This document package includes construction drawings and specifications for an upgrade project at a Department of Veterans Affairs medical facility. The project scope involves renovating and expanding sterile processing services in an existing building. Drawings show demolition plans, new construction plans, schedules, details and notes. Mechanical drawings depict HVAC, plumbing and piping demolition and new layouts. Specifications call for work including removing existing equipment and ductwork, filling floor penetrations, capping utilities, and preparing surfaces for new connections. The project aims to modernize sterile processing facilities while the hospital remains operational.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC BASIS OF DESIGN
SUMMER OUTDOOR
DESIGN DB (°F) 85 STATE COUNTY CLIMATE ZONE
SUMMER OUTDOOR
DESIGN WB (°F) 65 WASHINGTON KING 4C
WINTER OUTDOOR
DESIGN DB (°F) 25 DESIGN ALTITUDE 400 FT
CONNECT NEW TO EXISTING
SHEET NUMBER
SECTION DESIGNATION
BLANKED FOR 1-WAY
BLANKED FOR 2-WAY
BLANKED FOR 3-WAY
STANDARD 4-WAY
SELF-CLOSING FIRE DAMPER
AUTOMATIC SMOKE DAMPER
COMBINATION SMOKE/FIRE
ROOF EXHAUST FAN SHOWN
ROOF EXHAUST FAN SHOWN
AUTOMATIC CONTROL DAMPER
RISE/DROP
TAKE-OFFSUPPLY
CEILING
DUCT MTD.
DIFF/GRILLE
BULLHEAD SPLIT
TAKEOFF
DIFF/GRILLE
TO
OR
HARD
ELBOW
SUPPLY DUCT DOWN
SUPPLY DUCT UP
OR R
w
SINGLE LINE
RETURN/EXHAUST
CONVERGE
BULLHEAD
SUPPLY/RETURN/
RISE OR DROP
SUPPLY/RETURN
RETURN/EXHAUST
TAKE-OFF
90°F
TAP
45°F
TAP
/EXHAUST
HORIZONTAL
DUCT DOWN
EXHAUST
OFFSET
RING
DUCT
RISE/DROP
DUCT
FLEXIBLE
1/4"x1/4" WMS
OPEN END
DUCT W/
RETURN/EXHAUST
ACOUSTICALLY
LINED DUCT
CEILING
DUCT MTD.
DIFF/GRILLE
DUCT UP
DOUBLE LINE
DUCTWORK SYMBOLS
REG./GRILLE
DUCT MTD.
SIDEWALL
BD
LD MF'R
BOOT BY
VD VD
UC 1/2"
LVDR 1.5 SF
OR
SUPPLY AIR FLOW
BACKDRAFT DAMPER
UNDERCUT DOOR
LOUVERED DOOR
SGD
AVS
ACD
SFD
SD
FD
VD
VD VD
SLIDE GATE DAMPER
AIR VOLUME TRAVERSE STATION
MANUAL VOLUME DAMPER
W/ACCESS DOOR
W/ACCESS DOOR
W/ACCESS DOOR
DAMPER W/ACCESS DOOR
BLOW SUPPLY DIFFUSER
BLOW SUPPLY DIFFUSER
BLOW SUPPLY DIFFUSER
BLOW SUPPLY DIFFUSER
ON FLOOR PLAN
ON ROOF
ADDITIONAL SYMBOLS
EQUIPMENT
DUCTWORK OR
TO BE REMOVED
FIRE DAMPER
M MOTORIZED DAMPER POINT OF DEMOLITION
TURNING VANES
DUCT UP
SINGLE LINE DOUBLE LINE
TEMPERATURE SENSOR OR
THERMOSTAT
RETURN OR EXHAUST AIR
FLOW DIRECTION
SUPPLY SIDEWALL
LINEAR DIFFUSER
(W/SHEET METAL
PLENUM W/1"
LINING & BRANCH
CONN FOR EVERY
4' OF LENGTH)
SUPPLY CEILING
LINEAR DIFFUSER
(W/SHEET METAL
PLENUM W/1"
LINING & BRANCH
CONN FOR EVERY
4' OF LENGTH)
STANDARD RADIUS
ELBOW (R = W)
SUPPLY/RETURN
/EXHAUST
XxX [X] XXX,XxX,XX°
1 2 3 4 5
NECK SIZE (IN)
AIR OUTLET TYPE
AIRFLOW (CFM)
SIZE (IN) OF CONNECTING BRANCH DUCT
ANGLE OF THROW, DOWN FROM HORIZONTAL (°)
AIR OUTLET CALLOUT
BALL VALVE
UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)
WATER BALANCING VALVE
AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR
PIPE BREAK (SINGLE LINE)
RISE (SINGLE LINE - PLAN VIEW)
DROP (SINGLE LINE - PLAN VIEW)
BOTTOM TAKEOFF
TOP TAKEOFF
BLIND FLANGE
END CAP
BUTTERFLY VALVE
GATE VALVE THREADED
CHECK VALVE
GEOTHERMAL HEATING SUPPLY
GEOTHERMAL HEATING RETURN
PIPING LEGEND
INVERTED BUCKET TRAP
GEHR
GEHS
GATE VALVE FLANGED
GATE VALVE WITH 3/4" HOSE ADAPTER
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
SAFETY RELIEF VALVE
PRESSURE GAGE
THERMOMETER
FLOAT AND THERMOSTAT TRAP
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
ECCENTRIC REDUCER
DIRECTION OF PIPE PITCH (DOWN)
T
PROJECT NOTES
1. VA WILL SHUT DOWN EXISTING UTILITY SYSTEM AS NECESSARY FOR CONTRACTOR TO PERFORM
REQUIRED WORK. CONTRACTOR IS RESPONSIBLE FOR DRAINING EXISTING WET SYSTEMS, SUCH AS
WATER, CHILLED WATER, HEATING WATER ETC. AS REQUIRED TO ACCOMPLISH NEW WORK.
CONTRACTOR IS ALSO RESPONSIBLE FOR RE-FILLING SYSTEMS INCLUDING ADDING CHEMICAL AS REQUIRED. IT IS ACCEPTABLE TO SALVAGE EXISTING TREATED WATER IN CLEAN STORAGE CONTAINERS APPROVED BY THE VA, AND RE-INJECT IT INTO THE SYSTEM UPON COMPLETION OF WORK. ANY TREATED
WATER NOT RE-INJECTED IS TO BE PROPERLY DISPOSED OF.
