Attachment 13 - DWG - 09 - FP.pdf
PDF 14 MB Posted
- Attached to
- Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
- Solicitation number
- 36C77625B0035
About this file
These fire protection drawings (F-FI-01 through F-FX-01.01D) detail the fire sprinkler system design for a VA Sleep Disorder and Specialty Clinic renovation project in Murfreesboro, Tennessee. The comprehensive set of drawings includes fire protection symbols, legends, demolition plans, and new work plans for the basement level, with specific focus on Areas A through F of the facility.
Key technical specifications include a fully sprinklered wet pipe system designed per VA Fire Protection Design Manual and NFPA 13 (2022 Edition), with different hazard classifications (Light Hazard, Ordinary Hazard Group I and II) across various spaces. The design requires Tennessee-registered sprinkler contractors to install new sprinkler heads and piping, coordinate with structural and mechanical systems, and provide detailed shop drawings with hydraulic calculations. Critical notes emphasize maintaining continuous fire protection during construction, using temporary heat detectors, and ensuring sprinkler coverage in all renovated areas, with specific requirements for sprinkler head placement, piping routing, and coordination with existing building systems.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2 1/2"
2 1/2"
3-0
NOT TO SCALE
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (1-HR.)
INSTALL PER UL SYSTEM W-L-1054
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
TYPE MAX. DIA.
STEEL PIPE (SCH. 10
OR HEAVIER)
30"
CAST IRON PIPE 30"
COPPER PIPE 6"
STEEL CONDUIT 6"
EMT 4"
NOT TO SCALE
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (2-HR.)
INSTALL PER UL SYSTEM W-L-1054
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
TYPE MAX. DIA.
STEEL PIPE (SCH. 10
OR HEAVIER)
30"
CAST IRON PIPE 30"
COPPER PIPE 6"
STEEL CONDUIT 6"
EMT 4"
FIRE PROTECTION LEGEND
FIRE PROTECTION DESIGN CRITERIA
FIRE PROTECTION FLOW TEST DATA
THERE IS NO FIRE PUMP AT THIS FACILITY.
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
SYMBOL DESCRIPTION
- CONTROL VALVE w/TAMPER SWITCH
- HYDRAULIC REFERENCE NODE
- EXISTING SPRINKLER PIPING
- FIRE VALVE CABINET
- REVISION REFERENCE
OR
- CONNECT TO
- DEMO TO
- DEMOLISHED SPRINKLER PIPING
- NEW SPRINKLER PIPING
- U/G GATE VALVE
# - KEYNOTE
- HYDRAULIC REMOTE AREA
- CONTROL VALVE W/ TAMPER SWITCH
- PIPE SIZE
- 2-1/2" FIRE DEPARTMENT VALVE W/ CAP AND CHAIN
- PIPE SIZE AND LENGTH
1. FIRE PROTECTION DESIGN SHALL COMPLY WITH THE VA FIRE PROTECTION DESIGN MANUAL;
LATEST EDITION.
2. V.A. IS THE ONLY AHJ. SEE LATEST V.A. FIRE PROTECTION DESIGN MANUAL AND NFPA 13, 2022
EDITION.
3. THE FIRE PROTECTION SYSTEMS SHOWN REPRESENT THE DESIGN INTENT OF THE ENGINEER, IN
ACCORDANCE WITH ALL APPLICABLE LOCAL CODES. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE INSTALLATION WITH ALL OTHER TRADES. SUBMIT COMPLETE
SPRINKLER SYSTEM LAYOUT DRAWINGS WITH ANY ADDITIONAL OFFSETS, SPRINKLERS OR SYSTEM
COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM AND TO AVOID CONFLICTS
WITH OTHER TRADES.
4. SPRINKLER SHOP DRAWINGS AND MATERIAL CUT SHEETS SHALL BE SUBMITTED TO THE
ARCHITECT AND LOCAL FIRE MARSHAL FOR APPROVAL PRIOR TO ANY INSTALLATION.
5. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. PROVIDE ALL ADDITIONAL OFFSETS REQUIRED FOR
PROPER INSTALLATION AND COORDINATION WITH OTHER TRADES.
6. INSTALL PIPING IN AREAS WITH EXPOSED STRUCTURE AS HIGH AS POSSIBLE TO ALLOW THE
OWNER MAXIMUM USE OF THE SPACE.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.
8. COORDINATE SPRINKLERS WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND LISTING OF
THE SPRINKLER.
9. CENTER SPRINKLERS IN THE CENTER OF CEILING TILE. PROVIDE ARMOVER OR SWING JOINT AS
REQUIRED.
10. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE
INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF
DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID
SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE
PROOFING.
11. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. PROVIDE FIRESTOP ASSEMBLIES EQUAL TO OR EXCEEDING THE
RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR RATINGS.
12. FURNISH ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES, FOR
INSTALLATION BY GENERAL CONTRACTOR.
13. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.
14. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND
SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL 2023 EDITION AND NFPA 13, 2022 EDITION. HEADS UNDER DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED. PROVIDE IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL 2023 EDITION. COORDINATE SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND
OBSTRUCTIONS WITH FINAL INSTALLED LOCATIONS.
15. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR
ROOMS, ELEVATOR SHAFTS, STORAGE ROOMS, UTILITY ROOMS AND ON ANY HEADS LESS THAN
7'-0" ABOVE THE FLOOR.
16. PROVIDE HANGERS ON END HEADS IN PENDANT POSITION WITHIN 12" OF END OF LINE, IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2022 EDITION, WHEN SYSTEM
PRESSURE EXCEEDS 100 PSI.
17. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO
ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
CIRCUMSTANCES. REROUTE ANY PIPING RUN OVER ELECTRICAL EQUIPMENT.
18. ALL DRAIN SYSTEM PIPING AND FITTINGS SHALL BE GALVANIZED BOTH INSIDE AND OUTSIDE.
19. PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES.
20. SLOPE ALL PIPING TO THE SYSTEM MAIN DRAIN AS REQUIRED TO INSURE PROPER DRAINAGE.
INSTALL ADDITIONAL DRAINS AND PLUGS WHERE REQUIRED TO COMPLY WITH THE ABOVE
REFERENCED CODES.
21. SPRINKLER CONTRACTOR TO INDICATE SPRINKLER DESIGN DENSITIES FOR ALL AREAS/ROOMS ON
THEIR RESPECTIVE DRAWINGS.
22. THIS BUILDINGS STRUCTURAL SYSTEM HAS BEEN DESIGNED TO SUPPORT THE ADDITIONAL
WEIGHT ASSOCIATED WITH THE SPRINKLER SYSTEM.
23. PAINT ALL SPRINKLER PIPING INSTALLED BELOW THE CEILINGS AND IN EXPOSED LOCATIONS.
CLEAN, PRIME AND PAINT ALL EXPOSED PIPING RED, UNLESS OTHERWISE NOTED. COORDINATE
ALL COLORS WITH THE ARCHITECT.
24. COORDINATE HANGER LOCATIONS WITH THE BUILDING STRUCTURE. SUPPORT PIPING IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2023 EDITION. PROVIDE ALL
MISCELLANEOUS STEEL FRAMING AS REQUIRED TO SUPPORT PIPING. PROVIDE GALVANIZED OR
COATED HANGERS AND RODS.
25. THE OWNER AND ARCHITECT/ENGINEER SHALL BE NOTIFIED IN WRITING AT LEAST 10 DAYS PRIOR
TO ANY FIRE PROTECTION SYSTEM SHUTDOWNS. FIRE PROTECTION CONTRACTOR SHALL BE
RESPONSIBLE FOR A FIRE WATCH ON THE BUILDING WHILE THE SYSTEM IS DOWN.
26. TENNESSEE SPRINKLER CONTRACTOR TO PROVIDE SPRINKLER CALCS ON THE DRAWINGS.
27. SPRINKLER CONTRACTOR TO MOUNT INFORMATION PLATES ON SPRINKLER SYSTEMS WITH CALCS
ON THE PLATES.
28. SPRINKLER CONTRACTOR SHOW LOCATION OF SPRINKLER RISER AND ALL CONTROL AND TEST
VALVES FOR THIS AREA.
29. PROVIDE DETAILED DRAWING OF THE MAIN SPRINKLER RISER AND ALARM VALVE INCLUDING
TAMPER AND FLOW SWITCH LOCATIONS. SHOW BACKFLOW PREVENTER AND METHOD FOR
FRONT FLOW TESTING IT. SHOW ALL DRAINS DISCHARGING TO THE EXTERIOR OF THE BUILDING.
