This document provides details for a federal solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20. The solicitation, numbered 36C26023R0021, seeks proposals for upgrades to the SPS OM system under opportunity Y1DA--CON 663-20-102. Attachment 11 contains electrical drawings as part of the solicitation documentation. Responses are due based on the solicitation requirements for upgrades to the specified SPS OM system for the agency. Relevant details include the solicitation number, opportunity name, type of opportunity, and involved agency.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF UON.
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
COMMUNICATION OUTLETS
FOR ALL TELECOMMUNICATION OUTLETS, ROUTE 3/4" CONDUIT UNDERGROUND IF
NECESSARY AND STUB TO ACCESSIBLE CEILING SPACE WITH CABLING AS
DESCRIBED IN ELECTRICAL SPECIFICATIONS.
# - INDICATES QUANTITY OF VOICE AND DATA JACKS
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
OUTLET, TELEVISION
BLANK = 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CTTV SYSTEM).
INTERCOM; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
E-001 GENERAL NOTES, ABBREVIATIONS AND LEGENDS
ED101 OVERALL LIGHTING DEMOLITION PLAN
ED102 OVERALL POWER AND SPECIAL SYSTEMS DEMOLITION PLAN
ES100 SITE ELECTRICAL PLAN
ES101 OVERALL ELECTRICAL PLAN
EL101 LIGHTING PLAN - NORTH
EL102 LIGHTING PLAN - SOUTH
EP101 POWER PLAN - NORTH
EP102 POWER PLAN - SOUTH
EP103 POWER PLAN - BASEMENT WAREHOUSE
ET101 SPECIAL SYSTEMS PLAN - NORTH
ET102 SPECIAL SYSTEMS PLAN - SOUTH
E-401 ENLARGED DEMOLITION PLANS
E-402 ENLARGED PLANS
E-403 ENLARGED ENERGY PLANT - ELECTRICAL PLAN
E-404 ENLARGED FLOOR PLANS AND SECTION - CART LIFT
E-405 ENLARGED PARTIAL ROOF PLAN
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 SCOPE PROCESSING AREA ONE-LINE DIAGRAM - EXISTING
E-602 SCOPE PROCESSING AREA ONE-LINE DIAGRAM - REVISED
E-603 SPS TRAILER ONE-LINE DIAGRAMS
E-604 PARTIAL ONE-LINE DIAGRAM AND LOAD SCHEDULES - CART
LIFT
E-605 ELECTRICAL LOAD SCHEDULES - REVISED
E-606 ELECTRICAL LOAD SCHEDULES - REVISED
E-607 ELECTRICAL SCHEDULES
E-701 OVERALL ELECTRICAL PLAN
E-702 SWING SPACE-LIGHTING AND ELECTRICAL DEMO PLAN
E-703 REVISED LIGHTING AND ELECTRICAL PLAN
E-704 SWING ROOM PARTIAL ONE-LINE DIAGRAMS
E-705 ELECTRICAL LOAD SCHEDULES
S H E E T I N D E X
THIS SHEET IS FOR REFERENCE ONLY AND ALL SYMBOLS, NOTES
AND ABBREVIATIONS MAY NOT APPLY TO THIS PROJECT
SHUNT TRIP PUSHBUTTON OR KEY-SWITCH
PANELBOARD, SWITCHBOARD, OR SWITCHGEAR.
DASHED BOX INDICATES CODE REQUIRED WORKING
CLEARANCE
HARDWIRED CONNECTION
THERMOSTAT
ST
T
VFD VARIABLE FREQUENCY DRIVE
DRAW OUT SWITCH/PLUG-RECEPTACLE CONNECTION
NORMALLY OPEN CONTACT (WHEN DE-ENERGIZED)
NORMALLY CLOSED CONTACT (WHEN DE-ENERGIZED)
E L E C T R I C A L L E G E N D
CONDUIT OR EQUIPMENT TO BE REMOVED
HH
CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 GND. UNLESS
SHOWN OTHERWISE. (EXAMPLE SHOWN: TO PANEL
L1, CIRCUIT 2)
L1-2
CONDUIT HOME RUN - SEE FEEDER SCHEDULE
CONDUIT CONCEALED IN WALL, CEILING, UNDER
FLOOR, IN FLOOR SLAB, OR ROUTED UNDERGROUND
CONDUIT EXPOSED
OVERHEAD ELECTRICAL
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
CIRCUIT BREAKER, RATING/NO. OF POLES WITH
THERMAL MAGNETIC CIRCUIT BREAKER TRIP, UNLESS
OTHERWISE NOTED
MANUAL OR AUTOMATIC TRANSFER SWITCH.
JUNCTION BOX
HANDHOLE
TRANSFORMER
BATTERY
GROUND ROD IN GROUND ROD BOX
CB
T
ROD SYMBOLS
EXISTING CONDUIT ROUTED UNDERGROUND,
EXISTING TO REMAIN UNLESS OTHERWISE NOTED
##NG
EXISTING CONDUIT EXPOSED, EXISTING TO REMAIN
UNLESS OTHERWISE NOTED
# NEW LUMINAIRE CONTROL. SEE LIGHTING CONTROL
LEGEND LOCATED ON LIGHTING SHEETS.
OS CEILING MOUNTED OCCUPANCY SENSOR(S).
PROVIDE SHOP DRAWINGS OF OCCUPANCY SENSOR
SYSTEM AS PER PROJECT SPECIFICATION AS PART
OF THE SUBMITTAL PROCESS PRIOR TO
COMMENCEMENT OF LABOR. SEE LIGHTING
CONTROL LEGEND LOCATED ON LIGHTING SHEETS.
PE
SWITCH
2 = DOUBLE POLE SWITCH
3 = THREE WAY SWITCH
4 = FOUR WAY SWITCH
K = KEY OPERATED SWITCH
T = SWITCH WITH TIMER
MS = MASTER SWITCH TO CONTROL ALL
FIXED LUMINAIRES IN GUEST UNIT
X
LUMINAIRE, SURFACE
LUMINAIRE, RECESSED
STRIP, SURFACE
HALF SHADED FIXTURE DENOTES: EMERGENCY
LUMINAIRE
LUMINAIRE, WALL MOUNT
LIGHTED EXIT SIGN, ARROW INDICATES DIRECTION
EMERGENCY WALL PACK
LUMINAIRE, POLE MOUNTED
LUMINAIRE, PENDANT MOUNTED
POWER
LUMINAIRES (DIMENSIONS OF SYMBOL WILL VARY DEPENDING ON LUMINAIRE)
LUMINAIRE TYPE IDENTIFICATION: LUMINAIRES INDICATED BY THE FOLLOWING
NOTATIONS:
L# = NEW LUMINAIRE UON, REFER TO LUMINAIRE SCHEDULE FOR DETAILS
U# = NEW LUMINAIRE UON IN DWELLING UNIT, REFER TO LUMINAIRE SCHEDULE FOR
DETAILS
S# = NEW LUMINAIRE UON, EXTERIOR SITE, REFER TO LUMINAIRE SCHEDULE FOR
DETAILS
# = EXISTING LUMINAIRE, UNLESS OTHERWISE NOTED
EL# = EXISTING LUMINAIRE TO BE RELOCATED
EN# = NEW LOCATION OF EXISTING LUMINAIRE
100/3
FLOOR MOUNTED TELECOMMUNICATIONS OUTLET.
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
M
CS
WAP WIRELESS ACCESS PORT
WALL MOUNTED SPEAKER/CLOCK COMBINATION
C WALL CLOCK
CABLE TRAY
RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUITA/V
SPEAKER, CEILING MOUNTED
I = INTERCOM SPEAKER
SPEAKER, WALL MOUNTED, MTD. 7'-6" AFF UON.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" AFF UON.
M = SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE,
MTD. 4'-6" AFF.
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UON.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
S = STAFF STATION
FIBEROPTICS LINE = FO
TELEPHONE LINE = T
COMMUNICATION
LUMINAIRE, DOWNLIGHT
M
M
S
SPECIAL PURPOSE RECEPTACLE, RATING AS
INDICATED
STANDARD RECEPTACLES: 125V, 20A 18" AFF, UON.
TYPES: SIMPLEX /DUPLEX /QUADRUPLEX /FLOOR
DUPLEX /FLOOR QUADRUPLEX
GFCI RECEPTACLES: 125V, 20A 18" AFF, UON. TYPES:
SIMPLEX /DUPLEX /QUADRUPLEX
C = CEILING MOUNTED
S = HALF SWITCHED
I = ISOLATED GROUND
TR = TAMPER RESISTANT
a = LOWER CASE LETTER INDICATES SWITCH
CONTROL
2" = MEASUREMENT INDICATES HEIGHT
ABOVE BACKSPLASH/MILLWORK
A = INDICATES MOUNT ABOVE
BACKSPLASH/MILLWORK. COORDINATE
HEIGHT WITH TRADES.
