Attachment 12 - DWG - 08 - E.pdf
PDF 11 MB Posted
- Attached to
- Y1DA--626-310 Construct Sleep Disorder Clinic and Specialty Clinics Minor Construction - Murfreesboro
- Solicitation number
- 36C77625B0035
About this file
This document is an electrical engineering drawing set for the construction of a Sleep Disorder Clinic and Specialty Clinics at a VA Medical Center in Murfreesboro, Tennessee. The comprehensive set includes multiple detailed electrical system plans spanning 32 pages, covering areas such as electrical symbols legend, one-line diagrams, panel schedules, electrical site plans, power distribution plans, fire alarm systems, nurse call systems, and architectural electrical details.
Key technical components include electrical distribution with multiple switchboards (N6GM, L6GM, Q6GM), panel schedules for various electrical systems, lighting fixture specifications using LED technologies, mechanical equipment connection details, and comprehensive floor plans for basement and crawlspace levels showing electrical infrastructure. The drawings detail power distribution for medical equipment, lighting, emergency systems, and specialized clinic spaces, with precise electrical routing, circuit mapping, and system integration specifications. The project appears to be a fully sprinklered minor construction project for the VA, with detailed electrical engineering designs covering power, lighting, fire alarm, and communication systems.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
ELECTRICAL SYMBOL LEGEND
IN INCHES
IPCEA INSULATED POWER CABLE ENGINEERS ASSOCIATION
IT INSTANTANEOUS TRIP
JB OR J-BOX JUNCTION BOX
KCMIL ONE THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOURS
LBS POUNDS
LED LIGHT EMITTING DIODE
LP LIGHTNING PROTECTION
LT LIGHT
LTG LIGHTING
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND
LSIA LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM
LSI LONG TIME, SHORT TIME, INSTANTANEOUS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN SERVICE DISTRIBUTION PANEL
MIC MICROPHONE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SERVICE SWITCHBOARD
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MUX MULTIPLEX (TRANSPONDER) PANEL
MVA MEGA VOLT AMPS
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NF NON-FUSED
NL NON-LINEAR
NO NORMALLY OPEN OR NUMBER
OL OVERLOAD
OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
P POLE
PB PULLBOX
PF POWER FACTOR
PIV POST INDICATOR VALVE
PNL PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYLCHLORIDE
PWR POWER
REC, RECEPT RECEPTACLE
REF REFRIGERATOR
RGS, GRC RIGID GALVANIZED STEEL CONDUIT
RLA RUNNING LOAD AMPERES
RMS ROOT-MEAN-SQUARE
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SCA SHORT CIRCUIT AMPERES
SD SMOKE DETECTOR
SEC SECONDARY
S/N SOLID NEUTRAL
SPD SURGE PROTECTIVE DEVICE
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SS STAINLESS STEEL
SST SOLID STATE TRIP
STD SHORT TIME TRIP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TVEC TELEVISION EQUIPMENT CABINET
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UL UNDERWRITERS LABORATORIES
UTIL UTILITY
V VOLT
VA VOLTAMPERE
VAR VOLT AMPERE REACTIVE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
XFR TRANSFER
ABBREVIATIONS (CONT.)
A/C AIR CONDITIONING
AC ALTERNATING CURRENT
ABV CLG ABOVE CEILING
ADA AMERICANS WITH DISABILITIES ACT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AMP AMPERE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASA AMERICAN STANDARDS ASSOCIATION
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GUAGE
BC BARE COPPER
BIL BASIC IMPULSE LEVEL
BAS BUILDING AUTOMATION SYSTEM
BMS BUILDING MANAGEMENT SYSTEM
BRKR OR BKR BREAKER
C CONDUIT OR RACEWAY
CAB CABINET
CKT CIRCUIT
CB CIRCUIT BREAKER
CBM CERTIFIED BALLAST MANUFACTURERS
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CLEC CLOCK EQUIPMENT CABINET
CLG CEILING
CO CONDUIT OR RACEWAY ONLY
COAX COAXIAL CABLE
COND CONDUCTOR
CONN CONNECTION
CPU CENTRAL PROCESSING UNIT
CRT CATHODE RAY TERMINAL (VIDEO DISPLAY TERMINAL)
CT CURRENT TRANSFORMER
CU COPPER
CW COLD WATER
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DF DEMAND FACTOR
DISC DISCONNECT
DISC SW DISCONNECT SWITCH
DO DRAW OUT
DN DOWN
DPST DOUBLE POLE SINGLE THROW
EDH ELECTRIC DUCT HEATER
EMT ELECTRIC METALLIC TUBING
EO ELECTRICALLY OPERATED
EOL END OF LINE
EOR ENGINEER OF RECORD
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FATC FIRE ALARM TERMINAL CABINET
FBC FLORIDA BUILDING CODE
FCU FAN COIL UNIT
FLA FULL LOAD AMPERES
FM FACTORY MUTUAL
FPU FAN POWERED UNIT
FT FEET
GF GROUND FAULT
GFA GROUND FAULT ALARM
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
GND, G GROUND
HP HORSEPOWER
HOA HAND-OFF-AUTOMATIC
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
ICU INTENSIVE CARE UNIT
IECC INTERNATIONAL ENERGY CONSERVATION CODE
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
IES ILLUMINATING ENGINEERING SOCIETY
IMC INTERMEDIATE METAL CONDUIT
ABBREVIATIONS
DN
UP
SYMBOL DESCRIPTION
DDC
VFD
AUTOMATIC TRANSFER SWITCH
TRANSFORMERT
DIRECT DIGITAL CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR CONNECTION
NEW (HEAVY, SOLID LINE)
EXISTING TO REMAIN (LIGHT, SOLID LINE)
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
FLEXIBLE CONDUIT
CONDUIT CONTINUED
CONDUIT STUBBED OUT OR UP
CONDUIT TURNING DOWN
CONDUIT TURNING UP
GROUND OR GROUND ROD AS NOTED
CONDUIT EXPOSED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR
CONDUIT CONCEALED ABOVE CEILING OR IN WAL
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED
MULTI-SERVICE RACEWAY WITH 5-20R RECEPTACLES, 18" O.C. UNLESS
OTHERWISE NOTED
SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED
NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE
CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);
TYPICAL FOR ANY DEVICE IN LEGEND
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVER MOUNTED ABOVE COUNTER
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
GFCI RECEPTACLE; "WP" INDICATES CAST METAL "IN-USE" WEATHERPROOF COVER,
WEATHER-RESISTANT LISTED
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES
(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW
VOLTAGE REQUIREMENTS)
FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE
M
F
LV
OS
a
30AR
20AF
PEDESTAL MOUNTED DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
DIMMER SWITCH, LINE VOLTAGE
MOTOR RATED SWITCH
FAN SWITCH
LOW VOLTAGE SWITCH
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
FOUR-WAY SWITCH
THREE-WAY SWITCH
NF
