Attachment 14 - DWG - 10 - T.pdf

PDF 6 MB Posted

Attached to
Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
Solicitation number
36C77625B0035
Issued by

About this file

This document is a set of technology-related architectural drawings for a VA Sleep Disorder Clinic and Specialty Clinic project located in Murfreesboro, Tennessee. The drawings provide detailed technical specifications for technology infrastructure, including floor plans, riser diagrams, and installation details for various technology systems such as:

Key technology systems include wireless access points, security systems (card readers, electric strikes, cameras), audio-visual equipment, telecommunications infrastructure, data and fiber optic cabling, ground bars, rack elevations, and power distribution. The drawings cover multiple floor levels (basement, first, and second floors) and specify precise installation requirements for technology outlets, conduits, cable management, and networking equipment. The technical drawings are part of the construction documents for a fully sprinkled facility, with detailed notes on cable routing, mounting heights, and coordination requirements with electrical and architectural plans.

View the file

Other files

File Type Posted
36C77625B0035 Amendment 0004.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
VAAR 852.236-92 NOTICE TO BIDDERS—ADDITIVE OR DEDUCTIVE BID LINE ITEMS APR 2019.docx DOCX document
Attachment 23 - VA Sleep Lab - Civil Specs.pdf PDF
36C77625B0035 Amendment 0003.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
Attachment 19 - Site Layout.pdf PDF
Attachment 20 - 085653 Blast resistant Windows.pdf PDF
Attachment 22 - 102113 Toilet Compartments.pdf PDF
Attachment 18.docx DOCX document
Attachment 21 - 088000 Glazing.pdf PDF
Solicitation section 2.3 and 2.8 revisions.docx DOCX document
Attachment 17 - DWG - 02 - C.pdf PDF
36C77625B0035 Amendment 0002.docx DOCX document
Site Visit Sign-in Sheet - Murfreesboro - 7.16.pdf PDF
36C77625B0035 Amendment 0001.docx DOCX document
Attachment 10 - DWG - 06 - M.pdf PDF
Attachment 6 - DWG - 01 - G.pdf PDF
Attachment 11 - DWG - 07 - P.pdf PDF
Attachment 1 - Wage Rates - Rutherford County 6.6.25 - Murfreesboro.pdf PDF
Attachment 4 - Specs Vol 1.pdf PDF
Attachment 12 - DWG - 08 - E.pdf PDF
Attachment 2 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - Specs Vol 2.pdf PDF
Attachment 16 - VHA ICRA Sleep Disorder.docx DOCX document
Attachment 15 - VHA PCRA Sleep disorder.docx DOCX document
Attachment 8 - DWG - 04 - I.pdf PDF
Attachment 3 - Site Visit Instructions Murfreesboro.pdf PDF
Attachment 9 - DWG - 05 - S.pdf PDF
Attachment 7 - DWG - 03 - A.pdf PDF
36C77625B0035_1.docx DOCX document
Attachment 13 - DWG - 09 - FP.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BASIC MATERIALS

CONDUIT TURNED UP

CONDUIT TURNED DOWN

CAPPED CONDUIT

CONDUIT STUBBED AND BUSHED INTO ACCESSIBLE CEILING CAVITY

CONDUIT CONTINUED

TUBULAR RUNWAY, HUNG ABOVE CEILING OR AS NOTED

CABLE TRAY (TYPE), HUNG ABOVE CEILING OR AS NOTED

VOICE AND DATA SYSTEM

DISTRIBUTED ANTENNA SYSTEMS

DAS REPEATERRP

TECHNOLOGY SYSTEMS GENERAL NOTES

1. REFER TO SPECIFICATION SECTION "TECHNOLOGY GENERAL PROVISIONS" FOR MORE INFORMATION ABOUT DRAWINGS AND BID DOCUMENTS.

2. MANY SYMBOLS USED IN THIS PROJECT HAVE A TYPE ASSOCIATED WITH THEM. SEE SHEETS WITH DETAILS AND PROJECT SPECIFICATIONS FOR MORE

INFORMATION ON THE DESCRIPTION OF EACH TYPE.

3. ALL CONDUIT FOR TECHNOLOGY SYSTEMS INDOOR ABOVE GRADE SHALL BE EMT AND ALL CONDUIT FOR BELOW GRADE SHALL BE PVC.

4. SEE LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED PARTITIONS IN THIS PROJECT. PROVIDE AN APPROVED FIRE STOP SYSTEMS FOR EACH RACEWAY OR CABLE GOING THROUGH A RATED WALL. SEE SPECIFICATION "RACEWAYS FOR TECHNOLOGY" FOR MORE INFORMATION.

5. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 110.

COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN REQUIRED CLEARANCES.

6. SYMBOLS USED ON THE TECHNOLOGY DRAWINGS ARE NOT THE SAME SIZE AS THE ACTUAL OBJECT BEING REPRESENTED. THEREFORE LOCATIONS OF THE SYMBOLS ON THE FLOOR PLANS ARE AN APPROXIMATION TO THE ACTUAL LOCATION OF THE DEVICE AND NEED TO BE CAREFULLY COORDINATED

WITH OTHER ELEMENTS IN THE VICINITY. AS A GENERAL GUIDELINE:

A. VOICE/DATA OUTLET FOR WORK-AREAS SHALL BE INSTALLED WITHIN 6 INCHES OF A POWER OUTLET INDICATED IN ELECTRICAL DRAWINGS.

B. TV OUTLETS SHALL BE INSTALLED WITHIN 6 INCHES OF A POWER OUTLET SHOWN ON THE ELECTRICAL DRAWINGS.

C. WHEN MULTIPLE TECHNOLOGY SYSTEMS OUTLETS ARE INDICATED NEXT TO EACH OTHER WITH SYMBOLS, THE SPACING BETWEEN OUTLETS SHALL BE

CONSISTENT IF NO ELEVATION IS SHOWN ON THE DRAWINGS.

D. WHEN INSTALLER IS NOT CERTAIN ABOUT SPECIFIC ADJACENCIES OF A DEVICE, THE QUESTION SHALL BE ASKED TO THE ENGINEER PRIOR TO

INSTALLATION.

7. FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT NOT INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED WITH THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED EQUIPMENT

SHALL BE PRIOR TO ANY ROUGH-IN. NOTIFY ENGINEER OF ANY DISCREPANCY.

8. LOCATIONS OF FLOOR BOXES AND FLOOR PENETRATIONS SHALL NOT BE MEASURED FROM THIS SET OF DRAWINGS, INSTALLER SHALL REQUEST PRECISE

LOCATIONS FROM ARCHITECT.

9. EACH VOICE/DATA RJ45 JACK SHALL BE CONNECTED TO A DEDICATED 4 PR CABLE.

10. THE RESPONSIBILITY OF RACEWAY INSTALLATION SHALL BE AS DIRECTED BY THE CONSTRUCTION MANAGER OR GENERAL CONTRACTOR, BUT ALL

RACEWAYS FOR TECHNOLOGY ARE TO BE INCLUDED IN THIS CONTRACT.

11. WHEN CONDUIT RUNS ARE INDICATED ABOVE GRADE OR BELOW GRADE ON THESE DRAWINGS, NOT EVERY SINGLE JUNCTION BOX (OR COMMUNICATIONS VAULT) REQUIRED IS INDICATED ON THE DRAWINGS. TYPICALLY ONLY END POINT LOCATIONS OR SPECIFIC PASS-THROUGH LOCATIONS WHERE THE ENGINEER DESIRES A BOX ARE SHOWN ON THE DRAWINGS. SEE SPECIFICATION "RACEWAYS FOR TECHNOLOGY" FOR REQUIREMENTS THAT INDICATE ADDITIONAL JUNCTION BOXES OR COMMUNICATION VAULTS THAT SHALL BE PROVIDED UNDER THIS CONTRACT. SUCH REQUIREMENTS INCLUDE ADDITIONAL BOXES REQUIRED BECAUSE OF NUMBER OF CONDUIT BENDS OR CHANGES IN ELEVATION.

12. SOME SYMBOLS INCLUDED IN THE SYMBOL LEGEND MAY NOT BE USED IN THESE PROJECT DRAWINGS.

13. UNDER NO CONDITIONS, CONDUITS FOR LOW VOLTAGE FOR FLOOR BOXES SHALL BE DAISY CHAINED TOGETHER BETWEEN ADJACENT FLOOR BOXES.

ALL CONDUITS FOR FLOOR BOXES SHALL BE HOME RUNS TO NEAREST ACCESSIBLE CEILING SPACE.

14. THIS SET OF DRAWINGS DOES NOT INDICATE ALL GROUNDING AND BONDING REQUIREMENTS FOR TECHNOLOGY SYSTEMS. REFER TO SPECIFICATION

SECTION "GROUNDING FOR TELECOMMUNICATION SYSTEM" FOR ADDITIONAL REQUIREMENTS.

