This document provides details for a federal contract opportunity for EHRM Infrastructure Upgrades Construction at the Salt Lake City VAMC. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0041 to provide construction services to upgrade infrastructure at the Salt Lake City VA Medical Center. The opportunity type is a solicitation. An attachment to the solicitation includes drawings related to the project. Proposals are due by the date listed in the solicitation document. The awarded contractor will be expected to complete infrastructure upgrade construction work at the Salt Lake City VAMC facility.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
"12" 6"
ISOMETRIC VIEW
SIDE VIEW
UNISTRUT SUPPORT
THREADED ROD,
TYPICAL
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
NOTE:
MAXIMUM WIDTH OF
PERPENDICULAR CROSSING
IS 6 FEET WIDE
SECURE BASKET TRAY TO
UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS
DUCT WORK
FINISHED CEILING
CABLE TRAY
ISOMETRIC VIEW
CABLE TRAY
NOTE:
INSTALL UNISTRUT SUPPORT
1'-0" FROM EITHER SIDE OF
CABLE TRAY SPLICE POINT
UNISTRUT SUPPORT,
TYPICAL
CABLE TRAY
SPLICE POINT
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
SECURE BASKET TRAY
TO UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS, TYPICAL
USE MANUFACTURER'S JOINT
SPLICE SPECIFICATIONS TO
ENSURE PROPER BONDING
THREADED ROD,
TYPICAL
ISOMETRIC VIEW
CABLE TRAY
THREADED ROD,
TYPICAL
UNISTRUT SUPPORT
SEISMIC SUPPORT,
TYPICAL
SEISMIC
SUPPORT,
TYPICAL
NOTE:
SEISMIC ENGINEERING TO
BE DONE BY OTHERS
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
SECURE BASKET TRAY TO
UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS, TYPICAL
THREADED ROD,
TYPICAL
CABLE BASKET
TRAY
NOTE:
INSTALL UNISTRUT
SUPPORT 1'-0" FROM
EITHER END OF CABLE
BASKET TRAY ON EACH
10'-0" SECTION.
ISOMETRIC VIEW
UNISTRUT, TYPICAL
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
SECURE CABLE BASKET
TRAY TO UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS, TYPICAL
ISOMETRIC VIEW
NOTE:
INSTALL UNISTRUT
SUPPORT 1'-0" FROM
CABLE TRAY SPLICE
POINT, TYPICAL.
UNISTRUT SUPPORT,
TYPICAL.
THREADED ROD,
TYPICAL.
CABLE TRAY
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL.
SECURE BASKET TRAY
TO UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS,
TYPICAL.
12" 6"
ISOMETRIC VIEW
SIDE VIEW
CABLE TRAY
UNISTRUT SUPPORT
THREADED ROD,
TYPICAL
DUCT WORK
FINISHED
CEILING
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
SECURE BASKET TRAY TO
UNISTRUT PER MANUFACTURER'S
SPECIFICATIONS
UNISTRUT SUPPORT,
TYPICAL
THREADED ROD,
TYPICAL
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
SECURE BASKET TRAY
TO UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS,
TYPICAL
ISOMETRIC VIEW
NOTE:
INSTALL UNISTRUT
SUPPORT 1'-0" FROM
CABLE BASKET TRAY
SPLICE POINT, TYPICAL.
CABLE BASKET
TRAY
12"
6"
5' T
YPIC
AL
ISOMETRIC VIEW
SIDE VIEW
J-HOOKS, TYPICAL
CABLE TRAY
THREADED ROD,
TYPICAL
FINISHED CEILING
SECURE CABLE TRAY TO
UNISTRUT PER
MANUFACTURER'S
SPECIFICATIONS
WASHER AND NUT
ABOVE AND BELOW
UNISTRUT, TYPICAL
UNISTRUT SUPPORT,
TYPICAL
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /G e n
E L
E C
.r v t
/8
/2
:1
:4
P
M
ET503
TELECOM DETAILS EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
SCALE: NTSF2
TYPICAL CABLE TRAY W/ PERPENDICULAR CROSSING DETAIL
SCALE: NTSF5
TYPICAL CABLE TRAY W/ SUPPORT AT SPLICE POINT DETAIL
SCALE: NTSB8
TYPICAL CABLE TRAY W/ SEISMIC SUPPORTS DETAIL
SCALE: NTSF8
TYPICAL 10'-0" CABLE TRAY SECTION W/ SUPPORT DETAIL
SCALE: NTSD8
TYPICAL CABLE TRAY INTERSECTION W/ SUPPORTS DETAIL
SCALE: NTSB5
TYPICAL CABLE TRAY W/ PARALLEL OBSTRUCTION DETAIL
SCALE: NTSD5
TYPICAL CABLE TRAY 90 DEGREE BEND W/ SUPPORTS DETAIL
SCALE: NTSD2
TYPICAL CABLE TRAY W/ J-HOOK ABOVE DETAIL
Revisions: Date:
06/08/23
IP NETWORK
GENERAL DIVISION OF WORK
CARD READERS - BY SECURITY CONTRACTOR
CONTACT INDICATORS - BY SECURITY CONTRACTOR
ACCESS CONTROL SYSTEM - EXISITNG
TYCO SOFTWARE HOUSE
RACEWAYS - SECURITY CONTRACTOR
CABLING - BY SECURITY CONTRACTOR
ELECTRIFIED DOOR HARDWARE -BY SECURITY
CONTRACTOR
DOOR POWER SUPPLIES @ CONTROL PANEL -
BY SECURITY CONTRACTOR
2-DOOR
LOCAL
DOOR
POWER
SUPPLY
(WHERE
SHOWN
ON PLANS)
120V EMERGENCY
POWER
CABLETRAY W/CABLING
WHERE AVAILABLE OR
CONDUIT HOMERUN
1" CND W/
CABLING
ACCESS CONTROL PANEL
POWER SUPPLY
BATTERIES
TYPICAL ACCESS CONTROL PANEL (QTY AS REQUIRED)
ELECTRIFIED DOOR POWER
SUPPLY, SIZED FOR ELECTRIFIED
DOOR HARDWARE + 20% SPARE
BATTERIES
TYPICAL DOOR POWER SUPPLY PANEL "PS"
120V EMERGENCY
POWER
120V EMERGENCY
POWER
TYPICAL ACCESS CONTROL
PROVIDE QUANTITY AS REQUIRED
TYP, MONITORED INPUT FOR FIRE ALARM B
EPT
CR A
C
B
CI
TYPICAL CARD READER W/ KEYPAD
TYPICAL CONTACT INDICATOR
TYPICAL ELECTRIC POWER TRANSFER
J-BOX
(ABOVE
CEILING
AT
DOOR)
1" CND W/
CABLING
ACCESS CONTROL SYSTEM CONDUIT
AND CABLING SCHEULE
A
B
C
1" CND W/ (1) #22/6 TWSP
0.75" CND W/ (1) #12/2 TWP
0.75" CND W/ (2) #22/2 TWP
G E
N E
R A
L C
O N
T R
O L L E
R
M O
D U
L E
D
O O
R A
C M
B O
A R
D W
IT
H
I N
P U
T S
O U
T P
U T
S
D
O O
R A
C M
B O
A R
D W
IT
H
I N
P U
T S
O U
T P
U T
S
D 0.75" CND W/ (2) #22/4 TWP
ES BTYPICAL ELECTRIC STRIKE
DMSTYPICAL MOTION SENOR
REX (MOTION SENORS) - BY SECURITY CONTRACTOR
SOFTWARE HOUSE I-STAR SERIES CONTROLER
FINISHED FLOOR
FINISHED CEILING
120V POWER
CND & CABLING
TO ACCESS CONTROL PANEL
LOCAL DOOR POWER SUPPLY
(WHERE SHOWN ON PLANS)
CND & CABLING
(STUB CND INTO FRAME)
8"x8"x6" J-BOX
ELECTRIC STRIKE
HID RK40 CARD
READER 4-SQUARE
BOX W/ SINGLE RING
(WHERE SHOWN ON
PLANS)
(TYP) DOOR
CONTACT IN FRAME,
WHERE SHOWN ON
PLANS
ACCESS CONTROLLER
ENCLOSURE, SURFACE MOUNTED
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /G e n
E L
E C
.r v t
/8
/2
:1
:4
P
M
ET504
TELECOM SECURITY DETAILS AND
RISER DIAGRAMS
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
SCALE: NTSF6
ACCESS CONTROL RISER DIAGRAM
SCALE: 1/8" = 1'-0"F2
TYPE # 1 SINGLE DOOR ELECTRIC STRIKE
FB/PT
BEAM CLAMP,
TYPICAL
GENERAL NOTES:
1. ALL LOW VOLTAGE COMMUNICATIONS CONDUIT
SHALL BE GROUNDED TO BASKET TRAY OR
TELECOMMUNICATIONS GROUNDING BUS BAR.
