This is a solicitation for structural engineering services to upgrade sterile processing services at the VA Puget Sound Health Care System in Seattle, Washington. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20. Required services include structural design and drawings for renovations and expansion of sterile processing facilities in Building 100. Key deliverables are structural design plans, calculations, specifications, and construction support. The period of performance is six months from award. The anticipated award date is July 2021. Pricing will be fixed price. The solicitation is unrestricted and open to all responsible sources. The incumbent contractor is Spees Design Build.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL STRUCTURAL NOTES
SHEET INDEX
S-001
S-002
SF101
SF501
GENERAL
DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. TYPICAL DETAILS AND NOTES SHOWN
ON THESE DRAWINGS ARE PART OF THE CONSTRUCTION CONTRACT AND SHALL BE PROVIDED BY THE
CONTRACTOR. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS BUT SHALL APPLY AS
SHOWN OR DESCRIBED IN THE DETAILS AND NOTES. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT
ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS AND ALL OTHER
CONTRACT DOCUMENTS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND
CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY ARCHITECT OF ALL DISCREPANCIES PRIOR TO
CONSTRUCTION.
DISCREPANCIES: IN CASE OF DISCREPANCIES BETWEEN DRAWINGS, SPECIFICATIONS, REFERENCE STANDARDS, OR GOVERNING CODE, THE MORE STRINGENT REQUIREMENTS SHALL GOVERN. CONTRACTOR SHALL NOTIFY THE
ENGINEER OF DISCREPANCIES AND OBTAIN DIRECTION PRIOR TO PROCEEDING. NOTES ON INDIVIDUAL
STRUCTURAL DRAWINGS SHALL TAKE PRIORITY OVER GENERAL STRUCTURAL NOTES. DIMENSIONS NOTED IN THE
DRAWINGS SHALL BE FOLLOWED. DO NOT SCALE DRAWINGS.
SPECIFICATIONS: REFER TO SPECIFICATIONS FOR INFORMATION IN ADDITION TO THESE NOTES AND DRAWINGS.
ARCHITECTURAL: REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS, SLOPES, DEPRESSIONS, NON-
BEARING WALLS, FASCIA, ELEVATORS, STAIRS, CURBS, DRAINS, RAILINGS, WATERPROOFING, FINISHES, ETC.
CONTRACTOR-INITIATED CHANGES: SHALL BE SUBMITTED IN WRITING FOR APPROVAL PRIOR TO FABRICATION AND
CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS OR SUBMITTALS ONLY WILL NOT SATISFY THIS
REQUIREMENT.
CONTRACTOR RESPONSIBILITIES: DRAWINGS REPRESENT DESIGN OF STRUCTURE IN COMPLETED FORM.
CONTRACTOR SHALL BE RESPONSIBLE FOR METHODS, SEQUENCES, AND SAFETY PRECAUTIONS REQUIRED TO
PERFORM WORK.
CONTRACTOR SHALL DESIGN AND PROVIDE TEMPORARY SHORING AND BRACING OF ALL STRUCTURAL MEMBERS, EXISTING CONSTRUCTION, AND SOIL EXCAVATION AS REQUIRED. SHORING AND BRACING SHALL NOT BE REMOVED
UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE DRAWINGS, AND MATERIALS
HAVE ACHIEVED DESIGN STRENGTH.
EXISTING CONDITIONS: CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS
PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS
ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. EXISTING CONDITIONS SHOWN ON DRAWINGS ARE
BASED EITHER ON SITE OBSERVATIONS, ORIGINAL DRAWINGS, OR WERE ASSUMED BASED ON EXPECTED
CONDITIONS. IF EXISTING CONDITIONS DO NOT CLOSELY MATCH CONDITIONS SHOWN ON DRAWINGS, OR IF
EXISTING MATERIALS ARE OF QUESTIONABLE OR SUBSTANDARD QUALITY, NOTIFY ENGINEER PRIOR TO
COMMENCING ANY WORK.
STRUCTURAL OBSERVATION SHALL BE PERFORMED PER IBC SECTION 1704.6
SPECIAL INSPECTION PER IBC SECTION 1704, SHALL BE PERFORMED BY AN AGENCY APPROVED BY THE BUILDING
OFFICIAL AND AS OUTLINED IN THE STRUCTURAL INSPECTION SCHEDULE.
CODES
BUILDING CODE: ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE
DRAWINGS, SPECIFICATIONS AND THE INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION, AS AMENDED BY THE
STATE OF WASHINGTON.
STANDARDS: REFERENCE TO ASTM AND OTHER STANDARDS SHALL MEAN THE LATEST EDITION REFERENCED IN
THE 2015 IBC, UNLESS NOTED IN THESE DOCUMENTS OR DESIGNATED BY THE GOVERNING CODE.
DESIGN CRITERIA
FLOOR DESIGN DATA:
IN ADDITION TO THE SELF WEIGHT, THE FOLLOWING LOADS ARE USED FOR DESIGN:
UNIFORM CONCENTRATED SUPERIMPOSED
LIVE LOAD LIVE LOAD DEAD LOAD REDUCIBLE
(PSF) (LBS) (PSF) (SEE NOTE)
WALKWAY (UNO) 60 - NO
SNOW DESIGN DATA:
ROOF SNOW LOAD 25 PSF MIN UNIFORM SNOW
LOAD IN ACCORDANCE WITH SEAW WHITE PAPER 8-2010
WIND DESIGN DATA:
ANALYTICAL PROCEDURE DIRECTIONAL PROCEDURE, ASCE 7 CHAPTER 27
TYPE OF STRUCTURE RIGID (ASCE 7 SECTION 26.9.2)
BASIC WIND SPEED V = 115 MPH, ULTIMATE 3 SECOND GUST (ASCE 7 FIG 26.5-1A - 26.5-1C)
EXPOSURE CATEGORY B (ASCE 7 SECTION 26.7.3)
INTERNAL PRESSURE COEFFICIENT 0.18 (ASCE 7 FIGURE 26.11-1)
ENCLOSURE CLASSIFICATION OPEN (ASCE 7 SECTION 26.10.1)
DIRECTIONALITY FACTOR K
d
= 0.85 : MWFRS (ASCE 7 TABLE 26.6-1)
TOPOGRAPHIC FACTOR K
zt
= 1.0 (ASCE 7 SECTION 26.8)
GUST EFFECT FACTOR G = 0.85 (ASCE 7 SECTION 26.9.1)
EARTHQUAKE DESIGN DATA:
SEISMIC-FORCE-RESISTING SYSTEM: CANTILEVERED COLUMN SYSTEM DETAILED TO CONFORM TO THE
REQUIREMENTS FOR TIMBER FRAMES AT COVERED WALKWAY
ANALYTICAL PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE (COVERED WALKWAY)
SEISMIC RESPONSE COEFFICIENT: C
S
= 0.652
(ASCE 7 SECTION 12.8.1.1)
SEISMIC IMPORTANCE FACTOR I
e
1.5 (ASCE 7 TABLE 1.5-2)
SITE CLASS D (ASCE 7 SECTION 11.4.2)
S S
= 1.468 g (ASCE 7 SECTION 11.4.1)
S
= 0.565 g (ASCE 7 SECTION 11.4.1)
S
DS
= 0.978 g (ASCE 7 SECTION 11.4.4)
S D1
= 0.565 g (ASCE 7 SECTION 11.4.4)
SEISMIC DESIGN CATEGORY D (ASCE 7 SECTION 11.6)
RESPONSE MODIFICATION COEFFICIENT R = 1.5 (ASCE 7 TABLE 12.2-1)
GEOTECHNICAL
ALLOWABLE SOIL PRESSURE, LATERAL EARTH PRESSURE, AND SOIL PROFILE TYPE ARE ASSUMED AND
THEREFORE MUST BE VERIFIED BY THE CONTRACTOR'S GEOTECHNICAL ENGINEER OR INSPECTOR. IF SOILS ARE
FOUND TO BE OTHER THAN ASSUMED OR FOUND TO BE EXPANSIVE, NOTIFY THE CONTRACTING OFFICER FOR
POSSIBLE FOUNDATION REDESIGN.
FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED EARTH OR CONTROLLED, COMPACTED STRUCTURAL FILL AT
LEAST 18" BELOW LOWEST ADJACENT EXTERIOR FINISHED GRADE. FOOTING DEPTHS AND ELEVATIONS SHOWN ON
DRAWINGS ARE MINIMUM AND FOR GUIDANCE ONLY; CONTRACTOR SHALL ESTABLISH ACTUAL ELEVATIONS IN
FIELD. BACKFILL BEHIND ALL WALLS WITH FREE DRAINING, GRANULAR FILL AND PROVIDE FOR SUBSURFACE
DRAINAGE IN AN APPROVED MANNER.
