Attachment 10-Part 9 of 9-Drawings-EHRM-Salt Lake City.pdf

PDF 14 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction - Salt Lake City VAMC Project 660-21-700
Solicitation number
36C77623B0041
Issued by

About this file

This document contains details of a federal contract opportunity for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0041 for EHRM Infrastructure Upgrades Construction services at the Salt Lake City VAMC. The project, numbered 660-21-700, involves upgrades to infrastructure at the Salt Lake City VA Medical Center. An attachment provides drawings related to the project with a file size of 14MB. Proposals are due by the date listed in the solicitation document. The opportunity is for construction services and the selected contractor will be expected to complete the infrastructure upgrade project at the Salt Lake City VAMC.

View the file

Other files

File Type Posted
RESPONSE Attachment V5.1.docx DOCX document
Construction Wage Rates- Salt Lake County- 08-11-2023.pdf PDF
ADDENDUM No 01.pdf PDF
Bid opening call-in information.pdf PDF
RESPONSE Attachment V5.1 No. 30 Snippet.JPG JPG image
2017 AHERA 3-Year Reinspection v2.2 2017_1205_BT.xlsx XLSX spreadsheet
RESPONSE V10 - Technical Questions.docx DOCX document
RESPONSE Attachment V7.2.docx DOCX document
36C77623B0041 0004.pdf PDF
RESPONSE Attachment V2.1.docx DOCX document
RESPONSE Attachment V1.1.docx DOCX document
RESPONSE Attachment V7.1.docx DOCX document
RESPONSE Attachment V3.1.docx DOCX document
36C77623B0041 0003.pdf PDF
36C77623B0041 0003.pdf PDF
36C77623B0041 0002.pdf PDF
660-21-700 PreConstruction Site Visit Sing In Sheet 2023 07 14.pdf PDF
36C77623B0041 0001.pdf PDF
Attachment 13-Utah Tax Memo-EHRM-Salt Lake City.pdf PDF
Attachment 7-Part 6 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 12-Construction Wage Rates-Salt Lake County- 04-14-2023.pdf PDF
Attachment 14-Limitations on Subcontracting-EHRM-Salt Lake City.docx DOCX document
Attachment 2-Part 1 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 15-Contractor Safety-Environmental-EHRM-S.L.C..docx DOCX document
Attachment 1-Specifications-(1 of 1)-EHRM-Salt Lake City.pdf PDF
Attachment 6-Part 5 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 3-Part 2 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 9-Part 8 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 5-Part 4 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
36C77623B0041.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 11-Asbestos Site Survey-EHRM Salt Lake City.pdf PDF
Attachment 4-Part 3 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 8-Part 7 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

TR

2 HR. FIRE BARRIER

1 HR. FIRE BARRIER

SMOKE BARRIER

FIRE ALARM ZONE

CORRIDORS

AREA OF CONSTRUCTION

EXISTING TELECOMMUNICATION SPACE

TR TELECOMMUNICATION ROOM

GENERAL FIRE PROTECTION NOTES

1. THE SCOPE OF WORK FOR THIS PROJECT INCLUDES THE MODIFICATION OF THE EXISTING

FIRE SPRINKLER SYSTEMS IN THE REMODEL AREAS TO MEET VA GUIDELINES.

2. AREAS HIGHLIGHTED ON PLANS INDICATE PROJECT AREAS TO BE ADDRESSED. SCOPE OF

WORK IN AREAS OUTSIDE THE HIGHLIGHTED SPACES IDENTIFIED IS LIMITED TO WORK

REQUIRED TO FACILITATE CONNECTION OF NEW PIPING TO EXISTING SYSTEMS.

3. REVIEW PLANS FOR LOCATION OF ELECTRICAL EQUIPMENT AND COMPUTER SERVERS.

MODIFY PIPING TO AVOID RUNNING OVER THE TOP OF EQUIPMENT. IF EXISTING SPRINKLERS

ARE TO BE REMOVED, DUE TO CEILING WORK OR OTHER REMODEL WORK, REPLACE WITH NEW

QUICK RESPONSE TYPE SPRINKLERS UNLESS AS MODIFIED BELOW.

4. HALLWAYS, CORRIDORS, OFFICES, ETC. AS IDENTIFIED IN NFPA 13 AND VA FIRE PROTECTION

DESIGN GUIDE AS LIGHT HAZARD; SPACE SPRINKLERS FOR LIGHT HAZARD OCCUPANCY (225

SQ.FT. MAX PER SPRINKLER). MATCH SPRINKLER RESPONSE TO EXISTING SPRINKLERS. IF

ENTIRE SPACE IS MODIFIED REPLACE WITH QUICK RESPONSE TYPE SPRINKLERS.

5. TR'S, STORAGE ROOMS, ETC. AS IDENTIFIED IN NFPA 13 AND VA FIRE PROTECTION DESIGN

GUIDE AS ORDINARY HAZARD GROUP I OCCUPANCY (130 SQ.FT. MAX PER SPRINKLER). MATCH

SPRINKLER RESPONSE TO EXISTING SPRINKLERS. IF ENTIRE SPACE IS MODIFIED REPLACE

WITH QUICK RESPONSE TYPE SPRINKLERS.

RAND M.

EARDLEY

128806

S T

OF

A T

E UTA

H

ARED CH

IT

E C T

N S

C E

L I

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

A

R C

H .r v t

/1

/2

:0

:0

P M

08-FX120

OVERALL SECOND FLOOR FIRE

SPRINKLER PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 DUBOIS ROOKER

06/08/23

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

NORTH

1/8" = 1'-0"1

OVERALL SECOND FLOOR FIRE SPRINKLER PLAN

FIRE PROTECTION LEGEND

Revisions: Date:

06/02/2023

2A00

2A04

2A02A

2A02B

2A02

2A00B

2A11

2A092A13

2A08

2AB

2A06

2AA

2AAA

2A00A

2A01

2A03 2A05

2A07

CORRIDOR

EXTINGUISHER/HOSE

TEL/DATA

ELECTRICAL

ENTRY

CORRIDOR

TOILETTOILET

STORAGE

STAIRS LEVEL

OFFICE

STAIRS LEVEL

CORRIDOR

CONFERENCE

OFFICE

OFFICE

LOUNGE (HR-LINKS)

ROOF

ACCESS

ELEVATOR

T

08-MH401

F3

08-MH401

F6

MECHANICAL GENERAL NOTES:

1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN

PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.

COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.

2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.

COORDINATE LOCATION WITH OWNER.

3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,

AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER

INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL

HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE

ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER

OPERATION OF ACCESSORY.

5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING

STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING

AND/OR COMMUNICATION TO BMS.

6. MECHANICAL PIPING SCHEDULE:

1. REFRIGERANT PIPING = ACR TYPE L - BRAZED

7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.

PLUMBING GENERAL NOTES:

1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING

WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.