USB = INDICATES 20A 120V DUPLEX
RECEPTACLE WITH USB CHARGER.
CT = SWITCHED RECEP, INDICATES FULL
CONTROLLED DEDICATED 20A 125V
DUPLEX
CH = SWITCHED RECEP, INDICATES HALF
CONTROLLED DEDICATED 20A 125V
DUPLEX
200AS100AF
M
DISCONNECT SWITCH, FUSED 200=SWITCH RATING,
100=FUSE RATING
DISCONNECT SWITCH, NON FUSED (60A) INDICATES
AMPERAGE RATING
MAGNETIC MOTOR STARTER W/DISCONNECT
MAGNETIC MOTOR STARTER
FVNR = FULL VOLTAGE
NON-REVERSING
FVR = FULL VOLTAGE
00 = NEMA SIZE
UTILITY WATT HOUR METER
60A
M
MOTOR RATED SWITCH. WHERE "M" INDICATED,
PROVIDE A MANUAL MOTOR STARTER W/OVERLOAD
CIRCUIT BREAKER DISCONNECT
(60A) INDICATES AMPERAGE RATING
60A
MOTOR
POWER (CONTINUED)
3 CURRENT TRANSFORMER, NUMBER INDICATES
NUMBER OF C.T.'S
DROP CORD, SINGLE CONVENIENCE OUTLET
X
ELECTRICAL STRIP MOLD
ALARM, TAMPER SWITCH
DETECTION, GAS
C = CARBON DIOXIDE TRANSMITTER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, SMOKE
DETECTOR, SMOKE, FOR DUCT
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" AFF UNLESS NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS
DENOTE CODE.
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
FIRE SPRINKLER WATER FLOW SWITCH
2-4-6
2-4-6
1. "GENERAL NOTES" APPLY TO ALL ELECTRICAL DRAWINGS. "SHEET NOTES" APPLY TO ONLY THE SHEETS ON WHICH THEY OCCUR. "KEYNOTES"
APPLY ONLY WHERE CALLED OUT.
2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED, OR MODIFIED BY CONTRACTOR UNLESS OTHERWISE NOTED.
3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN.
4. LUMINAIRES SHOWN ON DRAWINGS FOR QUANTITY AND CIRCUITING ONLY. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS.
5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON CU COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS. IF ALUMINUM IS ALLOWED, CONTRACTOR IS RESPONSIBLE TO RE-SIZE CONDUCTORS AND CONDUIT ACCORDING TO NEC AMPACITIES FOR LOADS SHOWN ON DRAWINGS.
6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET. QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN FROM THE 75°C COLUMN.
7. MINIMUM CONDUIT IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1" UNLESS NOTED OTHERWISE ON PLANS. CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 1/2" OR AS INDICATED IN SPECIFICATIONS.
PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR
TRANSFER DEVICES.
8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE KEPT ENTIRELY INDEPENDENT OF ALL OTHER
WIRING AND EQUIPMENT AND SHALL MEET ALL REQUIREMENTS OF NEC SECTION 700.10.
9. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS.
10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE SPECIFICATIONS.
11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
12. COORDINATE EXACT LOCATION OF ALL OUTLETS, COMBINATION CLOCK/SPEAKERS, SPEAKER, FA DEVICES, ETC., WITH THE ARCHITECTURAL
ELEVATIONS PRIOR TO COMMENCING WORK.
13. COORDINATE USE OF CEILING SPACE WITH ALL TRADES PRIOR TO COMMENCING WORK. MANY AREAS ARE VERY CONGESTED AND REQUIRE
CLOSE COORDINATION.
14. COORDINATE INSTALLATION REQUIREMENTS FOR OCCUPANCY SENSOR LIGHTING CONTROL WITH THE MANUFACTURER. PROVIDE ALL APPURTENANCES AS REQUIRED BY THE MANUFACTURER. PROVIDE ADDITIONAL SENSORS WHERE NECESSARY TO PROVIDE COMPLETE
COVERAGE IN EACH ROOM CONTROLLED BY OCCUPANCY SENSORS.
15. COORDINATE THE INSTALLATION OF ALL EXTERIOR OUTLET BOXES WITH THE TYPE OF MASONRY IN EACH AREA. CUT ALL FLUTED BLOCKS SO THAT THE BOX IS INSTALLED FLUSH. SEE ARCHITECTURAL DETAILS FOR MOUNTING REQUIREMENTS.
16. SEAL ALL CONDUIT PENETRATIONS OF FLOORS & FIRE RATED ASSEMBLIES WITH U.L. APPROVED MATERIALS AND METHODS TO MAINTAIN FIRE RATING. PROTECT ALL OPENINGS FOR STEEL ELECTRICAL BOXES IN FIRE RATED WALLS WITH U.L. APPROVED MATERIALS AND METHODS TO
MAINTAIN THE FIRE INTEGRITY.
17. PROVIDE ADDITIONAL CONDUIT SLEEVES THROUGH WALLS WHERE REQUIRED FOR ROUTING OF SIGNAL SYSTEM WIRING NOT REQUIRED TO BE RUN IN CONDUIT. EACH SLEEVE SHALL BE DEDICATED TO EACH SIGNAL SYSTEM. SLEEVES ROUTED THROUGH RATED WALLS SHALL BE
SEALED WITH U.L. MATERIALS AND METHODS TO MAINTAIN FIRE RATING OF WALL.
18. SEE MECHANICAL/PLUMBING DRAWINGS AND SUBMITTALS FOR EXACT LOCATIONS AND ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO
INSTALLATION.
19. ALL LOW VOLTAGE SYSTEMS NOT RUN IN CONDUIT SHALL HAVE MINIMUM 3/4"C. ROUTED FROM THE DEVICE THROUGH WALLS INTO THE ACCESSIBLE CEILING SPACE. NO CABLING SHALL BE ROUTED IN THE WALLS OR INACCESSIBLE LOCATION WITHOUT CONDUIT.
20. GFI RECEPTACLES ARE REQUIRED WITHIN 6 FT OF ALL SINKS, ON THE EXTERIOR BELOW 8 FT FROM THE FINISH FLOOR, AND ON ALL ROOFS.
21. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER AND THE DIVISION OF THE STATE ARCHITECT.
G E N E R A L N O T E S
"a"
"NL"
"E"
INDICATES PANELBOARD AND CIRCUIT PROVIDING
POWER TO LUMINAIRES IN SAME ROOM/AREA, UON.
INDICATES TYPE PER LUMINAIRE SCHEDULE.
(SEE "LUMINAIRES" LEGEND ON THIS SHEET FOR MORE
INFORMATION)
INDICATES NIGHT LIGHT LUMINAIRE.
INDICATES CONTROL PER SWITCH.
INDICATES POWER TO EMERGENCY LIGHTING
CONTAINED IN SAME ROOM/AREA.
#ENLa
PNL-2
INDICATES CIRCUIT NUMBER.