15. ALL CABLES FOR TECHNOLOGY SYSTEMS RUN UNDER SLAB OR BELOW GRADE IN CONDUITS STUBBING UP INSIDE THE TELECOM ROOM SHALL BE INDOOR/OUTDOOR RATED. FOR CONDUITS STUBBING UP IN OTHER LOCATIONS DIFFERENT FROM TELECOM ROOMS AND FURTHER THAN 50 FT. FROM A

TELECOM ROOM, DO NOT USE INDOOR/OUTDOOR RATED CABLES.

16. GRAPHICS USED FOR EQUIPMENT IN ELEVATIONS AND CHANNELS (LINE DRAWINGS) DO NOT NECESSARILY REPRESENT THE PART NUMBER OF THE EQUIPMENT SPECIFIED. THE PART NUMBERS LISTED IN THE DRAWINGS AND SPECIFICATIONS ARE TO BE FOLLOWED FOR BASIS OF DESIGN, NOT THE

GRAPHICS.

17. THE TECHNOLOGY DRAWINGS DO NOT SHOW ALL REQUIRED CONDUITS/RACEWAYS TO BE PROVIDED UNDER THIS CONTRACT. TYPICALLY CONDUIT SLEEVES SMALLER THAN 2" ARE NOT SHOWN ON THE DRAWINGS. SEE SPECIFICATIONS "RACEWAYS FOR TECHNOLOGY" AND DRAWING DETAILS FOR

ADDITIONAL RACEWAY REQUIREMENTS.

18. DEFINITION OF ACRONYMS USED IN THESE DRAWINGS:

A. NIC (N.I.C.) - NOT IN CONTRACT

B. OFE (O.F.E.) = OWNER FURNISHED EQUIPMENT. SEE RESPONSIBILITY MATRIX FOR MORE INFORMATION.

C. DHI (D.H.I.) = DOOR HARDWARE INSTALLER

D. USC (U.S.C.) = UNDER SEPARATE CONTRACT.

19. ALL REQUIRED WALL PENETRATIONS, EXISTING AND NEW, SHALL MAINTAIN THE NEW WALL RATING AFTER CABLING HAS BEEN INSTALLED OR REMOVED.

20. ALL SPEAKERS MOUNTED IN A CEILING TILE SHALL BE CENTERED IN THE CEILING TILE.

1. SYMBOLS USED TO REPRESENT DEVICES SUCH AS CCTV CAMERAS, INTERCOM STATIONS, SECURITY WORKSTATIONS, CALL STATIONS, AND EMERGENCY PHONE STATIONS REQUIRE ONE (1) DATA DROP FOR SUCH DEVICE. THIS DATA DROP IS NOT SHOWN ON THE VOICE/DATA FLOOR PLANS, BUT SHALL BE PROVIDED FOLLOWING ALL REQUIREMENTS FOR VOICE/DATA DROPS INDICATED IN THE DRAWING DETAILS AND IN THE SPECIFICATION "STRUCTURED

CABLING SYSTEM".

2. ANY DATA DROPS FOR SECURITY DEVICES EXCEEDING 295 FT. OF PERMANENT LINK DISTANCE TO THE TELECOM ROOM WHERE CAMERA WILL BE WIRED TO, SHALL BE WIRED WITH FIBER OPTICS FOR HORIZONTAL CABLING AND A 2 CONDUCTOR AWG-16 CL2(P) CABLE. THE FIBER CABLE SHALL BE AS DESCRIBED IN SPECIFICATION "STRUCTURED CABLING SYSTEM". IF NO INDICATION IN SUCH SPECIFICATION, FIBER OPTIC CABLE SHALL BE A 2-STRAND OM1

CABLE WITH A SUITABLE JACKET FOR THE APPLICATION.

3. ALL DOUBLE DOORS THAT ARE SHOWN WITH TWO DOOR POSITIONS SWITCHES ARE TO RECEIVE (1) DOOR POSITION SWITCH ON EACH DOOR LEAF AND

SHALL REPORT AS ONE ALARM POINT.

4. ALL CAMERAS, CARD READERS AND/OR KEYPADS DEDICATED FOR ELEVATOR FLOOR SELECTION CONTROL ARE SHOWN INSIDE THE ELEVATOR CAB ON THE

LOWEST LEVEL FLOOR PLAN TO WHICH THE ELEVATOR TRAVELS.

5. LOCATION OF SURVEILLANCE CAMERAS SHALL BE CLOSELY COORDINATED WITH OTHER TRADES TO AVOID OBSTRUCTIONS IN THE FIELD OF VIEW. IT IS NOT REQUIRED FOR CAMERAS TO BE MOUNTED IN CENTER OF A CEILING TILE (OR CENTER OF A HALLWAY) IF THAT LOCATION CAUSES AN OBSTRUCTION IN THE FIELD OF VIEW OF THE CAMERA. ALL CAMERAS ARE TO BE INSTALLED AS TO MINIMIZE THE OBSTRUCTIONS IN THE FIELD OF VIEW WITHIN A 4' RADIUS

OF THE SPECIFIED LOCATION.

6. SURVEILLANCE CAMERAS INDICATED IN THE CORNER OF A ROOM SHALL BE INSTALLED AS CLOSE AS PHYSICALLY POSSIBLE TO THE CORNER OF THE ROOM

TO GAIN THE BEST FIELD OF VIEW FOR THAT CAMERA.

7. EACH ACCESS CONTROLLED DOOR IN THE PROJECT HAS A DOOR IDENTIFIER SYMBOL THAT ASSOCIATES THE DOOR TO A CORRESPONDING ROUGH-IN DETAIL IN THE DRAWINGS AND A SPECIFIC FUNCTIONALITY OF THE DOOR IN THE SECURITY SPECIFICATIONS.

SECURITY SYSTEM GENERAL NOTES

CONDUIT SLEEVES

X= QTY OF SLEEVES

Y= SIZE OF CONDUITS SLEEVES PENETRATING WALL ABOVE CEILING SPACE.

IF NO QUANTITY INDICATED USE AS MANY SLEEVES AS REQUIRED TO MATCH CROSS

SECTIONAL AREA OF CABLE TRAY NEXT TO SLEEVE.

X Y

SURFACE MOUNTED ENCLOSED TECHNOLOGY SYSTEMS. SEE SHEETS WITH DETAILS FOR

ADDITIONAL INFORMATION

CABLE ROUTING NOTESX

DRAWING KEYED NOTESX

DRAWING NOTES AND DESIGNATIONS

XXX

DOOR TYPE IDENTIFIER

X= TYPE (A1,C3,B6..) REFER TO SECURITY DOOR DETAILS

DETAIL OR SECTION REFERENCE TAG

X

X

GENERAL

JUNCTION BOX WALL MOUNTED. SIZE PER NEC IF NOT INDICATED ON DRAWING. NEMA 1 FOR

INTERIOR, NEMA 4X FOR EXTERIOR USE WITH HINGED COVER AND LOCKING COVER

J

JUNCTION BOX CEILING MOUNTED. SIZE PER NEC IF NOT INDICATED ON DRAWING. NEMA 1 FOR

INTERIOR, NEMA 4X FOR EXTERIOR USE WITH HINGED COVER AND LOCKING COVER

J

X V

TELECOMMUNICATIONS GROUND VAULT. SEE DETAILS AND SPECS FOR MORE INFORMATION

X= BOX TYPE. IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

X

PP

POWER POLE FOR COMBINED USE - TECHNOLOGY SYSTEMS AND POWER.