MECHANICAL SHEET INDEX
M-001 NOTES, SYMBOLS, & LEGENDS - MECHANICAL
MD401 BASEMENT MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL
MD402 BASEMENT DEMOLITION PLAN - SOUTH - MECHANICAL
MD403 BASEMENT DEMOLITION PLAN - NORTH - MECHANICAL
MD404 BASEMENT WAREHOUSE DEMOLITION PLAN - MECHANICAL
MD405 BASEMENT INTERSTITIAL DEMOLITION PLAN - SOUTH - MECHANICAL
MD406 BASEMENT INTERSTITIAL DEMOLITION PLAN - NORTH - MECHANICAL
MD407 BASEMENT WAREHOUSE INTERSTITIAL DEMOLITION PLAN - MECHANICAL
MD408 BASEMENT MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL PIPING
MD409 BASEMENT INTERSTITIAL DEMOLITION PLAN - SOUTH - MECHANICAL PIPING
MD410 BASEMENT INTERSTITIAL DEMOLITION PLAN - NORTH - MECHANICAL PIPING
MD411 BASEMENT WAREHOUSE INTERSTITIAL DEMOLITION PLAN - MECHANICAL PIPING
MH412 BASEMENT MECHANICAL ROOM - MECHANICAL
MH413 BASEMENT FLOOR PLAN - SOUTH - MECHANICAL
MH414 BASEMENT FLOOR PLAN - NORTH - MECHANICAL
MH415 BASEMENT WAREHOUSE FLOOR PLAN - MECHANICAL
MH416 BASEMENT INTERSTITIAL SPACE - SOUTH - MECHANICAL
MH417 BASEMENT INTERSTITIAL SPACE - NORTH - MECHANICAL
MH418 BASEMENT WAREHOUSE INTERSTITIAL SPACE - MECHANICAL
MP419 BASEMENT MECHANICAL ROOM - MECHANICAL PIPING
MP420 BASEMENT FLOOR PLAN - SOUTH - MECHANICAL PIPING
MP421 BASEMENT FLOOR PLAN - NORTH - MECHANICAL PIPING
MP422 BASEMENT INTERSTITIAL SPACE - SOUTH - MECHANICAL PIPING
MP423 BASEMENT INTERSTITIAL SPACE - NORTH - MECHANICAL PIPING
MP424 BASEMENT WAREHOUSE INTERSTITIAL SPACE - MECHANICAL PIPING
MH425 PRESSURIZATION MAP - SOUTH - MECHANICAL
MH426 PRESSURIZATION MAP - NORTH - MECHANICAL
M-501 DETAILS - MECHANICAL
M-502 DETAILS - MECHANICAL
MI503 CONTROLS - MECHANICAL
M-601 SCHEDULES - MECHANICAL
M-602 SCHEDULES - MECHANICAL
MD701 SWING SPACE DEMOLITION PLAN - MECHANICAL
MD702 SWING SPACE INTERSTITIAL DEMOLITION PLAN - MECHANICAL
MH703 SWING SPACE FLOOR PLAN - MECHANICAL
MH704 SWING SPACE INTERSTITIAL SPACE - MECHANICAL
ABBREVIATIONS
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
A AIR OR COMPRESSED AIR A/C AIR CONDITIONING
AD ACCESS DOOR ADA AMERICAN DISABILITIES ACT
AF AIR FOIL ADJ ADJUST, ADJUSTABLE, ADJACENT
AFF ABOVE FINISHED FLOOR AGA AMERICAN GAS ASSOCIATION
AHU AIR HANDLING UNIT AMB AMBIENT
AMP AMPERE, AMPACITY ANCH ANCHOR
AP ACCESS PANEL APPD APPROVED
APD AIR PRESSURE DROP ARCH ARCHITECT, ARCHITECTURAL
AS AIR STREAM ATC AUTOMATIC TEMPERATURE CONTROL
AVG AVERAGE ATM ATMOSPHERE
BDD BACK DRAFT DAMPER BTTM BOTTOM
BHP BREAK HORSE POWER BI BACKWARD INCLINED
BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR
BV BUTTERFLY VALVE BOD BOTTOM OF DUCT
CENT CENTER OR CENTRIFUGAL CAP CAPACITY
CFM CUBIC FEET PER MINUTE CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY CI CAST IRON
CF CUBIC FEET CLG CEILING
CLR CLEAR CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE CO CARBON MONOXIDE
COMB COMBINATION, COMBUSTION CO2 CARBON DIOXIDE
CV CHECK VALVE CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY CT COOLING TOWER
CONN CONNECTION OR CONNECT CTBD COOLING TOWER BLOW DOWN
CUH CABINET UNIT HEATER D DRAIN
DB DRY BULB DEG DEGREE
DDC DIRECT DIGITAL CONTROL DIA DIAMETER
DP DIFFERENTIAL PRESSURE DPS DIFFERENTIAL PRESSURE SWITCH
DET DETAIL DEMO DEMOLITION
DIA DIAMETER DF DRINKING FOUNTAIN
DIM DIMENSION DIFF DIFFUSER
DN DOWN DIV DIVISION
DS DOWNSPOUT, DISCONNECT SWITCH,
DOOR SWITCH DPR DAMPER
DX DIRECT EXPANSION DWG DRAWING
EA EACH OR EXHAUST AIR ELEV ELEVATOR, ELEVATION
ELEC ELECTRICAL ENCL ENCLOSURE
ENG ENGINEER EPDM ETHYLENE PROPYLENE DIENE MONOMER
EQ EQUAL EQUIP EQUIPMENT
EWH ELECTRIC WALL HEATER EXH EXHAUST
EXIST EXISTING EAHU EXHAUST AIR HANDLING UNIT
EAT ENTERING AIR TEMPERATURE EF EXHAUST FAN
EMER EMERGENCY EMS ENERGY MANAGEMENT SYSTEM
ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT FA FREE AREA
FC FLEXIBLE CONNECTION FCU FAN
FD FIRE DAMPER OR FIRE DEPARTMENT FLA FULL LOAD AMPS
FPM FEET PER MINUTE FS FLOW SWITCH
FT FEET FTR FIN TUBE RADIATION
G GAS GA GAUGE
GAL GALLONS GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE HB HOSE BIB
HD HEAD HP HORSEPOWER
HR HOUR HRU HEAT RECOVERY UNIT
HTG HEATING HZ HERTZ (CYCLES PER MINUTE)
ID INSIDE DIAMETER IN INCHES
KW KILOWATT LAT LEAVING AIR TEMPERATURE
LF LINEAR FEET LD LINEAR DIFFUSER
LRA LOCKED ROTOR AMPS LVR LOUVER
LWT LEAVING WATER TEMPERATURE MAX MAXIMUM
MBH 1000 BTU MCA MINIMUM CIRCUIT AMPS
MUA MAKE UP AIR MOCP MAXIMUM OVER CURRENT PROTECTION
NC NOISE CRITERIA NO NORMALLY OPEN
NOM NOMINAL OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE OC ON CENTER
OD OUTSIDE DIAMETER ODP OPEN DRIP PROOF
OV OUTLET VELOCITY PCF POUNDS PER CUBIC FEET
PD PRESSURE DROP PH PHASE
PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH
PSIA POUND PER SQUARE INCH - ABSOLUTE PSID POUND PER SQUARE INCH -
DIFFERENTIAL
PSIG POUND PER SQUARE INCH - GAUGE PVC POLYVINYL CHLORIDE
R RADIUS RA RETURN AIR
RET RETURN RH RELATIVE HUMIDITY
RLF RELIEF RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT SA SUPPLY AIR
SD SMOKE DETECTOR SE SMOKE EXHAUST
SEN SENSIBLE SFD COMBINATION SMOKE/FIRE DAMPER
SHC SENSIBLE HEAT CAPACITY SP STATIC PRESSURE
SF SQUARE FEET SS STAINLESS STEEL
SUP SUPPLY T TEMPERATURE OR THERMOSTAT
TEFC TOTALLY CLOSED FAN COOLED TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT
TYP TYPICAL UC UNDERCUT DOOR
V VOLTS VAV VARIABLE AIR VOLUME
VEL VELOCITY VFD VARIABLE FREQUENCY DRIVE
WB WET BULB TEMPERATURE WC WATER COLUMN
WG WATER GAUGE WPD WATER PRESSURE DROP
WTD WATER TEMPERATURE DIFFERENCE
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
M-001
LEGENDS, SYMBOLS,
ABBREVIATIONS, & NOTES -
MECHANICAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AIR
FLOWAD
AD
FAN
INLINE
NOTE: REFER TO CONSTRUCTION SPECIFICATIONS FOR MATERIALS,
EQUIPMENT, AND INSTALLATION REQUIREMENTS.