2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR

PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY

HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

M

E C

H .r v t

/1

/2

:0

:0

P M

08-MH111

SECOND FLOOR MECHANICAL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 RHB ARA AJB

GENERAL SHEET NOTES

NORTH

1/8" = 1'-0"F1

SECOND FLOOR MECHANICAL PLAN

6-8-23

S

S

SS-2MH401 1

MECHANICAL GENERAL NOTES:

1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN

PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.

COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.

2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.

COORDINATE LOCATION WITH OWNER.

3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,

AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER

INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL

HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE

ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER

OPERATION OF ACCESSORY.

5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING

STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING

AND/OR COMMUNICATION TO BMS.

6. MECHANICAL PIPING SCHEDULE:

1. REFRIGERANT PIPING = ACR TYPE L - BRAZED

7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.

PLUMBING GENERAL NOTES:

1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING

WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.

2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR

PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY

HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

M

E C

H .r v t

/1

/2

:0

:0

P M

08-MH113

OVERALL ROOF MECHANICAL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 RHB ARA AJB

NORTH

1/8" = 1'-0"1

OVERALL ROOF MECHANICAL PLAN

GENERAL SHEET NOTES

SHEET KEYNOTES

1 CONTRACTOR TO FIELD VERIFY LOCATION OF ROOFTOP UNIT WITH EXISTING

CONDITIONS. UNIT TO BE 10' AWAY FROM ROOFS EDGE. MAINTAIN

MANUFACTURER'S SERVICE CLEARANCE.

T

AC-2

RS/RL

DCW

CD

STORAGE

2A08-08

MECHANICAL GENERAL NOTES:

1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN

PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.

COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.

2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.

COORDINATE LOCATION WITH OWNER.

3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,

AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER

INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL

HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE

ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER

OPERATION OF ACCESSORY.

5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING

STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING

AND/OR COMMUNICATION TO BMS.

6. MECHANICAL PIPING SCHEDULE:

1. REFRIGERANT PIPING = ACR TYPE L - BRAZED

7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.

PLUMBING GENERAL NOTES:

1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING

WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.

2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO

ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR

CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE

CONDITIONS.

3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR

PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY

HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

M

E C

H .r v t

/1

/2

:0

:0

P M

08-MH401

ENLARGED MECHANICAL PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 RHB ARA AJB

GENERAL SHEET NOTES

SHEET KEYNOTES

NORTH

1/2" = 1'-0"F6

SECOND FLOOR ENLARGED TR - 2A10-08 NEW MECHANICAL PLAN

NORTH

1/2" = 1'-0"F3

SECOND FLOOR ENLARGED STORAGE - 2A08-08 MECHANICAL DEMOLITION PLAN

1 ROUTE REFRIGERANT LINES TO CONDENSING UNIT LOCATED ON ROOF. PIPE

SIZE BY MANUFACTURER. REFRIGERANT LINE REPRESENTS SUPPLY AND

LIQUID LINES.

2 ROUTE AND CONNECT WATER LINE TO NEAREST DOMESTIC WATER LINE IN

CORRIDOR. ASSUMED DISTANCE: 30'. SEE ENLARGED PLAN FOR SIZING.

3 ROUTE CONDENSATE LINE TO NEAREST SINK OR LAVATORY. TIE INTO

TAILPIECE. ASSUMED DISTANCE: 30'. SEE ENLARGED PLAN FOR SIZING.

4 COORDINATE ALL THERMOSTAT LOCATIONS WITH OWNER AND LATEST

FURNITURE PLAN. FAILURE TO DO SO MAY RESULT IN RELOCATING

THERMOSTAT AT NO ADDITIONAL COST TO THE OWNER.

UPC

C

PIPE TUNNEL (TO B.06)

GA07BA

MECHANICAL (POOL EQUIPMT)

GA03A

MECHANICAL (HOT TANK)

GA04

ELECTRICAL

GA08

ELECTRICAL

GA08A

OFFICE (137,EMS SUPPLY)

GA02

TRAINING (117,DRIVERS)

GA03

CORRIDOR (TO lOCKER ENTRY)

GA01

STORAGE (GENERAL)

GA06C

STORAGE (135)

GA06B

SHOP (138)

GA05

ENTRY (138, UTILITIES)

GA07

ELECTRICAL

GA08

LOCKERS (WOMEN)

GA01A

SHOP (138)

GA01CA

P

IP

E C

H A

S E

G A

B

A A

STORAGE (142,LIBRARY)

GA01CC

ELEVATOR LEVEL

BAE1

STORAGE (EQUIPMT. CLOTHING)

GA06

FIRE HOSE CLOSET

GA01B

STAIR LEVEL

GAA

STORAGE (135)

GA06A

STORAGE (EQUIPMT. CLOTHING)

GA06D

LOCKERS (MEN)

GA01C

STORAGE (137)

GA01CD

CORRIDOR (TO

LOCKER ENTRY)

GA00A

TOILET/SHOWER

(WOMEN)

GA01AA

TOILET/

SHOWER (MEN)

GA01CB

P

IP

E T

U N

N E

L

T O

C O

N C

O U

R S

E

G A

B

C O

R R

ID

O

R

T O

E L

E V

A T

O R

G

A

+48"

+48"

+72"

+72"

EXISTING TR LOCATION TO BE MOVED

EXISTING TR TO REMAIN

NEW TR LOCATION

SEPARATION LINE INDICATES

TERMINATION OF DATA CABLES TO

SPECIFIED TR LOCATION

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:3

A M

08-ED100

GROUND FLOOR ELECTRICAL

DEMOLITION PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/8" = 1'-0"F1

GROUND FLOOR ELECTRICAL DEMOLITION PLAN

1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING

FIXTURES DEVICES AND EQUIPMENT SHOWN

DASHED. REMOVE CONDUIT AND WIRING BACK TO

PANELBOARD OF ORIGIN OR TO FIRST ACTIVE

DEVICE THAT REMAINS.

2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK

RECEPTACLES AND WALLPLATES, CEILING SPEAKERS

AND SECURITY AND FIRE ALARM DEVICES TO

OWNER. PROTECT SALVAGED EQUIPMENT FROM

DAMAGE.

3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD

VERIFY THE EXTENT OF ELECTRICAL AND DATA

DEMOLITION WORK TO MEET THE INTENT OF THE BID

DOCUMENTS AND INCLUDE ALL COSTS IN BID.

4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT

OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR

WIRING IS INACTIVE OR NO LONGER IN USE.

5 REMOVE ALL DEVICES, RACEWAYS AND WIRING

FROM WALLS TO BE REMOVED. WHERE ACTIVE

RACEWAYS OCCUR IN WALLS TO BE REMOVED,

RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING

TO KEEP THE CIRCUIT OPERATIONAL.