INDICATES POWER SOURCE."PNL"
"2"
RECEPTACLE, TYPICAL:
LUMINAIRE, TYPICAL:
X-Xa/E
X-XE
X-Xa
X-X
CIRCUIT DESIGNATION
DETAIL/PLAN1
SCALE
SECTION
A
XXX
A
XXX
XXX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
DETAIL AREA
SHEET ON WHICH
SECTION APPEARS
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
SECTION LETTER
DETAIL/PLAN NUMBER
XXX
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
SHEET WHERE DETAIL
IS TAKEN FROM
FAULT CURRENT
TAG (AIC)
KEY NOTE
G E N E R A L S Y M B O L S
XX
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS OTHERWISE
NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
1 = SINGLE PATIENT STATION. MTD 4'-0" AFF UNLESS OTHERWISE NOTED
2 = DUPLICATE PATIENT STATIONS (SEPARATE INDICATORS AT MASTER
STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED
D = DUTY STATION. MTD 5'-0" AFF UNLESS OTHERWISE NOTED
E = STATION MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB
LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION, UON
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED
U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED
EM = EMERGENCY STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED
J = JACK STATION. MTD 4'-0" AFF UNLESS OTHERWISE NOTED
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF LAMP) MTD 6" ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
NIGHT LIGHT
PATIENT BED OUTLET
POWER SUPPLY WITH BATTERY BACKUP
NURSE CALL
FIRE ALARM
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL
REMOTE ANNUNCIATOR
ADDRESSABLE RELAY
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT = BATTERIES CHR = CHARGER FAR = RECORDER
ALARM, FIRE, TERMINAL CABINET.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, FIRE, MANUAL PULL STATION
C = WITH CLEAR PLASTIC COVER
ALARM, HORN/LIGHT, ONE ASSEMBLY
C = WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
C
SAFETY AND SECURITY
M = MOUNTING FOR ALL SAFETY AND SECURITY SYMBOLS:
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
SECURITY ACCESS, ANNUNCIATOR PANELAP
SECURITY ACCESS, VIDEO CAMERA WITH LENS
SECURITY ACCESS, DOME CAMERA
M T
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
M KEYPAD DEVICE
M CARD READER WITH KEYPAD
M T
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN
M T
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
M T
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
M T
DOOR CONTACT
PB PULL BOX
J
CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XXXNG
RECEPTACLE ON EMERGENCY POWER: 125V, 20A
18"AFF, UON. TYPES: DUPLEX / QUADRAPLEX /
SPECIAL
C
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
2-GANG COMPARTMENT BOX IN FLOOR FOR DATA,
AND RECEPTACLE
C
TELECOMMUNICATIONS SYSTEMS BONDING BUSBARTGB
PS
B
FS
D
M
FTR
FATC
BATT
R
FACC
FAC
A
N
N
NCT
NCS
FTT
DH
FAT
HD
TS
K
F
R
R
S
S
A B B R E V I A T I O N S
AFC
AFG
AF
AFCI
AFF
AI
AIC
AHJ
AO
ATS
C
CATV
CB
CCTV
CL
CO
DDC
DI
DO
DP
DPM
EC
EL
EM
EN
EMT
ER
EX
FAAP
FACP
FCIO
FOIC
GFCI
GFP
GND
HTR
IG
IMC
JBOX
LCP
MCA
MCB
MCC
MDP
MLO
MS
MTD
MTS
NAC
NEC
NFC
NIC
NL
NTS
OC
OH
OS
PIV
PNL
PS
PVC
R
RCPT
RMC
SAC
SB,SWBD
SG
SPD
TEL
TR
TYP
UC
UON
UL
UG
VD
VFD
W
WP
XFMR
AVAILABLE FAULT CURRENT
ABOVE FINISHED GRADE
AMP FRAME
ARC FLASH CIRCUIT INTERRUPTER
ABOVE FINISHED FLOOR
ANALOG INPUT
AMPERE INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ANALOG OUTPUT
AUTOMATIC TRANSFER SWITCH
CONDUIT OR CEILING
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CONNECTOR LIGHTING
CONDUIT ONLY
DIRECT DIGITAL CONTROLS
DISCRETE INPUT
DISCRETE OUTPUT
DISTRIBUTION PANELBOARD
DIGITAL POWER METER
ELECTRICAL CONTRACTOR
EXISTING TO BE RELOCATED
EMERGENCY
EXISTING IN NEW LOCATION
ELECTRICAL METALLIC TUBING
EXISTING TO REMAIN
EXISTING
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY CONTRACTOR, INSTALLED
BY OWNER
FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
GROUND
HEATER
ISOLATED GROUND
INTERMEDIATE METALLIC CONDUIT
JUNCTION BOX
LIGHTING CONTROL PANEL
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MAIN LUGS ONLY
MOTOR STARTER
MOUNTED
MANUAL TRANSFER SWITCH
NOTIFICATION APPLIANCE CABINET
NATIONAL ELECTRICAL CODE
NOT FOR CONSTRUCTION
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
ON CENTER
OVERHEAD
OCCUPANCY SENSOR
POST INDICATOR VALVE
PANEL
POWER SUPPLY
POLYVINYL CHLORIDE
EXISTING TO BE REMOVED
RECEPTACLE
RIGID METAL CONDUIT
SMALL APPLIANCE CIRCUIT
SWITCHBOARD
SWITCHGEAR
SURGE PROTECTIVE DEVICE
TELEPHONE
TAMPER RESISTANT
TYPICAL
UNDER COUNTER
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES
UNDERGROUND
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
WEATHERPROOF (WHILE IN USE)
WEATHERPROOF
TRANSFORMER
EQUIPMENT DESIGNATIONS
PHOTO ELECTRIC SENSOR
A.T.S.
PANEL DESIGNATIONS
VOLTAGE (4=480V, 2=208V)
SYSTEM (N=NORMAL, E=LIFE SAFETY,
C=LIFE SUPPORT, Q=EQUIPMENT)
R=XRAY, K=KITCHEN, E=ELEVATOR,
(IF USED)
RISER CLOSET (A THRU E D&T BUILDING
F&G NURSING TOWER
H NURSING HOME
J ENERGY PLANT
K THERAPY GYM)
FLOOR
UNIT SUBSTATION
ENERGY PLANT
D & T BUILDING
NURSING TOWER, NURSING HOME
DISTRIBUTION PANEL DESIGNATION:
NUMBER SUPPLIED FROM UNIT SUBSTATION OR RISER
CLOSET DESIGNATION
UNIT SUBSTATION
SYSTEM (SEE PANEL DESIGNATION)
MCC DESIGNATION
NUMBER SUPPLIED FROM UNIT SUBSTATION
UNIT SUBSTATION
SYSTEM (SEE PANEL DESIGNATION)
AUTOMATIC TRANSFER SWITCH DESIGNATION
NUMBER SUPPLIED FROM UNIT SUBSTATION
UNIT SUBSTATION
SYSTEM (SEE PANEL DESIGNATION)
A =
B =
C =
XXXX
XXXX-X
XXXXXX
XX-X
WIRELESS TRACKING MODULE, IR TECHNOLOGY
VW - INDICATES VIRTUAL WALL TYPEVW
WT
PRESSURE DEVICE
PRESSURE BEACONP
B-BELL PUSH D-DURESS P-PANIC R-DOOR OPENER
X-REQUEST-FOR-EXIT
EMERGENCY STOP PUSHBUTTONE
BUS DUCT
LOW VOLTAGE SWITCH. NUMBER OF BUTTONS PER SWITCHING
ZONES SHOWN. AUTO-OFF VIA OCCUPANCY SENSOR, AS
SHOWN. PROVIDE LIGHTING PACK(S) IN ACCESSIBLE CEILING
SPACE AS NECESSARY.
# = 3 OR 4 FOR 3-WAY/4-WAY CONDITIONS
a = SWITCHING ZONE
LINE VOLTAGE WALL OCCUPANCY SENSOR.
a = SWITCHING ZONE
LINE VOLTAGE MANUAL TOGGLE SWITCH.
LOW VOLTAGE DIMMER SWITCH. NUMBER OF DIMMER
SWITCHES PER SWITCHING ZONES SHOWN. AUTO-OFF VIA
OCCUPANCY SENSOR, AS SHOWN. PROVIDE LIGHTING PACK(S)
IN ACCESSIBLE CEILING SPACE AS REQUIRED.
# = 3 OR 4 FOR 3-WAY/4-WAY CONDITIONS
a = SWITCHING ZONE
ALL INTERIOR AREAS TO HAVE MANUAL ON/AUTO OFF LIGHTING
CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY
SENSORS. EXCEPT WHERE A WALL SWITCH OCCUPANCY
SENSOR IS NOTED.
SENSORS TO BE CEILING MOUNTED. VERIFY LAYOUT WITH
VENDOR SHOP DRAWINGS PRIOR TO PLACEMENT. ADDITIONAL
LIGHTING PACK(S) SHALL BE PROVIDED FOR ROOMS WITH
CONTROLLED RECEPTACLES.
1#
OS
a a a
4a
L I G H T I N G C O N T R O L S C H E D U L E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
E-001
GENERAL NOTES, ABBREVIATIONS
AND LEGENDSSPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
Revisions: Date:
DROP CORD, DATA JACK
# = QUANTITY OF DATA JACKS
C
C = CEILING MOUNTED
I
AC AUDIO/VISUAL CONTROLLER AND INPUT DEVICE
T
ELECTRICAL
BD-110
EXISTING
BUSDUCT
EXISTING
STERILIZER
TRANSFORMER
EXISTING
BDE4
EXISTING
BDN4
EXISTING
BDQ4
EXISTING
T3
EXISTING
BDQ2
EXISTING
BDN2/H
EXISTING
BDE2
EXISTING
BDN2.2
EXISTING
BDN2.12
BUSDUCT
T2
EXISTING TRANSFORMER 1
T9
EXISTING TRANSFORMER 2
EXISTING
EXISTING
18 SF
SIGNAL
BD-110B 20 SF
TELE
BD-110A
MRV-24
ACP-1
MRV-3 MRV-2
EXISTING EXISTING EXISTING
EXISTING
D & T NORTH
NURSING
TOWER
AREA SHOWN
CENTRAL CORE
NORTH
CENTRAL CORE
SOUTH
CENTRAL CORECENTRAL CORE
SE
152-0
SE
152-10
ENLARGED RM BD-110A AND BD-110B DEMOLITION PLAN ENLARGED RM BD110 MEZZANINE DEMOLITION PLAN
EXISTING DATA RACKS TO BE UTILIZED FOR ALL DATA
CONNECTIONS FOR RENOVATED AREAS. REFERENCE
SHEETS ET101 AND ET102 FOR ADDITIONAL INFORMATION.
