Attachment 9 Drawings 6 of 11 Mechanical.pdf

PDF 4 MB Posted

Attached to
Y1DA--CON 663-20-102 Upgrade SPS OM Solicitation
Solicitation number
36C26023R0021
Issued by

About this file

This document package includes construction drawings and specifications for an upgrade project at a Department of Veterans Affairs medical facility. The project scope involves renovating and expanding sterile processing services in an existing building. Drawings show demolition plans, new construction plans, schedules, details and notes. Mechanical drawings depict HVAC, plumbing and piping demolition and new layouts. Specifications call for work including removing existing equipment and ductwork, filling floor penetrations, capping utilities, and preparing surfaces for new connections. The project aims to modernize sterile processing facilities while the hospital remains operational.

View the file

Other files

File Type Posted
Attachment 23 Partial Architectural Set.pdf PDF
36C26023R0021 0002.docx DOCX document
Attachment 19 RFI Responses Rev 1.pdf PDF
Attachment 24 RFI Supplement.pptx PPTX presentation
Attachment 15 Wage Determination REV 1 20230825.pdf PDF
Attachment 22 Mobile Steris Trailer.pdf PDF
Attachment 21 Site Visit Agenda and Sign-In.pdf PDF
Attachment 20 36C26022Q0073 RFI List FOR INFORMATIONAL PURPOSES ONLY.pdf PDF
36C26023R0021 0001.docx DOCX document
Attachment 19 RFI Responses.pdf PDF
Attachment 20 36C26022Q0073 RFI List.pdf PDF
Attachment 18 Calculation of Self Performed Work REV 1.pdf PDF
Attachment 14 Drawings 11 of 11 Haz Mat.pdf PDF
Attachment 16 Price Breakout.xlsx XLSX spreadsheet
36C26023R0021.docx DOCX document
Attachment 8 Drawings 5 of 11 Fire Protection.pdf PDF
Attachment 7 Drawings 4 of 11 Structural.pdf PDF
Attachment 3 Specs 2 of 2.pdf PDF
Attachment 2 Specs 1 of 2.pdf PDF
Attachment 1 Construction SOW Rev5.docx DOCX document
Attachment 13 Drawings 10 of 11 Electrical 3 of 3.pdf PDF
Attachment 10 Drawings 7 of 11 Plumbing.pdf PDF
Attachment 17 Contractor Rules Of Behavior.pdf PDF
Attachment 18 Calculation of Self Performed Work.pdf PDF
Attachment 12 Drawings 9 of 11 Electrical 2 of 3.pdf PDF
Attachment 5 Drawings 2 of 11 Civil.pdf PDF
Attachment 15 Wage Determination.pdf PDF
Attachment 11 Drawings 8 of 11 Electrical 1 of 3.pdf PDF
Attachment 6 Drawings 3 of 11 Architectural.pdf PDF
Attachment 4 Drawings 1 of 11 General.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC BASIS OF DESIGN

SUMMER OUTDOOR

DESIGN DB (°F) 85 STATE COUNTY CLIMATE ZONE

SUMMER OUTDOOR

DESIGN WB (°F) 65 WASHINGTON KING 4C

WINTER OUTDOOR

DESIGN DB (°F) 25 DESIGN ALTITUDE 400 FT

CONNECT NEW TO EXISTING

SHEET NUMBER

SECTION DESIGNATION

BLANKED FOR 1-WAY

BLANKED FOR 2-WAY

BLANKED FOR 3-WAY

STANDARD 4-WAY

SELF-CLOSING FIRE DAMPER

AUTOMATIC SMOKE DAMPER

COMBINATION SMOKE/FIRE

ROOF EXHAUST FAN SHOWN

ROOF EXHAUST FAN SHOWN

AUTOMATIC CONTROL DAMPER

RISE/DROP

TAKE-OFFSUPPLY

CEILING

DUCT MTD.

DIFF/GRILLE

BULLHEAD SPLIT

TAKEOFF

DIFF/GRILLE

TO

OR

HARD

ELBOW

SUPPLY DUCT DOWN

SUPPLY DUCT UP

OR R

w

SINGLE LINE

RETURN/EXHAUST

CONVERGE

BULLHEAD

SUPPLY/RETURN/

RISE OR DROP

SUPPLY/RETURN

RETURN/EXHAUST

TAKE-OFF

90°F

TAP

45°F

TAP

/EXHAUST

HORIZONTAL

DUCT DOWN

EXHAUST

OFFSET

RING

DUCT

RISE/DROP

DUCT

FLEXIBLE

1/4"x1/4" WMS

OPEN END

DUCT W/

RETURN/EXHAUST

ACOUSTICALLY

LINED DUCT

CEILING

DUCT MTD.

DIFF/GRILLE

DUCT UP

DOUBLE LINE

DUCTWORK SYMBOLS

REG./GRILLE

DUCT MTD.

SIDEWALL

BD

LD MF'R

BOOT BY

VD VD

UC 1/2"

LVDR 1.5 SF

OR

SUPPLY AIR FLOW

BACKDRAFT DAMPER

UNDERCUT DOOR

LOUVERED DOOR

SGD

AVS

ACD

SFD

SD

FD

VD

VD VD

SLIDE GATE DAMPER

AIR VOLUME TRAVERSE STATION

MANUAL VOLUME DAMPER

W/ACCESS DOOR

W/ACCESS DOOR

W/ACCESS DOOR

DAMPER W/ACCESS DOOR

BLOW SUPPLY DIFFUSER

BLOW SUPPLY DIFFUSER

BLOW SUPPLY DIFFUSER

BLOW SUPPLY DIFFUSER

ON FLOOR PLAN

ON ROOF

ADDITIONAL SYMBOLS

EQUIPMENT

DUCTWORK OR

TO BE REMOVED

FIRE DAMPER

M MOTORIZED DAMPER POINT OF DEMOLITION

TURNING VANES

DUCT UP

SINGLE LINE DOUBLE LINE

TEMPERATURE SENSOR OR

THERMOSTAT

RETURN OR EXHAUST AIR

FLOW DIRECTION

SUPPLY SIDEWALL

LINEAR DIFFUSER

(W/SHEET METAL

PLENUM W/1"

LINING & BRANCH

CONN FOR EVERY

4' OF LENGTH)

SUPPLY CEILING

LINEAR DIFFUSER

(W/SHEET METAL

PLENUM W/1"

LINING & BRANCH

CONN FOR EVERY

4' OF LENGTH)

STANDARD RADIUS

ELBOW (R = W)

SUPPLY/RETURN

/EXHAUST

XxX [X] XXX,XxX,XX°

1 2 3 4 5

NECK SIZE (IN)

AIR OUTLET TYPE

AIRFLOW (CFM)

SIZE (IN) OF CONNECTING BRANCH DUCT

ANGLE OF THROW, DOWN FROM HORIZONTAL (°)

AIR OUTLET CALLOUT

BALL VALVE

UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)

WATER BALANCING VALVE

AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR

PIPE BREAK (SINGLE LINE)

RISE (SINGLE LINE - PLAN VIEW)

DROP (SINGLE LINE - PLAN VIEW)

BOTTOM TAKEOFF

TOP TAKEOFF

BLIND FLANGE

END CAP

BUTTERFLY VALVE

GATE VALVE THREADED

CHECK VALVE

GEOTHERMAL HEATING SUPPLY

GEOTHERMAL HEATING RETURN

PIPING LEGEND

INVERTED BUCKET TRAP

GEHR

GEHS

GATE VALVE FLANGED

GATE VALVE WITH 3/4" HOSE ADAPTER

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

FLEXIBLE CONNECTION

SAFETY RELIEF VALVE

PRESSURE GAGE

THERMOMETER

FLOAT AND THERMOSTAT TRAP

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

ECCENTRIC REDUCER

DIRECTION OF PIPE PITCH (DOWN)

T

PROJECT NOTES

1. VA WILL SHUT DOWN EXISTING UTILITY SYSTEM AS NECESSARY FOR CONTRACTOR TO PERFORM

REQUIRED WORK. CONTRACTOR IS RESPONSIBLE FOR DRAINING EXISTING WET SYSTEMS, SUCH AS

WATER, CHILLED WATER, HEATING WATER ETC. AS REQUIRED TO ACCOMPLISH NEW WORK.

