Attachment 7-Part 6 of 9-Drawings-EHRM-Salt Lake City.pdf

PDF 17 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction - Salt Lake City VAMC Project 660-21-700
Solicitation number
36C77623B0041
Issued by

About this file

This document contains details of a federal contract opportunity for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals for the EHRM Infrastructure Upgrades Construction project at the Salt Lake City VAMC. Offerors should submit proposals in response to solicitation number 36C77623B0041 by the specified deadline to be considered for award of a contract to provide construction services for upgrades and improvements at the medical center's facilities. Key project details include a scope of work involving infrastructure upgrades at the Salt Lake City VAMC, with Attachment 7 of the solicitation package containing relevant construction drawings. The award is expected to be finalized in 2021.

View the file

Other files

File Type Posted
RESPONSE Attachment V5.1.docx DOCX document
Construction Wage Rates- Salt Lake County- 08-11-2023.pdf PDF
ADDENDUM No 01.pdf PDF
Bid opening call-in information.pdf PDF
RESPONSE Attachment V5.1 No. 30 Snippet.JPG JPG image
2017 AHERA 3-Year Reinspection v2.2 2017_1205_BT.xlsx XLSX spreadsheet
RESPONSE V10 - Technical Questions.docx DOCX document
RESPONSE Attachment V7.2.docx DOCX document
36C77623B0041 0004.pdf PDF
RESPONSE Attachment V2.1.docx DOCX document
RESPONSE Attachment V1.1.docx DOCX document
RESPONSE Attachment V7.1.docx DOCX document
RESPONSE Attachment V3.1.docx DOCX document
36C77623B0041 0003.pdf PDF
36C77623B0041 0003.pdf PDF
36C77623B0041 0002.pdf PDF
660-21-700 PreConstruction Site Visit Sing In Sheet 2023 07 14.pdf PDF
36C77623B0041 0001.pdf PDF
Attachment 13-Utah Tax Memo-EHRM-Salt Lake City.pdf PDF
Attachment 12-Construction Wage Rates-Salt Lake County- 04-14-2023.pdf PDF
Attachment 14-Limitations on Subcontracting-EHRM-Salt Lake City.docx DOCX document
Attachment 2-Part 1 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 15-Contractor Safety-Environmental-EHRM-S.L.C..docx DOCX document
Attachment 1-Specifications-(1 of 1)-EHRM-Salt Lake City.pdf PDF
Attachment 6-Part 5 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 3-Part 2 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 9-Part 8 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 5-Part 4 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
36C77623B0041.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 11-Asbestos Site Survey-EHRM Salt Lake City.pdf PDF
Attachment 10-Part 9 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 4-Part 3 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 8-Part 7 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

C

B

131211 1514

T

T

T

SS-2

14-B-A-E-P4-7,9,11

SS-2

14-G-A-E-P1-7,9,11

SS-2

14-1-A-E-P1-7,9,11

SS-2

14-2-A-E-P1-7,9,11

SS-2

14-3-A-E-P1-7,9,11

W 14-3-A-E-P1-13

SS-2

14-G-C-E-P2-7,9,11

SS-2

14-1-C-E-P7-7,9,11

SS-2

14-2-C-E-P1-7,9,11

SS-2

14-3-C-E-P3-7,9,11

SS-2

14-B-C-E-P3-7,9,11

W14-3-C-E-P3-13

W 14-B-C-E-P3-13

W 14-B-A-E-P4-13

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:3

A M

14-EP140

OVERALL ROOF POWER PLAN EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

SHEET

KEYNOTES

GENERAL

SHEET NOTES

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

0' 8' 16' 32' 64'

GRAPHIC SCALE 1/16" = 1'-0"

4'

NORTH

1/16" = 1'-0"F3

OVERALL ROOF POWER PLAN

1 SPLIT CONDENSING UNIT LOCATED ON ROOF. SEE

MECHANICAL DRAWINGS FOR EXACT LOCATION.

2 SPLIT CONDENSING UNIT LOCATED ON ROOF. SEE

MECHANICAL DRAWINGS FOR EXACT LOCATION.

3 PROVIDE A SEPARATE 120 VOLT, 20 AMP, 1 PHASE

CIRCUIT AND WEATHER PROOF GFCI OUTLET

MOUNTED TO SIDE OF CONDENSING UNIT.

Revisions: Date:

06/08/23

DF

DOWN

UPUP

UP

UP

BAE1

BA09

BA06 BA05

BA04B

BA04ABA04C

BA04E

BA04F

BA04DA

BA04

BA07

BA04D

BB03D

B B

03 BB03C

BB03B

BB03A

BB07

BB08

BB09

BB11A

BB10

BB11

BB11B

BB04C

BB04B

BB04A

BB15

BB14

BB13

BB12C

BA03A

BA03BBA03.16

BA08

BA07AA

B A

A

BA03

BA01

BB06

BB05

BBE5

BB04

BB12D

BB12

BB12B

BC09

BC02

BC04

B C

BC10

BC11

BC01BB01

BBA

BD01BB

BD00

BB02

BB00

BC03

B C

BC07

BCOOD

BC08A

BC08B

BC08

BCOOC

BC00B

BCA

BCE1

BC00A

B C

BD01A

BD01B

BD02

BD01

BD03C

BD03A

BD03

BBE2 BBE4

BBB

BBE3

BAA

BA11

BA02

BA02A

BD03B

BBE4

B C

E

BC00F

"H" ELEVATOR LEVEL

EXTRASTITIAL (MECH/ELECT)

ELECTRICAL TEL/DATA

HAC

TOILET (WOMEN)TOILET (MEN)

OFFICE

OFFICE

COLD ROOM

ENTRY (MORGUE)

DEMONSTRATIONS (MORGUE)

MORGUE

OFFICE (90)

M A

IL

R

O O

M

OFFICE (90)

STORAGE (90)

OFFICE

TOILET (WOMEN)

HAC

TOILET (MEN)

OFFICE (04)

OFFICE (04)

OFFICE (04)

OFFICE (PATIENT

RECORDS)

OFFICE

EMS TRAINING

STORAGE (04 RECORDS)

MECHANICAL ROOM

MECHANICAL (WATER TREATMENT)

SHOP

STORAGE (PATIENT

EFFECTS)

OFFICE (136)

OFFICE (136)BREAKRM (136)

MECHANICAL ROOM

PREP (CHEMICAL)

S T

O R

A G

E (S

P E

C

IM

E N

S

OFFICES (136)

EXTRASTITIAL (MECH/ELECT)

EXTRASTITIAL (MECH/ELECT)

MECHANICAL ROOM

DUMBWAITER

STORAGE (04 RECORDS)

CLOTHING ROOM

WAITING (CLOTHING ROOM)

DRESSING

(CLOTHING ROOM)

STORAGE (138E)

CHUTE (TRASH)

CHUTE (LINEN)

S T

O R

A G

E (P

H A

R M

A C

Y R

E C

E

IV

IN

G

TOILET (UNISEX)

EXTRASTITIAL (MECH/ELECT)

EXTRASTITIAL (MECH/ELECT)MECHANICAL

STAIR LEVEL

STORAGE

VESTIBULE

MECH. RM.

