This addendum provides additional details for the solicitation seeking construction services for the EHRM Infrastructure Upgrades Project at the Salt Lake City VA Medical Center. The solicitation requests proposals to upgrade critical infrastructure systems at the facility, including electrical, mechanical, and plumbing work. Proposals are due by January 15, 2023, with award anticipated by March 31, 2023. The construction period is 240 calendar days. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency. Small businesses, veteran-owned small businesses, service-disabled veteran-owned small businesses, and HUBZone small businesses are encouraged to respond.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM No. 01 – 8/16/2023
TO: Brandon Wilkins
PROJECT: 660-21-700 EHRM Infrastructure Upgrades Construction
500 Foothill Dr.
Salt Lake City, UT
ARCHITECT: RDC+EA, LLLP
324 S State St., Suite 444
Salt Lake City, UT 84111
801-647-0334 will.felt@rdcea.com
Incorporate the following clarifications and revisions on the specifications, drawings and other contract documents of the above named project.
This addendum shall become a part of the contract documents, and the cost of all items covered herein shall be included in the contractor's proposal.
PROJECT MANUAL/SPECIFICATIONS
Item PM1 Specification 08 71 00 Door Hardware: Hardware Set B01-3
Doors GB24-14 and GB28-14 have been renumbered to GA24-14 and GA28-
14 respectively to correct an inconsistency between the specifications and drawings. See Attachment 01.
Item PM2 Specification 08 71 00 Door Hardware: Door GA14C-03
The hardware for door GA14C-03 has been changed from B3-06 to B01-01.
See Attachment 01.
Item PM3 Specification 01 45 35 Special Inspections: List of Special Inspections
The list of Special Inspections has been edited. See Attachment 04.
ARCHITECTURAL
Item A1 Door GA28-14
Although the hardware set was correct, the remarks column has been updated to clarify that this door has a card reader. The remark column now reads; DOOR SECURITY: CARD READER, C LABEL. See Attachment 02.
660-21-700 EHRM Infrastructure Upgrades Construction Addendum No. 1, page 2
Item A2 Doors GC31-14
Although the hardware set was correct, the remarks column has been updated to clarify that this door has a card reader. The remark column now reads; DOOR SECURITY: CARD READER, C LABEL. See Attachment 02.
Item A3 Door GA14C-03
The hardware for this door has been changed from set B3-06 to B01-1. See
Attachment 03.
ELECTRICAL
Item E1 01-EP120, 01-EP130, 01-EP150, 01-EP604, 01-EP605
Power information to SS units changed. See Attachment 05.
Item E6 01-ET100A, 01-ET100C, 01-ET110A, 01-ET110C, 01-ET110D, 01-ET120A, 01-ET120C, 01-ET130A, 01-ET130C, 01-ET140A, 01-ET140C, 01-ET150B, 03-ET100A, 03-ET100B, 03-ET110A, 03-ET110B, 03-ET120A, 03-ET120B, 05-ET110, 07-ET110A, 08-ET120, 09-
ET110, 14-ET1B0A, 14-ET1B0C, 14-ET100A, 14-ET100C, 14-ET110A, 14-ET110C, 14-
ET120A, 14-ET120C, 14-ET130A, 14-ET130C, GEN-ET504
Specifications: 28 13 00 Physical Access Control System Add#1
Access control information changed for TR. See Attachment 06.