CONTRACTOR IS ALSO RESPONSIBLE FOR RE-FILLING SYSTEMS INCLUDING ADDING CHEMICAL AS REQUIRED. IT IS ACCEPTABLE TO SALVAGE EXISTING TREATED WATER IN CLEAN STORAGE CONTAINERS APPROVED BY THE VA, AND RE-INJECT IT INTO THE SYSTEM UPON COMPLETION OF WORK. ANY TREATED

WATER NOT RE-INJECTED IS TO BE PROPERLY DISPOSED OF.

MECHANICAL SHEET INDEX

M-001 NOTES, SYMBOLS, & LEGENDS - MECHANICAL

MD401 BASEMENT MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL

MD402 BASEMENT DEMOLITION PLAN - SOUTH - MECHANICAL

MD403 BASEMENT DEMOLITION PLAN - NORTH - MECHANICAL

MD404 BASEMENT WAREHOUSE DEMOLITION PLAN - MECHANICAL

MD405 BASEMENT INTERSTITIAL DEMOLITION PLAN - SOUTH - MECHANICAL

MD406 BASEMENT INTERSTITIAL DEMOLITION PLAN - NORTH - MECHANICAL

MD407 BASEMENT WAREHOUSE INTERSTITIAL DEMOLITION PLAN - MECHANICAL

MD408 BASEMENT MECHANICAL ROOM DEMOLITION PLAN - MECHANICAL PIPING

MD409 BASEMENT INTERSTITIAL DEMOLITION PLAN - SOUTH - MECHANICAL PIPING

MD410 BASEMENT INTERSTITIAL DEMOLITION PLAN - NORTH - MECHANICAL PIPING

MD411 BASEMENT WAREHOUSE INTERSTITIAL DEMOLITION PLAN - MECHANICAL PIPING

MH412 BASEMENT MECHANICAL ROOM - MECHANICAL

MH413 BASEMENT FLOOR PLAN - SOUTH - MECHANICAL

MH414 BASEMENT FLOOR PLAN - NORTH - MECHANICAL

MH415 BASEMENT WAREHOUSE FLOOR PLAN - MECHANICAL

MH416 BASEMENT INTERSTITIAL SPACE - SOUTH - MECHANICAL

MH417 BASEMENT INTERSTITIAL SPACE - NORTH - MECHANICAL

MH418 BASEMENT WAREHOUSE INTERSTITIAL SPACE - MECHANICAL

MP419 BASEMENT MECHANICAL ROOM - MECHANICAL PIPING

MP420 BASEMENT FLOOR PLAN - SOUTH - MECHANICAL PIPING

MP421 BASEMENT FLOOR PLAN - NORTH - MECHANICAL PIPING

MP422 BASEMENT INTERSTITIAL SPACE - SOUTH - MECHANICAL PIPING

MP423 BASEMENT INTERSTITIAL SPACE - NORTH - MECHANICAL PIPING

MP424 BASEMENT WAREHOUSE INTERSTITIAL SPACE - MECHANICAL PIPING

MH425 PRESSURIZATION MAP - SOUTH - MECHANICAL

MH426 PRESSURIZATION MAP - NORTH - MECHANICAL

M-501 DETAILS - MECHANICAL

M-502 DETAILS - MECHANICAL

MI503 CONTROLS - MECHANICAL

M-601 SCHEDULES - MECHANICAL

M-602 SCHEDULES - MECHANICAL

MD701 SWING SPACE DEMOLITION PLAN - MECHANICAL

MD702 SWING SPACE INTERSTITIAL DEMOLITION PLAN - MECHANICAL

MH703 SWING SPACE FLOOR PLAN - MECHANICAL

MH704 SWING SPACE INTERSTITIAL SPACE - MECHANICAL

ABBREVIATIONS

ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION

A AIR OR COMPRESSED AIR A/C AIR CONDITIONING

AD ACCESS DOOR ADA AMERICAN DISABILITIES ACT

AF AIR FOIL ADJ ADJUST, ADJUSTABLE, ADJACENT

AFF ABOVE FINISHED FLOOR AGA AMERICAN GAS ASSOCIATION

AHU AIR HANDLING UNIT AMB AMBIENT

AMP AMPERE, AMPACITY ANCH ANCHOR

AP ACCESS PANEL APPD APPROVED

APD AIR PRESSURE DROP ARCH ARCHITECT, ARCHITECTURAL

AS AIR STREAM ATC AUTOMATIC TEMPERATURE CONTROL

AVG AVERAGE ATM ATMOSPHERE

BDD BACK DRAFT DAMPER BTTM BOTTOM

BHP BREAK HORSE POWER BI BACKWARD INCLINED

BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR

BV BUTTERFLY VALVE BOD BOTTOM OF DUCT

CENT CENTER OR CENTRIFUGAL CAP CAPACITY

CFM CUBIC FEET PER MINUTE CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY CI CAST IRON

CF CUBIC FEET CLG CEILING

CLR CLEAR CMU CONCRETE MASONRY UNIT

CNDS CONDENSATE CO CARBON MONOXIDE

COMB COMBINATION, COMBUSTION CO2 CARBON DIOXIDE

CV CHECK VALVE CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY CT COOLING TOWER

CONN CONNECTION OR CONNECT CTBD COOLING TOWER BLOW DOWN

CUH CABINET UNIT HEATER D DRAIN

DB DRY BULB DEG DEGREE

DDC DIRECT DIGITAL CONTROL DIA DIAMETER

DP DIFFERENTIAL PRESSURE DPS DIFFERENTIAL PRESSURE SWITCH

DET DETAIL DEMO DEMOLITION

DIA DIAMETER DF DRINKING FOUNTAIN

DIM DIMENSION DIFF DIFFUSER

DN DOWN DIV DIVISION

DS DOWNSPOUT, DISCONNECT SWITCH,

DOOR SWITCH DPR DAMPER

DX DIRECT EXPANSION DWG DRAWING

EA EACH OR EXHAUST AIR ELEV ELEVATOR, ELEVATION

ELEC ELECTRICAL ENCL ENCLOSURE

ENG ENGINEER EPDM ETHYLENE PROPYLENE DIENE MONOMER

EQ EQUAL EQUIP EQUIPMENT

EWH ELECTRIC WALL HEATER EXH EXHAUST

EXIST EXISTING EAHU EXHAUST AIR HANDLING UNIT

EAT ENTERING AIR TEMPERATURE EF EXHAUST FAN

EMER EMERGENCY EMS ENERGY MANAGEMENT SYSTEM

ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER EWT ENTERING WATER TEMPERATURE

F FAHRENHEIT FA FREE AREA

FC FLEXIBLE CONNECTION FCU FAN

FD FIRE DAMPER OR FIRE DEPARTMENT FLA FULL LOAD AMPS

FPM FEET PER MINUTE FS FLOW SWITCH

FT FEET FTR FIN TUBE RADIATION

G GAS GA GAUGE

GAL GALLONS GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE HB HOSE BIB

HD HEAD HP HORSEPOWER

HR HOUR HRU HEAT RECOVERY UNIT

HTG HEATING HZ HERTZ (CYCLES PER MINUTE)