6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING

WALLS AND CEILINGS ARE BEING REMOVED, WITH

ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE

ALARM DEVICES AND SYSTEM NOT INDICATED FOR

REMOVAL SHALL REMAIN ACTIVE THROUGHOUT

DEMOLITION AND CONSTRUCTION UNTIL THE NEW

SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN

ALL CLASS A FIRE ALARM INITIATING AND INDICATING

LOOPS WHERE EXISTING DEVICES ARE REMOVED.

7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,

WIRING AND CABLING WHETHER ABANDONED

PREVIOUS TO THIS PROJECT OR AS A RESULT OF

THIS PROJECT. NOT ALL ABANDONED ITEMS ARE

SHOWN ON THESE PLANS AND FIELD VERIFICATION

OF DEMOLITION SCOPE EXTENT IS REQUIRED.

8 DEVICES MARKED "RR" ARE TO BE REMOVED AND

RELOCATED PER NEW PLANS. EXTEND CIRCUITING

AS REQUIRED FOR RELOCATION.

9 REFER TO ARCHITECTURAL DRAWINGS FOR

REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND

CONTROL WIRING ASSOCIATED WITH EXISTING

MOTORIZED DOORS, PARTITIONS AND LIGHTING.

10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER

SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF

WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC

WI-FI ACCESS POINTS.

11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,

DISCONNETS, ETC. BACK TO SOURCE

12 ALL ITEMS INDICATED TO REMAIN SHALL BE

PROTECTED DURING ALL PHASES OF

CONSTRUCTION.

13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING

LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM

PANELS THAT ARE BEING DEMOLISHED IN THIS

PHASE. THESE LOADS TO BE RE-FED FROM NEW

PANELS IN NEXT PHASE.

14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL

CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE

ALL ASSOCIATED RACEWAYS AND CONDUCTORS

BACK TO SOURCE.

15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING

DATA LOCATIONS.

16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS

PART OF THIS PROJECT SHALL HAVE RACEWAYS

REMOVED AS PART OF THE DEMOLITION SCOPE OF

WORK. DEMOLISHED DATA DEVICES ARE INDICATED

AS DASHED DEVICES AND KEYNOTED.

17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED

UNLESS OTHERWISE SPECIFIED ON THE FLOOR

PLANS. ALL EXISTING DATA DEVICE PATHWAYS

SHALL REMAIN INTACT AND BE REUSED FOR NEW

CABLE INSTALLATION.

18 REMOVE ALL EXISTING CABLES THAT ARE TO BE

REPLACED BACK TO THE PATCH PANEL.

19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR

MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO

ADDITIONAL CABLES OR EQUIPMENT IN THEM.

20 REMOVE EXISTING FIBER FROM TR BACK TO THE

MCR AND ALL FIBER TERMINATION EQUIPMENT

AFTER ALL NETWORK SERVICES HAVE BEEN

REMOVED.

21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND

PROTECT DURING THE STRUCTURED CABLING

UPGRADE.

GENERAL

SHEET NOTES

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

SHEET

KEYNOTES

TR LEGEND

SPECIAL PROJECT

NOTES

1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA

LOCATIONS THAT MAY BE REMOVED AS PART OF

THIS PROJECT. CONTRACTOR TO VERIFY ALL

CABLES TO BE DEMOLISHED COMPLETELY TO THE

VA PATCH PANEL.

06/08/23

UP

C

W

C

C

C

C

W

W

C

C

W

C

C

W

W

GYM (WEST-COURT)

1A22A

GYM (EAST-COURT)

1A22B

GYMNASIUM (EAST & WEST COURTS)

1A22

FIRE EQUIP/HOSE

1A22C

OFFICE (117)

1A30

OFFICE (117)

1A28

POOL (117,THERAPY)

1A13A

WOMEN'S SHOWERS

1A19C

MEN'S LOCKERS

1A17A

MEN'S RESTROOM

1A17C

PIPE CHASE (138)

1A17B

ENTRY TO POOL

1A13

SAUNA (117)

1A13D

STORAGE

1A13C

WELLNESS (00)

1A11

1A11B

STAIRS

1AB STORAGE (MPC)

1A07

WAITING

IB01VESTIBULE

IB00A

OFFICE

IB02

RETAIL STORE (133)

1A01

ELEVATOR

STAIR

1AA

ELECTRICAL

1A26

CORRIDOR (TO ELEVATOR & MPC)

1A00B

STORAGE (MPC)

1A18

STAFF DINING (133)

1A02B

FIRE EQUIP/HOSE

1A02C

STORAGE (133)

1A02E

KITCHEN (133)

1A02G

W O

R K

R O

O M

3) 1A

H

PATIO #03 (MPC)

1A20.03

CORRIDOR

1A00

MEN'S RESTROOM

1A14

WOMEN'S RESTROOM

1A12

P

IP

E C

H A

S E

8) 1A

A

HAC

1A10

KITCHEN (142)

1A20A

STORAGE (142)

1A08A

STORAGE (133)

1A03

CHASE

OFFICE

IB04

OPEN OFFICE

IB06

CONF

IB08

HALL

IB00B

OFFICE

IB10

GAIT LAB

IB01

GAIT LAB

IB12

THEATER

IB14

EQUIP. HOLDING

IB14A

EXAM

IB03

RR

IB05

CLEAN LINENS

IB00D

CRASH CART

IB00E

IT

IB09

ELEC

IB11

HALL

IB00

MECH

IB13

VESTIBULE

IB00F

1A01A

ENTRY (TO REAR OF MPC)

1A08

1A06

OFFICE (133)

1A02A

MULI-PURPOSE CENTER (MPC)

1A20

1A04

DINING (133, CANTEEN)

1A02

PATIO #02 (MPC)

1A20.02

PATIO #01 (MPC)

1A20.01

VESTIBULE

(VENDING)

1A00A

STORAGE

(WELLNESS)

1A11A

OFFICE

(WELLNESS)

1A09

WAITING

(135, SHUTTLE)

1A13A

OFFICE

(133, CHIEF)

1A02AB

OFFICE

(133)

1A02AA

CLOCK ROOM

(MPC)

1A16

CORRIDOR (TO REAR

ENTRANCE)

1A00C

CORRIDOR

(TO GYM)

1A00DTEL/DATA

(142) 1A24

ENTRY (MEN'S

SHOWERS/LOCKERS)

1A17

M E

N 'S

S H

O W

E R

R O

O M

1A

A STORAGE (117,

SCUBA)

1A15ENTRY TO

SAUNA

1A13B

WOMEN'S

RESTROOM

1A19B

WOMEN'S

LOCKERS

1A19A

E N

T R

Y

W O

M E

N 'S

S H

O W

E R

S /L

O C

K E

R S

1A

HAC

(137) 1A02D

STORAGE

(VCS)

1A32

S T

A F

F L

O C

K E

R S

3) 1A

F

+72"

+48"

+48"

F

+84"

+84" +84" +84"

+144"

+144" +144"

+144"+144"

+144"

+144"

+96"

+96"

+96"

+96"

+96"

+144"

+144"+144"+144"+144"

+48"

+48"

+48"

+48"

+48"

KP

+48"

DIRTY

LINENS

IB00C

EXISTING TR LOCATION TO BE MOVED

EXISTING TR TO REMAIN

NEW TR LOCATION

SEPARATION LINE INDICATES

TERMINATION OF DATA CABLES TO

SPECIFIED TR LOCATION

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:4

A M

08-ED110

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/8" = 1'-0"F1

FIRST FLOOR ELECTRICAL DEMOLITION PLAN

1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING

FIXTURES DEVICES AND EQUIPMENT SHOWN

DASHED. REMOVE CONDUIT AND WIRING BACK TO

PANELBOARD OF ORIGIN OR TO FIRST ACTIVE

DEVICE THAT REMAINS.

