Attachment 11 - DWG - 07 - P.pdf

PDF 14 MB Posted

Attached to
Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
Solicitation number
36C77625B0035
Issued by

About this file

This document is a comprehensive set of plumbing engineering drawings for the VA Medical Center Sleep Disorder Clinic and Specialty Clinic construction project located in Murfreesboro, Tennessee. The drawings, prepared by TLC Engineers and dated July 10, 2024, include detailed plumbing system plans for multiple building levels including crawlspace, basement, first floor, second floor, and attic, with both gravity and pressure system diagrams.

The drawings specify intricate plumbing infrastructure details including sanitary drainage systems, domestic water supply lines (cold and hot water), medical gas systems, fixture locations, pipe routing, valve placements, and equipment specifications. Key components include a steam-to-water heater (HE-1), hot water recirculation pump (RP-1), various medical gas lines, floor drains, cleanouts, and multiple fixture types such as water closets, lavatories, and specialty clinical fixtures. The documents emphasize precise routing, compliance with VA plumbing guidelines, and careful coordination with architectural and structural elements across different building zones.

View the file

Other files

File Type Posted
36C77625B0035 Amendment 0004.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
VAAR 852.236-92 NOTICE TO BIDDERS—ADDITIVE OR DEDUCTIVE BID LINE ITEMS APR 2019.docx DOCX document
Attachment 23 - VA Sleep Lab - Civil Specs.pdf PDF
36C77625B0035 Amendment 0003.docx DOCX document
Tech Questions Tracker - Murfreesboro_Responses 8.6.25.docx DOCX document
Attachment 19 - Site Layout.pdf PDF
Attachment 20 - 085653 Blast resistant Windows.pdf PDF
Attachment 22 - 102113 Toilet Compartments.pdf PDF
Attachment 18.docx DOCX document
Attachment 21 - 088000 Glazing.pdf PDF
Solicitation section 2.3 and 2.8 revisions.docx DOCX document
Attachment 17 - DWG - 02 - C.pdf PDF
36C77625B0035 Amendment 0002.docx DOCX document
Site Visit Sign-in Sheet - Murfreesboro - 7.16.pdf PDF
36C77625B0035 Amendment 0001.docx DOCX document
Attachment 10 - DWG - 06 - M.pdf PDF
Attachment 6 - DWG - 01 - G.pdf PDF
Attachment 1 - Wage Rates - Rutherford County 6.6.25 - Murfreesboro.pdf PDF
Attachment 14 - DWG - 10 - T.pdf PDF
Attachment 4 - Specs Vol 1.pdf PDF
Attachment 12 - DWG - 08 - E.pdf PDF
Attachment 2 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - Specs Vol 2.pdf PDF
Attachment 16 - VHA ICRA Sleep Disorder.docx DOCX document
Attachment 15 - VHA PCRA Sleep disorder.docx DOCX document
Attachment 8 - DWG - 04 - I.pdf PDF
Attachment 3 - Site Visit Instructions Murfreesboro.pdf PDF
Attachment 9 - DWG - 05 - S.pdf PDF
Attachment 7 - DWG - 03 - A.pdf PDF
36C77625B0035_1.docx DOCX document
Attachment 13 - DWG - 09 - FP.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FDFD

- BALL VALVE (SHUT-OFF VALVE)

- DIRECTION OF FLOW

- REDUCED PRESSURE BACKFLOW PREVENTER

- DOMESTIC COLD WATER

- DOMESTIC HOT WATER

- FUEL OIL FILL

- BELOW GROUND SANITARY

- FLOOR CLEAN OUT

- FLOOR DRAIN

- CALIBRATED BALANCING VALVE (BV)

- CHECK VALVE (SWING)

- RELIEF OR SAFETY VALVE

- PRESSURE REDUCING VALVE

- SOLENOID OPERATED VALVE

- ABOVE GROUND SANITARY

- DENTAL AIR

CO

1 - REVISION REFERENCE

- DETAIL REFERENCE: TOP-DETAIL#,

BOTTOM-DRAWING# SHOWN ON

- DOMESTIC HOT WATER RETURN

1. REFERENCE THE SPECIFICATIONS FOR MATERIAL AND EQUIPMENT INSTALLATION STANDARDS.

2. UTILITIES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND NEW SURVEYS, AS-BUILT RECORDS AND FIELD INVESTIGATIONS. UNFORSEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND BURIAL DEPTHS, AS

DETERMINED DURING CONSTRUCTION, WILL BE NECESSARY.

3. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH ARE TO REMAIN ACTIVE, TO

FACILITATE RECONNECTION AND EXTENSION OF THE NEW WORK.

4. NOTIFY OWNER AT LEAST 10 DAYS PRIOR TO INTERRUPTING EXISTING SERVICE. SCHEDULE DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES. SERVICES ARE NOT TO BE LEFT DISRUPTED DURING NON-NORMAL CONTRACTOR WORKING HOURS. CONTRACTOR TO PRODUCE COORDINATION DRAWINGS AND SCHEDULES. THIS

MAY REQUIRE NIGHT AND OR WEEKEND WORK SCHEDULES.

5. PIPE ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO INDICATE EXACT ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL INSTALLATIONS AND OTHER POTENTIAL

OBSTRUCTIONS AND ROUTE PIPING TO AVOID INTERFERENCES.

6. PROVIDE ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO SITE UTILITIES.

7. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL ROOMS OR AS

SPECIFICALLY NOTED.

8. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN WALLS OR ABOVE NON-ACCESSIBLE CEILINGS.

9. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL TO OR EXCEED THE RATING OF THE WALL, CEILING OR

FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES.

10. FLASH AND COUNTER-FLASH ROOF PENETRATIONS. SEE ARCHITECTURAL DRAWINGS FOR DETAILS.

11. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH ALL TRADES, THE

ARCHITECT AND THE STRUCTURAL ENGINEER.

12. PROVIDE FOUNDATION PAD PENETRATION SLEEVES. ALLOW 1" MINIMUM CLEARANCE BETWEEN SLEEVE INSIDE

SURFACE AND PIPE EXTERIOR.

13. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.

14. PROVIDE ELECTRONIC AUTOMATIC TRAP PRIMERS FOR FLOOR DRAIN TRAP SEALS.

15. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND

APPARATUS.

16. ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED.

17. MOUNT HOSE BIBBS 24" ABOVE FINISHED GRADE, UNLESS OTHERWISE NOTED.

18. PROVIDE CLEANOUTS IN ACCORDANCE WITH V.A. PLUMBING GUIDELINES. INSTALL CLEANOUT WITH COVER FLUSH

TO FINISH SURFACE.

19. COORDINATE EXACT FLOOR DRAIN LOCATIONS WITH ARCHITECTURAL DRAWINGS. SET FLOOR DRAINS BELOW

FINISHED FLOOR TO ALLOW FOR FLOOR SLOPING TO THE DRAIN.

20. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY CIRCUMSTANCES. ANY

PIPING RUN OVER PANELS SHALL BE RE-ROUTED AT NO ADDITIONAL COST.

21. ALL WALL MOUNTED LAVATORIES SHALL BE ATTACHED TO FLOOR MOUNTED CARRIER DESIGNED TO WITHSTAND A

VERTICAL LOAD OF 250 POUNDS ON THE FRONT OF THE FIXTURE.

22. ALL WALL MOUNTED BARIATRIC LAVATORIES SHALL BE ATTACHED TO FLOOR MOUNTED CARRIER DESIGNED TO

WITHSTAND A VERTICAL LOAD OF 500 POUNDS ON THE FRONT OF THE FIXTURE.

23. ALL WALL MOUNTED BARIATRIC TOILETS SHALL BE ATTACHED TO FLOOR, DESIGNED TO WITHSTAND A LOAD OF

1000 POUNDS.

24. ALL WALL MOUNTED TOILETS SHALL BE ATTACHED TO FLOOR MOUNTED CARRIER DESIGNED TO WITHSTAND A

VERTICAL LOAD OF 750 POUNDS ON THE FRONT OF THE FIXTURE.

25. PROVIDE SANITARY WASTE, VENT, DOMESTIC WATER, ETC. ROUGH-IN AND MAKE FINAL CONNECTIONS (TO INCLUDE PROVIDING ALL NECESSARY RELATED STOPS, VALVES, TRAPS, ETC. AND MAKE READY FOR USE) TO ALL

EQUIPMENT, WHETHER FURNISHED BY THIS CONTRACTOR OR FURNISHED BY OTHERS.