ID INSIDE DIAMETER IN INCHES

KW KILOWATT LAT LEAVING AIR TEMPERATURE

LF LINEAR FEET LD LINEAR DIFFUSER

LRA LOCKED ROTOR AMPS LVR LOUVER

LWT LEAVING WATER TEMPERATURE MAX MAXIMUM

MBH 1000 BTU MCA MINIMUM CIRCUIT AMPS

MUA MAKE UP AIR MOCP MAXIMUM OVER CURRENT PROTECTION

NC NOISE CRITERIA NO NORMALLY OPEN

NOM NOMINAL OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE OC ON CENTER

OD OUTSIDE DIAMETER ODP OPEN DRIP PROOF

OV OUTLET VELOCITY PCF POUNDS PER CUBIC FEET

PD PRESSURE DROP PH PHASE

PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH

PSIA POUND PER SQUARE INCH - ABSOLUTE PSID POUND PER SQUARE INCH -

DIFFERENTIAL

PSIG POUND PER SQUARE INCH - GAUGE PVC POLYVINYL CHLORIDE

R RADIUS RA RETURN AIR

RET RETURN RH RELATIVE HUMIDITY

RLF RELIEF RPM REVOLUTIONS PER MINUTE

RTU ROOFTOP UNIT SA SUPPLY AIR

SD SMOKE DETECTOR SE SMOKE EXHAUST

SEN SENSIBLE SFD COMBINATION SMOKE/FIRE DAMPER

SHC SENSIBLE HEAT CAPACITY SP STATIC PRESSURE

SF SQUARE FEET SS STAINLESS STEEL

SUP SUPPLY T TEMPERATURE OR THERMOSTAT

TEFC TOTALLY CLOSED FAN COOLED TEMP TEMPERATURE

TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT

TYP TYPICAL UC UNDERCUT DOOR

V VOLTS VAV VARIABLE AIR VOLUME

VEL VELOCITY VFD VARIABLE FREQUENCY DRIVE

WB WET BULB TEMPERATURE WC WATER COLUMN

WG WATER GAUGE WPD WATER PRESSURE DROP

WTD WATER TEMPERATURE DIFFERENCE

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

M-001

LEGENDS, SYMBOLS,

ABBREVIATIONS, & NOTES -

MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text R

AIR

FLOWAD

AD

FAN

INLINE

NOTE: REFER TO CONSTRUCTION SPECIFICATIONS FOR MATERIALS,

EQUIPMENT, AND INSTALLATION REQUIREMENTS.

24"X24" ACCESS DOOR

(BOTH SIDES) FOR ALL FANS

WITH DUCT CONNECTIONS LARGER

THAN 36" (ROUND OR SQUARE)

WASHER (TYP.)

3/16" THICK FRAME W/EYELET

WELDED TO FAN HOUSING,

PRIMED AND PAINTED (TYP.)

2"X2"X1/8" ANGLE

REINFORCEMENT

CONN TO DUCT

FLEX CONNECTION (TYP)

VIBRATION ISOLATOR

SPRING ASSEMBLY

SUPPORT ROD

HUNG FROM CEILING

SUPPORT (TYP)

NUT (TYP)

ROD

RUBBER

GROMMET

(TYP.)

ANCHOR DUCT

TO PREVENT

LATERAL

MOVEMENT

EXHAUST FAN DETAIL

SCALE: NOT TO SCALE

EXIST MASONRY

WALL

PIPE SLEEVE

PIPE INSULATION

PIPE

MINERAL WOOL

INSIDEOUTSIDE

CAULK (TYP)

CAULK (TYP)

PIPE INSULATION

WITH JACKET

PIPE THRU WALL

SCALE: NOT TO SCALE

NOTE:

1.

2.

3.

4.

5.

6.

7.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR

SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR

FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER

FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH

ROCK WOOL FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND

MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3 (NOTE

FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

[2 5m m

TYPICAL TERMINAL UNIT

SCALE: NOT TO SCALE

BY-PASS CHEMICAL SHOT FEEDER

SCALE: NOT TO SCALE

FLOOR SUPPORTED IN-LINE PUMP

SCALE: NOT TO SCALE

HEATING COIL PIPING DETAIL

SCALE: NOT TO SCALE

WASHER VENTILATION CONNECTION DETAIL

SCALE: NOT TO SCALE

SECTION THRU FIRE DAMPER INSTALLATION

SCALE: NOT TO SCALE

MIN 4" TALL LIFTERS

CONDENSING UNIT (CU)

ROUND TUBING

4"CONCRETE PAD

3/8" Ø POWERS CARBON STEEL

WEDGE BOLT CONCRETE

ANCHOR WITH 1" Ø MIN

WASHER, 2-1/2" EMBEDMENT

AND 6" MIN EDGE DISTANCE

INSTALL LINE SET PER

MANUFACTURE

RECOMMENDATIONS.

RS AND RL LINES TO

DUCTLESS SPLIT

90° SWEEP

LS

PROVIDE ISOLATION

VALVES ON EACH SIDE

OF BRAIDED FLEXIBLE

REFRIGERANT LINE

MINIMUM 12"

BRAIDED

FLEXIBLE

REFRIGERANT

LINE

HEAT PUMP UNIT ROOF MOUNT SUPPORT DETAIL

SCALE: NOT TO SCALE

MPS

STEAM CONDENSATE

F&T

TRAP

STERILIZER STEAM PIPING

SCALE: NOT TO SCALE

NOTES:

1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON

VIBRATION ISOLATOR UNITS, THE RUNOUT PIPING FOR

CONNECTIONS TO COIL SHALL BE INSTALLED WITH

SWING JOINTS TO ALLOW FOR THE VIBRATION.

2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT

WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS

OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING

OF FILTERS, VALVES, OR EQUIPMENT.

3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A

BANK OF TWO OR MORE HIGH. ALSO PROVIDE SEPARATE

VACUUM BREAKER FOR EACH COIL.

4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO

TRAPS REQUIRED WHEN CONDENSATE LOAD IS 2400

KG/HR [5,000 LBS/HR] OR GREATER.

5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END.

REHEAT COIL MAY HAVE SUPPLY & RETURN PIPES FROM

OPPOSITE ENDS.

PIPE HANGER

SHALL SUPPORT

PIPING

INDEPENDENT

OF COIL (TYP.)

PITCH COIL DOWN

8mm [1/4"] PER FOOT

TO CONDENSATE

OUTLET

FULL SIZE

TAPPING

PRESSURE

GAGE

SCALE POCKET

SEE

NOTE

NO. 4 STEAM CONDENSATE

RETURN

15mm [1/2"] CHECK

VALVE VACUUM

BREAKER

INCREASER,

IF

REQUIRED

REDUCER,

IF REQUIRED

0m m [6

" M

IN

0m m [1

2" M

IN

STEAM SUPPLY

STEAM - PIPING CONNECTIONS

SCALE: NOT TO SCALE

SLOPE CR-30 AT 1" PER 40'

SLOPE S-30 AT 1" PER 40'

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

M-501

DETAILS - MECHANICAL

AutoCAD SHX Text

STEAM EQUIPMENT

AutoCAD SHX Text

6" DIRT TRAP

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

NOTE:

ALL DRIP POINTS ON STEAM MAINS

SHALL BE PROVIDED WITH A 300mm

[12"] MINIMUM HIGH DRIP LEG FROM

BOTTOM OF STEAM MAIN TO TRAP

INLET. DRIP LEG SHALL HAVE 150mm

[6"] SCALE POCKET BELOW TRAP

INLET.

TO RETURN MAIN

PIPE SIZE SHALL BE SAME SIZE AS

TRAP

FLOAT AND THERMOSTATIC

TRAP. SEE PLANS, AND

SCHEDULES

DIELECTRIC FITTING

WHERE RETURN IS

COPPER PIPE

FLOW

SCHEDULE 80

STEEL PIPE

BYPASS-INSTALL IN HORIZONTAL PLANE

LEVEL WITH TRAP OR IN VERTICAL PLANE

& BELOW TRAP PROVIDE BYPASS PIPING

FOR ALL TRAPS 25mm [1"] AND LARGER. 30

0m m

0m m

DRIP LEG OR EQUIPMENT

CONNECTION. MAKE THE

SAME SIZE AS THE SUPPLY

MAIN OR EQUIPMENT

CONNECTION. SEE NOTE 1

[1 2"

M

IN

[6

" M

IN

SCHEDULE 80 STEEL PIPE

SEE DRAWINGS FOR PIPE SIZES

25mm [1"]

GATE VALVE

USE 4-BOLT RAISED FACE FLANGES

TYPICAL MANUAL AIR VENT

TYPICAL CHILLED AND HOT WATER

PIPING DRAIN VALVE CONNECTIONS

ELEVATION

THREADED PIPING

ELEVATION

WELDED PIPING

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" [20mm] BALL VALVE

ADAPTER TO 3/4" [20mm] HOSE

THREAD-PROVIDE HOSE CAP NUT

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR

PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

AIR VENT

1/2" [15mm]

BALL VALVE

1/4" [8mm]

COPPER TUBING

1/2" [15mm] x 4" [100mm]

NIPPLE

CIRCULATING WATER PIPING

ELEVATION

NOTES:

1. VENT ALL HIGH POINTS INDICATED ABOVE.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.

MV

OR

AV

DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC)

SCALE: NOT TO SCALE

FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY

SCALE: NOT TO SCALE

FCU PIPING DETAIL

SCALE: NOT TO SCALE

SINGLE COIL

WATER COIL

AIR VENT

WHEN COIL

IS NOT

SELF-VENTING

DRAIN WHEN

COIL IS

NOT

SELF-DRAINING

TEST PLUG

(TYP.)