MODIFY/ADD TO EXISTING DATA RACK AND EQUIPMENT AS
REQUIRED TO PROVIDE A COMPLETE AND FULLY
FUNCTIONAL SYSTEM. FOR BIDDING PURPOSES,
CONTRACTOR SHALL ASSUME (4) NEW (1) RU, 48-PORT, CAT
6A PATCH PANELS AND THEIR APPURTENANCES ARE
REQUIRED.
1. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED
WITH THE CONTRACTORS PHASING OF THE PROJECT.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER
TRADES.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY.
CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL
DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH
DEMOLISHED EQUIPMENT SHALL BE DEMOLISHED BACK TO
THEIR SOURCE, UNLESS OTHERWISE NOTED.
3. ALL DEMOLITION OF ELECTRICAL SYSTEMS SHALL BE CLOSELY
COORDINATED WITH THE CONTRACTORS PHASING OF THE
PROJECT. VERIFY DEMOLITION OF ELECTRICAL WITH ALL
TRADES PRIOR TO START OF DEMOLITION.
4. PROTECT ALL EXISTING WORK FROM DAMAGE DURING
CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,
COMPONENTS, FINISHES AND THE LIKE, SHALL BE REPAIRED
OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
5. ALL CIRCUITS AND RELATED DEVICES THAT ARE TO REMAIN
ARE TO STAY "ENERGIZED" IN THE DEMOLITION AND NEW
CONSTRUCTION PHASES UNTIL THE COMPLETION OF THE
WORK INDICATED ON THESE PLANS.
6. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES.
DISPOSAL OF DEVICES SHALL COMPLY WITH ALL
APPROPRIATE CODES. REUSE EXISTING CONDUITS AND
JUNCTION BOXES WHERE NOTED AS IS PRACTICAL.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
SCALE : NTS
NOT USED1
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
SCALE : 1/2" = 1'-0"
ENLARGED RM BD-110 DEMOLITION PLAN2
SCALE : 1/2" = 1'-0"
SCALE : 1/2" = 1'-0"
0 1' 2' 4' 0 1' 2' 4'
0 1' 2' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL/WNM JPS/FEB
100% CD
Revisions: Date:
E-401
ENLARGED DEMOLITION PLANS
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
EXISTING PANEL TO BE REVISED. REFERENCE APPROPRIATE
PANEL SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
230 SF
CONFERENCE
B102
OS
OS
103 SF
RME COOP/SPD SEC.
B101
230 SF
CONFERENCE
CB-15D
G22
BDE4-3
G22
BDE4-3
G22
BDE4-3
G22
BDE4-3
G22
BDE4-3
G22
BDE4-3
G23
BDE4-3
G23
BDE4-3
BUSDUCT
T2
EXISTING TRANSFORMER 1
T9
EXISTING TRANSFORMER 2
EXISTING
EXISTING
18 SF
SIGNAL
BD-110B 20 SF
TELE
BD-110A
MRV-24
ACP-1
MRV-3 MRV-2
EXISTING EXISTING EXISTING
EXISTING
D & T NORTH
NURSING
TOWER
AREA SHOWN
CENTRAL CORE
NORTH
CENTRAL CORE
SOUTH
CENTRAL CORECENTRAL CORE
C
S
S
S
C
230 SF
B102
103 SF
B101
AC BDN2.2-50
BDN2.2-50
BDN2.2-50
BDN2.2-50
BDN2.2-50BDN2.2-50
ELECTRICAL
BD-110
EXISTING
BDN2/H
EXISTING
BDE2
BDN2.2BDN2.1
EXISTING
BUSDUCT
EXISTING
STERILIZER
TRANSFORMER
BDE4
EXISTING
BDN4 BDQ4 T3
BDQ2
ENLARGED RM BD-110A AND BD-110B ELECTRICAL PLAN ENLARGED RM BD110 MEZZANINE PLAN
RECEPTACLE AND DATA OUTLET FOR CEILING MOUNTED
PROJECTOR. COORDINATE FINAL LOCATION WITH OWNER.
REFERENCE ONE-LINE DIAGRAM AND PANEL SCHEDULES
FOR POWER DISTRIBUTION CONNECTIONS.
EXISTING DATA RACKS TO BE UTILIZED FOR ALL DATA
CONNECTIONS FOR RENOVATED AREAS. REFERENCE
SHEETS ET101 AND ET102 FOR ADDITIONAL INFORMATION.
MODIFY/ADD TO EXISTING DATA RACK AND EQUIPMENT,
INCLUDING BUT NOT LIMITED TO PATCH PANELS, AS
REQUIRED TO PROVIDE A COMPLETE AND FULLY
FUNCTIONAL SYSTEM.
AUDIO/VISUAL CONTROLLER AND INPUT DEVICE, PROVIDE
COMPLETE AND FULLY FUNCTIONAL AUDIO SYSTEM,
AUDIO SYSTEM SHALL INTEGRATE WITH OVERHEAD
PROJECTOR AND SPEAKER SYSTEM. COORDINATE WITH
A/V CONTRACTOR AND ARCHITECT FOR FINAL
INSTALLATION LOCATIONS.
PACS CARD READER ACCESS CONTROL PANEL, 8-CARD
READER PANEL. PROVIDE RACEWAY AND CABLING TO
CONNECT NETWORK CABLING FROM ACCESS CONTROL
PANEL AND VA NETWORK SWITCH LOCATED IN NEARBY
DATA RACK. REFERENCE SPECIFICATION 281300 AND KEY
NOTE '3' ON THIS SHEET FOR ADDITIONAL INFORMATION.
COORDINATE ALL VA NETWORK CONNECTIONS WITH VA
COR.
REVISED PANEL. REFERENCE APPROPRIATE PANEL
SCHEDULE FOR ADDITIONAL INFORMATION.
1. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED
WITH THE CONTRACTORS PHASING OF THE PROJECT.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER
TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. ROUTE ALL CONDUIT HOME RUNS TO PANELS OVERHEAD AND
ABOVE ACCESSIBLE CEILINGS WHERE AVAILABLE.
4. PROVIDE POWER RELAYS, LOW VOLTAGE TRANSFORMERS,
CONDUIT AND JUNCTION BOXES FOR FIRE ALARM AND
TELECOMMUNICATION SYSTEMS AS REQUIRED.
5. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
6. COORDINATE WITH OWNERS AGENT FOR FINAL LOCATIONS OF
ALL DATA PORTS AND SPECIAL CONNECTIONS FOR
EQUIPMENT PRIOR TO ROUGH-IN. COORDINATE RECEPTACLE
INSTALLATION WITH MILLWORK AND BACKSPLASH INSTALLERS
TO AVOID INTERFERENCES.
7. ELECTRICAL POWER AND TELECOMMUNICATIONS
CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW EACH
OTHER'S DRAWING AND SUBMITTALS AND COORDINATE FOR
FULLY OPERATIONAL SYSTEM.
8. COORDINATE MOUNTING HEIGHTS AND ORIENTATION OF
DEVICES IN MILLWORK WITH ARCHITECTURAL ELEVATIONS.
9. PROVIDE MODIFICATIONS TO THE EXISTING FIRE ALARM
SYSTEM TO SUPPORT THE ADDED FIRE ALARM FIELD DEVICES
AS REQUIRED. PROVIDE ADDITIONAL I/O CARDS/MODULES,
EQUIPMENT, CONNECTIONS, AND APPERTENANCES AS
REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL
SYSTEM. CONTRACTOR SHALL COORDINATE ALL FIRE ALARM
WORK WITH VA PRIOR TO INITIATING WORK.