26. MOUNT INFORMATION PLATES ON NEW SPRINKLER SYSTEMS. SEE LATEST VA FIRE PROTECTION GUIDELINES.

27. V.A. IS THE ONLY AHJ. SEE LATEST V.A. PLUMBING DESIGN MANUAL.

GENERAL NOTESPLUMBING ABBREVIATIONS

SYMBOL DESCRIPTION

- COMPRESSED AIR

- ABOVE FINISH FLOOR

- ACID WASTE

- ACID VENT

- BALANCING VALVE

- CATCH BASIN

- CONDENSATE DRAIN

- CUBIC FEET PER HOUR

- CLEANOUT

- CONTINUATION

- DOMESTIC COLD WATER

- DEIONIZED WATER

- DOWN

- DOWNSPOUT

- DRAWING

- EXISTING

- DEGREE FAHRENHEIT

- FLOOR CLEANOUT

- FLOOR DRAIN

- FUEL OIL FILL

- FUEL OIL GAGE

- FUEL OIL RETURN

- FUEL OIL SUPPLY

- FUEL OIL VENT

- FLOOR SINK

- GAS

- GALLONS PER HOUR

- GALLONS PER MINUTE

- KITCHEN WASTE (GREASE)

- HOSE BIBB

- HUB DRAIN

- DOMESTIC HOT WATER

- DOMESTIC HOT WATER RECIRCULATING

- INVERT ELEVATION

- INDIRECT WASTE

- KILOWATT

- POUNDS

-MEDICAL AIR

-MEDICAL VACUUM

- MANHOLE

-NITROGEN

-NITROUS OXIDE

- NORMALLY CLOSED

- NOT IN CONTRACT

- NORMALLY OPEN

- NON-POTABLE WATER

- NOT TO SCALE

- OUTSIDE DIAMETER

-OXYGEN

- PRESSURE REDUCING VALVE

- POUNDS PER SQUARE INCH

- POLYVINYL CHLORIDE PIPE

- ROOF DRAIN

- REDUCED PRESSURE BACKFLOW PREVENTOR

- SANITARY

- STORM DRAIN

- SQUARE FEET

- SHEET

- STORM

- OVERFLOW STORM DRAIN

- SOFT COLD WATER

- VENT

- VACUUM

- VACUUM CLEANING

- VENT THRU ROOF

- WALL CLEANOUT

- WATER

CA

AFF

AW

AV

BV

CB

CD

CFH

CO

CONT

CW

DI

DN

DS

DWG

EXIST

°F

FCO

FD

FOF

FOG

FOR

FOS

FOV

FS

G

GPH

GPM

GR

HB

HD

HW

HWR

IE

IW

KW

LBS

MA OR A

MV 0R V

MH

NI OR N

N20

NC

NIC

NO

NP

NTS

OD

OX OR O

PRV

PSI

PVC

RD

RPBP

SAN

SD

SF

SH

ST

STO

SW

V

VAC

VC

VTR

WCO

WTR

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

PLUMBING SYMBOL LEGEND

SYMBOL DESCRIPTION

P2.01

- ABOVE GROUND CONDENSATE DRAIN

- COMPRESSED AIRCA

- ACID VENTAV

- ACID WASTEAW

- BELOW GROUND ACID WASTEAW

CD

- BELOW GROUND CONDENSATE DRAINCD

DA

- DENTAL VACUUMDV

FOF

- FUEL OIL GAGEFOG

- FUEL OIL RETURNFOR

- FUEL OIL SUPPLYFOS

- DEIONIZED WATERDI

- FUEL OIL VENTFOV

- GASG

- KITCHEN WASTE (GREASE)GR

- MEDICAL COMPRESSED AIRMA

- MEDICAL VACUUMMV

- NITROGENN

- NITROUS OXIDEN20

- OXYGENOX

S

S

- SANITARY VENT

- ABOVE GROUND STORMST

- BELOW GROUND STORMST

- VACUUM (AIR)VAC

- BELOW GROUND OVERFLOW STORMSTO

- SOFT COLD WATERSW

- OVERFLOW STORM DRAINSTO

- WASTE OILWO

- WASTE OIL VENTWOV

- WATER METERM

- ROOF DRAIN

FS - FLOOR SINK

- CONNECT TO EXISTING

- DEMOLISH TO POINT INDICATED

• SCOPE OF WORK INDICATED HEREIN FOR THIS DISCIPLINE DOES NOT INDICATE

SPECIFIC REQUIREMENTS RELATED TO PHASING OF WORK, ALTHOUGH EVERY

EFFORT HAS BEEN MADE TO INCORPORATE SEQUENTIAL PHASES OF WORK AS

REQUESTED BY THE GOVERNMENT.

• PUBLIC AND STAFF ACCESS TO BUILDINGS 6 AND 5 SHALL NOT BE INTERRUPTED

AT ANY TIME DURING CONSTRUCTION.

• REFER TO SHEET GI 02.03 FOR FURTHER INFORMATION ON PROJECT PHASING

REQUIREMENTS

CONSTRUCTION PHASING/ PUBLIC AND

STAFF ACCESS/BUILDING OPERATIONS

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:4

P

M

P-PI-01

PLUMBING SYMBOLS, LEGEND,

NOTES AND INDEX

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

PLUMBING DRAWING INDEX

SHEET DESCRIPTION

P-PI-01 PLUMBING SYMBOLS, LEGEND, NOTES AND INDEX

P-PI-03 PLUMBING DETAILS

P-PI-02 PLUMBING SCHEDULES

P-PD-02 OVERALL BASEMENT FLOOR DEMO - GRAVITY

P-PD-01 OVERALL CRAWLSPACE LEVEL DEMO - GRAVITY

P-PD-03 OVERALL CRAWLSPACE LEVEL DEMO - PRESSURE

P-PD-04 OVERALL BASEMENT FLOOR DEMO - PRESSURE

P-PD-06 OVERALL BASEMENT FLOOR DEMO - MEDICAL GAS

P-PD-05 OVERALL CRAWLSPACE LEVEL DEMO - MEDICAL GAS

P-PP-01.05 GRAVITY ISOMETRIC DIAGRAM AREA A & B

P-PP-01.06 GRAVITY ISOMETRIC DIAGRAM AREA C

P-PP-01.07 GRAVITY ISOMETRIC DIAGRAM AREA D & E

P-PP-01.08 GRAVITY ISOMETRIC DIAGRAM AREA F

P-PP-01.02 OVERALL FIRST FLOOR PLAN - GRAVITY

P-PP-00.01 OVERALL CRAWLSPACE LEVEL NEW WORK - GRAVITY

P-PP-01.01 OVERALL BASEMENT FLOOR NEW WORK - GRAVITY

P-PP-02.00 OVERALL CRAWLSPACE LEVEL NEW WORK - PRESSURE

P-PP-02.01 OVERALL BASEMENT FLOOR NEW WORK - PRESSURE

P-PP-01.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - GRAVITY

P-PP-01.01B BASEMENT FLOOR PLAN AREA C NEW WORK - GRAVITY

P-PP-01.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - GRAVITY

P-PP-01.01D BASEMENT FLOOR PLAN AREA F NEW WORK - GRAVITY

P-PP-02.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - PRESSURE

P-PP-02.01B BASEMENT FLOOR PLAN AREA C NEW WORK - PRESSURE

P-PP-02.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - PRESSURE

P-PP-02.01D BASEMENT FLOOR PLAN AREA F NEW WORK - PRESSURE

Revisions: Date:

N/A

AMERICAN

STANDARD

PP-101 WATER CLOSET ADA - WALL HUNG, ELONGATED,

TOP SPUD, VITREOUS CHINA 1.28GPF MANUAL

AMERICAN

STANDARD

6047.821.002

MODEL DESCRIPTIONFIXTURE MFGMARK

BLDG1 PLUMBING FIXTURE SCHEDULE

FAUCET FLUSH VALVE

MFG MODEL MFG

N/A

PP-401

SEAT

MODEL MFG

1655SSCT BEMIS

CARRIER

MODEL MFG

STRAINER/TRAP

MODEL MFG

SUPPLIES

MODEL MFG

ZURN N/A Z1204

N/A N/A ZURN 1231

MODEL

NOTES

MCGUIRE 8872

3351.101 N/A N/A N/A

MCGUIRE LF158

INSTALL HANDLE ON WIDE SIDE OF

FIXTURE. EXTRA HEAVY DUTY

CARRIER, 750LBS.

FD-1 N/A N/A N/A N/A ZURN ZN-415-VP N/A N/A N/A N/A N/A N/A N/A N/A

N/A N/A

FLOOR DRAIN (FINISHED AREAS) - NICKLE BRONZE DURA-

COATED CAST IRON BODY W/ BOTTOM OUTLET. SQUARE GRATE. PROVIDE ELECTRONIC TRAP PRIMER

AMERICAN

STANDARD

WALL HUNG, LAVATORY 4" CENTERS ADA - WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

T&S BRASS B-1141-CR-B0199-29 MCGUIRE 2125PW MCGUIRE LF2165LK 0355.012

PROVIDE OFFSET DRAIN & SUPPLY/TRAP

COVERS/WRAPS. CHICAGO 131-CFMABRCF

THERMOSTATIC MIXING VALVE.

PP-531 N/A N/A N/A N/A

PROVIDED WITH

CASEWORK

SOLID SURFACE, 3-HOLE 4" CENTER ADA, WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

SOLID

SURFACE N/A N/A MCGUIRE MCGUIRE LF2165

STAINLESS STEEL WALL MOUNTED SERVICE SINK

23" x 18-1/2" x 12, 2-HOLE WALL FAUCET

60" x 30" SHOWER ADA, GLIDE RAIL, VACUUM BREAKER, S.S. HOSE, GRAB

BARS, LEAD-FREE TEMPERATURE/PRESSURE BALANCING MIXING VALVE .