2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK

RECEPTACLES AND WALLPLATES, CEILING SPEAKERS

AND SECURITY AND FIRE ALARM DEVICES TO

OWNER. PROTECT SALVAGED EQUIPMENT FROM

DAMAGE.

3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD

VERIFY THE EXTENT OF ELECTRICAL AND DATA

DEMOLITION WORK TO MEET THE INTENT OF THE BID

DOCUMENTS AND INCLUDE ALL COSTS IN BID.

4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT

OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR

WIRING IS INACTIVE OR NO LONGER IN USE.

5 REMOVE ALL DEVICES, RACEWAYS AND WIRING

FROM WALLS TO BE REMOVED. WHERE ACTIVE

RACEWAYS OCCUR IN WALLS TO BE REMOVED,

RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING

TO KEEP THE CIRCUIT OPERATIONAL.

6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING

WALLS AND CEILINGS ARE BEING REMOVED, WITH

ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE

ALARM DEVICES AND SYSTEM NOT INDICATED FOR

REMOVAL SHALL REMAIN ACTIVE THROUGHOUT

DEMOLITION AND CONSTRUCTION UNTIL THE NEW

SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN

ALL CLASS A FIRE ALARM INITIATING AND INDICATING

LOOPS WHERE EXISTING DEVICES ARE REMOVED.

7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,

WIRING AND CABLING WHETHER ABANDONED

PREVIOUS TO THIS PROJECT OR AS A RESULT OF

THIS PROJECT. NOT ALL ABANDONED ITEMS ARE

SHOWN ON THESE PLANS AND FIELD VERIFICATION

OF DEMOLITION SCOPE EXTENT IS REQUIRED.

8 DEVICES MARKED "RR" ARE TO BE REMOVED AND

RELOCATED PER NEW PLANS. EXTEND CIRCUITING

AS REQUIRED FOR RELOCATION.

9 REFER TO ARCHITECTURAL DRAWINGS FOR

REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND

CONTROL WIRING ASSOCIATED WITH EXISTING

MOTORIZED DOORS, PARTITIONS AND LIGHTING.

10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER

SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF

WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC

WI-FI ACCESS POINTS.

11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,

DISCONNETS, ETC. BACK TO SOURCE

12 ALL ITEMS INDICATED TO REMAIN SHALL BE

PROTECTED DURING ALL PHASES OF

CONSTRUCTION.

13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING

LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM

PANELS THAT ARE BEING DEMOLISHED IN THIS

PHASE. THESE LOADS TO BE RE-FED FROM NEW

PANELS IN NEXT PHASE.

14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL

CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE

ALL ASSOCIATED RACEWAYS AND CONDUCTORS

BACK TO SOURCE.

15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING

DATA LOCATIONS.

16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS

PART OF THIS PROJECT SHALL HAVE RACEWAYS

REMOVED AS PART OF THE DEMOLITION SCOPE OF

WORK. DEMOLISHED DATA DEVICES ARE INDICATED

AS DASHED DEVICES AND KEYNOTED.

17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED

UNLESS OTHERWISE SPECIFIED ON THE FLOOR

PLANS. ALL EXISTING DATA DEVICE PATHWAYS

SHALL REMAIN INTACT AND BE REUSED FOR NEW

CABLE INSTALLATION.

18 REMOVE ALL EXISTING CABLES THAT ARE TO BE

REPLACED BACK TO THE PATCH PANEL.

19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR

MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO

ADDITIONAL CABLES OR EQUIPMENT IN THEM.

20 REMOVE EXISTING FIBER FROM TR BACK TO THE

MCR AND ALL FIBER TERMINATION EQUIPMENT

AFTER ALL NETWORK SERVICES HAVE BEEN

REMOVED.

21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND

PROTECT DURING THE STRUCTURED CABLING

UPGRADE.

GENERAL

SHEET NOTES

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

SHEET

KEYNOTES

TR LEGEND

SPECIAL PROJECT

NOTES

1 JBOX THAT FEEDS MULTIPLE STATIONS. STATION

COUNT UNKNOWN.

1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA

LOCATIONS THAT MAY BE REMOVED AS PART OF

THIS PROJECT. CONTRACTOR TO VERIFY ALL

CABLES TO BE DEMOLISHED COMPLETELY TO THE

VA PATCH PANEL.

C

C

C

C

C

C

STAIRS/

LEVEL

2AB

C O

R R

ID

O

R

2A

B

STORAGE

2A08

OFFICE

2A06

TEL/DATA

2A02A

CONFERENCE

2A01

EXTINGUISHER/HOSE

2A04

CORRIDOR

2A00A

ELECTRICAL

2A02B

TOILET

2A13

TOILET

2A09

ELEVATOR

ENTRY

2A02

LOUNGE

(HR-LINKS)

2A07

2A11

STAIRS LEVEL

2AA

OFFICE

2A05

OFFICE

2A03

CORRIDOR

2A00

08-ED401

F3

+48"

08-ED401

F7 ROOF ACCESS

2AAA

EXISTING TR LOCATION TO BE MOVED

EXISTING TR TO REMAIN

NEW TR LOCATION

SEPARATION LINE INDICATES

TERMINATION OF DATA CABLES TO

SPECIFIED TR LOCATION

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:5

A M

08-ED120

SECOND FLOOR ELECTRICAL

DEMOLITION PLAN

EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/8" = 1'-0"F1

SECOND FLOOR ELECTRICAL DEMOLITION PLAN 0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING

FIXTURES DEVICES AND EQUIPMENT SHOWN

DASHED. REMOVE CONDUIT AND WIRING BACK TO

PANELBOARD OF ORIGIN OR TO FIRST ACTIVE

DEVICE THAT REMAINS.

2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK

RECEPTACLES AND WALLPLATES, CEILING SPEAKERS

AND SECURITY AND FIRE ALARM DEVICES TO

OWNER. PROTECT SALVAGED EQUIPMENT FROM

DAMAGE.

3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD

VERIFY THE EXTENT OF ELECTRICAL AND DATA

DEMOLITION WORK TO MEET THE INTENT OF THE BID

DOCUMENTS AND INCLUDE ALL COSTS IN BID.