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

NURSE CALL SYSTEMS

SINGLE PATIENT STATION, WALL MOUNTEDN1

DUAL PATIENT STATION, WALL MOUNTEDN2

DUTY STATION, WALL MOUNTEDD

STAFF ASSIST STATION, WALL MOUNTEDS

CODE BLUE/STAFF ASSIST STATION, WALL MOUNTEDCA

STAFF ASSIST STATION, WALL MOUNTEDSA

TOILET STATION, WALL MOUNTEDT

SHOWER PULL STATION, WALL MOUNTEDSH

CODE BLUE STATION, WALL MOUNTEDCB

CORRIDOR DOME LIGHT, WALL MOUNTEDC

CORRIDOR DOME LIGHT, CEILING MOUNTEDC

CORRIDOR ZONE DOME LIGHT, WALL MOUNTEDZ

CORRIDOR ZONE DOME LIGHT, CEILING MOUNTEDZ

STAFF TERMINAL, WALL MOUNTEDST

BED CONNECTOR, WALL MOUNTEDB

PILLOW SPEAKERPS

GUEST SPEAKER, WALL MOUNTEDGS

NURSE CALL MASTER STATION, DESK MOUNTEDNM

X

WHEN THIS SYMBOL IS INDICATED ON THE NURSE CALL DRAWINGS IT IDENTIFIES THE AUDIO

CONNECTION FOR THE WALL MOUNTED TV TO THE NURSE CALL SYSTEM. SEE SHEET WITH DETAILS

FOR MORE INFORMATION

X= TYPE

TV

CODE BLUE ANNUNCIATOR PANEL, WALL MOUNTED

CBAP

NURSE CALL EQUIPMENT CABINET, WALL MOUNTED

NCEC

NURSE CALL SYSTEM CONDUIT AND WIRING

ELECTRIC MORTISE LOCK OR ELECTRIC TRIMEM

ELECTRONIC SECURITY SYSTEM

VIDEO SURVEILLANCE SYSTEMS

CARD READER, WALL MOUNTEDCR

CARD READER WITH INTEGRATED KEYPAD, WALL MOUNTEDCK

BIOMETRIC ACCESS CONTROL DEVICE, WALL MOUNTEDBR

DELAYED EGRESS MAG LOCKDM

ELECTRIC LATCH RETRACTION LOCKEL

ELECTROMAGNETIC LOCKML

ELECTRIC DOOR STRIKEES

ELECTRIC DOOR OPERATOR (ACTUATOR ARM)DO

DOOR POSITION SWITCHDPS

A

DOOR RELEASE BUTTON, WALL MOUNTED

X= A: ADA ACCESSIBLE - (PALM ACTUATOR), W: HAND WAVE, NO TYPE: REGULAR PUSH BUTTON

DOOR RELEASE BUTTON, DESK MOUNTED

REQUEST TO EXIT DEVICE (IR SENSOR), MOUNT CENTERED ABOVE DOOR FRAMEREX

DURESS PANIC BUTTON, MOUNTED UNDER DESKD

MOTION DETECTOR, WALL MOUNTED, MOUNT 6" BELOW CEILING OR 8'-0" AFF MAXMD

MOTION DETECTOR, 360 DEGREE SENSOR, CEILING MOUNTEDMD

LINE BETWEEN SECURITY DEVICES, INDICATES ASSOCIATED EQUIPMENT

I CONTROLLED DOOR INTERLOCK GROUP. PROGRAMMED SO ONLY ONE DOOR CAN BE OPEN AT A

TIME.

X

FIBER BDA

X= FIBER BDA NUMBER

BDA

Z

DAS SPLITTER

X= SPLITTER NUMBER

ROOF ANTENNA, WALL MOUNTED

X

WHEN THIS SYMBOL IS INDICATED ON THE NURSE CALL DRAWINGS IT IDENTIFIES THE AUDIO

CONNECTION FOR THE CEILING MOUNTED TV TO THE NURSE CALL SYSTEM. SEE SHEET WITH

DETAILS FOR MORE INFORMATION

X= TYPE

TV

AUDIO VISUAL EQUIPMENT

FLIP TOP DEVICE MOUNTED ON TABLEFT

MX

MICROPHONE, DESK MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

X

TS

TOUCH SCREEN FOR AUDIO/VIDEO CONTROL, DESK MOUNTED

X= DENOTES TYPE OF OUTLET, SEE RISER FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

TT

XX

+YY

TT= DISPLAY TYPE WITH MOUNT

YY= HEIGHT TO CENTER OF SCREEN

XX= SCREEN SIZE

AUDIO VISUAL DISPLAY

Y-Z

NO ZONE INDICATES LOCAL ZONE FOR A/V SYSTEM IN ROOM

Z= DENOTES SPEAKER # IN ZONE

Y= SPEAKER ZONE

X= SPEAKER TYPE (S1=PUBLIC ADDRESS , S2=A/V SYSTEM SPEAKER)

CEILING MOUNTED SPEAKER

SX

W= DENOTES SPEAKER WATTAGE TAPW

Y-Z

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF DEVICE

Z= DENOTES SPEAKER # IN ZONE

Y= SPEAKER ZONE

X= SPEAKER TYPE

WALL MOUNTED SPEAKER

SX

W= DENOTES SPEAKER WATTAGE TAPW

+H

NO ZONE INDICATES LOCAL ZONE FOR A/V SYSTEM IN ROOM

PX

PODIUM FOR AV EQUIPMENT, REFER TO DETAIL SHEETS

X= DENOTES TYPE OF OUTLET, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

CAMERA FOR AV SYSTEM, CEILING MOUNTED

X= DENOTES TYPE OF OUTLET, SEE RISER FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

AV X

+H

CAMERA FOR AV SYSTEM, WALL MOUNTED

X= DENOTES TYPE OF OUTLET, SEE RISER FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET

AV X

X MOTORIZED PROJECTION SCREEN

X= DIAGONAL DIMENSION IN INCHES

X PULLDOWN PROJECTION SCREEN

X= DIAGONAL DIMENSION IN INCHES

OVERHEAD PROJECTOR WITH MOUNT

Y= LENS THROW RATIO

X= TYPE

Y

X

BROADBAND TELEVISION SYSTEM

RX ANTENNA

TX ANTENNA

TX/RX ANTENNA

2 WAY SPLITTER

3 WAY SPLITTER

4 WAY SPLITTER

8 WAY SPLITTER

SATELLITE DISHSD

I

T= TAP LEGS, QTY AS INDICATED IN RISER

O= OUTPUT LEG

I= INPUT LEG

DISTRIBUTION TAP

O

T

I

T= TAP LEGS, QTY AS INDICATED IN RISER

O= OUTPUT LEG

I= INPUT LEG

DIRECTIONAL COUPLER

O

T

CATV TAP DEFINITION TAG

Y= TAP VALUE IN dB

X= NUMBER OF TAP LEGSXW-Y

I

O= OUTPUT LEG

I= INPUT LEG

X= EQUALIZING VALUE IN dB

CATV EQUALIZER

O

EQ

-X

TERMINATOR

SURGE SUPRESSOR AT BUILDING ENTRY POINT

X

T= TEST PORT

O= OUTPUT LEG

I= INPUT LEG

CATV AMPLIFIER

O T

I

X= AMPLIFIER TYPE - SP: SERVICE PROVIDER, H: HEADEND AMPLIFIER, D: DISTRBUTION AMPLIFIER

KEYPAD, WALL MOUNTEDKP

WIRELESS MORTISE LOCK, DOOR MOUNTEDWM

INTRUSION ALARM KEYPADIK

DELAYED EGRESS LATCH LOCKDE

ELECTRIC GATE OPERATORGO

X

MX

MICROPHONE, CEILING MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

NEW EQUIPMENT

EXISTING WORK AND/OR EQUIPMENT REFERENCE, SHOWN ON MULTIPLE DRAWINGS

DEVICE TO BE REMOVED (DEMO PLANS) UNDERFLOOR CONDUIT (NEW PLANS)

MATCH LINE REFERENCING CONTINUATION ON OTHER DRAWINGS

CABLE ROUTING BOUNDARY

WIRE AND/OR CONDUIT RUN CONTINUED ON REFERENCED DETAIL

DETAIL AND/OR SECTION REFERENCE

FUTURE WORK

X

IM

INTERCOM MASTER STATION, DESK MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT, REFER TO RISER FOR TYPE

INFANT ABDUCTION SYSTEM, CEILING MOUNTED ABOVE DOORIA

X Y

Z Z= SPLITTER NUMBER THE ANTENNA IS ASSOCIATED WITH

Y= ANTENNA NUMBER

X= ANTENNA TYPE

DAS ANTENNA, CEILING MOUNTED

A

X Y Z +H

Z= SPLITTER NUMBER THE ANTENNA IS ASSOCIATED WITH

Y= ANTENNA NUMBER

X= ANTENNA TYPE

DAS ANTENNA, WALL MOUNTED

A

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF DEVICE

TT

XX

+YY

TT= DISPLAY TYPE WITH MOUNT

YY= HEIGHT TO CENTER OF SCREEN

XX= SCREEN SIZE

INTERACTIVE WHITEBOARD

MONITORED - DOOR MONITORED

BIOMETRIC - BIOMETRIC READER

CR - CARD READER

FREE - NO ACCESS CONTROL

ACCESS CONTROL DOOR DIRECTION, A1/A2 - REPRESENTS ACCESS CONTROL PATH

A1

CR/KP - CARD READER AND KEYPAD

A2

X

AS

ASSISTANCE STATION (BLUE LIGHT), TOWER STATION

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT, REFER TO SPECIFICATION FOR TYPE

SENS MICROPHONE FOR AMBIENT NOISE, CEILING MOUNTEDSM

FIBER OPTICS ROUTING TAG FOR BACKBONE CABLING

N= DENOTES CONNECTION TYPE (P=PRIMARY, S=SECONDARY)

XX= DENOTES FIBER STAND QUANTITY

Z= DENOTES RUN NUMBER

REFER TO FIBER OPTICS RISER FOR MORE INFORMATION.