2. "TMGB" SHOULD BE 1/4"x4"x24".
3. "TGB" SHOULD BE 1/4"x2"x24".
4. EMT CONDUIT GROUNDING CLAMP SHOULD BE
ELECTROLYTIC CAST BRONZE (PANDUIT PART
NUMBER GPL-"X"-"X", OR EQUAL).
5. RIGID CONDUIT GROUND CLAMP SHOULD BE
PART NUMBER O-Z/GEDNEY BLG-XXXX, OR
HBLG-XXXX, OR EQUAL.
6. GROUNDING LUGS SHOULD BE TWO-HOLE LONG
BARREL LUGS (PANDUIT PART NUMBER
LCC6, OR EQUAL).
CABLE BASKET TRAY.
FOLLOW MANUFACTURER'S
GROUNDING INSTRUCTIONS.
COMMUNICATION
OUTLET, TYPICAL
FLOOR BOX/POKE THRU
BOX, TYPICAL
CONDUIT, TYPICAL
ENTRANCE CONDUITS
OR METALLIC SLEEVES
GROUNDING ELECTRODE
TO BUILDING ELECTRODE
SYSTEM (OVERHEAD OR
UNDERGROUND)
1 EA., #6 CABLE,
GREEN
1 EA., #6 CABLE,
GREEN
1 EA., #6 CABLE,
GREEN
TMGB/TGB,
TYPICAL
TO ELECTRICAL
PANEL, TYPICAL
RBB1 (1RU) RBB1 (1RU)
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /G e n
E L
E C
.r v t
/8
/2
:1
:5
P
M
ET505
TELECOM EQUIPMENT RACK
GROUNDING DETAIL
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
SCALE: 1/8" = 1'-0"F2
TYPICAL TELECOM EQUIPMENT RACK GROUNDING DETAIL
HAZARDOUS ABATEMENT GENERAL NOTES
1. CONTRACTOR SHALL ABATE ALL ASBESTOS AND LEAD SHIELDING CONTAINING
MATERIAL, LEAD BASE PAINT, AND PCB ITEMS PRIOR TO ALL OTHER DEMOLITION. REFER
TO ABATEMENT SPECIFICATIONS FOR LOCATIONS OF HAZARDOUS CONTAINING
MATERIALS.
2. SEE THE ABATEMENT SCHEDULE LEFT FOR SPACES WITHIN THE PROJECT SCOPE THAT
CONSIST OF SIGNIFICANT ARCHITECTURAL RENOVATIONS.
3. THE INFORMATION IN THE ABATEMENT SCHEDULE WAS PROVIDED BY THE VA AND
INDICATES KNOWN ASBESTOS CONTAINING MATERIALS (ACMs).
4. THE CONTRACTOR IS RESPONSIBLE FOR CONDUCTING THEIR OWN HAZARDOUS
MATERIAL SURVEY AND FOR VERIFYING ANY MATERIALS IN QUESTION PRIOR TO
CONDUCTING WORK IN ANY PROJECT SPACE. THE SCHEDULE PROVIDED LEFT IS TO
ASSIT THE CONTRACTOR IN QUANTIFYING THE ABATEMENT, BUT SHOULD NOT BE
CONSIDERED A COMPLETE OR EXHAUSTIVE LIST OF ALL HAZARDOUS MATERIALS.
5. THE TWO DIGIT NUMBER SUCCEEDING THE HYPHEN IN THE ROOM NUMBER COLUMN OF
THE ABATEMENT SCHEDULE INDICATES THE BUILDING IN WHICH THE ROOM RESIDES.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S L
C V
A M
C E
H R
M I n fr a s tr u c tu re U p g ra d e s /G e n
A rc h .r v t
/1
/2
:4
:3
P M
HR101
HAZARDOUS MATERIAL
ABATEMENT
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 PURCELL ROOKER
ROOM DESIGNATION
DOOR DESIGNATION
WINDOW DESIGNATION
XX-AE110
4ELEVATION, (VIEW)
ELEVATION, (DATUM)
NORTH ARROW
A101
1 SIM
DETAIL
1 1/8" = 1'-0"
View NameDRAWING TITLE
STANDARD SYMBOLS
1REVISION DESIGNATION
GRID HEAD
MATCH
PROPERTY
GRID
HIDDEN
REMOVAL
OVERHEAD
LINE TYPES
NORTH
ARCHITECTURAL MATERIALS
GYPSUM BOARD CEILING / WALL
LAY-IN ACOUSTICAL CEILING
STEEL STUD
CONCRETE
CARPET / TILE (SECTION)
PLYWOOD (SECTION)
MASONRY WALL
DEMOLITION WALL
2 HR. FIRE BARRIER
1 HR. FIRE BARRIER
FIRE ALARM ZONE
SMOKE BARRIER
ROOM NAME
SQUARE FEET
GENERAL NOTES
1. ALL WORK SHALL CONFORM TO THE VA DESIGN MANUALS AND THE INTERNATIONAL BUILDING CODE (2018 EDITION), NFPA 101 (2021 EDITION) AND ALL LOCAL CODES, INCLUDING ANY AND ALL
COVENANTS, RULES AND REGULATIONS ADOPTED BY THE US DEPARTMENT OF VETERANS
AFFAIRS. INCLUDING BUT NOT LIMITED TO THE VA FIRE PROTECTION DESIGN MANUAL 2021.
2. COORDINATION OF WORK: THE GENERAL CONTRACTOR SHALL COMPARE ARCHITECTURAL
SPECIFICATIONS AND DRAWINGS WITH MECHANICAL AND ELECTRICAL SPECIFICATIONS AND
DRAWINGS. IF THERE ARE ANY DISCREPANCIES BETWEEN THEM, HE SHALL REPORT THE SAME
TO THE ARCHITECT IN WRITING AND OBTAIN FROM THE ARCHITECT WRITTEN INSTRUCTIONS
FOR NECESSARY CHANGES.
3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS ON THE DRAWINGS AND DIMENSIONS AND
CONDITIONS AT THE SITE.
4. ALL MATERIALS SHALL BE NEW (U.N.O.) AND BOTH MATERIALS AND WORKMANSHIP SHALL BE OF
BEST QUALITY.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY, SECURITY AND PROTECTION IN AND
AROUND THE JOB SITE AND ADJACENT PROPERTIES (IF APPLICABLE).
6. ALL DETAILS AND NOTES ON DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO
SIMILAR SITUATIONS ELSEWHERE UNLESS NOTED OR SHOWN OTHERWISE. CONSTRUCTION
NOT SPECIFICALLY SHOWN SHALL BE ACCOMPLISHED AS PER MINIMUM REQUIREMENTS OF THE
VA DESIGN MANUALS AND THE INTERNATIONAL BUILDING CODE (2018 EDITION) AND NFPA 101
(2021 EDITION).
7. THE CONTRACTOR SHALL REVIEW, APPROVE AND VERIFY ALL SHOP DRAWINGS, PRODUCT
DATA, SAMPLES AND SIMILAR SUBMITTALS TO ASSURE THEY COMPLY WITH THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS. SHOP DRAWINGS, PRODUCT DATA, SAMPLES,
AND SIMILAR SUBMITTALS SUBMITTED TO THE ARCHITECT WHICH HAVE NOT BEEN REVIEWED,
APPROVED, VERIFIED, STAMPED AND SIGNED BY THE GENERAL CONTRACTOR WILL BE
RETURNED TO THE GENERAL CONTRACTOR WITHOUT ACTION BY THE ARCHITECT. THE
ARCHITECT WILL REVIEW THE SHOP DRAWINGS FOR GENERAL CONFORMANCE WITH THE
DESIGN CONCEPT. THIS REVIEW BY THE ARCHITECT SHALL NOT BE CONSTRUED AS APPROVAL.
THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS AND OMISSIONS
IN SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY THE ARCHITECT'S
REVIEW.