4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT

OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR

WIRING IS INACTIVE OR NO LONGER IN USE.

5 REMOVE ALL DEVICES, RACEWAYS AND WIRING

FROM WALLS TO BE REMOVED. WHERE ACTIVE

RACEWAYS OCCUR IN WALLS TO BE REMOVED,

RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING

TO KEEP THE CIRCUIT OPERATIONAL.

6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING

WALLS AND CEILINGS ARE BEING REMOVED, WITH

ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE

ALARM DEVICES AND SYSTEM NOT INDICATED FOR

REMOVAL SHALL REMAIN ACTIVE THROUGHOUT

DEMOLITION AND CONSTRUCTION UNTIL THE NEW

SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN

ALL CLASS A FIRE ALARM INITIATING AND INDICATING

LOOPS WHERE EXISTING DEVICES ARE REMOVED.

7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,

WIRING AND CABLING WHETHER ABANDONED

PREVIOUS TO THIS PROJECT OR AS A RESULT OF

THIS PROJECT. NOT ALL ABANDONED ITEMS ARE

SHOWN ON THESE PLANS AND FIELD VERIFICATION

OF DEMOLITION SCOPE EXTENT IS REQUIRED.

8 DEVICES MARKED "RR" ARE TO BE REMOVED AND

RELOCATED PER NEW PLANS. EXTEND CIRCUITING

AS REQUIRED FOR RELOCATION.

9 REFER TO ARCHITECTURAL DRAWINGS FOR

REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND

CONTROL WIRING ASSOCIATED WITH EXISTING

MOTORIZED DOORS, PARTITIONS AND LIGHTING.

10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER

SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF

WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC

WI-FI ACCESS POINTS.

11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,

DISCONNETS, ETC. BACK TO SOURCE

12 ALL ITEMS INDICATED TO REMAIN SHALL BE

PROTECTED DURING ALL PHASES OF

CONSTRUCTION.

13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING

LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM

PANELS THAT ARE BEING DEMOLISHED IN THIS

PHASE. THESE LOADS TO BE RE-FED FROM NEW

PANELS IN NEXT PHASE.

14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL

CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE

ALL ASSOCIATED RACEWAYS AND CONDUCTORS

BACK TO SOURCE.

15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING

DATA LOCATIONS.

16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS

PART OF THIS PROJECT SHALL HAVE RACEWAYS

REMOVED AS PART OF THE DEMOLITION SCOPE OF

WORK. DEMOLISHED DATA DEVICES ARE INDICATED

AS DASHED DEVICES AND KEYNOTED.

17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED

UNLESS OTHERWISE SPECIFIED ON THE FLOOR

PLANS. ALL EXISTING DATA DEVICE PATHWAYS

SHALL REMAIN INTACT AND BE REUSED FOR NEW

CABLE INSTALLATION.

18 REMOVE ALL EXISTING CABLES THAT ARE TO BE

REPLACED BACK TO THE PATCH PANEL.

19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR

MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO

ADDITIONAL CABLES OR EQUIPMENT IN THEM.

20 REMOVE EXISTING FIBER FROM TR BACK TO THE

MCR AND ALL FIBER TERMINATION EQUIPMENT

AFTER ALL NETWORK SERVICES HAVE BEEN

REMOVED.

21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND

PROTECT DURING THE STRUCTURED CABLING

UPGRADE.

GENERAL

SHEET NOTES

SHEET

KEYNOTES

TR LEGEND

SPECIAL PROJECT

NOTES

1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA

LOCATIONS THAT MAY BE REMOVED AS PART OF

THIS PROJECT. CONTRACTOR TO VERIFY ALL

CABLES TO BE DEMOLISHED COMPLETELY TO THE

VA PATCH PANEL.

STORAGE

2A08

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:0

A M

08-ED401

ENLARGED DEMOLITION PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING

FIXTURES DEVICES AND EQUIPMENT SHOWN

DASHED. REMOVE CONDUIT AND WIRING BACK TO

PANELBOARD OF ORIGIN OR TO FIRST ACTIVE

DEVICE THAT REMAINS.

2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK

RECEPTACLES AND WALLPLATES, CEILING SPEAKERS

AND SECURITY AND FIRE ALARM DEVICES TO

OWNER. PROTECT SALVAGED EQUIPMENT FROM

DAMAGE.

3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD

VERIFY THE EXTENT OF ELECTRICAL AND DATA

DEMOLITION WORK TO MEET THE INTENT OF THE BID

DOCUMENTS AND INCLUDE ALL COSTS IN BID.

4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT

OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR

WIRING IS INACTIVE OR NO LONGER IN USE.

5 REMOVE ALL DEVICES, RACEWAYS AND WIRING

FROM WALLS TO BE REMOVED. WHERE ACTIVE

RACEWAYS OCCUR IN WALLS TO BE REMOVED,

RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING

TO KEEP THE CIRCUIT OPERATIONAL.

6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING

WALLS AND CEILINGS ARE BEING REMOVED, WITH

ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE

ALARM DEVICES AND SYSTEM NOT INDICATED FOR

REMOVAL SHALL REMAIN ACTIVE THROUGHOUT

DEMOLITION AND CONSTRUCTION UNTIL THE NEW

SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN

ALL CLASS A FIRE ALARM INITIATING AND INDICATING

LOOPS WHERE EXISTING DEVICES ARE REMOVED.

7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,

WIRING AND CABLING WHETHER ABANDONED

PREVIOUS TO THIS PROJECT OR AS A RESULT OF

THIS PROJECT. NOT ALL ABANDONED ITEMS ARE

SHOWN ON THESE PLANS AND FIELD VERIFICATION

OF DEMOLITION SCOPE EXTENT IS REQUIRED.

8 DEVICES MARKED "RR" ARE TO BE REMOVED AND

RELOCATED PER NEW PLANS. EXTEND CIRCUITING

AS REQUIRED FOR RELOCATION.

9 REFER TO ARCHITECTURAL DRAWINGS FOR

REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND

CONTROL WIRING ASSOCIATED WITH EXISTING

MOTORIZED DOORS, PARTITIONS AND LIGHTING.

10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER

SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF

WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC

WI-FI ACCESS POINTS.

11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,

DISCONNETS, ETC. BACK TO SOURCE

12 ALL ITEMS INDICATED TO REMAIN SHALL BE

PROTECTED DURING ALL PHASES OF

CONSTRUCTION.

13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING

LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM

PANELS THAT ARE BEING DEMOLISHED IN THIS

PHASE. THESE LOADS TO BE RE-FED FROM NEW

PANELS IN NEXT PHASE.

14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL

CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE

ALL ASSOCIATED RACEWAYS AND CONDUCTORS

BACK TO SOURCE.

15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING

DATA LOCATIONS.

16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS

PART OF THIS PROJECT SHALL HAVE RACEWAYS

REMOVED AS PART OF THE DEMOLITION SCOPE OF

WORK. DEMOLISHED DATA DEVICES ARE INDICATED

AS DASHED DEVICES AND KEYNOTED.

17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED

UNLESS OTHERWISE SPECIFIED ON THE FLOOR

PLANS. ALL EXISTING DATA DEVICE PATHWAYS

SHALL REMAIN INTACT AND BE REUSED FOR NEW

CABLE INSTALLATION.

18 REMOVE ALL EXISTING CABLES THAT ARE TO BE

REPLACED BACK TO THE PATCH PANEL.

19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR

MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO

ADDITIONAL CABLES OR EQUIPMENT IN THEM.

20 REMOVE EXISTING FIBER FROM TR BACK TO THE

MCR AND ALL FIBER TERMINATION EQUIPMENT

AFTER ALL NETWORK SERVICES HAVE BEEN

REMOVED.

21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND

PROTECT DURING THE STRUCTURED CABLING

UPGRADE.

NORTH

1/4" = 1'-0"F3

ENLARGED EXISTING TR 2A02A EQUIPMENT PLAN

Ground Floor

TR # G100A - 109

1st Floor

TR # 1A14

TR # 1A24

NORTH

1/4" = 1'-0"F7

ENLARGED EXISTING STORAGE 2A08A-8 DEMOLITION PLAN

GENERAL

SHEET NOTES

0' 2' 4' 8' 16'

GRAPHIC SCALE 1/4" = 1'-0"

1'

ADDENDUM #01 2/28/2023 06/08/23

PIPE TUNNEL (TO B.06)

GA07BA

MECHANICAL (POOL EQUIPMT)

GA03A

MECHANICAL (HOT TANK)

GA04

ELECTRICAL

GA08

ELECTRICAL

GA08A

OFFICE (137,EMS SUPPLY)

GA02

TRAINING (117,DRIVERS)

GA03

CORRIDOR (TO lOCKER ENTRY)

GA01

STORAGE (GENERAL)

GA06C

STORAGE (135)

GA06B

SHOP (138)

GA05

ENTRY (138, UTILITIES)

GA07

LOCKERS (WOMEN)

GA01A

SHOP (138)

GA01CA

P

IP

E C

H A

S E

G A

B

A A

STORAGE (142,LIBRARY)

GA01CC

ELEVATOR LEVEL

BAE1

STORAGE (EQUIPMT. CLOTHING)

GA06

STORAGE (135)

GA06A

STORAGE (EQUIPMT. CLOTHING)

GA06D

LOCKERS (MEN)

GA01C

STORAGE (137)

GA01CD

CORRIDOR (TO

LOCKER ENTRY)

GA00A

TOILET/

SHOWER (MEN)

GA01CB

P

IP

E T

U N

N E

L

T O

C O

N C

O U

R S

E

G A

B

CORRIDOR (TO

ELEVATOR)

GA00

ELECTRICAL

GA08

FIRE HOSE CLOSET

GA01B

STAIR LEVEL

GAA

TOILET/SHOWER

(WOMEN)

GA01AA

"8-G-A-E-P1" "8-G-A-N-D2"

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:1

A M

08-EP100

GROUND FLOOR POWER PLAN EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/8" = 1'-0"F1

GROUND FLOOR POWER PLAN

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

GENERAL

SHEET NOTES

SHEET

KEYNOTES

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

C

W

C

C

C

C

W

W

C

C

W

C

C

W

W

GYM (WEST-COURT)

1A22A

GYM (EAST-COURT)

1A22B

GYMNASIUM (EAST & WEST COURTS)

1A22

FIRE EQUIP/HOSE

1A22C

OFFICE (117)

1A30

OFFICE (117)

1A28

POOL (117,THERAPY)

1A13A

WOMEN'S SHOWERS

1A19C

MEN'S LOCKERS

1A17A

MEN'S RESTROOM

1A17C

PIPE CHASE (138)

1A17B

ENTRY TO POOL

1A13

SAUNA (117)

1A13D

STORAGE

1A13C

WELLNESS (00)

1A11

1A11B

STAIRS

1AB STORAGE (MPC)

1A07

WAITING

IB01VESTIBULE

IB00A

OFFICE

IB02

RETAIL STORE (133)

1A01

ELEVATOR

STAIR

1AA

ELECTRICAL

1A26

CORRIDOR (TO ELEVATOR & MPC)

1A00B

STORAGE (MPC)

1A18

STAFF DINING (133)

1A02B

FIRE EQUIP/HOSE

1A02C

STORAGE (133)

1A02E

KITCHEN (133)

1A02G

W O

R K

R O

O M

3) 1A

H

PATIO #03 (MPC)

1A20.03

CORRIDOR

1A00

MEN'S RESTROOM

1A14

WOMEN'S RESTROOM

1A12

P

IP

E C

H A

S E

8) 1A

A

HAC

1A10

KITCHEN (142)

1A20A

STORAGE (142)

1A08A

STORAGE (133)

1A03

CHASE

OFFICE

IB04

OPEN OFFICE

IB06

CONF

IB08

HALL

IB00B

OFFICE

IB10

GAIT LAB

IB01

GAIT LAB

IB12

THEATER

IB14

EQUIP. HOLDING

IB14A

EXAM

IB03

RR

IB05

CLEAN LINENS

IB00D

CRASH CART

IB00E

IT

IB09

ELEC

IB11

HALL

IB00

MECH

IB13

VESTIBULE

IB00F

1A01A

ENTRY (TO REAR OF MPC)

1A08

1A06

OFFICE (133)

1A02A

MULI-PURPOSE CENTER (MPC)

1A20

1A04

DINING (133, CANTEEN)

1A02

PATIO #02 (MPC)

1A20.02

PATIO #01 (MPC)

1A20.01

VESTIBULE

(VENDING)

1A00A

STORAGE

(WELLNESS)

1A11A

OFFICE

(WELLNESS)

1A09

WAITING

(135, SHUTTLE)

1A13A

OFFICE

(133, CHIEF)

1A02AB

OFFICE

(133)

1A02AA

CLOCK ROOM

(MPC)

1A16

CORRIDOR (TO REAR

ENTRANCE)

1A00C

CORRIDOR

(TO GYM)

1A00DTEL/DATA

(142) 1A24

ENTRY (MEN'S

SHOWERS/LOCKERS)

1A17

M E

N 'S

S H

O W

E R

R O

O M

1A

A STORAGE (117,

SCUBA)

1A15ENTRY TO

SAUNA

1A13B

WOMEN'S

RESTROOM

1A19B

WOMEN'S

LOCKERS

1A19A

E N

T R

Y

W O

M E

N 'S

S H

O W

E R

S /L

O C

K E

R S

1A

HAC

(137) 1A02D

STORAGE

(VCS)

1A32

S T

A F

F L

O C

K E

R S

3) 1A

F

DIRTY

LINENS

IB00C

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:2

A M

08-EP110

FIRST FLOOR POWER PLAN EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/8" = 1'-0"F1

FIRST FLOOR POWER PLAN

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

GENERAL

SHEET NOTES

SHEET

KEYNOTES

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

T

C

C

C

C

C

C

STAIRS/

LEVEL

2AB

CORRIDOR

2A00B

STORAGE

2A08

OFFICE

2A06

TEL/DATA

2A02A

CONFERENCE

2A01

EXTINGUISHER/HOSE

2A04

CORRIDOR

2A00A

ELECTRICAL

2A02B

TOILET

2A13

TOILET

2A09

ELEVATOR

ENTRY

2A02

LOUNGE

(HR-LINKS)

2A07

2A11

STAIRS LEVEL

2AA

OFFICE

2A05

OFFICE

2A03

CORRIDOR

2A00

08-EP401

F8

W

SS-2

8-2-A-E-P2-11,13,15

8-2-A-E-P2-17

ROOF ACCESS

2AAA

"8-2-A-N-P1"

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:3

A M

08-EP120

SECOND FLOOR POWER PLAN EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

NORTH

1/8" = 1'-0"F1

SECOND FLOOR POWER PLAN

GENERAL

SHEET NOTES

SHEET

KEYNOTES

1 SPLIT CONDENSING UNIT LOCATED ON ROOF. SEE

MECHANICAL DRAWINGS FOR EXACT LOCATION.

2 PROVIDE A SEPARATE 120 VOLT, 20 AMP, 1 PHASE

CIRCUIT AND WEATHER PROOF GFCI OUTLET

MOUNTED TO SIDE OF CONDENSING UNIT.

0' 4' 8' 16' 32'

GRAPHIC SCALE 1/8" = 1'-0"

2'

T

T

"8-2-A-E-P2"

"8-2-A-N-P2"

(PG4)

(PG4) (PG4)

(PG4)

8-2-A-N-P2-1,3,5

RACK-30

8-2-A-E-P2-1,3,5

RACK-30

AC-2

8-2-A-E-P2-7,9

8-2-A-E-P2-27

8-2-A-E-P2-19

8-2-A-E-P2-21

8-2-A-E-P2-23 8-2-A-E-P2-25

(G-4)

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

SHEET TO BE VIEWED AND PRINTED IN COLOR

A u to d e s k D o c s /2

S

L C

V A

M C

E H

R M

I n fr a s tr u c tu re U p g ra d e s /B ld g

E

L E

C .r v t

/8

/2

:2

:4

A M

08-EP401

ENLARGED POWER PLANS EHRM INFRASTRUCTURE

UPGRADES

SALT LAKE CITY, UT 84148

660-21-700

BUILDING 08

08 JUN 2023 ARNOLD,

FELT

TAYLOR,

SOUTHERN

NORTH

1/4" = 1'-0"F8

ENLARGED TR 2A10-08 POWER PLAN

ID DESCRIPTION

NOMINAL SIZE

M O

U N

T

IN

G

T Y

P E

C O

L O

R T

E M

P

C R

I

D R

IV

E

R C

O N

F

IG

U R

A T

IO

N

V O

L T

A G

E

W A

T T

S

F

IN

IS

H

F

IX

T U

R E

L U

M E

N S

D

IF

F U

S E

R /L

E N

S

R E

F L

E C

T O

R

O P

T

IO

N S

N O

T E

S

MANUFACTURER (CATALOG SERIES)

L E

N G

T H

D E

P T

H

H E

IG

H

T

D

IA

M E

T E

R A

P E

R T

U R

E

OPTION 1 OPTION 2 OPTION 3

(G-4) 2X4 LED FLAT PANEL, GRID LAY-IN 48" 24" 3" - CR LED 3500K LED DRIVER

(0-10V DIMMING)

120/277 41 - 4300 - - - METALUX (24FP4735C) APPROVED EQUAL APPROVED EQUAL

(PG4) STRIPLIGHT, GENERAL 48" 4" 4" - CP LED 4000K LED DRIVER

(0-10V DIMMING)

120/277 38 CBA 5000 - - - LITHONIA

(ZL1D-L48-5000LM-FST-M

VOLT-40K-80CRI-WH-HC3

6)

ILP (SS4) WILLIAMS (75R)

DIFFUSER/LENSFINISH PROVIDE UNIT PRICES AND FIXTURE BRAND SELECTED FOR ADD/DELETE CHANGES

FOR EACH FIXTURE TYPES SHOWN WITHIN 48 BUSINESS HOURS OF THE BID DATE.

FAILURE TO COMPLY WITH THIS REQUIREMENT MAY DISQUALIFY THE PRODUCTS

AND EMPOWER THE ENGINEER TO DETERMINE FAIR VALUE FOR FIXTURE AND

INSTALLATION CHANGES, WITHOUT FURTHER INPUT FROM THE CONTRACTOR OR

INSTALLER.

CONTRACTOR ALLOWANCE PRICES ARE ACCURATE WHEN THIS JOB WAS

SPECIFIED, CONTRACTOR AND ELECTRICAL DISTRIBUTOR SHALL VERIFY THIS

ALLOWANCE AND REPORT ANY PROBLEMS TO THE ENGINEER BEFORE THE BID.

ALLOWANCE PRICE MAY OR MAY NOT INCLUDE LAMP(S) OR FREIGHT AS NOTED,

AND DO NOT INCLUDE ANY TAXES.

SUBSTITUTIONS AND/OR EQUAL FIXTURES MUST RECEIVE APPROVAL PRIOR TO

BIDDING, THEY MUST BE SUBMITTED TO THE ENGINEER NO LESS THAN 2 WEEKS

PRIOR TO BID OPENING.

SAMPLES MUST BE PROVIDED FOR ANY AND ALL FIXTURES UPON A/E REQUEST

PRIOR TO RELEASING FIXTURES.

ALL FIXTURES SHALL BE LISTED AND APPROVED FOR THEIR INTENDED USE AND

LOCATION.

VERIFY THE PROPER MOUNTING KITS OR ACCESSORIES TO FACILITATE

INSTALLATION AS SHOWN AT EACH LOCATION ON THE DRAWINGS.

COMPLY WITH THE "INTERIOR LIGHTING" SECTION OF THE SPECIFICATIONS.

REFER TO SPECIFICATIONS FOR IMPORTANT TECHNICAL REQUIREMENTS FOR

LIGHTING FIXTURES, DRIVERS, AND LAMPS.

ALL LIGHT FIXTURES TO BE EITHER "DLC" OR "LIGHTING FACTS" LISTED OR TO BE

APPROVED BY ARCHITECT/ENGINEER AND OWNER.

LUMINAIRE OPTIONSMOUNTING REFLECTOR 1.

2.

3.

4.

5.

6.

7.

8.

9.

DIAMETER

H E

IG

H

T

LENGTH DEPTH

H E

IG

H

T

LENGTH

DEPTH

HEIGHT

NOTES

INTERIOR LIGHTING FIXTURE SCHEDULE

ABBREVIATIONS GENERAL NOTES

ARHR - AIR RETURN AND HEAT REJECTION

DL - DAMP LOCATION

EQC - EARTHQUAKE CLIPS

F - FUSING

HLD - HINGED AND LATCHED DOOR

HS - HOUSE SIDE SHIELD

PS - PHOTOCELL SWITCH

QRS - QUARTZ RESTRIKE

ST - STATIC

WG - WIRE GUARD

WL - WET LOCATION

B - BASE

C - CEILING

F - FLANGE

G - GRID

P - PENDANT

PL POLE

R - RECESSED

S - SURFACE

W - WALL

MW - MATTE WHITE

BL - BLACK

SL - SILVER

GL - GOLD

CL - CLEAR

PW - PAINTED WHITE

EA - EXTRUDED ALUMINUM

S - STEEL

GS - GALVANIZED STEEL

C - CAST

CBA - COLOR BY ARCHITECT

SCBA - STANDARD COLOR BY

ARCHITECT

CCA - CUSTOM COLOR BY

ARCHITECT

FS

209D

- MEETS FEDERAL

STANDARD 209D

TP - THERMALLY

PROTECTED

FL - FLUSH

R - REGRESS

M - MITERED

OP - NONE/OPEN

SP - SPECULAR

SS - SEMI-SPECULAR

D - DIFFUSE (WHITE ENAMEL)

SC - SPECULAR (COLORED)

PR - PRISMATIC

FDR - FULL DEPTH REFLECTOR

DS - DIFFUSE (SEMI SPECULAR) SILVER

LI - LOW IRIDESCENT

IR - IRIDESCENT

SL - SILVER

GL - GOLD

CA - CLEAR ALZAK

#A - ACRYLIC #THICK

#OA - ACRYLIC #THICK (OPAL)

GC - GLASS (CLEAR)

GO - GLASS (OPAL)

GF - GLASS (FROSTED)

SGL - SOFT GLOW LENS

HPL - HIGH PERFORMANCE LENS

DO - DROP OPAL

CGL - CONVEX GLASS LENS

S - SATIN LENS

1 PROVIDE AN OVERHEAD POWER DROP CORD WITH

A 30 AMP 208 VOLT THREE-PHASE TWISTED LOCK

RECEPTACLE (L21-30R); 8.5 FT AFF (WYE(5-WIRE))

COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR. SEE SHEET

EE002, EE501, AND PANEL SCHEDULE. PROVIDE

RACK MOUNTED POWER DIST. (2RU), RACK

MOUNTED UPS (6RU) AND PDU PER TELECOM

EQUIPMENT RACK ELEVATIONS ON ET500'S.

2 SECONDARY BONDING BUSBAR (SBB). SEE ET

SHEETS FOR PLACEMENT AND GROUNDING DETAIL.

CONTRACTOR TO PROVIDE A SEPARATELY

DERIVED #3/0 GROUND FROM BUILDING GROUND

TO TR BUSBARS. CONTRACTOR TO VERIFY

BUSBAR’S RESISTANCE IS UNDER 4 OHMS

MEASURED BY THE FOUR POINT

FALL-OF-POTENTIAL METHOD PER IEEE 81.

3 PROVIDE A 100 AMP, THREE-PHASE, FOUR WIRE,

208 VOLT SERVICE PANEL. PANEL SHALL BE

EQUIPPED WITH A POWER METER.

4 PROVIDE THERMAL SWITCH FOR SPLIT SYSTEM.

THERMAL SWITCH TO BE MOUNTED ON SIDE OF

UNIT.

5 LIGHTING CONTROL AND POWER TO BE

CONNECTED TO EXISTING LIGHT CIRCUIT FOR THE

SPACE.

1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.

2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,

GEAR, CABLE, CONDUCTORS, TERMINATIONS,

OVERCURRENT PROTECTION DEVICES, AND HEAD

END EQUIPMENT AS PART OF THIS PROJECT.

3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE

VOLTAGE AS PART OF THIS PROJECT. PROVIDE

LINE VOLTAGE REQUIRED TO ALL SYSTEMS

PROVIDED AS PART OF THIS PROJECT.

COORDINATE WITH ALL OTHER DISCIPLINES AND

DRAWINGS.

4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,

FLOORS, AND CEILING UNLESS OTHERWISE

NOTED. INSTANCES WHERE EXPOSED OR

SURFACE MOUNTED RACEWAYS IS REQUIRED A

ROUTING SKETCH SHALL BE PROVIDED TO

ARCHITECT AND ENGINEER. RACEWAY TYPE

SHALL BE SELECTED BY ENGINEER. FINISH OF

RACEWAY SHALL BE SELECTED BY ARCHITECT.

5 PROVIDE A NEW DEVICE AND TRIM PLATE IN

EXISTING DEVICE LOCATION. THE DEVICE SHALL

MATCH EXISTING TYPE OR AS SHOWN WHICHEVER

IS MORE STRINGENT. PROVIDE NEW RACEWAYS

AND CONDUCTORS ONLY AS REQUIRED.

6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING

PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY

PANELBOARD TYPE AND BREAKER TYPE.

7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN

IS APPROXIMATE. COORDINATE EXACT LOCATIONS

OF MECHANICAL EQUIPMENT WITH MECHANICAL

DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 18.6 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: 1.6 kVA @ 100% = 1.6 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 57

LIGHTING & CONTINUOUS LOADS: 0.2 kVA @ 125% = 0.2 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 20

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 57 55 48 AVERAGE CONNECTED AMPS PER PHASE = 53

TOTALS: CONNECTED kVA PER PHASE 7 7 6 CONNECTED TOTAL kVA = 19

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 0.2 0.0 0.0 LIGHTING... 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 20

17 20 1 0.0 0.0 0.2 CO 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 18

15 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 16

13 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 14

11 30 3 0.0 5.6 0.0 PWR: SS-2 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 12

9 -- -- -- -- -- -- -- 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 10

7 15 2 0.0 1.7 0.0 PWR: AC-2 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 8

5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6

3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4

1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2

NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO

CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT

ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0

120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB SURFACE TELECOMMUNICATIONS...

VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:

PANEL: "8-2-A-E-P2"

BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI

ALL OTHER LOADS @ 100% : 10.0 kVA -

MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH

LARGEST MOTOR CALCULATED @ 125% PER NEC

RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 28

LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 10

NEC DIVERSIFIED LOAD CALCULATIONS

CONNECTED AMPS PER PHASE 28 28 28 AVERAGE CONNECTED AMPS PER PHASE = 28

TOTALS: CONNECTED kVA PER PHASE 3 3 3 CONNECTED TOTAL kVA = 10

29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30

27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28

25 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 26

23 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 24

21 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 22

19 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1…