PIPE HANGER SHALL

SUPPORT

PIPING INDEPENDENT OF

COIL

REDUCER, IF REQUIRED

DRAIN

WATER COIL

AIR VENT

WHEN COIL IS

NOT

SELF-VENTING

TEST

PLUG

(TYP.)

PIPE HANGER SHALL

SUPPORT

PIPING INDEPENDENT OF

COIL

WATER COIL

REDUCER, IF REQUIRED

FLOW ELEMENT

DRAIN WHEN COIL

IS NOT

SELF-DRAINING

DRAIN

DOUBLE COIL

NOTES:

1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR

EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 100mm [4"]Ø PIPE & SMALLER. TYPE "H-P" FOR 125mm [5"]Ø PIPE & LARGER.

2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR

EQUIPMENT.

3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM

AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.

FE

MV

MV

MV

MV

MV

MV

FE

TI

TI

TEMPERATURE

INDICATION TO

ECC SEE

CONTROL

DIAGRAM

MV

DESIGNER'S NOTE:

1. CONSIDER WHETHER WATER

TEMPERATURE SENSOR AND FLOW

ELEMENT ARE NECESSARY ON EVERY

COIL, AS THIS CAN BECOME EXPENSIVE.

OTHER CONTROL

DEVICES (i.e., AIR SIDE TEMPERATURES

AND AIR FLOW) MAY PROVIDE EQUALLY

BENEFICIAL INFORMATION FOR

TROUBLESHOOTING.

2. BALANCING VALVES MAYBE OMITTED IF

REVERSE PIPING PROVIDED.

CALIBRATED

BALANCING VALVE

(TYP.)

CONDENSATE

TO DRAIN

MV

MANUAL

AIR

VENT

TO BUILDING

LOAD

INVERTED BUCKET

TRAP ASSEMBLY

WELDED

TEE

STEAM PIPE

300mm[12"]

150mm[6"] SCHEDULE 80 STEEL PIPE

25mm [1"] GATE VALVE

WELDED TEE

END OF STEAM LINE DRIP TRAP

SCALE: NOT TO SCALE

WATER COILS - PIPING CONNECTIONS

SCALE: NOT TO SCALE

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

M-502

DETAILS - MECHANICAL

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

TU

11-1

TU

11-2

TU

11-3

TU

11-4

TU

11-5

TU

11-6

TU

11-7

TU

11-8

TU

11-9

TU

11-10

TU

11-11

TU

11-12

TU

11-13

TU

11-14

TU

11-15

TU

11-16

SINGLE DUCT REHEAT TERMINAL UNIT SCHEDULE

TAG MANUFACTURER

& MODEL TYPE SERVES VALVE

CONNECTION

SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL

NOTES

INLET OUTLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI

TITUS DESV CRV OFFICE B105 2-WAY 05 12X8 80 80 0.5 0.25 0.02 - 15 80 3.0 55 90 160 140 0.01 0.3 0.36 1 10 1, 2, 3, 4, 5

TITUS DESV CRV OFFICE B104 2-WAY 06 12X8 145 145 0.5 0.25 0.06 - 13 145 5.4 55 90 160 140 0.04 0.5 1.94 2 10 1, 2, 3, 4, 5

TITUS DESV CRV OFFICE B106 2-WAY 06 12X8 100 100 0.5 0.25 0.03 - - 100 3.7 55 90 160 140 0.01 0.4 0.1 2 10 1, 2, 3, 4, 5

TITUS DESV CRV OFFICE B107 2-WAY 05 12X8 80 80 0.5 0.25 0.02 - 15 80 3.0 55 90 160 140 0.01 0.3 0.1 1 10 1, 2, 3, 4, 5

TITUS DESV CRV STERILE

COOLDOWN B108 2-WAY 40 38X18 2080 2080 0.5 0.25 0.15 29 22 2080 78.6 55 90 160 140 0.11 7.9 0.25 2 10 1, 2, 3, 4, 5

TITUS DESV CRV LOW TEMP B136 2-WAY 14 20X17.5 775 775 0.5 0.25 0.07 13 13 775 29.3 55 90 160 140 0.03 2.9 0.15 2 10 1, 2, 3, 4, 5

TITUS DESV CRV PREP AND PACK

B126 2-WAY 40 38X18 1750 1750 0.5 0.25 0.09 24 18 1750 66.1 55 90 160 140 0.04 6.6 0.91 2 10 1, 2, 3, 4, 5

TITUS DESV CRV PREP AND PACK

B126 2-WAY 40 38X18 1750 1750 0.5 0.25 0.09 24 18 1750 66.1 55 90 160 140 0.08 6.6 0.93 2 10 1, 2, 3, 4, 5

TITUS DESV CRV BREAK & STAFF

LOCKERS 2-WAY 14 20X17.5 905 900 0.5 0.25 0.09 14 14 905 34.2 55 90 160 140 0.08 3.4 0.93 2 10 1, 2, 3, 4, 5

TITUS DESV CRV STERILE

STORAGE B110 2-WAY 16 24X18 1290 1290 0.5 0.25 0.14 12 11 1290 48.7 55 90 160 140 0.16 4.9 0.39 2 10 1, 2, 3, 4, 5

TITUS DESV CRV STERILE

STORAGE B110 2-WAY 14 20X17.5 950 950 0.5 0.25 0.09 14 14 950 35.9 55 90 160 140 0.13 3.6 0.33 2 10 1, 2, 3, 4, 5

TITUS DESV CRV CLEAN SCOPE

STORAGE B124 2-WAY 06 12X8 120 120 0.5 0.25 0.03 - 10 120 4.5 55 90 160 140 0.03 0.5 3.52 2 10 1, 2, 3, 4, 5

TITUS DESV CRV COORD OFFICE

B115 3 - WAY 06 12X8 110 110 0.5 0.25 0.03 - 10 110 4.1 55 90 160 140 0.02 0.4 0.1 2 10 1, 2, 3, 4, 5

TITUS DESV CRV STAFF RR B-119

AND B-120 2-WAY 12 16X15 430 430 0.5 0.25 0.06 10 17 430 16.2 55 90 160 140 0.02 1.6 0.16 2 10 1, 2, 3, 4, 5

TITUS DESV CRV IMPLANT B111 2-WAY 10 14X12.5 240 240 0.5 0.25 0.05 16 15 240 9.0 55 90 160 140 0.06 0.9 0.34 2 10 1, 2, 3, 4, 5

TITUS DESV CRV BREAKDOWN

B114 2-WAY 10 14X12.5 180 180 0.5 0.25 0.05 16 15 180 6.8 55 90 160 140 0.05 0.7 0.72 2 10 1, 2, 3, 4, 5

TITUS DESV CRV CORRIDOR

CB-18B 2-WAY 12 16X15 600 600 0.5 0.25 0.06 10 17 600 22.6 55 90 160 140 0.02 2.3 0.09 2 10 1, 2, 3, 4, 5

TITUS DESV CRV DETERGENT

ROOM B117 2-WAY 10 14X12.5 250 250 0.5 0.25 0.05 16 15 250 9.4 55 90 160 140 0.02 0.9 0.09 2 10 1, 2, 3, 4, 5

TITUS DESV CRV ELECTRICAL

CB15K 2-WAY 12 16X15 450 450 0.5 0.25 0.06 10 17 450 17.0 55 90 160 140 0.03 1.7 0.16 2 10 1, 2, 3, 4, 5

TU

11-17

TU

11-18

TU

11-19

NOTES:

1. (CVR) CONSTANT AIR VOLUME TERMINAL UNITS WITH HOT WATER COIL REHEAT

2. DDC CONTROLS

3. PROVIDE LEFT OR RIGHT HAND COIL CONNECTION AND CONTROL BOX ACCESS AS

REQUIRED TO MATCH CONFIGURATION SHOWN ON PLANS.