30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED
SINGLE POLE SWITCH (SUBSCRIPT INDICATES ITEM CONTROLLED)
NF = NON-FUSED
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE
NOTED
30/3
3R
MCP
AMPERE
RATING
# OF POLES
NEMA STARTER SIZE
SINGLE RECEPTACLE
FUSED DISCONNECT
D
BASIC MATERIALS
S
S
S
S
S
S
S
S
MOTORIZED DAMPER CONNECTIONMD
K SINGLE POLE KEY SWITCHS
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
OSab WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH, DUAL RELAYS
DL DAYLIGHT SENSOR CEILING MOUNTED
DL DAYLIGHT SENSOR WALL MOUNTED
RECEPTACLE CONTROLLED PER ASHRAE 90.1 (2010); PROVIDE POWER PACK FOR
RECEPTACLE CIRCUIT, TO BE CONTROLLED THROUGH LOCAL ROOM OCCUPANCY
SENSOR(S); PROVIDE DEVICE WITH BLUE DOT OR UNIVERSAL POWER SYMBOL
RECEPTACLE MOUNTED ADJACENT TO TV OUTLET, COORDINATE HEIGHT W/ ARCHITECT
FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE
DUPLEX RECEPTACLE WITH (2) USB PORTS
DOUBLE DUPLEX RECEPTACLE WITH DEDICATED CIRCUIT FOR AV RACK OR CART
D,OS WALL MOUNTED DUAL TECHNOLOGY DIMMING/OCCUPANCY SENSOR SWITCHS
LVO
LOW VOLTAGE OVERRIDE SWITCHS
VS WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR SWITCHS
OS
C
TV
U
AV
HOSPITAL GRADE H
TAMPER RESISTANTTR
ISOLATED GROUND (ORANGE DEVICE) IG
WEATHERPROOFWP
OS
DEVICE ABBREVIATION TAGS:
DUPLEX RECEPTACLE, CEILING MOUNTED
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE, CEILING MOUNTED
J
FOUR-GANG FLOOR BOX4G
SIX-GANG FLOOR BOX6G
EIGHT-GANG FLOOR BOX8G
MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLES (QUAD) , VOICE/DATA/AV
DEVICES (REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR
LOW VOLTAGE REQUIREMENTS)
GFCI RECEPTACLE MOUNTED ABOVE COUNTER
DUPLEX RECEPTACLE; EACH RECEPTACLE ON SEPARATE CIRCUIT (PROVIDE
BREAKER WITH 2-POLE COMMON TRIP HANDLE)
SPLIT-WIRED CONTROLLED DUPLEX RECEPTACLE
TWO GFCI DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
MULTI-SERVICE POWER & DATA FLOOR BOX WITH FURNITURE FEED CONNECTION
(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW
VOLTAGE REQUIREMENTS)
J JUNCTION BOX WALL MOUNTED
J JUNCTION BOX MOUNTED IN OR ABOVE CEILING OR IN STRUCTURE
J WALL MOUNTED FURNITURE FEED POWER CONNECTION
P
MULTI-SERVICE POKE-THRU WITH TWO INTEGRAL DUPLEX RECEPTACLES AND
VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR
DRAWINGS FOR LOW VOLTAGE REQUIREMENTS), OR FURNITURE FEED CONNECTION;
REFER TO POKE-THRU DETAILS
PP
POWER POLE WITH POWER & DATA FURNITURE FEED POWER CONNECTIONS
POKE-THRU WITH 6" CORE DRILL6C
POKE-THRU WITH 8" CORE DRILL8C
PC PHOTOCELL, MOUNTED ON ROOF FACING NORTH
C CLOCK RECEPTACLE, WALL MOUNTED
GROUND BUS BAR, COPPERGND
CONDUIT SEAL-OFF FITTING
SPD SURGE PROTECTIVE DEVICE
ST
SHUNT-TRIP PUSHBUTTON; SEMI-FLUSH WALL MOUNTED UNLESS OTHERWISE NOTED;
NEMA 3R FOR EXTERIOR LOCATIONS
OVERHEAD DOOR PUSHBUTTON CONTROL STATION
PUSHBUTTON STATION
BAS BUILDING AUTOMATION SYSTEM CONTROL PANEL
LCP LIGHTING CONTROL PANEL
MANHOLEMH
SYMBOL DESCRIPTION
PULLBOXPB
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
3R
3R
AF = AMPERE RATING OF FUSE
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED
CONDUIT HOMERUN TO ELECTRICAL PANEL
EXISTING TO REMAIN ETR
RELOCATEDRL
PP PUSH BUTTON
HANDHOLEHH
ATS
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL
EPO EMERGENCY POWER OFF SHUNT-TRIP PUSHBUTTON, RED MUSHROOM HEAD, CLEAR
LEXAN PROTECTIVE COVER
T DIGITAL TIMER SWITCH W/ 5 MIN. WARNING FLASHS
LVD
LOW VOLTAGE OVERRIDE SWITCH WITH DIMMINGS
VS VACANCY SENSOR CEILING MOUNTED
VS VACANCY SENSOR WALL MOUNTED
A
EMERGENCY TWIN-HEAD LIGHT WITH INTEGRAL BATTERY PACK, WALL MOUNTED
TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF TRACK HEADS)
EXTERIOR POLE-MOUNTED AREA LIGHT FIXTURE, ARMS AS INDICATED ON DRAWINGS
EXIT LIGHT, WALL MOUNTED
EXIT LIGHT, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED;
SHADED QUADRANT INDICATES FACE(S) OF FIXTURE
CEILING WALLWASHER, ACCENT LIGHT, LANDSCAPING TREE ACCENT LIGHT, FACADE LIGHT
RECESSED, PENDANT OR SURFACE CEILING
DIAGONAL HALF SHADING INDICATE FIXTURE CONNECTED TO CRITICAL CIRCUIT OR
PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E" AFTER FIXTURE TYPE TAG
INDICATES INTEGRAL BATTERY PACK UNLESS OTHERWISE NOTED ON LIGHT FIXTURE
SCHEDULE (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)
FULL SHADING INDICATE FIXTURE CONNECTED TO LIFE SAFETY CIRCUIT.
FIXTURE, RECESSED, PENDANT OR SURFACE CEILING
STRIP FIXTURE
FIXTURE, WALL MOUNTED
FIXTURE TYPE
LOWER CASE LETTER INDICATES CONTROLLING SWITCH
a
CIRCUIT NUMBER
LIGHTING
WALL MOUNTED
LINEAR RECESSED, PENDANT OR SURFACE CEILING
ZX-X
LIGHTING CONTROL ZONE NUMBER
EXTERIOR PEDESTRIAN SIDEWALK BOLLARD OR POST-TOP LIGHT FIXTURE
FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
FIRE ALARM TERMINAL CABINET
FIRE ALARM CONTROL PANEL
HEAT DETECTOR 135°F FIXED TEMPERATURE, UNLESS OTHERWISE NOTED,
CEILING MOUNTED
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
SPRINKLER WATERFLOW SWITCH CONNECTION
SPRINKLER TAMPER SWITCH CONNECTION
FIREMAN'S PHONE JACK
STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE NOTED
CD = CANDELA RATING
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE, CEILING MOUNTED, 75CD
UNLESS OTHERWISE NOTED
HORN ONLY, WALL MOUNTED
DUCT SMOKE DETECTOR REMOTE TEST SWITCH WITH INDICATING LAMP, WALL
MOUNTED AT 48" AFF, UNLESS OTHERWISE NOTED
SUPERVISED ADDRESSABLE FIRE ALARM CONTROL RELAY
S = SUPPLY
R = RETURN
DUCT SMOKE DETECTOR
E = ELEVATOR WITH RECALL CONTACTS
I = IONIZATION
CEILING SMOKE DETECTOR, PHOTOELECTRIC TYPE UNLESS OTHERWISE
NOTED
MANUAL PULL STATION
FIRE ALARM / DETECTION SYSTEM
CD = CANDELA RATING
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE, WALL MOUNTED, 75CD
UNLESS OTHERWISE NOTED
CD = CANDELA RATING
STROBE, CEILING MOUNTED, 75 CD UNLESS OTHERWISE NOTED
SPEAKER ONLY, CEILING MOUNTED
PUSH BUTTON CONNECTION
BEAM SMOKE DETECTOR
BT OR T = BEAM DETECTOR TRANSMITTER
BR OR R = BEAM DETECTOR RECEIVER
SPEAKER ONLY, WALL MOUNTED
VOICE EVACUATION PANEL
MASS NOTIFICATION SYSTEM PANEL
SYMBOL DESCRIPTION
F
S
S
BR
S
H
DH
XXCD
F H
XXCD
C
S C
S
VS
WS
PS
FACP
FATC
FAA
EVAC
MNS
R
MASS NOTIFICATION SYSTEM PANELDACT
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF
DEVICE, UNLESS OTHERWISE NOTED.
2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK
SPLASH TO CENTERLINE OF DEVICE.
3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH
THEY ARE TO BE INSTALLED.
4. THE FOLLOWING NEC REQUIREMENTS SHALL BE MET:
A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH A
WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN
ACCORDANCE WITH NEC 408.