CORRIDOR

MECHANICAL

S T

O R

A G

E

TEL/DATA

DOCK (LOADING/UNLOADING)

ELECTRICAL (EMERGENCY GEN)

ELECTRICAL

ELECTRICAL

CORRIDOR (TO LOADING DOCK)

CORRIDOR (TO LOADING DOCK)

STAIR LEVEL

"G" ELEVATOR LEVEL

LOBBY (ELEVATOR)

C O

R R

ID

O

R

LIBRARY CENTER

OFFICE

MECHANICAL

LIBRARY AREA

TEL/DATA

ELECTRICAL

ENTRY (UTILITIES)

"D" ELEVATOR LEVEL "C" ELEVATOR LEVEL

STAIR LEVEL

"E" ELEVATOR LEVEL (FUTURE)

STAIR LEVEL

OFFICE (CAK)

SHOP (LOCKS & KEYS)

SHOP

TEL/DATA

"F" ELEVATOR LEVEL (FUTURE)

C O

R R

ID

O

R

TO

E

LE

V

A T

O R

S /B

.0 1)

LOBBY (ELEVATORS)

CORRIDOR

F .E

.C

F.E.C.

T

T

C

C

C

W

C

C

C

C

C

C

C

C

C

C

C

C

14-EP402

F7

14-EP402

D7

14-EP403

D5

14-EP403

B5

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:4

A M

14-EP1B0

OVERALL BASEMENT LEVEL

POWER PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/16" = 1'-0"F3

OVERALL BASEMENT POWER PLAN

SHEET

KEYNOTES

GENERAL

SHEET NOTES

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

0' 8' 16' 32' 64'

GRAPHIC SCALE 1/16" = 1'-0"

4'

F .E

.C

T

S T

CORRIDOR

GA00-14

"14-G-A-E-P1"

(PG4)

(PG4) (PG4)

(PG4)

14-G-A-E-P1-1,3,5

RACK-30

14-G-A-C1-P2-1,3,5

RACK-30

14-G-A-C1-P2-7

AC-2

14-G-A-E-P1-13,15

14-G-A-E-P1-17

14-G-A-E-P1-19

14-G-A-E-P1-21

14-G-A-E-P1-23

TELECOMMUNICATIONS

ROOM

GA24-14

INTERNAL

MEDICINE

SERVICES

GA26-14

BIOMED

GA28-14

HAC

GA30-14

14-1-B-N-P2

14-1-B-N-P2

14-1-B-N-P2

14-1-B-N-P2

14-1-B-N-P2

14-G-B-C1-P2

14-G-B-C1-P2

14-G-B-C1-P2

14-G-B-C1-P2

(PG4) (PG4)

(G-4)

(G-4)

(G-4)(G-4)

(G-4)

(G-4)

(G-4)

(G-4)

(G-4)

(G-4)(G-4)

(G-1)

(G-4) (G-4)

(G-4)(G-4)

CORRIDOR

GA00-14

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:5

A M

14-EP401

ENLARGED POWER PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

SHEET

KEYNOTES

GENERAL

SHEET NOTES

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

1 PROVIDE AN OVERHEAD POWER DROP CORD WITH

A 30 AMP 208 VOLT THREE-PHASE TWISTED LOCK

RECEPTACLE (L21-30R); 8.5 FT AFF (WYE(5-WIRE))

COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR. SEE SHEET

EE002, EE501, AND PANEL SCHEDULE. PROVIDE

RACK MOUNTED POWER DIST. (2RU), RACK

MOUNTED UPS (6RU) AND PDU PER TELECOM

EQUIPMENT RACK ELEVATIONS ON ET500'S.

2 SECONDARY BONDING BUSBAR (SBB). SEE ET

SHEETS FOR PLACEMENT AND GROUNDING

DETAIL. CONTRACTOR TO PROVIDE A SEPARATELY

DERIVED #3/0 GROUND FROM BUILDING GROUND

TO TR BUSBARS. CONTRACTOR TO VERIFY

BUSBAR’S RESISTANCE IS UNDER 4 OHMS

MEASURED BY THE FOUR POINT

FALL-OF-POTENTIAL METHOD PER IEEE 81.

3 PROVIDE A 100 AMP, THREE-PHASE, FOUR WIRE,

208 VOLT SERVICE PANEL. PANEL SHALL BE

EQUIPPED WITH A POWER METER.

4 LIGHTING CONTROL AND POWER TO BE

CONNECTED TO EXISTING LIGHT CIRCUIT FOR THE

SPACE.

5 PROVIDE THERMAL SWITCH FOR SPLIT SYSTEM.

THERMAL SWITCH TO BE MOUNTED ON SIDE OF

UNIT.

0' 2' 4' 8' 16'

GRAPHIC SCALE 1/4" = 1'-0"

1'

NORTH

3/8" = 1'-0"F1

ENLARGED GROUND FLOOR A-WING -

CORRIDOR - OUTSIDE OF GA24-14 ELECTRICAL PLAN

NORTH

3/8" = 1'-0"F5

ENLARGED GROUND FLOOR A-WING TECHNOLOGY ROOM GA24-14 ELECTRICAL PLAN

F .E

.C

T S

T

F.E.C.

T

ST

F.E.C.

T

ST

F .E

.C

S T

F.E.C.