4. SOUND LEVELS SHALL NOT EXCEED NC 25 (RADIATED OR DISCHARGE).

5. TERMINAL BOX SHALL BE CONSTRUCTED OF STAINLESS STEEL WITH NO EXPOSED

INSULATION ON THE AIR SIDE OF THE TERMINAL UNIT.

DUCTLESS SPLIT SYSTEM SCHEDULE

OUTDOOR HEAT PUMP INDOOR FAN COIL

EQUIP# MFR MODEL #

OPERATING

WEIGHT

(LBS)

SEER

COOLING

@ 95° F

(MBH)

HSPF

@ 47° F

HEATING

@ 4° F

(MBH)

ELECTRICAL

NOTES EQUIP# MFR MODEL # TYPE CFM SPEED

TOTAL

COOLING

@ 95° F

(MBH)

TOTAL

HEATING

@ 4° F

(MBH)

ELECTRICAL

NOTES

MCA MOCP VOLTS PHASE MCA / MOCP VOLTS PHASE

CARRIER 38MARB 24 145 21.5 25.9 12 29.1 25 35 208 1 1, 2, 3, 4 CARRIER 40MAH 24 HIGH WALL

HUNG 611 HIGH 25.9 29.1 POWERED BY OUTDOOR UNIT 5, 6, 7, 8

NOTES:

1. PROVIDE 3" ROOF PAD

2. ROUTE CONDENSATE LINE DOWN ONTO ROOF

3. PROVIDE LOW AMBIENT CONTROLS & CRANK CASE HEATER

4. PROVIDE REFRIGERANT LINE SET

5. PROVIDE FACTORY WALL MOUNTING HARDWARE

6. PROVIDE FACTORY WALL MOUNTED T-STAT.

7. PROVIDE SLIDE-IN AIR FILTER.

8. PROVIDE CONDENSATE DRAIN PUMP

HP

AC

11A

STEAM TRAP SCHEDULE

TAG SERVES LOCATION

CONDENSATE

LOAD (LBS/HR)

TRAP

SAFETY

FACTOR

MINIMUM

TRAP

CAPACITY

(LBS/HR)

DIFFERENTIAL

PRESSURE

(PSIG)

TYPE

CONNECTION

SIZE (INCH)

T-1 AC-11 STEAM

PRE-HEAT COIL

MECHANICAL

ROOM #3

BD-111

201 2 280 0.25 F&T 2-1/2

T-3 CART WASH SEE FLOOR

PLANS 10 2 280 0.25 F&T 3/4

T-4 WASHERS SEE FLOOR

PLANS 30 2 280 0.25 F&T 3/4

T-5 STERILIZERS SEE FLOOR

PLANS 38 2 280 0.25 F&T 3/4

AIR OUTLET SCHEDULE

TAG TYPE SERVICE MATERIAL MOUNTING PATTERN

BLADE

SPACING

(INCH)

BLADE

POSITION

BLADE

DEFLECTION NOTES

[1] MODULAR CORE CEILING

DIFFUSER SUPPLY STEEL LAY-IN 4-WAY

ADJUSTABLE N/A N/A N/A 1, 2, 3

[2] MODULAR CORE CEILING

DIFFUSER SUPPLY STEEL SURFACE 4-WAY

ADJUSTABLE N/A N/A N/A 1, 2

[3] SINGLE DEFLECTION FIXED

FACE GRILLE RETURN STEEL LAY-IN FIXED 3/4" FRONT

HORIZONTAL 35° 1, 2, 4

[4] SINGLE DEFLECTION FIXED

FACE GRILLE RETURN STEEL SURFACE FIXED 3/4" FRONT

HORIZONTAL 35° 1, 2

NOTES:

1. FINISH SHALL BE WHITE ANODIC ACRYLIC PAINT

2. PROVIDE SQUARE TO ROUND TRANSITION AS REQUIRED

3. PROVIDE 24"x24" PANEL FOR LAY-IN CEILING INSTALLATION AS REQUIRED (SEE ARCHITECTURAL PLANS FOR TBAR CEILING LOCATIONS)

4. PROVIDE FRAME WITH NO SCREW HOLES FOR INSTALLATION IN TBAR CEILING.

FAN COIL SCHEDULE

# MFG & MODEL LOCATION

SUPPLY FAN HYDRONIC COOLING COIL

NOTES

CFM

MIN

O.S.A.

CFM

E.S.P.

("W.C) HP RPM V/Ø FLA

SENSIBLE

CAPCAITY

(MBH)

EAT

(DB)

EAT

(WB)

LAT

(DB)

LAT

(WB)

EWT

(DB)

LWT

(DB) GPM

CARRIER 7.5 TON

MECHANICAL

ROOM #3

BD-111

3000 0 0.5 3 1009 460/3 4.4 92.9 80 67 51.9 51.6 45 55 27.6 1, 2, 3, 4, 5, 6

FC

GENERAL NOTES:

1. MINIMUM EFFICIENCY IS AT ARI STANDARD CONDITIONS.

2. ROUTE CONDENSATE DRAIN TO NEAREST DRAIN.

3. COOLING ONLY UNIT

4. PROVIDE FACTORY WALL MOUNTED T-STAT.

5. PROVIDE FULL ECONOMIZER

6. PROVIDE VFD FOR SPEED CONTROL

AIR HANDLING UNIT SCHEDULE

TAG MANUFACTURER

STANDARD

AIR FLOW

(CFM)

DESIGN

AIR FLOW

(CFM)

RETURN

AIR FLOW

(CFM)

MINIMUM

OSA

(CFM)

CHILLED WATER COOLING COIL HOT WATER HEATING COIL HEAT RECOVERY COIL SUPPLY FAN UNIT ELECTRICAL FILTERS

WEIGHT

(LBS) NOTES

TOTAL

(MBH)

SENS.

(MBH

EAT

DB/WB

(°F)

LAT

DB/WB

(°F)

COIL

ROW/FPI VELOCITY GPM

PD

(FT)

EWT/LWT

(DEG F)

SENS.

(MBH

EAT

(DB)

LAT

(DB)

COIL

ROW/FPI

VELOCITY

(FPM) GPM

PD

(FT)

TOTAL

(MBH)

SENS.

(MBH

EAT

DB/WB

(°F)

LAT

DB/WB

(°F)

COIL

ROW/FPI VELOCITY GPM

PD

(FT)

EWT/LWT

(DEG F)

TSP / ESP

(INCH) RPM MOTOR

BHP VOLT/PH

FLA

(PER FAN) PRE FINAL HEPA

NORTEK 16900 13240 0 13240 211.1 185.0 83/65 51.8 /

51.8 6/12 421.88 42 1.95 45/55 788.2 35 75.9 2 / 7 485 35 4.87 292 292 23 37.8 3/8 421.88 35 6.99 60.7/43.4 7.65 / 3.25 3600 (4) 7.4 480/3 9.4 MERV 8 MERV 11 99.97% 16900 1, 2, 3, 4, 5

AC

NOTES:

1. FAN WILL OPERATE AT CONSTANT VOLUME

2. PROVIDE SMOKE DETECTOR IN SUPPLY DUCT

3. PROVIDE VFD RATED MOTORS AND VFD ON SUPPLY FAN.

4. PROVIDE LIGHTS IN EACH ACCESS SECTION

5. AIR HANDLER UNIT TO BE DOUBLE WALL CONSTRUCTION PER VA STANDARDS

EXHAUST FAN SCHEDULE

TAG SERVICE LOCATION MANUF. FAN TYPE NUMBER

OF FANS

STANDARD

AIR FLOW

(CFM)

DESIGN

AIR

FLOW

(CFM)

TOTAL

SP (")

ESP

(") DRIVE RPM

SOUND DATA ELECTRICAL HEAT RECOVERY COIL

WEIGHT

(LBS) CONTROL NOTESSONES

IN/OUT

DBA

INLET

DBA

RAD. VOLT/PH

MOTOR BHP

(PER FAN)

FLA

(PER FAN)

TOTAL

(MBH)

SENS.