SOIL PROFILE TYPE SITE CLASS "D"
ALLOWABLE VERTICAL DESIGN PRESSURE 1,500 PSF
SUBMITTALS
SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION OR CONSTRUCTION OF THESE
ITEMS:
STRUCTURAL STEEL
CONCRETE MIX DESIGN
CONCRETE REINFORCING EMBEDDED ITEMS IN CONCRETE
CONTRACTOR SHALL REVIEW AND STAMP SUBMITTALS PRIOR TO SUBMISSION. DIMENSIONS AND QUANTITIES ARE
CONTRACTOR'S RESPONSIBILITY AND WILL NOT BE REVIEWED. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
MATERIALS PLACED PRIOR TO RECEIPT OF REVIEWED SHOP DRAWINGS. CONTRACTOR SHALL ALLOW SUFFICIENT
TIME FOR REVIEW.
SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS. THE PURPOSE OF SHOP
DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR
UNDERSTANDS THE DESIGN CONCEPT BY INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND
INSTALLED AND BY DETAILING THE INTENDED FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING SUBMITTALS AND THE CONTRACT DOCUMENTS ARE
DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE
DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED.
RENOVATION:
DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION.
SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE
TO THE WORK SEQUENCES. EXISTING REINFORCING SHALL BE SAVED WHERE POSSIBLE AND AS NOTED ON
DRAWINGS. SAW-CUTTING, IF AND WHERE USED, SHALL NOT CUT EXISTING REINFORCING THAT IS TO BE SAVED.
DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE.
CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS SHALL BE LIMITED TO 40
PSF.
1. ALL NEW OPENINGS THROUGH EXISTING WALLS, SLABS, AND BEAMS SHALL BE ACCOMPLISHED BY
SAWCUTTING WHEREVER POSSIBLE. ALL NEW OPENINGS SHALL BE SAWCUT NEAT AND CLEAN; NO
OVERCUTTING AT OPENING CORNERS SHALL BE ALLOWED, UNLESS NOTED OTHERWISE. AS REQUIRED, CORE
DRILL CORNERS AND CHIP, GRIND, OR CUT THE CORNERS TO PROVIDE REQUIRED DIMENSIONS.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS PRIOR TO CUTTING ANY
OPENINGS.
3. SMALL ROUND OPENINGS SHALL BE ACCOMPLISHED BY CORE DRILLING.
EXISTING REBAR SCANNING: THE GENERAL CONTRACTOR SHALL SELECT THE APPROPRIATE SCANNING METHODS
BASED ON CONSTRUCTION MEANS AND METHODS REQUIRED TO INSTALL POST-INSTALLED ANCHORS IN
ACCORDANCE WITH DETAILS. GROUND-PENETRATING RADAR, X-RAY, AND MAGNETIC-BASED METHODS ARE ALL
ACCEPTABLE METHODS OF SCANNING. HOWEVER, CERTAIN METHODS MAY HAVE LIMITATIONS AND THE
APPROPRIATE METHODS AND EQUIPMENT MUST BE DETERMINED BY THE CONTRACTOR PRIOR TO CONSTRUCTION.
DO NOT CUT, DAMAGE, OR REMOVE EXISTING REBAR TO INSTALL ANCHORS.
CONCRETE:
REFERENCE STANDARDS: CONCRETE SHALL CONFORM TO ALL REQUIREMENTS OF THE FOLLOWING DOCUMENTS, EXCEPT AS MODIFIED BELOW:
ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE"
ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
ACI 304 "GUIDE FOR MEASURING, MIXING, TRANSPORTING, AND PLACING CONCRETE"
ACI 311 "GUIDE FOR CONCRETE INSPECTION"
ACI SP-15* "FIELD REFERENCE MANUAL"
*A COPY SHALL BE KEPT IN THE CONTRACTOR'S FIELD OFFICE AT ALL TIMES.
MATERIALS:
CEMENT ASTM C150, C595
*AGGREGATES ASTM C33
ADMIXTURES ASTM C260, C494, C1017
* *FLY ASH ASTM C618, CLASS F OR C
*AGGREGATES THAT EXHIBIT DELETERIOUS ACTIVITY WHEN EVALUATED IN ACCORDANCE WITH ASTM C33
APPENDIX XI SHALL NOT BE USED. THE 'SAND EQUIVALENT' FOR FINE AGGREGATE SHALL NOT BE LESS THAN 75.*
*MAXIMUM LOSS ON IGNITION SHALL BE 1%.
CONCRETE MIXES SHALL BE PROPORTIONED TO ACHIEVE A WORKABLE MIX THAT CAN BE PLACED WITHOUT
SEGREGATION OR EXCESS FREE SURFACE WATER. MIX DESIGNS SHALL BE SUBMITTED FOR REVIEW BY ENGINEER
PRIOR TO USE. COMPLY WITH IBC SECTION 1904. MIXES SHALL MEET OR EXCEED THE FOLLOWING CRITERIA:
TYPE OF CONSTRUCTION SPECIFIED COMPRESSIVE MAXIMUM EXPOSURE CLASS
STRENGTH (f 'c) WATER/CEMENT (ACI 318-14 TABLES
AT 28 DAYS, UNO RATIO 19.3.1.1 AND 19.3.2.1)
CONCRETE EXPOSED TO WEATHER 4,500 PSI 0.45 F2, S0, W0, C1
INTERIOR SLAB AND WALL INFILL 4,000 PSI 0.55 F1, S0, W0, C1
CONCRETE MIXES SHALL MEET OR EXCEED THE REQUIREMENTS SPECIFIED ABOVE. MIXES SHALL BE SUBMITTED
TO THE ENGINEER AND BUILDING OFFICIAL FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE AND
SHALL INCLUDE THE AMOUNTS OF CEMENT, CEMENTITIOUS MATERIAL, FINE AND COARSE AGGREGATE, WATER
AND ADMIXTURES, AS WELL AS THE WATER-CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING
STRENGTH DATA IN ACCORDANCE WITH ACI 318, CHAPTER 26. REVIEW OF MIX SUBMITTALS BY THE ENGINEER OF
RECORD INDICATES ONLY THAT INFORMATION PRESENTED CONFORMS GENERALLY WITH CONTRACT DOCUMENTS.
CONTRACTOR OR SUPPLIER MAINTAINS FULL RESPONSIBILITY FOR SPECIFIED PERFORMANCE.
ADMIXTURES: ALL CONCRETE, INCLUDING SLABS ON GRADE, SHALL HAVE A WATER-REDUCING ADMIXTURE
COMPLYING WITH ASTM C494 ADDED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. CALCIUM
CHLORIDE OR OTHER CHLORIDE ADMIXTURES SHALL NOT BE USED.
ALL HORIZONTAL SURFACES EXPOSED TO WEATHER SHALL CONTAIN AN AIR-ENTRAINING AGENT COMPLYING WITH
ASTM C260. THE AMOUNT OF ENTRAINED AIR SHALL BE IN ACCORDANCE WITH ACI 318-14 TABLE 19.3.3.1. TESTS
FOR AIR CONTENT SHALL BE MADE AT THE DISCHARGE END OF THE TRUCK'S PLACING HOSE IN ACCORDANCE
WITH ASTM C173.
WATER/CEMENT RATIO SHALL BE MEASURED BY WEIGHT AND BE BASED ON TOTAL CEMENTITIOUS MATERIAL, INCLUDING CEMENT AND POZZOLANS SUCH AS FLY ASH AND SILICA FUME.
MAXIMUM AGGREGATE SIZE SHALL BE 3/4"
SLUMP REQUIRED FOR PROPER PLACEMENT SHALL BE DETERMINED BY CONTRACTOR AND SUPPLIER, AND
INCLUDED IN MIX DESIGN SUBMITTALS. FIELD MEASURED SLUMP SHALL CONFORM TO SUBMITTED CONCRETE MIX
DESIGN. SLUMP SHALL CONFORM TO ASTM C94.
BONDING AGENT SHALL BE EPOXY RESIN BASED CONFORMING TO ASTM C881, TYPE V, GRADE 2. USE WHERE NEW
CONCRETE IS PLACED AGAINST PREVIOUSLY PLACED OR EXISTING CONCRETE. PLACE IN STRICT ACCORDANCE
WITH MANUFACTURER'S INSTRUCTIONS, INCLUDING PREPARATION OF EXISTING SURFACES.
NON-SHRINK GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 6,000 PSI AT 28 DAYS, BUT NOT LESS
THAN THE MATERIAL ON WHICH IT IS PLACED UPON.
CONCRETE REINFORCEMENT
REFERENCE STANDARDS: CONCRETE REINFORCEMENT SHALL CONFORM TO ALL REQUIREMENTS OF
THEFOLLOWING CODES, SPECIFICATIONS, AND STANDARDS, EXCEPT AS MODIFIED BELOW:
ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE"
ACI SP-66 "ACI DETAILING MANUAL"
ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
CRSI "PLACING REINFORCING BARS"
CRSI "MANUAL OF STANDARD PRACTICE" MSP-1
MATERIALS:
DEFORMED BARS ASTM A615, GRADE 60
BAR SUPPORTS CONFORM TO CHAPTER 3, CRSI MSP-1
3. IF MILL TEST REPORTS ARE NOT AVAILABLE, REINFORCEMENT SHALL BE TESTED PER THE SPECIFICATIONS AT
THE CONTRACTOR'S EXPENSE.