T

ST

"14-B-A-E-P4"

"14-B-A-C1-P2"

(PG4) (PG4)

(PG4)

(PG4)

14-B-A-C1-P2-1,3,5

RACK-30

14-B-A-E-P4-1,3,5

RACK-30

14-B-A-C1-P2-7

AC-2

14-B-A-E-P4-15,17

14-B-A-E-P4-1914-B-A-E-P4-25

14-B-A-E-P4-21

14-B-A-E-P4-23

TELECOMMUNICATIONS

ROOM

BA04F-14

"14-B-C-C1-P3"

"14-B-C-E-P3"

(PG4)

(PG4) (PG4)

(PG4)

(PG4)

(PG4)

14-B-C-C1-P3-1,3,5

RACK-30

14-B-C-E-P3-1,3,5

RACK-30

14-B-C-C1-P3-2,4,6

RACK-30

14-B-C-E-P3-2,4,6

RACK-30

AC-2

14-B-C-E-P3-15,17

14-B-C-C1-P3-7

14-B-C-E-P3-25

14-B-C-E-P3-23

14-B-C-E-P3-21

14-B-C-E-P3-19

TELECOMMUNICATIONS

ROOM

BC07-14

(PG4) (PG4)

(PG4)(PG4)

"14-G-C-E-P2"

"14-G-C-C1-P3"

14-G-C-C1-P3-1,3,5

RACK-30

14-G-C-E-P2-1,3,5

RACK-30

AC-2

14-G-C-E-P2-15,17

14-G-C-E-P2-13 14-G-C-E-P2-19

14-G-C-E-P2-21

14-G-C-E-P2-23

14-G-C-E-P2-25

TELECOMMUNICATIONS

ROOM

GC31-14

"14-1-A-C1-P1"

"14-1-A-E-P1"

(PG4) (PG4)

(PG4)(PG4)

14-1-A-E-P1-1,3,5

RACK-30

14-1-A-C1-P1-1,3,5

RACK-30

14-1-A-C1-P1-7

AC-2

14-1-A-E-P1-13,15

14-1-A-E-P1-21

14-1-A-E-P1-23

14-1-A-E-P1-17

14-1-A-E-P1-19

TREATMENT

ROOM

1A14-14

TELECOMMUNICATIONS

ROOM

1A16-14

A

"14-1-C-C1-P5"

(PG4) (PG4)

(PG4)(PG4)

14-1-C-E-P7-1,3,5

RACK-30

14-1-C-C1-P5-1,3,5

RACK-30

AC-2

14-1-C-E-P7-13,15

14-1-C-C1-P5-7

14-1-C-E-P7-17 14-1-C-E-P7-21

"14-1-C-E-P7" 14-1-C-E-P7-19

TELECOMMUNICATIONS

ROOM

1C26-14

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:1

A M

14-EP402

ENLARGED POWER PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/4" = 1'-0"F7

ENLARGED TECHNOLOGY ROOM BA04F-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"D7

ENLARGED TEL/DATA BC07-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"F5

ENLARGED TECHNOLOGY ROOM GC31-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"D5

ENLARGED TECHNOLOGY ROOM 1A16-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"B7

ENLARGED TECHNOLOGY ROOM 1C25-14 ELECTRICAL PLAN

SHEET

KEYNOTES

GENERAL

SHEET NOTES

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

1 PROVIDE AN OVERHEAD POWER DROP CORD WITH

A 30 AMP 208 VOLT THREE-PHASE TWISTED LOCK

RECEPTACLE (L21-30R); 8.5 FT AFF (WYE(5-WIRE))

COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR. SEE SHEET

EE002, EE501, AND PANEL SCHEDULE. PROVIDE

RACK MOUNTED POWER DIST. (2RU), RACK

MOUNTED UPS (6RU) AND PDU PER TELECOM

EQUIPMENT RACK ELEVATIONS ON ET500'S.

2 SECONDARY BONDING BUSBAR (SBB). SEE ET

SHEETS FOR PLACEMENT AND GROUNDING

DETAIL. CONTRACTOR TO PROVIDE A SEPARATELY

DERIVED #3/0 GROUND FROM BUILDING GROUND

TO TR BUSBARS. CONTRACTOR TO VERIFY

BUSBAR’S RESISTANCE IS UNDER 4 OHMS

MEASURED BY THE FOUR POINT

FALL-OF-POTENTIAL METHOD PER IEEE 81.

3 PROVIDE A 100 AMP, THREE-PHASE, FOUR WIRE,

208 VOLT SERVICE PANEL. PANEL SHALL BE

EQUIPPED WITH A POWER METER.

4 PROVIDE THERMAL SWITCH FOR SPLIT SYSTEM.

THERMAL SWITCH TO BE MOUNTED ON SIDE OF

UNIT.

5 COORDINATE NEW POWER CONFIGURATION WITH

EXISTING RACKS AND EQUIPMENT.

0' 2' 4' 8' 16'

GRAPHIC SCALE 1/4" = 1'-0"

1'

ADDENDUM #1 Date 1 06/08/23

F.E.C.

T

S T

F.E.C.

T

ST

F .E

.C

ST

CR

F .E

.C

S T

(PG4)

(PG4)(PG4)

(PG4)

"14-2-A-C1-P1"

"14-2-A-E-P1"

2 3

14-2-A-E-P1-1,3,5

RACK-30

14-2-A-C1-P1-1,3,5

RACK-30

AC-2

14-2-A-E-P1-13,15

14-2-A-C1-P1-7

14-2-A-E-P1-1714-2-A-E-P1-21

14-2-A-E-P1-19

TELECOMMUNICATIONS

ROOM

2A17-14

"14-2-C-E-P1"

"14-2-C-C1-P6"

(PG4)

(PG4)(PG4)

(PG4)

14-2-C-C1-P6-1,3,5

RACK-30

14-2-C-E-P1-1,3,5

RACK-30

AC-2

14-2-C-E-P1-13,15

14-2-C-E-P1-17 14-2-C-E-P1-21

14-2-C-E-P1-19

HAC

2C16-14

TELECOMMUNICATIONS

ROOM

2C32-14

(PG4) (PG4)

(PG4)(PG4)

"14-3-A-E-P1"

"14-3-A-C1-P3"

1 12

14-3-A-E-P1-1,3,5

RACK-30

14-3-A-C1-P3-1,3,5

RACK-30

AC-2

14-3-A-E-P1-15,17

14-3-A-E-P1-19

14-3-A-C1-P3-7

14-3-A-E-P1-23

14-3-A-E-P1-21

(G-4)

HAC

3A12-14

TELECOMMUNICATIONS

ROOM

3A08-14

RR

"14-3-C-C1-P1"

"14-3-C-E-P3"

(PG4)

(PG4) (PG4)

(PG4)

14-3-C-C1-P1-1,3,5

RACK-30

14-3-C-E-P3-1,3,5

RACK-30

AC-2

14-3-C-E-P3-15,17

14-3-C-C1-P1-7

14-3-C-E-P3-21

14-3-C-E-P3-23

14-3-C-E-P3-19

14-3-C-E-P3-25

TELECOMMUNICATIONS

ROOM

3C16-14

"14-B-C-C1-P1"