(MBH

EAT

DB/WB (°F)

LAT DB/WB

(°F)

COIL

ROW/FPI VELOCITY GPM PD (FT) EWT/LWT

(DEG F)

AC-11 EXHAUST MECHANICAL

ROOM #3 BD-111 NORTEK UTILITY 4 14210 13470 3.4 2 DIRECT 2212 16.8 / 22 68 70 460/3 6.12 8.1 292 292 70 / 46 50.7 / 36.1 8 / 10 421.88 35 9.26 43.4 / 60.7 10000 DDC 1, 2

EF

NOTES:

1. FAN WILL OPERATE AT CONSTANT VOLUME

2. PROVIDE VFD RATED MOTOR

(EXISTING) SINGLE DUCT REHEAT TERMINAL UNIT SCHEDULE

TAG MANUFACTURER

& MODEL TYPE SERVES

SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL

NOTES

INLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI

TITUS DESV CRV COORIDOR CB-14 10 320 320 0.5 0.25 0.05 16 15 320 12.1 55 90 160 140 0.02 1.2 0.09 2 10 1

TITUS DESV CRV COORIDOR CB-15 10 360 360 0.5 0.25 0.05 16 15 360 13.6 55 90 160 140 0.03 1.4 0.09 2 10 1

TITUS DESV CRV OFFICE BD106A 06 90 90 0.5 0.25 0.03 - - 90 3.4 55 90 160 140 0.01 0.3 0.1 2 10 1

TITUS DESV CRV OFFICE BD106B 06 180 180 0.5 0.25 0.06 - 13 180 6.8 55 90 160 140 0.03 0.7 0.1 2 10 1

TU

11-20

TU

11-21

TU

11-22

TU

11-23

NOTES:

1. TERMINAL UNIT TO BE RE-BALANCED TO CFM AIRFLOW AND GPM FLOW LISTED

FILTER RACK SCHEDULE

TAG MANUFACTURER /

MODEL TYPE CFM

INITIAL

ESP

FINAL

ESP

MEDIA

AREA

(SF)

SIZE

(INCHES) NOTES

FARR FILTRA 2000 FA

1561 HEPA FILTER HEPA 620 0.25 0.75 390 24 X 24 X

11.5 -

FR

DH

DH

DH

REHEAT WATER COIL SCHEDULE

TAG MANUFACTURER

& MODEL TYPE SERVES VALVE

CONNECTION

SIZE CFM STATIC PRESSURE NC LEVELS HOT WATER HEAT COIL

NOTES

INLET OUTLET MAX MIN INLET DOWN MIN RAD. DISCH. CFM MBH EAT LAT EWT LWT APD GPM WPD ROWS FPI

VARITRANE VCWF ANTE B368B 2-WAY 08 08 200 200 0.5 0.25 0.05 16 15 200 7.6 55 90 160 140 0.04 0.76 0.34 2 10 1, 2, 3

VARITRANE VCWF VESTIBULE B367 2-WAY 08 08 200 200 0.5 0.25 0.05 16 15 200 7.6 55 90 160 140 0.04 0.76 0.34 2 10 1, 2, 3

VARITRANE VCWF SCOPE STORAGE

B368D 3 - WAY 08 08 220 220 0.5 0.25 0.05 16 15 220 8.3 55 90 160 140 0.04 0.83 0.34 2 10 1, 2, 3

1. PROVIDE TRANSFORMER FOR VALVES

2. DDC CONTROLS

3. PROVIDE LEFT OR RIGHT HAND COIL CONNECTION AS REQUIRED TO MATCH

CONFIGURATION SHOWN ON PLANS.

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

M-601

SCHEDULES - MECHANICAL

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

EXHAUST FAN SCHEDULE

# MFG MODEL SERVICE DRIVE HIGH

CFM

LOW

CFM

TSP (WG") FAN

RPM VFD

MOTOR

NOTES

HP VOLTS PHASE

GREENHECK QEID-12-100

WET

EXHAUST

SPS

DIRECT 4000 2350 1.75 3500 YES 3 480 3 1, 2, 3

GREENHECK SQ-130HP-VG SWING

SPACE DIRECT 1100 875 1.5 1900 NO 3/4 277 1 1, 3, 4, 5

EF

11A

GENERAL NOTES:

1. FAN WILL OPERATE AT CONSTANT VOLUME

2. PROVIDE VFD

FIRE AND SMOKE DAMPER SCHEDULE

TAG MANUFACTURER TYPE UL RATING

VELOCITY

RATING

(FPM)

BLADE POSITION

MAX

PRESSURE

DROP

(INCH WC)

APPLICATION NOTES

RUSKIN DYNAMIC FIRE

DAMPER 1-1/2 HOUR 3000

CURTAIN TYPE

OUT OF AIR

STREAM

0.03 VERTICAL /

HORIZONTAL 1, 2, 3

NOTES:

1. LEAKAGE CLASS I PER UL STANDARD 555S

2. PROVIDE SQUARE TO ROUND ADAPTOR AS REQUIRED

3. INTERLOCK FIRE DAMPER WITH FIRE ALARM SYSTEM

TEMPORARY PORTABLE AIR CONDITIONER UNIT

# MFR MODEL # CFM

COOLING

CAPACTIY

(MBH)

ELECTRICAL DUCT

SIZE (IN) EER NOTES

VOLT PHASE FLA MOCP

GLOBAL

INDUSTRIAL 292660 465 13.2 115 1 11.9 15 12 11 -

GLOBAL

INDUSTRIAL 292660 465 13.2 115 1 11.9 15 12 11 -

PAC

11A

PAC

11B

PUMP SCHEDULE

TAG MANUFACTURER

MODEL LOCATION SERVING TYPE FLUID

PERFORMANCE MOTOR

WEIGHT

(LBS) NOTESMAX

FLOW

(GPM)

MIN FLOW

(GPM)

HEAD

(FT. WC) PUMP EFF HP RPM VOLT/PH

ARMSTRONG

COMPASS

MECH RM

M.E.R. #13

HEAT

RECOVERY

COIL

IN-LINE WATER -

GLYCOL 35 35 15 66 1/6 1750 120/1 20 1, 2

ARMSTRONG

COMPASS

MECH RM

M.E.R. #13

HEAT

RECOVERY

COIL

IN-LINE WATER -

GLYCOL 35 35 15 66 1/6 1750 120/1 20 1, 2

NOTES:

1. 20% GLYCOL MIX

P 11A

P 11B

AIR SEPARATOR SCHEDULE

TAG MANUFACTURER

MODEL LOCATION SERVING

INLET

SIZE (IN)

FLOW

RATE

(GPM)

WEIGHT

(LBS) NOTES

SPIROVENT

VDT-200

MECH RM

M.E.R. #13

HEAT

RECOVERY 2 35 66 1

NOTES:

1. PROVIDE SEPARATOR WITH REMOVABLE HEAD CAPS FOR CLEANING

AS

EXPANSION TANK SCHEDULE

TAG MANUF /

MODEL LOCATION SERVING

ACCEPTABLE

VOLUME

(GALLON)

TANK

VOLUME

(GAL)

MIN / MAX

OPERATING

PRESSURE (PSI)

OPERATING

TEMP (°F) NOTES

AMTROL

AX-15V-DD

MECH RM

M.E.R. #13

HEAT

RECOVERY 3.2 8.6 12 / 54 40 - 70 1, 2

NOTES:

1. PROVIDE SEPARATOR WITH REMOVABLE HEAD CAPS FOR CLEANING

2. PROVIDE PRESSURE RELIEF VALVE AT 60 PSI

ET

SPECIAL EQUIPMENT CONNECTION SCHEDULE

SYMBOL DESCRIPTION MANUFACTURER AND

CATALOG # QUANTITY

CONNECTIONS

UTILITY REQUIREMENTS

ESTIMATED RO

WATER USAGE PER

EQUIPMENT UNIT

GALLONS / HOUR

COMBINED

ESTIMATED RO

WATER USAGE

GALLONS / HOUR

COMBINED

ESTIMATED RO

WATER USAGE

(GPM)