N-XX-Z

X

PB

TELECOMMUNICATIONS PULLBOX. SEE DETAILS AND SPECS FOR MORE INFORMATION

X= BOX TYPE. IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

TECHNOLOGY POLE. SEE SHEETS WITH DETAILS FOR ADDITIONAL INFORMATIONTP

BALANCED MAGNETIC SWITCHBMS

ELECTRONIC DETENTION LOCKDL

ELECTRIC CYLINDRICAL LOCKEC

WIRELESS CYLINDRICAL LOCK, DOOR MOUNTEDWC

WIRED IP LOCK, DOOR MOUNTEDIP

GATE PEDESTALGP

GLASS BREAK SENSOR, CEILING MOUNTEDGB

X +H

AV WALL BOX, REFER TO DETAIL SHEETS

X= DENOTES TYPE OF OUTLET, SEE DETAIL FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

AV

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 1'-6" AFF

LN

FLOOR BOX FOR TECHNOLOGY SYSTEMS AND POWER OUTLETS. REFER TO POKE-THRU/

FLOORBOX SCHEDULE FOR MORE INFORMATION

F= FLOOR CONDITION: (C= CONCRETE TYPE, G= GRADE, R= RAISED FLOOR, W= WOOD)

Y= DENOTES # OF GANGS (1,2,3...)

Z= DENOTES PLATE TYPE (A,B,C....), A= NO AUDIO/VISUAL

LN= AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

FYZ

LN

POKE-THRU FOR TECHNOLOGY SYSTEMS AND POWER OUTLETS. REFER TO POKE-THRU &

FLOOR BOX SCHEDULE FOR MORE INFORMATION

Y= DENOTES POKE-THRU SIZE (4=4", 6=6" 8=8".....)

Z= DENOTES PLATE TYPE (A,B,C....), A= NO AUDIO/VISUAL

LN= AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

YZ

X

FF

FLOOR BOX USED TO FEED CABLES TO MODULAR FURNITURE, REFER TO DETAIL SHEET

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

X

FP

POKE-THRU USED TO FEED CABLES TO MODULAR FURNITURE, REFER TO DETAIL SHEET

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT

+H

VOLUME CONTROL, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

VC

+H

SENS MICROPHONE FOR AMBIENT NOISE, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 8'-0" AFF

SM

+H

MICROPHONE, WALL MOUNTED

X= DENOTES TYPE OF OUTLET, IF NOT SHOWN, ONLY ONE TYPE

MX

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET

X +H

TOUCH SCREEN FOR AUDIO/VIDEO CONTROL, WALL MOUNTED, INCLUDES BACK BOX

X= DENOTES TYPE OF OUTLET, SEE RISER FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

TS

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

+H

AV INPUT WALL PLATE

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET

AVI

X +H

ROOM SCHEDULING PANEL, WALL MOUNTED, INCLUDES BACK BOX

X= DENOTES TYPE OF OUTLET, SEE RISER FOR MORE INFO, IF NOT SHOWN, ONLY ONE TYPE

RS

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

LV

WALL SWITCH FOR MOTORIZED SCREEN

+H

WIRELESS ANTENNA FOR WIRELESS MICRPHONE, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 8'-0" AFF

WA

+H

PIM MODULE FOR WIRELESS LOCKS, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

WG

+H

ALARM, BLUE LIGHT, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

BL

+H

LOCAL ALARM - HORN/STROBE, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

LA

+H

SIREN ALARM FOR INTRUSION DETECTION, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

SA

X +H

ASSISTANCE STATION, WALL MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT, REFER TO SPECIFICATION FOR TYPE

AS

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

X +H

INTERCOM SUBSTATION (DOOR STATION), WALL MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT, REFER TO RISER FOR TYPE

IS

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

X +H

INTERCOM MASTER STATION, WAll MOUNTED

X= TYPE, IF NOT SHOWN, ONLY ONE TYPE IN PROJECT, REFER TO RISER FOR TYPE

IM

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

+H

CALL STATION (THROUGH PHONE LINE) FOR BUILDING ENTRY, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF

CS

+H

GLASS BREAK SENSOR, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

GB

+H

DURESS PANIC BUTTON, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 4'-0" AFF D

+H

INFANT ABDUCTION SYSTEM, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 8'-0" AFF

IA

X U +H

TV WALL BOX WITH TV OUTLET, COORDINATE ROUGH-IN WITH TV MOUNT INSTALLER

X= DENOTES TYPE OF OUTLET, SEE DETAILS FOR MORE INFORMATION

TV

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

U=USER(IF APPLICABLE). THIS ONLY APPLIES TO DATA AND FIBER NOT COAX

X U +H

TELEVISION OUTLET, COORDINATE ROUGH-IN WITH TV MOUNT INSTALLER, CEILING MOUNTED

X= DENOTES TYPE OF OUTLET, SEE DETAIL FOR MORE INFORMATION

TV

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 7'-0" AFF

U=USER(IF APPLICABLE). THIS ONLY APPLIES TO DATA AND FIBER NOT COAX

SY

U +H

Y: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

MECH OUTLET FOR MECHANICAL/ ELECTRICAL/ FIRE ALARM/ ELEVATOR/ STAR CONNECTION

+H= IF NOT SHOWN, COORDINATE EXACT LOCATION WITH DEVICE

XY

U +H

Y: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

WAP OUTLET FOR WIRELESS ACCESS POINT, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 8'-0" AFF

XY

U XY: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

OUTLET FOR WIRELESS ACCESS POINT, MOUNTED ON FINISHED CEILINGWAP

W,WP

XNYZ

U +H

TELECOMMUNICATION OUTLET

X= MOUNTING: (E= EXISTING, F= FLUSH, S= SURFACE, M= MODULAR FURNITURE ADAPTER,

P= POLE, L= FLOOR, R= RACEWAY)

N= NUMBER OF DATA CABLES IN THE FACEPLATE

Y= NOT USED

Z= NUMBER OF FIBER OPTIC STRANDS IN THE FACEPLATE

U= USER(IF APPLICABLE)

+H= INSTALLATION HEIGHT IN INCHES AT CENTER OF OUTLET, COORDINATE WITH

ELECTRICAL. IF NOT SHOWN INSTALL AT TYPICAL RECEPTACLE HEIGHT.

W= WALL TELEPHONE FACEPLATE WITH SUPPORT STUDS, INSTALLED AT 48" AFF AT CENTER

OF OUTLET AND 12" FROM EDGE OF WALL.

WP=WEATHERPROOF

EXAMPLE: F2 = TWO DATA JACKS IN A SINGLE FACEPLATE, FLUSH MOUNTED

XY

U XY: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

CEILING MOUNTED INFORMATION OUTLET, MOUNTED ON FINISHED CEILING

XY

U

+H XY= AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

G= DENOTES # OF GANGS

AV BACKBOX, INSTALLED BEHIND DISPLAY/ CREDENZA RACK, COORDINATE BACKBOX PRIOR TO

AG

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF DEVICE

ROUGH-IN. REFER TO DETAIL & SCHEDULE FOR MORE INFORMATION

XY

U

+H XY= AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

U: AS DESCRIBED FOR TELECOMMUNICATIONS OUTLET

G= DENOTES # OF GANGS

RECESS IN-WALL STORAGE BOX, INSTALLED BEHIND DISPLAY, COORDINATE BACKBOX PRIOR TO

RG

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF DEVICE

ROUGH-IN. REFER TO DETAIL & SCHEDULE FOR MORE INFORMATION

MASTER WIRED CLOCK SYSTEM

DOUBLE FACE WALL MOUNTED CLOCK, 8" BELOW CEILING OR 9'-0" AFF, WHICHEVER IS LOWERC1

10" DIAMETER SEMI-FLUSH CLOCK, 1'-0" BELOW CEILING OR 9'-0" AFF, WHICHEVER IS LOWERC

12" DIAMETER SEMI-FLUSH CLOCK, 1'-0" BELOW CEILING OR 9'-0" AFF, WHICHEVER IS LOWERC1

DIGITAL CLOCK, 1'-6" BELOW CEILINGD

DIGITAL ELAPSED TIME CLOCK, 6" BELOW CEILINGDL

ANALOG ELAPSED TIME CLOCK, 1'-6" BELOW CEILINGEL

ELAPSED TIMER CONTROL UNIT, 3'-8" AFFET

PATIENT CLOCK, 8'-0" AFFP

MASTER TIME CENTER, TOP OF TRIM 6'-2" AFFMC

MASTER WIRELESS CLOCK SYSTEM

GPS ANTENNA

GPS RECEIVERGPS

WIRELESS TRANSMITTER/TRANSCEIVER, SHELF MOUNTEDWT

W 12" DIAMETER SEMI-FLUSH BATTERY OPERATED CLOCK, 1'-0" BELOW CEILING OR 9'-0" AFF, WHICHEVER IS LOWER. CLOCK INDICATED WITH 120V CIRCUIT SHALL NOT BE BATTERY OPERATED