"14-B-A-E-P3"

"14-B-A-C1-TR1"

"14-B-A-E-TR1"

F8

14-EP603

ELECTRICAL

BA05-14

"14-B-C-E-P2"

"14-B-C-C1-P2"

"14-B-A-C1-TR1"

"14-B-A-E-TR1"

F8

14-EP603

14-2-B-N-P12

14-2-B-N-P12

CHIEF

RESIDENTS

IN QUALITY

AND PATIENT

SAFETY

2C20-14

UTILITY

(SOILED)

2C18A-14

LOCKERS

2C18-14

+42"

14-2-B-C1-P5

14-2-B-N-P12

14-2-B-N-P12

PRINT

UC-REF

A

14-2-B-N-P4

(G-1) (G-1)

(G-4) (G-4) (G-4)

(G-4)

CHANGING

ROOM

3A28A-14

OFFICE

3A26-14

WHEELCHAIR

HOLDING

3A26A-14

CHANGING

ROOM

3A28-14

14-2-B-C2-P3

14-2-B-C2-P314-2-B-N-P414-2-B-N-P4

(G-1) (G-4)

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:2

A M

14-EP403

ENLARGED POWER PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/4" = 1'-0"F7

ENLARGED TECHNOLOGY ROOM 2A17-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"D7

ENLARGED TECHNOLOGY ROOM 2C32-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"B7

ENLARGED TECHNOLOGY ROOM 3A08-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"F5

ENLARGED TECHNOLOGY ROOM 3C16-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"D5

ENLARGED TELE/DATA BA05 & ELECTRICAL BA06 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"B5

ENLARGED ELECTRICAL BD03A ELECTRICAL PLAN

SHEET

KEYNOTES

GENERAL

SHEET NOTES

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

NORTH

1/4" = 1'-0"F2

ENLARGED CHIEF RESIDENTS OFFICE 2C20-14 ELECTRICAL PLAN

NORTH

1/4" = 1'-0"D2

ENLARGED OFFICE 3A26-14 ELECTRICAL PLAN

1 PROVIDE AN OVERHEAD POWER DROP CORD WITH

A 30 AMP 208 VOLT THREE-PHASE TWISTED LOCK

RECEPTACLE (L21-30R); 8.5 FT AFF (WYE(5-WIRE))

COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR. SEE SHEET

EE002, EE501, AND PANEL SCHEDULE. PROVIDE

RACK MOUNTED POWER DIST. (2RU), RACK

MOUNTED UPS (6RU) AND PDU PER TELECOM

EQUIPMENT RACK ELEVATIONS ON ET500'S.

2 SECONDARY BONDING BUSBAR (SBB). SEE ET

SHEETS FOR PLACEMENT AND GROUNDING

DETAIL. CONTRACTOR TO PROVIDE A SEPARATELY

DERIVED #3/0 GROUND FROM BUILDING GROUND

TO TR BUSBARS. CONTRACTOR TO VERIFY

BUSBAR’S RESISTANCE IS UNDER 4 OHMS

MEASURED BY THE FOUR POINT

FALL-OF-POTENTIAL METHOD PER IEEE 81.

3 PROVIDE A 100 AMP, THREE-PHASE, FOUR WIRE,

208 VOLT SERVICE PANEL. PANEL SHALL BE

EQUIPPED WITH A POWER METER.

4 PROVIDE GFCI CIRCUIT BREAKER IN PANEL

SERVING REFRIGERATOR.

5 PROVIDE THERMAL SWITCH FOR SPLIT SYSTEM.

THERMAL SWITCH TO BE MOUNTED ON SIDE OF

UNIT.

6 LIGHTING CONTROL AND POWER TO BE

CONNECTED TO EXISTING LIGHT CIRCUIT FOR THE

SPACE.

7 PROTECT BIOMED EQUIPMENT AND COPPER

TELEPHONE FROM CONSTRUCTION. BIOMED

EQUIPMENT AND COPPER TELEPHONE TO STAY IN

PLACE AND OPERATIONAL.

0' 2' 4' 8' 16'

GRAPHIC SCALE 1/4" = 1'-0"

1'

BASEMENT FLOOR

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

BASEMENT FLOOR

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

(PARTIAL) CRITICAL BRANCH

"14-B-C-C1-D1" 1000A, 480/277V, 3Ø, 4W

"14CDP" (EXISTING)

(PARTIAL) CRITICAL BRANCH

"14-B-C-C1-D1" 1000A, 480/277V, 3Ø, 4W

"14CDP" (EXISTING)

(PARTIAL) EQUIPMENT BRANCH

"14-B-C-E-D2" 1600A, 480/277V, 3Ø, 4W

"14EDP" (EXISTING)

(PARTIAL) EQUIPMENT BRANCH

"14-B-C-E-D2" 1600A, 480/277V, 3Ø, 4W

"14EDP" (EXISTING)

175/3

300/3

100/3

"14-G-A-E-P1"

100/3

"14-1-A-E-P1"

100/3

"14-2-A-E-P1"

100/3

"14-3-A-E-P1"

100/3

"14-B-A-E-P4"

100/3

100/3

100/3

100/3

100/3

"14-B-A-E-P3"

"14-B-A-E-TR1"

75 KVA

480-208Y/120V

3Ø, 4W

200/3

#2 CU

SE

175/3

300/3

100/3

"14-G-C-E-P2"

100/3

"14-1-C-E-P7"

100/3

"14-2-C-E-P1"

100/3

"14-3-C-E-P3"

100/3

"14-B-C-E-P3"

100/3

100/3

100/3

100/3

100/3

"14-B-C-E-P2"

"14-B-C-E-TR1"

75 KVA

480-208Y/120V

3Ø, 4W

200/3

#2 CU

SE

175/3

300/3

100/3

"14-G-A-C1-P2"

100/3

"14-1-A-C1-P1"

100/3

"14-2-A-C1-P1"

100/3

"14-3-A-C1-P3"

100/3

"14-B-A-C1-P2"

100/3

100/3

100/3

100/3

100/3

"14-B-A-C1-P1"

"14-B-A-C1-TR1"

75 KVA

480-208Y/120V

3Ø, 4W

200/3

#2 CU

SE

175/3

300/3

100/3

"14-G-C-C1-P1"

100/3

"14-1-C-C1-P5"

100/3

"14-2-C-C1-P6"

100/3

"14-3-C-C1-P1"

100/3

"14-B-C-C1-P3"

100/3

100/3

100/3

100/3

100/3

"14-B-C-C1-P2"

"14-B-C-C1-TR1"

75 KVA

480-208Y/120V

3Ø, 4W

200/3

#2 CU

SE

F5

POWER RISER ONE-LINE DIAGRAM -

BUILDING #14 - AREA "A"

F8

POWER RISER ONE-LINE DIAGRAM -

BUILDING #14 - AREA "C"

NO SCALE NO SCALE

TR

3AXX-14

TR

2A17-14

TR

1A16-14

TR

GB24-14

TELE/DATA

BA05

TR

3C16-14

TR

2C32-14

TR

1C25-14

TR

GC31-14

ELECTRICAL

BB03A

TR

BA04F-14

TR

BA04F-14

TR

BC07-14

TR

BC07-14

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:3

A M

14-EP601

PARTIAL ONE-LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

GENERAL

SHEET NOTES

1 PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT

LOCATED OUTDOORS. REFER TO PLANS FOR

EQUIPMENT LOCATIONS.