24"X24" ACCESS DOOR
(BOTH SIDES) FOR ALL FANS
WITH DUCT CONNECTIONS LARGER
THAN 36" (ROUND OR SQUARE)
WASHER (TYP.)
3/16" THICK FRAME W/EYELET
WELDED TO FAN HOUSING,
PRIMED AND PAINTED (TYP.)
2"X2"X1/8" ANGLE
REINFORCEMENT
CONN TO DUCT
FLEX CONNECTION (TYP)
VIBRATION ISOLATOR
SPRING ASSEMBLY
SUPPORT ROD
HUNG FROM CEILING
SUPPORT (TYP)
NUT (TYP)
ROD
RUBBER
GROMMET
(TYP.)
ANCHOR DUCT
TO PREVENT
LATERAL
MOVEMENT
EXHAUST FAN DETAIL
SCALE: NOT TO SCALE
EXIST MASONRY
WALL
PIPE SLEEVE
PIPE INSULATION
PIPE
MINERAL WOOL
INSIDEOUTSIDE
CAULK (TYP)
CAULK (TYP)
PIPE INSULATION
WITH JACKET
PIPE THRU WALL
SCALE: NOT TO SCALE
NOTE:
1.
2.
3.
4.
5.
6.
7.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR
SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR
FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER
FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH
ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND
MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3 (NOTE
FASTENED TO PARTITION)
ACCESS
PANEL
NOTE 5
[2 5m m
TYPICAL TERMINAL UNIT
SCALE: NOT TO SCALE
BY-PASS CHEMICAL SHOT FEEDER
SCALE: NOT TO SCALE
FLOOR SUPPORTED IN-LINE PUMP
SCALE: NOT TO SCALE
HEATING COIL PIPING DETAIL
SCALE: NOT TO SCALE
WASHER VENTILATION CONNECTION DETAIL
SCALE: NOT TO SCALE
SECTION THRU FIRE DAMPER INSTALLATION
SCALE: NOT TO SCALE
MIN 4" TALL LIFTERS
CONDENSING UNIT (CU)
ROUND TUBING
4"CONCRETE PAD
3/8" Ø POWERS CARBON STEEL
WEDGE BOLT CONCRETE
ANCHOR WITH 1" Ø MIN
WASHER, 2-1/2" EMBEDMENT
AND 6" MIN EDGE DISTANCE
INSTALL LINE SET PER
MANUFACTURE
RECOMMENDATIONS.
RS AND RL LINES TO
DUCTLESS SPLIT
90° SWEEP
LS
PROVIDE ISOLATION
VALVES ON EACH SIDE
OF BRAIDED FLEXIBLE
REFRIGERANT LINE
MINIMUM 12"
BRAIDED
FLEXIBLE
REFRIGERANT
LINE
HEAT PUMP UNIT ROOF MOUNT SUPPORT DETAIL
SCALE: NOT TO SCALE
MPS
STEAM CONDENSATE
F&T
TRAP
STERILIZER STEAM PIPING
SCALE: NOT TO SCALE
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON
VIBRATION ISOLATOR UNITS, THE RUNOUT PIPING FOR
CONNECTIONS TO COIL SHALL BE INSTALLED WITH
SWING JOINTS TO ALLOW FOR THE VIBRATION.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT
WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS
OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING
OF FILTERS, VALVES, OR EQUIPMENT.
3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A
BANK OF TWO OR MORE HIGH. ALSO PROVIDE SEPARATE
VACUUM BREAKER FOR EACH COIL.
4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO
TRAPS REQUIRED WHEN CONDENSATE LOAD IS 2400
KG/HR [5,000 LBS/HR] OR GREATER.
5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END.
REHEAT COIL MAY HAVE SUPPLY & RETURN PIPES FROM
OPPOSITE ENDS.
PIPE HANGER
SHALL SUPPORT
PIPING
INDEPENDENT
OF COIL (TYP.)
PITCH COIL DOWN
8mm [1/4"] PER FOOT
TO CONDENSATE
OUTLET
FULL SIZE
TAPPING
PRESSURE
GAGE
SCALE POCKET
SEE
NOTE
NO. 4 STEAM CONDENSATE
RETURN
15mm [1/2"] CHECK
VALVE VACUUM
BREAKER
INCREASER,
IF
REQUIRED
REDUCER,
IF REQUIRED
0m m [6
" M
IN
0m m [1
2" M
IN
STEAM SUPPLY
STEAM - PIPING CONNECTIONS
SCALE: NOT TO SCALE
SLOPE CR-30 AT 1" PER 40'
SLOPE S-30 AT 1" PER 40'
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
M-501
DETAILS - MECHANICAL
AutoCAD SHX Text
STEAM EQUIPMENT
AutoCAD SHX Text
6" DIRT TRAP
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
NOTE:
ALL DRIP POINTS ON STEAM MAINS
SHALL BE PROVIDED WITH A 300mm
[12"] MINIMUM HIGH DRIP LEG FROM
BOTTOM OF STEAM MAIN TO TRAP
INLET. DRIP LEG SHALL HAVE 150mm
[6"] SCALE POCKET BELOW TRAP
INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS
TRAP
FLOAT AND THERMOSTATIC
TRAP. SEE PLANS, AND
SCHEDULES
DIELECTRIC FITTING
WHERE RETURN IS
COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE
LEVEL WITH TRAP OR IN VERTICAL PLANE
& BELOW TRAP PROVIDE BYPASS PIPING
FOR ALL TRAPS 25mm [1"] AND LARGER. 30
0m m
0m m
DRIP LEG OR EQUIPMENT
CONNECTION. MAKE THE
SAME SIZE AS THE SUPPLY
MAIN OR EQUIPMENT
CONNECTION. SEE NOTE 1
[1 2"
M
IN
[6
" M
IN
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
25mm [1"]
GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" [15mm]
BALL VALVE
1/4" [8mm]
COPPER TUBING
1/2" [15mm] x 4" [100mm]
NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC)
SCALE: NOT TO SCALE
FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
SCALE: NOT TO SCALE
FCU PIPING DETAIL
SCALE: NOT TO SCALE
SINGLE COIL
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN
COIL IS
NOT
SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL
SUPPORT
PIPING INDEPENDENT OF
COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT
WHEN COIL IS
NOT
SELF-VENTING
TEST
PLUG
(TYP.)
PIPE HANGER SHALL
SUPPORT
PIPING INDEPENDENT OF
COIL
WATER COIL
REDUCER, IF REQUIRED
FLOW ELEMENT
DRAIN WHEN COIL
IS NOT
SELF-DRAINING
DRAIN
DOUBLE COIL
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR
EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 100mm [4"]Ø PIPE & SMALLER. TYPE "H-P" FOR 125mm [5"]Ø PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR
EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM
AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.
FE
MV
MV
MV
MV
MV
MV
FE
TI
TI
TEMPERATURE
INDICATION TO
ECC SEE
CONTROL
DIAGRAM
MV
DESIGNER'S NOTE:
1. CONSIDER WHETHER WATER
TEMPERATURE SENSOR AND FLOW
ELEMENT ARE NECESSARY ON EVERY
COIL, AS THIS CAN BECOME EXPENSIVE.