DIV. VALVE, SHOWERHEAD, HAND SHOWER WITH CHROME MOUNTING

BRACKET. SUPPLY ELBOW WITH QUICK DISCONNECT

ACORN

T&S BRASS

T&S BRASS B-2866-05CR-L15

ELKAY ESS23122

B-1141-CR-B0199-29 2125PW

N/A N/A

PP- 812 GUY GREY

SSIB1

88156

STAINLESS STEEL ICE MAKER BOX W/

QUARTER TURN VALVE N/A N/A N/A N/AN/A N/A

N/A N/A N/A N/A ZURN 1218

PP-529 MCGUIRE 8902 MCGUIRE LF2165N/A N/A N/A N/A N/A N/A

ELKAY LKVR18-CU DRAIN. CHICAGO 131-

CFMABRCF THERMOSTATIC MIXING

VALVE. COPPER TUBING

RECOMMENDED BY CHICAGO FAUCET.

T&S BRASS B-2866-05CR-L15PP-528 MCGUIRE 8902 MCGUIRE LF2165N/A N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A N/A N/A N/A SHOWER STALL PP- 705

PROVIDE SHOWER DRAIN, WITH STAINLESS

STEEL GRATE. ANTISCALD SHOWER VALVE &

CONTROLS

SEE INTERIOR

DRAWINGS

N/A N/A N/A N/A N/A N/A

SV-16-CSH20-HHC15-

HHSH-HHGBC-GR30-

DIV-EVB-QD

PP-500

32"X32"X12" TERRAZZO BASIN WITH STAINLESS STEEL CAP

AND TILE FLANGES. SERVICE SINK FAUCET POLISHED

CHROME

SB-702 T&S BRASS B-0665-CR-BSTR N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

PROVIDE 3" DRAIN WITH RUBBER GASKET.

HOSE & WALL HOOK. SS MOP HANGER &

SPLASH GUARDS.

N/A N/AT&S BRASS B-0669-CR-RGH

TP-1

PPP

PRECISION

PLUMBING

MPB-500-115V

WITH BOX

MINI-PRIME ELECTRONIC TRAP PRIMING MANIFOLD, 1

TO 4 FLOOR DRAINS. N/A N/A N/A N/AN/A N/A N/A N/A N/A N/A N/A N/A

PROVIDE D-814PC ACCESS DOOR.

PAINT TO MATCH WALL.

N/A N/A

CHICAGO 131-CFMABRCF THERMOSTATIC

MIXING VALVE. COPPER TUBING

RECOMMENDED BY CHICAGO FAUCET.

NOTES:

1. T&S BRASS FAUCET IS FACILITY STANDARD. RATED FOR 180 DEGREE HOT WATER.

2. PROVIDE CHICAGO 131-CFMABRCF MAX TEMP. RATING 200 DEGREES (F),THERMOSTATIC MIXING VALVES. 180 DEGREE HOT WATER

TO BE USED TO FLUSH SYSTEM IF LEGIONELLA IS DETECTED. DO NOT INSTALL WITH BRAIDED STAINLESS STEEL HOSES.

3. SYMMONS SHOWER VALVES IS FACILITY STANDARD.

CLEANOUTS:

1. PROVIDE ZURN ZN-1400-VP NICKLE BRONZE FLOOR CLEANOUTS OR EQUAL. REFER TO ARCHITECTURAL DRAWINGS FOR FLOOR TYPES.

2. PROVIDE ZURN Z-1445 WALL CLEANOUTS OR EQUAL.

3. PROVIDE ZANB-1460 NICKLE BRONZE WITH SS COVER WALL ACCESS DOORS OR EQUAL.

PP-201

AMERICAN

STANDARD

WHITEHALLPP-114

INSTALL HANDLE ON WIDE SIDE OF

FIXTURE. EXTRA HEAVY DUTY

CARRIER, 750LBS.

N/A

BARIATRIC WATER CLOSET ADA -FLOOR MTD, TOP SPUD, BOTTOM

OUTLET, 1.28GPF MANUAL FLUSH. HINGED TOILET SEAT. BED PAN

CLEANSER CHROME WITH HOOK, HOSE & VACUUM BREAKER

AMERICAN

STANDARD

6047.121.002

7582.167 N/A

HSBJ

RATED 1,200LBS

BIG JOHN ZURN N/A Z1204WH2125-A-T-3-FM-

LPFS

N/A N/A N/A

N/A

AMERICAN

STANDARD

6045.013.002 N/A ZURN N/A Z12216590001EC.020 N/A N/A N/A N/A N/A URINAL ADA - WALL HUNG,TOP SPUD, VITREOUS 0.125GPF MANUAL

ELKAY LKVR18-CU DRAIN. CHICAGO 131-

CFMABRCF THERMOSTATIC MIXING

VALVE. COPPER TUBING

RECOMMENDED BY CHICAGO FAUCET.

T&S BRASS B-2862PP-524 ELKAY

MCGUIRE

LK35

MCGUIRE LF2165N/A N/A N/A N/A N/A N/A

PROVIDE ELKAY LK53 DRAIN FITTING END

OUTLET FOR 2-COMP SINKS

FS-1 N/A N/A N/A N/A ZURN ZN-1910-P-2 N/A N/A N/A N/A N/A N/A N/A N/A

SANI-FLOR RECEPTOR 8" X 8" X 6" DEEP CAST IRONBODY AND SQUARE,

MEDIUM-DUTY GRATE WITH 7/16" SLOTTED OPENINGS,WHITE ACID

RESISTING PORCELAIN ENAMEL INTERIOR AND TOP, COMPLETE WITH

WHITE ABS ANTI-SPLASH INTERIOR BOTTOM DOME STRAINER, HALF GRATE

PROVIDE ELECTRONIC TRAP PRIMER

WH-1 WOODFORD 65CH

AUTOMATIC DRAINING,FREEZELESS WALL HYDRANTS WITH

SINGLE CHECK HOSE CONNECTION ANTI-SIPHON VACUUM

BREAKERS, CHROME FINISH.

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

HB-1 PRIER P-166NP75

EXPOSED PIPE ANGLE SILL FAUCET, METAL HANDLE OR OPERATING

KEY ON LOOSE KEY VANDAL PROOF, VACUUM BREAKER BACKFLOW

DOUBLE CHECK VALVE , SATIN NICKEL FINISH

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

RH-1 PRIER P-RH4

SANITARY ROOF HYDRANT , LEAD FREE, NO DRAIN REQUIRED

WITH MOUNTING BRACKET.

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

PP-421 N/A N/A WHITEHALL -MC N/A N/AT&S BRASS B-1141-CR-B0199-29 MCGUIRE 8902 MCGUIRE LF2165LK

SHOWER STALL PP- 706 SEE INTERIOR

DRAWINGS

SHOWER ADA, GLIDE RAIL, VACUUM BREAKER, S.S. HOSE, GRAB BARS,

LEAD-FREE TEMPERATURE/PRESSURE BALANCING MIXING VALVE . DIV.

VALVE, SHOWERHEAD, HAND SHOWER WITH CHROME MOUNTING

BRACKET. SUPPLY ELBOW WITH QUICK DISCONNECT

ACORN N/A N/A N/A N/A N/A N/A N/A N/A

PROVIDE SHOWER DRAIN, WITH STAINLESS

STEEL GRATE. ANTISCALD SHOWER VALVE &

CONTROLS

SV-16-CSH20-HHC15-

HHSH-HHGBC-GR30-

DIV-EVB-QD

N/A N/A

PP-506

STERN

WILLIAMS

PP- 610 OASIS

MODULAR CONTACTLESS QUASAR VERSAFILLER WITH

VERSAFILTER III AND REMEDI FILTER. SHALL HAVE UV-C LED TREATMENT

REFRIGERATED 8.0 GPH. (BOTTLE FILLER ONLY)

MW8F2EBQ

PP- 708 GUARDIAN EMERGENCY EYE/FACE WASHG1848

PROVIDED WITH

CASEWORK

SOLID SURFACE, 3-HOLE 4" CENTER ADA, WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

SOLID

SURFACE

CHICAGO 131-CFMABRCF THERMOSTATIC

MIXING VALVE. COPPER TUBING

RECOMMENDED BY CHICAGO FAUCET.

PROVIDED WITH

CASEWORK

SOLID SURFACE, 3-HOLE 4" CENTER ADA, WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

SOLID

SURFACE

PROVIDED WITH

CASEWORK

SOLID SURFACE, 3-HOLE 4" CENTER ADA, WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

SOLID

SURFACE

PROVIDED WITH

CASEWORK

SOLID SURFACE, 3-HOLE 4" CENTER ADA, WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

SOLID

SURFACE

CHICAGO 131-CFMABRCF THERMOSTATIC

MIXING VALVE. COPPER TUBING

RECOMMENDED BY CHICAGO FAUCET. SET

TO 90°F

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

PP-402 N/A N/A ZURN 1231 N/A N/A

AMERICAN

STANDARD

WALL HUNG, LAVATORY 4" CENTERS ADA - WRIST BLADE

HANDLES, GOOSE NECK, 1.5GPM NON-AERATOR

T&S BRASS B-1141-CR-B0199-29 MCGUIRE 2125PW MCGUIRE LF2165LK 0355.012

PROVIDE OFFSET DRAIN & SUPPLY/TRAP

COVERS/WRAPS. CHICAGO 131-CFMABRCF

THERMOSTATIC MIXING VALVE.

HOT WATER RECIRCULATING PUMP SCHEDULE

TYPE

MOTOR(HP)

MOTOR(VOLTS/PHASE/HERTZ)

MODEL NUMBER

MANUFACTURER

RP-1MARK

CAPACITY(GPM)

HEAD(FEET)

INLINE

1/6

208/1/60

BELL & GOSSETT

Ecocirc XL N 36-45

STAINLESS STEEL

PUMPS TO HAVE VARIABLE FREQUENCY DRIVES AND SHALL BE

MONITORED BY THE BUILDING MANAGEMENT SYSTEM.

EXISTING STEAM WATER HEATER IN BASEMENT MECHANICAL ROOM TO REMAIN.

INSTALLED ARRESTOR SHALL BE APPROVED DEVICE BY PLUMBING

CODE, ALL SUPPY PIPING SHALL HAVE ARRESTOR THE SAME SIZE AS

CONNECTION SIZE UP TO 1" I.E. PROVIDE P.D.I SIZE C FOR 1" OR

LARGER WATER SUPPLY TO FIXTURES, P.D.I SIZE B FOR ALL 3/4"

SUPPLY AND P.D.I SIZE 1/2" SUPPY

WATER HAMMER ARRESTOR SCHEDULE:

P.D.I. = PLUMBNG AND DRAINAGE INSTITUE STANDARD WH-201

50 GPMSP-1 912 SIMPLEX PACKAGE 208V, 1 PHASE

POWER

GPMMODEL NUMBERMANUFACTURERMARK

REQUIREMENTS

NOTES

SUMP PUMP SCHEDULE

ZOELLER

NOTE:

1. PACKAGE SYSTEM WITH 18" DIAMETER X 30" DEEP BASIN.

2. FIELD COORDINATE EXACT LOCATION.

3. PROVIDE ZOELLER OR APPROVED EQUAL.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:4

P

M

P-PI-02

PLUMBING SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

STEAM TO WATER HEATER SCHEDULE

HI-AA-30-SST-80-30-SW-V-P-10-DSS

1200000MBTUH OUTPUT

30STEAM PRESSURE(PSI)

MARK HE-1

HEScoMANUFACTURER

MODEL NUMBER

SIZE(W"xL"xH") 36"x36"x83"

CONTROL CIRCUIT 120/1/60

CONTROL VALVE TYPE

GALLON PER MINUTE

STORAGE(GALLONS)

DELIVERY TEMP(°F)

NA

1,005STEAM LB/HR

MAX. 180° SEE V.A. GUDIELINES FOR LEGIONELLA DIRECTIVE

NOTES:

PROVIDE SPARE HEAT EXCHANGER TEMP. CONTROL VALVE REPAIR KIT, ELECTRONIC TEMP. MONITOR PACKAGE AND BACNET GATEWAY.

NORMAL TEMP RANGE IS 135 TO 140 DEGREES. STEAM WATER HEATER NEEDS TO PROVIDE 180 DEGREES PER V.A. LEGIONELLA GUIDELINES.

NEW STEAM WATER HEATER TO BE MONITORED BY THE BUILDING MANAGEMENT SYSTEM.

REFER TO MECHANICAL SHEET M-MI-02.

HEATER WILL BE MOUNTED ON A STEEL SUPPORT SKID AND WILL HAVE LIFTING LUGS. HEATER WILL BE INSULATED WITH 3" FIBERGLASS PROTECTED BY AN ENAMELED METAL JACKET, 20 GAUGE THICKNESS. HEATER WILL BE FACTORY ASSEMBLED

AND PIPED INCLUDING:

1. INCOMING STEAM STRAINER

2. ELECTRIC OPERATED TEMPERATURE REGULATOR

3. MAIN STEAM PUMP TRAP W/ RECEIVER

4. AUXILIARY FLOAT AND THERMOSTATIC STEAM TRAPS

5. DOUBLE WALL “U” BEND COIL, COPPER /COPPER TUBES, COPPER LINED TANK SIDE TUBE SHEET, STEEL HEAD SIDE TUBE

AND CAST IRON STEAM CHAMBER.

6. INTRA TANK CIRCULATOR

7. ASME PRESSURE- TEMPERATURE RELIEF VALVE

8. WATER PRESSURE GAUGE AND STEAM PRESSURE GAUGE

9. CEM-TROL®II SOLID STATE CONTROL MODULE THAT INCLUDES THE FOLLOWING FUNCTIONS WITH INDIVIDUAL PILOT LIGHTS:

LED TOUCH SCREEN DISPLAY WITH BUILT IN ON-OFF SWITCH, REMOTE START-STOP, ALARM HORN WITH ALARM SILENCE BUTTON, POWER ON, PRIMARY HIGH LIMIT, AND SECONDARY HIGH LIMIT. MODULE WILL HAVE BUILT IN PID CONTROL SIGNAL WITH LED DISPLAY OF SET POINT AND OPERATING TEMPERATURE READ OUT AND CONTACTS FOR BUILDING AUTOMATION SYSTEM, BUILT

IN MODBUS RTU. NOTE: PID CONTROL SIGNAL IS NOT FUNCTIONAL WHEN USING A PILOT

OPERATED VALVE WITH A SELF CONTAINED TEMPERATURE PILOT.

10. DOUBLE SAFETY SYSTEM

11. VACUUM BREAKE

ELECTRONICALLY OPERATED

Notes:

1. Refer to the following specifications for firestopping.

a. 07 84 00 Firestopping

b. 07 84 13 Penetration Firestopping

c. 22 00 00 Plumbing

d. 23 00 00 HVAC

e. 26 00 00 Electrical

f. 27 06 37 Communication

For Quality Control requirements, refer to the Quality Control portion of the specification.

2. Details shown are typical details, containing general information only. Always refer to the full UL system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:

* Fire Rating (F-Rating)

* Temperature Rating (T-Rating)

* Leakage Rating (L-Rating)

* Water Rating (W-Rating)

* Annular Space

* Percent Fill

* Movement

* Type and thickness of fire-rated construction.

3. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable.

Contact Hilti Inc. for alternative systems or Engineering Judgment (800-879-8000) Drawings shall follow the International

Firestop Council (IFC) Guidelines for Evaluating Firestop Systems Engineering Judgments.

4. References:

* 2013 Underwriter's Laboratories Fire Resistance Directory, Volumes 1 & 2

* NFPA 101 Life Safety Code

* NFPA 70 - National Electric Code

* All governing local and regional building codes

5. Firestop System installation must meet requirements of ASTM E-814 (UL 1479) tested assemblies that provide a fire rating equal to that of construction being penetrated.

6. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:

*Warning! - Do Not Disturb *Through Penetration Firestop System

* UL System # * Product(s) used

* Hourly Rating (F-Rating)

* Installation Date

*Contractor's Name

7. For outlet boxes requiring protection, use only Wall Opening

Protective Materials, category CLIV as classified by Underwriter's Laboratories, Fire Resistance Directory (Volume 1.)

NOT TO SCALE

METAL PIPE THROUGH CONCRETE FLOOR (2-HR.)

INSTALL PER UL SYSTEM C-AJ-1226

USE HILTI FS-ONE MAX FIRESTOP SEALANT

SLEEVE OPTIONAL

METAL PIPE

TYPE MAX. DIA.

STEEL PIPE (SCH. 10

OR HEAVIER)

30"

CAST IRON PIPE 30"

COPPER PIPE 6"

STEEL CONDUIT 6"

EMT 4"

65 87

PIPE TO

SYSTEM

PRESSURE

GAUGE W/

PET COCK

(TYP)

PIPE

FROM

SYSTEM

NORMALL

Y OPEN

NORMALLY OPEN

UNION

CHECK VALVE

THERMOSTATIC BALANCING VALVE

BALANCING VALVE ASSEMBLY

No Scale

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:4

P

M

P-PI-03

PLUMBING DETAILS CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

TRAPEZE HANGER

No Scale

TYPICAL ALL-THREAD

CONTINUOUS, ONE PIECE

HANGER ROD. COUPLING

OF RODS IS NOT PERMITTED

TYPICAL DOUBLE NUT WITH SINGLE

WASHER. TYPICAL

BOTH SIDES OF STRUT

TYPICAL 12 GAUGE

CHANNEL STRUT WITH

SLOTS

TYPICAL GALVANIZED

SHEET METAL SADDLE.

REFER TO SPECIFICATIONS

TYPICAL PIPING INSULATION.

DO NOT CRUSH

TYPICAL STRUT MOUNTED

PIPE STRAP

NOTE

LENGTH AS REQUIRED BY

NUMBER OF PIPES AND SIZES

REQUIRED

NOTE:

1. REFER TO SPECIFICATIONS AND FLOOR PLANS FOR

2. SPECIFIED HANGER ROD, STRUT, NUTS, WASHER,

AND PIPE STRAPS SHALL BE OF GALVANIZED

PLATED MATERIALS

INSULATED PIPE HANGER

No Scale

(SEE SPECS.)