8. THE CONTRACTOR IS TO ENSURE THAT ANY SPRAY ON FIRE PROOFING, CONCRETE
ENCAPSULATED STRUCTURAL ELEMENTS, FLOOR ASSEMBLIES, OR FIRE RATED WALLS THAT
ARE DAMAGED, MODIFIED, OR PENETRATED DURING CONSTRUCTION ACTIVITIES ARE REPAIRED
IN SUCH A WAY THAT THE EXISTING FIRE RATING IS MAINTAINED AND CONTINUOUS.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S L
C V
A M
C E
H R
M I n fr a s tr u c tu re U p g ra d e s /G e n
A rc h .r v t
/1
/2
:4
:1
P M
AE001
GENERAL NOTES, SYMBOLS,
ABBREVIATIONS
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 PURCELL ROOKER
06/08/23
ABBREVIATIONS/ACRONYMS
A.B. anchor bolt
A/C air conditioning
ABV above
ADA americans with disabilities act
ADD'L additional
AFF above finished floor
ALT alternate
ALUM aluminum
ANOD anodized
ANSI american national standards institute
APPR approved
APPROX approximate
ARCH architect(ural)
ASPH asphalt
AUTO automatic
BD board
BLDG building
BLK block
BO bottom of ________
BRG bearing
BSMT basement
BTWN between
CF cubic foot
CG center of gravity
CI cast iron
CJ construction joint
CL center line or column line
CLG ceiling
CLR clear(ance), category of logistical responsibility
CMU concrete masonry unit
COL column
CONC concrete
CONST construction
CONT continuous, continue
CPT carpet
CRS course(s)
CSMT casement
CY cubic yard
DE door elevation
DET detail
DF drinking fountain
DF-L douglas fir
DIA diameter
DIM dimension
DIV division
DL dead load
DOD department of defense
DPR dispenser
DR door
DWB deformed weldable bar
DWG drawing
E east
EA each
EJ expansion joint
ELEC electrical
ELEV, EL elevation
EMT electrical metallic tubing
EN edge nail
EQ equal
EQUIP equipment
EST estimate
EX existing
EXP expansion
EXT extinguisher f'c concrete 28 day strength f'm masonry strength
FD floor drain
FDN foundation
FE fire extinguisher
FEC fire extinguisher cabinet
FGL fiberglass
FHS fire hose station
FIN finish(ed)
FIN. FLR finished floor elevation
FP fireplace
FRT fire-retardant treated
FS footing step
FT feet
FTG footing
GA gage, guage
GALV galvanized
GB grab bar
GD grade(ing)
GF government furnished
GI government installed
GL glass
GLB glue laminated timber beam
GYP. BD. gypsum wall board
HAS headed anchor stud
HB hose bib
HC hollow core
HCAP handicap
HD holdown
HDR header
HDWR hardware
HM hollow metal
HOR horizontal
HR hour
HRDWD hardwood
HT height
HTG heating
HVAC heating/ventilating/air cond.
HWH hot water heater
ID inside diameter
INCL include(d), (ing)
INSUL insulate(d), (ion)
INT interior
JSN joint schedule number
JT joint
LAM laminate(d)
LAV lavatory
LF linear feet
LH left hand
LL live load
LP low pressure
LTL lintel
LVL laminated veneer lumber
LW lightweight
MAS masonry
MAT'L material(s)
MAX maximum
MB machine bolt
MBR member
MC medicine cabinet
MECH mechanic(al)
MED medium
MFR manufacture(r)
MIN minimum
MISC miscellaneous
MLB microllam beam
MMB membrane
MO masonry opening
MTL metal
MULL mullion
N north
NIC not in contract
No. number
NOM nominal
NTS not to scale
O.C. on center
OD outside diameter
OH overhead
OPG opening
OPP opposite
OPT optimum
PBD particle board
PCB polychlorinated biphenyls
PL plate
PNL panel
PSI pounds per square inch
PSIG pounds per square inch gauge
PT pressure treated or post tension
PTD painted
PTN partition
QTY quantity
R riser(s), radius
RAD radius
REA Rand Eardley & Associates
REINF'D reinforced
REQ'D required
REV revised
RM room
RO rough opening
S south
S.S. stainless steel
SCHED schedule(ed)
SECT section
SF square feet
SHT sheet
SIM similar
SPEC specifications
SQ square
STD standard
STG storage
STRUC structure(al)
SW shear wall
T tread(s)
T.O. top of ________
TC top of curb
TYP typical
UL underwriters laboratories
UNO unless noted otherwise
VB vapor barrier
VCT vinyl composition tile
VERT vertical
W west
W/ with
W/O without
WC water closet
WD wood
WF wide flange
WP water proof(ing)
WR water repellant
WS wall step
WSCT wainscot
WWF welded wire fabric
VANACC
ESS
I BLE
VANACC
ESS
I BLE
S S M H
S D M H
S D M H
C O
S D M H
21.8
HP
HP
A
B
C
D
E
DD
SEQUENCING PHASING NOTES
PHASE 1 – SITE FIBER BACKBONE
THIS PHASE OF THE CONSTRUCTION WOULD INCLUDE COORDINATION OF NEW PATHWAYS FROM THE
CAMPUS MRC LOCATED IN THE BASEMENT OF BUILDING 1 INTO THE NEW OR REMODELED
DEMARCATION FACILITY. IN ADDITION TO BRINGING IN NEW FIBER-BASED UTILITY THIS WILL CREATE A
SECONDARY SERVICES PATH, PROVIDING THE NEEDED REDUNDANCY DURING CONSTRUCTION.
DURING THIS PHASE, NO EXISTING CARRIER SERVICES WOULD BE DISRUPTED AND THERE WOULD BE
NO POTENTIAL ADVERSE IMPACT ON THE ONGOING MEDICAL OPERATIONS.
PHASE 2 – PATHWAYS & BACKBONE FIBER
IN A PARALLEL AND CONCURRENT TIME FRAME WITH PHASE ONE, CONSTRUCTION PHASE TWO WILL BE WORKING ON THE INTERNAL SIDE, BUILDING A SECONDARY FIBER FEED FROM THE CORE TO THE EDGE. ONCE THIS NEW FIBER RING IS FULLY INSTALLED AND TESTED, IT WILL BE CONNECTED TO THE NEW CORE SERVICE, PROVIDING FULLY OPERATIONAL AND REDUNDANT SERVICES. DURING THIS
PHASE, EXISTING PATHWAYS OR BACKBONE FIBER WILL REMAIN IN OPERATION TO ENSURE NO
IMPACT TO SERVICE OR OPERATION OF THE HOSPITAL.
PHASE 3 – TELECOMMUNICATION DATA ROOM BUILDOUT
THE THIRD PHASE OF CONSTRUCTION INCLUDES THE BUILDOUT OF THE EXISTING AND NEW
TELECOMMUNICATION ROOMS (TRS) AND THE INSTALL OF NEW EQUIPMENT IN THE TRS. IT WILL INCLUDE REDUNDANT POWER AND HVAC IN EACH OF THE TRS. THE TR BUILDOUT WILL INCLUDE
PULLING A-SIDE AND B-SIDE REDUNDANT FIBER PATHS TO ENSURE NETWORK CONTINUITY.
THIS PHASE WILL ALSO INCLUDE THE BUILD OUT OF ANY AND ALL IMPACT SPACES AFFECTED BY THE
NEW TR LOCATIONS AND SIZES.
PHASE 4 - HORIZONTAL CABLING, OWNER EQUIPMENT
THE FOURTH PHASE INCLUDES THE INSTALLATION OF HORIZONTAL CABLING FOLLOWED BY THE
INSTALLATION OF ACTIVE OWNER EQUIPMENT. FOR THE COMPLETION OF THE HORIZONTAL CABLING, THIS WILL BE PHASED BY PROVIDING A SERVICE LOOP NEAR THE AREA TO BE REFIT; THE CUTOVER OF
THE CABLING WILL OCCUR AT A TIME APPROVED AND COORDINATED BY THE OWNER. THOUGH A
DISTINCT PHASE OF THE PROJECT, THE INSTALLATION OF HORIZONTAL CABLING AND THE
ACQUISITION OF ACTIVE OWNER EQUIPMENT MAY OVERLAP WITH THE EARLIER PHASES, TO ENSURE A TIMELY SEQUENCE OF CONSTRUCTION AND SEAMLESS SWITCH OF SERVICES ACROSS THE ENTIRE CAMPUS. MANY OF THESE PHASES WILL RUN CONCURRENTLY AND IN TIGHT COORDINATION WITH THE
DESIGNERS, CONTRACTORS AND OWNER REPRESENTATIVES.