2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL

DIMENSIONS AND CLEARANCE REQUIREMENTS OF

EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS

THAT FALL WITHIN THE CONSTRAINTS OF EACH

SPECIFIC LOCATION.

3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND

BRACED FOR THE SEISMIC CONDITIONS OF THE

PROJECT. REFER TO ELECTRICAL SPECIFICATIONS

FOR REQUIREMENTS.

4 PROVIDE PERFORMANCE TESTING FOR

GROUND-FAULT PROTECTION SYSTEMS ON SITE

WITH A WRITTEN RECORD OF THIS TEST

SUBMITTED TO THE AUTHORITY HAVING

JURISDICTION PER NEC 230.95(C).

SYM AMP

HH

AMPS

CONDUIT

SIZE

CONDUCTOR (NOTE 1)

IG/HH SE NOTESQTY SIZE G

1 20 - .75 2 12 12 12 8 2

2 20 - .75 3 12 12 12 8 2,3

3 20 24 .75 4 12 12 12 8 2,3

4 30 - .75 2 10 10 10 8 2

5 30 - .75 3 10 10 10 8 2

6 30 32 .75 4 10 10 10 8 2

7 40 - 1 2 8 10 8 6 2

8 40 - 1 3 8 10 8 6 2

9 40 44 1 4 8 10 8 6 2

10 55 - 1 2 6 10 8 4 2

11 55 - 1 3 6 10 8 4 2

12 55 60 1.25 4 6 10 8 4 2

13 70 - 1 2 4 8 4 2 2

14 70 - 1.25 3 4 8 4 2 2

15 70 76 1.25 4 4 8 4 2 2

16 85 - 1.25 2 3 8 3 2 2

17 85 - 1.25 3 3 8 3 2 2

18 85 92 1.25 4 3 8 3 2 2

19 95 - 1.25 3 2 8 2 2 2

20 95 104 1.50 4 2 8 2 2 2

21 130 - 1.50 3 1 6 2 2 2

22 130 116 1.50 4 1 6 2 2 2

23 150 - 2 3 1/0 6 2 1/0 2

24 150 136 2 4 1/0 6 2 1/0 2

25 175 - 2 3 2/0 6 2 2/0 2

26 175 156 2 4 2/0 6 2 2/0 2

27 200 - 2 3 3/0 6 2 2/0 2

28 200 180 2.50 4 3/0 6 2 2/0 2

29 230 - 2.50 3 4/0 4 2 2/0 2

30 230 208 2.50 4 4/0 4 2 2/0 2

31 255 - 2.50 3 250 4 1 2/0 2

32 255 232 2.50 4 250 4 1 2/0 2

33 310 - 3 3 350 3 1/0 3/0 2

34 310 280 3 4 350 3 1/0 3/0 2

35 380 - 3.50 3 500 3 3/0 3/0 2

36 380 344 4 4 500 3 3/0 3/0 2

37 400 - 2 EA 2 3 3/0 3 3/0 3/0 2

38 400 360 2 EA 2.50 4 3/0 3 3/0 3/0 2

39 510 - 2 EA 2.50 3 250 1 4/0 3/0 2

40 510 464 2 EA 3 4 250 1 4/0 3/0 2

41 620 - 2 EA 3 3 350 1/0 4/0 3/0 2,4

42 620 560 2 EA 3 4 350 1/0 4/0 3/0 2,4

43 760 - 2 EA 3.50 3 500 1/0 4/0 3/0 2,4

44 760 688 2 EA 4 4 500 1/0 4/0 3/0 2,4

45 855 - 3 EA 3 3 300 2/0 4/0 3/0 2,4

46 855 768 3 EA 3 4 300 2/0 4/0 3/0 2,4

47 1000 - 3 EA 3.50 3 400 2/0 4/0 3/0 4

48 1000 912 3 EA 3.50 4 400 2/0 4/0 3/0 4

49 1140 - 3 EA 4 3 500 3/0 4/0 3/0 4

50 1140 1032 3 EA 4 4 500 3/0 4/0 3/0 4

51 1240 - 4 EA 3 3 350 3/0 4/0 3/0 4

52 1240 1120 4 EA 3 4 350 3/0 4/0 3/0 4

53 1675 1520 5 EA 4 4 400 4/0 4/0 4/0 4

54 2010 1824 6 EA 4 4 400 250 250 250 4

55 2660 2408 7 EA 4 4 500 350 350 350 4

56 3040 2752 8 EA 4 4 500 500 500 500 4

57 4180 3784 11 EA 4 4 500 500 500 500 4

58 - - 5 EA 4 - - - - - 6

59 - - 5 - - - - - 6

60 - - 10 EA 4 - - - - - 6

IG

(E.G.)

COPPER CONDUCTOR AND

CONDUIT SCHEDULE

SUBSCRIPT (NOTE 5)

SCHEDULE NUMBER

1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS

AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE THWN UNLESS

OTHERWISE NOTED.

2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122 WHEN

CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN IN

TABLE.

3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING

COMPUTERS.

4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE

CONDUCTORS.

5. SYMBOL SUBSCRIPTS:

"2N": INCLUDE TWO NEUTRAL CONDUCTORS SIZED AS SCHEDULED FOR

PHASE AND NEUTRAL CONDUCTORS WHERE THE CONDUCTOR IS #1/0

OR LARGER. INCLUDE A SINGLE 200% RATED CONDUCTOR THAT IS

TWICE THE AMPACITY OF THE SCHEDULED PHASE AND NEUTRAL

CONDUCTOR WHERE THE CONDCUTOR IS BELOW #1/0 IN SIZE.