PIPE HANGER

PIPE SADDLE W/FLARED ENDS

GALVANIZED SHEETMETAL

1'-0"

INSULATED PIPE

WATER CLOSET

No Scale

THE HANDLE OF THE FLUSH VALVE

SHALL FACE THE WIDE SIDE OF

THE STALL (NO EXCEPTIONS).

WATER SUPPLY

VENT LINE

CARRIER

SAN. LINE

CONCRETE ANCHOR

WATER CLOSET

GRAB BAR (BY OTHERS)

SOLID RING PIPE SUPPORT (2 REQUIRED)

FLUSH VALVE (MAX. 44" AFF FOR HANDLE OPERATION)

FINISHED WALL

W A

T E

R C

LO

S

E T

S E

A T

A F

F

WALL CLEANOUT

No Scale

TEST TEE

THREADED CLEANOUT PLUG

ACCESS COVER AND FRAME

FINISHED WALL SURFACE

ELECTRONIC TRAP PRIMER

No Scale

4' -0

FLOOR DRAIN

P-TRAP

4 TO 30

FLOOR

DRAINS

BALL VALVE

3/4" COLD WATER

FINISH FLOOR

1/2" TYPE "K" SOFT SEAMLESS COPPER

WITH NO JOINTS BELOW FLOOR SLAB.

SLOPE AT 1/8" PER FOOT MINIMUM TO

FLOOR DRAIN CONNECTION.

120/1/60 ELECTRICAL

CONNECTION

ELECTRONIC TRAP PRIMING MANIFOLD

SUITABLE FOR 4 TO 30 FLOOR DRAINS.

COMPLETE WITH CIRCUIT BREAKER,

TIMER, BALL VALVE, SOLENOID VALVE &

VACUUM BREAKER COMPLETLY MOUNTED

IN STEEL CABINET ENCLOSURE.

(PRECISION PLUMBING PRODUCTS

PT-4 THRU PT-30)

SOLENOID VALVE

24-HOUR TIME CLOCK

WITH TEST AND

OVERRIDE BUTTONS.

VACUUM BREAKER

GALVANIZED STEEL

CABINET

RECIRCULATING PUMP

No Scale

UNION

F

LO

W

AQUASTAT(IF REQUIRED BY

CODE) FOR CONTROL OF PUMP

INLINE RECIRCULATING PUMP

SEE PUMP SCHEDULE

GAUGE COCK

CHECK VALVE

TEMPERATURE GAUGE

GATE (OR BALL) VALVE

STEAM WATER HEATER

No Scale

SEE FLOOR PLAN FOR PIPE SIZES

EXPANSION TANK

BALANCING VALVE

VACUUM RELIEF VALVE

RECIRCULATION PUMP

FLOOR DRAIN WITH FUNNEL

CONDENSATE

STEAM

BALL VALVE

CONDENSATE TRAP W/VACUUM

BREAKER

STEAM SUPPLY LINE CONDENSATE TRAP

Y STRAINER

STEAM VALVE

HEATER

WATER

DRAINPAN

FULL SIZE OF RELIEF VALVE

DRAIN VALVE

T & P RELIEF VALVE

EQUIP STOR

G24

RECEP/CHECK IN

G25

849 SF

CORRIDOR

G37

A

B

C

D

G

I

J

K

L

M N

O P

Q R

S

T

U

4E4

E5

6 7 8 9 10 11 12 13

16 18

25 E28 E29 2829

F

E

26 27E-LL

H

FIELD VERIFY EXISTING SANITARY

PIPE ROUTING AND LOCATION.

FIELD VERIFY EXISTING SANITARY

PIPE ROUTING AND LOCATION.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:4

P

M

P-PD-01

OVERALL CRAWLSPACE LEVEL

DEMO - GRAVITY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/8" = 1'-0"

1 CRAWLSPACE LEVEL DEMO - GRAVITY

SANITARY GENERAL NOTES

1. CONTRACTOR TO INCLUDE IN PRICING, REMOVAL OF 500 LINEAR FEET

OF SANITARY PIPING AND ACCESSORIES NOT SHOWN ON THE

CRAWLSPACE GRAVITY DEMO PLAN. DRAWINGS ARE CONCEPTUAL,

FOR GENERAL INFORMATION ONLY AND NOT AN EXACT INDICATOR OF

PIPE LOCATIONS.

2. FIRST FLOOR AND SECOND FLOOR TO REMAIN IN SERVICE DURING

CONSTRUCTION. INTERUPTIONS CAN ONLY OCCUR AFTER HOURS OR

DURING WEEKEND HOURS. NOTIFY FACILITY AT LEAST 10 DAYS PRIOR

TO INTERRUPTING EXISTING SERVICE.

3. CONTRACTOR TO REMOVE ALL EXISTING SANITARY PIPING AND

ACCESSORIES NOT IN SERVICE, LOCATED IN THE CRAWLSPACE

SCOPE OF WORK AREAS.

4. FIELD VERIFY IF EXISTING SANITARY PIPING IS ROUTED ABOVE OR

BELOW THE SLAB OF THE CRAWLSPACE.

5. LOCATION FOR SANITARY PIPE TRANSITION FROM ABOVE SLAB TO

BELOW SLAB IS UNKNOWN.

FIELD VERIFY EXISTING SANITARY

MAIN PIPE ROUTING

1. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO DEMOLITION. FIELD CONDITIONS SHALL GOVERN.

FIELD VERIFY LOCATIONS OF EXISTING PIPING BEFORE DEMOLITION. PROVIDE ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT. COORDINATE WITH THE ARCHITECTURAL DRAWING FOR ITEMS NOT INDICATED. COORDINATE DEMOLITION OF EXISTING PIPING WITH NEW WORK. PIPING CONNECTING TO AREAS OUTSIDE OF RENOVATED SPACE SHALL NOT TO BE DISCONNECTED UNTIL AFTER NEW PIPING IS

INSTALLED. COORDINATE SYSTEM SHUT DOWNS WITH THE FACILITY PRIOR TO DEMOLITION.

2. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF OR TURNED OVER TO THE OWNER AT

THE OWNER'S DISCRETION.

3. ALL WATER PIPING INDICATED ON THIS DRAWING IS LOCATED IN THE CEILING SPACE OR WALL SPACES

UNLESS NOTED OTHERWISE, FIELD VERIFY BEFORE CONSTRUCTION.

4. CARE MUST BE TAKEN WHEN REMOVING PIPE AROUND LOAD BEARING WALLS. THE WALL OR FOOTING BELOW

IS NOT TO BE DESTROYED.

5. CUT AND PATCH CEILINGS, WALLS AND FLOOR SLAB AS REQUIRED TO FACILITATE PLUMBING RENOVATION.

SEE ARCHITECTURAL DRAWINGS FOR PATCHING DETAILS.

6. COORDINATE WITH MECHANICAL DUCTWORK. DUCTWORK MAY NEED TO BE REMOVED OR RE-WORKED FOR

ACCESS TO DOMESTIC WATER PIPING BY PLUMBING CONTRACTOR.

7. COORDINATE WITH ELECTRICAL. ELECTRICAL PIPING, CABLE TRAYS OR CABLES MAY HAVE TO BE RE-WORKED

FOR ACCESS TO DOMESTIC WATER PIPING BY PLUMBING CONTRACTOR.

8. PIPES MAY HAVE BEEN REPURPOSED AND FLOW/SERVICE IDENTIFICATION NEEDS TO BE VERIFIED IN THE

FIELD.

9. PIPE SIZES, FLOW DIRECTION AND SERVICE ARE GIVEN FOR GENERAL INFORMATION ONLY. THIS INFORMATION

COULD NOT BE CONFIRMED BY ENGINEER AND MUST BE FIELD VERIFIED

GENERAL PLUMBING ZONE NOTESGENERAL GRAVITY DEMOLITION NOTES

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL DRAWINGS. ALL EXISTING CONDITIONS

MUST BE VERIFIED PRIOR TO DEMOLITION. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY LOCATIONS OF EXISTING PIPING BEFORE DEMOLITION. PROVIDE ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

COORDINATE WITH THE ARCHITECTURAL DRAWING FOR ITEMS NOT INDICATED. COORDINATE DEMOLITION OF EXISTING PIPING WITH NEW WORK. PIPING CONNECTING TO AREAS OUTSIDE OF RENOVATED SPACE SHALL NOT TO BE DISCONNECTED UNTIL AFTER NEW PIPING IS INSTALLED. COORDINATE SYSTEM SHUT DOWNS WITH THE FACILITY PRIOR

TO DEMOLITION.

2. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE TURNED OVER TO THE OWNER, OR DISPOSED OF AT THE

OWNER'S DISCRETION.

3. ALL VENT PIPING INDICATED ON THIS DRAWING IS LOCATED IN THE CEILING SPACE OR WALL SPACES UNLESS NOTED

OTHERWISE, FIELD VERIFY BEFORE CONSTRUCTION.