PHASE 5 - OWNER COORDINATION FOR EDGE TURNOVER
WE RECOMMEND SWITCHING OF SERVICE STARTING WITH THE LEAST IMPACTFUL AREAS OF THE
CAMPUS TO THE MOST CRITICAL AREAS. IN ADDITION TO THE ONGOING TESTING AND COMMISSIONING
OF THE ENTIRE SYSTEM THROUGHOUT THE PHASED PROCESS, THIS APPROACH OF SWITCHING
SERVICES GREATLY MINIMIZES THE POTENTIAL IMPACT OF THE ENTIRE UPGRADE AND ENSURES ALL
ASPECTS OF THE SYSTEM FUNCTION AS DESIGNED. WE RECOGNIZE THAT ULTIMATELY THE
SEQUENCE AND TIMING DECISIONS RELATED TO SWITCHING SERVICES WILL BE MADE BY THE
OWNER’S KEY STAKEHOLDERS (ENGINEERING, MEDICAL, EXECUTIVE).
GENERAL
DURING EACH OF THE ABOVE PHASES, THERE WILL BE TESTING AND COMMISSIONING ACROSS ALL ASPECTS OF THE EHRM SYSTEM, INCLUDING ELECTRICAL SYSTEMS, HVAC SYSTEMS, UNINTERRUPTED
POWER SUPPLY (UPS), BACKBONE FIBER AND HORIZONTAL CABLE.
SEQUENCING GENERAL NOTES
1. ALL CONSTRUCTION SEQUENCING SHALL BE COORDINATED WITH THE VA FOR WORK RELATED
TIMES FOR DAY, NIGHT AND WEEKEND WORK. CONTRACTOR SHALL COORDINATE WITH VA AHJ
FOR CODE AND LIFE SAFETY RELATED MEASURES ASSOCIATED WITH PHASING OF DEMOLITION
AND CONSTRUCTION WORK TO MAINTAIN LIFE SAFETY MEASURES.
2. COORDINATE SCHEDULING AND HOURS OF WORK WITH FACILITIES AND OIT PERSONNEL. SOME
WORK MAY NEED TO BE PERFORMED AFTER NORMAL WORKING HOURS AND/OR ON WEEKENDS.
PROVIDE 14 CALENDAR DAYS ADVANCE NOTICE WHENEVER POSSIBLE.
CONSTRUCTION STAGING AREA
TEMPORARY CONSTRUCTION TRAILER
CONSTRUCTION PATH OF TRAVEL
CONSTRUCTION ENTRANCE
FOOTHILL DRIVE
M
AR
IO
C
AP
EC
C H
I D
R
IV
E
FO
O
TH
ILL D
R
IVE
W ah len W ay
Bennion Blvd
Baker Street
Wahlen Way
W ah le n
W ay
Kisters Street
V aldez D rive
Valdez Drive Th ac ke r S tre et
Kist er s Stre et
Val de z D riv e
T2 T1
5 CU
A
20 57
PH
SITE ACCESS
SEQUENCING NOTES
1. REFER TO SHEET AE003 FOR INFECTION CONTROL NOTES.
2. EXIT PATH SHALL BE MAINTAINED DURING DEMOLITION AND CONSTRUCTION.
3. FACILITY MUST REMAIN OPEN AND OPERATIONAL THROUGHOUT
CONSTRUCTION- COORDINATE ALL UTILITY SERVICE INTERRUPTIONS WITH
THE VA FACILITY MANAGER.
4. WHERE TEMPORARY CONSTRUCTION BARRIER PARTITIONS ARE BUILT IN THE
EXISTING CORRIDORS, PARALLEL WITH THE CORRIDOR WALLS, PROVIDE 6
FEET MINIMUM EGRESS WIDTH WHERE SERVING PATIENTS AND 44 INCHES
ELSEWHERE.
5. CONTRACTOR SHALL ORGANIZE WORK TO LIMIT DISRUPTION OF
DEPARTMENTS.
6. CONSTRUCTION PROJECT ACTIVITY TYPES (PER ASHE INFECTION CONTROL
RISK ASSESSMENT MATRIX) AND PRECAUTION CLASS AS LISTED BELOW.
REFER TO SPECIFICATION FOR INFECTION CONTROL REQUIREMENTS.
POTENTIAL IMPACT BASED ON UNITS ABOVE, BELOW AND SURROUNDING THE
CONSTRUCTION WORK AREA.
7. INFECTION CONTROL ASSESSMENT SHALL BE VERIFIED BY FACILITES IC
COMMITTEE
A. APPROVAL WILL BE REQURED WHEN THE CONSTRUCTION ACTIVITY
AND RISK LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL
PROCEDURES ARE NECESSARY.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S L
C V
A M
C E
H R
M I n fr a s tr u c tu re U p g ra d e s /G e n
A rc h .r v t
/1
/2
:4
:2
P M
AE002
CONSTRUCTION SEQUENCING -
SITE
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 PURCELL ROOKER
06/08/23
SEQUENCING SHEET INDEX
SEQUENCING
01-GC110 SEQUENCING PLAN - FIRST FLOOR
01-GC120 SEQUENCING PLAN - SECOND FLOOR
01-GC130 SEQUENCING PLAN - THIRD FLOOR
01-GC140 SEQUENCING PLAN - FOURTH FLOOR
01-GC150 SEQUENCING PLAN - FIFTH FLOOR
14-GC1B0 SEQUENCING PLAN - BASEMENT FLOOR
14-GC100 SEQUENCING PLAN - GROUND FLOOR
14-GC110 SEQUENCING PLAN - FIRST FLOOR
14-GC120 SEQUENCING PLAN - SECOND FLOOR
14-GC130 SEQUENCING PLAN - THIRD FLOOR
02-GC100 SEQUENCING PLAN - GROUND FLOOR
02-GC110 SEQUENCING PLAN - FIRST FLOOR
02-GC120 SEQUENCING PLAN - SECOND FLOOR
03-GC100 SEQUENCING PLAN - GROUND FLOOR
03-GC110 SEQUENCING PLAN - FIRST FLOOR
03-GC120 SEQUENCING PLAN - SECOND FLOOR
04-GC110 SEQUENCING PLAN - FIRST FLOOR
05-GC110 SEQUENCING PLAN - FIRST FLOOR
06-GCB01 SEQUENCING PLAN - BASEMENT FLOOR
06-GC110 SEQUENCING PLAN - FIRST FLOOR
07-GC110 SEQUENCING PLAN - FIRST FLOOR
08-GC120 SEQUENCING PLAN - SECOND FLOOR
09-GC100 SEQUENCING PLAN - GROUND FLOOR
16-GC100 SEQUENCING PLAN - GROUND FLOOR
16-GC110 SEQUENCING PLAN - FIRST FLOOR
16-GC120 SEQUENCING PLAN - SECOND FLOOR
38-GC110 SEQUENCING PLAN - FIRST FLOOR
47-GC110 SEQUENCING PLAN - FIRST FLOOR
550-GC110 SEQUENCING PLAN - FIRST FLOOR
550-GC120 SEQUENCING PLAN - SECOND FLOOR
550-GC130 SEQUENCING PLAN - THIRD FLOOR
590-GC100 SEQUENCING PLAN - GROUND FLOOR
590-GC110 SEQUENCING PLAN - FIRST FLOOR
590-GC120 SEQUENCING PLAN - SECOND FLOOR
SEQUENCING LEGEND
NORTH 1" = 100'-0"1
CONSTRUCTION SEQUENCING - SITE
GRAPHIC SCALE 1:100
1 0 2 4 6m
INFECTION CONTROL NOTES
1. ALL BUILDINGS WILL REMAIN OPERATIONAL 24 HOURS A DAY, 7 DAYS A WEEK.
THE CONTRACTOR SHALL ENSURE THAT A PATH OF TRAVEL BETWEEN
BUILDINGS IS MAINTAINED AT ALL TIMES.
2. BEFORE STARTING CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE A
COMPLETE ACCESS PATH / ROUTE FROM THE PROPOSED CONSTRUCTION
STAGING AREA ON SITE TO THE ARE OF WORK WITHIN EACH BUILDING.
3. WITH COR APPROVAL THE CONTRACTOR MAY USE DESIGNATED ELEVATORS
AND STAIRS TO TRANSPORT EQUIPMENT AND MATERIALS INTO AND OUT OF
THE WORK AREA. MATERIAL AND CONSTRUCTION DEBRIS TRANSPORTED VIA
CORRIDORS AND ELEVATOR/STAIRS SHALL BE TRANSPORTED AS INDICATED
IN NOTE 4, BELOW. CONTRACTOR TO INCLUDE THIS REQUIREMENT IN THE
LOGISTICS PLAN.
4. COVER CONSTRUCTION WASTE IN TIGHTLY SEALED RECEPTACLES OR CARTS
BEFORE TRANSPORTING. TAPE AND SEAL COVERING OVER CONTAINERS
UNLESS A SOLID TIGHT CONTAINER LID IS PROVIDED. DEBRIS REMOVAL,
TRAVEL PATH AND SCHEDULE SHALL BE COORDINATED WITH THE OWNERS
OPERATIONAL HOURS.