SCALE : 1/4" = 1'-0"
ENLARGED RM B101 & B102 LIGHTING PLAN1
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
SCALE : 1/2" = 1'-0"
ENLARGED RM BD-110 ELECTRICAL PLANS2
SCALE : 1/2" = 1'-0"
-SCALE : 1/2" = 1'-0"
SCALE : 1/4" = 1'-0"SCALE : 1/4" = 1'-0"
ENLARGED RM B101 & B102 POWER AND SPECIAL SYSTEMS PLAN5
0 1' 2' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL/WNM JPS/FEB
100% CD
Revisions: Date:
E-402
ENLARGED PLANS
PROJECT
NORTH
0 1' 2' 4'
PROJECT
NORTH
0 1' 2' 4'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
0 2' 4' 8'
0 2' 4' 8'
ACCESS CONTROL PANEL
BDE2-39
ACCESS CONTROL PANEL
BDE2-39
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
SU
PP
LY
W
AR
EH
OU
SE
BR
EA
K
OF
FI
CE
CO
RR
ID
OR
EN
CL
OS
UR
E
FO
R
BU
LK
O
XY
GE
N
ST
OR
AG
E
TA
NK
P
H
ST
OR
AG
E
CY
LIN
DE
R
ST
OR
AG
E
M
ED
IC
AL
G
AS
RO
OM
M
EC
HA
NI
CA
L
M .E
.R
#4
VE
ST
IB
UL
E♦♦♦♦♦♦♦♦♦
TRANSFORMERS AND
SWITCHGEAR ROOM
COMPRESSOR ROOM
REACTOR ROOM
GENERATOR
EMERGENCY
PIT
STAIR #11
TO
ILE
T
MAL
E
EMERGENCY SWITCHGEAR
CH
ILL
ER
RO
OM
ENGINEERING
CONTROL RM
BO
ILE
R R
OOM
GRO
UN
DS
C
RE
W
INDUSTRIAL
STAIR #17
INDUSTRIAL
STAIR #22
SHOWER
MALE LOCKERS/
TR
AN
SP
ORT
AT
IO
N
CA
GE
TR
AN
SP
ORT
AT
IO
N
OFFICE
FL
OOR C
RA
TE
CO
VE
R O
VE
R P
IT
E
CONTINUE TO SPS TRAILER
DISCONNECTS
(SEE DRAWING ES100)
D & T NORTH
NURSING
TOWER
AREA SHOWN
SWITCH BOARD "SWBD-AN-1".
EXISTING SPARE CIRCUIT BREAKER "AL3" TO BE UTILIZED FOR NEW FEEDER.
1. REFERENCE ONE-LINE DIAGRAM ON SHEET E-603, DETAIL "1", FOR ALL
CONDUIT AND WIRE SIZING.
SCALE : 1/8" = 1'-0"
ENLARGED ENERGY PLANT - ELECTRICAL PLAN1
0 4' 8' 16'
TRUE
NORTH
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
E-403
ENLARGED ENERGY PLANT -
ELECTRICAL PLAN
KEY PLAN
ENERGY
PLANT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
Revisions: Date:
LEVEL 1
0' - 0"
LEVEL BASEMENT
-18' - 0"
LEVEL BASEMENT
- INTERSTITIAL
-7' - 11"
LEVEL 7
126' - 0"
PENTHOUSE
LEVEL
153' - 0"
'-9
LEVEL 3'
36' - 0"
6' -0
6' -0
NEW CART LIFT
ROOF
172' - 0"
LEVEL 8
144' - 0"
9' -0
9' -6
E-404
S-5
UPDN
UP
EXISTING LINEN CHUTESPD LIFT SHAFT
T-13
SOILED
RETURN
T-14
CLEAN
SUPPLY/
RETURN
ELEVATOR MACHINE ROOM
P8QE4
P8N4
8N2.1
8Q2.1
T-13
SOILED
RETURN
T-13 CAB LTG DISC
8N2-1-7
T-13 CONTROL
SWITCH
P8N4-3
AC-11A
L2E 8N2-1-9
L2 8N2-1-9
L2 8N2-1-9
D & T
TRUE
NORTH
CENTRAL CORE
NORTH
NURSING
TOWER
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
E-404
ENLARGED FLOOR PLANS AND
SECTION - CART LIFTSPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
1/4" = 1'-0"
CART LIFT T-13 MACHINE ROOM ELECTRICAL PLAN
1/4" = 1'-0"
3 CART LIFT T-13 SHAFT SECTION VIEW
Revisions: Date:
1/4" = 1'-0"
CART LIFT T-13 MACHINE ROOM DEMOLITION PLAN
PROJECT
NORTH
KEY NOTES (THIS SHEET ONLY)
GENERAL NOTES
KEY PLAN
EXISTING ELECTRICAL POWER AND CONTROL EQUIPMENT AND ALL ASSOCIATED
CONDUIT AND WIRE TO BE DEMOLISHED.
ALL EXISTING CART LIFT EQUIPMENT, INCLUDED MOTOR-GENERATOR AND
OPERATOR SHALL BE DEMOLISHED. ALL EQUIPMENT LOCATIONS NOT SHOWN
FOR CLARITY; CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS AS
REQUIRED.
T-13 CART LIFT CONTROL UNIT.
CART LIFT EQUIPMENT OPERATOR AND RELATED EQUIPMENT. EQUIPMENT
LOCATIONS NOT SHOWN FOR CLARITY; CONTRACTOR SHALL COORDINATE WITH
MANUFACTURER AS REQUIRED FOR EXACT LOCATION.
EXISTING PANELBOARDS TO BE REVISED. REFERENCE ONE-LINE DIAGRAM ON
SHEET E-604 FOR ADDITIONAL INFORMATION.
REPLACE EXISTING DUPLEX RECEPTACLE WITH NEW GFCI, WR, TR, 20A, 120V
RECEPTACLE WITH WHILE-IN-USE COVER.
1. COORDINATE EXACT CART LIFT T-13 EQUIPMENT LAYOUT WITH CART LIFT
MANUFACTURER AS REQUIRED.
2. ALL FIRE ALARM DEVICES SHALL BE CONNECTED TO THE EXISTING FIRE
ALARM SYSTEM. IF REQUIRED, PROVIDE ADDITIONAL INPUT CARDS FOR THE
FIRE ALARM CONTROL PANEL.
3. REFERENCE ONE-LINE DIAGRAM ON SHEET E-604 FOR ADDITONAL
CIRCUITING INFORMATION.
PROJECT
NORTH
DN
ROOF LEVEL
ELE 172'-0"
LAUNDRY CHUTE VENT
EXISTING TRAFFIC PADS
EXISTING MAINTENENCE
EQUIPMENT HOLD DOWN
8N2-1-7
HP-11
8N2-1-9,11
D & T
NORTH
CENTRAL CORE
NORTH
NURSING
TOWER
AREA SHOWN
E-405
ENLARGED PARTIAL ROOF PLAN
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Revisions: Date:
ENLARGED PARTIAL ROOF PLAN
PROVIDE LOCAL DISCONNECT AND RECEPTACLE ON ADJACENT
STAINLESS-STEEL RACK UTILIZING STAINLESS STEEL FASTENING HARDWARE
AS REQUIRED.
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
Revisions: Date:
1. COORDINATE FINAL EQUIPMENT LOCATIONS WITH MECHANICAL AND
ARCHITECTURAL DRAWINGS.
SCALE : 1/4" = 1'-0"-
PROJECT
NORTH
GROUNDING ELECTRODE AND BONDING SYSTEM1
- SCALE: NTS
ITEM
CONCRETE ENCASED REBAR (UFER)
GROUND RODS (IF WITHOUT GROUND RING)
GROUND RING (WITH OR WITHOUT GROUND RODS AS NOTED)
SIZE
METAL WATER PIPES
OTHER CONNECTIONS AS NOTED ON PLANS
STRUCTURAL STEEL
SPECIAL SYSTEMS GROUNDING BUS BARS
POWER CABLE TRAY, SPECIAL SYSTEMS CABLE TRAY
#3/0 #6
#2
#3/0 #6
#3/0 #2
GAS PIPES
GROUNDING ELECTRODE AND BONDING CONDUCTOR SIZING SCHEDULE
* BY EQUIPMENT MANUFACTURER, PER NEC 250.66
GROUNDING ELECTRODE CONDUCTOR #3/0
ANTENNA MAST TELECOM RACK ENCLOSURES #2
#3/0
MAIN BONDING JUMPER
INTERSYSTEM BONDING BUS BAR
#6
#3/0
#6
1. MAKE CONNECTION TO ALL AVAILABLE ELECTRODES. NOT ALL MAY BE PRESENT.
2. ALL GROUNDING AND BONDING TO BE IN ACCORDANCE WITH THE CURRENT VERSION
OF THE NEC THAT HAS BEEN ACCEPTED FOR USE IN EACH JURISDICTION AND AS
AMENDED BY LOCAL AUTHORITY HAVING JURISDICTION.