4. ALL SANITARY PIPING INDICATED ON THIS DRAWING IS LOCATED BELOW THE FLOOR SLAB OR WALL CHASE UNLESS NOTED OTHERWISE. OFFSET ALL EXISTING SANITARY AND VENT RISERS FROM FLOOR ABOVE TO WALLS ON NEW FLOOR PLAN, FIELD VERIFY EXACT LOCATION AND PROVIDE REQUIRED OFFSET TO FACILITATE OPERATION OF PLUMBING

SYSTEMS TO THE FLOORS ABOVE AND BELOW.

5. CARE MUST BE TAKEN WHEN REMOVING PIPE AROUND LOAD BEARING WALLS. THE WALL OR FOOTING BELOW IS NOT TO

BE DESTROYED.

6. EXISTING ROOF DRAINS AND RAIN WATER LEADER PIPING TO REMAIN UNLESS OTHERWISE NOTED. FIELD VERIFY ROUTING OF EXISTING PIPING BEFORE CONSTRUCTION BEGINS. EXISTING RAIN WATER PIPING LOCATED IN WALLS TO BE REMOVED SHALL BE REROUTED OVER HEAD TO A NEW WALL LOCATION AND RECONNECTED TO THE UNDERGROUND

STORM.

7. CUT AND PATCH CEILINGS, WALLS AND FLOOR SLAB AS REQUIRED TO FACILITATE PLUMBING RENOVATION. SEE

ARCHITECTURAL DRAWINGS FOR PATCHING DETAILS.

8. EXISTING BUILDING DRAINS UNDER CONCRETE SLABS AND EXISTING BUILDING SEWERS THAT SERVES THE SYSTEM SHALL BE INTERNALLY EXAMINED TO VERIFY THAT THE PIPING IS SLOPING IN THE CORRECT DIRECTION, IS NOT BROKEN, IS NOT OBSTRUCTED AND IS SIZED FOR THE DRAINAGE LOAD OF THE NEW PLUMBING DRAINAGE SYSTEM TO BE

INSTALLED.

KEY NOTES THIS SHEET ONLY

1. SANITARY UP TO REMAIN.

2. REMOVE EXISITNG SANITARY PIPING.

UP

CORRIDOR

1 / AD 01.02

A

D

.0

A

D

.0

/ A

D

.0

A

D

.0

7 / AD 01.02

/ A

D

.0

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:5

P

M

P-PD-02

OVERALL BASEMENT FLOOR

DEMO - GRAVITY

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 BASMENT OVERALL DEMO PLAN - GRAVITY

0 4' 8' 12'

1/8" = 1'-0"

2 ENTRANCE CORR DEMO - GRAVITY

0 4' 8' 12'

KEY NOTES THIS SHEET ONLY

1. REMOVE EXISITNG LAVATORY AND ACCESSORIES. CAP SANITARY PIPING BELOW. REMOVE VENT PIPING BACK TO MAIN VENT UP.

2. REMOVE EXISITNG WATER CLOSET AND ACCESSORIES. CAP SANITARY PIPING BELOW. REMOVE VENT PIPING BACK TO MAIN VENT UP.

3. REMOVE EXISTING URINAL AND ACCESSORIES. CAP SANITARY PIPING BELOW. REMOVE VENT PIPING BACK TO MAIN VENT UP.

4. REMOVE EXISTING MOP SINK AND ACCESSORIES. CAP SANITARY PIPING BELOW. REMOVE VENT PIPING BACK TO NEAREST VTR.

5. REMOVE EXISTING FLOOR DRAIN. REMOVE VENT PIPING BACK TO NEAREST VTR. PATCH FLOOR SLAB.

6. REMOVE EXISITNG SINK AND ACCESSORIES. CAP SANITARY PIPING BELOW. REMOVE VENT PIPING BACK TO NEAREST VTR.

7. FIELD VERIFY EXISTING PIPE SYSTEM, SIZE AND ROUTING.

8. REMOVE EXISTING VENT PIPING BACK TO NEAREST VTR.

9. REMOVE EXISTING SANITARY PIPING ABOVE THE CEILING. CAP SANITARY FROM FIXTURES ABOVE IN CEILING.

10. PERMANETLY CAP EXISTING VENT ABOVE CEILING. CONTRACTOR TO FIELD VERIFY EXACT LOCATION.

11. EXISTING MECHANICAL PIPING TO REMAIN.

12. EXISTING 4" SANITARY DOWN. CONTRACTOR TO FIELD VERIFY EXACT LOCATION.

SANITARY/VENT GENERAL NOTES

1. CONTRACTOR TO INCLUDE IN PRICING, REMOVAL OF 500 LINEAR FEET

OF SANITARY AND VENT PIPING, NOT SHOWN ON THE BASEMENT

DEMO GRAVITY PLAN. DRAWINGS ARE CONCEPTUAL, FOR GENERAL

INFORMATION ONLY AND NOT AN EXACT INDICATOR OF PIPE

LOCATIONS.

2 CONTRACTOR TO REMOVE ALL EXISTING SANITARY AND VENT PIPING

NOT IN SERVICE, LOCATED IN THE BASEMENT SCOPE OF WORK

AREAS.

3. FIRST FLOOR AND SECOND FLOOR TO REMAIN IN SERVICE DURING

CONSTRUCTION. INTERUPTIONS CAN ONLY OCCUR AFTER HOURS OR

DURING WEEKEND HOURS. NOTIFY FACILITY AT LEAST 10 DAYS PRIOR

TO INTERRUPTING EXISTING SERVICE.

4. PATCH FLOOR SLAB AND LEVEL FLOORS FOR NEW FINISHES.

5 5

8 8

GENERAL GRAVITY DEMOLITION NOTES

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL DRAWINGS. ALL EXISTING CONDITIONS

MUST BE VERIFIED PRIOR TO DEMOLITION. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY LOCATIONS OF EXISTING PIPING BEFORE DEMOLITION. PROVIDE ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

COORDINATE WITH THE ARCHITECTURAL DRAWING FOR ITEMS NOT INDICATED. COORDINATE DEMOLITION OF EXISTING PIPING WITH NEW WORK. PIPING CONNECTING TO AREAS OUTSIDE OF RENOVATED SPACE SHALL NOT TO BE DISCONNECTED UNTIL AFTER NEW PIPING IS INSTALLED. COORDINATE SYSTEM SHUT DOWNS WITH THE FACILITY PRIOR

TO DEMOLITION.

2. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE TURNED OVER TO THE OWNER, OR DISPOSED OF AT THE

OWNER'S DISCRETION.

3. ALL VENT PIPING INDICATED ON THIS DRAWING IS LOCATED IN THE CEILING SPACE OR WALL SPACES UNLESS NOTED

OTHERWISE, FIELD VERIFY BEFORE CONSTRUCTION.

4. ALL SANITARY PIPING INDICATED ON THIS DRAWING IS LOCATED BELOW THE FLOOR SLAB OR WALL CHASE UNLESS NOTED OTHERWISE. OFFSET ALL EXISTING SANITARY AND VENT RISERS FROM FLOOR ABOVE TO WALLS ON NEW FLOOR PLAN, FIELD VERIFY EXACT LOCATION AND PROVIDE REQUIRED OFFSET TO FACILITATE OPERATION OF PLUMBING

SYSTEMS TO THE FLOORS ABOVE AND BELOW.

5. CARE MUST BE TAKEN WHEN REMOVING PIPE AROUND LOAD BEARING WALLS. THE WALL OR FOOTING BELOW IS NOT TO

BE DESTROYED.

6. EXISTING ROOF DRAINS AND RAIN WATER LEADER PIPING TO REMAIN UNLESS OTHERWISE NOTED. FIELD VERIFY ROUTING OF EXISTING PIPING BEFORE CONSTRUCTION BEGINS. EXISTING RAIN WATER PIPING LOCATED IN WALLS TO BE REMOVED SHALL BE REROUTED OVER HEAD TO A NEW WALL LOCATION AND RECONNECTED TO THE UNDERGROUND

STORM.

7. CUT AND PATCH CEILINGS, WALLS AND FLOOR SLAB AS REQUIRED TO FACILITATE PLUMBING RENOVATION. SEE

ARCHITECTURAL DRAWINGS FOR PATCHING DETAILS.

8. EXISTING BUILDING DRAINS UNDER CONCRETE SLABS AND EXISTING BUILDING SEWERS THAT SERVES THE SYSTEM SHALL BE INTERNALLY EXAMINED TO VERIFY THAT THE PIPING IS SLOPING IN THE CORRECT DIRECTION, IS NOT BROKEN, IS NOT OBSTRUCTED AND IS SIZED FOR THE DRAINAGE LOAD OF THE NEW PLUMBING DRAINAGE SYSTEM TO BE

INSTALLED.