REINFORCEMENT SHALL BE PLACED AND SUPPORTED IN ACCORDANCE WITH CRSI MSP-1. REINFORCEMENT SHALL
BE DETAILED IN ACCORDANCE WITH ACI SP-66. NO BENDING OR STRAIGHTENING OF REINFORCEMENT WILL BE
PERMITTED AFTER PARTIAL EMBEDMENT IN CONCRETE.
CONCRETE COVER: UNLESS NOTED OTHERWISE, MINIMUM CONCRETE COVER FOR REINFORCEMENT SHALL BE:
SLABS ON GRADE 2" BOTTOM
EXPOSED FORMED WALL FACES 1 1/2" (#5 AND SMALLER), 2" (#6 AND LARGER)
FOOTINGS 3" (EXCEPT 2" TOP AND FORMED SIDES)
CONCRETE ANCHORAGE
EXPANSION BOLTS INTO CONCRETE SHALL BE ONE OF THE FOLLOWING. INSTALL PER MANUFACTURER'S
INSTRUCTIONS AND APPLICABLE IAPMO OR ICC-ES REPORTS. NOMINAL EMBEDMENT DEPTH SHALL BE AS NOTED
BELOW, UNLESS NOTED OTHERWISE.
HEAVY DUTY SCREW ANCHORS INTO CONCRETE SHALL BE SIMPSON TITEN HD (ESR-2713), DEWALT SCREW-BOLT+
(ESR-3889) OR HILTI KWIK HUS EZ (ESR-3027).
SHALLOW EMBEDMENT MECHANICAL ANCHORS TO THE UNDERSIDE OF CONCRETE SLABS SHALL BE HILTI HDI-P TZ
(ESR-4236) EXPANSION ANCHORS OR DEWALT MINI-UNDERCUT+ UNDERCUT ANCHOR (ESR-3912).
POST-INSTALLED ANCHORS SHALL NOT BE USED AS SUBSTITUTES FOR CAST-IN-PLACE ANCHOR BOLTS OR
REINFORCING STEEL UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER.
PRODUCT SUBSTITUTES PROPOSED BY THE CONTRACTOR SHALL BE SUBMITTED FOR REVIEW WITH IAPMO OR ICC-
ES REPORTS INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES.
NO REINFORCING BARS SHALL BE CUT TO PLACE POST-INSTALLED ANCHORS. ALL DEFECTIVE ANCHOR HOLES
SHALL BE GROUTED WITH EPOXY ADHESIVE AND A NEW HOLE DRILLED A MINIMUM OF 3 BOLT DIAMETERS AWAY.
STEEL
REFERENCE STANDARDS: STRUCTURAL STEEL SHALL CONFORM TO ALL REQUIREMENTS OF THE FOLLOWING
DOCUMENTS:
AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES"
AWS D1.1 "STRUCTURAL WELDING CODE - STEEL"
AISC 348 "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS"
MATERIALS:
TYPE OF MEMBER ASTM SPECIFICATION YIELD
PLATES, ANGLES, CHANNELS A36 36 KSI
THREADED RODS (TR) AND BARS
ANCHOR RODS (AR) F1554 GRADE 36, WELDABLE
LOAD-INDICATING WASHERS F959, TYPE A325
WELDING: ALL WELDS SHALL COMPLY WITH AWS D1.1. WELDS SHALL BE MADE USING LOW HYDROGEN E70XX
ELECTRODES. ONLY AWS PREQUALIFIED WELDED JOINTS SHALL BE USED. SHOP DRAWINGS SHALL SHOW ALL
WELDING WITH AWS A2.4 STANDARD SYMBOLS. WELDS SHOWN ON DRAWINGS ARE MINIMUM SIZES. INCREASE
WELD SIZE TO AWS MINIMUM SIZES BASED ON PLATE THICKNESS.
ALL WELDS SHALL BE MADE WITH A FILLER WELD METAL THAT HAS A MINIMUM CHARPY V-NOTCH TOUGHNESS OF
20 FT.-LBS. AT 0 DEGREES F. IN ADDITION TO MEETING THE ABOVE REQUIREMENTS, ALL WELDS INDICATED AS
"DEMAND CRITICAL" SHALL BE MADE WITH MATERIAL WITH A MINIMUM CHARPY V-NOTCH TOUGHNESS OF 40 FT-LBS
AT 70 DEGREES F. SEE AISC 341-10 CHAPTER A AND AWS D1.8 SECTION 6.3 FOR ADDITIONAL REQUIREMENTS.
PROPOSED FILLER MATERIAL FOR BOTH SHOP AND FIELD WELDS SHALL BE SUBMITTED FOR REVIEW PRIOR TO
CONSTRUCTION.
WELDS SHOWN ON DRAWINGS ARE FOR FINAL CONNECTIONS. UNLESS FIELD WELD SYMBOLS ARE SHOWN, CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING IF A WELD SHOULD BE SHOP OR FIELD WELDED IN
ORDER TO FACILITATE STEEL ERECTION.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL JOINT PREPARATIONS AND WELDING PROCEDURES, INCLUDING
ROOT OPENINGS AND FACE DIMENSIONS, GROOVE ANGLES, BACKING BARS, COPES, WELD ACCESS HOLES, TAPERS, AND SURFACE ROUGHNESS.
WELDER CERTIFICATION: AWS OR WASHINGTON ASSOCIATION OF BUILDING OFFICIALS (WABO).
ANCHOR RODS SHALL BE INSTALLED TO AISC SNUG-TIGHT CRITERIA WITH HEX NUTS AND LOCK WASHERS OR JAM
NUTS AT THE TOP. AT THE BOTTOM, PROVIDE A STANDARD SIZE HEAD, TACK-WELDED NUT OR DOUBLE NUT. NO
HEATING OR BENDING OF ANCHOR RODS IS PERMITTED. ENLARGEMENT OF ANCHOR ROD HOLES BY BURNING IS
NOT PERMITTED. BASE PLATE HOLES FOR ANCHOR RODS SHALL BE AS SHOWN BELOW
AR MAXIMUM HOLE MINIMUM WASHER MINIMUM WASHER
DIAMETER DIAMETER DIAMETER THICKNESS
5/8" 1 1/16" 1 1/2" 3/16"
3/4" 1 5/16" 2" 1/4"
7/8" 1 9/16" 2 1/2" 5/16"
1" 1 13/16" 3" 3/8"
WOOD
REFERENCE STANDARDS: WOOD SHALL CONFORM TO ALL REQUIREMENTS OF THE FOLLOWING DOCUMENTS:
AITC TCM "TIMBER CONSTRUCTION MANUAL"
ANSI/AWC NDS "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION"
ANSI/AWC SDPWS " SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC"
ALL WOOD FRAMING DETAILS SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE IBC. MINIMUM
NAILING SHALL CONFORM TO IBC TABLE 2304.10.1 OR CURRENT ICC-ES REPORT ESR-1539, UNLESS OTHERWISE
NOTED. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL
DRAWINGS. INSTALL WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON
WOOD. INSTALLATION OF LAG SCREWS SHALL CONFORM TO NDS SECTION 12.1.4, AND INSTALLATION OF BOLTS
SHALL CONFORM TO NDS SECTION 12.1.3.
WALL FRAMING: TWO STUDS MINIMUM SHALL BE INSTALLED AT THE ENDS OF ALL WALLS, UNLESS OTHERWISE
NOTED. INSTALL SOLID BLOCKING FOR WOOD COLUMNS THROUGH FLOOR SPACES TO SUPPORTS BELOW.
ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH 16d NAILS
AT 12" OC STAGGERED OR BOLTED TO CONCRETE WITH 5/8" DIAMETER ANCHOR BOLTS @ 4'-0"oc PER IBC SECTION
2308.3 (EMBED 7"), UNLESS OTHERWISE NOTED. 3" x 3" x 0.229" PLATE WASHERS SHALL BE USED WITH ALL SILL
PLATE ANCHOR BOLTS PER IBC SECTION 2308.3.2 AND SDPWS SECTION 4.3.6.4.3. INDIVIDUAL MEMBERS OF BUILT-
UP STUD POSTS SHALL BE NAILED TO EACH OTHER WITH 16d @ 12"oc STAGGERED.