3. GROUND RODS TO BE INSTALLED OUTSIDE OF BUILDING ROOF'S DRIP LINE.
DETAIL NOTES
ITEM SIZE
UFER
GROUND
METAL
WATER
PIPES
OTHER
CONNECTIONS
AS NOTED
ON THE
PLANS
STRUCTURAL
STEEL
SPECIAL
SYSTEMS
GROUNDING
BUS
BARS
TELECOM
RACK
SPECIAL
SYSTEMS
CABLE
TRAY
SIZE PER TABLE
BELOW, TYPICAL
BOND AT
LOCATIONS
REQUIRED TO
MAINTAIN
CONTINUITY
GAS
PIPES
GROUND RODS
MINIMUM 6'-0"
OR 20'-0"
SPACING
WHERE
GROUND RING
PROVIDED
GROUND RING
CONDUCTOR WHERE
PROVIDED
NEUTRAL BUSGROUND BUS
MAIN BONDING
JUMPER
POWER
CABLE
TRAY
ANTENNA
MAST
AS SHORT AND
STRAIGHT AS
POSSIBLE
SERVICE EQUIPMENT
GROUNDING ELECTRODE
CONDUCTOR
SERVICE
GROUND BUS
BAR -
E-502
E-502
1. ALL HARDWARE SHALL BE HOT DIP GALVANIZED.
DETAIL NOTES
CONDUIT CLAMP AND
HANGER - 3' MAX.
FROM BOX TO HANGER
& 8' MAX. SPACING
BETWEEN HANGERS
(TYP.)
STEEL OUTLET BOX
- SIZED PER N.E.C.
AND SUPPORTED
RIGIDLY FROM
STRUCTURE (TYP.)
CONDUIT (TYP.)
6' MAX. LENGTH
FLEX CONDUIT
W/ (3)#12
CONDUCTORS
INTO FIXTURE
(TYP.)
TYPICAL
LAY-IN
RECESSED
LIGHT
FIXTURE
(TYP.)
SECURE
FIXTURES
TO GRID
WITH CLIPS
PER N.E.C.
(TYP.)
T-BAR LAY-IN
CEILING
SUSPENSION
SYSTEM (TYP.)
PROVIDE
SUPPORT
WIRES TO
STRUCTURE
FOR FIXTURE
SUPPORT, TWO
PER FIXTURE
(TYP.) SEE
SPEC SECTION
265100.
TYPICAL RECESSED LIGHTING INSTALLATION3
1. DO NOT SUPPORT CONDUIT OR BOX FROM CEILING GRID HANGERS.
DETAIL NOTES
JOIST (TYP.)
SCALE: NTS
POWER
POWER
COMMON
CONTROL
CONTROL
COMMON
POWER
CONTROL
COMMON
NEUTRAL
HOT
PO
W
ER
PACK
C O
M M
O N
C O
N
TR
O L
POWER
MOUNT IN
ACCESSIBLE SPACE
LUMINARIES
AS
REQUIRED/
INDICATED
CLNG./WALL
SENSOR
OCCUPANCY/VACANCY SENSOR SCHEMATIC4
1. COORDINATE INSTALLATION WITH SPECIFIC MANUFACTURER'S INSTALLATION REQUIREMENTS AND WIRING DIAGRAMS. PROVIDE ALL BOXES, RACEWAY, COMPONENTS AND CONDUCTORS AS REQUIRED FOR COMPLETE OPERATIONAL SYSTEM.
2. ALL CONDUCTORS SHALL BE 600V RATED UNLESS OTHERWISE NOTED.
3. POWER PACKS SHALL BE LOCATED WITHIN ACCESSIBLE CEILING SPACE WITHIN 5' OF DOOR FOR ROOM SERVED WHERE POSSIBLE.
4. OCCUPANCY SENSOR SHALL BE PROVIDED WITH AUXILIARY RELAY FOR CONNECTION TO HVAC CONTROL SYSTEM AND SHALL BE UL916
LISTED FOR ENERGY MANAGEMENT.
5. ALL LOW VOLTAGE WIRING CONCEALED WITHIN WALLS OR ABOVE HARD-LID CEILING SHALL BE ROUTED WITHIN RACEWAY.
6. RECEPTACLE SHALL HAVE "CONTROLLED" ENGRAVED ON FACE.
DETAIL NOTES
TO
HVAC
NEUTRAL
HOT
PO
W
ER
PACK
C O
M M
O N
C O
N
TR
O L
POWER
N
EU
TR
A L
C O
N
TR
O
LL
ED
H
O
TO
V
ER
R
ID
E
OVERRIDE
COMMON
MOMENTARY
CONTACT
SWITCH
O V
ER
R
ID
E
MOUNT IN
ACCESSIBLE SPACE
LIGHTING
CIRCUIT
RECEPTACLE
CIRCUIT
CLNG./WALL
SENSOR
TO
HVAC
(NOTE 4)
(NOTE 4)
SCALE: NTS
WHERE
APPLICABLE
TYPICAL FIRE ALARM RISER DIAGRAM6
FACP
FAN SHUTDOWN
CONTROL
HOOD FIRE
SUPPRESSION SYSTEM
ROLL-UP DOOR
FUSIBLE LINK
PRIMARY
ELEVATOR RECALL
ALTERNATE
ELEVATOR RECALL
CAR VISUAL RECALL
SIGNAL (HAT)
FA
A REMOTE
ANNUNICATOR
J
JUNCTION BOX FOR 120V
POWER TO SPRINKLER BELL.
SEE PLANS FOR LOCATION IF
REQUIRED.
NOTIFICATION
CIRCUIT
BELL-CKT
NOTIFICATION
CIRCUIT
(TYP.) (TYP.) (TYP.) (TYP.)
AUXILIARY POWER
SUPPLY (NAC)
120 VAC
S S
(TYP.) (TYP.) (TYP.)
FAN SHUT DOWN
CONTROL
SMOKE, HEAT,
DUCT DETS
PULL STATIONS
(TYP.)
DH
DH
120 VAC
MAGNETIC DOOR
HOLDERS
(TYP.)
#12 (TYP.)
F/S
F/S
120 VAC
FIRE/SMOKE
DAMPERS (TYP)
#12 (TYP.)
BATTERIES
120 VAC
TO PHONE
DEMARC BOARD
3/4" C 4-PAIR
TELEPHONE CABLE.
DACT (AUTO DIALER)
TYPICAL COMMUNICATIONS RISER DIAGRAM5
TELEPHONE/CATV
TERMINAL BOARD
SIZE AS INDICATED ON
PLANS.
NETWORK/VOICE
(TYP.)
VOICE
(TYP.)
TV OUTLET
2"C w/(2)-RG11/U TO CABLE TV SERVICE
4" CONDUIT TO TELEPHONE COMPANY MAIN SERVICE
6 AWG 3/4" C.
COPPER TO
SERVICE GROUND
OR INTERSYSTEM
BONDING BUS
(TYP.) (TYP.) (TYP.) (TYP.)
NUMBER OF CONDUCTORS
AS REQUIRED FOR
APPLICABLE ZONES
LF LF
LF LF
3/4"C w/
(1)-CAT6
3/4"C w/
(1)-CAT6
3"C 3/4"C w/(1)-RG6/U
AND (1)-CAT6
ALARM
CIRCUIT
TAMPER, FLOW SENSORS
SCALE: NTSSCALE: NTS
120V DEDICATED
CIRCUIT
1. FIRE ALARM SYSTEM AS SHOWN IS SCHEMATIC ONLY AND DOES NOT INDICATE ALL DEVICES, EQUIPMENT, WIRING. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED DEVICES AND EQUIPMENT AND SUBMIT ENGINEERED DRAWINGS TO AHJ FOR REVIEW AND APPROVAL.
DETAIL NOTES
1. COMMUNICATIONS DIAGRAM AS SHOWN IS SCHEMATIC AND DOES NOT INDICATE ALL DEVICES, EQUIPMENT, WIRING. PROVIDE
COMPLETE SYSTEM WITH ALL REQUIRED DEVICES AND EQUIPMENT.
DETAIL NOTES
ACCESSIBLE CEILING
TV
F
TF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
Revisions: Date:
E-501
ELECTRICAL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL JPS/FEB
100% CD
Revisions: Date:
E-501
ELECTRICAL DETAILS
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE
PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS
& WEATHER-PROOF PRESSURE
SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE BY
ROOFING CONTRACTOR MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF ROOF
BY ROOFING CONTRACTOR. PRIME
FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED 1.52mm
(0.06") THICK ALUMINUM
FLASHING ROUND COLLAR WITH
MIN. 76mm (3") WIDE FLANGE.
ATTACH TO ROOF PER
MANUFACTURER'S INSTRUCTIONS
CONDUIT CLAMP. SIZE AS
REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
STAINLESS CLAMP, TYP.
9.52mm (3/8")
MIN
GALVANIZED
THREADED ROD,
TYP.
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
CONDUIT,
TYP.
CONDUIT CLAMP.