NOTES

HW CW V W IW STEAM CD

RETURN RO AIR

VISION 1327 (QT.2) SIDE BY SIDE CART AND UTENSIL

WASHER/DISINFECTOR - SHARED SERVICE / DOUBLE DOOR / PIT

MOUNTED / COMMON SERVICE AREA JUNCTION PANELS

STERIS VISION 1327 1 1" 1" - - F.D. 1-1/2" 1-1/2" 3/4" 1/2"

HARDNESS: 50-80 PPM. PURE WATER

USAGE: 50 GAL INITIAL CYCLE, 14 GAL /

SEQUENTIAL CYCLES. MAX 28 GPM

112 112 1.9 1, 2, 7

AMSCO 50 REPROCESSING SINK - 3 BAY/120" LONG/HEIGHT

ADJUSTABLE/RIGHT TO LEFT WORK FLOW STERIS AMSCO 50 4 1/2" 1/2" - - F.S. - - 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER

USAGE: 2 GMP 15 60 1.0 1, 2, 8, 9

AMSCO 50 REPROCESSING SINK - 3 BAY/120" LONG/HEIGHT

ADJUSTABLE/LEFT TO RIGHT WORK FLOW STERIS AMSCO 50 2 1/2" 1/2" - - F.S. - - 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER

USAGE: 2 GMP 15 30 0.5 1, 2, 8, 9

AMSCO 7052HP SINGLE-CHAMBER WASHER/ DISINFECTOR - DOUBLE

DOOR/ STEAM HEAT/ ACU-RINSE/ VENTED/ OFFSET MOUNTED AMSCO 705HP 3 1/2" 1/2" - - F.D. 1/2" 1/2" 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER

USAGE: 12 GAL / CYCLE. 14 GPM 12 36 0.6 1, 2, 5, 6, 7

AMSCO 7052HP SINGLE-CHAMBER WASHER/DISINFECTOR - DOUBLE

DOOR/ STEAM HEAT/ ACU-RINSE/ VENTED/ OFFSET MOUNTED AMSCO 705HP 2 1/2" 1/2" - - F.D. 1/2" 1/2" 1/2" 1/4" HARDNESS: 100-200 PPM. PURE WATER

USAGE: 12 GAL / CYCLE. 14 GPM 12 24 0.4 1, 2, 5, 6, 7

AMSCO EVOLUTION-NA MEDIUM STEAM STERILIZER -

26X37.5X66"(660X953X1676MM)(958L) DOUBLE

HINGED LR DOORS/ RECESSED 2 WALLS/ STEAM HEAT

AMSCO EVOLUTION

STEAM STERILIZER 4 - 3/4" - - F.D. 3/4" 3/4" - 1/4" - - - - -

ADVANTAGE PLUS ENDOSCOPE WASHER / DISINFECTOR MEDIVATORS

ADVANTAGE PLUS 2 1/2" - - - F.D. - - 1/2" 1/4" HARDNESS: 50-200 PPM. PURE WATER

USAGE: 11.5 GAL / CYCLE. 2.6 GPM 3 6 0.1 1, 2, 3, 4, 7

INNOWAVE PRO SONIC IRRIGATOR - 60 LUMEN CAPACITY/ 208-220

VOLT/3 PHASE, 18kW. CENTER OVER DRAIN.

INNOWAVE PRO SONIC

IRRIGATOR 4 3/4" 3/4" - 2-1/8" F.D. - - 3/4" 1/2" HARDNESS: 125 PPM. PURE WATER USAGE:

38 GAL / CYCLE. 8 GPM 25 100 1.7 PROVIDE ELIMINIZER

COMBO DRYER/FILTER

INNOWAVE UNITY ULTRASONIC IRRIGATOR INNOWAVE IRRIGATOR 1 3/4" 3/4" - 2-1/8" F.D. - - - - - - - - 1, 2

ESTIMATED TOTAL RO WATER

DEMAND (GPM) 6.1

NOTES:

1. PROVIDE UTILITY CONNECTIONS WITH SHUTOFF DISCONNECTS WITHIN 2'

OF UNIT PER MANUFACTURE RECOMMENDATIONS.

2. PROVIDE VACUUM BEAKERS ON SERVICE LINES PER MANUFACTURE

RECOMMENDATIONS.

3. PROVIDE 1 MICRON FILTER FOR TEMPERED WATER CONNECTION

4. PROVIDE THERMAL MIXING VALVE FOR WATER CONNECTION

5. PROVIDE 1/4"CA CONNECTION FROM WASHER SUPPLY AIR CONNECTION.

6. PROVIDE 3/4" DRAIN KIT FOR CONVEYERS (UP TO 4 CONVEYERS).

7. ROUTE EACH WET VENT CONDENSATE DRAIN TO NEAREST FLOOR DRAIN

8. PROVIDE PRESSURE REGULATOR FOR AIR GUN.

9. PROVIDE PRESSURE REDUCING VALVE FOR WATER GUN.

2A

2B

EF

9A

3. PROVIDE CORROSION RESISTANT COMPONENTS

4. PROVIDE SPEED CONTROL

5. ELECTRIC STARTER NOT REQUIRED WITH VARIGREEN SPEED

CONTROL MOTOR

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

M-602

SCHEDULES - MECHANICAL

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

SE

38'-0"

NW

SE

0'-0"

S 176'-7"

S 143'-3"

E 146'-6"

E 197'-4"

E 201'-0"

SE

76-0

SE

114-0

SE

152-0

SE

190-0

SE

179-4

NW

14-9

NW

3-6

SE

152-10

NE

380-0

NE

304-0

NE

342-0

SE

152-0

SE

190-0

SE

179-4

SE

152-10

SE

38'-0"

NW

SE

0'-0"

SE

76-0

SE

114-0

NW

14-9

NW

3-6

NE

383'-9"

NE

342-0

NE

304-0

UP

NE

421'-9"

NE

380-0 NE

383'-9"

SEE MD401 FOR DEMO WORK

IN MECHANICAL ROOM

SEE MD402 FOR DEMO

WORK IN THIS AREA

SEE MD403 FOR DEMO

WORK IN THIS AREA

REMOVE EXISTING CEILING GRILLES AND

DIFFUSERS IN THIS SPACE. CLEAN AND

PREPARE GRILLS TO BE REPLACED IN SAME

LOCATIONS AS BEFORE IN NEW CEILING.

SEE MD404 FOR DEMO

WORK IN THIS AREA

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

DEMO NOTES

KEY PLAN

LEGEND

MD101

BASEMENT DEMOLITION PLAN - OVERALL -

MECHANICAL

D & T

TRUE

NORTH

PROJECT

NORTH

NURSING

TOWER

AREA OF

RENOVATION

WORK

KEY PLAN:NTS

1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN

DEMOLITION AND NEW WORK. COORDINATE DEMOLITION

WORK WITH THAT OF OTHER TRADES.

2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT

WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED

TO BE RETURNED TO THE OWNER, SHALL BECOME THE

PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF

ITEMS ON THE PROJECT SITE IS PROHIBITED.

3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR

PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT

AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST

AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN

AND AROUND BUILDING DURING DEMOLITION. PREVENT

INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE

ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.

IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE

CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE

MEASURES TO PREVENT DUST MIGRATION.

4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING

REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND

PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES

SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT

FIRST OBTAINING PERMISSION FROM THE UTILITY COMPANY

AND/OR OWNER. PROVIDE TEMPORARY SERVICES AS

REQUIRED.

5. REMOVE AND DISPOSE OF EXISTING MECHANICAL

EQUIPMENT AS SHOWN, UNLESS NOTED OTHERWISE.

COORDINATE WITH ARCHITECT, AREAS OF DEMOLITION

AROUND, ADJACENT, OR CONNECTED TO EXISTING

MECHANICAL EQUIPMENT THAT IS TO REMAIN.