RECEP/CHECK IN

G25

849 SF

CORRIDOR

G37

A

B

C

D

G

I

J

K

L

M N

O P

Q R

S

T

U

4E4

E5

6 7 8 9 10 11 12 13

16 18

25 E28 E29 2829

F

E

26 27E-LL

H

EXIST 1 1/4"HW

EXIST 2 1/2"CW

EXIST 2"HWEXIST 3"CW

EXIST 1 1/2"HWR

EXIST 3"CWEXIST 2"HW

EXIST 1"HW EXIST 1"HW

E X

IS

T

"H

W

E X

IS

T

"H

W

E X

IS

T

"C

W E

X

IS

T

"C W

E X

IS

T

"H

W E

X

IS

T

"H W

E X

IS

T

/2 "C

W

EXIST 3/4"CW

EXIST 1 1/2"CW

E X

IS

T

/2 "C

W

E X

IS

T

/4

"H W

E X

IS

T

"C

W E

X

IS

T

"H W

E X

IS

T

"C

W

E X

IS

T

/4

"H W

E X

IS

T

/4

"H W

E X

IS

T

/4

"C W

EXIST 1/2"CW

EXIST 1/2"HW

EXIST 1 1/2"CW

EXIST 3/4"CW

EXIST 1/2"HW

EXIST 3/4"HW

EXIST 1/2"HW

EXIST 1/2"CW

EXISTING MECHANICAL ROOM

6 7

6 6 6

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:0

P

M

P-PD-03

OVERALL CRAWLSPACE LEVEL

DEMO - PRESSURE

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

0 4' 8' 12'

1/8" = 1'-0"

1 CRAWLSPACE LEVEL DEMO - PRESSURE

PRESSURE GENERAL NOTES

1. CONTRACTOR TO INCLUDE IN PRICING, REMOVAL OF 500 LINEAR OFDOMESTIC

WATER PIPING AND MATERIALS NOT SHOWN ON THE CRAWLSPACE DEMO

PRESSURE PLAN. DRAWINGS ARE CONCEPTUAL, FOR GENERAL INFORMATION

ONLY AND NOT AN EXACT INDICATOR OF PIPE LOCATIONS.

2. FIRST FLOOR AND SECOND FLOOR TO REMAIN IN SERVICE DURING

CONSTRUCTION. INTERUPTIONS CAN ONLY OCCUR AFTER HOURS OR

DURING WEEKEND HOURS. NOTIFY OWNER AT LEAST 10 DAYS PRIOR TO

INTERRUPTING EXISTING SERVICE.

3. PATCH FLOOR SLAB PENETRATIONS AND LEVEL FLOORS FOR NEW FINISHES.

KEY NOTES THIS SHEET ONLY

1. REMOVE EXISTING HOT WATER, COLD WATER AND HOT WATER RETURN PIPING, NOT IN SERVICE IN CRAWLSPACE SCOPE OF WORK AREA.

2. EXISTING CW, HW AND HWR SUPPLY LINES FOR FIRST AND SECOND FLOOR TO REMAIN.

3. REMOVE EXISTING HOT WATER, COLD WATER PIPING AND MATERIALS.

4. STEAM WATER HEATER TO REMAIN. SUPPLIES HOT WATER FOR BASEMENT, FIRST AND SECOND LEVELS.

5. EXISTING HOT WATER RETURN PUMP FOR FIRST AND SECOND LEVEL TO REMAIN.

6. VALVE AND CAP.

7. FIELD VERIFY EXISTING WALL HYDRANT LOCATIONS AND PIPE ROUTING.

8. FIELD VERIFY 2-1/2" CW SUPPLY LINE IS FOR GROUND FLOOR ONLY.

CRAWLSPACE MECHANICAL ROOM EXISTING STEAM WATER HEATER

MECHANICAL ROOM MEZZANINE LEVEL ABOVE EXISTING STEAM WATER HEATER

MECHANICAL ROOM MEZZANINE LEVEL ACCESS

1 1

2 2

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL DRAWINGS. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO DEMOLITION. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY LOCATIONS OF EXISTING PIPING BEFORE DEMOLITION. PROVIDE ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

COORDINATE WITH THE ARCHITECTURAL DRAWING FOR ITEMS NOT INDICATED. COORDINATE DEMOLITION OF EXISTING PIPING WITH NEW WORK. PIPING CONNECTING TO AREAS OUTSIDE OF RENOVATED SPACE SHALL NOT TO BE DISCONNECTED UNTIL AFTER NEW PIPING IS INSTALLED. COORDINATE SYSTEM SHUT DOWNS WITH THE FACILITY PRIOR

TO DEMOLITION.

2. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF OR TURNED OVER TO THE OWNER AT THE OWNER'S

DISCRETION.

3. ALL WATER PIPING INDICATED ON THIS DRAWING IS LOCATED IN THE CEILING SPACE OR WALL SPACES UNLESS NOTED

OTHERWISE, FIELD VERIFY BEFORE CONSTRUCTION.

4. CARE MUST BE TAKEN WHEN REMOVING PIPE AROUND LOAD BEARING WALLS. THE WALL OR FOOTING BELOW IS NOT TO

BE DESTROYED.

5. CUT AND PATCH CEILINGS, WALLS AND FLOOR SLAB AS REQUIRED TO FACILITATE PLUMBING RENOVATION. SEE

ARCHITECTURAL DRAWINGS FOR PATCHING DETAILS.

GENERAL PRESSURE DEMOLITION NOTES

CORRIDOR

1 / AD 01.02

A

D

.0

A

D

.0

/ A

D

.0

A

D

.0

7 / AD 01.02

/ A

D

.0

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:0

P

M

P-PD-04

OVERALL BASEMENT FLOOR

DEMO - PRESSURE

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 BASMENT OVERALL DEMO PLAN - PRESSURE

0 4' 8' 12'

1/8" = 1'-0"

2 ENTRANCE CORR DEMO - PRESSURE

0 4' 8' 12'

KEY NOTES THIS SHEET ONLY

1. REMOVE EXISITNG LAVATORY AND ACCESSORIES. REMOVE EXISTING HOT AND COLD WATER PIPING.

2. REMOVE EXISITNG WATER CLOSET AND ACCESSORIES. REMOVE EXISTING COLD WATER PIPING.

3. REMOVE EXISTING URINAL AND ACCESSORIES. REMOVE EXISTING COLD WATER PIPING.

4. REMOVE EXISTING MOP SINK AND ACCESSORIES. REMOVE EXISTING HOT AND COLD WATER PIPING.

5. REMOVE EXISTING SINK AND ACCESSORIES. REMOVE EXISTING HOT AND COLD WATER PIPING.

6. REMIOVE EXISTING SHOWER CONTROL VALVE STATION AND PIPING.

7. EXISTING WALL HYDRANT TO REMAIN.

8. EXISTING MECHANICAL PIPING TO REMAIN.

9. REMOVE EXISTING CW COPPER PIPING AND ACCESSORIES ROUTED ON WALL. EXISTING DRINKING FOUNTAIN WAS REMOVED

PREVIOUSLY. FIELD VERIFY EXACT ROUTING.

10. EXISTING CW, HW AND HWR PIPING DOWN TO CRAWLSPACE.

11. EXISTING 3" CW, 2" HW AND 1-1/2" HWR UP TO 1ST AND 2ND FLOORS.

PRESSURE GENERAL NOTES

1. CONTRACTOR TO INCLUDE IN PRICING, REMOVAL OF 500 LINEAR OF

DOMESTIC WATER PIPING AND MATERIALS NOT SHOWN ON THE

BASEMENT DEMO PRESSURE PLAN. DRAWINGS ARE CONCEPTUAL,

FOR GENERAL INFORMATION ONLY AND NOT AN EXACT INDICATOR OF

PIPE LOCATIONS.

2. FIRST FLOOR AND SECOND FLOOR TO REMAIN IN SERVICE DURING

CONSTRUCTION. INTERUPTIONS CAN ONLY OCCUR AFTER HOURS OR

DURING WEEKEND HOURS. NOTIFY OWNER AT LEAST 10 DAYS PRIOR TO

INTERRUPTING EXISTING SERVICE.

3. PATCH FLOOR SLAB AND LEVEL FLOORS FOR NEW FINISHES.

4. EXISTING DOMESTIC WATER PIPING SUPPLY LINES ARE LOCATED IN

CRAWLSPACE BELOW UNLESS OTHERWISE NOTED.

5. FIELD VERIFY EXISTING PIPE ROUTING AND SIZES.

EXISTING MECHANICAL PIPING TO REMAIN.

1. EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL DRAWINGS. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO DEMOLITION. FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY LOCATIONS OF EXISTING PIPING BEFORE DEMOLITION. PROVIDE ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.

COORDINATE WITH THE ARCHITECTURAL DRAWING FOR ITEMS NOT INDICATED. COORDINATE DEMOLITION OF EXISTING PIPING WITH NEW WORK. PIPING CONNECTING TO AREAS OUTSIDE OF RENOVATED SPACE SHALL NOT TO BE DISCONNECTED UNTIL AFTER NEW PIPING IS INSTALLED. COORDINATE SYSTEM SHUT DOWNS WITH THE FACILITY PRIOR

TO DEMOLITION.

2. ALL ITEMS REMOVED UNDER THIS PROJECT SHALL BE DISPOSED OF OR TURNED OVER TO THE OWNER AT THE OWNER'S

DISCRETION.

3. ALL WATER PIPING INDICATED ON THIS DRAWING IS LOCATED IN THE CEILING SPACE OR WALL SPACES UNLESS NOTED

OTHERWISE, FIELD VERIFY BEFORE CONSTRUCTION.

4. CARE MUST BE TAKEN WHEN REMOVING PIPE AROUND LOAD BEARING WALLS. THE WALL OR FOOTING BELOW IS NOT TO

BE DESTROYED.

5. CUT AND PATCH CEILINGS, WALLS AND FLOOR SLAB AS REQUIRED TO FACILITATE PLUMBING RENOVATION. SEE

ARCHITECTURAL DRAWINGS FOR PATCHING DETAILS.

GENERAL PRESSURE DEMOLITION NOTES

RECEP/CHECK IN

G25

849 SF

CORRIDOR

G37

A

B

C

D

G

I

J

K

L

M N

O P

Q R

S

T

U

4E4

E5

6 7 8 9 10 11 12 13

16 18

25 E28 E29 2829

F

E

26 27E-LL

H

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:1

P

M

P-PD-05

OVERALL CRAWLSPACE LEVEL

DEMO - MEDICAL GAS

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 CRAWLSPACE LEVEL DEMO - MEDICAL GAS

0 4' 8' 12'

MEDICAL GAS GENERAL NOTES

1. CONTRACTOR TO INCLUDE IN PRICING, REMOVAL OF 500 LINEAR OF

MEDICAL GAS PIPING NOT SHOWN ON THE CRAWLSPACE DEMO MEDICAL

GAS PLAN. DRAWINGS ARE CONCEPTUAL, FOR GENERAL INFORMATION

ONLY AND NOT AN EXACT INDICATOR OF PIPE LOCATIONS.

2. CONTRACTOR TO REMOVE ALL MEDICAL GAS SYSTEM PIPING AND

ACCESSORIES NOT IN SERVICE, LOCATED IN THE CRAWLSPACE SCOPE

OF WORK AREAS.

3. VERIFY IF EXISTING OXYGEN SUPPLY ROUTES TO OTHER BUILDINGS ON

THE SITE. MEDICAL OXYGEN TO OTHER BUILDINGS MUST REMAIN IN

SERVICE DURING CONSTRUCTION.

4. VERIFY MEDICAL SYSTEM IS NOT IN OPERATION ON 1ST AND 2ND FLOORS,

BEFORE REMOVING ANY EXISTING MEDICAL GAS PIPING IN SCOPE OF

WORK AREA.

GENERAL PLUMBING ZONE NOTES

1. THE INTENT OF IDENTIFYING THE PLUMBING ZONES IS TO PROVIDE THE CONTRACTOR LIMITS TO WHICH

AREA'S ARE AFFECTED BY PLUMBING DEMO AND NEW WORK.

2. THE IDENTIFYING OF PLUMBING ZONES IS NOT TO BE TAKEN AS AN ALL INCLUSIVE THE IDENTIFYING OF PLUMBING ZONES IS NOT TO BE TAKEN AS AN ALL INCLUSIVE WORK AREA. PLEASE REFER TO ALL DISCIPLINES

AND CONTRACT DOCUMENTS FOR ALL WORK ASSOCIATED AND AFFECTED BY THESE AREAS.

3. WORK CAN OCCUR CONCURRENTLY BETWEEN DIFFERENT IDENTIFIED ZONES AND WORK CAN OCCUR CONCURRENTLY BETWEEN DIFFERENT IDENTIFIED ZONES AND WORK BETWEEN ZONES DOES NOT NEED TO

OCCUR IN SEQUENCE.

4. WORK ACROSS ALL DISCIPLINES IS SUBJECT TO THE CONTRACTORS MEANS AND WORK ACROSS ALL DISCIPLINES IS SUBJECT TO THE CONTRACTORS MEANS AND METHODS, SCHEDULING AND TO EXISTING

CONDITIONS AND TIME RESTRAINTS.

5. THE CONTRACTOR TO HAVE ALL MATERIALS AND EQUIPMENT ON SITE PRIOR TO THE CONTRACTOR TO

STARTING ANY WORK THAT IS DESIGNATED TO BE COMPLETED OFF-HOURS.

6. WORK ASSOCIATED WITH THESE ZONES CAN BE DONE AT HOURS APPROVED BY FACILITY.

7. REFER TO SLEEP LAB RENOVATION PLANS.

GENERAL SEQUENCE OF WORK NOTES

1. CONTRACTOR SHALL BE RESPONSIBLE FOR SEQUENCING AND COORDINATION OF CONSTRUCTION PHASING WITH THE VA'S SCHEDULE, INFECTION CONTROL, AND INTERIM LIFE SAFETY REQUIREMENTS. REFER TO SPECIFICATIONS FOR PROJECT GENERAL CONDITIONS, INFECTION CONTROL, SPECIAL NOTES, PROJECT

SCHEDULE, ETC. FOR ALL PROJECT REQUIREMENTS.

2. CONTRACTOR SHALL PROVIDE ALL SUB-PHASING ACTIVITIES AS REQUIRED FOR WORK OCCURRING BETWEEN

VARIOUS PHASES.

3. CONTRACTOR SHALL REFER TO ALL DEMOLITION AND CONSTRUCTION DRAWINGS FOR CONTRACTOR SHALL REFER TO ALL DEMOLITION AND CONSTRUCTION DRAWINGS FOR A COMPLETE UNDERSTANDING OF THE

SPECIFIED SCOPE OF WORK.

4. CONTRACTOR SHALL MAINTAIN EGRESS PASSAGE WAYS AT INTERIOR OF BUILDING.CONTRACTOR SHALL MAINTAIN EGRESS PASSAGE WAYS AT INTERIOR OF BUILDING. DURING COMPLETE PROJECT DURATION. ALSO

MAINTAIN ALL EGRESS/EXIT DOORS OF THE FACILITY.

5. CONTRACTOR SHALL REFER TO DRAWING GI 01.03 AND GI- 01.40 FOR INFECTION CONTROL NOTES AND

SUGGESTED LOCATION OF CONSTRUCTION BARRIERS AND ENTRANCES.

6. CONTRACTOR SHALL NOTE THAT BUILDING SHALL BE OCCUPIED DURING CONSTRUCTION.

7. HOURS OF OPERATION FOR NOISE AND VIBRATION OPERATIONS ARE DURING OFF HOURS OF OPERATION FOR NOISE AND VIBRATION OPERATIONS ARE DURING OFF NORMAL HOSPITAL OPERATION HOURS (6:00PM TO 6:00AM). SERVICE INTERRUPTIONS DURING OFF NORMAL WORK HOURS AND SCHEDULED MINIMUM (2) WEEK

ADVANCED NOTICE.

8. PLUMBING ZONES ARE TO BE DETERMINED BY COR. VERIFY HOW MANY ROOMS OR SPACES DURING

CONSTRUCTION. NO SEQUENCE IS INFERRED. SUBMIT PHASING TO FACILITY FOR APPROVAL.

E X

IS

T

/2

"O

E X

IS

T

/2

"M A

E X

IS

T

"M

V

EXIST 1"O2

EXIST 1 1/2"MV

EXIST 1 1/4"MA EXIST 1 1/4"MA

EXIST 1 1/2"MV

EXIST 1"O2

E X

IS

T

/4

"M V

E X

IS

T

/2

"M A

E X

IS

T

/2

"O

E X

IS

T

/4

"O

E X

IS

T

/4

"M A

E X

IS

T

"M

V

EXIST 1/2"MV

EXIST 1/2"MA

EXIST 1/2"O2

EXIST 3/4"MV

EXIST 1/2"O2

EXIST 1/2"MA

EXIST 1/2"MV

EXIST 1/2"MA

EXIST 1/2"MV

EXIST 3/4"MV

EXIST 1/2"MA

EXIST 1/2"O2

1/2"MA

1/2"MV

1/2"O2

EXIST 1/2"O2

EXIST 1/2"MA

EXIST 1/2"MV

1 1

1 1

3EXIST 1 1/2"MV

EXIST 1"O2

EXIST 1 1/4"MA

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

923116

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

214 Centerview Drive Suite 300 Brentwood, TN 37027

615.370.8500woldae.com

102 THIRD AVENUE NE

HICKORY, NC 28601

PHONE: 828.315.9962

FAX: 828.315.9966

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

MURFREESBORO, TN

A

B

C

D

E

F

A u to d e s k D o c s /2

V A

M C

S le e p

D is o rd e r

C lin ic /9

-T

V H

S A

C Y

V A

M C

S le e p L a b

P

F P

R

.r v t

/1

/2

:5

:1

P

M

P-PD-06

OVERALL BASEMENT FLOOR

DEMO - MEDICAL GAS

CONSTRUCT SLEEP DISORDER CLINIC

AND SPECIALTY CLINIC

SHK07/10/2024

626-310

KLS

100% CONSTRUCTION

DOCUMENTS

1/8" = 1'-0"

1 BASMENT OVERALL DEMO PLAN - MEDICAL GAS

0 4' 8' 12'

KEY NOTES THIS SHEET ONLY

1. REMOVE ALL EXISITNG MEDICAL GAS PIPING AND ACCESSORIES IN SCOPE OF WORK AREAS.

2. CAP EXISTING MEDICAL AIR AND MEDICAL VACUUM LINES FROM ABOVE.

3. VALVE AND CAP EXISTING MEDICAL AIR, MEDICAL VACUUM AND OXYGEN LINES ABOVE…