This document contains responses to questions about existing electrical equipment at various buildings for a construction project at the Salt Lake City Veterans Affairs Medical Center. The responses list the manufacturer, type, voltage rating, amperage rating, and interrupting capacity for existing switchboards and panelboards at each building location. Buildings include Buildings 1, 2, 3, 5, 7, 8, and 9, with equipment manufacturers including GE, Square D, and others. The related federal contract opportunity is for EHRM Infrastructure Upgrades Construction at the Salt Lake City VAMC with solicitation number 36C77623B0041 from the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity type is a solicitation.

View the file

Other files

File Type Posted
RESPONSE Attachment V5.1.docx DOCX document
Construction Wage Rates- Salt Lake County- 08-11-2023.pdf PDF
ADDENDUM No 01.pdf PDF
Bid opening call-in information.pdf PDF
RESPONSE Attachment V5.1 No. 30 Snippet.JPG JPG image
2017 AHERA 3-Year Reinspection v2.2 2017_1205_BT.xlsx XLSX spreadsheet
RESPONSE V10 - Technical Questions.docx DOCX document
RESPONSE Attachment V7.2.docx DOCX document
36C77623B0041 0004.pdf PDF
RESPONSE Attachment V1.1.docx DOCX document
RESPONSE Attachment V7.1.docx DOCX document
RESPONSE Attachment V3.1.docx DOCX document
36C77623B0041 0003.pdf PDF
36C77623B0041 0003.pdf PDF
36C77623B0041 0002.pdf PDF
660-21-700 PreConstruction Site Visit Sing In Sheet 2023 07 14.pdf PDF
36C77623B0041 0001.pdf PDF
Attachment 13-Utah Tax Memo-EHRM-Salt Lake City.pdf PDF
Attachment 7-Part 6 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 12-Construction Wage Rates-Salt Lake County- 04-14-2023.pdf PDF
Attachment 14-Limitations on Subcontracting-EHRM-Salt Lake City.docx DOCX document
Attachment 2-Part 1 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 15-Contractor Safety-Environmental-EHRM-S.L.C..docx DOCX document
Attachment 1-Specifications-(1 of 1)-EHRM-Salt Lake City.pdf PDF
Attachment 6-Part 5 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 3-Part 2 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 9-Part 8 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 5-Part 4 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
36C77623B0041.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 11-Asbestos Site Survey-EHRM Salt Lake City.pdf PDF
Attachment 10-Part 9 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 4-Part 3 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Attachment 8-Part 7 of 9-Drawings-EHRM-Salt Lake City.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Since we were unable to visit every building at the pre-bid, can someone at the VA take a picture and (publish in the solicitation website) of each one of these existing panels and nameplate data with the door in the open position. We need to verify panel manufacturer and AIC rating in order get the correct breakers to install in existing panels. RESPONSE: See below.

· Building 1

· Switchboard 1-G-A-E-D1, GE – Type CCB, Style 2, 208V, 800A, Plant S, 65k AIC

· Switchboard 1-G-A-C-D1, GE – Type CCB, Style 2, 208V, 1000A, Plant S, 65k AIC

· Panelboard 1-1-D-E-P2, Square D – NQOD, 208V, 225A, 10k AIC

· Panelboard 1-1-D-C-P1, Square D – NQOD, 208V, 225A, 10k AIC

· Building 14

· Switchboard 14-B-C-E-D2, Square D – Power Style Switchboard QED S, 480V, 1600A, 65k AIC

· Switchboard 14-B-C-C1-D1, Square D – I-Line HCP 06431, 480V, 1000A, 65k AIC

· Building 2

· Switchboard 2-G-B-E-D1, Square D – I-Line HCM, 208V, 800A, 42k AIC

· Switchboard 2-G-B-C-D1, Square D – I-Line HCW, 208V, 800A, 42k AIC

· Building 3 Switchboard 3-G-B-E-D3, Square D – I-Line HCM, 208V, 400A, 42k AIC, (Switchboard is located in room GB05B) Switchboard 3-G-B-N-D1, Square D – Power Style Switchboard QED 1, 208V, 1600A, 42k AIC (Switchboard is located in room GB05B)

· Building 5 Distribution Panel 5-G-A-E-D1, Square D – I-Line, 208V, 600A, 21k AIC Panelboard 5-G-A-C-P1, Square D – NQOD, 208V, 100A, 14k AIC

· Building 7 Distribution Panel 7-B-B-E-D1, Square D – I-Line HCM, 208V, 600A, 42k AIC Switchboard 7-B-B-N-D1, Square D – Power Style Switchboard QED L, 208V, 2000A, 42k AIC

· Building 8 Switchboard 8-G-A-N-D2, Square D – I-Line HCM, 208V, 800A, 42k AIC Panelboard 8-G-A-E-P1, Square D – NQOD, 208V, 225A, 22k AIC

· Building 9 Main Distribution Panel 9-1-A-N-D1, Square D – I-Line HCWM, 208V, 1200A, 42k AIC