OTHER CONTROL
DEVICES (i.e., AIR SIDE TEMPERATURES
AND AIR FLOW) MAY PROVIDE EQUALLY
BENEFICIAL INFORMATION FOR
TROUBLESHOOTING.
2. BALANCING VALVES MAYBE OMITTED IF
REVERSE PIPING PROVIDED.
CALIBRATED
BALANCING VALVE
(TYP.)
CONDENSATE
TO DRAIN
MV
MANUAL
AIR
VENT
TO BUILDING
LOAD
INVERTED BUCKET
TRAP ASSEMBLY
WELDED
TEE
STEAM PIPE
300mm[12"]
150mm[6"] SCHEDULE 80 STEEL PIPE
25mm [1"] GATE VALVE
WELDED TEE
END OF STEAM LINE DRIP TRAP
SCALE: NOT TO SCALE
WATER COILS - PIPING CONNECTIONS
SCALE: NOT TO SCALE
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
M-502
DETAILS - MECHANICAL
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
TU
11-1
TU
11-2
TU
11-3
TU
11-4
TU
11-5
TU
11-6
TU
11-7
TU
11-8
TU
11-9
TU
11-10
TU
11-11
TU
11-12
TU
11-13
TU
11-14
TU
11-15
TU
11-16
SINGLE DUCT REHEAT TERMINAL UNIT SCHEDULE
TAG MANUFACTURER
& MODEL TYPE SERVES VALVE
CONNECTION
SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL
NOTES
INLET OUTLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI
TITUS DESV CRV OFFICE B105 2-WAY 05 12X8 80 80 0.5 0.25 0.02 - 15 80 3.0 55 90 160 140 0.01 0.3 0.36 1 10 1, 2, 3, 4, 5
TITUS DESV CRV OFFICE B104 2-WAY 06 12X8 145 145 0.5 0.25 0.06 - 13 145 5.4 55 90 160 140 0.04 0.5 1.94 2 10 1, 2, 3, 4, 5
TITUS DESV CRV OFFICE B106 2-WAY 06 12X8 100 100 0.5 0.25 0.03 - - 100 3.7 55 90 160 140 0.01 0.4 0.1 2 10 1, 2, 3, 4, 5
TITUS DESV CRV OFFICE B107 2-WAY 05 12X8 80 80 0.5 0.25 0.02 - 15 80 3.0 55 90 160 140 0.01 0.3 0.1 1 10 1, 2, 3, 4, 5
TITUS DESV CRV STERILE
COOLDOWN B108 2-WAY 40 38X18 2080 2080 0.5 0.25 0.15 29 22 2080 78.6 55 90 160 140 0.11 7.9 0.25 2 10 1, 2, 3, 4, 5
TITUS DESV CRV LOW TEMP B136 2-WAY 14 20X17.5 775 775 0.5 0.25 0.07 13 13 775 29.3 55 90 160 140 0.03 2.9 0.15 2 10 1, 2, 3, 4, 5
TITUS DESV CRV PREP AND PACK
B126 2-WAY 40 38X18 1750 1750 0.5 0.25 0.09 24 18 1750 66.1 55 90 160 140 0.04 6.6 0.91 2 10 1, 2, 3, 4, 5
TITUS DESV CRV PREP AND PACK
B126 2-WAY 40 38X18 1750 1750 0.5 0.25 0.09 24 18 1750 66.1 55 90 160 140 0.08 6.6 0.93 2 10 1, 2, 3, 4, 5
TITUS DESV CRV BREAK & STAFF
LOCKERS 2-WAY 14 20X17.5 905 900 0.5 0.25 0.09 14 14 905 34.2 55 90 160 140 0.08 3.4 0.93 2 10 1, 2, 3, 4, 5
TITUS DESV CRV STERILE
STORAGE B110 2-WAY 16 24X18 1290 1290 0.5 0.25 0.14 12 11 1290 48.7 55 90 160 140 0.16 4.9 0.39 2 10 1, 2, 3, 4, 5
TITUS DESV CRV STERILE
STORAGE B110 2-WAY 14 20X17.5 950 950 0.5 0.25 0.09 14 14 950 35.9 55 90 160 140 0.13 3.6 0.33 2 10 1, 2, 3, 4, 5
TITUS DESV CRV CLEAN SCOPE
STORAGE B124 2-WAY 06 12X8 120 120 0.5 0.25 0.03 - 10 120 4.5 55 90 160 140 0.03 0.5 3.52 2 10 1, 2, 3, 4, 5
TITUS DESV CRV COORD OFFICE
B115 3 - WAY 06 12X8 110 110 0.5 0.25 0.03 - 10 110 4.1 55 90 160 140 0.02 0.4 0.1 2 10 1, 2, 3, 4, 5
TITUS DESV CRV STAFF RR B-119
AND B-120 2-WAY 12 16X15 430 430 0.5 0.25 0.06 10 17 430 16.2 55 90 160 140 0.02 1.6 0.16 2 10 1, 2, 3, 4, 5
TITUS DESV CRV IMPLANT B111 2-WAY 10 14X12.5 240 240 0.5 0.25 0.05 16 15 240 9.0 55 90 160 140 0.06 0.9 0.34 2 10 1, 2, 3, 4, 5
TITUS DESV CRV BREAKDOWN
B114 2-WAY 10 14X12.5 180 180 0.5 0.25 0.05 16 15 180 6.8 55 90 160 140 0.05 0.7 0.72 2 10 1, 2, 3, 4, 5
TITUS DESV CRV CORRIDOR
CB-18B 2-WAY 12 16X15 600 600 0.5 0.25 0.06 10 17 600 22.6 55 90 160 140 0.02 2.3 0.09 2 10 1, 2, 3, 4, 5
TITUS DESV CRV DETERGENT
ROOM B117 2-WAY 10 14X12.5 250 250 0.5 0.25 0.05 16 15 250 9.4 55 90 160 140 0.02 0.9 0.09 2 10 1, 2, 3, 4, 5
TITUS DESV CRV ELECTRICAL
CB15K 2-WAY 12 16X15 450 450 0.5 0.25 0.06 10 17 450 17.0 55 90 160 140 0.03 1.7 0.16 2 10 1, 2, 3, 4, 5
TU
11-17
TU
11-18
TU
11-19
NOTES:
1. (CVR) CONSTANT AIR VOLUME TERMINAL UNITS WITH HOT WATER COIL REHEAT
2. DDC CONTROLS
3. PROVIDE LEFT OR RIGHT HAND COIL CONNECTION AND CONTROL BOX ACCESS AS
REQUIRED TO MATCH CONFIGURATION SHOWN ON PLANS.
4. SOUND LEVELS SHALL NOT EXCEED NC 25 (RADIATED OR DISCHARGE).
5. TERMINAL BOX SHALL BE CONSTRUCTED OF STAINLESS STEEL WITH NO EXPOSED
INSULATION ON THE AIR SIDE OF THE TERMINAL UNIT.