W2 DOUBLE FACE WALL MOUNTED WIRELESS CLOCK, 8" BELOW CEILING OR 9'-0" AFF, WHICHEVER IS

LOWER

W1 18" DIAMETER SEMI-FLUSH BATTERY OPERATED CLOCK, 1'-6" BELOW CEILING OR 14'-0" AFF, WHICHEVER IS LOWER. CLOCK INDICATED WITH 120V CIRCUIT SHALL NOT BE BATTERY OPERATED

CCTV

XX

+YY

FLAT PANEL DISPLAY WITH MOUNT

YY= HEIGHT TO CENTER OF SCREEN

XX= SCREEN SIZE

X

PC

SECURITY SYSTEM WORKSTATION, DESK MOUNTED

X= TYPE

X,C

PAN/TILT/ZOOM CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

PAN/TILT/ZOOM CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

FIXED CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

FIXED CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

360° CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

360° CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

180° MULTI-IMAGER CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

180° MULTI-IMAGER CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

180° CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

180° CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

360° MULTI-IMAGER CCTV CAMERA, WALL MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

X,C

360° MULTI-IMAGER CCTV CAMERA, CEILING MOUNTED

X= CAMERA TYPE (1,2,3), SEE DETAIL SHEETS FOR MORE INFORMATION, C = CAMERA NUMBER

WALL MOUNTED FURNITURE FEED USED TO FEED CABLES TO MODULAR FURNITURE OR CABLESFF

XO

OCCUPANCY SENSOR, CEILING MOUNTED

X= TYPE, C= CRESNET, E= ETHERNET

+H

SOUND BAR WITH CAMERA, WALL MOUNTED

+H= MOUNTING HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN, INSTALL AT 8'-0" AFF

SB

FC

DAS FIRE RATED ACCESS PANEL SYSTEM. REFER TO DAS ACCESS PANEL CHASE ELEVATION

ON TECHONLOGY ELEVATION SHEET FOR MORE INFORMATION

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:1

A

M

T-TJ-00

TECHNOLOGY SYMBOLS, LEGEND,

NOTES AND INDEX

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

TECH Sheet List

Sheet Number Sheet Name

T-TJ-00 TECHNOLOGY SYMBOLS, LEGEND, NOTES AND INDEX

T-TD-01 OVERALL BASEMENT FLOOR DEMO - TECHNOLOGY

T-TJ-01 OVERALL BASEMENT FLOOR NEW WORK - TECHNOLOGY

T-TJ-02.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - TECHNOLOGY

T-TJ-02.01B BASEMENT FLOOR PLAN AREA C NEW WORK - TECHNOLOGY

T-TJ-02.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - TECHNOLOGY

T-TJ-02.01D BASEMENT FLOOR PLAN AREA F NEW WORK - TECHNOLOGY

T-TJ-04 ENLARGED PLANS - TECHNOLOGY

T-TJ-07 TECHNOLOGY - RISER

T-TJ-08 TECHNOLOGY - DETAILS

T-TJ-09 TECHNOLOGY - DETAILS

T-TJ-10 TECHNOLOGY DETAILS

Revisions: Date:

UP

ELECTMECHSTAIR

ELECT ELEVATOR

ELEVATOR

ELEVATOR

SUPPORT

ELECT

STAIR

COMM

OFFICE OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HR

CORR.

SERVER

HAC TELE

HR MULTI

PURPOSE

CORRIDOR

ENTRY

OFFICE

HR

CORR.

MECH

TOILET

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE

OFFICE OFFICE

OFFICE OFFICE

OFFICE

STOR

OFFICE OFFICE

OFFICE

ELEVATOR

LOBBY

CORRIDOR

TOILET

TOILET

TOILET

TOILET

PROSTHETIC

WHEELCHAIR

CLINIC

PROS

STORAGE

MRSA

OFFICE

INFECTION

CONTROL

NURSE IRM

PH/DATA

STORAGE

CORRIDOR

ISO

ENGINEERING

LOCKSMITH

VISN

LEAD

EEO

MGR

DRUG

CONTROL

PHARMACIST

CMOP

PROGRAM

MGR

TELE

CARE

TECHS

TOILET

STOR.

PHARM.

TELE

CARE

TECHS

ADPAC

MECH

MULTI

PURPOSE

INTERN

KITCHEN

TELE

CARE

TECHS

TELE

CARE

TECHS

TOILET

DAY CARE

ADMINISTRATOR

STORAGE

FOOD

PREP

TWO

YEAR

OLD

DAY

CARE

INFANT

TELE

STORSIGNAL

TOILET TOILET

CHILD

CARE 3, 4, 5

YEAR OLD

IT EQUIPMENT AND STRUCTURED

CABLING SYSTEM TO BE REMOVED

FROM IRM PH/DATA G25 AFTER NEW

IT/DATA G03A & TELECOM G03B IS

COMPLETE AND ACTIVE

EXISTING EQUIPMENT IN COMM ROOM G-

X02 TO REMAIN. PROTECT ALL CABLING

ROUTED TO THIS ROOM DURING DEMO

EXISTING INACTIVE TELE ROOM TO BE DEMO

INTERN

KITCHEN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:0

A

M

T-TD-01

OVERALL BASEMENT FLOOR

DEMO - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 BASEMENT OVERALL DEMO PLAN - TECHNOLOGY

0 4' 8' 12'

1/8" = 1'-0"

2 ENTRANCE CORR DEMO - TECHNOLOGY

0 4' 8' 12'

DEMOLITION GENERAL NOTES:

1. CONTRACTOR TO REMOVE EXISTING CEILING MOUNTED AV EQUIPMENT AND TURN OVER TO VA.

2. REMOVE AND TURN OVER TO VA ALL EXISTING WIRELESS ACCESS POINTS AND PUBLIC ADDRESS SPEAKERS.

3. REMOVE ALL EXISTING DATA CABLING.

4. REMOVE AND TURN OVER TO VA ALL NURSE CALL HEAD END EQUIPMENT.

5. NEW TR MUST BE COMPLETED AND ACTIVATED BEFORE EXISTING IRM/DATA ROOM CAN BE DEMOLISHED.

6. ALL EXISTING FIBER TERMINATED IN EXISTING TR MUST BE EXTENDED TO NEW TR, TERMINATED & ACTIVATED BEFORE

EXISTING IRM/DATA ROOM CAN BE DEMOLISHED.