Attachments
No. 01 – Specification 08 71 00 – Door Hardware
No. 02 – Architectural Sheet 14-AE600
No. 03 – Architectural Sheet 03-AE600
No. 04 – Specification 01 45 35 – Special Inspections
No. 05 – Electrical Sheets 01-EP120, 01-EP130, 01-EP150, 01-EP604, 01-EP605
No. 06 – Electrical Sheets 01-ET100A, 01-ET100C, 01-ET110A, 01-ET110C, 01-ET110D, 01-ET120A, 01-ET120C, 01-ET130A, 01-ET130C, 01-ET140A, 01-ET140C, 01-
ET150B, 03-ET100A, 03-ET100B, 03-ET110A, 03-ET110B, 03-ET120A, 03-ET120B,
05-ET110, 07-ET110A, 08-ET120, 09-ET110, 14-ET1B0A, 14-ET1B0C, 14-ET100A,
14-ET100C, 14-ET110A, 14-ET110C, 14-ET120A, 14-ET120C, 14-ET130A, 14-
ET130C, GEN-ET504
Specifications 28 13 00 Physical Access Control System Add#1
End of Addendum No. 01
ATTACHMENT 01
05-01-22
EHRM INFRASTRUCTURE UPGRADES, GEORGE E. WAHLEN VAMC (ISSUED FOR CONSTRUCTION)
PROJECT # 660-21-700
08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
Caulking: Section 07 92 00 JOINT SEALANTS.
Application of Hardware: Section 08 14 00, WOOD DOORS Section 08 11 13
Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.
Painting: Section 09 91 00, PAINTING.
E. Electrical: Division 26, ELECTRICAL.
F. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
All hardware shall comply with ABAAS, (Architectural Barriers Act
Accessibility Standard) unless specified otherwise.
Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
PROJECT # 660-21-700
08 71 00-2
1.4 WARRANTY
Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled
"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name and
Catalog
No.
Key
Control
Symbols
UL Mark
(if fire rated and listed)
ANSI/BHMA
Finish
Designation
Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
PROJECT # 660-21-700
08 71 00-3
Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
COR for reference purposes. Tag shall identify items by Project
Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and
Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols
PROJECT # 660-21-700
08 71 00-4 for hardware sets consist of letters (e.g., "HW") followed by a number.
Each number designates a set of hardware items applicable to a door type.
Keying: All cylinders shall be keyed into existing Great Grand Master
Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset.
Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.
Keying: A new Great Grandmaster key shall be established for this project. The key system shall be small format (Best size and profile) removable core type as previously described. The key blanks shall be protected by a utility patent with a minimum seven years remaining on the patent from the start of construction and protected by contract-controlled distribution. The manufacturer shall furnish code pattern listings in both paper and electronic formats so keys may be reproduced by code.; provide electronic format in file type required by project’s key control software. The manufacturer shall design the new key system with the capacity to rekey the existing system and also provide for 25 percent expansion capability beyond this requirement. Submit a keying chart for approval showing proposed keying layout and listing expansion capacity.
1. Keying information will be furnished to the Contractor by the COR.
2. Supply information regarding key control of cylinder locks to manufacturers of equipment having cylinder type locks. Notify COR immediately when and to whom keys or keying information is supplied.
Return all such keys to the COR.
1.10 APPLICABLE PUBLICATIONS
The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
ASTM International(ASTM):
F883-13.................Padlocks
E2180-18................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
PROJECT # 660-21-700
08 71 00-5
American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 BUTT HINGES
ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of
PROJECT # 660-21-700
08 71 00-6 butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.
Provide quantity and size of hinges per door leaf as follows:
1. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
2. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
3. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
4. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
5. Provide heavy-weight hinges where specified.
6. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.
See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.2 DOOR CLOSING DEVICES
Closing devices shall be products of one manufacturer for each type specified.
2.3 OVERHEAD CLOSERS
Conform to ANSI A156.4, Grade 1.
Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
PROJECT # 660-21-700
08 71 00-7
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.4 DOOR STOPS
Conform to ANSI A156.16.
Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
PROJECT # 660-21-700
08 71 00-8
Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.
Omit stops where floor mounted door holders are required and where automatic operated doors occur.
Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.5 OVERHEAD DOOR STOPS AND HOLDERS
Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.6 FLOOR DOOR HOLDERS
Conform to ANSI Standard A156.16. Provide extension strikes for Types
L01301 and L01311 holders where necessary.
PROJECT # 660-21-700
08 71 00-9
2.7 LOCKS AND LATCHES
Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System.
Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel.
Provide sectional (lever x rose) lever design matching [__________].
No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension.
Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latch sets shall be furnished with
122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm
PROJECT # 660-21-700
08 71 00-10
(7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design.
Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)
3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
2.8 ELECTROMAGNETIC LOCKS
ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product
Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 1500 pound force (6672 N) 1000 pound force
(4448 N),500 pound force (2224 N).
3. Inductive Kickback Peak Voltage: Not more than 53V.
4. Residual Magnetism: Not more than 4-pound force (18 N) 0 pound force
(0 N) to separate door from magnet.
Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's
"Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 pound force (67 N) for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
2.9 ELECTRIC STRIKES
ANSI/ BHMA A156.31 Grade 1.
General: Use fail-secure electric strikes at fire-rated doors.
PROJECT # 660-21-700
08 71 00-11
2.10 KEYS
Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
Psychiatric keys shall be cut so that first two bittings closest to the key shoulder are shallow to provide greater strength at point of greatest torque.
2.11 KEY CABINET
ANSI Standard A156.11. Provide key cabinet made of cold rolled, 1.2 mm
(0.0478 inch) thick furniture steel electro-welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam and mechanical pushbutton door lock. Key Cabinet and Key Control System shall accommodate all keys for this project plus 25 percent. Provide minimum number of multiple cabinets where a single cabinet of largest size will not accommodate the required number of keys.
Key tags shall consist of two sets: Permanent self-locking and loan key snaphook type with tag colors as follows: Red fiber marker of the permanent self-locking type approximately 32 mm (1-1/4 inch) in diameter engraved with the legend "FILE KEY MUST NOT BE LOANED." Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with the legend "LOAN KEY."
The manufacturer of the lock cylinders and locks shall attach a key tag to keys of each lock cylinder and shall mark thereon the respective item number and key change number. Provide each group of keys in a key gathering envelope (supplied by Key Cabinet Manufacturer) in which the lock manufacturer shall include the following information: Item number, key change number and door number. The contractor shall furnish the Key
Cabinet Manufacturer the hardware and keying schedules and change keys.
PROJECT # 660-21-700
08 71 00-12
The Key Cabinet Manufacturer shall set up a three-way cross index system, including master keys, listing the keys alphabetically, the hooks numerically and the key changes numerically on different colored index cards. Index cards shall be typewritten and inserted in a durable binder. Attach the keys to the two sets of numbered tags supplied with the cabinet. (The permanent tag and the loan key tag). Instruct the owner in proper use of the system. Install cabinet as directed by the
COR.
2.12 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
Conform to ANSI Standard A156.6.
Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be
152 mm (6 inches) high. Both kick and mop plates shall be minimum
1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors
PROJECT # 660-21-700
08 71 00-13 equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.
5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.
6. Provide stainless steel edge guards where so specified at wood doors.
Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
2.13 FLUSH BOLTS (LEVER EXTENSION)
Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI
A156.16, for flush bolts required on lower part of doors.
Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).
2.14 FLUSH BOLTS (AUTOMATIC)
Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
PROJECT # 660-21-700
08 71 00-14
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.15 DOOR PULLS WITH PLATES
Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by
381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
2.16 PUSH PLATES
Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by
406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
2.17 COMBINATION PUSH AND PULL PLATES
Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.18 COORDINATORS
Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
PROJECT # 660-21-700
08 71 00-15
2.19 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR SOUND
CONTROL DOORS
Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).
2.20 MISCELLANEOUS HARDWARE
Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):
Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.
Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as otherwise specified. Provide cylinders to operate locking devices where specified for following partitions and doors:
1. Folding doors and partitions.
2. Wicket door (in roll-up door assemblies).
3. Slide-up doors.
4. Swing-up doors.
5. Fire-rated access doors-Engineer's key set.
6. Doors from corridor to electromagnetic shielded room.
7. Day gate on vault door.
Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers
Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and
2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame.
2.21 FINISHES
Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
PROJECT # 660-21-700
08 71 00-16
626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
Miscellaneous Finishes:
1. Hinges --interior doors: 652 or 630.
2. Pivots: Match door trim.
3. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
4. Cover plates for floor hinges and pivots: 630.
5. Other primed steel hardware: 600.
Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.
Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors.
Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.
Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
2.22 BASE METALS
Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.
Hardware Heights from Finished Floor:
1. Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches).
PROJECT # 660-21-700
08 71 00-17
2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).
3. Deadlocks centerline of strike 1219 mm (48 inches).
4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.
5. Centerline of door pulls to be 1016 mm (40 inches).
6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.
7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.
Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)
45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)
125 mm (5 inches)
35 mm (1-3/8 inch)
(hollow core wood doors)
Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)
Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by
COR. Existing hinges shall not be reused on door openings having new
PROJECT # 660-21-700
08 71 00-18 doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.
Hinges Required Per Door:
Door Description Number butts
Doors 1500 mm (5 ft) or less in height 2 butts
Doors over 1500 mm (5 ft) high and not over 2280 mm
(7 ft 6 in) high
3 butts
Doors over 2280 mm (7 feet 6 inches) high 4 butts
Dutch type doors 4 butts
Doors with spring hinges 1370 mm (4 feet 6 inches) high or less
2 butts
Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts
Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.
After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements.
(All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance
PROJECT # 660-21-700
08 71 00-19 procedures, to satisfaction of Resident/Project Engineer and VA
Locksmith.
3.5 HARDWARE SETS
Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator
EMCH = Electro-Mechanical Closer-Holder
MHO = Magnetic Hold-Open (wall- or floor-mounted)
INTERIOR SINGLE DOORS
Set: B01-1
Doors: 1C06-01, GC01A-01, GC10-01, GC10B-01, GC10C-01, GC10CA-01, GA14C-03, 1A15D-09, 2C16-14, 3A12-14, BA05-14, GB07C-14, GB30-14
Description: int sing wd/hm x hm, storeroom
3 Hinge (A8112) TA2714 US26D MK
Storeroom/Closet Lock
(F86)
10XG04 LL US26D SA
1 Cylinder & Core as req'd to match facility standard
626 AA
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
1 Wall Stop (L02251) 403 US26D RO
Adhesive Gasketing
(R0Y154)
S88BL PE
PROJECT # 660-21-700
08 71 00-20
Set: B01-2
Doors: 2A11A-01, 3A20-01, 4A11B-01, 5B08-01, 1B10-03, 1B12-03, 1B14-03, 1D01-
03, 2C20-14, 3A28A-14
Description: int sing hm x hm, office
1 Entry/Office Lock (F109) 10XG05 LL US26D SA
1 Cylinder & Core as req'd to match facility standard
626 AA
1 Wall Stop (L02251) 403 US26D RO
1 Acoustic Seal Set PEMKOSTCSET-1A BL PE
PROJECT # 660-21-700
08 71 00-21
Set: B01-3
Doors: 1A04-01, 1A15A-01, 1D42B-01, 1E02-01, 2A11-01, 2C08-01, 3A11B-01, 3A11C-01, 3C08A-01, 4A05A-01, 4A11A-01, 4C08-01, 5B08A-01, GA16-01, GC01-01, 1A13B-03, 1B13-03, 2A15B-03, 2B07-03, GA12C-03, GB09-03, 1A02A-07, 2A08A-08, 1A15C-09, 1A16-14, 1C26-14, 2A17-14, 2C18A-14, 2C32-14, 3A08-14, 3C16-14, BA04F-14, GA24-14, GA28-14, GC31-14
Description: int sing wd x hm, CR
1 Access Control Mort Lock SN200-82271-24V LNL US26D SA
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
1 Wall Stop (L02251) 403 US26D RO
Adhesive Gasketing
(R0Y154)
S88BL PE
1 Frame Harness QC-C1500P MK
1 Door Harness QC-C___ MK
1 Card Reader BY SECURITY INTEGRATOR
1 Power Supply AQD series SU
1 Electric Power Transfer EL-CEPT 630 SU
Set: B01-4
Doors: 3C06-01, 3C08-01, 4A12-01, 1A14-14
Description: int sing wd x hm, passage
1 Passage Latch (F75) 10XU15 LL US26D SA
1 Acoustic Seal Set PEMKOSTCSET-1A BL PE
PROJECT # 660-21-700
08 71 00-22
Set: B01-5
Doors: 2C08A-01, 2D02A-01, 1B14A-03, 1B16-03
Description: int sing wd x hm, push pull
3 Hinge (A8111) T4A3786 US26D MK
1 Push Plate (J301) 70C-RKW US32D RO
1 Pull Plate (J405) 111x70C US26D RO
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
3 Silencer (L03011) 608 RO
Set: B03-1
Doors: 1A13A-03
Description: int sing wd/hm x hm, storeroom
Storeroom/Closet Lock
(F86)
10XG04 LL US26D SA
1 Cylinder & Core as req'd to match facility standard
626 AA
1 Overhead Stop (C01541) 1ADJ-X36 652 RF
Adhesive Gasketing
PROJECT # 660-21-700
08 71 00-23
Set: B03-4
Doors: 2B06-03, 2A08-08, 2A12-08, GB26-14
Description: int sing wd/hm x hm, office
1 Entry/Office Lock (F109) 10XG05 LL US26D SA
1 Cylinder & Core as req'd to match facility standard
626 AA
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
1 Wall Stop (L02251) 403 US26D RO
Adhesive Gasketing
Set: B03-6
Doors: 1A12-05
Description: int sing wd x hm, CR
1 Electric Power Transfer EL-CEPT 630 SU
1 Access Control Mort Lock SN200-82271-24V LNL US26D SA
Surface Closer (C02021-Spg
Stop)
CPS7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
Adhesive Gasketing
(R0Y154)
S88BL PE
1 Frame Harness QC-C1500P MK
1 Door Harness QC-C___ MK
1 Card Reader BY SECURITY INTEGRATOR
1 Power Supply AQD series SU
PROJECT # 660-21-700
08 71 00-24
Set: B03-9
Doors: GB02A-03
Description: int sing wd/hm x hm, office
Flush Bolt (A156.3 Type
25) 2842 / 2942 as req'd US26D RO
1 Dust Proof Strike (L04021) 570 US26D RO
1 Entry/Office Lock (F109) 10XG05 LL US26D SA
1 Cylinder & Core as req'd to match facility standard
626 AA
Coordinator (A156.3 Type
21A) 2600 series US28 RO
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
1 Wall Stop (L02251) 403 US26D RO
Adhesive Gasketing
PROJECT # 660-21-700
08 71 00-25
Set: B14-1
Doors: 3A26-14, 3A28-14
Privacy Lock (F22 w/
Indicator)
V21 8265 LNL US26D SA
Surface Closer (C02011 /
C02021)
R 7500 / PR 7500 689 NO
1 Kick Plate (J102) K1050 10" BEV CSK US32D RO
1 Adhesive Gasketing (R0Y154) S88BL PE
Set: B14-2
Doors: 2C18-14
1 All Hardware Hardware by door manufacturer
OT
- - - E N D - - -
ATTACHMENT 02
DE1
H E
IG
H
T
WIDTH
DE2
H E
IG
H
T
WIDTH
DE3
H E
IG
H
T
WIDTH
9" 9"
2' -1
3'
-6
9"
2' -1
3'
-6
A
HOLLOW METAL
(PAINT)
VARIES
7'
2"
2"
2"
B
HOLLOW METAL
(PAINT)
5' - 0"
7'
2"
2"
2"
1/2" 1/2"
5/ 8"
2"
DEPTH
1 15/16" 1 9/16"
2" 5/
8"
1 9/16"1 15/16"
DEPTH
FP1 FP2
7/
" B A
C K
B E
N D
1/2" 1/2"
SIGNAGE GENERAL NOTES
1. CONTRACTOR TO COORDINATE SIGNAGE TYPE, SIZE, MATERIALS, FONTS, COLORS AND
VERBIAGE WITH VA INTERIOR DESIGNER.
2. CONTRACTOR TO INCLUDE A TOTAL ALLOWANCE OF $12,500 FOR PROJECT SIGNAGE.
RAND M.
EARDLEY
128806
S T
OF
A T
E UTA
H
ARED CH
IT
E C T
N S
C E
L I
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
A u to d e s k D o c s /2
S
L C
V A
M C
E H
R M
I n fr a s tr u c tu re U p g ra d e s /B ld g
A
R C
H .r v t
/1
/2
:0
:0
P
M
14-AE600
SCHEDULES EHRM INFRASTRUCTURE
UPGRADES
SALT LAKE CITY, UT 84148
660-21-700
BUILDING 14
08 JUN 2023 PURCELL ROOKER
06/08/23
GRAPHIC SCALE 3/8" = 1'-0"
4'2'0" 1' 8'1'32"
0' 3" 9" 16"
GRAPHIC SCALE 3" = 1'-0"
1'6"
3/8" = 1'-0"1
DOOR ELEVATIONS
3/8" = 1'-0"2
FRAME ELEVATIONS
3" = 1'-0"3
FRAME PROFILE
AQUISITIONAL CODE
A CONTRACTOR FURNISHED AND INSTALLED
B GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
C GOVERNMENT FURNISHED AND INSTALLED
JSN CATEGORIES
A ARCHITECTURAL
F FURNITURE AND FURNISHING
M MISCELLANEOUS
P PLUMBING FIXTURES
U USER SPECIFIC ITEMS
LEGEND OF UTILITIES
1 - PLUMBING (WATER AND DRAINAGE)
A HOT AND COLD WATER
B COLD WATER AND DRAIN
C HOT WATER AND DRAIN
D COLD AND HOT WATER AND DRAIN
E TREATED WATER AND DRAIN
F COLD, HOT AND TREATED WATER AND DRAIN
G COLD AND TREATED WATER AND DRAIN
H HOT AND TREATED WATER AND DRAIN
I DRAIN ONLY
J COLD WATER ONLY
2 - ELECTRICAL
A 120 VOLT, CONVENTIONAL OUTLET
B 120 VOLT, SPECIAL OUTLET
C 208/220 VOLT
D 120 AND 208/220 VOLT
E 440 VOLT, 3 PHASE
F SPECIAL ELECTRICAL REQUIREMENTS
G 208/220 VOLT, 3 PHASE
DOOR SCHEDULE
tt WIDTH HEIGHT THICK TYPE
DOOR
ELEV. DOOR MAT'L & FIN. FRAME MAT'L & FIN
FRAME
PROFILE
FRAME
ELEVATION
FIRE
RATE HDWR REMARKS
1A14-14 3' - 0" 7' - 0" 1 3/4" HINGED DE2 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A B01-4 TEMPERED GLASS
1A16-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
1C26-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
2A17-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
2C16-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A B01-1
2C18-14 3' - 0" 7' - 0" - - - METAL - PAINTED - PT-5 FP2 A B14-2 FRAME ONLY
2C18A-14 3' - 8" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL, FIRE RATED GLASS (NO
WIRE), TEMPERED GLASS
2C20-14 3' - 0" 7' - 0" 1 3/4" HINGED DE2 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A B01-2 SOUND RATED, TEMPERED GLASS
2C32-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
3A08-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL, NOTE 1
3A12-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B01-1 NOTE 1
3A26-14 3' - 0" 7' - 0" 1 3/4" HINGED DE2 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B14-1 SOUND RATED, TEMPERED GLASS, NOTE 1
3A28-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B14-1 NOTE 1
3A28A-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B01-2 NOTE 1
3C16-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
BA04F-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
BA05-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 - - B01-1 EXISTING DOOR AND FRAME TO REMAIN
GA24-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
GA26-14 3' - 0" 7' - 0" 1 3/4" HINGED DE2 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B03-4 SOUND RATED, TEMPERED GLASS
GA28-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
GA30-14 3' - 6" 7' - 0" 1 3/4" HINGED DE1 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 A B01-1
GB07C-14 3' - 0" 7' - 0" 1 3/4" HINGED - GLAZING DE3 WOOD STAINED - WS-1 METAL - PAINTED - PT-5 FP2 B 20 MIN B01-1 SMOKE BARRIER, 45 MIN. RATED GLASS, DOOR AND SIDE LITE GLASS
TO BE TRANSLUCENT
GC31-14 3' - 0" 7' - 0" 1 3/4" HINGED DE1 METAL - PAINTED - PT-5 METAL - PAINTED - PT-5 FP2 A 45 MIN B01-3 DOOR SECURITY: CARD READER, C LABEL
EQUIPMENT SCHEDULE
COUNT JSN DESCRIPTION CLR
UTILITY REQUIREMENTS
COMMENTS1 2 3 4 5 6
16 A1030 Locker, 2 Person, Over / Under C - - - - - -
1 A5075 Dispenser, Soap, Disposable C - - - - - -
1 A5080 Dispenser, Paper Towel, SS, Surface Mounted C - - - - - -
2 A5109 Grab Bar, 1-1/4" Dia., SS, 2 Wall, W/C Accessible A - - - - - - 36" LENGTH, BLOCKING REQUIRED
3 A5135 Shelf, Utility W/ MOB / Broom Holders, SS, Surf Mntd. C - - - - - -
3 F0500 Cart, Janitors C - - - - - -
2 F0505 Bucket, Mop, With Wringer, 26 Quart C - - - - - -
2 F2020 Can, Trash, 44 Gallon C - - - - - -
1 M2055 Shelving, Storage, With Adjustable Shelves A
1 P3100 Lavatory, Vitreous China, Slab Type A D - - - - -
2 P4700 Sink, Mop, Molded Stone A D - - - - -
2 U0001 Open Metal Cabinet C - - - - - -
1 U0002 Plastic Rack C - - - - - -
3 U0003 Wall Shelf C - - - - - -
1 U0005 Lavatory, Pedal Operated, Vitreous China, Slab Type A D - - - - -
2 U0007 Flushable, Wall Mounted Utility Sink, Pedal Operated B
1 U0008 Vernacare 400+, Pulp Product Bedpan Disposer B B A - - - -
ROOM FINISH SCHEDULE
ROOM # ROOM NAME
FLOOR
FINISH
BASE FINISH
WALLS CEILING
FINISH
REMARKS
NE SE SW NW
1A00-14 CORRIDOR - NOTE 4 NOTE 4 NOTE 4 NOTE 4 NOTE 4 - RB-1 AND PT-1
1A14-14 TREATMENT ROOM - RB-1 PT-1 PT-1 - PT-1 - -
1A16-14 TELECOMMUNICATIONS ROOM RF-2 RB-1 PT-1 PT-1 PT-1 PT-1 - -
1C00C-14 CORRIDOR - RB-1 PT-1 - - - - -
1C22-14 CONFERENCE (151) - NOTE 5 NOTE 5 NOTE 5 NOTE 5 NOTE 5 - RB-1 AND PT-1
1C26-14 TELECOMMUNICATIONS ROOM RF-2 RB-1 PT-1 PT-1 PT-1 PT-1 - -
2A17-14 TELECOMMUNICATIONS ROOM RF-2 RB-1 PT-1 PT-1 PT-1 PT-1 - -
2B00C-14 CORRIDOR - NOTE 4 NOTE 4 NOTE 4 NOTE 4 NOTE 4 - RB-1 AND PT-1
2C00-14 CORRIDOR - RB-1 PT-1 - - - - -
2C…