROOMS ON

THEIR RESPECTIVE DRAWINGS.

22. THIS BUILDINGS STRUCTURAL SYSTEM HAS BEEN DESIGNED TO SUPPORT THE ADDITIONAL

WEIGHT ASSOCIATED WITH THE SPRINKLER SYSTEM.

23. PAINT ALL SPRINKLER PIPING INSTALLED BELOW THE CEILINGS AND IN EXPOSED LOCATIONS.

CLEAN, PRIME AND PAINT ALL EXPOSED PIPING RED, UNLESS OTHERWISE NOTED. COORDINATE

ALL COLORS WITH THE ARCHITECT.

24. COORDINATE HANGER LOCATIONS WITH THE BUILDING STRUCTURE. SUPPORT PIPING IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2023 EDITION. PROVIDE ALL

MISCELLANEOUS STEEL FRAMING AS REQUIRED TO SUPPORT PIPING. PROVIDE GALVANIZED OR

COATED HANGERS AND RODS.

25. THE OWNER AND ARCHITECT/ENGINEER SHALL BE NOTIFIED IN WRITING AT LEAST 10 DAYS PRIOR

TO ANY FIRE PROTECTION SYSTEM SHUTDOWNS. FIRE PROTECTION CONTRACTOR SHALL BE

RESPONSIBLE FOR A FIRE WATCH ON THE BUILDING WHILE THE SYSTEM IS DOWN.

26. TENNESSEE SPRINKLER CONTRACTOR TO PROVIDE SPRINKLER CALCS ON THE DRAWINGS.

27. SPRINKLER CONTRACTOR TO MOUNT INFORMATION PLATES ON SPRINKLER SYSTEMS WITH CALCS

ON THE PLATES.

28. SPRINKLER CONTRACTOR SHOW LOCATION OF SPRINKLER RISER AND ALL CONTROL AND TEST

VALVES FOR THIS AREA.

29. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM VALVE INCLUDING

TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW PREVENTER AND METHOD FOR

FRONT FLOW TESTING IT. SHOW ALL DRAINS DISCHARGING TO THE EXTERIOR OF THE BUILDING.

GENERAL NOTES

HANGER - STEEL

No Scale

PIPE HANGER RING

(UL LISTED OR FM APPROVED)

ALL THREAD ROD

TOP BEAM CLAMP

(UL LISTED OR FM APPROVED)

RETURN BEND

No Scale

SPRINKLER HEAD

1" DROP

1" 90° ELL

1" 90° ELL

BRANCH LINE

1x1/2 REDUCER

CEILING

LIGHT HAZARD

WET PIPE

.10 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

30 MIN.

225 SQ. FT.

100 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

ENTIRE BUILDING (EXCEPT AS NOTED):

FIRE SPRINKLER:

WATER SUPPLY DATA:

THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER VA FIRE PROTECTION

DESIGN MANUAL 2023 EDITION AND NFPA 13, 2022 EDITION. THE CONTRACTOR SHALL PERFORM

HYDRAULIC CALCULATIONS. CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP DRAWINGS),

HYDRAULIC CALCULATIONS AND MATERIAL DATA SHALL BE SUBMITTED TO THE

ARCHITECT/ENGINEER AND AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO

SYSTEM INSTALLATION.

THE CONTRACTOR SHALL PERFORM HYDRANT-FLOW TEST TO VERIFY WATER PRESSURE

REQUIRED FOR HYDRAULIC CALCULATIONS.

UNLESS OTHERWISE NOTED ALL STORAGE ROOMS:

DESIGN CRITERIA:

DESIGN OF THE FIRE SUPPRESSION SYSTEM ON THIS PROJECT. THE

FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE.

1. VA FIRE PROTECTION MANUAL, 2023 EDITION AND NFPA 13, 2022 EDITION.

ORDINARY HAZARD GROUP II

WET PIPE

0.2 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

60-90 MIN.

130 SQ. FT.

250 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

STANDPIPE DESIGN CRITERIA:

HYDRAULIC DESIGN CRITERIA: EXISTING

SPRINKLER LEGEND

SWING JOINT

No Scale

1" DROP

1" 90° ELL

1" NIPPLE

BRANCH LINE

1" 90° ELL

REDUCER

CEILING

SPRINKLER HEAD

UNLESS OTHERWISE NOTED ALL MECHANICAL AND ELECTRICAL ROOMS:

ORDINARY HAZARD GROUP I

WET PIPE

.15 GPM/SQ. FT.

1,500 SQ. FT.

1/2"

60-90 MIN.

130 SQ. FT.

250 GPM

OCCUPANCY CLASSIFICATION:

SYSTEM TYPE:

DESIGN DENSITY:

HYDRAULIC REMOTE AREA:

SPRINKLER ORIFICE SIZE:

DURATION OF SUPPLY:

MAXIMUM COVERAGE/SPRINKLER HEAD:

HOSE STREAM ALLOWANCE:

• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE

SPECIFIC REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY

EFFORT HAS BEEN MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS

REQUESTED BY THE GOVERNMENT.

• FIRST AND SECOND FLOOR ACCESS SHALL NOT BE INTERRUPTED AT ANY TIME

DURING CONSTRUCTION.

CONSTRUCTION PHASING/ PUBLIC AND STAFF

ACCESS/BUILDING OPERATIONS

MIN.RADIUS = 7"

MAX NUMBER OF BENDS = 2

SHEET METAL SCREW

DROP CEILING TILE

CEILING COVER PLATE

SPRINKLER HEAD

END BRACKET ASSEMBLY

SQUARE BAR

CENTER BRACKET ASSEMBLYREDUCING OUTLET

NUT

COLLAR

STAINLESS STEEL FLEXIBLE

BRAIDED HOSE

COLLAR

ISOLATION RING

NUT

INLET NIPPLE

MAX LENGTH OF PIPE = 48"

FLEX PIPE TO SPRINKLER

No Scale

FLEXIBLE HOSE SHALL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF THE LISTING INCLUDING INSTALLATION INSTRUCTIONS SEE 9.2.1.3.3.1 OF THE 2018 NFPA-13. FLEXIBLE SPRINKLER HOSE SHALL BE FM APPROVED AND LIMITED TO HOSE WITH THREADED END FITTINGS WITH A MINIMUM INSIDE

DIAMETER OR 1-INCH AND A MAXIMUM LENGTH OF 6-FEET.

SUSPENDED CEILINGS SHALL BE CERTIFIED AS

MEETING ASTM C 635 SPECIFICATION AND ASTM

C 636 STANDARD PRACTICE FOR INSTALLATION.

SEE NFPA-13, 2019 EIDTION. ADD A NOTE THAT

THE CEILING INSTALLING CONTRACTOR SHALL

PROVIDE A SIGNED STATEMENT CONFIRMING

THE LAY-IN CEILING SYSTEMS COMPLY WITH

ASTM C 635 AND ASTM C 636 AT THE AHCA

SURVEY.

FLEXIBLE HOSE EXCEEDING 6 FEET IN

LENGTH SERVING SPRINKLERS IN

SUSPENDED CEILINGS SHALL HAVE

HANGER ATTACHED TO THE STRUCTURE

TO LIMIT THE MAXIMUM UNSUPPORTED

LENGTH TO 6 FEET. SEE NFPA-13, 2019

EDITION.

TEST AND DRAIN VALVE

VIC ZONE CONTROL RISER

SITE GLASS

SHUT OFF VALVE

PRESSURE RELIEF VALVE

RISERDRAIN RISER

BUTTERFLY VALVE w/ T.S.

GROOVED CHECK VALVE

FLOW SWITCH

ISOLATION VALVE FOR GUAGE

PRESSURE GUAGE

TO SPRINKLER SYSTEM

ZONE CONTROL RISER MODULE CAN BE MOUNTED IN THE

HORIZONTAL OR VERTICAL UPFLOW POSITION

FLOOR CONTROL VALVE AND TEST MODULE

No Scale

Notes:

1. Refer to the following specifications for firestopping.

a. 07 84 00 Firestopping

b. 07 84 13 Penetration Firestopping

c. 22 00 00 Plumbing

d. 23 00 00 HVAC

e. 26 00 00 Electrical

f. 27 06 37 Communication

For Quality Control requirements, refer to the Quality Control portion of the specification.

2. Details shown are typical details, containing general information only. Always refer to the full UL system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:

* Fire Rating (F-Rating)

* Temperature Rating (T-Rating)

* Leakage Rating (L-Rating)

* Water Rating (W-Rating)

* Annular Space

* Percent Fill

* Movement

* Type and thickness of fire-rated construction.

3. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable.

Contact Hilti Inc. for alternative systems or Engineering

Judgment (800-879-8000) Drawings shall follow the International

Firestop Council (IFC) Guidelines for Evaluating Firestop

Systems Engineering Judgments.

4. References:

* 2013 Underwriter's Laboratories Fire Resistance Directory, Volumes 1 & 2

* NFPA 101 Life Safety Code

* NFPA 70 - National Electric Code

5. Firestop System installation must meet requirements of ASTM

E-814 (UL 1479) tested assemblies that provide a fire rating equal to that of construction being penetrated.

6. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:

*Warning! - Do Not Disturb

*Through Penetration Firestop System

* UL System # * Product(s) used

* Hourly Rating (F-Rating)

* Installation Date

*Contractor's Name

7. For outlet boxes requiring protection, use only Wall Opening

Protective Materials, category CLIV as classified by Underwriter's

Laboratories, Fire Resistance Directory (Volume 1.)

* NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition FIRE SPRINKLER LEGEND

SYMBOL ORF.

1/2"

1/2"

TEMP.

155 DEG.

155 DEG.

RESPONSE

QUICK

QUICK

K-FACTOR

5.6

5.6

FINISH

BRASS

BRASS

MODEL STYLE PLATE

WHITE

WHITE

MFG

RELIABLE

RELIABLERECESSED

UPRIGHTF1-FR

DESIGN NOTES:

1. PROVIDE F1FR SPRINKLERS WITH 175 DEG. F. TEMPERATURE RATING IN ALL MECHANICAL

AND ELECTRICAL ROOMS

2. RELIABLE IS BASIS OF DESIGN, APPROVED EQUALS ARE ALLOWED.

3. PROVIDE FM APPROVED SORIKLER HEADS. REFER TO VA FIRE PROTECTION GUIDELINES.

1/2" 155 DEG. QUICK 5.6 BRASS RELIABLESIDEWALL

EXISTING

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:5

P

M

F-FI-01

FIRE PROTECTION SYMBOLS,

LEGEND, NOTES AND INDEX

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

FIRE PROTECTION DRAWING INDEX

SHEET DESCRIPTION

F-FI-01 FIRE PROTECTION SYMBOLS, LEGEND, NOTES AND INDEX

F-FD-01 OVERALL CRAWLSPACE LEVEL DEMO - FIRE PROTECTION

F-FD-02 OVERALL BASEMENT FLOOR DEMO - FIRE PROTECTION

F-FX-01.00 OVERALL CRAWLSPACE LEVEL - FIRE PROTECTION

F-FX-01.01 OVERALL BASEMENT RCP PLAN NEW WORK - FIRE PROTECTION

F-FX-01.01A BASEMENT RCP PLAN AREA A & B NEW WORK - FIRE PROTECTRION

F-FX-01.01B BASEMENT RCP PLAN AREA C NEW WORK - FIRE PROTECTION

F-FX-01.01C BASEMENT RCP PLAN AREA D & E NEW WORK - FIRE PROTECTION

F-FX-01.01D BASEMENT RCP PLAN AREA F NEW WORK - FIRE PROTECTION

Revisions: Date:

EQUIP STOR

G24

RECEP/CHECK IN

G25

849 SF

CORRIDOR

G37

A

B

C

D

G

I

J K

L

MN

O P

Q R

S

T

U

4E4

E5

6 7 8 9 10 11 12 13

16 18

25 E28 E29 2829

F

E

26 27E-LL

H

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:5

P

M

F-FD-01

OVERALL CRAWLSPACE LEVEL

DEMO - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/8" = 1'-0"

1 CRAWLSPACE LEVEL DEMO - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-

FUNCTIONAL AND COVERAGE IS PROVIDED.

FIRE SPRINKLER CONSTRUCTION CONSIDERATIONS

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN

TO VA FOR STORAGE.

3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.

UP

UP

A/S ZONE #1 A/S ZONE #2

EXISTING

4" STANDPIPE

WITH FDC

EXISTING

6" STANDPIPE

WITH FDC

REMOVE EXISTING

ZONE CONTROL VALVE

AND ACCESSORIES.

CORRIDOR

1 / AD 01.02

A

D

.0

A

D

.0

/ A

D

.0

A

D

.0

7 / AD 01.02

/ A

D

.0

NOTE: FIELD VERIFY FIRE ZONE SUPPLY FOR THE CONNECTOR

FROM BUILDING 6. EXSITING FIRE PROTECTION PLAN FOR

CONNECTOR WAS NOT PROVIDED.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:0

P

M

F-FD-02

OVERALL BASEMENT FLOOR

DEMO - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 BASMENT OVERALL DEMO PLAN - FIRE PROTECTION

0 4' 8' 12'

1/8" = 1'-0"

2 ENTRANCE CORR DEMO - FIRE PROTECTION

0 4' 8' 12'

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN

TO VA FOR STORAGE.

3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.

4. REMOVE EXISTING SPRINKLER HEADS.

5. DEMO AND REMOVE EXSITING FIRE PROTECTION

PIPING UP TO ZONE VALVE ASSEMBLY.

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

EQUIP STOR

G24

RECEP/CHECK IN

G25

ENTRY

G34

FAMILY TOILET

G34A

849 SF

CORRIDOR

G37

WOMENS

G36

MENS

G35

WASTE, VV

WASTE,VVWASTE,VV

A

B

C

D

G

I

J K

L

MN

O P

Q R

S

T

U

4E4

E5

6 7 8 9 10 11 12 13

16 18

25 E28 E29 2829

F

E

26 27E-LL

H

EXISTING FIRE PROTECTION MAIN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:0

P

M

F-FX-01.00

OVERALL CRAWLSPACE LEVEL -

FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/8" = 1'-0"

1 CRAWLSPACE LEVEL - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR

GENERAL INFORMATION ONLY AND NOT AN EXACT

INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.

AUTODOOR

A U

T O

D O

O R

AUTODOOR

AUTODOOR

S C

U P

P E

R S

C U

P P

E R

S C

U P

P E

R S

C U

P P

E R

S C

U P

P E

R

S C

U P

P E

R

H O

L D

O P

E N

S C

U P

P E

R

S C

U P

P E

R

A U

T O

D O

O R

A U

T O

D O

O R

C

C

CC

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

Z

Z

Z

Z

8' - 0"

8' - 0"8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0" 8' - 0" 8' - 0"

8' - 0"

8' - 0" 8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 5"

7' - 8"

7' - 8"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

7' - 8"

7' - 8"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

9' - 0"

8' - 0"

8' - 0"

7' - 8"

BREAKROOM

G18

FITTING

G15

RECEPTION, OPTHA

G13

TOILET

G16

PULM/SLEEP STUDY

G23C

TOILET/SHOWER

G23E

PULM FUNCT, SLEEP STUDY

G23F

SOILED

G23B

CLEAN LINEN

G23A

TOILET

G23L

TELEHEALTH/ MONITORING

G23H

EXAM

G23K

EXAM

G23J

EXAM

G23I

EQUIP STOR

G24

RECEP/CHECK IN

G25

COPY/PRINT

G25A

EXAM/CPAP

G26

EXAM/CPAP

G28

TOILET

G30

EXAM/CPAP

G31

WORK

G-006G

WORK

G-006F

WORK

G-006H

WORK

G-006J

WORK

G-006E

WORK

G-006D

WORK

G-006C

WORK

G-006B

SUPPLY

G-006A

COPY/FAX

G-006K

SUITE

G29

SLEEP LAB WAITING

G-011

STORAGE

G17A

CONFERENCE

G17

NURSE MANAGER

G21

OFFICE

G22

HAC

G01B

TELECOM

G03B

IT/DATA

G03A

ASST CHIEF

G05

STERILE SUPPLY

G04

RME

G02A

CLEAN UTILITY

G02

EXAM

G07F

PHOTOCOAG LASER

G07D

SPEC TESTING

G07C

VISUAL FIELDS

G07B

ULTRASOUND

G07A

CLINIC MANAGER

G07E

YAG LASER

G07G

TOMOGRAPHY/ CAMERA

G07H

MEDS

G07I

TOILET

G07J

SOILED

G08A

RECEIVING

G08

EXAM

G09E

EXAM

G09D

EXAM

G09B

EXAM

G09A

EXAM

G09G

EXAM

G09H

EXAM

G09I

EXAM

G09J

EXAM

G09K

FAMILY TOILET

G08B

SUB WAITING

G09

WORK

G-074C

WORK

G-074D

WORK

G-074E

WORK

G-074F

WORK

G-074G

WORK

G-074B COPY/FAX

G-074A

FILES

G-074H

CORRIDOR

G09L

ELEVATOR SUPPORT

G01A

ELEVATOR

G-X05

ELEVATOR

G-X04

WORK

G-026C

WORK

G-026D

WORK

G-026E

WORK

G-026F

WORK

G-026G

WORK

G-026H

WORK

G-026A

WORK

G-026B

COPY/PRINT

G13A

SUPPLY STO

G-026J

TOILET/SHOWER

G23D

ELECT

G03

ELECT

G12

COMM

G33

MECH

G11

MECH

G06

ELECT

G19

STAIR

G10

STAIR

G20

CORRIDOR

G07

CORRIDOR

G32

EXAM

G23M

EXAM

G09C

WAITING

G14

WORK STATIONS

G23G

CORRIDOR

G23

WORKSTATIONS

G09F

ENTRY

G34

FAMILY TOILET

G34A

CORRIDOR

G37

WOMENS

G36

CORRIDOR

G-003

MENS

G35

FIRE PROTION GENRERAL NOTES:

1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED

BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC

LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR

SHOP DRAWINGS.

2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND

MECHANICAL.

3. INSTALL NEW SPRINKLER HEADS IN RENOVATED AREAS. SEE VA FIRE GUIDELINES.

4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED AREAS.

5. UNLESS OTHERWISE NOTED, ALL AREAS ARE LIGHT HAZARD CLASSIFICATION.

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP IIORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

W

S NEW 3" FP PIPE TO

AREA F. PROVIDE WITH

FLOW AND TAMPER

SWITCH

VS

W S

VS

W S

VS

ORDINARY HAZARD GROUP II

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:1

P

M

F-FX-01.01

OVERALL BASEMENT RCP PLAN

NEW WORK - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/8" = 1'-0"

1 BASMENT OVERALL NEW WORK RCP - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

EXISTING EAST AND WEST ZONES STAIRWELL G20.

OS OS OS

OS

OS

OS

OS

OS

S

C

C

C

C

C

C

C

C

D

3Dz

3Dz

J

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

AUTODOOR

AUTODOOR

A U

T O

D O

O R

J

J

J J

J

J

J

J

OS OS OS

OS

OS

OS

OS

OS

O S

D b

D b

D b

D b

OS

OS

OS

S

3D b

C

C

C

C

C

C

C

C

OS

3Dz

OS

J

J

J

J

OS

3D a

Dz

OS

OS

OS

OS

OS

OS

OS

OS

OS

Z

Z

AREA A

AREA A

AREA B

AREA B

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

10.20

10.20

10.20

10.20

10.20

10.20

10.20

10.20

10.20

10.20

9' - 0"

9' - 0" 9' - 0"

9' - 0"

8' - 0"

8' - 0"

8' - 0"

EXAM

G09E

EXAM

G09D

EXAM

G09B

EXAM

G09A

EXAM

G09G

EXAM

G09H

EXAM

G09I

EXAM

G09J

EXAM

G09K

FAMILY TOILET

G08B

SUB WAITING

G09

WORK

G-074C

WORK

G-074D

WORK

G-074E

WORK

G-074F

WORK

G-074GWORK

G-074B

COPY/FAX

G-074A

FILES

G-074H

CORRIDOR

G09L

STAIR

G10

EXAM

G09C

WORKSTATIONS

G09F

AREA CAREA B

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

7' - 8"

8' - 0"

10.20

10.20

10.20

10.20

10.20

10.20

10.20

7' - 10"

P-4

P-1

9' - 2"

9' - 2" 8' - 7"

9' - 0"

9' - 0"

9' - 0"

9' - 0" 9' - 0" 9' - 0"

9' - 2"

9' - 2"

9' - 2"

P-3 (VERTICAL SIDE)

(HORIZONTAL SIDE)

ASST CHIEF

G05

EXAM

G07F

PHOTOCOAG LASER

G07D

SPEC TESTING

G07C

VISUAL FIELDS

G07B

ULTRASOUND

G07A

CLINIC MANAGER

G07E

YAG LASER

G07G

TOMOGRAPHY/ CAMERA

G07H

MEDS

G07I

TOILET

G07J

SOILED

G08A

RECEIVING

G08

FAMILY TOILET

G08B

SUB WAITING

G09

MECH

G06

STAIR

G10

CORRIDOR

G07

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:2

P

M

F-FX-01.01A

BASEMENT RCP PLAN AREA A & B

NEW WORK - FIRE PROTECTRION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 2' 4' 6'0 2' 4' 6'

1/4" = 1'-0"

1 BASMENT AREA A NEW WORK RCP - FIRE PROTECTION

1/4" = 1'-0"

2 BASMENT AREA B NEW WORK RCP - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

FIRE PROTION GENRERAL NOTES:

1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED

BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC

LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR

SHOP DRAWINGS.

2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND

MECHANICAL.

3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.

4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.

5. UNLESS OTHERWISE NOTED, ALL AREAS ARE LIGHT HAZARD CLASSIFICATION.

OS OS OSOSOSOS

OS

OS

OS

OS

OS OS

OS

OS

OS

OS OS OS

O S

OS

OS

OS

S

SS

S

S

OS

D

D

OS

D

D

OS

OS

OS

OS

OS

OS

OS

OS

OS

AREA A

AREA C

AREA CAREA B

8' - 0"

8' - 0" 8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

7' - 8"

7' - 8"

8' - 5"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

P -3

P-1

9' - 0" 9' - 0"

9' - 0"

9' - 0"

9' - 0" 9' - 0"

9' - 2"9' - 2"9' - 2"

9' - 2"

9' - 2"

9' - 2"

9' - 2"9' - 2"9' - 2"

9' - 0"

9' - 0" 9' - 0"

P-1

(HORIZONTAL AND

VERTICAL)

P-7

8' - 0"

8' - 0"

7' - 8"

9' - 2"9' - 2"

9' - 2"

9' - 2"

(HORIZONTAL)

P-3 (VERTICAL)

(V E

R T

IC

A

L

P -1

(H O

R

IZ

O N

T A

L

BREAKROOM

G18

FITTING

G15

RECEPTION, OPTHA

G13

TOILET

G16

STORAGE

G17A

CONFERENCE

G17

HAC

G01B

TELECOM

G03B

IT/DATA

G03A

STERILE SUPPLY

G04

RME

G02A

CLEAN UTILITY

G02

ELEVATOR SUPPORT

G01A

ELEVATOR

G-X05

ELEVATOR

G-X04

COPY/PRINT

G13A

ELECT

G03

ELECT

G12

MECH

G11

WAITING

G14

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP IORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

C

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:2

P

M

F-FX-01.01B

BASEMENT RCP PLAN AREA C

NEW WORK - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/4" = 1'-0"

1 BASMENT AREA C NEW WORK RCP - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED

BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC

LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR

SHOP DRAWINGS.

2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND

MECHANICAL.

3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.

4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.

OSOS

OS

OS

OS

OS

OS

OS

OS

O S

D

D D

D

D D

D D

D

D

D D

OS

CC

C

C

C

C

C

J

AUTODOOR

H O

L D

O P

E N

OSOSOS

OS

OS

OS

OS OS

OS

OS OS

D

OS

OS

OS

D D

O S

D

OS

S

C

C

C

C w x y z

OS

OS

J

Z

Z

AREA DAREA C

AREA D

AREA F

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

9' - 0" 8' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

2'-6 3/16" 2'-6 3/16"

1' -7

1'

-7

1'-7" 1'-7"

1' -7

1'

-7

10.20

10.20

10.20

10.20

10.20

BREAKROOM

G18

PULM/SLEEP STUDY

G23C

TOILET/SHOWER

G23E

PULM FUNCT, SLEEP STUDY

G23F

SOILED

G23B

CLEAN LINEN

G23A

TOILET

G23L

TELEHEALTH/ MONITORING

G23H

EXAM

G23K

EXAM

G23J

EXAM

G23I

EQUIP STOR

G24

WORK

G-026C

WORK

G-026D

WORK

G-026E

WORK

G-026F

WORK

G-026G

WORK

G-026H

WORK

G-026A

WORK

G-026B

SUPPLY STO

G-026J

TOILET/SHOWER

G23D

STAIR

G20

EXAM

G23M

WORK STATIONS

G23G

CORRIDOR

G23

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP II

AREA C

AREA E

AREA E

AREA F

AREA FAREA D

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

7' - 8"

8' - 0"

8' - 0"

8' - 0"

7' - 8"

10.20

10.20

10.20

1'-0 5/16" 4'-3 9/16" 8'-3 3/8" 3'-8 3/4" 3'-8 3/4"

5' -0

/4

2'

-4

P -3

'-8

/8

10'-6" 1'-6"

'-8

/8

10'-7 1/8" 1'-6"

P-3

P-1

1' -2

1'

-6

/1 6"

3' -1

5/

1' -1

5/

8"

9' - 0"

9' - 0" 9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 2" 8' - 0"

9' - 2"

(VERTICAL)

P-1

(HORIZONTAL)

(V E

R T

IC

A

L

P -1

(H O

R

IZ

O N

T A

L

BREAKROOM

G18 EQUIP STOR

G24

RECEP/CHECK IN

G25

COPY/PRINT

G25A

EXAM/CPAP

G26

EXAM/CPAP

G28

TOILET

G30

EXAM/CPAP

G31

WORK

G-006G

WORK

G-006F

WORK

G-006H

WORK

G-006J

WORK

G-006E

WORK

G-006D

WORK

G-006C

WORK

G-006B

SUPPLY

G-006A

COPY/FAX

G-006K

SUITE

G29

SLEEP LAB WAITING

G-011

OFFICE

G22

COMM

G33

STAIR

G20

CORRIDOR

G32

ORDINARY HAZARD GROUP II

ORDINARY HAZARD GROUP I

NEW 3" FP PIPE TO

AREA F. PROVIDE WITH

FLOW AND TAMPER

SWITCH

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

D

E

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:2

P

M

F-FX-01.01C

BASEMENT RCP PLAN AREA D & E

NEW WORK - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 2' 4' 6'0 2' 4' 6'

1/4" = 1'-0"

1 BASMENT AREA D NEW WORK RCP - FIRE PROTECTION

1/4" = 1'-0"

2 BASMENT AREA E NEW WORK RCP - FIRE PROTECTION

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED

BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC

LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR

SHOP DRAWINGS.

2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND

MECHANICAL.

3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.

4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.

H O

L D

O P

E N

A U

T O

D O

O R

A U

T O

D O

O R

OS

OS

OS OS OS OS

OS

OS OS

OSOS

J

OS

JJ

J

J

S

S

S

J

AREA D

AREA F

AREA FAREA E

11' - 6"

10' - 1" 10' - 6"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 6"

9' - 6"

WDP-1

9' - 0"

1'-6 1/4" 16'-9 3/4" 1'-6"

1' -5

/4

6'

-4

/2

1' -5

/4

1'-0" 6'-8" 1'-0"

1' -0

6'

-8

1' -0

P-3

1'-0"

9' - 0"

P-3

P-3

P-1

WDP-1

ENTRY

G34

FAMILY TOILET

G34A

CORRIDOR

G37

WOMENS

G36

CORRIDOR

G-003MENS

G35

FIRE PROTION GENRERAL NOTES:

1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED

BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC

LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR

SHOP DRAWINGS.

2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND

MECHANICAL.

3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.

4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.

5. FIRE SPRINKLER CONTRACTOR TO ROUTE SPRINKLER PIPING TO CONNECTOR ORIGINATING FROM BUILDING 6.

6. FIRE SPRINKLER CONTRACTOR TO DETERMINE IF EXISTING ZONE FROM BUIDLING 6 CAN BE MODIFIED TO SERVE

THE CONNECTOR. PROVIDE A NEW FIRE ZONE AS REQUIRED.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:0

:2

P

M

F-FX-01.01D

BASEMENT RCP PLAN AREA F

NEW WORK - FIRE PROTECTION

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 2' 4' 6'

1/4" = 1'-0"

1 BASMENT AREA F NEW WORK RCP - FIRE PROTECTION

EXISTING CONNECTOR BUILDING 5 SIDE OF EXISTING CONNECTOR BUILDING 6 SIDE OF EIXSTING CONNECTOR BUILDING 5 EXISTING CONNECTOR

HIGH CEILING OF EXISTING CONNECTOR

(EXTERIOR) EXISTING CONNECTOR

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION

AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS

INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE

EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE

SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF

CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72

HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE

OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO

IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO

NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT

DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.

QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR

THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN

THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS

File details come from the government source that posted it. Updated .