7. SEE ARCHITECTURAL PHASING PLAN FOR ADDITIONAL INFORMATION.

CORRIDOR TO

BUILDING 5

ADO POST

PRIMARY J-HOOK PATHWAY

55 SEATSAREA AAREA B

AREA A

AREA C

AREA CAREA B

AREA DAREA C

AREA C

AREA E

AREA D

AREA F

AREA FAREA E

BREAKROOM

G18

FITTING

G15

RECEPTION, OPTHA

G13

TOILET

G16

PULM/SLEEP STUDY

G23C

TOILET/SHOWER

G23E

PULM FUNCT, SLEEP STUDY

G23F

SOILED

G23B

CLEAN LINEN

G23A

TOILET

G23L

TELEHEALTH/ MONITORING

G23H

EXAM

G23K

EXAM

G23J

EXAM

G23I

EQUIP STOR

G24

RECEP/CHECK IN

G25

COPY/PRINT

G25A

EXAM/CPAP

G26

EXAM/CPAP

G28

TOILET

G30

EXAM/CPAP

G31

WORK

G-006G WORK

G-006F

WORK

G-006H

WORK

G-006J

WORK

G-006E

WORK

G-006D

WORK

G-006C

WORK

G-006B

SUPPLY

G-006A

COPY/FAX

G-006K

SUITE

G29

SLEEP LAB WAITING

G-011

STORAGE

G17A CONFERENCE

G17

NURSE MANAGER

G21

OFFICE

G22

HAC

G01B

TELECOM

G03B

IT/DATA

G03A

ASST CHIEF

G05

STERILE SUPPLY

G04

RME

G02A

CLEAN UTILITY

G02

EXAM

G07F PHOTOCOAG LASER

G07D

SPEC TESTING

G07C

VISUAL FIELDS

G07B

ULTRASOUND

G07A

CLINIC MANAGER

G07E

YAG LASER

G07G

TOMOGRAPHY/ CAMERA

G07H

MEDS

G07I

TOILET

G07J

SOILED

G08A

RECEIVING

G08

EXAM

G09E

EXAM

G09D

EXAM

G09B

EXAM

G09A

EXAM

G09G

EXAM

G09H

EXAM

G09I

EXAM

G09J

EXAM

G09K

FAMILY TOILET

G08B

SUB WAITING

G09

WORK

G-074C

WORK

G-074D

WORK

G-074E

WORK

G-074F

WORK

G-074GWORK

G-074B

COPY/FAX

G-074A

FILES

G-074H

CORRIDOR

G09L

ELEVATOR SUPPORT

G01A

ELEVATOR

G-X05

ELEVATOR

G-X04

WORK

G-026C

WORK

G-026D

WORK

G-026E

WORK

G-026F

WORK

G-026G

WORK

G-026H

WORK

G-026A

WORK

G-026B

COPY/PRINT

G13A

SUPPLY STO

G-026J

TOILET/SHOWER

G23D

ELECT

G03

ELECT

G12

COMM

G33

MECH

G11

MECH

G06

ELECT

G19

STAIR

G10

STAIR

G20

CORRIDOR

G07

CORRIDOR

G32

EXAM

G23M

EXAM

G09C

WAITING

G14

WORK STATIONS

G23G

CORRIDOR

G23

WORKSTATIONS

G09F

T-TJ-04

T-TJ-04

TELECOM G03B & IT/DATA G03A MUST

BE COMPLETED BEFORE DEMO BEGINS

EXISTING ACCESS

CONTROL TO REMAIN

EXIT ONLY

EXIT ONLY

EXIT ONLY

EXISTING ACCESS

CONTROL TO REMAIN

EXISTING ACCESS

CONTROL TO REMAIN

EXISTING EQUIPMENT IN COMM ROOM G33 TO

REMAIN. PROTECT ALL CABLING ROUTED TO

THIS ROOM DURING DEMO

PRIMARY J-HOOK PATHWAY

PRIMARY J-HOOK PATHWAY

PRIMARY J-HOOK PATHWAY

EXIT ONLY

EXISTING ACCESS

CONTROL TO REMAIN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:3

A

M

T-TJ-01

OVERALL BASEMENT FLOOR NEW

WORK - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

2 ENTRANCE CORR NEW WORK - TECHNOLOGY

0 4' 8' 12' 0 4' 8' 12'

1/8" = 1'-0"

3 BASMENT OVERALL NEW WORK - TECHNOLOGY

TV

S1

S1

S1

S1

S1

CR

D P

S

REX

E S

D P

S

REX

CR

D P

S

E S

REX

TV

S1S1

S1

S1

S1

CR

D P

S

REX

E S

CR

D P

S

E S

REX

C R

ES

R E

X

DPS

C R

DPS

ES

R E

X

COPIER

MED LOCK BOX.

L

N

P

R

S

T

U

2 4 E4 E5 5 6

E-JJ

EXAM

G09E

EXAM

G09D

EXAM

G09B

EXAM

G09A

EXAM

G09G

EXAM

G09H

EXAM

G09I

EXAM

G09J

EXAM

G09K

FAMILY TOILET

G08B

SUB WAITING

G09

WORK

G-074C

WORK

G-074D

WORK

G-074E

WORK

G-074F

WORK

G-074GWORK

G-074B COPY/FAX

G-074A

FILES

G-074H

CORRIDOR

G09L

STAIR

G10

EXAM

G09C

WORKSTATIONS

G09F

WAP

S 2

F 2 F 2 F 2

F 2

F 2

F 1

F 2F 2

F 2

F 1

F 1

F 2

F 2

F 1

WAP

S 2

F 2

F 1

F 2

F 2

F 1

F 2

F 1

WAP

S 2

F 1

F 2

F 1

F 2

F 1

F 1

+66"+66"

F 2

EXIT ONLY

L 2

L 2

L 2

L 2

L 2

L 2

L 2

L 2

L 2

L 2

A

B

C

D

G

I

J

K

L

1 2

E4 E5 6

E-JJ

H

ASST CHIEF

G05

EXAM

G07F

PHOTOCOAG LASER

G07D

SPEC TESTING

G07C

VISUAL FIELDS

G07B

ULTRASOUND

G07A

CLINIC MANAGER

G07E

YAG LASER

G07G

TOMOGRAPHY/ CAMERA

G07H

MEDS

G07I

TOILET

G07J

SOILED

G08A

RECEIVING

G08

EXAM

G09A

FAMILY TOILET

G08B

SUB WAITING

G09

MECH

G06

STAIR

G10

CORRIDOR

G07

F 1

F 1 +66"+66"

WAP

S 2

360° CAMERA

WAP

S 2

F 2

F 2

F 2

F 1

F 1

W F 1

F 2F 2

F 2 F 2

F 2

F 2

F 2 F 4

F 2

F 2F 2

F 2

WAP

S 2

WAP

S 2

F 2

F 1

EXISTING ACCESS

CONTROL TO REMAIN

L 2

L 2

F 1 1

L 2

L 2

L 2

F 2

F 2

F 2

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:4

A

M

T-TJ-02.01A

BASEMENT FLOOR PLAN AREA A &

B NEW WORK - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/4" = 1'-0"1

BASEMENT FLOOR AREA A NEW WORK - TECHNOLOGY

1/4" = 1'-0"2

BASEMENT FLOOR AREA B NEW WORK - TECHNOLOGY

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION OF TERMINATION IN DATA ROOM WITH

OWNER IT.

DATA FOR VISUAL ACUITY MONITOR. COORDINATE EXACT LOCATION & ELEVATION WITH

ARCHITECTURAL DRAWINGS & VENDOR SHOP DRAWINGS PRIOR TO ROUGH IN

DATA OUTLET IN FLOOR BOX. SEE ELECTRICAL DRAWINGS & SPECIFICATIONS FOR ADDITIONAL

INFORMATION. COORDINATE EXACT FLOOR BOX LOCATION WITH ARCHITECTURAL DRAWINGS.

T V

A V

I

T V

S1S1S1S1S1

S1

S1

S1

S1

S1

S2 S2

D P

S

D P

S

E S

E S

CR CR

REXREX

T V

REX

D P

S

T V

CR

E S

D P

S

REX

D

D

D

MX MX

T V

CR

D P

S

E S

REX

G

I

J

K

L

M

O

Q

11 12

16 18

19 20

F

E

H

BREAKROOM

G18

FITTING

G15

RECEPTION, OPTHA

G13

TOILET

G16

STORAGE

G17A

CONFERENCE

G17

NURSE MANAGER

G21

HAC

G01B

TELECOM

G03B

IT/DATA

G03A

ASST CHIEF

G05

STERILE SUPPLY

G04

RME

G02A

CLEAN UTILITY

G02

ELEVATOR SUPPORT

G01A

ELEVATOR

G-X05

ELEVATOR

G-X04

COPY/PRINT

G13A

ELECT

G03

ELECT

G12

MECH

G11

WAITING

G14

WAP

S 2

WAP

S 2

WAP

S 2

AV

L 2 F 1

F 2

+66"+66"

W F 1

360° CAMERA

F 1

F 2

F 4

F 4

F 4

360° CAMERA

WAP

S 2

F 2

W F 1

WAP

S 2

+66"+66"

(1) 1" CONDUIT FROM FLOOR BOX TO

TV BACKBOX FOR AV INPUTS

AV INPUT WALL PLATE

(1) 1-1/2" CONDUIT FROM TV BACKBOX TO

AV INPUT WALL PLATE FOR AV

CONNECTIONS

SPEAKER CONNECTIONS TO AV INPUT

WALL PLATE AND WALL MOUNTED

DISPLAY FOR IN ROOM AUDIO

T-TJ-04

EXIT ONLY

TELECOM G03B & IT/DATA G03A MUST BE

COMPLETED BEFORE DEMO BEGINS

TELECOM G03B & IT/DATA G03A MUST BE

COMPLETED BEFORE DEMO BEGINS

F 1

+66"+66"

F 1

+66"+66"

(1) 1" CONDUIT FROM FLOOR BOX TO

AV INPUT PLATE AV INPUTS

CEILING MOUNTED MIC'S

FOR ROOM AV SYSTEM

F 1

+66"+66"

F 1

F 1

F 1 1

F 1

F 1

F 1

F 1

DATA FOR WALL MOUNTED AED.

COORDINATE EXACT LOCATION

AND TERMINATION REQUIREMENTS

WITH OWNER & VENDOR SHOP

DRAWINGS PRIOR TO ROUGH IN.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

C

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:0

A

M

T-TJ-02.01B

BASEMENT FLOOR PLAN AREA C

NEW WORK - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/4" = 1'-0"

BASEMENT FLOOR AREA C NEW WORK - TECHNOLOGY

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION OF TERMINATION IN DATA ROOM WITH

OWNER IT.