"CI": PROVIDE CIRCUIT INTEGRITY CABLE; TYPE TWO-HOUR FIRE

RESISTIVE CABLES IN CONDUIT OR PROVIDE FEEDER ENCASED IN

CONCRETE.

"FG" FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING CONDUCTOR TO

BE SAME SIZE AS THE PHASE CONDUCTORS.

"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC "NONLINEAR"

LOADS. CURRENT CARRYING CONDUCTORS DERATED

ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT

GROUNDING CONDUCTOR.

"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)

SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND

CONDUCTOR.

"MC": PROVIDE FEEDER IN METAL-CLAD CABLE; TYPE MC IN PLACE OF

SINGLE CONDUCTORS IN CONDUIT.

"SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN, WHICH

IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE

SEPARATELY DERIVED SYSTEM.

"SER": PROVIDE SERVICE-ENTRANCE CABLE; TYPE SE OR SER IN PLACE OF

SINGLE CONDUCTORS IN CONDUIT.

CONDUCTOR AND CONDUIT SCHEDULE NOTES

EQUIPMENT NAMEPLATE

SCHEDULE

EQUIPMENT ID SCHEME

LABEL FORMAT [NAME]

[SYSTEM]

[VOLTAGE]

[FED FROM]

[SOURCE(S)]

LABEL EXAMPLE PANEL "14-4-A-C-P1"

STANDBY POWER

120/208V

FED FROM

BUS-A / XFMR 4TA

BUSWAY

OTHER

COLOR SCHEME

SYSTEM EQUIPMENT

NORMAL POWER ALL GEAR NOT INCLUDED BELOW

TEXT BACKGROUND

NAMEPLATE COLOR

STANDBY POWER

EMERGENCY POWER

LEGALLY-REQUIRED

STANDBY POWER

UPS "A" POWER

UPS "B" POWER

LABEL BUSWAY EVERY 6' WHERE EXPOSED TO VIEW AND

EVERY 15' WHERE NOT EXPOSED TO VIEW

WHITE

WHITE

WHITE

RED

WHITE

BLACK

BLACK

ORANGE

RED

WHITE

BLUE

YELLOW

MDPS1 AND ALL DOWNSTREAM

GEAR, EXCEPT UPS GEAR AS

NOTED

GDP1, GDP2, ATS-E AND ALL

DOWNSTREAM GEAR

ATS-S AND ALL DOWNSTREAM

GEAR

UPSA AND ALL DOWNSTREAM

GEAR

UPSB AND ALL DOWNSTREAM

GEAR

CIRCUIT

AMPACITY/VOLTAGE

CIRCUIT

LENGTH

CONDUCTOR SIZE

(PHASE, NEUTRAL AND GR) CONDUIT SIZE

20A/120V 0' - 60' #12 AWG 0.75" Ø

20A/120V 60' - 95' #10 AWG 0.75" Ø

20A/120V 95' - 150' #8 AWG 1" Ø

20A/120V 150' - 240' #6 AWG 1.25" Ø

20A/277V 0' - 140' #12 AWG 0.75" Ø

20A/277V 140' - 220' #10 AWG 0.75" Ø

20A/277V 220' - 350' #8 AWG 1" Ø

20A/277V 350' - 550' #6 AWG 1.25" Ø

NOTES:

1. WIRE SIZING IS BASED ON COPPER CONDUCTORS SUPPLYING A 20A,

120V CIRCUIT AT THE INDICATED VOLTAGE, ASSUMED TO BE 80%

LOADED (16A), WITH MAXIMUM VOLTAGE DROP OF 3% AT THE LOAD.

2. DOWN-SIZED WIRE AT DEVICE/LOAD AS REQUIRED AND TERMINATE

CONDUCTORS IN A SAFE AND CODE COMPLIANT MANNER.

3. CONDUIT SIZE IS BASED ON A MAXIMUM OF 3 CIRCUITS PER CONDUIT,

EACH WITH A SEPARATE NEUTRAL CONDUCTOR.

BRANCH CIRCUIT CONDUCTOR

AND CONDUIT SIZING TABLE

6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.

FIRST DIGIT - BUILDING NUMBER (1, 2, 3, ETC)

SECOND DIGIT - BUILDING LEVEL (0, 1, 2, ETC)

THIRD DIGIT - BUILDING AREA (A, B, C, ETC)

FOURTH DIGIT - ELECTRICAL SYSTEM TYPE

N - NORMAL

C- CRITICAL (C, C1, C2, ETC)

L - LIFE SAFETY

E - EMERGENCY

FIFTH DIGIT - EQUIPMENT TYPE

S - SWITCHGEAR

D - DISTRIBUTION PANEL

TR - TRANSFORMER

P - BRANCH PANEL

ATS - AUTOMATIC TRANSFER SWITCH

SIXTH DIGIT SEQUENCE # (1,2,3,...)

SYM

GROUNDING SCHEDULE

ALL CONDUCTORS ARE INSULATED UNLESS

INDICATED OTHERWISE

#500 KCMIL CU

#350 KCMIL CU

#250 KCMIL CU

#4/0 CU

#1/0 CU

#4 CU

#6 CU

12"X2"X1/4" COPPER BUS WITH

PRE-DRILLED HOLES MOUNTED ON

INSULATORS IN MAIN ELECTRICAL ROOM

GROUNDING CONDUCTOR PER POWER

ONE-LINE DIAGRAM

12"X2"X1/4" COPPER BUS WITH

PRE-DRILLED HOLES MOUNTED ON

INSULATORS IN ELECTRICAL & TELECOMM.

CLOSETS

SIZE

BASEMENT FLOOR

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

G1

G2

G3

G4

G5

G6

G7

G8

G9

G10

TR

BA04F-14

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

TR

GB24-14

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

TR

1A16-14

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

TR

2A17-14

G4

TR

3AXX-14

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

EXISTING BUILDING MAIN

GROUNDING BUSBAR

G4

THIRD FLOOR

SECOND FLOOR

FIRST FLOOR

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

G1G1

G1

TO EQUIPMENT

RACKS (TYP)

TO LADDER

RACK (TYP)

BOND TO ELEC

PANEL GR BUSES

G8

G4

TR

BC07-14

TR

GC31-14

TR

1C25-14

TR

2C32-14

TR

3C16-14

ROOF

MAIN ELECTRICAL ROOM

BC08B-14

GROUND FLOOR

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:4

A M

14-EP602

GROUNDING RISER DIAGRAM EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

SCALE: NTSF1

GROUNDING RISER DIAGRAM

SIDE VIEW

FRONT VIEW

TOP VIEW

TRANSFORMER, SEE ELECTRICAL

CONNECT TO UNISTRUT WITH 1/2" θ A325

THRU BOLT AND STANDARD WASHERS (4)

TOTAL OR PER MANUF. WHICHEVER IS

MORE STRINGENT.