5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE
CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED
WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES
PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE
SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN
THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
GENERAL NOTES
Z
C
RK
CB
SH
T
E
S
D
N
N
SE
SA
N NURSE CALL SYSTEM CONDUIT AND WIRING
NCMS
NURSE CALL MASTER STATION
NCEC
NURSE CALL EQUIPMENT CABINET
CODE BLUE ANNUNCIATOR PANEL WALL MOUNTED
CBAP
CORRIDOR ZONE LIGHT
CORRIDOR DOME LIGHT WALL MOUNTED
37-PIN PATIENT BED CONNECTOR
CODE BLUE EMERGENCY STATION
SHOWER EMERGENCY STATION
TOILET EMERGENCY STATION
EMERGENCY STATION
STAFF TERMINAL STATION
DUTY STATION
DUAL PATIENT STATION
SINGLE PATIENT ENHANCED STATION
NURSE CALL SYSTEMS
STAFF EMERGENCY STATION
STAFF ASSIST/CODE BLUE
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p
L a b
E
T
R
.r v t
/9
/2
:0
:0
A
M
E-EI-01
ELECTRICAL SYMBOLS, LEGEND,
NOTES AND INDEX
CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
VMR07/10/2024
626-310
AN
100% CONSTRUCTION
DOCUMENTS
ELECTRICAL DRAWING INDEX
SHEET DESCRIPTION
E-EI-01 ELECTRICAL SYMBOLS, LEGEND, NOTES AND INDEX
E-EI-02 ELECTRICAL ONE-LINE DIAGRAM
E-EI-03 ELECTRICAL PANEL SCHEDULES
E-EI-04 ELECTRICAL PANEL SCHEDULES
E-EI-05 ELECTRICAL DETAILS
E-EI-06 ELECTRICAL DETAILS
E-EI-07 ELECTRICAL DETAILS
E-EI-08 ELECTRICAL DETAILS
E-EI-09 ELECTRICAL SCHEDULES
E-ES-01 ELECTRICAL SITE PLAN
E-ED-01.01 OVERALL CRAWLSPACE LEVEL DEMO - ELECTRICAL
E-ED-02.01 OVERALL BASEMENT FLOOR DEMO - ELECTRICAL
E-EL-02.01 OVERALL BASEMENT RCP PLAN NEW WORK - LIGHTING
E-EL-02.01A BASEMENT RCP PLAN AREA A & B NEW WORK - LIGHTING
E-EL-02.01B BASEMENT RCP PLAN AREA C NEW WORK - LIGHTING
E-EL-02.01C BASEMENT RCP PLAN AREA D & E NEW WORK - LIGHTING
E-EL-02.01D BASEMENT RCP PLAN AREA F NEW WORK - LIGHTING
E-EP-01.01 OVERALL CRAWLSPACE LEVEL NEW WORK - POWER
E-EP-02.01 OVERALL BASEMENT FLOOR NEW WORK - POWER
E-EP-02.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - POWER
E-EP-02.01B BASEMENT FLOOR PLAN AREA C NEW WORK - POWER
E-EP-02.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - POWER
E-EP-02.01D BASEMENT FLOOR PLAN AREA F NEW WORK - POWER
E-EF-02.01 OVERALL BASEMENT FLOOR NEW WORK - FIRE ALARM
E-EF-02.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - FIRE ALARM
E-EF-02.01B BASEMENT FLOOR PLAN AREA C NEW WORK - FIRE ALARM
E-EF-02.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - FIRE ALARM
E-EF-02.01D BASEMENT FLOOR PLAN AREA F NEW WORK - FIRE ALARM
E-EN-02.01 OVERALL BASEMENT FLOOR NEW WORK - NURSE CALL
E-EN-02.01A BASEMENT FLOOR PLAN AREA A & B NEW WORK - NURSE CALL
E-EN-02.01B BASEMENT FLOOR PLAN AREA C NEW WORK - NURSE CALL
E-EN-02.01C BASEMENT FLOOR PLAN AREA D & E NEW WORK - NURSE CALL
Revisions: Date:
3W CU MTR 3W CU MTR60A FDR (70A@60°C) 45A FDR (55A@60°C)
T-N6GM
225 KVA
480V- 208Y/120
2N6GM
208Y/120V, 3PH, 4W
800A
(25,000 AIC)
MCC AC6
600225
N6GM
480Y/277V, 3PH, 4W
800A
(35,000 AIC)
350 400
EXISTING SQUARE D I-LINE
1500KVA
4.16KV (PRI)
480Y/277V (SEC)
PT-6
LSI
PG 5.0
JD 3.2S
HD
HD LG 5.3A
JD 3.2S
LSI
PG 5.0
LG 5.3A
N63
N6GW
(65,000 AIC)
EXISTING SQUARE D I-LINE
LC
LC
HJ
HJ
HJ
SPD
SPARE SPARE
LG 5.3A
LG 5.3A
N63
HG 3.2S
LIFE SAFETY
ATS-6L
260A,4-POLE
L6GM
480Y/277V, 3PH, 4W
250A
(35,000 AIC)
10030
EXISTING SQUARE D I-LINE
HG
HG
SPD
T-L6GM
15 KVA
480V- 208Y/120
HG
T-L62E
15 KVA
480V- 208Y/120
2L62E
L61E
HG
L62E
HG
T-L61E
15 KVA
480V- 208Y/120
2L61E
T-N61W
HG 3.2S
T-N61E
HG 3.2S
N61E
HG 3.2S
N62E
HG 3.2S
T-N62W
HG 3.2S
T-N62E
LG 5.3A
CRITICAL
ATS-6C
400A,4-POLE
C6GM
480Y/277V, 3PH, 4W
400A
(35,000 AIC)
EXISTING SQUARE D I-LINE
HG
T-C6GM
45 KVA
480V- 208Y/120
HG
T-C61W
30 KVA
480V- 208Y/120
2C61W
PG 5.0
HG
T-C62W
30 KVA
480V- 208Y/120
2C62W
HG
T-C61E
30 KVA
480V- 208Y/120
2C61E
HG
C61E
HG
C62E
HG
T-C62E
30 KVA
480V- 208Y/120
2C62E
SPD
EQUIPMENT
ATS-6Q
600A,4-POLE
EXISTING SQUARE D I-LINE
LG 5.3A
T-Q6GM
112.5 KVA
480V- 208Y/120
LG 5.3A
HG
T-Q62E
75 KVA
480V- 208Y/120
2Q62E
HG
T-Q61E
30 KVA
480V- 208Y/120
2Q61E
SPD
EXISTING SQUARE QED SWITCHBOARD
LG 5.3A
2QCG
EXISTING SQUARE D I-LINE
LSI
LD 5.3A
LG 5.3A
HG
LG 5.3A
ELEV-2 ELEV-1
Q63
HG
T-Q61W
30 KVA
480V- 208Y/120
2Q61W
HG
T-Q62W
30 KVA
480V- 208Y/120
2Q62W
E5GM (BUILDING 5)
480Y/277V, 3PH, 4W
1000A
(65,000 AIC)
250 400 600 450
ATS-5C
ATS-5L
ATS-5Q
PARTIAL ONE-LINE DIAGRAM
SCALE: N.T.S.
60AT
100AF
3R
40AT
60AF
3R
2N6GW1
(22,000 AIC)
2N6GW3
(22,000 AIC)
2N6GE
(22,000 AIC)
2P6GW2
(22,000 AIC)
42 42
N6DP
480Y/277V, 3PH, 4W
600A
(65,000 AIC)
2L6GM
(10,000 AIC)
2C6GM
(10,000 AIC)
Q6GM
480Y/277V, 3PH, 4W
600A
(35,000 AIC)
2Q6GM-1
208Y/120V, 3PH, 4W
400A
(25,000 AIC)
2Q6GM-2
HG 3.3S
DOAS-1
HG 3.3S
ODU-1
(3) #4,
(1) #4 GND,
1-1/2" C.
(3) #6,
(1) #6 GND,
1-1/4" C.
GENERAL ONELINE NOTES
REFER TO PANEL SCHEDULES, FLOOR PLANS, ETC FOR ADDITIONAL LOADS, GENERAL
INFORMATION AND PANELBOARD REQUIREMENTS NOT SPECIFICALLY INDICATED ON THIS SHEET.
1.
EXISTING DEMAND LOADS INDICATED ARE COMPRISED OF EITHER LOAD READINGS OR EXISTING
CALCULATED DEMAND LOADS FROM PREVIOUS PROJECTS.
2.
EQUIPMENT NOT AFFECTED BY PROJECT SCOPE ARE SHOWN FOR INFORMATION REFERENCE ONLY.
EQUIPMENT CURRENTLY SERVING ELECTRICAL DEVICES BEING REMOVED AS PART OF PROJECT
SCOPE ARE TO ILLUSTRATE INFORMATION OBTAINED FROM FIELD SURVEY AND EXISTING DRAWINGS.
3.
COORDINATE CIRCUIT BREAKER SELECTION AND LUG CAPACITIES WITH SPECIFIED WIRE SIZES, PROVIDE LUG KITS AS REQUIRED.
4.
CONTRACTOR SHALL VERIFY ALL CIRCUIT BREAKER(S) IN PANELBOARDS AFFECTED BY SCOPE OF
WORK HAVE AN "AIC" RATING EQUAL TO OR GREATER THAN THE AIC INDICATED FOR EACH
PANELBOARD PER THE ONE-LINE DIAGRAM. VERIFY WITH ENGINEER FOR BREAKER TYPE(S) WITH
CORRECT SELECTIVE COORDINATION PRIOR TO PURCHASE.
5.
VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT WITH
MANUFACTURER'S RECOMMENDATIONS PRIOR TO INSTALLATION OF EQUIPMENT.
6.
CONDUCTORS IN VERTICAL RACEWAY SHALL BE SUPPORTED PER NEC 300.19. REFER TO NEC
TABLE 300.19(A).
7.
THE EQUIPMENT GROUNDING TERMINAL OF NORMAL AND ESSENTIAL PANELBOARDS SERVING THE
SAME PATIENT CARE AREA SHALL BE BONDED BY A #10AWG CU CONDUCTOR IN ACCORDANCE
WITH NEC 517.14.
8.
CONTRACTOR SHALL PROVIDE A FEEDER ROUTING PLAN FOR ALL PANELS FOR OWNER/ENGINEER
APPROVAL PRIOR TO INSTALLATION. OWNER/ENGINEER CAN ADJUST ROUTING AS REQUIRED AT
NO ADDITIONAL CHARGE.
9.
THE PANEL/GEAR SUPPLIER SHALL PROVIDE A SELECTIVE CIRCUIT BREAKER COORDINATION STUDY
ALONG WITH THE GEAR SUBMITTAL. THE CIRCUIT BREAKERS IN THE STUDY SHALL MATCH THE
BREAKERS SUPPLIED AND INSTALLED IN THE FIELD.
10.
CONTRACTOR AND PANEL/GEAR SUPPLIER SHALL PROVIDE A TABLE/SUMMARY OF ALL ADJUSTABLE TRIP BREAKERS FOR FIELD VERIFICATION AND SETTING. THE TABLE/SUMMARY SHALL INCLUDE
TRIP SETTINGS, BREAKER TYPE, AMPERAGE, VOLTAGE AND PANEL LOCATION. CONTRACTOR
SHALL HAVE A MANUFACTURER'S REPRESENTATIVE SET ALL BREAKERS PRIOR TO THE AHCA 80%
INSPECTION. THE MANUFACTURER'S REPRESENTATIVE SHALL PROVIDE A REPORT STATING ALL
BREAKERS MATCH THE COORDINATION STUDY AND ALL SETTINGS ARE COMPLETE.
11.
UNLESS NOTED OTHERWISE, CIRCUIT BREAKERS AND ALL DISTRIBUTION BASIS OF DESIGN SHALL BE
SCHNEIDER/SQUARE-D.
12.
CONTRACTOR (CM & EC) SHALL COORDINATE ALL ELECTRICAL SHUTDOWNS WITH OWNER. PRIOR
TO REQUESTING AND STARTING A SHUTDOWN, THE CONTRACTOR SHALL PREPARE A DETAILED
SEQUENCE OF STEPS FOR EACH SHUTDOWN. THIS SEQUENCE SHALL INCLUDE INDIVIDUAL STEPS, WORK DESCRIPTION, RESPONSIBILITY, PROPOSED TIME, TIME DURATION AND COMMENT COLUMNS.
EACH SEQUENCE SHALL INCLUDE A PARTIAL ONE-LINE DIAGRAM SHOWING THE WORKED BEING
EXECUTED. THIS SEQUENCE CAN BE ADJUSTED AS NEEDED AS MANY TIMES BY THE OWNER AND
EOR AT NO ADDITIONAL CHARGE/COST.
13.
ALL VARIABLE FREQUENCY DRIVES (VFD) SHALL BE PROVIDED WITH INTEGRAL DISCONNECTING MEANS, CAPABLE OF BEING LOCKED IN THE OFF POSITION FOR LOCKOUT / TAGOUT PROCEDURES.
VFD'S TO BE PROVIDE BY DIVISION 23 AND INSTALLED BY DIVISION 26. DIVISION 26 CONTRACTOR SHALL COORDINATE VFD AIC RATING REQUIREMENTS WITH DIVISION 23 CONTRACTOR PRIOR TO
ORDERING.
ALL CONDUIT SIZES SHOWN COMPLY WITH NEC FILL CALCULATIONS FOR EMT CONDUIT. WHERE WIRE IS PULLED IN PVC SCHEDULE 40/80 OR OTHER RACEWAY SHALL PROVIDE CONDUIT AS REQUIRED BY
NEC FILL CALCULATIONS.
PROVIDE GROUNDING BUSHINGS FOR FEEDER TERMINATIONS AND INTERMEDIATE
ALL BREAKERS RATED 1200A OR LARGER SHALL HAVE ARC FLASH REDUCTION MEASURES BUILT INTO
THE DEVICE VIA MAINTENANCE SWITCH.
ALL DISTRIBUTION BOARDS SHALL BE FULL-HEIGHT.
UNLESS OTHERWISE NOTED, ALL 120V PANELS SHALL BE RATED AT 10,000 AIC.
14.
15.
16.
17.
18.
19.
ONE-LINE DIAGRAM LEGEND
EXISTING AFFECTED BY THIS PROJECT
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW EQUIPMENT
20. FOR ALL SURGE PROTECTIVE DEVICES; PROVIDE CIRCUIT BREAKER AND WIRE SIZE AS
21.
RECOMMENDED BY SURGE PROTECTIVE DEVICE MANUFACTURER. MINIMIZE LEAD LENGTH AND
TWIST LEADS IN CONDUIT.
PROVIDE UPDATED TYPED PANEL DIRECTORIES AND/OR ENGRAVED PHENOLIC LABELS FOR ALL
PANELBOARDS AND SWITCHBOARDS AFFECTED BY SCOPE OF WORK.
PULLBOXES/CABINETS.
ONE-LINE DIAGRAM NOTES:
1 CONTRACTOR SHALL TRACE EVERY CIRCUIT ON PANEL, PROVIDE INFORMATION TO
ENGINEER, AND PROVIDE ALLOWANCE TO RECIRCUIT EVERY CIRCUIT ON PANEL TO
ANOTHER PANEL WITHIN 50'.
2 PROVIDE NEW BREAKER IN EXISTING PANELBOARD SPACE.
1 1
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p
L a b
E
T
R
.r v t
/9
/2
:0
:0
A
M
E-EI-02
ELECTRICAL ONE-LINE DIAGRAM CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
VMR07/10/2024
626-310
AN
100% CONSTRUCTION
DOCUMENTS
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p
L a b
E
T
R
.r v t
/9
/2
:0
:1
A
M
E-EI-03
ELECTRICAL PANEL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
VMR07/10/2024
626-310
AN
100% CONSTRUCTION
DOCUMENTS
GENERAL NOTES
1 ALL PANELBOARDS SHOWN ARE EXISTING TO BE REUSED.
2 EXISTING CIRCUIT BREAKERS ARE TO BE REUSED EXCEPT FOR LOCATIONS WHERE NEW
EQUIPMENT/DEVICES REQUIRE A DIFFERENT CIRCUIT BREAKER SIZE. COMPARE EXISTING
PANELBOARD WITH NEW REQUIREMENT OF CIRCUIT BREAKER SIZES SHOWN ON THIS SHEET.