TRUE

NORTH

PROJECT

NORTH

1/8" = 1'-0"1 BASEMENT DEMOLITION PLAN - OVERALL - MECHANICAL

EXISTING WORK (LIGHT)

DEMOLITION (DARK)

POINT OF DEMOLITION

DEMOLITION KEY

SPS

SWING

SPACE

WAREHOUSE

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

NE

342-0

NE

304-0

FLASH TANK100-CP-#6

20X4 TR

(HIGH) O.A.I. OPN'G

22X20 W/ WMS 3,300

(LOW)

O.A.I. OPN'G

44X44 W/ WMS

13,300

24X24 DN

AC-#11

22X20

FC

4"T & SD

36X18

36X18 TR

20X20

UV-#44

8X8

3A-#11

34X24 DN

MCC

EF-#11

24X18 DN

18X24 DN

18X24 24X16

EF-#44

14X60 TR

AFM-#11-B

AFM-#11-A

24X24

SH-11

24X18

34X24

12"ØAUTO. D

EF-#74

12"Ø DN

24X18

24X16 34X24

R

R

PLEMUM-42"L

X 50"W X 60"H

24X18

34X24

(E) STEAM PRESSURE REDUCING

STATION TO REMAIN

DEMO AND REMOVE AIR

HANDLER, HUMIDIFIER, AND

ASSOCIATED DUCTWORK

DEMO AND REMOVE EXHAUST FAN

AND ASSOCIATED DUCTWORK

DEMO AND REMOVE EXHAUST FAN

AND ASSOCIATED DUCTWORK

DEMO AND REMOVE EXHAUST FAN

AND ASSOCIATED DUCTWORK

(E) CONDENSATE RECEIVER, PUMP,

FLASH TANK, AND ASSOCIATED

STEAM PIPING TO REMAIN

DEMO AND REMOVE FAN

COIL AND ASSOCIATED

SUPPLY AND OUTSIDE AIR

DUCTWORK

DEMO ETO STERILIZER EXHAUST DUCT AND

REMOVE ETO EXHAUST FAN ON ROOF. CAP,

SEAL, AND ABANDON DUCT UP TO ROOF

AUTO DAMPER (TYP)

(E) STEAM HEATING WATER

SYSTEM TO REMAIN

(E) OUTSIDE AIR DUCT AND

DAMPER TO REMAIN. CAP FOR

FUTURE RECONNECTION.

(E) 48X30

(E) 48X30

DEMO AND REMOVE

HEAT EXCHANGER

(E) 48X30 DUCT THRU EXTERIOR

WALL TO REMAIN. COORDINATE

EXTENT OF DEMOLITION WITH

NEW WORK.

(E) EXPANSION TANK

TO REMAIN

LOADING DOCK

TRASH & LINEN DOCK

(E) LOUVER

REUSE EXISTING HVAC

GRILLES IN THIS AREA

DEMO AND REMOVE

EQUIPMENT PAD

DEMO AND REMOVE

EQUIPMENT PAD

SEE MD405 FOR

CONTINUATION

(TYP)

MECHANICAL #3

BD-111

ELECTRICAL

BD-110

SIGNAL

BD-110B

TELE

BD-110A

VESTIBULE

BD-110C

COMMON SPACE

CONFERENCE

BD-113

CORRIDOR

CB-12

PROVIDE 76" WIDE BY 120" HIGH

WALL OPENING FLUSH WITH

LOADING DOCK FLOOR. SEE

STRUCTURAL FOR OPENING

FRAMING DETAILS.

DEMO AND REMOVE 9.5'

SECTION OF CEMENT

EQUIPMENT PAD FLUSH

TO FLOOR

RF-#11

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

DEMO NOTES

KEY PLAN

LEGEND

MD401

BASEMENT MECHANICAL ROOM

DEMOLITION PLAN - MECHANICAL

D & T

TRUE

NORTH

PROJECT

NORTH

NURSING

TOWER

AREA OF

RENOVATION

WORK

KEY PLAN:NTS

1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN

DEMOLITION AND NEW WORK. COORDINATE DEMOLITION

WORK WITH THAT OF OTHER TRADES.

2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT

WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED

TO BE RETURNED TO THE OWNER, SHALL BECOME THE

PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF

ITEMS ON THE PROJECT SITE IS PROHIBITED.

3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR

PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT

AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST

AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN

AND AROUND BUILDING DURING DEMOLITION. PREVENT

INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE

ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.

IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE

CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE

MEASURES TO PREVENT DUST MIGRATION.

4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING

REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND

PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES

SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT

FIRST OBTAINING PERMISSION FROM THE UTILITY COMPANY

AND/OR OWNER. PROVIDE TEMPORARY SERVICES AS

REQUIRED.

5. REMOVE AND DISPOSE OF EXISTING MECHANICAL

EQUIPMENT AS SHOWN, UNLESS NOTED OTHERWISE.

COORDINATE WITH ARCHITECT, AREAS OF DEMOLITION

AROUND, ADJACENT, OR CONNECTED TO EXISTING

MECHANICAL EQUIPMENT THAT IS TO REMAIN.

DEMO KEY PLAN

TRUE

NORTH

PROJECT

NORTH

1/4" = 1'-0"1 BASEMENT MECHANICAL ROOM DEMOLITION PLAN- MECHANICAL

EXISTING WORK (LIGHT)

DEMOLITION (DARK)

POINT OF DEMOLITION

DEMOLITION KEY

SPS

SWING

SPACE

WAREHOUSE

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text

EXPIRES 2/20/22

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 44961

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text K

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

76-0

SE

114-0

SE

152-0

SE

190-0

SE

179-4

SE

152-10

SE

76-0

SE

114-0

NE

383'-9"

NE

342-0

NE

304-0

UP

NE

380-0

CG-4

CD-B-4

8X12

11-13

CD-B-4

6X12

CD-B-4

8X12

CD-B-4

6X12

16X10

CG-4

CG-4

11-14

11-16

CD-A-4

6X8

CG-1

8X8

CG-1

12X4

CD-A-4

11-17

6X8

12X6

12X8

CG-2

CG-1

12X4

12X10

11-19

12X6

CD-A-4

6X8

CG-1

CD-A-3

130 CG-2

11-15

11-9

CD-A-4

CD-A-4

6x8

UP TO

INTERSTITIAL

CD-A-4

100 3

CD-A-4

100 3

CD-A-4

100 3

CD-A-4

FOR DEMOLITION WORK

IN MECHANICAL ROOM

SEE MD401

NON-STERILE

STORAGE

BD-104

M TOILET

BD-103

HAC

BD-103A

BREAK ROOM

BD-112D

OFFICE

BD-112C

OFFICE

BD-112B

OFFICE

BD-112A

OFFICE

BD-112

CORRIDOR

CB-14

CORRIDOR

CB-13

CORRIDOR

CB-10

F TOILET

BD-103C

CORRIDOR

CB-8

LOADING DOCK

BD-107

SPEES DESIGN BUILD

625 1ST AVE, UNIT 301

SEATTLE, WA 98101

(360) 223-8994

RAY SPEES, PRINCIPAL

VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA

06/25/2021 Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MKK AGG

RENOVATE & EXPAND SEATTLE

STERILE PROCESSING SERVICES

IN BUILDING 100

663-20-102

KARTCHNER ENGINEERING

101 S STEVENS, SUITE 201

SPOKANE, WA 99201

(509) 922-0383

100% CD

DEMO NOTES

KEY PLAN

LEGEND

MD402

BASEMENT DEMOLITION PLAN - SOUTH -

MECHANICAL

D & T

TRUE

NORTH

PROJECT

NORTH

NURSING

TOWER

AREA OF

RENOVATION

WORK

KEY PLAN:NTS

1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN

DEMOLITION AND NEW WORK. COORDINATE DEMOLITION

WORK WITH THAT OF OTHER TRADES.

2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT

WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED

TO BE RETURNED TO THE OWNER, SHALL BECOME THE

PROPERTY OF THE CONTRACTOR. STORAGE OR SALE OF

ITEMS ON THE PROJECT SITE IS PROHIBITED.

3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR

PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT

AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST

AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN

AND AROUND BUILDING DURING DEMOLITION. PREVENT

INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE

ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE.

IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE

CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE

MEASURES TO PREVENT DUST MIGRATION.

4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING

REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND

PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES

SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT

FIRST…