P1000T UNISTRUT,

TYPICAL ALL BEAM

UNLESS NOTED

OTHERWISE

P1001T UNISTRUT

COLUMN, TYPICAL ALL

COLUMNS UNLESS

NOTED OTHERWISE

UNISTRUT P2037SQ POST

BASE WITH (2) 1/2"⌀

HILT KWIK BOLT TZ- 2-5/8"

EMBEDMENT MIN.

UNISTRUT P1000T KICKER

BRACE, TYPICAL UNLESS

NOTED OTHERWISE. PROVIDE

UNISTRUT (2) P2260 ANGLED

CONNECTORS TOP AND

BOTTOM OF BRACE WITH (4)

1/2"θ

THRU BOLTS WITH STANDARD

WASHERS AND SPRING NUTS

(P1010 OR SIM.)

UNISTRUT P1026

CONNECTOR WITH 1/2"θ

THRU BOLTS, STANDARD

WASHERS AND SPRING

NUTS (P1010 OR SIM.)

STACKED

TRANSFORMER

FLOOR MOUNTED TRANSFORMER

WITH (4) 1/2"⌀

HILTI KWIK BOLT TZ ANCHORS

WITH 2-5/8" MIN EMBEDMENT.

INSTALL ANCHOR BOLTS IN

HOLES PROVIDED BY MANUF.

(E)

CONCRETE

FLOOR

DOTTED LINE IS

THE OUTLINE OF

THE TOP OF THE

TRANSFORMER

DETAIL A

UNISTRUT BEAM

1/2"⌀ THRU BOLT WITH

STANDARD WASHER AND

UNISTRUT P1010 SPRING NUT OR

SIMILAR

A

A

48" max; 36" min

48" max; 36" min

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:4

A M

14-EP603

DETAILS & LIGHTING FIXTURE

SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

ID DESCRIPTION

NOMINAL SIZE

M O

U N

T

IN

G

T Y

P E

C O

L O

R T

E M

P

C R

I

D R

IV

E

R C

O N

F

IG

U R

A T

IO

N

V O

L T

A G

E

W A

T T

S

F

IN

IS

H

F

IX

T U

R E

L U

M E

N S

D

IF

F U

S E

R /L

E N

S

R E

F L

E C

T O

R

O P

T

IO

N S

N O

T E

S

MANUFACTURER (CATALOG SERIES)

L E

N G

T H

D E

P T

H

H E

IG

H

T

D

IA

M E

T E

R A

P E

R T

U R

E

OPTION 1 OPTION 2 OPTION 3

(G-1) 2X2 LED FLAT PANEL, GRID LAY-IN 24" 24" 3" - CR LED 3500K LED DRIVER

(0-10V DIMMING)

120/277 41 - 3400 - - - METALUX (22FP4735C) APPROVED EQUAL APPROVED EQUAL

(G-4) 2X4 LED FLAT PANEL, GRID LAY-IN 48" 24" 3" - CR LED 3500K LED DRIVER

(0-10V DIMMING)

120/277 41 - 4300 - - - METALUX (24FP4735C) APPROVED EQUAL APPROVED EQUAL

(PG4) STRIPLIGHT, GENERAL 48" 4" 4" - CP LED 4000K LED DRIVER

(0-10V DIMMING)

120/277 38 CBA 5000 - - - LITHONIA

(ZL1D-L48-5000LM-FST-M

VOLT-40K-80CRI-WH-HC3

6)

ILP (SS4) WILLIAMS (75R)

DIFFUSER/LENSFINISH PROVIDE UNIT PRICES AND FIXTURE BRAND SELECTED FOR ADD/DELETE CHANGES

FOR EACH FIXTURE TYPES SHOWN WITHIN 48 BUSINESS HOURS OF THE BID DATE.

FAILURE TO COMPLY WITH THIS REQUIREMENT MAY DISQUALIFY THE PRODUCTS

AND EMPOWER THE ENGINEER TO DETERMINE FAIR VALUE FOR FIXTURE AND

INSTALLATION CHANGES, WITHOUT FURTHER INPUT FROM THE CONTRACTOR OR

INSTALLER.

CONTRACTOR ALLOWANCE PRICES ARE ACCURATE WHEN THIS JOB WAS

SPECIFIED, CONTRACTOR AND ELECTRICAL DISTRIBUTOR SHALL VERIFY THIS

ALLOWANCE AND REPORT ANY PROBLEMS TO THE ENGINEER BEFORE THE BID.

ALLOWANCE PRICE MAY OR MAY NOT INCLUDE LAMP(S) OR FREIGHT AS NOTED,

AND DO NOT INCLUDE ANY TAXES.

SUBSTITUTIONS AND/OR EQUAL FIXTURES MUST RECEIVE APPROVAL PRIOR TO

BIDDING, THEY MUST BE SUBMITTED TO THE ENGINEER NO LESS THAN 2 WEEKS

PRIOR TO BID OPENING.

SAMPLES MUST BE PROVIDED FOR ANY AND ALL FIXTURES UPON A/E REQUEST

PRIOR TO RELEASING FIXTURES.

ALL FIXTURES SHALL BE LISTED AND APPROVED FOR THEIR INTENDED USE AND

LOCATION.

VERIFY THE PROPER MOUNTING KITS OR ACCESSORIES TO FACILITATE

INSTALLATION AS SHOWN AT EACH LOCATION ON THE DRAWINGS.

COMPLY WITH THE "INTERIOR LIGHTING" SECTION OF THE SPECIFICATIONS.

REFER TO SPECIFICATIONS FOR IMPORTANT TECHNICAL REQUIREMENTS FOR

LIGHTING FIXTURES, DRIVERS, AND LAMPS.

ALL LIGHT FIXTURES TO BE EITHER "DLC" OR "LIGHTING FACTS" LISTED OR TO BE

APPROVED BY ARCHITECT/ENGINEER AND OWNER.

LUMINAIRE OPTIONSMOUNTING REFLECTOR 1.

2.

3.

4.

5.

6.

7.

8.

9.