3 TOTAL LOAD SHOWN ARE FOR NEW CONNECTED LOADS.
Panel Keynotes (KN):
Total Demand Current (A): 50
RECEPTACLE 23600 VA 71.19% 16800 VA Total Demand Load (KVA): 17.852
LIGHTING 52 VA 100.00% 52 VA Total Connected Load (KVA): 24.652
EQUIPMENT 1000 VA 100.00% 1000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 58.500 75.538 75.938
Connected Phase Load (KVA) 7.020 8.792 8.840
41 REC - ROOMS G17, G17A 20 1 0.920 0.000 1 20 Spare 42
39 REC - ROOMS G16, G17 20 1 0.900 0.052 1 20 DECORATIVE LIGHTING - CORRIDOR 40
37 ICE MACHINE - BREAKROOM G18 20 1 0.180 0.180 1 20 REC - CORRIDOR 38
35 MICROWAVE - BREAKROOM G18 20 1 0.180 1.080 1 20 REC - CORRIDOR 36
33 COFFEE - BREAKROOM G18 20 1 0.180 1.000 1 20 DECORATIVE FEATURES - CORRIDOR 34
31 REFRIDGE - BREAKROOM G18 20 1 0.180 0.540 1 20 REC - EQUIPMENT G24 32
29 REC - BREAKROOM G18 20 1 0.360 0.180 1 20 PRINT - PRINT G25A 30
27 REC - BREAKROOM G18 20 1 0.900 0.360 1 20 REC - RECEPTION G25 28
25 REC - FITTING G15 20 1 0.360 1.080 1 20 REC - RECEPTION G25 26
23 REC - FITTING G15 20 1 0.540 0.720 1 20 REC - EXAM G27 24
21 REC - FITTING G15 20 1 0.360 0.720 1 20 REC - EXAM G28 22
19 REC - FITTING G15 20 1 0.540 0.180 1 20 PRINT - SUITE G29 20
17 REC - WAITING G14 20 1 1.080 1.080 1 20 REC - SUITE G30 18
15 REC - WAITING G14 20 1 0.540 1.080 1 20 REC - SUITE G30 16
13 COPY - COPY/PRINT G13A 20 1 0.180 1.080 1 20 REC - SUITE G30 14
11 REC - RECEPTION G13 20 1 0.720 1.080 1 20 REC - SUITE G30 12
9 REC - RECEPTION G13 20 1 1.080 0.360 1 20 REC - ROOMS G29,G30 10
7 REC - SUPPLY G04 20 1 0.540 0.720 1 20 REC - EXAM G31 8
5 REC - RME G02A 20 1 0.360 0.540 1 20 REC - WAITING G-011 6
3 REC - CLEAN UTILITY G02 20 1 0.540 0.720 1 20 REC - OFFICE G22 4
1 REC - ROOMS G01A, G01B 20 1 0.540 0.720 1 20 REC - OFFICE G21 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2N6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MLO MCB Rating: 225 A
Location: ELECT G19 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 225 A
Panel: 2N6GW1
Panel Keynotes (KN):
Total Demand Current (A): 39
Total Demand Load (KVA): 13.890
RECEPTACLE 12780 VA 89.12% 11390 VA Total Connected Load (KVA): 15.280
EQUIPMENT 2500 VA 100.00% 2500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 35.667 52.192 40.859
Connected Phase Load (KVA) 4.280 6.180 4.820
41 Spare 20 1 0.000 0.000 1 20 Spare 42
39 Spare 20 1 0.000 0.000 1 20 Spare 40
37 Spare 20 1 0.000 0.000 1 20 Spare 38
35 Spare 20 1 0.000 0.000 1 20 Spare 36
33 Spare 20 1 0.000 0.000 1 20 Spare 34
31 Spare 20 1 0.000 0.540 1 20 REC - EXAM G23M 32
29 Spare 20 1 0.000 0.540 1 20 REC - EXAM G23K 30
27 Spare 20 1 0.000 0.540 1 20 REC - EXAM G23J 28
25 Spare 20 1 0.000 0.540 1 20 REC - EXAM G23I 26
23 Spare 20 1 0.000 0.180 1 20 PRINT - TELEHEALTH G23H 24
21 Spare 20 1 0.000 1.080 1 20 REC - TELEHEALTH G23H 22
19 Spare 20 1 0.000 0.360 1 20 REC - ROOMS G23G,G23H 20
17 REC - MECH 171A 20 1 0.180 1.080 1 20 REC - WORK STATION G23G 18
15 REC - EXTERIOR 20 1 0.180 1.080 1 20 REC - WORK STATION G23G 16
13 AUTODOOR 20 1 0.500 1.080 1 20 REC - WORK STATION G23G 14
11 AUTODOOR 20 1 0.500 1.080 1 20 REC - WORK STATION G23G 12
9 TRAP PRIMER 20 1 1.500 0.720 1 20 REC - SLEEP STUDY G23F 10
7 REC - CORRIDOR 20 1 0.180 0.540 1 20 REC - TOILET G23D,G23E,G23L 8
5 REC - TOILET G34A,G35,G36 20 1 0.540 0.720 1 20 REC - SLEEP STUDY G23C 6
3 REC - ENTRY G34 20 1 0.720 0.360 1 20 REC - SOILED G23B 4
1 PP-610 20 1 0.180 0.360 1 20 REC - CLEAN G23A 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2N6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MLO MCB Rating: 100 A
Location: ELECT G19 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 100 A
Panel: 2N6GW2
Panel Keynotes (KN):
Total Demand Current (A): 0
Total Demand Load (KVA): 0.000
Total Connected Load (KVA): 0.000
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 0.000 0.000 0.000
Connected Phase Load (KVA) 0.000 0.000 0.000
41 Spare 20 1 0.000 0.000 1 20 Spare 42
39 Spare 20 1 0.000 0.000 1 20 Spare 40
37 Spare 20 1 0.000 0.000 1 20 Spare 38
35 Spare 20 1 0.000 0.000 1 20 Spare 36
33 Spare 20 1 0.000 0.000 1 20 Spare 34
31 Spare 20 1 0.000 0.000 1 20 Spare 32
29 Spare 20 1 0.000 0.000 1 20 Spare 30
27 Spare 20 1 0.000 0.000 1 20 Spare 28
25 Spare 20 1 0.000 0.000 1 20 Spare 26
23 Spare 20 1 0.000 0.000 1 20 Spare 24
21 Spare 20 1 0.000 0.000 1 20 Spare 22
19 Spare 20 1 0.000 0.000 1 20 Spare 20
17 Spare 20 1 0.000 0.000 1 20 Spare 18
15 Spare 20 1 0.000 0.000 1 20 Spare 16
13 Spare 20 1 0.000 0.000 1 20 Spare 14
11 Spare 20 1 0.000 0.000 1 20 Spare 12
9 Spare 20 1 0.000 0.000 1 20 Spare 10
7 Spare 20 1 0.000 0.000 1 20 EXISTING LOAD 8
5 Spare 20 1 0.000 0.000 1 20 EXISTING LOAD 6
3 EXISTING LOAD 20 1 0.000 0.000 1 20 EXISTING LOAD 4
1 EXISTING LOAD 20 1 0.000 0.000 1 20 EXISTING LOAD 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2N6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MLO MCB Rating: 100 A
Location: ELECT G19 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 100 A
Panel: 2N6GW3
Panel Keynotes (KN):
Total Demand Current (A): 57
Total Demand Load (KVA): 20.480
Total Connected Load (KVA): 30.960
RECEPTACLE 30960 VA 66.15% 20480 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 82.611 80.111 95.944
Connected Phase Load (KVA) 9.873 9.613 11.473
41 REC - MEDS G07I 20 1 0.540 0.720 1 20 REC - IT/DATA G03A 42
39 REC - TOMOGRAPHY G07H 20 1 0.360 0.533 40
37 REC - YAG LASER G07G 20 1 1.080 0.533 38
35 REC - EXAM G07F 20 1 1.080 0.533
3 20 RACK - IT/DATA G03A
33 REC - PHOTOCOAG LASER G07D 20 1 0.920 0.720 1 20 REC - TELECOM G03B 34
31 EQUIP - SPEC TESTING G07C 20 1 0.180 0.800 32
29 EQUIP - SPEC TESTING G07C 20 1 0.180 0.800
2 30 RACK - TELECOM G03B
27 REC - SPEC TESTING G07C 20 1 0.900 0.180 1 20 AC-2 COND PUMP 28
25 EQUIP - VISUAL FIELDS G07B 20 1 0.180 0.180 1 20 AC-1 COND PUMP 26
23 REC - VISUAL FIELDS G07B 20 1 0.900 0.900 1 20 REC - OFFICE G05 24
21 REC - ULTRASOUND G07A 20 1 0.720 0.540 1 20 REC - G08B, G09 22
19 REC - EXAM G09K 20 1 1.100 0.900 1 20 REC - CORRIDOR 20
17 REC - EXAM G09J 20 1 1.100 0.720 1 20 REC - ROOMS G07J, G08, G08A 18
15 REC - EXAM G09I 20 1 1.100 0.180 1 20 EQUIP - TOMOGRAPHY G07H 16
13 REC - EXAM G09H 20 1 1.280 0.180 1 20 EQUIP - TOMOGRAPHY G07H 14
11 REC - EXAM G09G 20 1 1.100 0.720 1 20 REC - OFFICE G07E 12