5. CONTRACTOR SHALL PROVIDE CONSTRUCTION BARRIERS, TEMPORARY ONE
HOUR PARTITIONS AND SMOKE BARRIERS.
6. INCLUDE TEMPORARY 20 MINUTE DOORS AT TEMPORARY 1 HOUR WALLS AS
REQUIRED FOR CONSTRUCTION.
7. UPON COMPLETION OF WORK, REMOVE BARRIERS CAREFULLY TO MINIMIZE
SPREAD OF DIRT AND DEBRIS ASSOCIATED WITH THE CONSTRUCTION. DO NOT
REMOVE FINAL CONSTRUCTION BARRIERS UNTIL COMPLETED PROJECT IS
INSPECTED AND APPROVED BY THE COR.
8. THE WORK AREAS ARE TO BE KEPT CLEAN, CLEAR AND FREE OF DEBRIS.
CONSTRUCTION MATERIALS AND PARTIALLY INSTALLED WORK CANNOT
INTERFERE WITH THE FACILITY OPERATIONS OR CREATE A SAFETY HAZARD.
9. THE CONTRACTOR SHALL SWEEP, VACUUM, MOP CONSTRUCTION AREAS
CLEAN AT THE END OF THE WORKDAY. KEEP NOISE AND DUST TO A MINIMUM
AT ALL TIMES. USE FILTERED VACUUMS.
10. WET MOP AREA WITH DISINFECTANT WHERE APPLICABLE.
11. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK AREA. PROVIDE 'AIR
SCRUBBERS' AT CONSTRUCTION AREAS. UST, FUMES, ETC. MUST BE
EXHAUSED OUTSIDE AND AWAY FROM ANY AIR INTAKE EQUIPMENT.
12. ISOLATE HVAC SYSTEMS IN AREAS WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEMS.
13. COMPLETE ALL CRITICAL CONSTRUCTION BARRIERS BEFORE DEMOLITION /
CONSTRUCTION WORK BEGINS. COR AND INFECTION CONTROL DEPARTMENT
SHALL INSPECT INFECTION CONTROL BARRIERS BEFORE DEMOLITION BEGINS.
14. SEAL ALL EXISTING UNUSED DOORS TO PREVENT THE GENEAL PUBLIC FROM
ENTERING THE DEMOLITION /CONSTRUCTION AREAS.
15. ALL CONSTRUCTION PERSONEL ENTERING / EXITING THE WORK AREA VIA
PUBLIC PATH OF TRAVEL MUST WEAR SHOE COVERS. SHOE COVERS MUST BE
CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.
16. PLACE DUST MATS AND ENTRANCES / EXITS TO THE WORK AREA. CLEAN MATS
FROM DUST DAILY OR EARLIER AS REQUIRED.
17. IF EXISTING LIFE SAFETY SYSTEM IS SHUT OFF FOR CONSTRUCTION, THE
CONTRACTOR IS TO PROVIDE A 24 HOUR FIRE WATCH UNTIL THE SYSTEM IS
BACK ON LINE.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S L
C V
A M
C E
H R
M I n fr a s tr u c tu re U p g ra d e s /G e n
A rc h .r v t
/1
/2
:4
:2
P M
AE003
INFECTION CONTROL EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 PURCELL ROOKER
06/08/23
INFECTION CONTROL ASSESSMENT
FLOOR
ROOM
NUMBER ROOM NAME
INFECTION CONTROL ASSESSMENT
REMARKS
ACTIVITY
TYPE
RISK
GROUP
REQUIREMENT
S
BUILDING 01
GROUND GA00-01 CORRIDOR TYPE B LOW CLASS II
GROUND GA16-01 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II GA14-01 REMOVED
GROUND GA18-01 RELEASE OF INFORMATION TYPE C LOW CLASS II
GROUND GB05-01 TELE. DATA TYPE B LOW CLASS II
GROUND GB08-01 TELE. DATA/LINEN TYPE B LOW CLASS II
GROUND GC00-01 CORRIDOR TYPE C LOW CLASS II NEAR GC01-01
GROUND GC00-01 CORRIDOR TYPE C LOW CLASS II NEAR GC10-01
GROUND GC01-01 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
GROUND GC01A-01 HAC TYPE C LOW CLASS II
GROUND GC10-01 ENTRY (UTILITIES) TYPE C LOW CLASS II
GROUND GC10A-01 AUX. SYSTEMS TYPE B LOW CLASS II
GROUND GC10B-01 HAC TYPE C LOW CLASS II
GROUND GC10C-01 MECHANICAL {PAINT SHOP} TYPE C LOW CLASS II
GROUND GC10CA-01 SHOP PLUMBING {BREAK ROOM} TYPE C LOW CLASS II
GROUND GD13-01 COMPUTER ROOM TYPE C LOW CLASS II
FIRST 1A00-01 CORRIDOR TYPE C MEDIUM CLASS III NEAR 1A04-01
FIRST 1A00-01 CORRIDOR TYPE B MEDIUM CLASS II NEAR 1A15A-01
FIRST 1A04-01 CLEAN UTILITY TYPE C MEDIUM CLASS III
FIRST 1A15A-01 TELECOMMUNICATIONS ROOM TYPE C MEDIUM CLASS III
FIRST 1A19C-01 TELE. DATA TYPE B LOW CLASS II
FIRST 1B05-01 UTILITIES TYPE B LOW CLASS II
FIRST 1B29-01 TELE. DATA TYPE B LOW CLASS II
FIRST 1C00-01 CORRIDOR TYPE C LOW CLASS II
FIRST 1C06-01 STORAGE TYPE C LOW CLASS II
FIRST 1C12-01 TELE. DATA TYPE B LOW CLASS II
FIRST 1D00D-01 CORRIDOR (WC) TYPE B MEDIUM CLASS II
FIRST 1D18-01 PHONE TYPE B MEDIUM CLASS II
FIRST 1D42B-01 TELECOMMUNICATIONS ROOM TYPE C MEDIUM CLASS III
FIRST 1D71-01 STORAGE {TELE. DATA} TYPE B MEDIUM CLASS II
FIRST 1E02-01 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
FIRST 1E02A-01 WAITING AREA TYPE C MEDIUM CLASS III
FIRST 1EAC-01 TELE. DATA TYPE B LOW CLASS II
FIRST 1F02-01 TELE. DATA TYPE B MEDIUM CLASS II
FIRST 1F33G-01 TELE. DATA TYPE B MEDIUM CLASS II
FIRST 1H17-01 DATA TYPE B MEDIUM CLASS II
SECOND 2A00-01 CORRIDOR TYPE C HIGHEST CLASS III/IV
SECOND 2A11-01 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV
SECOND 2A11A-01 WORKROOM TYPE C HIGHEST CLASS III/IV
SECOND 2A15C-01 AUX, TELE. DATA TYPE B HIGHEST CLASS III/IV
SECOND 2B09-01 AUX. SYSTEMS TYPE B HIGHEST CLASS III/IV
SECOND 2C00-01 CORRIDOR TYPE C HIGHEST CLASS III/IV
SECOND 2C08-01 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV
SECOND 2C08A-01 LOCKERS TYPE C HIGHEST CLASS III/IV
SECOND 2C20B-01 TELE. DATA TYPE B HIGHEST CLASS III/IV
SECOND 2D02-01 WAITING AREA TYPE C HIGHEST CLASS III/IV 2D01-01 & 2D07-01 REMOVED
SECOND 2D02A-01 LOCKER/LOUNGE TYPE C HIGHEST CLASS III/IV
SECOND 2EAC-01 TELE. DATA TYPE B LOW CLASS II
SECOND 2F55-01 IT CLOSET TYPE B MEDIUM CLASS II
THIRD 3A00-01 CORRIDOR TYPE C HIGHEST CLASS III/IV
THIRD 3A00B-01 CORRIDOR TYPE C HIGHEST CLASS III/IV
THIRD 3A08-01 CLEAN LINEN RM TYPE C HIGHEST CLASS III/IV
THIRD 3A11A-01 ALCOVE TYPE C HIGHEST CLASS III/IV
THIRD 3A11B-01 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV
THIRD 3A11C-01 CLEAN ROOM TYPE C HIGHEST CLASS III/IV
THIRD 3A15D-01 TELE. DATA TYPE B HIGHEST CLASS III/IV
THIRD 3A20-01 TEAM ROOM TYPE C HIGHEST CLASS III/IV 3A22-01 REMOVED
THIRD 3A33-01 OFFICE TYPE C HIGHEST CLASS III/IV
THIRD 3B09-01 TELE. DATA TYPE B MEDIUM CLASS II
THIRD 3C00-01 CORRIDOR TYPE C HIGH CLASS III/IV
THIRD 3C06-01 PROCEDURE TYPE C HIGH CLASS III/IV
THIRD 3C08-01 PROCEDURE TYPE C HIGH CLASS III/IV