DUCTLESS SPLIT SYSTEM SCHEDULE
OUTDOOR HEAT PUMP INDOOR FAN COIL
EQUIP# MFR MODEL #
OPERATING
WEIGHT
(LBS)
SEER
COOLING
@ 95° F
(MBH)
HSPF
@ 47° F
HEATING
@ 4° F
(MBH)
ELECTRICAL
NOTES EQUIP# MFR MODEL # TYPE CFM SPEED
TOTAL
COOLING
@ 95° F
(MBH)
TOTAL
HEATING
@ 4° F
(MBH)
ELECTRICAL
NOTES
MCA MOCP VOLTS PHASE MCA / MOCP VOLTS PHASE
CARRIER 38MARB 24 145 21.5 25.9 12 29.1 25 35 208 1 1, 2, 3, 4 CARRIER 40MAH 24 HIGH WALL
HUNG 611 HIGH 25.9 29.1 POWERED BY OUTDOOR UNIT 5, 6, 7, 8
NOTES:
1. PROVIDE 3" ROOF PAD
2. ROUTE CONDENSATE LINE DOWN ONTO ROOF
3. PROVIDE LOW AMBIENT CONTROLS & CRANK CASE HEATER
4. PROVIDE REFRIGERANT LINE SET
5. PROVIDE FACTORY WALL MOUNTING HARDWARE
6. PROVIDE FACTORY WALL MOUNTED T-STAT.
7. PROVIDE SLIDE-IN AIR FILTER.
8. PROVIDE CONDENSATE DRAIN PUMP
HP
AC
11A
STEAM TRAP SCHEDULE
TAG SERVES LOCATION
CONDENSATE
LOAD (LBS/HR)
TRAP
SAFETY
FACTOR
MINIMUM
TRAP
CAPACITY
(LBS/HR)
DIFFERENTIAL
PRESSURE
(PSIG)
TYPE
CONNECTION
SIZE (INCH)
T-1 AC-11 STEAM
PRE-HEAT COIL
MECHANICAL
ROOM #3
BD-111
201 2 280 0.25 F&T 2-1/2
T-3 CART WASH SEE FLOOR
PLANS 10 2 280 0.25 F&T 3/4
T-4 WASHERS SEE FLOOR
PLANS 30 2 280 0.25 F&T 3/4
T-5 STERILIZERS SEE FLOOR
PLANS 38 2 280 0.25 F&T 3/4
AIR OUTLET SCHEDULE
TAG TYPE SERVICE MATERIAL MOUNTING PATTERN
BLADE
SPACING
(INCH)
BLADE
POSITION
BLADE
DEFLECTION NOTES
[1] MODULAR CORE CEILING
DIFFUSER SUPPLY STEEL LAY-IN 4-WAY
ADJUSTABLE N/A N/A N/A 1, 2, 3
[2] MODULAR CORE CEILING
DIFFUSER SUPPLY STEEL SURFACE 4-WAY
ADJUSTABLE N/A N/A N/A 1, 2
[3] SINGLE DEFLECTION FIXED
FACE GRILLE RETURN STEEL LAY-IN FIXED 3/4" FRONT
HORIZONTAL 35° 1, 2, 4
[4] SINGLE DEFLECTION FIXED
FACE GRILLE RETURN STEEL SURFACE FIXED 3/4" FRONT
HORIZONTAL 35° 1, 2
NOTES:
1. FINISH SHALL BE WHITE ANODIC ACRYLIC PAINT
2. PROVIDE SQUARE TO ROUND TRANSITION AS REQUIRED
3. PROVIDE 24"x24" PANEL FOR LAY-IN CEILING INSTALLATION AS REQUIRED (SEE ARCHITECTURAL PLANS FOR TBAR CEILING LOCATIONS)
4. PROVIDE FRAME WITH NO SCREW HOLES FOR INSTALLATION IN TBAR CEILING.
FAN COIL SCHEDULE
# MFG & MODEL LOCATION
SUPPLY FAN HYDRONIC COOLING COIL
NOTES
CFM
MIN
O.S.A.
CFM
E.S.P.
("W.C) HP RPM V/Ø FLA
SENSIBLE
CAPCAITY
(MBH)
EAT
(DB)
EAT
(WB)
LAT
(DB)
LAT
(WB)
EWT
(DB)
LWT
(DB) GPM
CARRIER 7.5 TON
MECHANICAL
ROOM #3
BD-111
3000 0 0.5 3 1009 460/3 4.4 92.9 80 67 51.9 51.6 45 55 27.6 1, 2, 3, 4, 5, 6
FC
GENERAL NOTES:
1. MINIMUM EFFICIENCY IS AT ARI STANDARD CONDITIONS.
2. ROUTE CONDENSATE DRAIN TO NEAREST DRAIN.
3. COOLING ONLY UNIT
4. PROVIDE FACTORY WALL MOUNTED T-STAT.
5. PROVIDE FULL ECONOMIZER
6. PROVIDE VFD FOR SPEED CONTROL
AIR HANDLING UNIT SCHEDULE
TAG MANUFACTURER
STANDARD
AIR FLOW
(CFM)
DESIGN
AIR FLOW
(CFM)
RETURN
AIR FLOW
(CFM)
MINIMUM
OSA
(CFM)
CHILLED WATER COOLING COIL HOT WATER HEATING COIL HEAT RECOVERY COIL SUPPLY FAN UNIT ELECTRICAL FILTERS
WEIGHT
(LBS) NOTES
TOTAL
(MBH)
SENS.
(MBH
EAT
DB/WB
(°F)
LAT
DB/WB
(°F)
COIL
ROW/FPI VELOCITY GPM
PD
(FT)
EWT/LWT
(DEG F)
SENS.
(MBH
EAT
(DB)
LAT
(DB)
COIL
ROW/FPI
VELOCITY
(FPM) GPM
PD
(FT)
TOTAL
(MBH)
SENS.
(MBH
EAT
DB/WB
(°F)
LAT
DB/WB
(°F)
COIL
ROW/FPI VELOCITY GPM
PD
(FT)
EWT/LWT
(DEG F)
TSP / ESP
(INCH) RPM MOTOR
BHP VOLT/PH
FLA
(PER FAN) PRE FINAL HEPA
NORTEK 16900 13240 0 13240 211.1 185.0 83/65 51.8 /
51.8 6/12 421.88 42 1.95 45/55 788.2 35 75.9 2 / 7 485 35 4.87 292 292 23 37.8 3/8 421.88 35 6.99 60.7/43.4 7.65 / 3.25 3600 (4) 7.4 480/3 9.4 MERV 8 MERV 11 99.97% 16900 1, 2, 3, 4, 5
AC
NOTES:
1. FAN WILL OPERATE AT CONSTANT VOLUME
2. PROVIDE SMOKE DETECTOR IN SUPPLY DUCT
3. PROVIDE VFD RATED MOTORS AND VFD ON SUPPLY FAN.
4. PROVIDE LIGHTS IN EACH ACCESS SECTION
5. AIR HANDLER UNIT TO BE DOUBLE WALL CONSTRUCTION PER VA STANDARDS
EXHAUST FAN SCHEDULE
TAG SERVICE LOCATION MANUF. FAN TYPE NUMBER
OF FANS
STANDARD
AIR FLOW
(CFM)
DESIGN
AIR
FLOW
(CFM)
TOTAL
SP (")
ESP
(") DRIVE RPM
SOUND DATA ELECTRICAL HEAT RECOVERY COIL
WEIGHT
(LBS) CONTROL NOTESSONES
IN/OUT
DBA
INLET
DBA
RAD. VOLT/PH
MOTOR BHP
(PER FAN)
FLA
(PER FAN)
TOTAL
(MBH)
SENS.