DATA FOR VISUAL ACUITY MONITOR. COORDINATE EXACT LOCATION & ELEVATION WITH

ARCHITECTURAL DRAWINGS & VENDOR SHOP DRAWINGS PRIOR TO ROUGH IN

S1

S1

S1

D P

S

CR

E S

REX

D P

S

REX

CR

D P

S

E S

REX

UP

S1S1

S1

S1

S1

D P

S

CR

E S

REX

CR

D P

S

REX

E S

TV

REX

D P

S

DD

C R

ES

DPS

R E

X

E28 E29

26 27

E-LL

BREAKROOM

G18

PULM/SLEEP STUDY

G23C

TOILET/SHOWER

G23E

PULM FUNCT, SLEEP STUDY

G23F

SOILED

G23B

CLEAN LINEN

G23A

TOILET

G23L

TELEHEALTH/ MONITORING

G23H

EXAM

G23K

EXAM

G23J

EXAM

G23I

EQUIP STOR

G24

WORK

G-026C

WORK

G-026D

WORK

G-026E

WORK

G-026F

WORK

G-026G

WORK

G-026H

WORK

G-026A

WORK

G-026B

SUPPLY STO

G-026J

TOILET/SHOWER

G23D

STAIR

G20

EXAM

G23M

WORK STATIONS

G23G

CORRIDOR

G23

WAP

S 2

F 2 F 2 F 2 F 2

F 2

F 4

F 4

F 2F 2 F 2

F 2

F 2

F 1

WAP

S 2

WAP

S 2

F 2

F 2

F 2

F 2

EXIT ONLY

3 3 3 3

F 1 1

I

J

25 E28 E29 28 29 30

BREAKROOM

G18

EQUIP STOR

G24

RECEP/CHECK IN

G25

COPY/PRINT

G25A

EXAM/CPAP

G26

EXAM/CPAP

G28

TOILET

G30

EXAM/CPAP

G31

WORK

G-006G

WORK

G-006F

WORK

G-006H

WORK

G-006J

WORK

G-006E WORK

G-006D

WORK

G-006C

WORK

G-006B

SUPPLY

G-006A

COPY/FAX

G-006K

SUITE

G29

SLEEP LAB WAITING

G-011

NURSE MANAGER

G21

OFFICE

G22

COMM

G33

ELECT

G19

STAIR

G20

CORRIDOR

G32

WAP

S 2

F 2F 2

F 2

F 2

C F 2

F 2

F 2

F 2F 2

F 2

F 2

WAP

S 2

F 2

F 2

F 1

F 2

+66"+66"

F 4 F 4

WAP

S 2

F 2

360° CAMERA

WAP

S 2

F 2 F 2

EXIT ONLY

EXISTING EQUIPMENT IN COMM ROOM G33

TO REMAIN. PROTECT ALL CABLING

ROUTED TO THIS ROOM DURING DEMO

F 2

EXISTING ACCESS

CONTROL TO REMAIN

3 3 3 3

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

D

E

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:1

A

M

T-TJ-02.01C

BASEMENT FLOOR PLAN AREA D &

E NEW WORK - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/4" = 1'-0"

BASEMENT FLOOR AREA D NEW WORK - TECHNOLOGY

1/4" = 1'-0"

BASEMENT FLOOR AREA E NEW WORK - TECHNOLOGY

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION OF TERMINATION IN DATA ROOM WITH

OWNER IT.

DATA FOR VISUAL ACUITY MONITOR. COORDINATE EXACT LOCATION & ELEVATION WITH

ARCHITECTURAL DRAWINGS & VENDOR SHOP DRAWINGS PRIOR TO ROUGH IN

COORDINATE EXACT LOCATION OF DATA OUTLET WITH ARCHITECTURAL PLANS AND FURNITURE PRIOR

TO ROUGH IN.

D P

S

E S

ES

DPSDPS

CR

REX

REX

CR

S1 S1 S1 S1

I

F 4

WAP

S 2

WAP

S 2

180° CAMERA180° CAMERA

180° CAMERA

WAP

S 2

WAP

S 2

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

F

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:3

A

M

T-TJ-02.01D

BASEMENT FLOOR PLAN AREA F

NEW WORK - TECHNOLOGY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/4" = 1'-0"

BASEMENT FLOOR AREA F NEW WORK - TECHNOLOGY

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION OF TERMINATION IN DATA ROOM WITH

OWNER IT.

DATA FOR VISUAL ACUITY MONITOR. COORDINATE EXACT LOCATION & ELEVATION WITH

ARCHITECTURAL DRAWINGS & VENDOR SHOP DRAWINGS PRIOR TO ROUGH IN

COORDINATE EXACT LOCATION OF DATA OUTLET WITH ARCHITECTURAL PLANS AND FURNITURE PRIOR

TO ROUGH IN.

MD MD

IT/DATA

G03A

TELECOM

G03B

SE

CU

RI

TY

IN

TE

RC

O

M

RA

D

IO

D

AS

PU

BL

IC

A

D

DR

ES

S

TE

LE

VI

SI

O N

TE

LC

O T

ER

M

. F

IB

ER

C O

PP

ER

T

ER

M

IN

AT

IO

N S

FIXED CAMERA, PAN / TILT /

ZOOM, PASSIVE INFRARED

CAMERA - DUAL TECHNOLOGY

PRIMARY BONDING

GROUND BUSBAR

PRIMARY BONDING

GROUND BUSBAR

CEILING MOUNTED

MOTION SENSOR

(LOCATION AS

REQUIRED FOR FULL

ROOM COVERAGE

TWO POST RACKTWO POST RACK

RISER CONDUITS

AS REQUIRED

RISER CONDUITS

AS REQUIRED

3 55

F 1 F 1

AC-2AC-1

IT/DATA

G03A

TELECOM

G03B

F 1

TELEVISION

RADIO OR DAS

AC-1

PUBLIC ADDRESS TELEVISION

SECURITY

SECURITY

GROUND BUS BAR

F 1

AC-2

EXTENDED DEMARC

GROUND

BUS BAR

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:4

A

M

T-TJ-04

ENLARGED PLANS - TECHNOLOGY CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1/2" = 1'-0"1

ENLARGED IT/DATA G03A & TELECOM G03B

1/2" = 1'-0"2

ENLARGED IT/DATA G-042 & TELECOM G-044 LADDER RACK

TECHNOLOGY KEY NOTES

45RU, 30"D x 7'H x 23.75"W NETWORK EQUIPMENT RACK. MIGHTY MO 20 CABLE MANAGEMENT RACK WITH WHITE

FINISH OR APPROVED EQUAL.

6" WIDE VERTICAL CABLE MANAGEMENT. WHITE MM20 VERTICAL CABLE MANAGEMENT "CAGE" OR APPROVED

EQUAL

HORIZONTAL DISTRIBUTION TO WORK AREA OUTLETS . PROVIDE 4" FIRE STOP SLEEVES AS REQUIRED FOR

DENSITY + 10% GROWTH

WIRE MESH CABLE TRAY MINIMUM OF 4" X 12" WITH SECOND LEVEL OF FIBER CHANNEL PATHWAY (4" X 4")

MAIN CROSS CONNECT (CAMPUS/BUILDING DISTRIBUTOR) - BACKBONE CABLING (MCR-TELECOMMUNICATIONS

ROOMS) PROVIDE 4" HILTI SPEED SLEEVES AS REQUIRED FOR DENSITY + 10% GROWTH

PROVIDE 4' BY 8' AC GRADE 3/4" TRADE SIZE PLYWOOD BACKBOARD ON ALL WALLS, PAINTED HIGH-GLOSS

WHITE WITH TWO COATS OF FIRE RESISTANT PAINT.

IT/DATA ROOM ELECTRICAL DESIGN BASIS

CIRCUIT VOLTS AMPS TYPE TYP LOAD DESCRIPTION

1 208V 20A EMER 50% RACK 1 - L21-20R TWIST LOCK

2 208V 20A EMER 50% RACK 2 - L21-20R TWIST LOCK

3 120V 20A NORMAL 25% TELCO

4 120V 20A NORMAL 25% CONVENIENCE OUTLETS - MIN 2 PER WALL

TELECOM ROOM ELECTRICAL DESIGN BASIS

CIRCUIT VOLTS. AMPS. TYPE. TYP LOAD. DESCRIPTION.