THIRD 3C08A-01 TELECOMMUNICATIONS ROOM TYPE C HIGH CLASS III/IV 3C06A-01 REMOVED
THIRD 3C20B-01 TELE. DATA TYPE B HIGH CLASS II
THIRD 3D07-01 TELE. DATA TYPE B HIGHEST CLASS III/IV
FORTH 4A00-01 CORRIDOR TYPE C MEDIUM CLASS III NEAR 4A11B-01
FORTH 4A00-01 CORRIDOR TYPE C MEDIUM CLASS III NEAR 4A12-01
FORTH 4A00-01 CORRIDOR TYPE C MEDIUM CLASS III NEAR 4A07-01
FORTH 4A00-01 CORRIDOR TYPE C MEDIUM CLASS III NEAR 4A05A-01
FORTH 4A05A-01 MED. ROOM TYPE C MEDIUM CLASS III 4A03A-01 REMOVED
FORTH 4A07-01 WAITING ROOM TYPE C MEDIUM CLASS III 4A07A-01 REMOVED
FORTH 4A11-01 ALCOVE TYPE C MEDIUM CLASS III
FORTH 4A11A-01 TELECOMMUNICATIONS ROOM TYPE C MEDIUM CLASS III
FORTH 4A11B-01 VITALS ROOM TYPE C MEDIUM CLASS III
FORTH 4A12-01 EXAM ROOM TYPE C MEDIUM CLASS III 4A10CA-01 REMOVED
FORTH 4A15D-01 TELE. DATA AND LOCKS TYPE B MEDIUM CLASS III
FORTH 4B13-01 AUX. SYSTEMS TYPE B MEDIUM CLASS II
FORTH 4C00-01 CORRIDOR TYPE C MEDIUM CLASS III
FORTH 4C08-01 TELECOMMUNICATIONS ROOM TYPE C MEDIUM CLASS III 4C08A-01 REMOVED
FORTH 4C22B-01 TELE. DATA TYPE B MEDIUM CLASS II
FORTH 4D05-01 TELE. DATA TYPE B HIGH CLASS II
FIFTH 5B00-01 CORRIDOR TYPE C LOW CLASS II
FIFTH 5B08-01 WORKROOM (HBHC STAFF) TYPE C LOW CLASS II
FIFTH 5B08A-01 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
FIFTH 5B13B-01 TELE. DATA TYPE B LOW CLASS II
INFECTION CONTROL ASSESSMENT
FLOOR
ROOM
NUMBER ROOM NAME
INFECTION CONTROL ASSESSMENT
REMARKS
ACTIVITY
TYPE
RISK
GROUP
REQUIREMENT
S
BUILDING 02
GROUND GA28-02 TELE. DATA TYPE B HIGH CLASS II
GROUND GB03-02 TELE. DATA TYPE B LOW CLASS II
GROUND GC02A-02 TELECOMMUNICATIONS / ENTRY TYPE C HIGH CLASS III/IV
GROUND GC21-02 TELE. DATA TYPE B HIGH CLASS II
GROUND GD05-02 TELE. DATA TYPE B LOW CLASS II
FIRST 1A36-02 TELE. DATA TYPE B LOW CLASS II
FIRST 1B09-02 ELECTRICAL TYPE B LOW CLASS II
FIRST 1C31-02 TELE. DATA TYPE B HIGH CLASS II
FIRST 1D09-02 TELE. DATA TYPE B HIGH CLASS II
FIRST 1D35-02 AUX. SYSTEMS TYPE B HIGH CLASS II
SECOND 2A24-02 TELE. DATA TYPE B HIGH CLASS II
SECOND 2B07-02 TELE. DATA TYPE B LOW CLASS II
SECOND 2C33-02 STO. TYPE B HIGH CLASS II
SECOND 2D13-02 DATA TYPE B HIGH CLASS II
SECOND 2D29-02 DATA TYPE B HIGH CLASS II
BUILDING 03
GROUND GA00-03 CORRIDOR TYPE C LOW CLASS II
GROUND GA08C-03 TELE. DATA TYPE B LOW CLASS II
GROUND GA12C-03 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
GROUND GA14C-03 HAC TYPE C LOW CLASS II
GROUND GA16-03 MECHANICAL TYPE C LOW CLASS II
GROUND GB00-03 CORRIDOR TYPE C LOW CLASS II NEAR GB02A-03
GROUND GB00-03 CORRIDOR TYPE C LOW CLASS II NEAR GB09-03
GROUND GB01A-03 TELE. DATA TYPE B LOW CLASS II
GROUND GB02A-03 STORAGE/CLOTHING TYPE C LOW CLASS II
GROUND GB09-03 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
GROUND GB09A-03 STORAGE TYPE C LOW CLASS II
GROUND GC14B-03 TELE. DATA TYPE B LOW CLASS II
FIRST (UNKNOWN) CORRIDOR TYPE C LOW CLASS II NEAR 1B13-03 (NEW DOOR)
FIRST (UNKNOWN) CORRIDOR TYPE C HIGHEST CLASS III/IV NEAR 1B13-03 (DOOR INFILL)
FIRST 1A13-03 ENTRY (UTILITIES) TYPE C HIGHEST CLASS III/IV
FIRST 1A13A-03 AUX. SYSTEMS TYPE C HIGHEST CLASS III/IV
FIRST 1A13B-03 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV 1A13C-03 REMOVED
FIRST 1B00D-03 LOBBY (MAIN) TYPE C LOW CLASS II
FIRST 1B01A-03 TELE. DATA TYPE B LOW CLASS II
FIRST 1B10-03 OFFICE TYPE C LOW CLASS II
FIRST 1B11-03 OFFICE TYPE C LOW CLASS II
FIRST 1B12-03 OFFICE TYPE C LOW CLASS II
FIRST 1B13-03 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II 1C01-03 REMOVED
FIRST 1B14-03 OFFICE TYPE C LOW CLASS II
FIRST 1B14A-03 RESTROOM (WOMEN) TYPE C LOW CLASS II
FIRST 1B16-03 RESTROOM (MEN) TYPE C LOW CLASS II
FIRST 1C18B-03 TELE. DATA TYPE B HIGHEST CLASS III/IV
FIRST 1D00-03 CORRIDOR TYPE C LOW CLASS II
FIRST 1D01-03 CHAPLAIN TYPE C LOW CLASS II
SECOND 2A11-03 ENTRY (UTILITIES) TYPE C HIGHEST CLASS III/IV
SECOND 2A11B-03 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV 2A11C-03 REMOVED
SECOND 2B00B-03 CORRIDOR TYPE C LOW CLASS II
SECOND 2B00C-03 CORRIDOR TYPE B LOW CLASS II
SECOND 2B01A-03 TELE. DATA TYPE B LOW CLASS II
SECOND 2B05D-03 OFFICE TYPE C LOW CLASS II
SECOND 2B06-03 LAUNDRY TYPE C LOW CLASS II
SECOND 2B07-03 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
SECOND 2C16B-03 TELE. DATA TYPE B HIGHEST CLASS III/IV
BUILDING 04
FIRST 1A30A-04 TELE. DATA TYPE B LOW CLASS II
FIRST 1B14-04 TELE. DATA TYPE B LOW CLASS II
FIRST 1C40A-04 TELE. DATA TYPE B LOW CLASS II
BUILDING 05
FIRST 1A00-05 CORRIDOR TYPE C HIGHEST CLASS III/IV
FIRST 1A12-05 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV
FIRST 1A14-05 PANEL ROOM TYPE B HIGHEST CLASS III/IV
BUILDING 06
BASEMENT BB01E-06 TELE. DATA TYPE B LOW CLASS II
FIRST 1C03-06 OFFICE (OPS FORMAN) TYPE B LOW CLASS II
BUILDING 07
FIRST 1A00-07 CORRIDOR TYPE C HIGH CLASS III/IV
FIRST 1A02-07 OFFICE (TO 151) TYPE C HIGH CLASS III/IV
FIRST 1A02A-07 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
FIRST 1A40-07 TELE. DATA TYPE B HIGH CLASS II
FIRST 1B00C-07 CORRIDOR TYPE C LOW CLASS II
FIRST 1C10-07 TELE. DATA TYPE B LOW CLASS II
BUILDING 08
SECOND 2A00A-08 CORRIDOR TYPE C LOW CLASS II
SECOND 2A00B-08 CORRIDOR TYPE C LOW CLASS II
SECOND 2A00C-08 CORRIDOR TYPE C LOW CLASS II
SECOND 2A02A-08 TELE. DATA TYPE B LOW CLASS II
SECOND 2A08-08 STORAGE TYPE C LOW CLASS II
SECOND 2A08A-08 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
SECOND 2A12-08 STORAGE TYPE C LOW CLASS II
INFECTION CONTROL ASSESSMENT
FLOOR
ROOM
NUMBER ROOM NAME
INFECTION CONTROL ASSESSMENT
REMARKS
ACTIVITY
TYPE
RISK
GROUP
REQUIREMENT
S
BUILDING 09
FIRST (UNKNOWN) CORRIDOR TYPE C LOW CLASS II NEAR 1A15A-09 (NEW DOOR)