FLOOR AND ROOF FRAMING: INSTALL DOUBLE JOISTS UNDER ALL PARALLEL PARTITIONS THAT EXTEND OVER
MORE THAN HALF THE JOIST LENGTH AND AROUND ALL OPENINGS IN FLOORS OR ROOFS. INSTALL SOLID
BLOCKING AT ALL BEARING POINTS. TOENAIL JOISTS TO SUPPORTS WITH TWO 16d NAILS. ATTACH TIMBER JOISTS
TO FLUSH HEADERS OR BEAMS WITH SIMPSON METAL JOIST HANGERS IN ACCORDANCE WITH NOTES ABOVE. NAIL
ALL MULTI-JOIST BEAMS TOGETHER WITH 16d @ 12" OC STAGGERED.
ROOF, FLOOR & WALL SHEATHING SHALL BE APA RATED, STRUCTURAL I PLYWOOD OR ORIENTED STRAND BOARD
(OSB) IN CONFORMANCE WITH IBC SECTION 2303.1.5. SHEATHING SHALL BE MANUFACTURED UNDER THE
PROVISIONS OF VOLUNTARY PRODUCT STANDARDS PS 1-09, PS 2-10, OR APA PRP-108 PERFORMANCE STANDARDS
AND POLICIES FOR STRUCTURAL USE PANELS. SEE DRAWINGS FOR THICKNESS, SPAN RATING, AND NAILING
REQUIREMENTS. UNLESS OTHERWISE NOTED, WALL SHEATHING SHALL BE 1/2" (NOMINAL) WITH SPAN RATING OF
24/0. GLUE FLOOR SHEATHING TO ALL SUPPORTING MEMBERS WITH ADHESIVE CONFORMING TO APA
SPECIFICATION AFG-01.
ROOF AND FLOOR SHEATHING SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS AND NAILED AS
SHOWN ON THE DRAWINGS. INSTALL APPROVED PANEL EDGE CLIPS CENTERED BETWEEN JOISTS/TRUSSES AT
UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED TONGUE-AND-
GROOVE JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES
AND ENDS OF FLOOR AND ROOF SHEATHING. TOENAIL BLOCKING TO SUPPORTS WITH 16d @ 12" OC. AT BLOCKED
FLOOR AND ROOF DIAPHRAGMS, INSTALL FLAT 2x BLOCKING AT ALL UNFRAMED PANEL EDGES AND NAIL WITH
EDGE NAILING SPECIFIED.
ALL PRESSURE-TREATED (P.T.) WOOD MEMBERS SPECIFIED ON THE DRAWINGS SHALL BE PRESSURE-TREATED
WITH COPPER AZOLE CA-B (HEM-FIR ONLY), OR ALKALINE COPPER QUAT (ACQ-C FOR DOUGLAS-FIR, OR ACQ-D FOR
HEM-FIR) PRESERVATIVES UNLESS OTHERWISE NOTED. AMMONIACAL COPPER ZINC ARSENATE (ACZA)
PRESERVATIVE, OR OTHER PRESERVATIVES WITH AMMONIA CARRIERS, SHALL NOT BE USED. SEE GENERAL
STRUCTURAL NOTES BELOW FOR MATERIAL REQUIREMENTS OF CONNECTORS AND FASTENERS IN CONTACT WITH
PRESSURE-TREATED MEMBERS. INSTALL (2) LAYERS OF ASPHALT-IMPREGNATED BUILDING PAPER BETWEEN
UNTREATED LEDGERS, BLOCKING, ETC., AND CONCRETE OR MASONRY.
SAWN LUMBER: SAWN LUMBER SHALL BE IDENTIFIED BY THE GRADE MARK OF A LUMBER GRADING OR
INSPECTION AGENCY APPROVED BY AN ACCREDITATION BODY COMPLYING WITH US DEPARTMENT OF COMMERCE
PS20. FRAMING LUMBER SHALL BE KILN DRIED OR MC-19, AND GRADED AND MARKED IN CONFORMANCE WITH
W.C.L.B. STANDARD GRADING RULES FOR WEST COAST LUMBER NO. 17. SAWN LUMBER SPECIES AND GRADES
SHALL BE AS FOLLOWS:
JOISTS: (2x MEMBERS) DOUGLAS FIR NO. 2
Fb = 900 PSI, Fv = 180 PSI, E = 1600 KSI
(3x AND 4x MEMBERS) DOUGLAS FIR NO. 1
Fb = 1000 PSI, Fv = 180 PSI, E = 1700 KSI
BEAMS AND STRINGERS: DOUGLAS FIR NO. 1
(INCLUDING 6x AND LARGER MEMBERS) Fb = 1350 PSI, Fv = 170 PSI, E = 1600 KSI
POSTS: (4x MEMBERS) DOUGLAS-FIR NO. 1
Fc = 1500 PSI, E = 1700 KSI
(6x AND LARGER MEMBERS) DOUGLAS FIR NO. 1
Fc = 1000 PSI, E = 1600 KSI
STUDS, PLATES, LEDGERS & DOUGLAS FIR NO. 2
MISCELLANEOUS LIGHT FRAMING: Fb = 900 PSI, E = 1600 PSI, Fc = 1350 PSI, Ft = 575 PSI
SF102
SF103
NONSTRUCTURAL COMPONENTS (EQUIPMENT SUPPORT ANCHORAGE)
R p
= 2.5 (ASCE 7 TABLE 13.5-1)
a p
= 1.0 (ASCE 7 SECTION 13.5-1)
I = 1.5 (ASCE 7 SECTION 13.5-1)
ARCHITECTURAL COMPONENT COEFFICIENTS:
p
SF103
SF104
SF502
GENERAL STRUCTURAL NOTES AND SHEET INDEX
ABBREVIATIONS AND SPECIAL INSPECTION SCHEDULES
LEVEL BASEMENT PLAN
COVERED WALKWAY FOUNDATION PARTIAL PLAN
COVERED WALKWAY ROOF FRAMING PLAN
COVERED WALKWAY SECTIONS
TYPICAL SECTIONS AND DETAILS
TYPICAL SECTIONS AND DETAILS
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
LNA
P
FOR
SSE
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
GENERAL STRUCTURAL NOTES AND
SHEET INDEX
S-001
EPPPNC06/25/2021
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
AutoCAD SHX Text 06/25/21
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
ABBREVIATIONS AND SPECIAL
INSPECTION SCHEDULES
S-002
EPPPNC06/25/2021
SPECIAL INSPECTION SCHEDULE
STRUCTURAL STEEL SPECIAL INSPECTION
SPECIAL INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION
REFERENCED
STANDARD
CONTINUOUS PERIODIC
IBC
REFERENCE
1. INSPECT ANCHORS POST-INSTALLED
IN HARDENED CONCRETE MEMBERS
ACI 318: 17.8.2.4 -
SPECIAL INSPECTION FOR STRUCTURAL STEEL SHALL BE ACCORDANCE WITH AISC 341, AISC 360, AND THE FOLLOWING INFORMATION.
TASK - INDICATES WHETHER TO OBSERVE OR PERFORM (OR BOTH) THE INSPECTION TASK.
DOC - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS.
O - OBSERVE THESE FUNCTIONS ON A RANDOM, DAILY BASIS, OPERATIONS NEED NOT BE DELAYED PENDING INSPECTIONS.
FREQUENCY OF OBSERVATIONS SHALL BE ADEQUATE TO CONFIRM THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE
WITH THE APPLICABLE DOCUMENTS.
P - PERFORM, FOR EACH JOINT OR MEMBER PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.
QC - TASKS INDICATED AS "QC" SHALL BE EXECUTED BY THE FABRICATOR AND ERECTOR IN ACCORDANCE WITH AISC 360 CHAPTER N
QA - TASKS INDICATED AS "QA" SHALL BE EXECUTED BY THE SPECIAL INSPECTOR IN ACCORDANCE WITH AISC 360 CHAPTER N.
X
- X ACI 318: 17.8.2 -
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY
OR UPWARDLY INCLINED ORIENTATIONS TO RESIST
SUSTAINED TENSION LOADS
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS
NOT DEFINED IN 4.a
SEE EARTHQUAKE DESIGN DATA SECTION OF THE GENERAL STRUCTURAL NOTES ON SHEET S001 FOR SEISMIC-FORCE RESISTING-SYSTEMS.
SEISMIC-FORCE-RESISTING SYSTEMS (INCLUDING DRAG STRUTS AND CHORDS) ARE SUBJECT TO SPECIAL INSPECTION IN ACCORDANCE WITH THE
FOLLOWING SEISMIC AND NON-SEISMIC TABLES. STRUCTURAL SYSTEMS NOT PART OF THE SEISMIC-FORCE-RESISTING SYSTEM NEED ONLY BE INSPECTED IN
ACCORDANCE WITH NON-SEISMIC TABLES.
WHERE APPLICABLE, SEE ALSO IBC SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE
ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION
PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE
SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR
TO THE COMMENCEMENT OF WORK.