1 208V 20A EMER 50% RACK 1 - L21-20R TWIST LOCK

2 208V 20A EMER 50% RACK 2 - L21-20R TWIST LOCK

3 120V 20A EMER 50% SECURITY

4 120V 20A EMER 50% INTERCOM

5 120V 20A EMER 50% PUBLIC ADDRESS

6 120V 20A EMER 50% DDC

7 120V 20A EMER 50% TELEVISION

8 120V 20A EMER 50% RADIO/DAS

9 120V 20A NORMAL 25% CONVENIENCE OUTLETS - MIN 2 PER WALL

1/2" = 1'-0"3

TELECOM - N

1/2" = 1'-0"4

TELECOM - S

1/2" = 1'-0"

TELECOM - E

1/2" = 1'-0"6

TELECOM - W

1/2" = 1'-0"

IT/DATA - N

1/2" = 1'-0"8

IT/DATA - S

1/2" = 1'-0"

IT/DATA - E

1/2" = 1'-0"10

IT/DATA - W

FIRST FLOOR

SECOND FLOOR

TELECOM G03B IT/DATA G03A

BASEMENT

24 STRAND SM TO EXISTING MCR IN BUILDING 05 VIA EXISTING CRAWLSPACE CABLE TRAY AND J-HOOKS AS REQUIRED (BLDG CONNECTIVITY)

12 STRAND SM (HC)

12 STRAND MM (HC)

100 PAIR COPPER TO EXISTING PBX ROOM IN BUILDING 117 VIA EXISTING CRAWLSPACE CABLE TRAY AND J-HOOKS AS REQUIRED (BLDG CONNECTIVITY)

100 PAIR COPPER TO EXISTING PBX ROOM IN BUILDING 117 VIA EXISTING CRAWLSPACE CABLE TRAY AND J-HOOKS AS REQUIRED (BLDG CONNECTIVITY)

TECHNOLOGY GENERAL NOTES

1. COORDINATE FIBER & COPPER TERMINATION LOCATION & ROUTE WITH OWNER IT PRIOR TO INSTALL

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:5

A

M

T-TJ-07

TECHNOLOGY - RISER CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

1 FIBER & COPPER RISER DIAGRAM

F2 / F4

ROOM #

PORT #

TR # - PP #

TELEPHONE WALL PLATE

CABLE TO TR.

W F1

MAX

5'

TO COMM/DATA ROOM

NOTE:

WIRELESS ACCESS POINT AND

ANTENNA NOT IN CONTRACT.

WAP

S2

J-HOOK

ACCESSIBLE CEILING

COIL 15' SERVICE LOOP IN CEILING.

DETAIL NOTE:

COIL CABLE IN CEILING

3/4" CONDUIT

2 GANG BACK BOX

FIN. FL.

LOCATED IN TV WALL BOX AS SHOWN

IN DETAIL #5 ON SHEET T-TJ-08

RG6 COAX

CAT 6A F-TYPE ADAPTER

SINGLE GANG FACE PLATE FOR (2) MODULES

TV NOTE: ALL DATA AT TV LOCATIONS TO TERMINATE IN TV WALL BOX

2) RANDOMLY INSTALL J-HOOKS AT 3', 4' AND 5'

APART.

TREE SYSTEM IS FOR MAIN CORRIDOR PATHWAYS.

DOUBLE AND SINGLE TREES MAYBE USED IN

ROOMS. CABLE J-HOOK SYSTEM CAN BE SECURED

TO METAL STUDS, WHERE PERMISSIBLE.

NOTES:

CADDY CABLE J-HOOKS

CONCRETE ANCHOR ROOF DECK

BAR JOIST CLAMP

1)

CEILING

M

IN

M

A X

STRUCTURED CABLING

SECURITY,

CCTV, MISC.

NURSE CALL, PUBLIC

ADDRESS, CATV

3/4" CONDUIT

PROVIDE CAT6 PATCH

CORD FROM CEILING

OUTLET TO CAMERA

JUNCTION BOX

WITH DATA BISCUIT

CONDUIT STRAP

SECURED TO

STRUCTURE

CONCRETE

DECK ABOVE

"C" BRACKET AND TILE RAIL

SELF-LOCKING TAB SCREWS

LAY IN CEILING TILECEILING TEE'S

WIRING COMPARTMENT

CEILING TILE WIRE

SECURE SECONDARY

SUPPORT CABLE FROM

BUILDING STRUCTURE

SECONDARY SUPPORT TAB

L2

COVER

1" EMPTY CONDUIT WITH

PULLSTRING, RUN TO

NEAREST WALL AND STUB 6"

ABOVE ACCESSIBLE CEILING

POWER CONDUIT TO NEXT

FLOORBOX OR TO

PANELBOARD

POWER RECEPTACLE SEE

ELECTRICAL DRAWINGS

AV CHAMBERS REQUIRED FOR FLOOR

BOXES WITH "AV" SUBSCRIPT.

TELE. DATA CHAMBER

1" EMPTY CONDUIT WITH

PULLSTRING, RUN TO NEAREST

WALL AND STUB 6" ABOVE

ACCESSIBLE CEILING UNLESS

NOTED OTHERWISE ON

DRAWINGS

1" EMPTY CONDUIT WITH

PULLSTRING, RUN TO NEAREST

WALL AND STUB 6" ABOVE

ACCESSIBLE CEILING UNLESS

NOTED OTHERWISE ON

DRAWINGS

COORDINATE WITH ELECTRICAL & ARCHITECTURAL DRAWINGS

AV

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V

A M

C S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p

L a b

E

T

R

.r v t

/1

/2

:5

:0

A

M

T-TJ-08

TECHNOLOGY - DETAILS CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

TH07/10/2024

626-310

JK

100% CONSTRUCTION

DOCUMENTS

No Scale

WALL MOUNTED OUTLET - FOUR PORT FACEPLATE 1

No Scale

WALL PHONE OUTLET - W/FI 2

No Scale

WIRELESS ACCESS POINT (COILED IN CEILING) 3

No Scale

TV OUTLET 4No Scale

CABLE HANGER (MULTI J-HOOK) 8 No Scale

GROUND BAR 6

No Scale

INTERIOR RECESSED MOUNTED FIXED CAMERA 7 No Scale

POWER/DATA/AV FLOOR BOX 5

PROVIDE

DOUBLE-GANG BOX

WITH SINGLE GANG

MUD RING

FOR READER. SEE

FLOOR PLAN

FOR SPECIFIC TYPE

AND PLACEMENT.

44" A.F.F.

6"

4" x 4" SQUARE J-BOX.

MAGNETIC DOOR

CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

ELECTRIC STRIKE

AND

ACCOMMODATING

HARDWARE

FINISHED FLOOR

FINISHED CEILING

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

ELECTRIFIED HINGE

(PROVIDED BY DOOR

HARDWARE

INSTALLER)

2" x 4" J-BOX FLUSH MOUNTED

FOR EGRESS MOTION SENSOR.

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND PLACEMENT.

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND

PLACEMENT.

44" A.F.F.

6"

44" A.F.F.

6"

ELECTRIC STRIKE AND

ACCOMMODATING

HARDWARE

FINISHED CEILING FINISHED CEILING

MAGNETIC DOOR CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

FINISHED FLOOR

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

4" x 4" SQUARE J-BOX.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

UNSECURE SIDE SECURE SIDE

POWER

SUPPLY

5'

MAX

WALL

1" CONCEALED CONDUIT EMT

FACEPLATE

DEEP 4 SQUARE BOX WITH

SINGLE GANG STEEL PLASTER

RING.

ACCESSIBLE CEILING

FLOOR SLAB

CABLE TRAY

J-HOOKS BY DIV. 17

COORDINATE EXACT

HEIGHT WITH

ARCHITECTURAL PLANS

AND SECTIONS PRIOR

TO ROUGH-IN

ACCESSIBLE CEILING

FINISHED FLOOR

COORDINATE WITH TV / MONITOR MOUNTING BRACKET.

CENTER BEHIND WALL MOUNTED TV / MONITOR.

AV / TV WALL BOX. SEE DETAILS

(1) 1-1/2" CONDUIT IN WALL

FOR LOW VOLTAGE CABLES

CONDUIT STUBBED ABOVE CEILING

WITH CONDUIT BUSHING

TO ELECTRICAL PANEL

(1) 3/4" CONDUIT FOR POWER

(1) 1-1/2" CONDUIT TO FLOOR BOX IF APPLICABLE. SEE TECHNOLOGY

DRAWINGS FOR LOCATION AND ADDITIONAL INFORMATION

WALL MOUNTED TV / MONITOR

AV

FSR PWB-100

BOX (OR EQUAL)

SHOWN WITH ACCESSORY

LOW-VOLTAGE CONDUIT

ENTRY BOX

120VAC POWER PROVIDED BY

ELECTRICAL CONTRACTOR

COVER TO BE

FLUSH WITH WALL

CENTER COVER TO BE

FLUSH WITH WALL

PROVIDE CATV CABLE AND FSR

CONNECTOR PLATES FOR

CONNECTION TO WALL MOUNTED

DISPLAY: PLATE #'S…