FIRST 1A04-09 CLASSROOM TYPE C LOW CLASS II
FIRST 1A15-09 WORKROOM TYPE C LOW CLASS II
FIRST 1A15A-09 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
FIRST 1A15B-09 STORAGE TYPE C LOW CLASS II
FIRST 1A21-09 TELE. DATA TYPE B LOW CLASS II
BUILDING 14
BASEMENT BA00-14 CORRIDOR TYPE C LOW CLASS II
BASEMENT BA04-14 ENTRY (MORGUE) TYPE C LOW CLASS II
BASEMENT BA04F-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
BASEMENT BA05-14 ELECTRICAL ROOM TYPE B LOW CLASS II
BASEMENT BC07-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
GROUND (UNKNOWN) CORRIDOR TYPE C MEDIUM CLASS III NEAR GB31-14 (DOOR INFILL)
GROUND GA00-14 CORRIDOR TYPE D HIGH CLASS IV GB34-14, GB36-14 & GB38-14 REMOVED
GROUND GA24-14 TELECOMMUNICATIONS ROOM TYPE D HIGH CLASS IV
GROUND GA26-14 INTERNAL MEDICINE SERVICES TYPE D HIGH CLASS IV
GROUND GA28-14 BIOMED TYPE D HIGH CLASS IV
GROUND GA30-14 HAC TYPE D HIGH CLASS IV
GROUND GB07C-14 WORKSTATIONS (STAFF) TYPE C LOW CLASS II
GROUND GB51A-14 TELE. DATA TYPE B LOW CLASS II
GROUND GB64-14 TELE. DATA TYPE B LOW CLASS II
GROUND GC28-14 WAITING TYPE C MEDIUM CLASS III
GROUND GC29-14 HAC TYPE C LOW CLASS II
GROUND GC31-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II GC33-14 REMOVED
FIRST (UNKNOWN) CORRIDOR TYPE C LOW CLASS II NEAR 1C26-14
FIRST 1A00-14 CORRIDOR TYPE C LOW CLASS II
FIRST 1A14-14 TREATMENT ROOM {OFFICE} TYPE C LOW CLASS II
FIRST 1A16-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
FIRST 1B01-14 TELE. DATA TYPE B LOW CLASS II
FIRST 1B25-14 TELE. DATA TYPE B LOW CLASS II
FIRST 1C22-14 CONFERENCE(151) TYPE C LOW CLASS II
FIRST 1C26-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II 1C24-14 REMOVED
SECOND (UNKNOWN) CORRIDOR TYPE C HIGHEST CLASS III/IV NEAR 2C26-14
SECOND 2A17-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II
SECOND 2B00C-14 CORRIDOR TYPE B LOW CLASS II
SECOND 2B02-14 TELE. DATA TYPE B LOW CLASS II
SECOND 2B43-14 TELE. DATA TYPE B LOW CLASS II
SECOND 2C00-14 CORRIDOR TYPE C LOW CLASS II
SECOND 2C16-14 UTILITY (SOILED) TYPE C HIGHEST CLASS III/IV
SECOND 2C18-14 LOCKERS TYPE C HIGHEST CLASS III/IV
SECOND 2C20-14 CHIEF RESIDENTS IN QUALITY & PATIENT SAFETY TYPE C LOW CLASS II
SECOND 2C24-14 HAC TYPE C HIGHEST CLASS III/IV
SECOND 2C32-14 TELECOMMUNICATIONS ROOM TYPE C LOW CLASS II 2C34-14 REMOVED
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 3C16-14 (NEW DOOR)
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 2C16-14 (DOOR INFILL)
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 3A12-14
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 3A26-14
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 3A08-14
THIRD (UNKNOWN) CORRIDOR TYPE C HIGH CLASS III/IV NEAR 3A28-14
THIRD 3A00-14 CORRIDOR TYPE C HIGHEST CLASS III/IV
THIRD 3A08-14 TELECOMMUNICATIONS ROOM TYPE C HIGHEST CLASS III/IV 3A10-14 REMOVED
THIRD 3A12-14 HAC TYPE C HIGH CLASS III/IV
THIRD 3A26-14 OFFICE TYPE C HIGH CLASS III/IV
THIRD 3A26A-14 WHEELCHAIR HOLDING TYPE C HIGH CLASS III/IV CORRIDOR 3A00F-14? REMOVED
THIRD 3A28-14 CHANGING ROOM TYPE C HIGH CLASS III/IV
THIRD 3A28A-14 CHANGING ROOM TYPE C HIGH CLASS III/IV
THIRD 3B02-14 TELE. DATA TYPE B LOW CLASS II
THIRD 3B14-14 TELE. DATA TYPE B HIGH CLASS II
THIRD 3C16-14 TELECOMMUNICATIONS ROOM TYPE C HIGH CLASS III/IV 3C18-14 REMOVED
BUILDING 16
GROUND GA50-16 CLOSET (142, TELE. DATA) TYPE B LOW CLASS II
FIRST 1A46-16 DATA TYPE B LOW CLASS II
SECOND 2A48-16 DATA TYPE B LOW CLASS II
BUILDING 38
FIRST 1A08-38 TELE. DATA TYPE B LOW CLASS II
BUILDING 47
FIRST 1A29D-47 TELE. DATA TYPE B LOW CLASS II
BUILDING 550
FIRST (UNKNOWN) TELE. DATA TYPE B LOW CLASS II
SECOND (UNKNOWN) TELE. DATA TYPE B LOW CLASS II
THIRD (UNKNOWN) TELE. DATA TYPE B LOW CLASS II
BUILDING 590
GROUND GA05-90 TELECOM ROOM TYPE B LOW CLASS II
FIRST 1A00F1-90 TELE. DATA TYPE B LOW CLASS II
SECOND 245-90 TELE. DATA TYPE B LOW CLASS II
BASE FINISH AS SCHEDULED
CEILING AS SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
2 1/2" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM AND TOP TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON EXTERIOR SIDE OF WALL
5/8" GYPSUM ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1"
LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF BOARD AND 12"
O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED
ON OPPOSITE SIDES OF THE ASSEMBLY.
NOTE: THE INTENTION FOR THIS WALL IS TO FUR OUT THE WALL TO MAKE THE
INTERIOR FINISH A SINGLE PLANE. WALL CONDITION SHOULD BE VERIFIED TO
ENSURE THE FINSHES WILL ALIGN.
TOPS OF STUDS TO BE CUT 3/4" SHORT
OF FLOOR TO CEILING DIMENSION
INTERIOREXTERIOR
9"
BASE FINISH AS SCHEDULED
CEILING AS SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM AND TOP TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
5/8" GYPSUM ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1"
LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF BOARD AND 12"
O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED
ON OPPOSITE SIDES OF THE ASSEMBLY.
C-1 (1 HOUR FIRE-RESISTIVE RATING)
FOR WALL TYPE C-1 ONLY: EXTEND GYPSUM BOARD TO UNDERSIDE OF DECK
ABOVE. SEAL ALL PENETRATIONS WITH 1 HOUR FIRE-RESISTIVE RATED SEALANT.
TOPS OF STUDS TO BE CUT 3/4" SHORT
OF FLOOR TO CEILING DIMENSION
INTERIOREXTERIOR
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(1) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON EXTERIOR SIDE OF WALL
5/8" GYPSUM ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1"
LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF BOARD AND 12" O.C.
IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED ON
OPPOSITE SIDES OF THE ASSEMBLY.