9 REC - EXAM G09E 20 1 1.100 0.180 1 20 COPY - WORKSTATIONS G09F 10
7 REC - EXAM G09D 20 1 1.100 0.180 1 20 REC - WORKSTATIONS G09F 8
5 REC - EXAM G09C 20 1 1.100 1.080 1 20 REC - WORKSTATIONS G09F 6
3 REC - EXAM G09B 20 1 1.100 1.080 1 20 REC - WORKSTATIONS G09F 4
1 REC - EXAM G09A 20 1 1.100 1.080 1 20 REC - WORKSTATIONS G09F 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2N6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB Rating: 225 A
Location: ELECT G12 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 225 A
Panel: 2N6GE-1
Panel Keynotes (KN):
Total Demand Current (A): 9
Total Demand Load (KVA): 3.240
Total Connected Load (KVA): 3.240
RECEPTACLE 3240 VA 100.00% 3240 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 9.231 10.731 7.500
Connected Phase Load (KVA) 1.080 1.260 0.900
41 0.000 1 20 Spare 42
39 DESK - YAG LASER G07G 20 1 0.180 0.000 1 20 Spare 40
37 DESK - PHOTOCOAG LASER G07D 20 1 0.180 0.000 1 20 Spare 38
35 DESK - VISUAL FIELDS G07B 20 1 0.180 0.000 1 20 Spare 36
33 DESK - EXAM G09K 20 1 0.180 0.000 1 20 Spare 34
31 DESK - EXAM G09J 20 1 0.180 0.000 32
29 DESK - EXAM G09I 20 1 0.180 0.000
2 30 EXISTING LOAD
27 DESK - EXAM G09H 20 1 0.360 0.000 1 15 Spare 28
25 DESK - EXAM G09G 20 1 0.180 0.000 1 20 Spare 26
23 DESK - EXAM G09D 20 1 0.180 0.000 1 20 Spare 24
21 DESK - EXAM G09E 20 1 0.180 0.000 1 20 EXISTING LOAD 22
19 DESK - EXAM G09C 20 1 0.180 0.000 1 20 EXISTING LOAD 20
17 DESK - EXAM G09B 20 1 0.180 0.000 18
15 DESK - EXAM G09A 20 1 0.180 0.000 16
13 REC - CORRIDOR 20 1 0.360 0.000
3 20 EXISTING LOAD
11 REC - MECH 110A 20 1 0.180 0.000 12
9 REC - MAINTENANCE 20 1 0.180 0.000 10
7 0.000 0.000
3 20 EXISTING LOAD
EXISTING LOAD 15 2
0.000 0.000 6
3 0.000 0.000 4
EXISTING LOAD 20 2
0.000 0.000
3 50 EXISTING LOAD
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2N6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB Rating: 225 A
Location: ELECT G12 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 225 A
Panel: 2N6GE-2
Panel Keynotes (KN):
Total Demand Current (A): 53
Total Demand Load (KVA): 19.260
RECEPTACLE 16520 VA 80.27% 13260 VA Total Connected Load (KVA): 22.520
Other 6000 VA 100.00% 6000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 67.368 61.368 59.444
Connected Phase Load (KVA) 8.053 7.333 7.133
41 REC - EXAM G23M 20 1 0.360 42
39 REC - EXAM G23K 20 1 0.360 0.180 1 20 FRIDGE - MEDS G07I 40
37 REC - EXAM G23J 20 1 0.360 0.720 1 20 REC - TOMOGRAPHY G07H 38
35 REC - EXAM G23I 20 1 0.360 0.540 1 20 REC - YAG LASER G07G 36
33 REC - SLEEP STUDY G23F 20 1 0.360 0.540 1 20 REC - EXAM G07F 34
31 REC - SLEEP STUDY G23C 20 1 0.720 0.360 1 20 REC - PHOTOCOAG LASER G07D 32
29 REC - EXAM G26 20 1 0.360 0.540 1 20 REC - ROOMS G01B,G02,G02A 30
27 REC - EXAM G28 20 1 0.360 0.360 1 20 REC - SPEC TESTING G07C 28
25 REC - EXAM G31 20 1 0.360 0.360 1 20 REC - VISUAL FIELDS G07B 26
23 REC - TELECOM G03B 20 1 1.080 0.180 1 20 EQUIP - ULTRASOUND G07A 24
21 RADIO/DAS - TELECOM G03B 20 1 1.200 0.360 1 20 REC - ULTRASOUND G07A 22
19 TELEVISION - TELECOM G03B 20 1 1.200 0.360 1 20 REC - EXAM GO9K 20
17 PUBLIC ADDRESS - TELECOM G03B 20 1 1.200 0.360 1 20 REC - EXAM GO9J 18
15 TELECOM - TELECOM G03B 20 1 1.200 0.360 1 20 REC - EXAM GO9I 16
13 SECURITY - TELECOM G03B 20 1 1.200 0.360 1 20 REC - EXAM GO9H 14
11 REC - IT/DATA G03A 20 1 0.900 0.360 1 20 REC - EXAM GO9G 12
9 0.533 0.360 1 20 REC - EXAM GO9E 10
7 0.533 0.360 1 20 REC - EXAM GO9D 8
RACK - IT/DATA G03A 20 3
0.533 0.360 1 20 REC - EXAM GO9C 6
3 0.800 0.360 1 20 REC - EXAM GO9B 4
RACK - TELECOM G03B 30 2
0.800 0.360 1 20 REC - EXAM GO9A 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: TC6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB Rating:
Location: ELECT G03 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 150 A
Panel: 2C6GM
Panel Keynotes (KN):
Total Demand Current (A): 13
Total Demand Load (KVA): 4.700
Other 1200 VA 100.00% 1200 VA Total Connected Load (KVA): 4.700
EQUIPMENT 3500 VA 100.00% 3500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 18.974 8.333 13.141
Connected Phase Load (KVA) 2.200 1.000 1.500
29 Space -- 1 -- 0.500 1 20 EQUIPMENT 30
27 EXISTING LOAD 20 1 0.000 0.000 1 20 Spare 28
25 EXISTING LOAD 20 1 0.000 1.200 1 20 FIRE ALARM CONTROL PANEL 26
23 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 24
21 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 22
19 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 20
17 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 18
15 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 16
13 EXISTING LOAD 20 1 0.000 0.500 1 20 AUTODOOR 14
11 EXISTING LOAD 20 1 0.000 0.000 1 20 Spare 12
9 EXISTING LOAD 20 1 0.000 0.000 1 20 Spare 10
7 EXISTING LOAD 20 1 0.000 0.000 1 20 Spare 8
5 EXISTING LOAD 20 1 0.000 0.000 1 20 Spare 6
3 EXISTING LOAD 20 1 0.000 0.000 1 20 EXISTING LOAD 4
1 EXISTING LOAD 20 1 0.000 0.000 1 20 EXISTING LOAD 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: TL6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB Rating:
Location: ELECT G03 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 60 A
Panel: 2L6GM
Panel Keynotes (KN):
Total Demand Current (A): 27
RECEPTACLE 16520 VA 80.27% 13260 VA Total Demand Load (KVA): 22.760
Other 6000 VA 100.00% 6000 VA Total Connected Load (KVA): 26.020
EQUIPMENT 3500 VA 100.00% 3500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 33.397 30.797 29.964
Connected Phase Load (KVA) 9.220 8.500 8.300
41 0.167 0.000 42
39 0.167 0.000 40
PROVISION 250 3
0.167 0.000
3 100 Spare
35 0.167 0.000 36
33 0.167 0.000 34
C62E 100 3
0.167 0.000
3 125 Spare
29 0.167 0.000 30
27 0.167 0.000 28
C61E 100 3
0.167 0.000
3 50 Spare
23 0.167 0.000 24
21 0.167 0.000 22
2C61E (TC61E) 50 3
0.167 0.000
3 100 Spare
17 0.167 0.167 18
15 0.167 0.167 16
2C62W (TC62W) 50 3
0.167 0.167
3 50 2C62E (TC62E)
11 0.167 0.000 1 20 Spare 12
9 0.167 0.000 1 20 Spare 10
2C61W (TC61W) 50 3
0.167 0.000 1 20 Spare 8
5 7.133 0.000 1 20 Spare 6
3 7.333 0.000 1 20 Spare 4
2C6GM (TC6GM) 70 3
8.053 0.000 1 20 Spare 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MLO MCB Rating:
Location: ELECT G03 Mounting: SURFACE Dist. / Phase / Wires: 480/277 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 400 A