(MBH
EAT
DB/WB (°F)
LAT DB/WB
(°F)
COIL
ROW/FPI VELOCITY GPM PD (FT) EWT/LWT
(DEG F)
AC-11 EXHAUST MECHANICAL
ROOM #3 BD-111 NORTEK UTILITY 4 14210 13470 3.4 2 DIRECT 2212 16.8 / 22 68 70 460/3 6.12 8.1 292 292 70 / 46 50.7 / 36.1 8 / 10 421.88 35 9.26 43.4 / 60.7 10000 DDC 1, 2
EF
NOTES:
1. FAN WILL OPERATE AT CONSTANT VOLUME
2. PROVIDE VFD RATED MOTOR
(EXISTING) SINGLE DUCT REHEAT TERMINAL UNIT SCHEDULE
TAG MANUFACTURER
& MODEL TYPE SERVES
SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL
NOTES
INLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI
TITUS DESV CRV COORIDOR CB-14 10 320 320 0.5 0.25 0.05 16 15 320 12.1 55 90 160 140 0.02 1.2 0.09 2 10 1
TITUS DESV CRV COORIDOR CB-15 10 360 360 0.5 0.25 0.05 16 15 360 13.6 55 90 160 140 0.03 1.4 0.09 2 10 1
TITUS DESV CRV OFFICE BD106A 06 90 90 0.5 0.25 0.03 - - 90 3.4 55 90 160 140 0.01 0.3 0.1 2 10 1
TITUS DESV CRV OFFICE BD106B 06 180 180 0.5 0.25 0.06 - 13 180 6.8 55 90 160 140 0.03 0.7 0.1 2 10 1
TU
11-20
TU
11-21
TU
11-22
TU
11-23
NOTES:
1. TERMINAL UNIT TO BE RE-BALANCED TO CFM AIRFLOW AND GPM FLOW LISTED
FILTER RACK SCHEDULE
TAG MANUFACTURER /
MODEL TYPE CFM
INITIAL
ESP
FINAL
ESP
MEDIA
AREA
(SF)
SIZE
(INCHES) NOTES
FARR FILTRA 2000 FA
1561 HEPA FILTER HEPA 620 0.25 0.75 390 24 X 24 X
11.5 -
FR
DH
DH
DH
REHEAT WATER COIL SCHEDULE
TAG MANUFACTURER
& MODEL TYPE SERVES VALVE
CONNECTION
SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL
NOTES
INLET OUTLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI
VARITRANE VCWF ANTE B368B 2-WAY 08 08 200 200 0.5 0.25 0.05 16 15 200 7.6 55 90 160 140 0.04 0.76 0.34 2 10 1, 2, 3
VARITRANE VCWF VESTIBULE B367 2-WAY 08 08 200 200 0.5 0.25 0.05 16 15 200 7.6 55 90 160 140 0.04 0.76 0.34 2 10 1, 2, 3
VARITRANE VCWF SCOPE STORAGE
B368D 3 - WAY 08 08 220 220 0.5 0.25 0.05 16 15 220 8.3 55 90 160 140 0.04 0.83 0.34 2 10 1, 2, 3
1. PROVIDE TRANSFORMER FOR VALVES
2. DDC CONTROLS
3. PROVIDE LEFT OR RIGHT HAND COIL CONNECTION AS REQUIRED TO MATCH
CONFIGURATION SHOWN ON PLANS.
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
M-601
SCHEDULES - MECHANICAL
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
EXHAUST FAN SCHEDULE
# MFG MODEL SERVICE DRIVE HIGH
CFM
LOW
CFM
TSP (WG") FAN
RPM VFD
MOTOR
NOTES
HP VOLTS PHASE
GREENHECK QEID-12-100
WET
EXHAUST
SPS
DIRECT 4000 2350 1.75 3500 YES 3 480 3 1, 2, 3
GREENHECK SQ-130HP-VG SWING
SPACE DIRECT 1100 875 1.5 1900 NO 3/4 277 1 1, 3, 4, 5
EF
11A
GENERAL NOTES:
1. FAN WILL OPERATE AT CONSTANT VOLUME
2. PROVIDE VFD
FIRE AND SMOKE DAMPER SCHEDULE
TAG MANUFACTURER TYPE UL RATING
VELOCITY
RATING
(FPM)
BLADE POSITION
MAX
PRESSURE
DROP
(INCH WC)
APPLICATION NOTES
RUSKIN DYNAMIC FIRE
DAMPER 1-1/2 HOUR 3000
CURTAIN TYPE
OUT OF AIR
STREAM
0.03 VERTICAL /
HORIZONTAL 1, 2, 3
NOTES:
1. LEAKAGE CLASS I PER UL STANDARD 555S
2. PROVIDE SQUARE TO ROUND ADAPTOR AS REQUIRED
3. INTERLOCK FIRE DAMPER WITH FIRE ALARM SYSTEM
TEMPORARY PORTABLE AIR CONDITIONER UNIT
# MFR MODEL # CFM
COOLING
CAPACTIY
(MBH)
ELECTRICAL DUCT
SIZE (IN) EER NOTES
VOLT PHASE FLA MOCP
GLOBAL
INDUSTRIAL 292660 465 13.2 115 1 11.9 15 12 11 -
GLOBAL
INDUSTRIAL 292660 465 13.2 115 1 11.9 15 12 11 -
PAC
11A
PAC
11B
PUMP SCHEDULE
TAG MANUFACTURER
MODEL LOCATION SERVING TYPE FLUID
PERFORMANCE MOTOR
WEIGHT
(LBS) NOTESMAX
FLOW
(GPM)
MIN FLOW
(GPM)
HEAD
(FT. WC) PUMP EFF HP RPM VOLT/PH
ARMSTRONG
COMPASS
MECH RM
M.E.R. #13
HEAT
RECOVERY
COIL
IN-LINE WATER -
GLYCOL 35 35 15 66 1/6 1750 120/1 20 1, 2
ARMSTRONG
COMPASS
MECH RM
M.E.R. #13
HEAT
RECOVERY
COIL
IN-LINE WATER -
GLYCOL 35 35 15 66 1/6 1750 120/1 20 1, 2
NOTES:
1. 20% GLYCOL MIX
P 11A
P 11B
AIR SEPARATOR SCHEDULE
TAG MANUFACTURER
MODEL LOCATION SERVING
INLET
SIZE (IN)
FLOW
RATE
(GPM)
WEIGHT
(LBS) NOTES
SPIROVENT
VDT-200
MECH RM
M.E.R. #13
HEAT
RECOVERY 2 35 66 1
NOTES:
1. PROVIDE SEPARATOR WITH REMOVABLE HEAD CAPS FOR CLEANING
AS
EXPANSION TANK SCHEDULE
TAG MANUF /
MODEL LOCATION SERVING
ACCEPTABLE
VOLUME
(GALLON)
TANK
VOLUME
(GAL)
MIN / MAX
OPERATING
PRESSURE (PSI)
OPERATING
TEMP (°F) NOTES
AMTROL
AX-15V-DD
MECH RM
M.E.R. #13
HEAT
RECOVERY 3.2 8.6 12 / 54 40 - 70 1, 2
NOTES:
1. PROVIDE SEPARATOR WITH REMOVABLE HEAD CAPS FOR CLEANING
2. PROVIDE PRESSURE RELIEF VALVE AT 60 PSI
ET
SPECIAL EQUIPMENT CONNECTION SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER AND
CATALOG # QUANTITY
CONNECTIONS
UTILITY REQUIREMENTS
ESTIMATED RO
WATER USAGE PER
EQUIPMENT UNIT
GALLONS / HOUR
COMBINED
ESTIMATED RO
WATER USAGE
GALLONS / HOUR
COMBINED
ESTIMATED RO
WATER USAGE
(GPM)
NOTES
HW CW V W IW STEAM CD
RETURN RO AIR
VISION 1327 (QT.2) SIDE BY SIDE CART AND UTENSIL
WASHER/DISINFECTOR - SHARED SERVICE / DOUBLE DOOR / PIT