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASK
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING CAPACITY
- X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL
- X
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS - X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESS
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL
X -
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND
VERIFY THAT SITE HAS BEEN PREPARED PROPERLY
- X
REFERENCE
STANDARD
IBC
REFERENCE
1705.6
1705.6
1705.6
1705.6
1705.6
PERIODICCONTINUOUS
a. VERIFICATION OF SPECIFIED CONCRETE COMPRESSIVE STRENGTH, f'
C
, IN ACCORDANCE WITH ACI 318-14 SECTION 26.12.
b. VERIFICATION OF SPECIFIED AIR CONTENT, SLUMP, AND TEMPERATURE IN ACCORDANCE WITH ACI 318-14 SECTION 26.12 AT
TIMES FRESH CONCRETE IS SAMPLED.
c. VERIFICATION OF SPECIFIED SHOTCRETE COMPRESSIVE STRENGTH, f' c
, IN ACCORDANCE WITH IBC 1908.10 AT LEAST ONCE PER
SHIFT, BUT NOT LESS THAN 50 CUBIC YARDS OF SHOTCRETE.
CONCRETE
TESTS
2. VERIFY USE OF REQUIRED DESIGN MIX
ACI 318:
CH. 19, 26.4.3, 26.4.4
X
1904.1, 1904.2, 1908.2, 1908.3, 1908.10
3. PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE
ASTM C 172
ASTM C 31
ACI 318: 26.4, 26.12
1908.10
PLYWOODPLWD
APA AMERICAN PLYWOOD ASSOCIATION
BLKG BLOCKING
PENNYWEIGHT (NAILS)d
BC
DS
BOF
CA
DRAG STRUT
CONCRETE (EXPANSION) ANCHOR
BOTTOM CHORD
EPOXY (ADHESIVE) ANCHOR
BOTTOM OF FOOTING
PA
NLG
GRD
HDR
POWDER ACTUATED
GIRDER
NAILING
HEADER
TOW
TC
SHTHG
TOP OF WALL
SHEATHING
TOP CHORD
TWS THREADED WELDED STUD
THREADED RODTR
SJI STEEL JOIST INSTITUTE
POUNDS PER CUBIC FOOTPCF
MILES PER HOURMPH
IJ ISOLATION JOINT
HIGH STRENGTH BOLTHSB
DEEPDP
DEMOLISH, DEMOLITIONDEMO
DIVIDER BEAM, DROPPED BEAMDBAMERICAN SOCIETY OFASCE
AMERICAN IRON ANDAISI
ELEV ELEVATOR
JOIST
JOINT
JST
K
JT
POUND
LEVEL
KSI
LB, #
LEV
L
LL
LLH
LONGIT
LOC
LLV
LF
KSF
KIP (1,000 LB)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH, ANGLE
LINEAL FOOT
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LOCATION, LOCATE
MATERIAL
MINIMUM
MAXIMUM
LSH
MATL
MB
MECH
MIN
MISC
MFR
MAX
NOMINAL
NUMBER
NF
NO, #
NOM
NIC
NS
NTS
OD
OC
N-S
MTL METAL
MECHANICAL
MANUFACTURER
MISCELLANEOUS
NEAR FACE
NOT IN CONTRACT
NORTH-SOUTH
NEAR SIDE
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
MACHINE BOLT
LONG SLOTTED HOLE
OPENING
OPPOSITE
PANEL
PLACES
OPP
OPNG
PCC
OSH
PERP
PL
PNL
PLCS
PEN
RADIUS
PS
PSI
PSF
PT
PVC
RD
R, RAD
P.T.
PREFAB
PP, PJP
PRECAST CONCRETE
PENETRATION
PERPENDICULAR
PLATE, PROPERTY LINE
PARTIAL JOINT PENETRATION
PREFABRICATED
PRESTRESSED CONCRETE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
POINT, PRESSURE TREATED
POLYVINYL CHLORIDE
ROOF DRAIN
POST-TENSIONED
OVERSIZED HOLE
OUTSIDE FACEO.F.
LOW POINTLPT
AB
ACI
AND
AT
ANCHOR BOLT
ADJ
ANCH
ALT
AISC
AR
AWS
ASTM
ARCH
APPROX
ANCHOR ROD
APPROXIMATE
ANCHOR
ALTERNATE
ADDITIONALADDL
AMERICAN WELDING SOCIETY
AMERICAN SOCIETY FOR
ARCHITECT, ARCHITECTURAL
AMERICAN INSTITUTE OF
ADJACENT, ADJUSTABLE
AMERICAN CONCRETE INSTITUTE
BAL
B/
BLDG
BF
BOT
BRG
BTWN
BU
BM
BALANCE
BETWEEN
BEARING
BOTTOM
BEAM
BUILDING
BUILT-UP
BRACED FRAME, BOTTOM FLANGE
BOTTOM OF
C
CANTIL
CC
CAP
CIP
CJ
CLR
CL
CG
CAPACITY
CLEAR
CENTERLINE
CAST-IN-PLACE
CANTILEVER
CONTROL JOINT,
CENTER OF GRAVITY
CENTER-TO-CENTER
CAMBER, CHANNEL
COL
CONC
CONT
CONN
CONST
CU YD
CTR
COORD
CONTR
CUBIC YARD
CENTER, CENTERED
COORDINATE
CONTRACTOR
CONSTRUCTION
CONNECTION
CONCRETE
COLUMN
DBA
DBL
DET
DEG,
DIAG
DIA
DIM
DICA
DIAPH
DIMENSION
DIAPHRAGM
DIAGONAL
DIAMETER
DETAIL
DEGREE
DOUBLE
DEFORMED BAR ANCHOR
CONTINUE, CONTINUOUS
DRILLED-IN CONCRETE ANCHOR
CONCRETE MASONRY UNITCMU
REQUIRED
RETURN
SCHEDULE
SECTION
SHEET
SIMILAR
REQD
REINF
RTN
SCHED
SIM
SHT
SECT
SQUARE
STIFFENER
STIRRUP
STEEL
SUPPORT
SPEC
SPC
SST
STD
SSH
SQ
STL
STIR
STIF
SYMM
SPRT
STRUCT
SOG SLAB ON GRADE
SPACE, SPACED, SPACING
SPECIFICATION
STAINLESS STEEL
SHORT SLOTTED HOLE
STANDARD
STRUCTURAL
SYMMETRICAL, SYMMETRY
REINFORCING
TOP OF
THROUGH
SW
T&B
T/
THK
THRU
TOF
TOS
TOC
TEMP
TYPICAL
WIDTH, WIDE FLANGE
WITH
WOOD
VERTICAL
TYP
UNO
W
WD
WHS
W/
VERT
TRANS
THICK, THICKNESS
TRANSVERSE
UNLESS NOTED OTHERWISE
WELDED HEADED STUD
TOP OF CONCRETE
TOP OF STEEL
TOP OF FOOTING
TOP AND BOTTOM
TEMPERATURE
SHEAR WALL
WEIGHTWT
WP
WWR
WORK POINT
WELDED WIRE REINFORCEMENT
W/O WITHOUT
DO
DN
DWL
DWG
EA
EE
EJ
EL
EF
(E), EXIST
ELEVATION
EACH FACE
EACH END
EACH
EXISTING
DOWEL
DRAWING
DITTO
DOWN
ENGR
ETC
ES
EQUIP
EQ
EMBED
EXP
EW
E-W
FD
EXT
ET CETERA
FLOOR DRAIN
EAST-WEST
EACH WAY
EXPANSION
EXTERIOR
EMBEDMENT
ENGINEER
EQUIPMENT
EACH SIDE
ELECTRICALELEC
EXPANSION JOINT
EARTHQUAKE, EQUAL
FF
FEMA
FDN
FIN
FLG
FLR
FS
FT, '
FTG
GALV
GA
FAR SIDE
GALVANIZED
FEET
FOOTING
GAGE, GAUGE
FOUNDATION
FAR FACE, FINISH FLOOR
FINISH
FLOOR
FLANGE
GEN
GB, GR BM
GRND
HGR
HPT
HK
HORIZ
HIGH POINT
HANGER
HOOK
HORIZONTAL
GROUND
GRADE BEAM
GENERAL
FEDERAL EMERGENCY
INSIDE FACE
INCH
INCLUDE
INFORMATION
INTERIOR
HT
HSS
I.F.