Panel: C6GM
P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
923116
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
214 Centerview Drive Suite 300 Brentwood, TN 37027
615.370.8500woldae.com
102 THIRD AVENUE NE
HICKORY, NC 28601
PHONE: 828.315.9962
FAX: 828.315.9966
NC ENGINEERING LICENSE NO: P-0214
NC ARCHITECTURE LICENSE NO: 51254
MURFREESBORO, TN
A u to d e s k D o c s /2
V
A M
C S le e p
D is o rd e r
C lin ic /9
-T
V H
S A
C Y
V A
M C
S le e p
L a b
E
T
R
.r v t
/9
/2
:0
:2
A
M
E-EI-04
ELECTRICAL PANEL SCHEDULES CONSTRUCT SLEEP DISORDER CLINIC
AND SPECIALTY CLINIC
VMR07/10/2024
626-310
AN
100% CONSTRUCTION
DOCUMENTS
GENERAL NOTES
1 ALL PANELBOARDS SHOWN ARE EXISTING TO BE REUSED.
2 EXISTING CIRCUIT BREAKERS ARE TO BE REUSED EXCEPT FOR LOCATIONS WHERE NEW
EQUIPMENT/DEVICES REQUIRE A DIFFERENT CIRCUIT BREAKER SIZE. COMPARE EXISTING
PANELBOARD WITH NEW REQUIREMENT OF CIRCUIT BREAKER SIZES SHOWN ON THIS SHEET.
3 TOTAL LOAD SHOWN ARE FOR NEW CONNECTED LOADS.
Switchboard Notes:
Total Demand Current (A): 122 A
RECEPTACLE 70580 VA 57.08% 40290 VA Total Connected Demand (KVA): 43.84 kVA
LIGHTING 52 VA 100.00% 52 VA Total Conn. Load: 74.13 kVA
EQUIPMENT 3500 VA 100.00% 3500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
12 Space 3 -- --
11 Space 3 -- --
10 Space 3 -- --
9 Space 1 -- --
8 Space 1 -- --
7 Space 3 -- --
6 2N6GE-2 3 250 A 3.24
5 2N6GE-1 3 250 A 30.96
4 MCC-AC6 1 600 A 0.00
3 2N6GW3 3 100 A 0.00
2 2N6GW2 3 100 A 15.28
1 2N6GW1 3 250 A 24.65
CKT Circuit Description # of
Poles Trip Rating (A) Load (KVA) Remarks
Supply From: TN6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB MCB Rating: 800 A
Location: ELECT G12 Mounting: SURFACE Distribution / Phase / Wires: 120/208 Wye K.A.I.C. Rating: Bus Rating: 800 A
SWITCHBOARD: 2N6GM
Panel Keynotes (KN):
HVAC 0 VA 0.00% 0 VA Total Demand Current (A): 52
Other 1200 VA 100.00% 1200 VA Total Demand Load (KVA): 18.727
Motor 16076 VA 107.01% 17203 VA Total Connected Load (KVA): 17.600
EQUIPMENT 324 VA 100.00% 324 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 44.271 48.827 54.784
Connected Phase Load (KVA) 5.313 5.786 6.501
41 Spare 20 1 0.000 0.000 1 20 Spare 42
39 Spare 20 1 0.000 0.000 1 20 Spare 40
37 Spare 20 1 0.000 0.000 1 20 Spare 38
35 Spare 20 1 0.000 0.000 1 20 Spare 36
33 Spare 20 1 0.000 0.000 1 20 Spare 34
31 Spare 20 1 0.000 0.000 1 20 Spare 32
29 Spare 20 1 0.000 0.000 1 20 Spare 30
27 Spare 20 1 0.000 0.000 1 20 Spare 28
25 Spare 20 1 0.000 0.000 1 20 Spare 26
23 DOAS HEAT TRACE 20 1 0.200 0.000 1 20 Spare 24
21 P-DOAS-1 20 1 0.124 0.000 1 20 Spare 22
19 EF-3 15 1 0.101 1.200 1 20 DDC PANEL 20
17 EF-2 15 1 0.035 2.255 18
15 EF-1 15 1 0.070 2.255
2 30 AC-2
13 FCU-3 15 1 0.176 2.255 14
11 FCU-2 15 1 0.176 2.255
2 30 AC-1
9 FCU-1 15 1 0.176 1.581 10
7 0.000 1.581
2 30 CU-2
EXISTING LOAD 15 2
0.000 1.581 6
3 0.000 1.581
2 30 CU-1
EXISTING LOAD 20 2
0.000 0.000 1 20 EXISTING LOAD 2
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: 2Q6GM-1 Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB Rating: 400
Location: ELECT G03 Mounting: SURFACE Dist. / Phase / Wires: 120/208 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 400 A
Panel: 2Q6GM-2
Panel Keynotes (KN):
HVAC 0 VA 0.00% 0 VA Total Demand Current (A): 38
Other 1200 VA 100.00% 1200 VA Total Demand Load (KVA): 31.494
Motor 24343 VA 104.63% 25470 VA Total Connected Load (KVA): 30.367
EQUIPMENT 4824 VA 100.00% 4824 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Connected Phase Amps (A) 34.542 36.516 39.097
Connected Phase Load (KVA) 9.568 10.042 10.757
41 0.133 0.000 42
39 0.133 0.000 40
RF-18 20 3
0.133 0.000
3 60 Spare
35 0.133 0.249 36
33 0.133 0.249 34
RF-17 20 3
0.133 0.249
3 15 HWP-6D
29 0.998 0.249 30
27 0.998 0.249 28
DOAS-1 40 3
0.998 0.249
3 15 HWP-6C
23 0.167 0.497 24
21 0.167 0.497 22
2Q61E (TQ61E) 50 3
0.167 0.497
3 15 CHWP-6D
17 0.167 0.497 18
15 0.167 0.497 16
2Q62E (TQ62E) 125 3
0.167 0.497
3 15 CHWP-6C
11 0.167 0.167 12
9 0.167 0.167 10
Q63 400 3
0.167 0.167
3 20 2Q62W (TQ62W)
5 7.168 0.167 6
3 6.453 0.167 4
2Q6GM (TQ6GM) 175 3
5.979 0.167
3 20 2Q61W (TQ61W)
KN CKT Circuit Description Trip(A) P A (KVA) B (KVA) C (KVA) P Trip(A) Circuit Description CKT KN
Supply From: Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MLO MCB Rating:
Location: ELECT G03 Mounting: SURFACE Dist. / Phase / Wires: 480/277 Wye / 3 / 4 K.A.I.C. Rating: BUS Rating: 400 A
Panel: Q6GM
Switchboard Notes:
Total Demand Current (A): 7 A
Other 1200 VA 100.00% 1200 VA Total Connected Demand (KVA): 6.19 kVA
LIGHTING 1494 VA 100.00% 1494 VA Total Conn. Load: 6.19 kVA
EQUIPMENT 3500 VA 100.00% 3500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
12 Spare 1 20 A 0.00
11 Spare 1 20 A 0.00
10 Spare 1 20 A 0.00
9 Spare 3 60 A 0.00
8 Spare 3 60 A 0.00
7 LIGHTING 1 20 A 0.67
6 LIGHTING 1 20 A 0.82
5 L62E 3 100 A 0.00
4 L61E 3 100 A 0.00
3 TL62E 3 100 A 0.00
2 TL61E 3 30 A 0.00
1 TL6GM 3 30 A 4.70
CKT Circuit Description # of
Poles Trip Rating (A) Load (KVA) Remarks
Supply From: Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB MCB Rating: 60
Location: ELECT G03 Mounting: SURFACE Distribution / Phase / Wires: 480/277 Wye K.A.I.C. Rating: Bus Rating: 250 A
SWITCHBOARD: L6GM
Switchboard Notes:
Total Demand Current (A): 63 A
RECEPTACLE 70580 VA 57.08% 40290 VA Total Connected Demand (KVA): 52.34 kVA
LIGHTING 52 VA 100.00% 52 VA Total Conn. Load: 82.63 kVA
EQUIPMENT 12000 VA 100.00% 12000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
21 PROVISION 3 250 A 0.50
20 PROVISION 3 250 A 0.50
19 PROVISION 3 250 A 0.50
18 PROVISION 3 400 A 0.50