MOUNTED / COMMON SERVICE AREA JUNCTION PANELS
STERIS VISION 1327 1 1" 1" - - F.D. 1-1/2" 1-1/2" 3/4" 1/2"
HARDNESS: 50-80 PPM. PURE WATER
USAGE: 50 GAL INITIAL CYCLE, 14 GAL /
SEQUENTIAL CYCLES. MAX 28 GPM
112 112 1.9 1, 2, 7
AMSCO 50 REPROCESSING SINK - 3 BAY/120" LONG/HEIGHT
ADJUSTABLE/RIGHT TO LEFT WORK FLOW STERIS AMSCO 50 4 1/2" 1/2" - - F.S. - - 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER
USAGE: 2 GMP 15 60 1.0 1, 2, 8, 9
AMSCO 50 REPROCESSING SINK - 3 BAY/120" LONG/HEIGHT
ADJUSTABLE/LEFT TO RIGHT WORK FLOW STERIS AMSCO 50 2 1/2" 1/2" - - F.S. - - 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER
USAGE: 2 GMP 15 30 0.5 1, 2, 8, 9
AMSCO 7052HP SINGLE-CHAMBER WASHER/ DISINFECTOR - DOUBLE
DOOR/ STEAM HEAT/ ACU-RINSE/ VENTED/ OFFSET MOUNTED AMSCO 705HP 3 1/2" 1/2" - - F.D. 1/2" 1/2" 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER
USAGE: 12 GAL / CYCLE. 14 GPM 12 36 0.6 1, 2, 5, 6, 7
AMSCO 7052HP SINGLE-CHAMBER WASHER/DISINFECTOR - DOUBLE
DOOR/ STEAM HEAT/ ACU-RINSE/ VENTED/ OFFSET MOUNTED AMSCO 705HP 2 1/2" 1/2" - - F.D. 1/2" 1/2" 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER
USAGE: 12 GAL / CYCLE. 14 GPM 12 24 0.4 1, 2, 5, 6, 7
AMSCO EVOLUTION-NA MEDIUM STEAM STERILIZER -
26X37.5X66"(660X953X1676MM)(958L) DOUBLE
HINGED LR DOORS/ RECESSED 2 WALLS/ STEAM HEAT
AMSCO EVOLUTION
STEAM STERILIZER 4 - 3/4" - - F.D. 3/4" 3/4" - 1/4" - - - - -
ADVANTAGE PLUS ENDOSCOPE WASHER / DISINFECTOR MEDIVATORS
ADVANTAGE PLUS 2 1/2" - - - F.D. - - 1/2" 1/4" HARDNESS: 50-200 PPM. PURE WATER
USAGE: 11.5 GAL / CYCLE. 2.6 GPM 3 6 0.1 1, 2, 3, 4, 7
INNOWAVE PRO SONIC IRRIGATOR - 60 LUMEN CAPACITY/ 208-220
VOLT/3 PHASE, 18kW. CENTER OVER DRAIN.
INNOWAVE PRO SONIC
IRRIGATOR 4 3/4" 3/4" - 2-1/8" F.D. - - 3/4" 1/2" HARDNESS: 125 PPM. PURE WATER USAGE:
38 GAL / CYCLE. 8 GPM 25 100 1.7 PROVIDE ELIMINIZER
COMBO DRYER/FILTER
INNOWAVE UNITY ULTRASONIC IRRIGATOR INNOWAVE IRRIGATOR 1 3/4" 3/4" - 2-1/8" F.D. - - - - - - - - 1, 2
ESTIMATED TOTAL RO WATER
DEMAND (GPM) 6.1
NOTES:
1. PROVIDE UTILITY CONNECTIONS WITH SHUTOFF DISCONNECTS WITHIN 2'
OF UNIT PER MANUFACTURE RECOMMENDATIONS.
2. PROVIDE VACUUM BEAKERS ON SERVICE LINES PER MANUFACTURE
RECOMMENDATIONS.
3. PROVIDE 1 MICRON FILTER FOR TEMPERED WATER CONNECTION
4. PROVIDE THERMAL MIXING VALVE FOR WATER CONNECTION
5. PROVIDE 1/4"CA CONNECTION FROM WASHER SUPPLY AIR CONNECTION.
6. PROVIDE 3/4" DRAIN KIT FOR CONVEYERS (UP TO 4 CONVEYERS).
7. ROUTE EACH WET VENT CONDENSATE DRAIN TO NEAREST FLOOR DRAIN
8. PROVIDE PRESSURE REGULATOR FOR AIR GUN.
9. PROVIDE PRESSURE REDUCING VALVE FOR WATER GUN.
2A
2B
EF
9A
3. PROVIDE CORROSION RESISTANT COMPONENTS
4. PROVIDE SPEED CONTROL
5. ELECTRIC STARTER NOT REQUIRED WITH VARIGREEN SPEED
CONTROL MOTOR
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
M-602
SCHEDULES - MECHANICAL
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
SE
38'-0"
NW
SE
0'-0"
S 176'-7"
S 143'-3"
E 146'-6"
E 197'-4"
E 201'-0"
SE
76-0
SE
114-0
SE
152-0
SE
190-0
SE
179-4
NW
14-9
NW
3-6
SE
152-10
NE
380-0
NE
304-0
NE
342-0
SE
152-0
SE
190-0
SE
179-4
SE
152-10
SE
38'-0"
NW
SE
0'-0"
SE
76-0
SE
114-0
NW
14-9
NW
3-6
NE
383'-9"
NE
342-0
NE
304-0
UP
NE
421'-9"
NE
380-0 NE
383'-9"
SEE MD401 FOR DEMO WORK
IN MECHANICAL ROOM
SEE MD402 FOR DEMO
WORK IN THIS AREA
SEE MD403 FOR DEMO
WORK IN THIS AREA
REMOVE EXISTING CEILING GRILLES AND
DIFFUSERS IN THIS SPACE. CLEAN AND
PREPARE GRILLS TO BE REPLACED IN SAME
LOCATIONS AS BEFORE IN NEW CEILING.
SEE MD404 FOR DEMO
WORK IN THIS AREA
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
DEMO NOTES
KEY PLAN
LEGEND
MD101
BASEMENT DEMOLITION PLAN - OVERALL -
MECHANICAL
D & T
TRUE
NORTH
PROJECT
NORTH
NURSING
TOWER
AREA OF
RENOVATION
WORK
KEY PLAN:NTS
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION
WORK WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED
TO BE RETURNED TO THE OWNER, SHALL BECOME THE
PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF
ITEMS ON THE PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN
AND AROUND BUILDING DURING DEMOLITION. PREVENT
INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE
ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.
IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE
CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE
MEASURES TO PREVENT DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT
FIRST OBTAINING PERMISSION FROM THE UTILITY COMPANY
AND/OR OWNER. PROVIDE TEMPORARY SERVICES AS
REQUIRED.
5. REMOVE AND DISPOSE OF EXISTING MECHANICAL
EQUIPMENT AS SHOWN, UNLESS NOTED OTHERWISE.
COORDINATE WITH ARCHITECT, AREAS OF DEMOLITION
AROUND, ADJACENT, OR CONNECTED TO EXISTING
MECHANICAL EQUIPMENT THAT IS TO REMAIN.