IBC
ID
INFO
INCL
IN, "
INT
HEIGHT
INTERNATIONAL BUILDING CODE
HOLLOW STRUCTURAL SECTION
INSIDE DIAMETER
DEAD LOADDL
REFERENCEREF
PLF POUNDS PER LINEAR FOOT
LONG LEGS BACK TO BACKLLBB
COMPLETE JOINT PENETRATIONCJP, CP
REMAINDERREM
OPEN WEB JOISTOWJ
CONCRETE REINFORCEDCRSI
STAG STAGGER, STAGGERED
MF MOMENT FRAME
CONTROL DENSITY FILLCDF
STEEL CONSTRUCTION
STEEL INSTITUTE
CIVIL ENGINEERS
TESTING AND MATERIALS
CONSTRUCTION JOINT
STEEL INSTITUTE
MANAGEMENT AGENCY
BP BASE PLATE
DESIGN-BUILDD-B
EXT GR EXTERIOR GRADE
GL, GLU LAM GLUE LAMINATED WOOD
GLB GLUE LAMINATED BEAM
HLDN HOLD DOWN
PRCST PRECAST
REBAR REINFORCING STEEL BARS
T&G TONGUE AND GROOVE
LVL LAMINATED VENEER LUMBER
PSL PARALLEL STRAND LUMBER
GWB
HF HEM-FIR
GYPSUM WALL BOARD
FL
FOS
FLUSH LEDGER
FACE OF STUD
OSB
GE GABLE END
ORIENTED STRAND BOARD
SWS SHEAR WALL SCHEDULE
WIJ WOOD I-JOIST
LSL LAMINATED STRAND LUMBER
DIST DISTANCE
THP TENDON HIGH POINT
HD HOLDOWN
AFF ABOVE FINISHED FLOOR
FB FLUSH BEAM
DOUGLAS FIRDF
ABBREVIATIONS
COR CONTRACTING OFFICERS
REPRESENTATIVE
INSPECTION TASKS PRIOR TO WELDING
INSPECTION TASKS PRIOR TO WELDING
QAQC
WELDING PROCEDURE SPECIFICATIONS (WPSS) AVAILABLE
PP
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
PP
MATERIAL IDENTIFICATION (TYPE/GRADE)
OO
WELDER IDENTIFICATION SYSTEM
OO
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY), JOINT PREPARATION, DIMENSIONS
(ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL), CLEANLINESS (CONDITION OF STEEL
SURFACES), TACKING (TACK WELD QUALITY AND LOCATION), BACKING TYPE AND FIT (IF
APPLICABLE)
OO
FIT-UP OF FILLET WELDS, DIMENSIONS (ALIGNMENT, GAPS AT ROOT), CLEANLINESS (CONDITION
OF STEEL SURFACES), TACKING (TACK WELD QUALITY AND LOCATION)
OO
CHECK WELDING EQUIPMENT -O
THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT OR
MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW-STRESS TYPE.
INSPECTION TASKS DURING WELDING
INSPECTION TASKS DURING WELDING
QAQC
USE OF QUALIFIED WELDERS
OO
CONTROL AND HANDLING OF WELDING CONSUMABLES, PACKAGING, EXPOSURE
CONTROL
OO
NO WELDING OVER CRACKED TACK WELDS
OO
ENVIRONMENTAL CONDITIONS, WIND SPEED WITHIN LIMITS, PRECIPITATION
AND TEMPERATURE
OO
WPS FOLLOWED, SETTINGS ON WELDING EQUIPMENT, TRAVEL SPEED, SELECTED
WELDING MATERIALS, SHIELDING GAS TYPE/FLOW RATE, PREHEAT APPLIED, INTERPASS
TEMPERATURE MAINTAINED (MIN / MAX), PROPER POSITION (F, V, H, OH)
OO
WELDING TECHNIQUES, INTERPASS AND FINAL CLEANING, EACH PASS WITHIN PROFILE
LIMITATIONS, EACH PASS MEETS QUALITY REQUIREMENTS
OO
REFERENCED
STANDARD
IBC
REFERENCE
1705.2.1
AISC 360 CH. N
& AWS D1.1
REFERENCED
STANDARD
IBC
REFERENCE
1705.2.1
AISC 360 CH. N
& AWS D1.1
WELDING
INSPECTION TASKS AFTER WELDING
INSPECTION TASKS AFTER WELDING
QAQC
WELDS CLEANED
OO
SIZE, LENGTH AND LOCATION OF WELDS
PP
WELDS MEET VISUAL ACCEPTANCE CRITERIA, CRACK PROHIBITION, WELD / BASE-METAL FUSION, CRATER CROSS SECTION, WELD PROFILES, WELD SIZE, UNDERCUT, POROSITY
PP
ARC STRIKES
PP
REPAIR ACTIVITIES
PP
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER
PP
REFERENCED
STANDARD
IBC
REFERENCE
1705.2.1
AISC 360 CH. N
& AWS D1.1
INSPECTION TASKS
INSPECT THE FABRICATED STEEL AND ERECTED STEEL FRAME TO VERIFY COMPLIANCE WITH THE DETAILS
SHOWN ON THE CONSTRUCTION DOCUMENTS, SUCH AS BRACES, STIFFENERS, MEMBER LOCATIONS AND
PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION
QAQC
REFERENCED
STANDARD
AISC 360
CH. N
STEEL DETAILS
OO
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
DW
GFI
G F
I
SE
38-0
NW
SE
0-0
S
176-7
S143-3
S
128-9
E
146-6
E
197-4
E
201-0
SE
76-0
SE
114-0
SE
152-0
SE
190-0
SE
179-4
NW
14-9
NW
3-6
SE
152-10
LOW TEMP
B130
STERILIZATION COOL
DOWN
B108
OFFICE
B106
DIRTY PROCESSING
B122
STERILE/
NON-STERILE EQUIP
STORAGE
B110
CLEAN HAC
B110A
MACHINE
B109
CORR
CB-18B
RECEIVING /
BREAKDOWN
B114
CORRIDOR
CB-14
OUTPATIENT LOBBY
CB15A
CORRIDOR
CB-16
CORRIDOR
CB15C
CONFERENCE
B102
CORRIDOR
CB13
CORRIDOR
CB-12
MECHANICAL ROOM
#3
BD-111
AUTOPSY PREP
ROOM
BD-117
CORRIDOR
CB-10
ELECTRICAL
CB15K
SIGNAL
BD-110B
VESTIBULE
BD-110A
TELE
BD-110A
EDUCATION LAB
BD-152
OFFICE
BD-149H
BD-149F
OFFICE
BD-149G
SUPERVISOR OFFICE
BD143F
STAFF
BD-143E
CORRIDOR
CB-15
SPD CORRIDOR
CB-18B
ELEV #10
CB-18C
ELEV #9
CB-18D
STAIR #1
CB-18E
ELEV #6
CB-18F
ELEV #5
CB-18G
STAFF ELEV LOBBY
CB-16A
OFFICE
BA-102I
OFFICE
BA-102J
FEMALE LOCKERS /
TOILET
BA-105
MALE LOCKERS /
TOILET
BA-106
BULK STORAGE
BD-105A
MAIL ROOM
BD-105
OFFICE
BA-103
RME COOR / SPD
SECRETARY
B101
ENDO PROCESSING /
HIGH LEVEL
DISINFECTION
B123
DETERGENT
B117
COORD OFFICE
B115
BREAK
B127
FEMALE STAFF
TOILET / LOCKER /
SHOWER
B129
C L
E A
N
A
N T
E
B
OFFICE
B104
OFFICE
B107
UPGRADE
CART
ELEVATOR
PROVIDE
PROJECTOR
SYSTEM WITH
SPEAKERS
CLEAN SCOPE
STORAGE
B124
MALE STAFF TOILET /
LOCKER / SHOWER
B128
FEMALE STAFF
TOILET / SHOWER
B119
MALE STAFF TOILET /
LOCKER / SHOWER
B120
HAC
B118
Room
B405
PREP AND PACK
B126
OFFICE
B105
DECONTAM
B116
PRZ CLOSET
B116A
S O
I L
E D
A
N T
E
B
ANTE
B112
IMPLANT
B111
SUPPLY CLOSET
D & T
TRUE
NORTH
NURSING
TOWER
AREA SHOWN
BUILDING 100
BASEMENT LEVEL
NE
380-0
NE
342-0
NE
304-0
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
LEVEL BASEMENT PLAN
SF101
EPPPNC06/25/2021
SHEET NOTE:
ALL DIMENSIONS, ELEVATIONS, AND LOCATIONS OF EXISTING STRUCTURAL
COMPONENTS ARE BASED ON INFORMATION GATHERED FROM ORIGINAL
DRAWINGS OR CURSORY FIELD MEASUREMENTS AND ARE SHOWN FOR
GENERAL INFORMATION ONLY. CONTRACTOR SHALL FIELD MEASURE AND
VERIFY ALL CONDITIONS PRIOR TO COMMENCING ANY WORK. NOTIFY THE
VA CONTRACTING OFFICER'S REPRESENTATIVE (COR) WHERE CONDITIONS
VARY FROM THOSE SHOWN.
LEVEL BASEMENT PLAN
SCALE: 1/8"=1'-0"
PROJECT
NORTH
GENERAL NOTES
1. SEE ARCHITECTURAL FOR LAYOUT AND
EQUIPMENT LOCATIONS.
KEY PLAN
2. LOCATE EXISTING REINFORCEMENT PRIOR TO CORING
INTO EXISTING CONCRETE SLAB.