DIAMETER

H E

IG

H

T

LENGTH DEPTH

H E

IG

H

T

LENGTH

DEPTH

HEIGHT

NOTES

INTERIOR LIGHTING FIXTURE SCHEDULE

ABBREVIATIONS GENERAL NOTES

ARHR - AIR RETURN AND HEAT REJECTION

DL - DAMP LOCATION

EQC - EARTHQUAKE CLIPS

F - FUSING

HLD - HINGED AND LATCHED DOOR

HS - HOUSE SIDE SHIELD

PS - PHOTOCELL SWITCH

QRS - QUARTZ RESTRIKE

ST - STATIC

WG - WIRE GUARD

WL - WET LOCATION

B - BASE

C - CEILING

F - FLANGE

G - GRID

P - PENDANT

PL POLE

R - RECESSED

S - SURFACE

W - WALL

MW - MATTE WHITE

BL - BLACK

SL - SILVER

GL - GOLD

CL - CLEAR

PW - PAINTED WHITE

EA - EXTRUDED ALUMINUM

S - STEEL

GS - GALVANIZED STEEL

C - CAST

CBA - COLOR BY ARCHITECT

SCBA - STANDARD COLOR BY

ARCHITECT

CCA - CUSTOM COLOR BY

ARCHITECT

FS

209D

- MEETS FEDERAL

STANDARD 209D

TP - THERMALLY

PROTECTED

FL - FLUSH

R - REGRESS

M - MITERED

OP - NONE/OPEN

SP - SPECULAR

SS - SEMI-SPECULAR

D - DIFFUSE (WHITE ENAMEL)

SC - SPECULAR (COLORED)

PR - PRISMATIC

FDR - FULL DEPTH REFLECTOR

DS - DIFFUSE (SEMI SPECULAR) SILVER

LI - LOW IRIDESCENT

IR - IRIDESCENT

SL - SILVER

GL - GOLD

CA - CLEAR ALZAK

#A - ACRYLIC #THICK

#OA - ACRYLIC #THICK (OPAL)

GC - GLASS (CLEAR)

GO - GLASS (OPAL)

GF - GLASS (FROSTED)

SGL - SOFT GLOW LENS

HPL - HIGH PERFORMANCE LENS

DO - DROP OPAL

CGL - CONVEX GLASS LENS

S - SATIN LENS

F8

STACKED TRANSFORMER DETAIL

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:5

A M

14-EP604

PANEL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 14

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 87.5 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: 7.2 kVA @ 100% = 7.2 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 263

LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 95

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 258 266 254 AVERAGE CONNECTED AMPS PER PHASE = 259

TOTALS: CONNECTED kVA PER PHASE 31 32 30 CONNECTED TOTAL kVA = 93

41 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 42

39 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 40

37 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 38

35 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 36

33 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 34

31 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 32

29 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 100 3 0.0 17.2 1.6 14-B-A-E-P4 6.1 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 -- -- -- -- -- -- -- 5.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 100 3 0.0 17.2 1.4 14-1-A-E-P1 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 -- -- -- -- -- -- -- 6.6 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 100 3 0.0 17.2 1.4 14-3-A-E-P1 5.7 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 -- -- -- -- -- -- -- 5.7 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 100 3 0.0 17.2 1.3 14-2-A-E-P1 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 5.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 100 3 0.0 17.2 1.4 14-G-A-E-P1 6.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 300 AMPERE MAIN CB SURFACE ELECTRICAL BA05-14

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-B-A-E-P3"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 18.6 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: 1.6 kVA @ 100% = 1.6 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 56

LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 20

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 51 53 53 AVERAGE CONNECTED AMPS PER PHASE = 52

TOTALS: CONNECTED kVA PER PHASE 6 6 6 CONNECTED TOTAL kVA = 19

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 -- -- -- -- -- -- -- 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 15 2 0.0 1.7 0.0 PWR: AC-2... 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 20 1 0.0 0.0 0.2 CO EXTERIOR TO SS-2 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 30 3 0.0 5.6 0.0 PWR: SS-2 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB 14-B-A-E-P3 SURFACE TELECOMMUNICATIONS...

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-B-A-E-P4"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 50.0 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 141

LIGHTING & CONTINUOUS LOADS: 0.8 kVA @ 125% = 1.0 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 51

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 145 139 139 AVERAGE CONNECTED AMPS PER PHASE = 141

TOTALS: CONNECTED kVA PER PHASE 17 17 17 CONNECTED TOTAL kVA = 51

41 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 42

39 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 40

37 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 38

35 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 36

33 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 34

31 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 32

29 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 100 3 0.2 10.0 0.0 14-3-A-C1-P3 3.5 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 100 3 0.2 10.0 0.0 14-2-A-C1-P1 3.5 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 100 3 0.2 10.0 0.0 14-1-A-C1-P1 3.5 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 100 3 0.2 10.0 0.0 14-G-A-C1-P2 3.5 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 100 3 0.2 10.0 0.0 14-B-A-C1-P2 3.5 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 300 AMPERE MAIN CB SURFACE ELECTRICAL BA05-14

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-B-C-C1-P1"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 10.0 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 28

LIGHTING & CONTINUOUS LOADS: 0.2 kVA @ 125% = 0.2 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 10

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 29 28 28 AVERAGE CONNECTED AMPS PER PHASE = 28

TOTALS: CONNECTED kVA PER PHASE 3 3 3 CONNECTED TOTAL kVA = 10

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 20 1 0.2 0.0 0.0 LIGHTING... 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB 14-B-C-C1-P1 SURFACE TELECOMMUNICATIONS...

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-B-A-C1-P2"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 10.0 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 28

LIGHTING & CONTINUOUS LOADS: 0.2 kVA @ 125% = 0.2 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 10

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 29 28 28 AVERAGE CONNECTED AMPS PER PHASE = 28

TOTALS: CONNECTED kVA PER PHASE 3 3 3 CONNECTED TOTAL kVA = 10

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 20 1 0.2 0.0 0.0 LIGHTING... 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB 14-B-C-C1-P1 SURFACE TELECOMMUNICATIONS...

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-G-A-C1-P2"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 18.6 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: 1.4 kVA @ 100% = 1.4 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 56

LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 20

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 54 54 49 AVERAGE CONNECTED AMPS PER PHASE = 52

TOTALS: CONNECTED kVA PER PHASE 6 6 6 CONNECTED TOTAL kVA = 19

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 -- -- -- -- -- -- -- 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 15 2 0.0 1.7 0.0 PWR: AC-2... 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 30 3 0.0 5.6 0.0 PWR: SS-2 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB 14-B-A-E-P3 SURFACE TELECOMMUNICATIONS...

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "14-G-A-E-P1"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER…