This document contains details of a federal contract opportunity for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0041 for EHRM Infrastructure Upgrades Construction services at the Salt Lake City VAMC. The project, numbered 660-21-700, involves upgrades to infrastructure at the Salt Lake City VA Medical Center. An attachment provides drawings related to the project with a file size of 14MB. Proposals are due by the date listed in the solicitation document. The opportunity is for construction services and the selected contractor will be expected to complete the infrastructure upgrade project at the Salt Lake City VAMC.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
TR
2 HR. FIRE BARRIER
1 HR. FIRE BARRIER
SMOKE BARRIER
FIRE ALARM ZONE
CORRIDORS
AREA OF CONSTRUCTION
EXISTING TELECOMMUNICATION SPACE
TR TELECOMMUNICATION ROOM
GENERAL FIRE PROTECTION NOTES
1. THE SCOPE OF WORK FOR THIS PROJECT INCLUDES THE MODIFICATION OF THE EXISTING
FIRE SPRINKLER SYSTEMS IN THE REMODEL AREAS TO MEET VA GUIDELINES.
2. AREAS HIGHLIGHTED ON PLANS INDICATE PROJECT AREAS TO BE ADDRESSED. SCOPE OF
WORK IN AREAS OUTSIDE THE HIGHLIGHTED SPACES IDENTIFIED IS LIMITED TO WORK
REQUIRED TO FACILITATE CONNECTION OF NEW PIPING TO EXISTING SYSTEMS.
3. REVIEW PLANS FOR LOCATION OF ELECTRICAL EQUIPMENT AND COMPUTER SERVERS.
MODIFY PIPING TO AVOID RUNNING OVER THE TOP OF EQUIPMENT. IF EXISTING SPRINKLERS
ARE TO BE REMOVED, DUE TO CEILING WORK OR OTHER REMODEL WORK, REPLACE WITH NEW
QUICK RESPONSE TYPE SPRINKLERS UNLESS AS MODIFIED BELOW.
4. HALLWAYS, CORRIDORS, OFFICES, ETC. AS IDENTIFIED IN NFPA 13 AND VA FIRE PROTECTION
DESIGN GUIDE AS LIGHT HAZARD; SPACE SPRINKLERS FOR LIGHT HAZARD OCCUPANCY (225
SQ.FT. MAX PER SPRINKLER). MATCH SPRINKLER RESPONSE TO EXISTING SPRINKLERS. IF
ENTIRE SPACE IS MODIFIED REPLACE WITH QUICK RESPONSE TYPE SPRINKLERS.
5. TR'S, STORAGE ROOMS, ETC. AS IDENTIFIED IN NFPA 13 AND VA FIRE PROTECTION DESIGN
GUIDE AS ORDINARY HAZARD GROUP I OCCUPANCY (130 SQ.FT. MAX PER SPRINKLER). MATCH
SPRINKLER RESPONSE TO EXISTING SPRINKLERS. IF ENTIRE SPACE IS MODIFIED REPLACE
WITH QUICK RESPONSE TYPE SPRINKLERS.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
A
R C
H .r v t
/1
/2
:0
:0
P M
08-FX120
OVERALL SECOND FLOOR FIRE
SPRINKLER PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 DUBOIS ROOKER
06/08/23
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
NORTH
1/8" = 1'-0"1
OVERALL SECOND FLOOR FIRE SPRINKLER PLAN
FIRE PROTECTION LEGEND
Revisions: Date:
06/02/2023
2A00
2A04
2A02A
2A02B
2A02
2A00B
2A11
2A092A13
2A08
2AB
2A06
2AA
2AAA
2A00A
2A01
2A03 2A05
2A07
CORRIDOR
EXTINGUISHER/HOSE
TEL/DATA
ELECTRICAL
ENTRY
CORRIDOR
TOILETTOILET
STORAGE
STAIRS LEVEL
OFFICE
STAIRS LEVEL
CORRIDOR
CONFERENCE
OFFICE
OFFICE
LOUNGE (HR-LINKS)
ROOF
ACCESS
ELEVATOR
T
08-MH401
F3
08-MH401
F6
MECHANICAL GENERAL NOTES:
1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN
PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.
COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.
2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.
COORDINATE LOCATION WITH OWNER.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,
AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER
INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL
HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE
ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER
OPERATION OF ACCESSORY.
5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING
STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING
AND/OR COMMUNICATION TO BMS.
6. MECHANICAL PIPING SCHEDULE:
1. REFRIGERANT PIPING = ACR TYPE L - BRAZED
7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.
PLUMBING GENERAL NOTES:
1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING
WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR
PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY
HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
M
E C
H .r v t
/1
/2
:0
:0
P M
08-MH111
SECOND FLOOR MECHANICAL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 RHB ARA AJB
GENERAL SHEET NOTES
NORTH
1/8" = 1'-0"F1
SECOND FLOOR MECHANICAL PLAN
6-8-23
S
S
SS-2MH401 1
MECHANICAL GENERAL NOTES:
1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN
PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.
COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.
2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.
COORDINATE LOCATION WITH OWNER.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,
AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER
INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL
HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE
ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER
OPERATION OF ACCESSORY.
5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING
STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING
AND/OR COMMUNICATION TO BMS.
6. MECHANICAL PIPING SCHEDULE:
1. REFRIGERANT PIPING = ACR TYPE L - BRAZED
7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.
PLUMBING GENERAL NOTES:
1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING
WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR
PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY
HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
M
E C
H .r v t
/1
/2
:0
:0
P M
08-MH113
OVERALL ROOF MECHANICAL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 RHB ARA AJB
NORTH
1/8" = 1'-0"1
OVERALL ROOF MECHANICAL PLAN
GENERAL SHEET NOTES
SHEET KEYNOTES
1 CONTRACTOR TO FIELD VERIFY LOCATION OF ROOFTOP UNIT WITH EXISTING
CONDITIONS. UNIT TO BE 10' AWAY FROM ROOFS EDGE. MAINTAIN
MANUFACTURER'S SERVICE CLEARANCE.
T
AC-2
RS/RL
DCW
CD
STORAGE
2A08-08
MECHANICAL GENERAL NOTES:
1. THIS PROJECT WILL REQUIRE AFTER HOURS AND WEEKEND WORK TO RUN
PIPING/DUCTWORK OR MODIFY SYSTEMS IN OR AFFECTING OCCUPIED SPACES.
COORDINATE ALL SHUTDOWNS 72 HOURS IN ADVANCE WITH OWNER.
2. PROVIDE TEMPORARY NEGATIVE PRESSURE UNIT DURING CONSTRUCTION.
COORDINATE LOCATION WITH OWNER.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
4. INSTALL INSULATION OVER FITTINGS, VALVES, STRAINERS, FLANGES, UNIONS,
AND OTHER SPECIALTIES WITH CONTINUOUS THERMAL AND VAPOR-RETARDER
INTEGRITY. STRAINERS, CONTROL VALVES, AND BALANCING VALVES SHALL
HAVE REMOVABLE INSULATION WITH LABEL INDICATED WHAT TYPE OF PIPE
ACCESSORY IS BELOW INSULATION. INSULATION SHALL NOT IMPEDE PROPER
OPERATION OF ACCESSORY.
5. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING
STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING
AND/OR COMMUNICATION TO BMS.
6. MECHANICAL PIPING SCHEDULE:
1. REFRIGERANT PIPING = ACR TYPE L - BRAZED
7. PROVIDE WALK PADS TO NEW ROOF EQUIPMENT.
PLUMBING GENERAL NOTES:
1. THE CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING
WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
3. WHERE JURISDICTION REQUIRES, THE CONTRACTOR IS RESPONSIBLE FOR
PROVIDING SEISMIC RESTRAINT. PROVIDE DESIGN DRAWINGS TO AUTHORITY
HAVING JURISDICTION AND MECHANICAL ENGINEER FOR REVIEW.
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
M
E C
H .r v t
/1
/2
:0
:0
P M
08-MH401
ENLARGED MECHANICAL PLANS EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 RHB ARA AJB
GENERAL SHEET NOTES
SHEET KEYNOTES
NORTH
1/2" = 1'-0"F6
SECOND FLOOR ENLARGED TR - 2A10-08 NEW MECHANICAL PLAN
NORTH
1/2" = 1'-0"F3
SECOND FLOOR ENLARGED STORAGE - 2A08-08 MECHANICAL DEMOLITION PLAN
1 ROUTE REFRIGERANT LINES TO CONDENSING UNIT LOCATED ON ROOF. PIPE
SIZE BY MANUFACTURER. REFRIGERANT LINE REPRESENTS SUPPLY AND
LIQUID LINES.
2 ROUTE AND CONNECT WATER LINE TO NEAREST DOMESTIC WATER LINE IN
CORRIDOR. ASSUMED DISTANCE: 30'. SEE ENLARGED PLAN FOR SIZING.
3 ROUTE CONDENSATE LINE TO NEAREST SINK OR LAVATORY. TIE INTO
TAILPIECE. ASSUMED DISTANCE: 30'. SEE ENLARGED PLAN FOR SIZING.
4 COORDINATE ALL THERMOSTAT LOCATIONS WITH OWNER AND LATEST
FURNITURE PLAN. FAILURE TO DO SO MAY RESULT IN RELOCATING
THERMOSTAT AT NO ADDITIONAL COST TO THE OWNER.
UPC
C
PIPE TUNNEL (TO B.06)
GA07BA
MECHANICAL (POOL EQUIPMT)
GA03A
MECHANICAL (HOT TANK)
GA04
ELECTRICAL
GA08
ELECTRICAL
GA08A
OFFICE (137,EMS SUPPLY)
GA02
TRAINING (117,DRIVERS)
GA03
CORRIDOR (TO lOCKER ENTRY)
GA01
STORAGE (GENERAL)
GA06C
STORAGE (135)
GA06B
SHOP (138)
GA05
ENTRY (138, UTILITIES)
GA07
ELECTRICAL
GA08
LOCKERS (WOMEN)
GA01A
SHOP (138)
GA01CA
P
IP
E C
H A
S E
G A
B
A A
STORAGE (142,LIBRARY)
GA01CC
ELEVATOR LEVEL
BAE1
STORAGE (EQUIPMT. CLOTHING)
GA06
FIRE HOSE CLOSET
GA01B
STAIR LEVEL
GAA
STORAGE (135)
GA06A
STORAGE (EQUIPMT. CLOTHING)
GA06D
LOCKERS (MEN)
GA01C
STORAGE (137)
GA01CD
CORRIDOR (TO
LOCKER ENTRY)
GA00A
TOILET/SHOWER
(WOMEN)
GA01AA
TOILET/
SHOWER (MEN)
GA01CB
P
IP
E T
U N
N E
L
T O
C O
N C
O U
R S
E
G A
B
C O
R R
ID
O
R
T O
E L
E V
A T
O R
G
A
+48"
+48"
+72"
+72"
EXISTING TR LOCATION TO BE MOVED
EXISTING TR TO REMAIN
NEW TR LOCATION
SEPARATION LINE INDICATES
TERMINATION OF DATA CABLES TO
SPECIFIED TR LOCATION
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:3
A M
08-ED100
GROUND FLOOR ELECTRICAL
DEMOLITION PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/8" = 1'-0"F1
GROUND FLOOR ELECTRICAL DEMOLITION PLAN
1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING
FIXTURES DEVICES AND EQUIPMENT SHOWN
DASHED. REMOVE CONDUIT AND WIRING BACK TO
PANELBOARD OF ORIGIN OR TO FIRST ACTIVE
DEVICE THAT REMAINS.
2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK
RECEPTACLES AND WALLPLATES, CEILING SPEAKERS
AND SECURITY AND FIRE ALARM DEVICES TO
OWNER. PROTECT SALVAGED EQUIPMENT FROM
DAMAGE.
3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD
VERIFY THE EXTENT OF ELECTRICAL AND DATA
DEMOLITION WORK TO MEET THE INTENT OF THE BID
DOCUMENTS AND INCLUDE ALL COSTS IN BID.
4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT
OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR
WIRING IS INACTIVE OR NO LONGER IN USE.
5 REMOVE ALL DEVICES, RACEWAYS AND WIRING
FROM WALLS TO BE REMOVED. WHERE ACTIVE
RACEWAYS OCCUR IN WALLS TO BE REMOVED,
RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING
TO KEEP THE CIRCUIT OPERATIONAL.
6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING
WALLS AND CEILINGS ARE BEING REMOVED, WITH
ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE
ALARM DEVICES AND SYSTEM NOT INDICATED FOR
REMOVAL SHALL REMAIN ACTIVE THROUGHOUT
DEMOLITION AND CONSTRUCTION UNTIL THE NEW
SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN
ALL CLASS A FIRE ALARM INITIATING AND INDICATING
LOOPS WHERE EXISTING DEVICES ARE REMOVED.
7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,
WIRING AND CABLING WHETHER ABANDONED
PREVIOUS TO THIS PROJECT OR AS A RESULT OF
THIS PROJECT. NOT ALL ABANDONED ITEMS ARE
SHOWN ON THESE PLANS AND FIELD VERIFICATION
OF DEMOLITION SCOPE EXTENT IS REQUIRED.
8 DEVICES MARKED "RR" ARE TO BE REMOVED AND
RELOCATED PER NEW PLANS. EXTEND CIRCUITING
AS REQUIRED FOR RELOCATION.
9 REFER TO ARCHITECTURAL DRAWINGS FOR
REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND
CONTROL WIRING ASSOCIATED WITH EXISTING
MOTORIZED DOORS, PARTITIONS AND LIGHTING.
10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER
SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF
WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC
WI-FI ACCESS POINTS.
11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,
DISCONNETS, ETC. BACK TO SOURCE
12 ALL ITEMS INDICATED TO REMAIN SHALL BE
PROTECTED DURING ALL PHASES OF
CONSTRUCTION.
13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING
LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM
PANELS THAT ARE BEING DEMOLISHED IN THIS
PHASE. THESE LOADS TO BE RE-FED FROM NEW
PANELS IN NEXT PHASE.
14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL
CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE
ALL ASSOCIATED RACEWAYS AND CONDUCTORS
BACK TO SOURCE.
15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING
DATA LOCATIONS.
16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS
PART OF THIS PROJECT SHALL HAVE RACEWAYS
REMOVED AS PART OF THE DEMOLITION SCOPE OF
WORK. DEMOLISHED DATA DEVICES ARE INDICATED
AS DASHED DEVICES AND KEYNOTED.
17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED
UNLESS OTHERWISE SPECIFIED ON THE FLOOR
PLANS. ALL EXISTING DATA DEVICE PATHWAYS
SHALL REMAIN INTACT AND BE REUSED FOR NEW
CABLE INSTALLATION.
18 REMOVE ALL EXISTING CABLES THAT ARE TO BE
REPLACED BACK TO THE PATCH PANEL.
19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR
MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO
ADDITIONAL CABLES OR EQUIPMENT IN THEM.
20 REMOVE EXISTING FIBER FROM TR BACK TO THE
MCR AND ALL FIBER TERMINATION EQUIPMENT
AFTER ALL NETWORK SERVICES HAVE BEEN
REMOVED.
21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND
PROTECT DURING THE STRUCTURED CABLING
UPGRADE.
GENERAL
SHEET NOTES
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
SHEET
KEYNOTES
TR LEGEND
SPECIAL PROJECT
NOTES
1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA
LOCATIONS THAT MAY BE REMOVED AS PART OF
THIS PROJECT. CONTRACTOR TO VERIFY ALL
CABLES TO BE DEMOLISHED COMPLETELY TO THE
VA PATCH PANEL.
06/08/23
UP
C
W
C
C
C
C
W
W
C
C
W
C
C
W
W
GYM (WEST-COURT)
1A22A
GYM (EAST-COURT)
1A22B
GYMNASIUM (EAST & WEST COURTS)
1A22
FIRE EQUIP/HOSE
1A22C
OFFICE (117)
1A30
OFFICE (117)
1A28
POOL (117,THERAPY)
1A13A
WOMEN'S SHOWERS
1A19C
MEN'S LOCKERS
1A17A
MEN'S RESTROOM
1A17C
PIPE CHASE (138)
1A17B
ENTRY TO POOL
1A13
SAUNA (117)
1A13D
STORAGE
1A13C
WELLNESS (00)
1A11
1A11B
STAIRS
1AB STORAGE (MPC)
1A07
WAITING
IB01VESTIBULE
IB00A
OFFICE
IB02
RETAIL STORE (133)
1A01
ELEVATOR
STAIR
1AA
ELECTRICAL
1A26
CORRIDOR (TO ELEVATOR & MPC)
1A00B
STORAGE (MPC)
1A18
STAFF DINING (133)
1A02B
FIRE EQUIP/HOSE
1A02C
STORAGE (133)
1A02E
KITCHEN (133)
1A02G
W O
R K
R O
O M
3) 1A
H
PATIO #03 (MPC)
1A20.03
CORRIDOR
1A00
MEN'S RESTROOM
1A14
WOMEN'S RESTROOM
1A12
P
IP
E C
H A
S E
8) 1A
A
HAC
1A10
KITCHEN (142)
1A20A
STORAGE (142)
1A08A
STORAGE (133)
1A03
CHASE
OFFICE
IB04
OPEN OFFICE
IB06
CONF
IB08
HALL
IB00B
OFFICE
IB10
GAIT LAB
IB01
GAIT LAB
IB12
THEATER
IB14
EQUIP. HOLDING
IB14A
EXAM
IB03
RR
IB05
CLEAN LINENS
IB00D
CRASH CART
IB00E
IT
IB09
ELEC
IB11
HALL
IB00
MECH
IB13
VESTIBULE
IB00F
1A01A
ENTRY (TO REAR OF MPC)
1A08
1A06
OFFICE (133)
1A02A
MULI-PURPOSE CENTER (MPC)
1A20
1A04
DINING (133, CANTEEN)
1A02
PATIO #02 (MPC)
1A20.02
PATIO #01 (MPC)
1A20.01
VESTIBULE
(VENDING)
1A00A
STORAGE
(WELLNESS)
1A11A
OFFICE
(WELLNESS)
1A09
WAITING
(135, SHUTTLE)
1A13A
OFFICE
(133, CHIEF)
1A02AB
OFFICE
(133)
1A02AA
CLOCK ROOM
(MPC)
1A16
CORRIDOR (TO REAR
ENTRANCE)
1A00C
CORRIDOR
(TO GYM)
1A00DTEL/DATA
(142) 1A24
ENTRY (MEN'S
SHOWERS/LOCKERS)
1A17
M E
N 'S
S H
O W
E R
R O
O M
1A
A STORAGE (117,
SCUBA)
1A15ENTRY TO
SAUNA
1A13B
WOMEN'S
RESTROOM
1A19B
WOMEN'S
LOCKERS
1A19A
E N
T R
Y
W O
M E
N 'S
S H
O W
E R
S /L
O C
K E
R S
1A
HAC
(137) 1A02D
STORAGE
(VCS)
1A32
S T
A F
F L
O C
K E
R S
3) 1A
F
+72"
+48"
+48"
F
+84"
+84" +84" +84"
+144"
+144" +144"
+144"+144"
+144"
+144"
+96"
+96"
+96"
+96"
+96"
+144"
+144"+144"+144"+144"
+48"
+48"
+48"
+48"
+48"
KP
+48"
DIRTY
LINENS
IB00C
EXISTING TR LOCATION TO BE MOVED
EXISTING TR TO REMAIN
NEW TR LOCATION
SEPARATION LINE INDICATES
TERMINATION OF DATA CABLES TO
SPECIFIED TR LOCATION
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:4
A M
08-ED110
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/8" = 1'-0"F1
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING
FIXTURES DEVICES AND EQUIPMENT SHOWN
DASHED. REMOVE CONDUIT AND WIRING BACK TO
PANELBOARD OF ORIGIN OR TO FIRST ACTIVE
DEVICE THAT REMAINS.
2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK
RECEPTACLES AND WALLPLATES, CEILING SPEAKERS
AND SECURITY AND FIRE ALARM DEVICES TO
OWNER. PROTECT SALVAGED EQUIPMENT FROM
DAMAGE.
3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD
VERIFY THE EXTENT OF ELECTRICAL AND DATA
DEMOLITION WORK TO MEET THE INTENT OF THE BID
DOCUMENTS AND INCLUDE ALL COSTS IN BID.
4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT
OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR
WIRING IS INACTIVE OR NO LONGER IN USE.
5 REMOVE ALL DEVICES, RACEWAYS AND WIRING
FROM WALLS TO BE REMOVED. WHERE ACTIVE
RACEWAYS OCCUR IN WALLS TO BE REMOVED,
RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING
TO KEEP THE CIRCUIT OPERATIONAL.
6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING
WALLS AND CEILINGS ARE BEING REMOVED, WITH
ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE
ALARM DEVICES AND SYSTEM NOT INDICATED FOR
REMOVAL SHALL REMAIN ACTIVE THROUGHOUT
DEMOLITION AND CONSTRUCTION UNTIL THE NEW
SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN
ALL CLASS A FIRE ALARM INITIATING AND INDICATING
LOOPS WHERE EXISTING DEVICES ARE REMOVED.
7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,
WIRING AND CABLING WHETHER ABANDONED
PREVIOUS TO THIS PROJECT OR AS A RESULT OF
THIS PROJECT. NOT ALL ABANDONED ITEMS ARE
SHOWN ON THESE PLANS AND FIELD VERIFICATION
OF DEMOLITION SCOPE EXTENT IS REQUIRED.
8 DEVICES MARKED "RR" ARE TO BE REMOVED AND
RELOCATED PER NEW PLANS. EXTEND CIRCUITING
AS REQUIRED FOR RELOCATION.
9 REFER TO ARCHITECTURAL DRAWINGS FOR
REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND
CONTROL WIRING ASSOCIATED WITH EXISTING
MOTORIZED DOORS, PARTITIONS AND LIGHTING.
10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER
SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF
WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC
WI-FI ACCESS POINTS.
11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,
DISCONNETS, ETC. BACK TO SOURCE
12 ALL ITEMS INDICATED TO REMAIN SHALL BE
PROTECTED DURING ALL PHASES OF
CONSTRUCTION.
13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING
LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM
PANELS THAT ARE BEING DEMOLISHED IN THIS
PHASE. THESE LOADS TO BE RE-FED FROM NEW
PANELS IN NEXT PHASE.
14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL
CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE
ALL ASSOCIATED RACEWAYS AND CONDUCTORS
BACK TO SOURCE.
15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING
DATA LOCATIONS.
16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS
PART OF THIS PROJECT SHALL HAVE RACEWAYS
REMOVED AS PART OF THE DEMOLITION SCOPE OF
WORK. DEMOLISHED DATA DEVICES ARE INDICATED
AS DASHED DEVICES AND KEYNOTED.
17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED
UNLESS OTHERWISE SPECIFIED ON THE FLOOR
PLANS. ALL EXISTING DATA DEVICE PATHWAYS
SHALL REMAIN INTACT AND BE REUSED FOR NEW
CABLE INSTALLATION.
18 REMOVE ALL EXISTING CABLES THAT ARE TO BE
REPLACED BACK TO THE PATCH PANEL.
19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR
MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO
ADDITIONAL CABLES OR EQUIPMENT IN THEM.
20 REMOVE EXISTING FIBER FROM TR BACK TO THE
MCR AND ALL FIBER TERMINATION EQUIPMENT
AFTER ALL NETWORK SERVICES HAVE BEEN
REMOVED.
21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND
PROTECT DURING THE STRUCTURED CABLING
UPGRADE.
GENERAL
SHEET NOTES
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
SHEET
KEYNOTES
TR LEGEND
SPECIAL PROJECT
NOTES
1 JBOX THAT FEEDS MULTIPLE STATIONS. STATION
COUNT UNKNOWN.
1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA
LOCATIONS THAT MAY BE REMOVED AS PART OF
THIS PROJECT. CONTRACTOR TO VERIFY ALL
CABLES TO BE DEMOLISHED COMPLETELY TO THE
VA PATCH PANEL.
C
C
C
C
C
C
STAIRS/
LEVEL
2AB
C O
R R
ID
O
R
2A
B
STORAGE
2A08
OFFICE
2A06
TEL/DATA
2A02A
CONFERENCE
2A01
EXTINGUISHER/HOSE
2A04
CORRIDOR
2A00A
ELECTRICAL
2A02B
TOILET
2A13
TOILET
2A09
ELEVATOR
ENTRY
2A02
LOUNGE
(HR-LINKS)
2A07
2A11
STAIRS LEVEL
2AA
OFFICE
2A05
OFFICE
2A03
CORRIDOR
2A00
08-ED401
F3
+48"
08-ED401
F7 ROOF ACCESS
2AAA
EXISTING TR LOCATION TO BE MOVED
EXISTING TR TO REMAIN
NEW TR LOCATION
SEPARATION LINE INDICATES
TERMINATION OF DATA CABLES TO
SPECIFIED TR LOCATION
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:5
A M
08-ED120
SECOND FLOOR ELECTRICAL
DEMOLITION PLAN
EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/8" = 1'-0"F1
SECOND FLOOR ELECTRICAL DEMOLITION PLAN 0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING
FIXTURES DEVICES AND EQUIPMENT SHOWN
DASHED. REMOVE CONDUIT AND WIRING BACK TO
PANELBOARD OF ORIGIN OR TO FIRST ACTIVE
DEVICE THAT REMAINS.
2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK
RECEPTACLES AND WALLPLATES, CEILING SPEAKERS
AND SECURITY AND FIRE ALARM DEVICES TO
OWNER. PROTECT SALVAGED EQUIPMENT FROM
DAMAGE.
3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD
VERIFY THE EXTENT OF ELECTRICAL AND DATA
DEMOLITION WORK TO MEET THE INTENT OF THE BID
DOCUMENTS AND INCLUDE ALL COSTS IN BID.
4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT
OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR
WIRING IS INACTIVE OR NO LONGER IN USE.
5 REMOVE ALL DEVICES, RACEWAYS AND WIRING
FROM WALLS TO BE REMOVED. WHERE ACTIVE
RACEWAYS OCCUR IN WALLS TO BE REMOVED,
RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING
TO KEEP THE CIRCUIT OPERATIONAL.
6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING
WALLS AND CEILINGS ARE BEING REMOVED, WITH
ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE
ALARM DEVICES AND SYSTEM NOT INDICATED FOR
REMOVAL SHALL REMAIN ACTIVE THROUGHOUT
DEMOLITION AND CONSTRUCTION UNTIL THE NEW
SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN
ALL CLASS A FIRE ALARM INITIATING AND INDICATING
LOOPS WHERE EXISTING DEVICES ARE REMOVED.
7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,
WIRING AND CABLING WHETHER ABANDONED
PREVIOUS TO THIS PROJECT OR AS A RESULT OF
THIS PROJECT. NOT ALL ABANDONED ITEMS ARE
SHOWN ON THESE PLANS AND FIELD VERIFICATION
OF DEMOLITION SCOPE EXTENT IS REQUIRED.
8 DEVICES MARKED "RR" ARE TO BE REMOVED AND
RELOCATED PER NEW PLANS. EXTEND CIRCUITING
AS REQUIRED FOR RELOCATION.
9 REFER TO ARCHITECTURAL DRAWINGS FOR
REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND
CONTROL WIRING ASSOCIATED WITH EXISTING
MOTORIZED DOORS, PARTITIONS AND LIGHTING.
10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER
SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF
WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC
WI-FI ACCESS POINTS.
11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,
DISCONNETS, ETC. BACK TO SOURCE
12 ALL ITEMS INDICATED TO REMAIN SHALL BE
PROTECTED DURING ALL PHASES OF
CONSTRUCTION.
13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING
LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM
PANELS THAT ARE BEING DEMOLISHED IN THIS
PHASE. THESE LOADS TO BE RE-FED FROM NEW
PANELS IN NEXT PHASE.
14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL
CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE
ALL ASSOCIATED RACEWAYS AND CONDUCTORS
BACK TO SOURCE.
15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING
DATA LOCATIONS.
16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS
PART OF THIS PROJECT SHALL HAVE RACEWAYS
REMOVED AS PART OF THE DEMOLITION SCOPE OF
WORK. DEMOLISHED DATA DEVICES ARE INDICATED
AS DASHED DEVICES AND KEYNOTED.
17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED
UNLESS OTHERWISE SPECIFIED ON THE FLOOR
PLANS. ALL EXISTING DATA DEVICE PATHWAYS
SHALL REMAIN INTACT AND BE REUSED FOR NEW
CABLE INSTALLATION.
18 REMOVE ALL EXISTING CABLES THAT ARE TO BE
REPLACED BACK TO THE PATCH PANEL.
19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR
MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO
ADDITIONAL CABLES OR EQUIPMENT IN THEM.
20 REMOVE EXISTING FIBER FROM TR BACK TO THE
MCR AND ALL FIBER TERMINATION EQUIPMENT
AFTER ALL NETWORK SERVICES HAVE BEEN
REMOVED.
21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND
PROTECT DURING THE STRUCTURED CABLING
UPGRADE.
GENERAL
SHEET NOTES
SHEET
KEYNOTES
TR LEGEND
SPECIAL PROJECT
NOTES
1 DRAWINGS MAY NOT SHOW OR INDICATE ALL DATA
LOCATIONS THAT MAY BE REMOVED AS PART OF
THIS PROJECT. CONTRACTOR TO VERIFY ALL
CABLES TO BE DEMOLISHED COMPLETELY TO THE
VA PATCH PANEL.
STORAGE
2A08
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:0
A M
08-ED401
ENLARGED DEMOLITION PLANS EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
1 UNLESS NOTED OTHERWISE REMOVE ALL LIGHTING
FIXTURES DEVICES AND EQUIPMENT SHOWN
DASHED. REMOVE CONDUIT AND WIRING BACK TO
PANELBOARD OF ORIGIN OR TO FIRST ACTIVE
DEVICE THAT REMAINS.
2 SALVAGE ALL LIGHT FIXTURES, TWIST-LOCK
RECEPTACLES AND WALLPLATES, CEILING SPEAKERS
AND SECURITY AND FIRE ALARM DEVICES TO
OWNER. PROTECT SALVAGED EQUIPMENT FROM
DAMAGE.
3 PRIOR TO SUBMITTING BID, VISIT THE SITE AND FIELD
VERIFY THE EXTENT OF ELECTRICAL AND DATA
DEMOLITION WORK TO MEET THE INTENT OF THE BID
DOCUMENTS AND INCLUDE ALL COSTS IN BID.
4 PRIOR TO REMOVAL OF ANY ELECTRICAL EQUIPMENT
OR WIRING, FIELD VERIFY THAT THE EQUIPMENT OR
WIRING IS INACTIVE OR NO LONGER IN USE.
5 REMOVE ALL DEVICES, RACEWAYS AND WIRING
FROM WALLS TO BE REMOVED. WHERE ACTIVE
RACEWAYS OCCUR IN WALLS TO BE REMOVED,
RE-ROUTE THE RACEWAY WITH ASSOCIATED WIRING
TO KEEP THE CIRCUIT OPERATIONAL.
6 REMOVE ALL FIRE ALARM DEVICES WHERE EXISTING
WALLS AND CEILINGS ARE BEING REMOVED, WITH
ASSOCIATED CONDUIT AND WIRING. EXISTING FIRE
ALARM DEVICES AND SYSTEM NOT INDICATED FOR
REMOVAL SHALL REMAIN ACTIVE THROUGHOUT
DEMOLITION AND CONSTRUCTION UNTIL THE NEW
SYSTEM IS TESTED AND OPERATIONAL. MAINTAIN
ALL CLASS A FIRE ALARM INITIATING AND INDICATING
LOOPS WHERE EXISTING DEVICES ARE REMOVED.
7 REMOVE ALL ABANDONED RACEWAY, CONDUIT,
WIRING AND CABLING WHETHER ABANDONED
PREVIOUS TO THIS PROJECT OR AS A RESULT OF
THIS PROJECT. NOT ALL ABANDONED ITEMS ARE
SHOWN ON THESE PLANS AND FIELD VERIFICATION
OF DEMOLITION SCOPE EXTENT IS REQUIRED.
8 DEVICES MARKED "RR" ARE TO BE REMOVED AND
RELOCATED PER NEW PLANS. EXTEND CIRCUITING
AS REQUIRED FOR RELOCATION.
9 REFER TO ARCHITECTURAL DRAWINGS FOR
REMOVAL OF MOTORS, CONDUIT, CONDUCTOR AND
CONTROL WIRING ASSOCIATED WITH EXISTING
MOTORIZED DOORS, PARTITIONS AND LIGHTING.
10 DEMOLISH ALL OIT WI-FI ACCESS POINTS WHETHER
SHOWN ON DRAWINGS OR NOT WITHIN SCOPE OF
WORK AREA. DO NOT REMOVE THE BIO-MED PUBLIC
WI-FI ACCESS POINTS.
11 REMOVE FEEDERS FOR ALL DEMOLISHED PANELS,
DISCONNETS, ETC. BACK TO SOURCE
12 ALL ITEMS INDICATED TO REMAIN SHALL BE
PROTECTED DURING ALL PHASES OF
CONSTRUCTION.
13 CONTRACTOR TO TRACE AND LABEL ALL EXISTING
LOADS TO REMAIN, THAT ARE CURRENTLY FED FROM
PANELS THAT ARE BEING DEMOLISHED IN THIS
PHASE. THESE LOADS TO BE RE-FED FROM NEW
PANELS IN NEXT PHASE.
14 ALL HVAC UNITS TO BE REMOVED BY MECHANICAL
CONTRACTOR UNLESS NOTED OTHERWISE. REMOVE
ALL ASSOCIATED RACEWAYS AND CONDUCTORS
BACK TO SOURCE.
15 REPLACE DATA DEVICES IN HEADWALLS OF EXISTING
DATA LOCATIONS.
16 ALL DATA DEVICES SHOWN TO BE DEMOLISHED AS
PART OF THIS PROJECT SHALL HAVE RACEWAYS
REMOVED AS PART OF THE DEMOLITION SCOPE OF
WORK. DEMOLISHED DATA DEVICES ARE INDICATED
AS DASHED DEVICES AND KEYNOTED.
17 ALL DATA DEVICES SHOWN ARE TO BE REPLACED
UNLESS OTHERWISE SPECIFIED ON THE FLOOR
PLANS. ALL EXISTING DATA DEVICE PATHWAYS
SHALL REMAIN INTACT AND BE REUSED FOR NEW
CABLE INSTALLATION.
18 REMOVE ALL EXISTING CABLES THAT ARE TO BE
REPLACED BACK TO THE PATCH PANEL.
19 REMOVE ANY WALL MOUNT RACKS, OR FLOOR
MOUNT RACKS ONCE THEY ARE EMPTY AND HAVE NO
ADDITIONAL CABLES OR EQUIPMENT IN THEM.
20 REMOVE EXISTING FIBER FROM TR BACK TO THE
MCR AND ALL FIBER TERMINATION EQUIPMENT
AFTER ALL NETWORK SERVICES HAVE BEEN
REMOVED.
21 ALL BIOMED EQUIPMENT TO REMAIN. PRESERVE AND
PROTECT DURING THE STRUCTURED CABLING
UPGRADE.
NORTH
1/4" = 1'-0"F3
ENLARGED EXISTING TR 2A02A EQUIPMENT PLAN
Ground Floor
TR # G100A - 109
1st Floor
TR # 1A14
TR # 1A24
NORTH
1/4" = 1'-0"F7
ENLARGED EXISTING STORAGE 2A08A-8 DEMOLITION PLAN
GENERAL
SHEET NOTES
0' 2' 4' 8' 16'
GRAPHIC SCALE 1/4" = 1'-0"
1'
ADDENDUM #01 2/28/2023 06/08/23
PIPE TUNNEL (TO B.06)
GA07BA
MECHANICAL (POOL EQUIPMT)
GA03A
MECHANICAL (HOT TANK)
GA04
ELECTRICAL
GA08
ELECTRICAL
GA08A
OFFICE (137,EMS SUPPLY)
GA02
TRAINING (117,DRIVERS)
GA03
CORRIDOR (TO lOCKER ENTRY)
GA01
STORAGE (GENERAL)
GA06C
STORAGE (135)
GA06B
SHOP (138)
GA05
ENTRY (138, UTILITIES)
GA07
LOCKERS (WOMEN)
GA01A
SHOP (138)
GA01CA
P
IP
E C
H A
S E
G A
B
A A
STORAGE (142,LIBRARY)
GA01CC
ELEVATOR LEVEL
BAE1
STORAGE (EQUIPMT. CLOTHING)
GA06
STORAGE (135)
GA06A
STORAGE (EQUIPMT. CLOTHING)
GA06D
LOCKERS (MEN)
GA01C
STORAGE (137)
GA01CD
CORRIDOR (TO
LOCKER ENTRY)
GA00A
TOILET/
SHOWER (MEN)
GA01CB
P
IP
E T
U N
N E
L
T O
C O
N C
O U
R S
E
G A
B
CORRIDOR (TO
ELEVATOR)
GA00
ELECTRICAL
GA08
FIRE HOSE CLOSET
GA01B
STAIR LEVEL
GAA
TOILET/SHOWER
(WOMEN)
GA01AA
"8-G-A-E-P1" "8-G-A-N-D2"
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:1
A M
08-EP100
GROUND FLOOR POWER PLAN EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/8" = 1'-0"F1
GROUND FLOOR POWER PLAN
1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.
2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,
GEAR, CABLE, CONDUCTORS, TERMINATIONS,
OVERCURRENT PROTECTION DEVICES, AND HEAD
END EQUIPMENT AS PART OF THIS PROJECT.
3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE
VOLTAGE AS PART OF THIS PROJECT. PROVIDE
LINE VOLTAGE REQUIRED TO ALL SYSTEMS
PROVIDED AS PART OF THIS PROJECT.
COORDINATE WITH ALL OTHER DISCIPLINES AND
DRAWINGS.
4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,
FLOORS, AND CEILING UNLESS OTHERWISE
NOTED. INSTANCES WHERE EXPOSED OR
SURFACE MOUNTED RACEWAYS IS REQUIRED A
ROUTING SKETCH SHALL BE PROVIDED TO
ARCHITECT AND ENGINEER. RACEWAY TYPE
SHALL BE SELECTED BY ENGINEER. FINISH OF
RACEWAY SHALL BE SELECTED BY ARCHITECT.
5 PROVIDE A NEW DEVICE AND TRIM PLATE IN
EXISTING DEVICE LOCATION. THE DEVICE SHALL
MATCH EXISTING TYPE OR AS SHOWN WHICHEVER
IS MORE STRINGENT. PROVIDE NEW RACEWAYS
AND CONDUCTORS ONLY AS REQUIRED.
6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING
PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY
PANELBOARD TYPE AND BREAKER TYPE.
7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN
IS APPROXIMATE. COORDINATE EXACT LOCATIONS
OF MECHANICAL EQUIPMENT WITH MECHANICAL
DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.
GENERAL
SHEET NOTES
SHEET
KEYNOTES
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
C
W
C
C
C
C
W
W
C
C
W
C
C
W
W
GYM (WEST-COURT)
1A22A
GYM (EAST-COURT)
1A22B
GYMNASIUM (EAST & WEST COURTS)
1A22
FIRE EQUIP/HOSE
1A22C
OFFICE (117)
1A30
OFFICE (117)
1A28
POOL (117,THERAPY)
1A13A
WOMEN'S SHOWERS
1A19C
MEN'S LOCKERS
1A17A
MEN'S RESTROOM
1A17C
PIPE CHASE (138)
1A17B
ENTRY TO POOL
1A13
SAUNA (117)
1A13D
STORAGE
1A13C
WELLNESS (00)
1A11
1A11B
STAIRS
1AB STORAGE (MPC)
1A07
WAITING
IB01VESTIBULE
IB00A
OFFICE
IB02
RETAIL STORE (133)
1A01
ELEVATOR
STAIR
1AA
ELECTRICAL
1A26
CORRIDOR (TO ELEVATOR & MPC)
1A00B
STORAGE (MPC)
1A18
STAFF DINING (133)
1A02B
FIRE EQUIP/HOSE
1A02C
STORAGE (133)
1A02E
KITCHEN (133)
1A02G
W O
R K
R O
O M
3) 1A
H
PATIO #03 (MPC)
1A20.03
CORRIDOR
1A00
MEN'S RESTROOM
1A14
WOMEN'S RESTROOM
1A12
P
IP
E C
H A
S E
8) 1A
A
HAC
1A10
KITCHEN (142)
1A20A
STORAGE (142)
1A08A
STORAGE (133)
1A03
CHASE
OFFICE
IB04
OPEN OFFICE
IB06
CONF
IB08
HALL
IB00B
OFFICE
IB10
GAIT LAB
IB01
GAIT LAB
IB12
THEATER
IB14
EQUIP. HOLDING
IB14A
EXAM
IB03
RR
IB05
CLEAN LINENS
IB00D
CRASH CART
IB00E
IT
IB09
ELEC
IB11
HALL
IB00
MECH
IB13
VESTIBULE
IB00F
1A01A
ENTRY (TO REAR OF MPC)
1A08
1A06
OFFICE (133)
1A02A
MULI-PURPOSE CENTER (MPC)
1A20
1A04
DINING (133, CANTEEN)
1A02
PATIO #02 (MPC)
1A20.02
PATIO #01 (MPC)
1A20.01
VESTIBULE
(VENDING)
1A00A
STORAGE
(WELLNESS)
1A11A
OFFICE
(WELLNESS)
1A09
WAITING
(135, SHUTTLE)
1A13A
OFFICE
(133, CHIEF)
1A02AB
OFFICE
(133)
1A02AA
CLOCK ROOM
(MPC)
1A16
CORRIDOR (TO REAR
ENTRANCE)
1A00C
CORRIDOR
(TO GYM)
1A00DTEL/DATA
(142) 1A24
ENTRY (MEN'S
SHOWERS/LOCKERS)
1A17
M E
N 'S
S H
O W
E R
R O
O M
1A
A STORAGE (117,
SCUBA)
1A15ENTRY TO
SAUNA
1A13B
WOMEN'S
RESTROOM
1A19B
WOMEN'S
LOCKERS
1A19A
E N
T R
Y
W O
M E
N 'S
S H
O W
E R
S /L
O C
K E
R S
1A
HAC
(137) 1A02D
STORAGE
(VCS)
1A32
S T
A F
F L
O C
K E
R S
3) 1A
F
DIRTY
LINENS
IB00C
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:2
A M
08-EP110
FIRST FLOOR POWER PLAN EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/8" = 1'-0"F1
FIRST FLOOR POWER PLAN
1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.
2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,
GEAR, CABLE, CONDUCTORS, TERMINATIONS,
OVERCURRENT PROTECTION DEVICES, AND HEAD
END EQUIPMENT AS PART OF THIS PROJECT.
3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE
VOLTAGE AS PART OF THIS PROJECT. PROVIDE
LINE VOLTAGE REQUIRED TO ALL SYSTEMS
PROVIDED AS PART OF THIS PROJECT.
COORDINATE WITH ALL OTHER DISCIPLINES AND
DRAWINGS.
4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,
FLOORS, AND CEILING UNLESS OTHERWISE
NOTED. INSTANCES WHERE EXPOSED OR
SURFACE MOUNTED RACEWAYS IS REQUIRED A
ROUTING SKETCH SHALL BE PROVIDED TO
ARCHITECT AND ENGINEER. RACEWAY TYPE
SHALL BE SELECTED BY ENGINEER. FINISH OF
RACEWAY SHALL BE SELECTED BY ARCHITECT.
5 PROVIDE A NEW DEVICE AND TRIM PLATE IN
EXISTING DEVICE LOCATION. THE DEVICE SHALL
MATCH EXISTING TYPE OR AS SHOWN WHICHEVER
IS MORE STRINGENT. PROVIDE NEW RACEWAYS
AND CONDUCTORS ONLY AS REQUIRED.
6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING
PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY
PANELBOARD TYPE AND BREAKER TYPE.
7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN
IS APPROXIMATE. COORDINATE EXACT LOCATIONS
OF MECHANICAL EQUIPMENT WITH MECHANICAL
DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.
GENERAL
SHEET NOTES
SHEET
KEYNOTES
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
T
C
C
C
C
C
C
STAIRS/
LEVEL
2AB
CORRIDOR
2A00B
STORAGE
2A08
OFFICE
2A06
TEL/DATA
2A02A
CONFERENCE
2A01
EXTINGUISHER/HOSE
2A04
CORRIDOR
2A00A
ELECTRICAL
2A02B
TOILET
2A13
TOILET
2A09
ELEVATOR
ENTRY
2A02
LOUNGE
(HR-LINKS)
2A07
2A11
STAIRS LEVEL
2AA
OFFICE
2A05
OFFICE
2A03
CORRIDOR
2A00
08-EP401
F8
W
SS-2
8-2-A-E-P2-11,13,15
8-2-A-E-P2-17
ROOF ACCESS
2AAA
"8-2-A-N-P1"
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:3
A M
08-EP120
SECOND FLOOR POWER PLAN EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.
2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,
GEAR, CABLE, CONDUCTORS, TERMINATIONS,
OVERCURRENT PROTECTION DEVICES, AND HEAD
END EQUIPMENT AS PART OF THIS PROJECT.
3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE
VOLTAGE AS PART OF THIS PROJECT. PROVIDE
LINE VOLTAGE REQUIRED TO ALL SYSTEMS
PROVIDED AS PART OF THIS PROJECT.
COORDINATE WITH ALL OTHER DISCIPLINES AND
DRAWINGS.
4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,
FLOORS, AND CEILING UNLESS OTHERWISE
NOTED. INSTANCES WHERE EXPOSED OR
SURFACE MOUNTED RACEWAYS IS REQUIRED A
ROUTING SKETCH SHALL BE PROVIDED TO
ARCHITECT AND ENGINEER. RACEWAY TYPE
SHALL BE SELECTED BY ENGINEER. FINISH OF
RACEWAY SHALL BE SELECTED BY ARCHITECT.
5 PROVIDE A NEW DEVICE AND TRIM PLATE IN
EXISTING DEVICE LOCATION. THE DEVICE SHALL
MATCH EXISTING TYPE OR AS SHOWN WHICHEVER
IS MORE STRINGENT. PROVIDE NEW RACEWAYS
AND CONDUCTORS ONLY AS REQUIRED.
6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING
PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY
PANELBOARD TYPE AND BREAKER TYPE.
7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN
IS APPROXIMATE. COORDINATE EXACT LOCATIONS
OF MECHANICAL EQUIPMENT WITH MECHANICAL
DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.
NORTH
1/8" = 1'-0"F1
SECOND FLOOR POWER PLAN
GENERAL
SHEET NOTES
SHEET
KEYNOTES
1 SPLIT CONDENSING UNIT LOCATED ON ROOF. SEE
MECHANICAL DRAWINGS FOR EXACT LOCATION.
2 PROVIDE A SEPARATE 120 VOLT, 20 AMP, 1 PHASE
CIRCUIT AND WEATHER PROOF GFCI OUTLET
MOUNTED TO SIDE OF CONDENSING UNIT.
0' 4' 8' 16' 32'
GRAPHIC SCALE 1/8" = 1'-0"
2'
T
T
"8-2-A-E-P2"
"8-2-A-N-P2"
(PG4)
(PG4) (PG4)
(PG4)
8-2-A-N-P2-1,3,5
RACK-30
8-2-A-E-P2-1,3,5
RACK-30
AC-2
8-2-A-E-P2-7,9
8-2-A-E-P2-27
8-2-A-E-P2-19
8-2-A-E-P2-21
8-2-A-E-P2-23 8-2-A-E-P2-25
(G-4)
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
E
L E
C .r v t
/8
/2
:2
:4
A M
08-EP401
ENLARGED POWER PLANS EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 08
08 JUN 2023 ARNOLD,
FELT
TAYLOR,
SOUTHERN
NORTH
1/4" = 1'-0"F8
ENLARGED TR 2A10-08 POWER PLAN
ID DESCRIPTION
NOMINAL SIZE
M O
U N
T
IN
G
T Y
P E
C O
L O
R T
E M
P
C R
I
D R
IV
E
R C
O N
F
IG
U R
A T
IO
N
V O
L T
A G
E
W A
T T
S
F
IN
IS
H
F
IX
T U
R E
L U
M E
N S
D
IF
F U
S E
R /L
E N
S
R E
F L
E C
T O
R
O P
T
IO
N S
N O
T E
S
MANUFACTURER (CATALOG SERIES)
L E
N G
T H
D E
P T
H
H E
IG
H
T
D
IA
M E
T E
R A
P E
R T
U R
E
OPTION 1 OPTION 2 OPTION 3
(G-4) 2X4 LED FLAT PANEL, GRID LAY-IN 48" 24" 3" - CR LED 3500K LED DRIVER
(0-10V DIMMING)
120/277 41 - 4300 - - - METALUX (24FP4735C) APPROVED EQUAL APPROVED EQUAL
(PG4) STRIPLIGHT, GENERAL 48" 4" 4" - CP LED 4000K LED DRIVER
(0-10V DIMMING)
120/277 38 CBA 5000 - - - LITHONIA
(ZL1D-L48-5000LM-FST-M
VOLT-40K-80CRI-WH-HC3
6)
ILP (SS4) WILLIAMS (75R)
DIFFUSER/LENSFINISH PROVIDE UNIT PRICES AND FIXTURE BRAND SELECTED FOR ADD/DELETE CHANGES
FOR EACH FIXTURE TYPES SHOWN WITHIN 48 BUSINESS HOURS OF THE BID DATE.
FAILURE TO COMPLY WITH THIS REQUIREMENT MAY DISQUALIFY THE PRODUCTS
AND EMPOWER THE ENGINEER TO DETERMINE FAIR VALUE FOR FIXTURE AND
INSTALLATION CHANGES, WITHOUT FURTHER INPUT FROM THE CONTRACTOR OR
INSTALLER.
CONTRACTOR ALLOWANCE PRICES ARE ACCURATE WHEN THIS JOB WAS
SPECIFIED, CONTRACTOR AND ELECTRICAL DISTRIBUTOR SHALL VERIFY THIS
ALLOWANCE AND REPORT ANY PROBLEMS TO THE ENGINEER BEFORE THE BID.
ALLOWANCE PRICE MAY OR MAY NOT INCLUDE LAMP(S) OR FREIGHT AS NOTED,
AND DO NOT INCLUDE ANY TAXES.
SUBSTITUTIONS AND/OR EQUAL FIXTURES MUST RECEIVE APPROVAL PRIOR TO
BIDDING, THEY MUST BE SUBMITTED TO THE ENGINEER NO LESS THAN 2 WEEKS
PRIOR TO BID OPENING.
SAMPLES MUST BE PROVIDED FOR ANY AND ALL FIXTURES UPON A/E REQUEST
PRIOR TO RELEASING FIXTURES.
ALL FIXTURES SHALL BE LISTED AND APPROVED FOR THEIR INTENDED USE AND
LOCATION.
VERIFY THE PROPER MOUNTING KITS OR ACCESSORIES TO FACILITATE
INSTALLATION AS SHOWN AT EACH LOCATION ON THE DRAWINGS.
COMPLY WITH THE "INTERIOR LIGHTING" SECTION OF THE SPECIFICATIONS.
REFER TO SPECIFICATIONS FOR IMPORTANT TECHNICAL REQUIREMENTS FOR
LIGHTING FIXTURES, DRIVERS, AND LAMPS.
ALL LIGHT FIXTURES TO BE EITHER "DLC" OR "LIGHTING FACTS" LISTED OR TO BE
APPROVED BY ARCHITECT/ENGINEER AND OWNER.
LUMINAIRE OPTIONSMOUNTING REFLECTOR 1.
2.
3.
4.
5.
6.
7.
8.
9.
DIAMETER
H E
IG
H
T
LENGTH DEPTH
H E
IG
H
T
LENGTH
DEPTH
HEIGHT
NOTES
INTERIOR LIGHTING FIXTURE SCHEDULE
ABBREVIATIONS GENERAL NOTES
ARHR - AIR RETURN AND HEAT REJECTION
DL - DAMP LOCATION
EQC - EARTHQUAKE CLIPS
F - FUSING
HLD - HINGED AND LATCHED DOOR
HS - HOUSE SIDE SHIELD
PS - PHOTOCELL SWITCH
QRS - QUARTZ RESTRIKE
ST - STATIC
WG - WIRE GUARD
WL - WET LOCATION
B - BASE
C - CEILING
F - FLANGE
G - GRID
P - PENDANT
PL POLE
R - RECESSED
S - SURFACE
W - WALL
MW - MATTE WHITE
BL - BLACK
SL - SILVER
GL - GOLD
CL - CLEAR
PW - PAINTED WHITE
EA - EXTRUDED ALUMINUM
S - STEEL
GS - GALVANIZED STEEL
C - CAST
CBA - COLOR BY ARCHITECT
SCBA - STANDARD COLOR BY
ARCHITECT
CCA - CUSTOM COLOR BY
ARCHITECT
FS
209D
- MEETS FEDERAL
STANDARD 209D
TP - THERMALLY
PROTECTED
FL - FLUSH
R - REGRESS
M - MITERED
OP - NONE/OPEN
SP - SPECULAR
SS - SEMI-SPECULAR
D - DIFFUSE (WHITE ENAMEL)
SC - SPECULAR (COLORED)
PR - PRISMATIC
FDR - FULL DEPTH REFLECTOR
DS - DIFFUSE (SEMI SPECULAR) SILVER
LI - LOW IRIDESCENT
IR - IRIDESCENT
SL - SILVER
GL - GOLD
CA - CLEAR ALZAK
#A - ACRYLIC #THICK
#OA - ACRYLIC #THICK (OPAL)
GC - GLASS (CLEAR)
GO - GLASS (OPAL)
GF - GLASS (FROSTED)
SGL - SOFT GLOW LENS
HPL - HIGH PERFORMANCE LENS
DO - DROP OPAL
CGL - CONVEX GLASS LENS
S - SATIN LENS
1 PROVIDE AN OVERHEAD POWER DROP CORD WITH
A 30 AMP 208 VOLT THREE-PHASE TWISTED LOCK
RECEPTACLE (L21-30R); 8.5 FT AFF (WYE(5-WIRE))
COORDINATE INSTALLATION LOCATION WITH
TELECOMMUNICATIONS CONTRACTOR. SEE SHEET
EE002, EE501, AND PANEL SCHEDULE. PROVIDE
RACK MOUNTED POWER DIST. (2RU), RACK
MOUNTED UPS (6RU) AND PDU PER TELECOM
EQUIPMENT RACK ELEVATIONS ON ET500'S.
2 SECONDARY BONDING BUSBAR (SBB). SEE ET
SHEETS FOR PLACEMENT AND GROUNDING DETAIL.
CONTRACTOR TO PROVIDE A SEPARATELY
DERIVED #3/0 GROUND FROM BUILDING GROUND
TO TR BUSBARS. CONTRACTOR TO VERIFY
BUSBAR’S RESISTANCE IS UNDER 4 OHMS
MEASURED BY THE FOUR POINT
FALL-OF-POTENTIAL METHOD PER IEEE 81.
3 PROVIDE A 100 AMP, THREE-PHASE, FOUR WIRE,
208 VOLT SERVICE PANEL. PANEL SHALL BE
EQUIPPED WITH A POWER METER.
4 PROVIDE THERMAL SWITCH FOR SPLIT SYSTEM.
THERMAL SWITCH TO BE MOUNTED ON SIDE OF
UNIT.
5 LIGHTING CONTROL AND POWER TO BE
CONNECTED TO EXISTING LIGHT CIRCUIT FOR THE
SPACE.
1 VERIFY ALL EXISTING CONDITIONS BEFORE BID.
2 CONTRACTOR IS RESPONSIBLE FOR ALL DEVICES,
GEAR, CABLE, CONDUCTORS, TERMINATIONS,
OVERCURRENT PROTECTION DEVICES, AND HEAD
END EQUIPMENT AS PART OF THIS PROJECT.
3 CONTRACTOR IS RESPONSIBLE FOR ALL LINE
VOLTAGE AS PART OF THIS PROJECT. PROVIDE
LINE VOLTAGE REQUIRED TO ALL SYSTEMS
PROVIDED AS PART OF THIS PROJECT.
COORDINATE WITH ALL OTHER DISCIPLINES AND
DRAWINGS.
4 ALL RACEWAYS SHALL BE CONCEALED IN WALLS,
FLOORS, AND CEILING UNLESS OTHERWISE
NOTED. INSTANCES WHERE EXPOSED OR
SURFACE MOUNTED RACEWAYS IS REQUIRED A
ROUTING SKETCH SHALL BE PROVIDED TO
ARCHITECT AND ENGINEER. RACEWAY TYPE
SHALL BE SELECTED BY ENGINEER. FINISH OF
RACEWAY SHALL BE SELECTED BY ARCHITECT.
5 PROVIDE A NEW DEVICE AND TRIM PLATE IN
EXISTING DEVICE LOCATION. THE DEVICE SHALL
MATCH EXISTING TYPE OR AS SHOWN WHICHEVER
IS MORE STRINGENT. PROVIDE NEW RACEWAYS
AND CONDUCTORS ONLY AS REQUIRED.
6 PROVIDE NEW CIRCUIT BREAKERS IN EXISTING
PANEL FOR ALL NEW CIRCUITS. FIELD VERIFY
PANELBOARD TYPE AND BREAKER TYPE.
7 LOCATIONS OF MECHANICAL EQUIPMENT SHOWN
IS APPROXIMATE. COORDINATE EXACT LOCATIONS
OF MECHANICAL EQUIPMENT WITH MECHANICAL
DRAWINGS AND INSTALLER PRIOR TO ROUGH-IN.
BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI
ALL OTHER LOADS @ 100% : 18.6 kVA -
MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH
LARGEST MOTOR CALCULATED @ 125% PER NEC
RECEPTACLES: 1.6 kVA @ 100% = 1.6 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 57
LIGHTING & CONTINUOUS LOADS: 0.2 kVA @ 125% = 0.2 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 20
NEC DIVERSIFIED LOAD CALCULATIONS
CONNECTED AMPS PER PHASE 57 55 48 AVERAGE CONNECTED AMPS PER PHASE = 53
TOTALS: CONNECTED kVA PER PHASE 7 7 6 CONNECTED TOTAL kVA = 19
29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30
27 20 1 0.2 0.0 0.0 LIGHTING... 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 28
25 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 26
23 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 24
21 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 22
19 20 1 0.0 0.0 0.4 CO TELECOMMUNICATIONS... 0.4 -- SPACE 0.0 0.0 0.0 -- 1 -- 20
17 20 1 0.0 0.0 0.2 CO 0.2 -- SPACE 0.0 0.0 0.0 -- 1 -- 18
15 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 16
13 -- -- -- -- -- -- -- 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 14
11 30 3 0.0 5.6 0.0 PWR: SS-2 1.9 -- SPACE 0.0 0.0 0.0 -- 1 -- 12
9 -- -- -- -- -- -- -- 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 10
7 15 2 0.0 1.7 0.0 PWR: AC-2 0.8 -- SPACE 0.0 0.0 0.0 -- 1 -- 8
5 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 6
3 -- -- -- -- -- -- -- 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 4
1 30 3 0.0 10.0 0.0 RACK POWER 3.3 -- SPACE 0.0 0.0 0.0 -- 1 -- 2
NO AMP POLE BKR LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG BKR POLE AMP NO
CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT
ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING: 0
120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 100 AMPERE MAIN CB SURFACE TELECOMMUNICATIONS...
VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: FED FROM: CABINET: LOCATION: NOTES:
PANEL: "8-2-A-E-P2"
BKR: GF=GFCI, GF3=30mA GFCI CAPABLE OF BEING LOCKED OUT IN OPEN POSITION, IG=ISOLATED GROUND, AF=AFCI, ST=SHUNT TRIP, RED=PROVIDE RED COLORED BREAKER, AF=ARC FAULT CURRENT INTERRUPTER, GA=COMBINATION OF GROUND FAULT AND ARC FAULT CIRCUIT INTERRUPTER, GS=COMBINATION OF SHUNT TRIP WITH GFCI
ALL OTHER LOADS @ 100% : 10.0 kVA -
MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITH
LARGEST MOTOR CALCULATED @ 125% PER NEC
RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 28
LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 10
NEC DIVERSIFIED LOAD CALCULATIONS
CONNECTED AMPS PER PHASE 28 28 28 AVERAGE CONNECTED AMPS PER PHASE = 28
TOTALS: CONNECTED kVA PER PHASE 3 3 3 CONNECTED TOTAL kVA = 10
29 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 30
27 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 28
25 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 26
23 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 24
21 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1 -- 22
19 20 1 -- 0.0 0.0 0.0 SPARE 0.0 -- SPACE 0.0 0.0 0.0 -- 1…