3. SEE SF501 FOR TYPICAL DETAILS.
4. SEE B4 AND C4/501 FOR TYPICAL EQUIPMENT ANCHOR
DETAILS FOR USE AT EQUIPMENT WHERE
ANCHORAGE IS NOT SPECIFICALLY NOTED ON THIS
PLAN. EACH PIECE OF EQUIPMENT THAT IS NOT
INTENDED TO BE MOBILE MUST BE ANCHORED.
RECESSED SLAB,
SEE F4/SF501
E4
SF501
WASHER /DISINFECTOR, ENDOSCOPE, (2) LOC
MAX WEIGHT = 1543 LBS
CONNECT SINK BP W/ (4) 1/2" DIA
ADHESIVE ANCHORS W/ 4 1/2" MIN
EMBED TO SOG, TYP SEE C6/SF501
AMSCO 50 3-COMPARTMENT
REPROCESSING SINK, (6) LOC
MAX WEIGHT = 490 LBS
CONNECT SINK BP W/ (4) 1/2" DIA
ADHESIVE ANCHORS W/ 4 1/2" MIN
EMBED TO SOG, TYP SEE C6/SF501
TYP (4) SIDES OF
RECESSED SLAB
SEE F4/SF501 FOR WALL BLKG AT CABINET,
LOCATIONS COORD W/ CABINET SUPPLIER
BRACING REQUIREMENTS
5. FIELD VERIFY OPENING ALIGNMENT AND COORDINATE
WITH MECHANICAL AND EQUIPMENT SUPPLIER PRIOR
TO FABRICATION OF STEEL OR CUTTING OF OPENING.
DO NOT OVERCUT OPENING OR DAMAGE WALL.
OPENING SHALL BE INFILLED WHEN MOVEMENT OF
EQUIPMENT AND MATERIALS THROUGH THE
TEMPORARY OPENING IS COMPLETED. TIME BETWEEN
CUTTING AND INFILL SHALL NOT EXCEED TWO WEEKS
10" (FIELD VERIFY TO MATCH
(E) WALL THICKNESS)
76" W x 120" H TEMPORARY
WALL OPNG, SEE NOTE 5
(E) CONC WALL(E) CONC WALL
(E) BM ABOVE,
FIELD VERIFY
CENTER OPNG BTWN BEAMS
ABOVE, FIELD VERIFY LOC
PRIOR TO CUTTING
B6
SF501
B2
SF502
WALL INFILL
STL
SUPPORT
FRAME
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
DN
SPS SUPPORT
POD
TEMP SPS
PET / CT
HVAC
ENCLOSURE
RADIATION THERAPY
BUILDING 33
STORAGE
8x8 POST W/ SIMPSON RPBZ
POST BASE AND CPS
STAND-OFF, TYP (3) LOC
(E) COVERED WALKWAY (ROOF ABOVE)
4x12 BM, UNO TYP
2x12
DO
DO
DO
DO
DO
DO
DO
DO
4x12
E Q
(3) EQ SPC
TYP
EDGE OF (E) LOADING DOCK AND
WALKWAY, FIELD VERIFY
2x12 @ 24" MAX, (ADDED JOISTS AT
SOME POST LOCATIONS) TYP
DO
x
D O x
E Q
8x8 POST, SEE C6/SF104
FOR POST BASE AND CONC
PAD, TYP (26) LOCATIONS
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
2x12
DO
DO
DO
DO
DO
DO
DO
x
D O x x
D O x x
D O x
4x12 BM, TYP
ALONG THIS LINE
4x12 BM, TYP
ALONG THIS LINE
D & T
TRUE
NORTH
NURSING
TOWER
AREA SHOWN
BUILDING 100
BASEMENT LEVEL
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
COVERED WALKWAY
FOUNDATION PARTIAL PLAN
SF102
EPPPNC06/25/2021
SHEET NOTE:
ALL DIMENSIONS, ELEVATIONS, AND LOCATIONS OF EXISTING STRUCTURAL
COMPONENTS ARE BASED ON INFORMATION GATHERED FROM ORIGINAL
DRAWINGS OR CURSORY FIELD MEASUREMENTS AND ARE SHOWN FOR
GENERAL INFORMATION ONLY. CONTRACTOR SHALL FIELD MEASURE AND
VERIFY ALL CONDITIONS PRIOR TO COMMENCING ANY WORK. NOTIFY THE
VA CONTRACTING OFFICER'S REPRESENTATIVE (COR) WHERE CONDITIONS
VARY FROM THOSE SHOWN.
COVERED WALKWAY FOUNDATION AND FLOOR PARTIAL PLAN
SCALE: 1/8"=1'-0"
PROJECT
NORTH
GENERAL NOTES
1. SEE ARCHITECTURAL FOR WALKWAY LOCATIONS
DIMENSIONS, AND INFORMATION NOTE NOTED.
KEY PLAN
2. LOCATE EXISTING REINFORCEMENT PRIOR TO CORING
INTO EXISTING CONCRETE SLAB.
3. SEE SF104 FOR SECTIONS.
C6
SF104
CONT RIM BOARD, SEE C10/FS104
C10
SF104
4. WOOD JOIST, POST, AND BLOCKING FRAMING SHALL
BE PRESSURE TREATED. CONNECTIONS SHALL USE
HOT-DIP GALVANIZED NAILS AND BOLTS. SIMPSON
CONNECTORS SHALL BE ZMAX OR BETTER.
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
DN
TEMP SPS
PET / CT
HVAC
ENCLOSURE
RADIATION THERAPY
BUILDING 33
[No Slope]
SPS SUPPORT
POD
1/2" / 1'-0"
1/2" / 1'-0"
SEE SF104 POST, TYP
4x8 BM, UNO TYP
(E) COVERED WALKWAY
x
4x8
D O
D O
D O
D O
D O
D O
D O
D O x
2x8 @ 24" MAX (ADDED JOISTS AT
SOME POST LOCATIONS) TYP
2x8
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
D O
DO
DO
DO
DO
DO
DO
DO
DO
D O
D O
D O x
4x8 BM, TYP
ALONG THIS LINE
4x8 BM, TYP
ALONG THIS LINE
x x x x x x x
D & T
TRUE
NORTH
NURSING
TOWER
AREA SHOWN
BUILDING 100
BASEMENT LEVEL
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
COVERED WALKWAY ROOF
FRAMING PLAN
SF103
EPPPNC06/25/2021
SHEET NOTE:
ALL DIMENSIONS, ELEVATIONS, AND LOCATIONS OF EXISTING STRUCTURAL
COMPONENTS ARE BASED ON INFORMATION GATHERED FROM ORIGINAL
DRAWINGS OR CURSORY FIELD MEASUREMENTS AND ARE SHOWN FOR
GENERAL INFORMATION ONLY. CONTRACTOR SHALL FIELD MEASURE AND
VERIFY ALL CONDITIONS PRIOR TO COMMENCING ANY WORK. NOTIFY THE
VA CONTRACTING OFFICER'S REPRESENTATIVE (COR) WHERE CONDITIONS
VARY FROM THOSE SHOWN.
COVERED WALKWAY ROOF FRAMING PLAN
SCALE: 1/8"=1'-0"
PROJECT
NORTH
GENERAL NOTES
KEY PLAN
C6
SF104
SEE ARCHITECTURAL FOR WALKWAY LOCATIONS
DIMENSIONS, AND INFORMATION NOT NOTED.
2. LOCATE EXISTING REINFORCEMENT PRIOR TO CORING
INTO EXISTING CONCRETE SLAB.
3. SEE F104 FOR SECTIONS.
1.
C10
SF104
4. WOOD JOIST, POST, AND BLOCKING FRAMING SHALL
BE PRESSURE TREATED. CONNECTIONS SHALL USE
HOT-DIP GALVANIZED NAILS AND BOLTS. SIMPSON
CONNECTORS SHALL BE ZMAX OR BETTER.
AutoCAD SHX Text
(3) EQ SPC
AutoCAD SHX Text
(3) EQ SPC
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
LEVEL BASEMENT
-18' - 0"
PAVING
-21' - 6"
PET / CT
CONC BASE W/ 5/8" DIA
ANCH SEE NOTE 1, TYP
SIMPSON STRONG-TIE
CB88 POST BASE, TYP
4x12 BM W/ SIMPSON STRONG
TIE LUS410 HANGER, TYP
SIMPSON STRONG-TIE H1, TYP
EACH END OF EACH JST
2x12 FLR JST
POST PER PLAN, TYP
4x8 BM W/ SIMPSON STRONG-TIE
LUS46 HANGER, AT EACH END TYP
2x8 RAFTER
2x12 CONT
SIMPSON STRONG-TIE
LUS210, TYP
SIMPSON STRONG-TIE H1,
EACH END OF EACH JST TYP
LEVEL BASEMENT
-18' - 0"
LEVEL BASEMENT -
INTERSTITIAL
-7' - 11"
PAVING
-21' - 6"
CONT RIM BOARD CONNECT
TO (E) CONC WALKWAY W/ (2) 1/2" DIA EPOXY
ANCH W/ 3" MIN EMBED @ 12" OC
4x12 BM W/ SIMPSON STRONG-TIE
LUS410 HANGER, TYP
(E) CONC WALKWAY
NOTE:
1. SEE C6/SF104 FOR INFORMATION NOT SHOWN HERE.
3/4" APA-RATED PLWD ROOF SHTHG W/ 10d
NLG @ 12" OC FIELD, 4" OC AT PANEL EDGES
SEE ARCH FOR ROOFING, TYP
SEE ARCH FOR RAILING, TYP
2x BLKG, TYP
NOTE:
1. CONCRETE BASE DIMENSIONS SHALL BE A MINIMUM OF 22" BY 22" SQUARE AT THE BASE, TAPERING TO A
MINIMUM OF 12" BY 12" SQUARE AT THE TOP, AND A MINIMUM OF 1'-5" TALL. MINIMUM WEIGHT IS 350 POUNDS.