17 PROVISION 3 800 A 0.50
16 2N62E (TN62E) 3 70 A 0.50
15 2N62W (TN62W) 3 70 A 0.50
14 2N61E (TN61E) 3 70 A 0.50
13 2N61W (TN61W) 3 70 A 0.50
12 N62E 3 100 A 0.50
11 N61E 3 100 A 0.50
10 N63 3 400 A 0.50
9 N63 (HVAC UPGRADE PROJ.) 3 400 A 0.50
8 Spare 1 225 A 0.00
7 Spare 1 400 A 0.00
6 Spare 1 600 A 0.00
5 NG6W 3 400 A 0.50
4 ATS-6Q 3 600 A 0.50
3 ATS-6C 3 400 A 0.50
2 ATS-6L 3 250 A 0.50
1 TN6GM 3 350 A 74.13
CKT Circuit Description # of
Poles Trip Rating (A) Load Remarks
Supply From: Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB MCB Rating: 800
Location: ELECT G12 Mounting: FLOOR Distribution / Phase / Wires: 480/277 Wye K.A.I.C. Rating: Bus Rating: 800 A
SWITCHBOARD: N6GM
Switchboard Notes:
Total Demand Current (A): 95 A
Total Connected Demand (KVA): 79.27 kVA
Motor 65000 VA 110.00% 71500 VA Total Conn. Load: 72.77 kVA
LIGHTING 7774 VA 100.00% 7774 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
15 Space 1 -- --
14 LIGHTING 1 20 A 0.38
13 LIGHTING 1 20 A 1.15
12 LIGHTING 1 20 A 0.83
11 LIGHTING 1 20 A 0.86
10 LIGHTING 1 20 A 1.06
9 LIGHTING 1 20 A 1.28
8 LIGHTING 1 20 A 1.06
7 CF-4 3 20 A 13.00
6 CF-3 3 20 A 13.00
5 CF-2 3 20 A 13.00
4 CF-1 3 40 A 26.00
3 SITE CANOPY LIGHTING 1 20 A 0.17
2 SITE LIGHTING 1 20 A 0.98
1 N6GW 3 20 A 0.00
CKT Circuit Description # of
Poles Trip Rating (A) Load Remarks
Supply From: Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB MCB Rating: 600
Location: ELECT G12 Mounting: SURFACE Distribution / Phase / Wires: 480/277 Wye K.A.I.C. Rating: Bus Rating: 800 A
SWITCHBOARD: N6DP
Switchboard Notes:
Other 1200 VA 100.00% 1200 VA Total Demand Current (A): 58 A
Motor 16076 VA 107.01% 17203 VA Total Connected Demand (KVA): 20.73 kVA
HVAC 0 VA 0.00% 0 VA Total Conn. Load: 19.60 kVA
EQUIPMENT 2324 VA 100.00% 2324 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
12 Space 1 -- --
11 Space 1 -- --
10 Space 1 -- --
9 Space 1 -- --
8 Space 1 -- --
7 Space 1 -- --
6 Space 1 -- --
5 2Q6GM-2 3 20 A 17.60
4 2Q6G 3 20 A 0.50
3 MAIN 3 20 A 0.50
2 ELEVATOR 2 3 20 A 0.50
1 ELEVATOR 1 3 20 A 0.50
CKT Circuit Description # of
Poles Trip Rating (A) Load (KVA) Remarks
Supply From: TQ6GM Enclosure: TYPE 1 Max Height Busing: Yes Mains Type: MCB MCB Rating: 800 A
Location: ELECT G03 Mounting: SURFACE Distribution / Phase / Wires: 120/208 Wye K.A.I.C. Rating: Bus Rating: 800 A
SWITCHBOARD: 2Q6GM-1
7CABLE PENETRATION OF FIREBARRIER
NOTES:
WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED
CABLES - MAX 4" DIAM TIGHT BUNDLE OF CABLES CENTERED IN CIRCULAR CUTOUTS IN GYPSUM WALLBOARD AND RIGIDLY
USED:
A. MAX 350 KCMIL SINGLE CONDUCTOR POWER CABLES; CROSS-LINKED POLYETHYLENE (XLPE) OR
POLYVINYL CHLORIDE (PVC) INSULATION.
B. MAX 7/C NO. 12 AWG CABLES; PVC INSULATION AND JACKET.
C. MAX 3/C NO. 2/0 AWG MULTICONDUCTOR POWER AND CONTROL CABLES; XLPE OR PVC INSULATION, XLPE OR PVC JACKET.
D. MAX 200 PAIR NO. 24 AWG TELECOMMUNICATION CABLES; PVC INSULATION AND JACKET.
E. MAX 6/94 FIBER OPTIC CABLE; PVC INSULATION AND JACKET.
FILL VOID OR CAVITY MATERIAL - WRAP STRIP BEARING THE UL CLASSIFICATION MARKING -NOM 1/4" THICK INTUMESCENT
WITH STEEL WRIE TIE AND SLID INTO ANNULAR SPACE APPROX 1-1/4" SUCH THAT APPROX 3/4" OF THE WRAP STRIP
FILL VOID OR CAVITY MATERIAL - CAULK OR PUTTY BEARING THE UL CLASSIFICATION MARKING - MIN 1/4" DIAM
INTO THE INTERSTICES OF THE CABLE BUNDLE TO THE MAX EXTENT POSSIBLE WITHIN THE
CONFINES OF THE WRAP STRIP ON EACH SIDE OF THE WALL ASSEMBLY.
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION
DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY.
SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF COPPER CONDUCTOR
CABLES MAY BE
ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN NOM 2" WIDE STRIPS. NOM 2" WIDE STRIP
TIGHTLY WRAPPED AROUND CABLE BUNDLE (FOIL SIDE OUT) WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND
PROTRUDES FROM THE WALL SURFACE ON EACH SIDE OF THE ASSEMBLY.
CONTINUOUS BEAD OF CAULK OR PUTTY APPLIED TO THE WRAP STRIP/WALL INTERFACE AND TO THE EXPOSED EDGE OF THE
WRAP STRIP APPROX 3/4" FROM THE WALL SURFACE ON EACH SIDE OF THE WALL ASSEMBLY. CAULK OR PUTTY TO BE FORCED
CONDUIT PENETRATION OF FIREBARRIER
WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES
WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY.
CONDUIT - NOM 4" DIA OR SMALLER STEEL ELECTRICAL METALLIC TUBING. A MAX OF ONE CONDUIT IS
PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND
TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSIFICATION MARKING INSTALLED
TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN
1/4" DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT ITS EGRESS FROM THE WALL. CAULK
INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP
SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS
SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON
THE TYPE OR SIZE OF THE CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS
INSTALLED, AS TABULATED BELOW:
EQUIPMENT NAMEPLATE
AHU-X
AHU-X
2COVERPLATES & NAMEPLATES 1
CVTU
FUSE
INTERIOR
SWITCH
SWITCH
No Scale
SEPARATION OF DEVICES IN A MULTI-GANG BOX 4
UL SYSTEM NO. W-L-3030
UL SYSTEM NO. W-L-1001
NOTES:
MAX CONDUIT
DIAM, IN.
F RATING, HR.
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING, HR.
0, 1 OR 2
3 OR 4
ANNULAR SPACE,
IN.
0 TO 3/16
1/4 TO 1/2
0 TO 1-1/2
1/4 TO 1/2
3/16 TO 3/8
TYPICAL 120/208V PANELBOARD
TYPICAL 277/480V PANELBOARD
No Scale
PANELBOARD NAMEPLATES
PANEL "XXXX"
120/208V, 3ᶲ , 4W
FED FROM PANEL "XXXX", VIA T-XXX
NORMAL BRANCH
FED FROM PANEL "XXXX"
277/480V, 3ᶲ , 4W
PANEL "XXX"
1/2" HIGH LETTERING FOR
PANELBOARD NAME
1…