GENERAL NOTES
HANGER - STEEL
No Scale
PIPE HANGER RING
(UL LISTED OR FM APPROVED)
ALL THREAD ROD
TOP BEAM CLAMP
(UL LISTED OR FM APPROVED)
RETURN BEND
No Scale
SPRINKLER HEAD
1" DROP
1" 90° ELL
1" 90° ELL
BRANCH LINE
1x1/2 REDUCER
CEILING
LIGHT HAZARD
WET PIPE
.10 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
30 MIN.
225 SQ. FT.
100 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
ENTIRE BUILDING (EXCEPT AS NOTED):
FIRE SPRINKLER:
WATER SUPPLY DATA:
THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER VA FIRE PROTECTION
DESIGN MANUAL 2023 EDITION AND NFPA 13, 2022 EDITION. THE CONTRACTOR SHALL PERFORM
HYDRAULIC CALCULATIONS. CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP DRAWINGS),
HYDRAULIC CALCULATIONS AND MATERIAL DATA SHALL BE SUBMITTED TO THE
ARCHITECT/ENGINEER AND AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO
SYSTEM INSTALLATION.
THE CONTRACTOR SHALL PERFORM HYDRANT-FLOW TEST TO VERIFY WATER PRESSURE
REQUIRED FOR HYDRAULIC CALCULATIONS.
UNLESS OTHERWISE NOTED ALL STORAGE ROOMS:
DESIGN CRITERIA:
DESIGN OF THE FIRE SUPPRESSION SYSTEM ON THIS PROJECT. THE
FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE.
1. VA FIRE PROTECTION MANUAL, 2023 EDITION AND NFPA 13, 2022 EDITION.
ORDINARY HAZARD GROUP II
WET PIPE
0.2 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
60-90 MIN.
130 SQ. FT.
250 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
STANDPIPE DESIGN CRITERIA:
HYDRAULIC DESIGN CRITERIA: EXISTING
SPRINKLER LEGEND
SWING JOINT
No Scale
1" DROP
1" 90° ELL
1" NIPPLE
BRANCH LINE
1" 90° ELL
REDUCER
CEILING
SPRINKLER HEAD
UNLESS OTHERWISE NOTED ALL MECHANICAL AND ELECTRICAL ROOMS:
ORDINARY HAZARD GROUP I
WET PIPE
.15 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
60-90 MIN.
130 SQ. FT.
250 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE
SPECIFIC REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY
EFFORT HAS BEEN MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS
REQUESTED BY THE GOVERNMENT.
• FIRST AND SECOND FLOOR ACCESS SHALL NOT BE INTERRUPTED AT ANY TIME
DURING CONSTRUCTION.
CONSTRUCTION PHASING/ PUBLIC AND STAFF
ACCESS/BUILDING OPERATIONS
MIN.RADIUS = 7"
MAX NUMBER OF BENDS = 2
SHEET METAL SCREW
DROP CEILING TILE
CEILING COVER PLATE
SPRINKLER HEAD
END BRACKET ASSEMBLY
SQUARE BAR
CENTER BRACKET ASSEMBLYREDUCING OUTLET
NUT
COLLAR
STAINLESS STEEL FLEXIBLE
BRAIDED HOSE
COLLAR
ISOLATION RING
NUT
INLET NIPPLE
MAX LENGTH OF PIPE = 48"
FLEX PIPE TO SPRINKLER
No Scale
FLEXIBLE HOSE SHALL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF THE LISTING INCLUDING INSTALLATION INSTRUCTIONS SEE 9.2.1.3.3.1 OF THE 2018 NFPA-13. FLEXIBLE SPRINKLER HOSE SHALL BE FM APPROVED AND LIMITED TO HOSE WITH THREADED END FITTINGS WITH A MINIMUM INSIDE
DIAMETER OR 1-INCH AND A MAXIMUM LENGTH OF 6-FEET.
SUSPENDED CEILINGS SHALL BE CERTIFIED AS
MEETING ASTM C 635 SPECIFICATION AND ASTM
C 636 STANDARD PRACTICE FOR INSTALLATION.
SEE NFPA-13, 2019 EIDTION. ADD A NOTE THAT
THE CEILING INSTALLING CONTRACTOR SHALL
PROVIDE A SIGNED STATEMENT CONFIRMING
THE LAY-IN CEILING SYSTEMS COMPLY WITH
ASTM C 635 AND ASTM C 636 AT THE AHCA
SURVEY.
FLEXIBLE HOSE EXCEEDING 6 FEET IN
LENGTH SERVING SPRINKLERS IN
SUSPENDED CEILINGS SHALL HAVE
HANGER ATTACHED TO THE STRUCTURE
TO LIMIT THE MAXIMUM UNSUPPORTED
LENGTH TO 6 FEET. SEE NFPA-13, 2019
EDITION.