BASES MAY BE PRECAST OR CAST ON-SITE. CONCRETE STRENGTH SHALL BE 3,500 PSI, MINIMUM.
3/4" APA-RATED EXPOSURE 1 PLWD ROOF
SHTHG W/ 10d NLG @ 12" OC FIELD, 4" OC
AT PANEL EDGES
SIMPSON STRONG-TIE DTT2Z, TYP @
4'-0"OC MAX ALONG THE RIM BOARD
E10
SF104
SIM, TYP EA END OF JOISTS
AT POST LOCATIONS
E10
SF104
TYP AT EA END OF JOISTS
AT POST LOCATIONS
E10
SF104
SIM, TYP EA END OF JOISTS
AT POST LOCATIONS
E10
SF104
TYP AT EA END OF JOISTS
AT POST LOCATIONS
2"
TYP
POST PER PLAN
(4) 1/2" DIA THRU-BOLTS
JST PER PLAN, TYP
EA FACE OF POST
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
COVERED WALKWAY SECTIONS
SF104
EPPPNC06/25/2021
SHEET NOTE:
ALL DIMENSIONS, ELEVATIONS, AND LOCATIONS OF EXISTING STRUCTURAL
COMPONENTS ARE BASED ON INFORMATION GATHERED FROM ORIGINAL
DRAWINGS OR CURSORY FIELD MEASUREMENTS AND ARE SHOWN FOR
GENERAL INFORMATION ONLY. CONTRACTOR SHALL FIELD MEASURE AND
VERIFY ALL CONDITIONS PRIOR TO COMMENCING ANY WORK. NOTIFY THE
VA CONTRACTING OFFICER'S REPRESENTATIVE (COR) WHERE CONDITIONS
VARY FROM THOSE SHOWN.
COVERED WALKWAY CROSS SECTION
SCALE: 1/2" = 1'-0"
C6
COVERED WALKWAY CROSS SECTION
SCALE: 1/2" = 1'-0"
C10
JOIST CONNECTION AT POST LOCATIONS
SCALE: 1/2" = 1'-0"
E10
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text C
NEWEXIST
10" THK SOG W/
#5 @ 16" EW
CENTERED
S E
E
A R
C H
L2x2x3/8 W/
3/8" DIA x 4 WHS @ 12"
(E) SOG
#5 CONT
DOWEL TO
MATCH SLAB REINF
10"
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
REID MIDDLETON
728 134 th
Street SW
(425) 741 - 3800
A/E:
625 IST AVE, UNIT #301
Seattle, WA, 98104
(360) 223 - 8994
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CD
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMP
CONSULTANT
321 4 5 6 7 8 9 10
Structural Engineer:
Everett, WA, 98204
PAUL CROCKER PE SE, SENIOR ENGINEER
663-20-102
Revisions: Date:
SPEES DESIGN BUILD
RENOVATE & EXPAND SEATTLE
STERILE PROCESSING SERVICES
IN BUILDING 100
VA PUGET SOUND HEALTH CARE SYSTEM - Seattle, WA
Suite 200
FULLY SPRINKLERED37358
S
F
E T
TA
IN
O
GT
N
O WASH
IGE
EEN
O
R
I N
GNELARUTCUR
TS
E R
NI
E
100% CD 06/25/2021
TYPICAL SECTIONS AND DETAILS
SF501
EPPPNC06/25/2021
TYPICAL SCREWED STUD GROUP
SCALE: NTS
B10
METAL FRAMING NOTES
SCALE: NTS
C8
@ TRACKS, UNO
DRIVE PIN SPC
HEIGHT
MAX WALL
DEPTH
STUD
600S162-33
600S200-43
600S200-43
600S200-68
600S137-33
600S137-33
600S137-33
600S137-33
400S162-33
400S200-43
400S137-33
400S137-33
METAL STUD WALL TYPES
SPACING
STUD
STUD
TYPE
6" OC
5" OC
8" OC
6" OC
8" OC
10" OC
METAL FRAMING NOTES:
1. METAL FRAMING USED SHALL CONFORM TO THE SPECIFICATIONS OUTLINED IN THE
GENERAL NOTES IN ADDITION TO REQUIREMENTS NOTED HERE.
2. METAL FRAMING AND STRAP BRACING SHALL BE GALVANIZED UNLESS NOTED
OTHERWISE CONFORMING AS FOLLOWS:
12, 14, 16 GAGE ASTM A653, QUALITY SQUARE GRADE 50, CLASS 1
18, 20 GAGE ASTM A653, QUALITY SQUARE GRADE 33.
3. ALL STUDS AND STUD GROUPS SHALL BE LATERALLY SUPPORTED TO PREVENT WEAK
AXIS BUCKLING BY CONNECTING EACH FLANGE TO GYPSUM WALLBOARD. WALLS
WHICH HAVE SHEATHING CONNECTED ON ONE SIDE ONLY SHALL HAVE UNSHEATHED
FLANGES LATERALLY SUPPORTED PER DETAIL.
4. TRACK SECTIONS SHALL BE UNPUNCHED WITH GAGE MATCHING STUDS, AND HAVE
LEAST 1" FLANGES.
5. WELDING OF COLD-FORMED METAL FRAMING SHALL CONFORM TO AWS D1.3 AND
SHALL BE PERFORMED BY WELDERS QUALIFIED TO PRODUCE THE SPECIFIED
CLASSES OF WELD.
6. SCREWS TO BE #8 SIZE, UNLESS NOTED OTHERWISE.
7. WALL FRAMING:
TWO STUD MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH
SIDE OF ALL OPENINGS. SEE DETAIL FOR FRAMING OF OPENINGS, UNLESS NOTED
OTHERWISE.
8. SEE DETAIL FOR REQUIRED BRIDGING.
9. SEE ARCHITECTURAL FOR SIZING AND DETAILING OF INTERIOR NON-BEARING WALLS.
10. TRACK CONNECTED TO CONCRETE OR STRUCTURAL STEEL SHALL BE FASTENED
WITH .138" MINIMUM DIAMETER DRIVE PINS AT SPACING PER TABLE BELOW.
F
S
F
4'-0" MAX
PLAN
TRACK TO MATCH
TOTAL STUD WIDTH, ES
SCREWS @ 2'-0" OC
TYP (6) PLCS
SCREWS @ 2'-0" OC
TYP (4) PLCS
STUDS, PER PLAN OR SCHED
TRACK SAME GA
AS STUD W/ 1"
WIDE FLG MIN
L16GAx1 1/2x1 1/2
BRIDGE CLIP, TYP
1/2
(4) SCREWS
16 GA
TRACK
(2) ROWS OF
(4) #12 SCREWS
ES OF SPLICE
UNPUNCHED STUD
GAGE TO MATCH
TRACK
TYP STUDS, PER NOTES
STUD GROUP, ES OF OPNG
SEE B10/SF501
HEADER & SILL
SEE F8/SF501
NOTES:
1. BRIDGING IS REQUIRED FOR LOADINGS APPLIED BEFORE SHEATHING IS
ATTACHED TO BOTH FLANGES. BRIDGING PROVIDES RESISTANCE TO ROTATION
CAUSED BY WIND LOADING, AND RESISTANCE TO BOTH ROTATIONAL AND
MINOR AXIS BENDING CAUSED BY AXIAL LOADING.
2. BRIDGING SHALL BE EITHER WELDED OR SCREWED AS SHOWN.
18GA BRIDGING C @
4'-0" OC VERT MAX, TYP
L 1 1/2x1 1/2, SAME GA
AS STUD LENGTH =
STUD WIDTH LESS 1/2"
USE (3) SCREWS TO
ATTCH L TO WEB
NOTES:
1. STUD WEBS SHALL BEAR AGAINST TRACK WEBS.
2. ATTACH ANGLE TO TRACK WITH SCREWS WHERE POSSIBLE. WHERE TRACKS IS ON CONCRETE OR
AGAINST STEEL, SHOOT (2) .138 MIN DIA DRIVE PINS THROUGH…