TRUE
NORTH
PROJECT
NORTH
1/8" = 1'-0"1 BASEMENT DEMOLITION PLAN - OVERALL - MECHANICAL
EXISTING WORK (LIGHT)
DEMOLITION (DARK)
POINT OF DEMOLITION
DEMOLITION KEY
SPS
SWING
SPACE
WAREHOUSE
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
NE
342-0
NE
304-0
FLASH TANK100-CP-#6
20X4 TR
(HIGH) O.A.I. OPN'G
22X20 W/ WMS 3,300
(LOW)
O.A.I. OPN'G
44X44 W/ WMS
13,300
24X24 DN
AC-#11
22X20
FC
4"T & SD
36X18
36X18 TR
20X20
UV-#44
8X8
3A-#11
34X24 DN
MCC
EF-#11
24X18 DN
18X24 DN
18X24 24X16
EF-#44
14X60 TR
AFM-#11-B
AFM-#11-A
24X24
SH-11
24X18
34X24
12"ØAUTO. D
EF-#74
12"Ø DN
24X18
24X16 34X24
R
R
PLEMUM-42"L
X 50"W X 60"H
24X18
34X24
(E) STEAM PRESSURE REDUCING
STATION TO REMAIN
DEMO AND REMOVE AIR
HANDLER, HUMIDIFIER, AND
ASSOCIATED DUCTWORK
DEMO AND REMOVE EXHAUST FAN
AND ASSOCIATED DUCTWORK
DEMO AND REMOVE EXHAUST FAN
AND ASSOCIATED DUCTWORK
DEMO AND REMOVE EXHAUST FAN
AND ASSOCIATED DUCTWORK
(E) CONDENSATE RECEIVER, PUMP,
FLASH TANK, AND ASSOCIATED
STEAM PIPING TO REMAIN
DEMO AND REMOVE FAN
COIL AND ASSOCIATED
SUPPLY AND OUTSIDE AIR
DUCTWORK
DEMO ETO STERILIZER EXHAUST DUCT AND
REMOVE ETO EXHAUST FAN ON ROOF. CAP,
SEAL, AND ABANDON DUCT UP TO ROOF
AUTO DAMPER (TYP)
(E) STEAM HEATING WATER
SYSTEM TO REMAIN
(E) OUTSIDE AIR DUCT AND
DAMPER TO REMAIN. CAP FOR
FUTURE RECONNECTION.
(E) 48X30
(E) 48X30
DEMO AND REMOVE
HEAT EXCHANGER
(E) 48X30 DUCT THRU EXTERIOR
WALL TO REMAIN. COORDINATE
EXTENT OF DEMOLITION WITH
NEW WORK.
(E) EXPANSION TANK
TO REMAIN
LOADING DOCK
TRASH & LINEN DOCK
(E) LOUVER
REUSE EXISTING HVAC
GRILLES IN THIS AREA
DEMO AND REMOVE
EQUIPMENT PAD
DEMO AND REMOVE
EQUIPMENT PAD
SEE MD405 FOR
CONTINUATION
(TYP)
MECHANICAL #3
BD-111
ELECTRICAL
BD-110
SIGNAL
BD-110B
TELE
BD-110A
VESTIBULE
BD-110C
COMMON SPACE
CONFERENCE
BD-113
CORRIDOR
CB-12
PROVIDE 76" WIDE BY 120" HIGH
WALL OPENING FLUSH WITH
LOADING DOCK FLOOR. SEE
STRUCTURAL FOR OPENING
FRAMING DETAILS.
DEMO AND REMOVE 9.5'
SECTION OF CEMENT
EQUIPMENT PAD FLUSH
TO FLOOR
RF-#11
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
DEMO NOTES
KEY PLAN
LEGEND
MD401
BASEMENT MECHANICAL ROOM
DEMOLITION PLAN - MECHANICAL
D & T
TRUE
NORTH
PROJECT
NORTH
NURSING
TOWER
AREA OF
RENOVATION
WORK
KEY PLAN:NTS
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION
WORK WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED
TO BE RETURNED TO THE OWNER, SHALL BECOME THE
PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF
ITEMS ON THE PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN
AND AROUND BUILDING DURING DEMOLITION. PREVENT
INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE
ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.
IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE
CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE
MEASURES TO PREVENT DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT
FIRST OBTAINING PERMISSION FROM THE UTILITY COMPANY
AND/OR OWNER. PROVIDE TEMPORARY SERVICES AS
REQUIRED.
5. REMOVE AND DISPOSE OF EXISTING MECHANICAL
EQUIPMENT AS SHOWN, UNLESS NOTED OTHERWISE.
COORDINATE WITH ARCHITECT, AREAS OF DEMOLITION
AROUND, ADJACENT, OR CONNECTED TO EXISTING
MECHANICAL EQUIPMENT THAT IS TO REMAIN.
DEMO KEY PLAN
TRUE
NORTH
PROJECT
NORTH
1/4" = 1'-0"1 BASEMENT MECHANICAL ROOM DEMOLITION PLAN- MECHANICAL
EXISTING WORK (LIGHT)
DEMOLITION (DARK)
POINT OF DEMOLITION
DEMOLITION KEY
SPS
SWING
SPACE
WAREHOUSE
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
76-0
SE
114-0
SE
152-0
SE
190-0
SE
179-4
SE
152-10
SE
76-0
SE
114-0
NE
383'-9"
NE
342-0
NE
304-0
UP
NE
380-0
CG-4
CD-B-4
8X12
11-13
CD-B-4
6X12
CD-B-4
8X12
CD-B-4
6X12
16X10
CG-4
CG-4
11-14
11-16
CD-A-4
6X8
CG-1
8X8
CG-1
12X4
CD-A-4
11-17
6X8
12X6
12X8
CG-2
CG-1
12X4
12X10
11-19
12X6
CD-A-4
6X8
CG-1
CD-A-3
130 CG-2
11-15
11-9
CD-A-4
CD-A-4
6x8
UP TO
INTERSTITIAL
CD-A-4
100 3
CD-A-4
100 3
CD-A-4
100 3
CD-A-4
FOR DEMOLITION WORK
IN MECHANICAL ROOM
SEE MD401
NON-STERILE
STORAGE
BD-104
M TOILET
BD-103
HAC
BD-103A
BREAK ROOM
BD-112D
OFFICE
BD-112C
OFFICE
BD-112B
OFFICE
BD-112A
OFFICE
BD-112
CORRIDOR
CB-14
CORRIDOR
CB-13
CORRIDOR
CB-10
F TOILET
BD-103C
CORRIDOR
CB-8
LOADING DOCK
BD-107
SPEES DESIGN BUILD
625 1ST AVE, UNIT 301
SEATTLE, WA 98101
(360) 223-8994
RAY SPEES, PRINCIPAL
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
06/25/2021 Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MKK AGG
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
663-20-102
KARTCHNER ENGINEERING
101 S STEVENS, SUITE 201
SPOKANE, WA 99201
(509) 922-0383
100% CD
DEMO NOTES
KEY PLAN
LEGEND
MD402
BASEMENT DEMOLITION PLAN - SOUTH -
MECHANICAL
D & T
TRUE
NORTH
PROJECT
NORTH
NURSING
TOWER
AREA OF
RENOVATION
WORK
KEY PLAN:NTS
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION
WORK WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED
TO BE RETURNED TO THE OWNER, SHALL BECOME THE
PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF
ITEMS ON THE PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN
AND AROUND BUILDING DURING DEMOLITION. PREVENT
INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE
ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.
IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE
CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE
MEASURES TO PREVENT DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT
FIRST…