TEST AND DRAIN VALVE
VIC ZONE CONTROL RISER
SITE GLASS
SHUT OFF VALVE
PRESSURE RELIEF VALVE
RISERDRAIN RISER
BUTTERFLY VALVE w/ T.S.
GROOVED CHECK VALVE
FLOW SWITCH
ISOLATION VALVE FOR GUAGE
PRESSURE GUAGE
TO SPRINKLER SYSTEM
ZONE CONTROL RISER MODULE CAN BE MOUNTED IN THE
HORIZONTAL OR VERTICAL UPFLOW POSITION
FLOOR CONTROL VALVE AND TEST MODULE
No Scale
Notes:
1. Refer to the following specifications for firestopping.
a. 07 84 00 Firestopping
b. 07 84 13 Penetration Firestopping
c. 22 00 00 Plumbing
d. 23 00 00 HVAC
e. 26 00 00 Electrical
f. 27 06 37 Communication
For Quality Control requirements, refer to the Quality Control portion of the specification.
2. Details shown are typical details, containing general information only. Always refer to the full UL system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:
* Fire Rating (F-Rating)
* Temperature Rating (T-Rating)
* Leakage Rating (L-Rating)
* Water Rating (W-Rating)
* Annular Space
* Percent Fill
* Movement
* Type and thickness of fire-rated construction.
3. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable.
Contact Hilti Inc. for alternative systems or Engineering
Judgment (800-879-8000) Drawings shall follow the International
Firestop Council (IFC) Guidelines for Evaluating Firestop
Systems Engineering Judgments.
4. References:
* 2013 Underwriter's Laboratories Fire Resistance Directory, Volumes 1 & 2
* NFPA 101 Life Safety Code
* NFPA 70 - National Electric Code
5. Firestop System installation must meet requirements of ASTM
E-814 (UL 1479) tested assemblies that provide a fire rating equal to that of construction being penetrated.
6. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:
*Warning! - Do Not Disturb
*Through Penetration Firestop System
* UL System # * Product(s) used
* Hourly Rating (F-Rating)
* Installation Date
*Contractor's Name
7. For outlet boxes requiring protection, use only Wall Opening
Protective Materials, category CLIV as classified by Underwriter's
Laboratories, Fire Resistance Directory (Volume 1.)
* NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition FIRE SPRINKLER LEGEND
SYMBOL ORF.
1/2"
1/2"
TEMP.
155 DEG.
155 DEG.
RESPONSE
QUICK
QUICK
K-FACTOR
5.6
5.6
FINISH
BRASS
BRASS
MODEL STYLE PLATE
WHITE
WHITE
MFG
RELIABLE
RELIABLERECESSED
UPRIGHTF1-FR
DESIGN NOTES:
1. PROVIDE F1FR SPRINKLERS WITH 175 DEG. F. TEMPERATURE RATING IN ALL MECHANICAL
AND ELECTRICAL ROOMS
2. RELIABLE IS BASIS OF DESIGN, APPROVED EQUALS ARE ALLOWED.
3. PROVIDE FM APPROVED SORIKLER HEADS. REFER TO VA FIRE PROTECTION GUIDELINES.
1/2" 155 DEG. QUICK 5.6 BRASS RELIABLESIDEWALL
EXISTING
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:5
P
M
F-FI-01
FIRE PROTECTION SYMBOLS,
LEGEND, NOTES AND INDEX
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
FIRE PROTECTION DRAWING INDEX
SHEET DESCRIPTION
F-FI-01 FIRE PROTECTION SYMBOLS, LEGEND, NOTES AND INDEX
F-FD-01 OVERALL CRAWLSPACE LEVEL DEMO - FIRE PROTECTION
F-FD-02 OVERALL BASEMENT FLOOR DEMO - FIRE PROTECTION
F-FX-01.00 OVERALL CRAWLSPACE LEVEL - FIRE PROTECTION
F-FX-01.01 OVERALL BASEMENT RCP PLAN NEW WORK - FIRE PROTECTION
F-FX-01.01A BASEMENT RCP PLAN AREA A & B NEW WORK - FIRE PROTECTRION
F-FX-01.01B BASEMENT RCP PLAN AREA C NEW WORK - FIRE PROTECTION
F-FX-01.01C BASEMENT RCP PLAN AREA D & E NEW WORK - FIRE PROTECTION
F-FX-01.01D BASEMENT RCP PLAN AREA F NEW WORK - FIRE PROTECTION
Revisions: Date:
EQUIP STOR
G24
RECEP/CHECK IN
G25
849 SF
CORRIDOR
G37
A
B
C
D
G
I
J K
L
MN
O P
Q R
S
T
U
4E4
E5
6 7 8 9 10 11 12 13
16 18
25 E28 E29 2829
F
E
26 27E-LL
H
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:5
P
M
F-FD-01
OVERALL CRAWLSPACE LEVEL
DEMO - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8" = 1'-0"
1 CRAWLSPACE LEVEL DEMO - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-
FUNCTIONAL AND COVERAGE IS PROVIDED.
FIRE SPRINKLER CONSTRUCTION CONSIDERATIONS
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN
TO VA FOR STORAGE.
3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.
UP
UP
A/S ZONE #1 A/S ZONE #2
EXISTING
4" STANDPIPE
WITH FDC
EXISTING
6" STANDPIPE
WITH FDC
REMOVE EXISTING
ZONE CONTROL VALVE
AND ACCESSORIES.
CORRIDOR
1 / AD 01.02
A
D
.0
A
D
.0
/ A
D
.0
A
D
.0
7 / AD 01.02
/ A
D
.0
NOTE: FIELD VERIFY FIRE ZONE SUPPLY FOR THE CONNECTOR
FROM BUILDING 6. EXSITING FIRE PROTECTION PLAN FOR
CONNECTOR WAS NOT PROVIDED.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:0
P
M
F-FD-02
OVERALL BASEMENT FLOOR
DEMO - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"
1 BASMENT OVERALL DEMO PLAN - FIRE PROTECTION
0 4' 8' 12'
1/8" = 1'-0"
2 ENTRANCE CORR DEMO - FIRE PROTECTION
0 4' 8' 12'
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN
TO VA FOR STORAGE.
3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.
4. REMOVE EXISTING SPRINKLER HEADS.
5. DEMO AND REMOVE EXSITING FIRE PROTECTION
PIPING UP TO ZONE VALVE ASSEMBLY.
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
EQUIP STOR
G24
RECEP/CHECK IN
G25
ENTRY
G34
FAMILY TOILET
G34A
849 SF
CORRIDOR
G37
WOMENS
G36
MENS
G35
WASTE, VV
WASTE,VVWASTE,VV
A
B
C
D
G
I
J K
L
MN
O P
Q R
S
T
U
4E4
E5
6 7 8 9 10 11 12 13
16 18
25 E28 E29 2829
F
E
26 27E-LL
H
EXISTING FIRE PROTECTION MAIN
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:0
P
M
F-FX-01.00
OVERALL CRAWLSPACE LEVEL -
FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8" = 1'-0"
1 CRAWLSPACE LEVEL - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
AUTODOOR
A U
T O
D O
O R
AUTODOOR
AUTODOOR
S C
U P
P E
R S
C U
P P
E R
S C
U P
P E
R S
C U
P P
E R
S C
U P
P E
R
S C
U P
P E
R
H O
L D
O P
E N
S C
U P
P E
R
S C
U P
P E
R
A U
T O
D O
O R
A U
T O
D O
O R
C
C
CC
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
Z
Z
Z
Z
8' - 0"
8' - 0"8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0" 8' - 0" 8' - 0"
8' - 0"
8' - 0" 8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 5"
7' - 8"
7' - 8"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
7' - 8"
7' - 8"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
9' - 0"
8' - 0"
8' - 0"
7' - 8"
BREAKROOM
G18
FITTING
G15
RECEPTION, OPTHA
G13
TOILET
G16
PULM/SLEEP STUDY
G23C
TOILET/SHOWER
G23E
PULM FUNCT, SLEEP STUDY
G23F
SOILED
G23B
CLEAN LINEN
G23A
TOILET
G23L
TELEHEALTH/ MONITORING
G23H
EXAM
G23K
EXAM
G23J
EXAM
G23I
EQUIP STOR
G24
RECEP/CHECK IN
G25
COPY/PRINT
G25A
EXAM/CPAP
G26
EXAM/CPAP
G28
TOILET
G30
EXAM/CPAP
G31
WORK
G-006G
WORK
G-006F
WORK
G-006H
WORK
G-006J
WORK
G-006E
WORK
G-006D
WORK
G-006C
WORK
G-006B
SUPPLY
G-006A
COPY/FAX
G-006K
SUITE
G29
SLEEP LAB WAITING
G-011
STORAGE
G17A
CONFERENCE
G17
NURSE MANAGER
G21
OFFICE
G22
HAC
G01B
TELECOM
G03B
IT/DATA
G03A
ASST CHIEF
G05
STERILE SUPPLY
G04
RME
G02A
CLEAN UTILITY
G02
EXAM
G07F
PHOTOCOAG LASER
G07D
SPEC TESTING
G07C
VISUAL FIELDS
G07B
ULTRASOUND
G07A
CLINIC MANAGER
G07E
YAG LASER
G07G
TOMOGRAPHY/ CAMERA
G07H
MEDS
G07I
TOILET
G07J
SOILED
G08A
RECEIVING
G08
EXAM
G09E
EXAM
G09D
EXAM
G09B
EXAM
G09A
EXAM
G09G
EXAM
G09H
EXAM
G09I
EXAM
G09J
EXAM
G09K
FAMILY TOILET
G08B
SUB WAITING
G09
WORK
G-074C
WORK
G-074D
WORK
G-074E
WORK
G-074F
WORK
G-074G
WORK
G-074B COPY/FAX
G-074A
FILES
G-074H
CORRIDOR
G09L
ELEVATOR SUPPORT
G01A
ELEVATOR
G-X05
ELEVATOR
G-X04
WORK
G-026C
WORK
G-026D
WORK
G-026E
WORK
G-026F
WORK
G-026G
WORK
G-026H
WORK
G-026A
WORK
G-026B
COPY/PRINT
G13A
SUPPLY STO
G-026J
TOILET/SHOWER
G23D
ELECT
G03
ELECT
G12
COMM
G33
MECH
G11
MECH
G06
ELECT
G19
STAIR
G10
STAIR
G20
CORRIDOR
G07
CORRIDOR
G32
EXAM
G23M
EXAM
G09C
WAITING
G14
WORK STATIONS
G23G
CORRIDOR
G23
WORKSTATIONS
G09F
ENTRY
G34
FAMILY TOILET
G34A
CORRIDOR
G37
WOMENS
G36
CORRIDOR
G-003
MENS
G35
FIRE PROTION GENRERAL NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC
LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR
SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND
MECHANICAL.
3. INSTALL NEW SPRINKLER HEADS IN RENOVATED AREAS. SEE VA FIRE GUIDELINES.
4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED AREAS.
5. UNLESS OTHERWISE NOTED, ALL AREAS ARE LIGHT HAZARD CLASSIFICATION.
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP IIORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
W
S NEW 3" FP PIPE TO
AREA F. PROVIDE WITH
FLOW AND TAMPER
SWITCH
VS
W S
VS
W S
VS
ORDINARY HAZARD GROUP II
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
C
D
E
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:1
P
M
F-FX-01.01
OVERALL BASEMENT RCP PLAN
NEW WORK - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/8" = 1'-0"
1 BASMENT OVERALL NEW WORK RCP - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
EXISTING EAST AND WEST ZONES STAIRWELL G20.
OS OS OS
OS
OS
OS
OS
OS
S
C
C
C
C
C
C
C
C
D
3Dz
3Dz
J
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
AUTODOOR
AUTODOOR
A U
T O
D O
O R
J
J
J J
J
J
J
J
OS OS OS
OS
OS
OS
OS
OS
O S
D b
D b
D b
D b
OS
OS
OS
S
3D b
C
C
C
C
C
C
C
C
OS
3Dz
OS
J
J
J
J
OS
3D a
Dz
OS
OS
OS
OS
OS
OS
OS
OS
OS
Z
Z
AREA A
AREA A
AREA B
AREA B
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
10.20
10.20
10.20
10.20
10.20
10.20
10.20
10.20
10.20
10.20
9' - 0"
9' - 0" 9' - 0"
9' - 0"
8' - 0"
8' - 0"
8' - 0"
EXAM
G09E
EXAM
G09D
EXAM
G09B
EXAM
G09A
EXAM
G09G
EXAM
G09H
EXAM
G09I
EXAM
G09J
EXAM
G09K
FAMILY TOILET
G08B
SUB WAITING
G09
WORK
G-074C
WORK
G-074D
WORK
G-074E
WORK
G-074F
WORK
G-074GWORK
G-074B
COPY/FAX
G-074A
FILES
G-074H
CORRIDOR
G09L
STAIR
G10
EXAM
G09C
WORKSTATIONS
G09F
AREA CAREA B
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
7' - 8"
8' - 0"
10.20
10.20
10.20
10.20
10.20
10.20
10.20
7' - 10"
P-4
P-1
9' - 2"
9' - 2" 8' - 7"
9' - 0"
9' - 0"
9' - 0"
9' - 0" 9' - 0" 9' - 0"
9' - 2"
9' - 2"
9' - 2"
P-3 (VERTICAL SIDE)
(HORIZONTAL SIDE)
ASST CHIEF
G05
EXAM
G07F
PHOTOCOAG LASER
G07D
SPEC TESTING
G07C
VISUAL FIELDS
G07B
ULTRASOUND
G07A
CLINIC MANAGER
G07E
YAG LASER
G07G
TOMOGRAPHY/ CAMERA
G07H
MEDS
G07I
TOILET
G07J
SOILED
G08A
RECEIVING
G08
FAMILY TOILET
G08B
SUB WAITING
G09
MECH
G06
STAIR
G10
CORRIDOR
G07
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A
B
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:2
P
M
F-FX-01.01A
BASEMENT RCP PLAN AREA A & B
NEW WORK - FIRE PROTECTRION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 6'0 2' 4' 6'
1/4" = 1'-0"
1 BASMENT AREA A NEW WORK RCP - FIRE PROTECTION
1/4" = 1'-0"
2 BASMENT AREA B NEW WORK RCP - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
FIRE PROTION GENRERAL NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC
LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR
SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND
MECHANICAL.
3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.
4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.
5. UNLESS OTHERWISE NOTED, ALL AREAS ARE LIGHT HAZARD CLASSIFICATION.
OS OS OSOSOSOS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS OS OS
O S
OS
OS
OS
S
SS
S
S
OS
D
D
OS
D
D
OS
OS
OS
OS
OS
OS
OS
OS
OS
AREA A
AREA C
AREA CAREA B
8' - 0"
8' - 0" 8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
7' - 8"
7' - 8"
8' - 5"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
P -3
P-1
9' - 0" 9' - 0"
9' - 0"
9' - 0"
9' - 0" 9' - 0"
9' - 2"9' - 2"9' - 2"
9' - 2"
9' - 2"
9' - 2"
9' - 2"9' - 2"9' - 2"
9' - 0"
9' - 0" 9' - 0"
P-1
(HORIZONTAL AND
VERTICAL)
P-7
8' - 0"
8' - 0"
7' - 8"
9' - 2"9' - 2"
9' - 2"
9' - 2"
(HORIZONTAL)
P-3 (VERTICAL)
(V E
R T
IC
A
L
P -1
(H O
R
IZ
O N
T A
L
BREAKROOM
G18
FITTING
G15
RECEPTION, OPTHA
G13
TOILET
G16
STORAGE
G17A
CONFERENCE
G17
HAC
G01B
TELECOM
G03B
IT/DATA
G03A
STERILE SUPPLY
G04
RME
G02A
CLEAN UTILITY
G02
ELEVATOR SUPPORT
G01A
ELEVATOR
G-X05
ELEVATOR
G-X04
COPY/PRINT
G13A
ELECT
G03
ELECT
G12
MECH
G11
WAITING
G14
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP IORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP II
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
C
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:2
P
M
F-FX-01.01B
BASEMENT RCP PLAN AREA C
NEW WORK - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 4' 8' 12'
1/4" = 1'-0"
1 BASMENT AREA C NEW WORK RCP - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC
LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR
SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND
MECHANICAL.
3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.
4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.
OSOS
OS
OS
OS
OS
OS
OS
OS
O S
D
D D
D
D D
D D
D
D
D D
OS
CC
C
C
C
C
C
J
AUTODOOR
H O
L D
O P
E N
OSOSOS
OS
OS
OS
OS OS
OS
OS OS
D
OS
OS
OS
D D
O S
D
OS
S
C
C
C
C w x y z
OS
OS
J
Z
Z
AREA DAREA C
AREA D
AREA F
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
9' - 0" 8' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
2'-6 3/16" 2'-6 3/16"
1' -7
1'
-7
1'-7" 1'-7"
1' -7
1'
-7
10.20
10.20
10.20
10.20
10.20
BREAKROOM
G18
PULM/SLEEP STUDY
G23C
TOILET/SHOWER
G23E
PULM FUNCT, SLEEP STUDY
G23F
SOILED
G23B
CLEAN LINEN
G23A
TOILET
G23L
TELEHEALTH/ MONITORING
G23H
EXAM
G23K
EXAM
G23J
EXAM
G23I
EQUIP STOR
G24
WORK
G-026C
WORK
G-026D
WORK
G-026E
WORK
G-026F
WORK
G-026G
WORK
G-026H
WORK
G-026A
WORK
G-026B
SUPPLY STO
G-026J
TOILET/SHOWER
G23D
STAIR
G20
EXAM
G23M
WORK STATIONS
G23G
CORRIDOR
G23
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP II
AREA C
AREA E
AREA E
AREA F
AREA FAREA D
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
7' - 8"
8' - 0"
8' - 0"
8' - 0"
7' - 8"
10.20
10.20
10.20
1'-0 5/16" 4'-3 9/16" 8'-3 3/8" 3'-8 3/4" 3'-8 3/4"
5' -0
/4
2'
-4
P -3
'-8
/8
10'-6" 1'-6"
'-8
/8
10'-7 1/8" 1'-6"
P-3
P-1
1' -2
1'
-6
/1 6"
3' -1
5/
1' -1
5/
8"
9' - 0"
9' - 0" 9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 2" 8' - 0"
9' - 2"
(VERTICAL)
P-1
(HORIZONTAL)
(V E
R T
IC
A
L
P -1
(H O
R
IZ
O N
T A
L
BREAKROOM
G18 EQUIP STOR
G24
RECEP/CHECK IN
G25
COPY/PRINT
G25A
EXAM/CPAP
G26
EXAM/CPAP
G28
TOILET
G30
EXAM/CPAP
G31
WORK
G-006G
WORK
G-006F
WORK
G-006H
WORK
G-006J
WORK
G-006E
WORK
G-006D
WORK
G-006C
WORK
G-006B
SUPPLY
G-006A
COPY/FAX
G-006K
SUITE
G29
SLEEP LAB WAITING
G-011
OFFICE
G22
COMM
G33
STAIR
G20
CORRIDOR
G32
ORDINARY HAZARD GROUP II
ORDINARY HAZARD GROUP I
NEW 3" FP PIPE TO
AREA F. PROVIDE WITH
FLOW AND TAMPER
SWITCH
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
D
E
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:2
P
M
F-FX-01.01C
BASEMENT RCP PLAN AREA D & E
NEW WORK - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 6'0 2' 4' 6'
1/4" = 1'-0"
1 BASMENT AREA D NEW WORK RCP - FIRE PROTECTION
1/4" = 1'-0"
2 BASMENT AREA E NEW WORK RCP - FIRE PROTECTION
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC
LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR
SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND
MECHANICAL.
3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.
4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.
H O
L D
O P
E N
A U
T O
D O
O R
A U
T O
D O
O R
OS
OS
OS OS OS OS
OS
OS OS
OSOS
J
OS
JJ
J
J
S
S
S
J
AREA D
AREA F
AREA FAREA E
11' - 6"
10' - 1" 10' - 6"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 6"
9' - 6"
WDP-1
9' - 0"
1'-6 1/4" 16'-9 3/4" 1'-6"
1' -5
/4
6'
-4
/2
1' -5
/4
1'-0" 6'-8" 1'-0"
1' -0
6'
-8
1' -0
P-3
1'-0"
9' - 0"
P-3
P-3
P-1
WDP-1
ENTRY
G34
FAMILY TOILET
G34A
CORRIDOR
G37
WOMENS
G36
CORRIDOR
G-003MENS
G35
FIRE PROTION GENRERAL NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC
LOCATIONS AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR
SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL AND
MECHANICAL.
3. INSTALL NEW SPRINKLER HEADS IN RENOVATED CONNECTOR. SEE VA FIRE GUIDELINES.
4. PROVIDE NEW SPRINKLER PIPING IN RENOVATED CONNECTOR AND NEW.AREAS.
5. FIRE SPRINKLER CONTRACTOR TO ROUTE SPRINKLER PIPING TO CONNECTOR ORIGINATING FROM BUILDING 6.
6. FIRE SPRINKLER CONTRACTOR TO DETERMINE IF EXISTING ZONE FROM BUIDLING 6 CAN BE MODIFIED TO SERVE
THE CONNECTOR. PROVIDE A NEW FIRE ZONE AS REQUIRED.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
F
A u to d e s k D o c s /2
V A
M C
S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p L a b
P
F P
R
.r v t
/1
/2
:0
:2
P
M
F-FX-01.01D
BASEMENT RCP PLAN AREA F
NEW WORK - FIRE PROTECTION
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
SHK07/10/2024
626-310
KLS
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 6'
1/4" = 1'-0"
1 BASMENT AREA F NEW WORK RCP - FIRE PROTECTION
EXISTING CONNECTOR BUILDING 5 SIDE OF EXISTING CONNECTOR BUILDING 6 SIDE OF EIXSTING CONNECTOR BUILDING 5 EXISTING CONNECTOR
HIGH CEILING OF EXISTING CONNECTOR
(EXTERIOR) EXISTING CONNECTOR
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
File details come from the government source that posted it. Updated .