9"
2 1/2" x 20 GA. KICKERS @
48" O.C. STAGGERED EACH
SIDE OF THE WALL
2 1/2" x 2 1/2"
CLIP ANGLES(3) #8 SCREWS
EACH BRACE
(4) #8 SCREWS
EACH BRACE
(2) 1 1/4" PAF AT
EACH CLIP
INTERIOREXTERIOR
BASE FINISH AS
SCHEDULED
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON EXTERIOR SIDE OF WALL
ATTACH FIRST LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1" LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF
BOARD AND 12" O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY.
ATTACH SECOND LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1 3/4" LONG, TYPE S STEEL SCREWS SPACED 8" O.C.
PROVIDE 3" GLASS FIBER SOUND ATTENUATION INSULATION (THERMAFIBER SAFB OR
EQUIVALENT) FROM FLOOR TO 4" ABOVE CEILING. SEAL BOTTOM OF WALL AND
PENETRATIONS WITH ACOUSTICAL SEALANT.
9"
2 1/2" x 20 GA. KICKERS @
48" O.C. STAGGERED EACH
SIDE OF THE WALL
2 1/2" x 2 1/2"
CLIP ANGLES(3) #8 SCREWS
EACH BRACE
(4) #8 SCREWS
EACH BRACE
(2) 1 1/4" PAF AT
EACH CLIP
SOUND ATTENUATION
INSULATION
INTERIOREXTERIOR
SOUND ATTENUATION
INSULATION
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
5/8" GYPSUM ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1"
LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF BOARD AND 12" O.C.
IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED ON
OPPOSITE SIDES OF THE ASSEMBLY.
9"
2 1/2" x 20 GA. KICKERS @
48" O.C. STAGGERED EACH
SIDE OF THE WALL
2 1/2" x 2 1/2"
CLIP ANGLES(3) #8 SCREWS
EACH BRACE
(4) #8 SCREWS
EACH BRACE
(2) 1 1/4" PAF AT
EACH CLIP
INTERIOREXTERIOR
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
ATTACH FIRST LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1" LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF
BOARD AND 12" O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY.
ATTACH SECOND LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1 3/4" LONG, TYPE S STEEL SCREWS SPACED 8" O.C.
PROVIDE 3" GLASS FIBER SOUND ATTENUATION INSULATION (THERMAFIBER SAFB OR
EQUIVALENT) FROM FLOOR TO 4" ABOVE CEILING. SEAL BOTTOM OF WALL AND
PENETRATIONS WITH ACOUSTICAL SEALANT.
9"
2 1/2" x 20 GA. KICKERS @
48" O.C. STAGGERED EACH
SIDE OF THE WALL
2 1/2" x 2 1/2"
CLIP ANGLES
(3) #8 SCREWS
EACH BRACE
(4) #8 SCREWS
EACH BRACE
(2) 1 1/4" PAF AT
EACH CLIP
INTERIOREXTERIOR
SOUND ATTENUATION
INSULATION
SOUND ATTENUATION
INSULATION
BASE FINISH AS SCHEDULED
CEILING AS SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM AND TOP TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
ATTACH FIRST LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1" LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF
BOARD AND 12" O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY
AND STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY.
ATTACH SECOND LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1 3/4" LONG, TYPE S STEEL SCREWS SPACED 8" O.C.
PROVIDE 3" GLASS FIBER SOUND ATTENUATION INSULATION (THERMAFIBER SAFB
OR EQUIVALENT) FROM FLOOR TO DECK. SEAL TOP AND BOTTOM OF WALL AND
PENETRATIONS WITH ACOUSTICAL SEALANT.
E-1 (1 HOUR FIRE-RESISTIVE RATING) & E-2 (2 HOUR FIRE-RESISTIVE RATING)
FOR WALL TYPE E-1 AND E-2 ONLY: EXTEND GYPSUM BOARD TO UNDERSIDE OF
DECK ABOVE. SEAL ALL PENETRATIONS WITH 1 OR 2 HOUR FIRE-RESISTIVE RATED
SEALANT RELATIVE TO WALL RATING.
TOPS OF STUDS TO BE CUT 3/4" SHORT
OF FLOOR TO CEILING DIMENSION
SOUND ATTENUATION
INSULATION
INTERIOREXTERIOR
BASE FINISH AS SCHEDULED
CEILING AS SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM AND TOP TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON EXTERIOR SIDE OF WALL
5/8" GYPSUM ATTACHED TO STEEL STUDS AND FLOOR AND CEILING TRACK WITH 1"
LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF BOARD AND 12"
O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED
ON OPPOSITE SIDES OF THE ASSEMBLY.
G-1 (1 HOUR FIRE-RESISTIVE RATING)
FOR WALL TYPE G-1 ONLY: EXTEND GYPSUM BOARD TO UNDERSIDE OF DECK
ABOVE. SEAL ALL PENETRATIONS WITH 1 HOUR FIRE-RESISTIVE RATED SEALANT.
TOPS OF STUDS TO BE CUT 3/4" SHORT
OF FLOOR TO CEILING DIMENSION
INTERIOREXTERIOR
BASE FINISH AS SCHEDULED
CEILING AS SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
3 5/8" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM AND TOP TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
(1) LAYER 5/8" TYPE 'X' GYPSUM BOARD ON EXTERIOR SIDE OF WALL
ATTACH FIRST LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1" LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF
BOARD AND 12" O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY
AND STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY.
ATTACH SECOND LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1 3/4" LONG, TYPE S STEEL SCREWS SPACED 8" O.C.
PROVIDE 3" GLASS FIBER SOUND ATTENUATION INSULATION (THERMAFIBER SAFB
OR EQUIVALENT) FROM FLOOR TO DECK. SEAL TOP AND BOTTOM OF WALL AND
PENETRATIONS WITH ACOUSTICAL SEALANT.
J-1 (1 HOUR FIRE-RESISTIVE RATING)
FOR WALL TYPE J-1 ONLY: EXTEND GYPSUM BOARD TO UNDERSIDE OF DECK
ABOVE. SEAL ALL PENETRATIONS WITH 1 HOUR FIRE-RESISTIVE RATED SEALANT.
TOPS OF STUDS TO BE CUT 3/4" SHORT
OF FLOOR TO CEILING DIMENSION
BASE FINISH AS SCHEDULED
INTERIOREXTERIOR
SOUND ATTENUATION
INSULATION
WALL SECTION GENERAL NOTES
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
2 1/2" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
ATTACH FIRST LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1" LONG, TYPE S STEEL SCREWS SPACED 8" O.C. ALONG EDGES OF
BOARD AND 12" O.C. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND
STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY.
ATTACH SECOND LAYER OF 5/8" GYPSUM TO STEEL STUDS AND FLOOR AND CEILING
TRACK WITH 1 3/4" LONG, TYPE S STEEL SCREWS SPACED 8" O.C.
9"
2 1/2" x 20 GA. KICKERS @
48" O.C. STAGGERED EACH
SIDE OF THE WALL
2 1/2" x 2 1/2"
CLIP ANGLES
(3) #8 SCREWS
EACH BRACE
(4) #8 SCREWS
EACH BRACE
(2) 1 1/4" PAF AT
EACH CLIP
INTERIOREXTERIOR
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S L
C V
A M
C E
H R
M I n fr a s tr u c tu re U p g ra d e s /G e n
A rc h .r v t
/1
/2
:4
:2
P M
AE201
WALL SECTIONS EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
GENERAL
08 JUN 2023 PURCELL ROOKER
06/08/23
3/4" = 1'-0"A
WALL TYPE A
3/4" = 1'-0"C
WALL TYPE C, C-1
3/4" = 1'-0"H
WALL TYPE H
3/4" = 1'-0"K
WALL TYPE K
3/4" = 1'-0"D
WALL TYPE D
3/4" = 1'-0"F
WALL TYPE F
3/4" = 1'-0"E
WALL TYPE E, E-1, E-2
3/4" = 1'-0"G
WALL TYPE G, G-1
3/4" = 1'-0"J
WALL TYPE J, J-1
3/4" = 1'-0"B
WALL TYPE B
BASE FINISH AS
SCHEDULED
CEILING AS
SCHEDULED
UNDERSIDE OF
FLOOR SLAB ABOVE
6" x 20 GAUGE STEEL STUDS @ 16" O.C.
ATTACH BOTTOM TRACK TO STRUCTURE WITH 3/16" x 1 1/4" PAF @ 16" O.C.
BRACE TOP OF WALL
(2) LAYERS 5/8" TYPE 'X' GYPSUM BOARD ON INTERIOR SIDE OF WALL
(2) LAYERS…