SIZE AS
REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT
SEALANT, TYP
CONDUIT ROOF PENETRATION DETAIL2
- SCALE: NTS
SCALE: NTS SCALE: NTS
1. REFERENCE SPECIFICATIONS 087100 AND 281300 FOR ADDITIONAL INFORMATION/REQUIREMENTS.
2. COORDINATE ALL VA NETWORK CONNECTIONS WITH VA COR.
3. PROVIDE REQUEST-TO-EXIT ON ALL ACCESS CONTROLLED DOORS; REFERENCE SPECIFICATION FOR EXACT
REQUIREMENTS.
DETAIL NOTES
SCALE: NTS
STEEL BEAM
CADWELD CONNECTION TYPE
QW (OR TYPE VN TO WEB OF
LARGE BEAM)
STEEL COLUMN
CADWELD CONNECTION TYPE VV
TO GROUND
EXOTHERMIC WELD
CONNECTION
NO. GBIT14412M-22T OR APPROVED EQUAL, 1/4" x 4" x
12" SOLID COPPER GROUND BAR WITH INSULATORS
AND BRACKETS, AND WITH TWO 25'-0" NO. 2T, #2 AWG
TIN COATED COPPER GROUND CONDUCTORS
#2AWG SOLID
TINNED CU
25FT LO
NG
SINGLE SWITCH
NEUTRAL
LINE
GREEN AND YELLOW
GREEN
BLACK
GROUND
RED
120V/230V/277V GROUND OR
347V (PW-100-347) (SEE
INSTALLATION INSTRUCTIONS)
DETAIL NOTES
1. ALL SENSORS TO BE DUAL TECHNOLOGY TYPE. SENSOR MUST INCLUDE
VISIBLE STATUS SIGNAL. REFER TO ALL APPLICABLE ENERGY CODES FOR
PRODUCT REQUIREMENTS. SENSOR MUST HAVE BUILT-IN SENSITIVITY
CALIBRATION AND ADJUSTMENT.
SCALE: NTS
SCALE: NTS
TYPICAL MV AND BUILDING TELECOMMUNICATIONS TRENCHING SECTION5
3"
3"
4"
3"3"3" 3"
3" 3"
12"
BACKFILL TO MATCH
EXISTING GRADE
ASPHALT OR CONCRETE
PAVING
PAVING BASE
SELECTED BACKFILL FREE OF
LARGE DEBRIS AND COMPACTED
PER VA SPECIFICATIONS
CONCRETE SLURRY MIX
MEETING VA STANDARDS
CONCRETE
ENCASEMENT IF
REQUIRED AS
SHOWN ON
PLANS
CONTINUOUS
WARNING TAPE.
TRACER WIRE
SHALL BE
ACCESSIBLE IN
ALL HAND
HOLES OR MAN
HOLE
X" MIN.
24"
MIN.
3"
PROVIDE AND SIZE CONDUITS
PER PLANS
- SCALE: NTS
SPS TRAILER EQUIPMENT DISCONNECT DETAIL6
WALL OCCUPANCY/VACANCY SENSOR4
TYPICAL GROUND BUS BAR FOR
INTERSYSTEM AND SERVICE GROUNDING3
BUILDING STEEL GROUND2
TYPICAL SECURITY ACCESS DOOR CONTROL (MAGNETIC LOCK TYPE)1
SCALE: NTS
EXISTING CT TRAILER DISCONNECT7
RELOCATE DISCONNECT AND REROUTE
CONDUITS AND CONNECTIONS AS REQUIRED
BUILDING #33
EXTERIOR WALL
MANUFACTURER
PROVIDED CORD,
TYP.
PLUG,
TYP.
DISCONNECT
TYP.
MEYERS HUB
TYP.
STAINLESS STEEL
UNISTRUT WITH
STAINLESS STEEL
FASTENING
HARDWARE, TYP.
RIGID METAL
CONDUIT,
TYP.
ID PLACARD
DETAIL NOTES
1. COORDINATE WITH CIVIL ENGINEER FOR ALL TRENCHING MATTERS
INCLUDING, BUT NOT LIMITED TO, PAVEMENT RESTORATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL/WNM JPS/FEB
100% CD
Revisions: Date:
E-502
ELECTRICAL DETAILS
JUNCTION BOX, 8" x 8" x 4"
MINIMUM
TO SECURE LOCAL ACCESS
CONTROL PANEL, 1-1/2" CONDUIT
ELECTRIC STRIKE PER SYSTEM
REQUIREMENTS, PROVIDE
BACKBOX AS REQUIRED BY
MANUFACTURER
DUAL AUTHENTICATION CARD
READER AND KEYPAD, 42" AFF,
HID pivCLASS #RK40 OR
EQUIVALENT, PROVIDE 4"
SQUARE BACKBOX WITH MUD
RING. INSTALL PER
MANUFACTURER'S
INSTRUCTIONS.
SUSPENDED CEILING
FLOOR
DOOR POSITION SWITCH AND
MAGNET
CONTINUE TO REQUEST-TO-EXIT
FIELD MOUNTED DEVICE, 3/4"
CONDUIT
3/4" CONDUIT
LOAD
SCALE : NTS
SCOPE PROCESSING AREA ONE-LINE DIAGRAM - EXISTING1
ROOF
INTERSTITIAL
4TH FLOOR
INTERSTITIAL
3RD FLOOR
INTERSTITIAL
2ND FLOOR
INTERSTITIAL
1ST FLOOR
INTERSTITIAL
BASEMENT
1QC4 (E)
XXX/XXXV
3P 4W
TO QDPB #2
RM 1D-139
3QC2 (E)
XXX/XXXV
3P 4W
RM 3D-136 RM 3D-127
QMCCB3 (E)
XXX/XXXV
3P 4W
RM 3F-105
TRANSFORMER
"T2" (E)
BDE2 (E)
208/120V 3P 4W
TRANSFORMER
"T2" (E)
TO PANEL "EDPB",
CIRCUIT #4
60AS60AF
175AS175AF
450AS450AF
50AS50AF
J
RIDER D-N 1200A 3PH, 4W
BUS DUCT 480V
J
J
J
TRANSFORMER "T9"
3PH (E)
(3) 4"C - (12)
400KCM, #3/0G
QMCCB2 (E)
480/277V 3P 4W
NMCCB3 (E)
480/277V 3P 4W
QMCCB2.1 (E)
480/277V 3P 4W
TRANSFORMER
"T3" (E)
PBN4 (E)
480/277V 3P 4W
4DQ2 (E)
208/120V 3P 4W
3DQ2 (E)
208/120V 3P 4W
2DQ2 (E)
208/120V 3P 4W
1DQ2 (E)
208/120V 3P 4W
RM BD-110
BF-104
RM JD-123
1F-105
RM 2D-151
2F-104
3F-104
4F-104
RM 3D-120
RM 4D-114
G
TO QMCC-A3
TO QMCC-B2
SUPPLY FAN
EXISTING PANEL TO BE DEMOLISHED.
EXISTING CONDUCTORS TO BE DEMOLISHED BACK TO
SOURCE. EXISTING RACEWAY TO REMAIN TO BE REUSED.
REFERENCE DRAWING E-602 FOR ADDITIONAL INFORMATION.
EXISTING MOTOR CONTROL CENTER PROVIDES POWER TO
BONE MARROW UNIT. COORDINATE ALL WORK WITH VA
PRIOR TO COMMENCING WORK ASSOCIATED WITH MOTOR
CONTROL CENTER. CONTRACTOR SHALL PROVIDE 30-DAY
NOTIFICATION OF OUTAGE WITH PROPOSED OUTAGE PLANT
TO ENGINEER AND VA COR. OUTAGE SHALL BE LIMITED TO
1-HOUR. REFERENCE SHEET E-602 FOR ADDITIONAL
INFORMATION.
COORDINATE DEMOLITION WORK WITH BONE MARROW UNIT
POWER REQUIREMENTS. REFERENCE GENERAL NOTE '3' AND
KEY NOTES '2' AND '3' FOR ADDITIONAL INFORMATION.
EXISTING PANEL TO BE MODIFIED. REFERENCE PANEL
SCHEDULE ON SHEET E-607 FOR ADDITIONAL INFORMATION.
1. WHEN REPLACING A BRANCH PANELBOARD, RE-CIRCUIT
EXISTING LOADS TO SAME POLE NUMBERS AS PREVIOUS.
IDENTIFY ALL EXISTING LOADS TO REMAIN AND PROVIDE
COMPLETE ACCURATE PANEL INDEX. EXAMPLE: IF EXISTING
DOCK RECEPTACLES ARE CIRCUITED TO BDN2.1-28,
RE-CIRCUIT TO BDN2.1-28 IN NEW PANEL BDN2.1, UNLESS
OTHERWISE INDICTED.
2. EXISTING LOAD INFORMATION IS BASED ON RECORD
DRAWINGS AND FIELD OBSERVATIONS. CONTRACTOR SHALL
FIELD VERIFY ALL EXISTING LOADS TO REMAIN.
3. CONTRACTOR SHALL PROVIDE TEMPORARY POWER AS
REQUIRED TO MAINTAIN EQUIPMENT/FACILITY OPERATION;
DOWN TIME SHALL BE MINIMIZED AS MUCH AS POSSIBLE.
PRIOR TO ANY OUTAGES, CONTRACTOR SHALL PROVIDE
30-DAY NOTIFICATION OF OUTAGE WITH PROPOSED OUTAGE
PLAN TO ENGINEER AND VA COR.
4. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
ANY DISCREPANCIES FOUND SHALL BE REPORTED TO THE
ENGINEER.
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
BDE4 (E)
480/277V 3P 4W
BDN4 (E)
208/120V 3P 4W
BDN2.1 (E)
208/120V 3P 4W
BDN2.2 (E)
208/120V 3P 4W
BDQ4 (E)
480/277V 3P 4W
BDQ2 (E)
208/120V 3P 4W
BDN3 (E)
208/120V 3P 4W
TO SUBSTATION "B",
CIRCUIT BREAKER #1
RM BD-100C RM BD-100C RM BD-111C
TO QDPB #3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL/WNM JPS/FEB
100% CD
Revisions: Date:
E-601
SCOPE PROCESSING AREA
ONE-LINE DIAGRAM - EXISTING
PREP & STERILE
WORKROOM
CONTAINMENT
ROOM
TYP.
REFERENCE SHEET E-603 FOR
ADDITIONAL INFORMATION
SCALE : NTS
SCOPE PROCESSING AREA ONE-LINE DIAGRAM - REVISED1
REFERENCE LOAD SCHEDULES FOR FOR ADDITIONAL
INFORMATION.
PRIOR TO DISCONNECTING POWER TO "QMCCB2.1" (BONE
MARROW UNIT), PROVIDE CONDUIT AND WIRE EXTENDING
FROM PANELBOARD "BDQ4" TO NEW JUNCTION BOX (SIZE
PER NEC); WIRE PROVIDED SHALL BE ENOUGH TO EXTEND
FROM "BDQ4" TO "QMCCB2.1" - COIL EXCESS WIRE AS
REQUIRED. ONCE POWER HAS BEEN DISCONNECTED FROM
"QMCCB2.1", DEMOLISH EXISTING FEEDER CONDUCTORS
EXTENDING FROM "BDQ4" TO "QMCCB2.1", EXTEND EXISTING
CONDUIT FEEDING "QMCCB2.1" TO NEW JUNCTION BOX, AND
INSTALL AND TERMINATE NEW WIRE THROUGH EXISTING
CONDUIT TO "QMCCB2.1" AS REQUIRED.
EXISTING MOTOR CONTROL CENTER PROVIDES POWER TO
BONE MARROW UNIT. COORDINATE ALL WORK WITH VA
PRIOR TO COMMENCING WORK ASSOCIATED WITH MOTOR
CONTROL CENTER.
MODIFIED PANEL. REFERENCE PANEL SCHEDULE ON SHEET
E-607 FOR ADDITIONAL INFORMATION.
1. WHEN REPLACING A BRANCH PANELBOARD, RE-CIRCUIT
EXISTING LOADS TO SAME POLE NUMBERS AS PREVIOUS.
IDENTIFY ALL EXISTING LOADS TO REMAIN AND PROVIDE
COMPLETE ACCURATE PANEL INDEX. EXAMPLE: IF EXISTING
DOCK RECEPTACLES ARE CIRCUITED TO BDN2.1-28,
RE-CIRCUIT TO BDN2.1-28 IN NEW PANEL BDN2.1, UNLESS
OTHERWISE INDICTED.
2. EXISTING LOAD INFORMATION IS BASED ON RECORD
DRAWINGS AND FIELD OBSERVATIONS. CONTRACTOR SHALL
VERIFY ALL EXISTING LOADS TO REMAIN.
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
ROOF
INTERSTITIAL
4TH FLOOR
INTERSTITIAL
3RD FLOOR
INTERSTITIAL
2ND FLOOR
INTERSTITIAL
1ST FLOOR
INTERSTITIAL
BASEMENT
TO QDPB #2
RM 1D-139
RM 3D-136 RM 3D-127
RM 3F-105
60AS60AF
175AS175AF
450AS450AF
50AS50AF
J
RIDER D-N 1200A 3PH, 4W
BUS DUCT 480V
J
J
J
(3) 4"C - (12)
400KCM, #3/0G
RM BD-110
BF-104
RM JD-123
1F-105
RM 2D-151
2F-104
3F-104
4F-104
RM 3D-120
RM 4D-114
TO QMCC-A3
TO QMCC-B2
SUPPLY FAN
G
(1) 3" C. W/(4) 4/0 AWG &
(1) 6 AWG GND
1 1 1 1 1 1
1 1
TO PANEL "EDPB",
CIRCUIT #4
TO SUBSTATION "B",
CIRCUIT BREAKER #1
B126 BD121
RM BD-111C
TO QDPB
1QC4 (E)
XXX/XXXV
3P 4W
3QC2 (E)
XXX/XXXV
3P 4W
QMCCB3 (E)
XXX/XXXV
3P 4W
TRANSFORMER
"T2" (E)
BDE2 (E)
208/120V 3P 4W
TRANSFORMER
"T2" (E)
TRANSFORMER "T9"
3PH (E)
QMCCB2
480/277V 3P 4W
NMCCB3
480/277V 3P 4W
QMCCB2.1 (E)
480/277V 3P 4W
TRANSFORMER "T3"
112.5kVA, 480-120/208V
PBN4
480/277V 3P 4W
4DQ2 (E)
208/120V 3P 4W
3DQ2 (E)
208/120V 3P 4W
2DQ2 (E)
208/120V 3P 4W
1DQ2 (E)
208/120V 3P 4W
BDE4
480/277V 3P 4W
BDN4(E)
208/120V 3P 4W
BDN2.1
208/120V 3P 4W
BDN2.2
208/120V 3P 4W
BDQ4
480/277V 3P 4W
BDQ2
208/120V 3P 4W
BDN3
208/120V 3P 4W
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
663-20-102
06/25/2021 LRL/WNM JPS/FEB
100% CD
Revisions: Date:
E-602
SCOPE PROCESSING AREA
ONE-LINE DIAGRAM - REVISED
PREP & PACK SOILED ANTE
J 2
(1) 2" C. (4) 3/0 AWG & (1)
6 AWG GND
(1) 2" C. (3) 3/0 AWG & (1) 6
AWG GND
(1) 4" C. W/(4) 600 KCMIL &
(1) 3 AWG GND
REFERENCE SHEET E-603 FOR
ADDITIONAL INFORMATION
(1) 2-1/2" C. W/(4) 250KCMIL
& (1) 4 AWG GND
EXISTING CONDUIT.
REFERENCE KEY NOTE 2.
(1) 1" C. W/(3) 8 AWG
& (1) 8 AWG GND
(2) 3" C. EA. W/(4) 350KCMIL
& (1) 1 AWG GND
REFERENCE LOAD SCHEDULES FOR FOR ADDITIONAL INFORMATION.
TRAILER MANUFACTURER TO PROVIDE CORD. CONTRACTOR TO INSTALL AND
PROVIDE PVC RACEWAY TO PROVIDE PROTECTION FOR CORD; CONTRACTOR
SHALL COORDINATE EXACT ROUTING AND SIZE OF PVC RACEWAY WITH TAILER
MANUFACTURER.
SCALE : NTS
MOBILE STERILIZATION TRAILER PARTIAL ONE-LINE DIAGRAM1
K K
SUBSTATION
"A"
K 5252K 5252
2500 kVA 13.8kV:
480Y/277V
LV
AL1
LV
AL2
LV
AL3
LV
AL4
LV
AL5
LV
AL6
LV
AL7
LV
AL8
LV
AR8
LV
AR7
LV
AR6
LV
AR5
LV
AR4
LV
AR3
LV
AR2
LV
AR1
2500 kVA 13.8kV:
480Y/277V
MAL1 MAR1
MAL2 MAR2
AUTOMATIC
THROWOVER
SYSTEM
TA
S1AR N1ARS1AL N1AL
50P
SEL 351-7
51P 51G 50P
SEL 351-7
51P 51G
CONTINUE TO
EXISTING FEEDERS
CONTINUE TO
EXISTING FEEDERS
60/3
SPD
250/3
LS
I
800/3
LSI
SWITCHBOARD "SWBD-AN-1",
800A, 480/277V, 3PH, 4W, 65KAIC
250A/3P
DPM
PWR
CONNECTION
#1
250/3
LS
I 250A/3P
PWR
CONNECTION
#2
SPS MOBILE TRAILER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
625 1ST AVE, UNIT #301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING…