This document provides details for a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in Hines, Illinois. The solicitation number is 36C77623B0043 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The related file is a set of drawings for the project titled "Attachment 21 - Drawings - 578-701.T.20230531_1.pdf" and is 19MB in size. The opportunity is for infrastructure upgrades to the EHRM system at the Hines VA location. Responses are due based on the dates outlined in the solicitation document.
View the file
Other files for this federal contract opportunity
Show all 50
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:
EQUIPMENT
LIST ABBREV.:
#D
#D
#D-GWAP 1.
CEILING INFORMATION OUTLET, DATA
COMMUNICATION, GUEST WIRELESS ACCESS POINT
SC-IO-C
1.WALL INFORMATION OUTLET, DATA COMMUNICATIONSC-IO-W
1.
FLOOR INFORMATION OUTLET, DATA COMMUNICATION
ONLY
SC-IO-F
#D-WAP
1.
CEILING INFORMATION OUTLET, DATA
COMMUNICATION ONLY, WIRELESS ACCESS POINT
SC-IO-C
#D 1.
CEILING INFORMATION OUTLET, DATA
COMMUNICATION ONLY
SC-IO-C
M
T
M
T
M
T
M 2.AC-CR1
2.ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M = MOUNT
C - CEILING D - DESK F - FLUSH H - HIDDEN
M-MULLION
P - PEDESTAL R - RACK S - SURFACE W - WALL
T = TECHNOLOGY/TYPE
D - DEADBOLT H - HYBRID L - LATCH SET
M - MAGNATIC S - STRIKE
AC-EDH
2.REQUEST TO EXIST; LETTER INDICATES AS FOLLOWS:
M = MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T = TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
AC-REX
2.DOOR CONTACT; LETTER INDICATES AD FOLLOWS:
M = MOUNT
S - SURFACE R - RECESSED
T = TECHNOLOGY/TYPE
M = MAGNETIC REED
AC-DC
CARD ACCESS READER WITH KEYPAD; LETTER
INDICATES AS FOLLOWS:
M = MOUNT
C - CEILING D - DESK F- FLUSH H - HIDDEN M -
MULLION
P - PEDESTAL R - RACK S - SURFACE W - WALL
CSS 2.CONTROLLED SECURITY SCHEME SCHEDULE
IDENTIFIER
N/A
M
T
2.MOTION DETECTOR; LETTER INDICATES AD FOLLOWS:
M = MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T = TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE
U-ULTRASONIC X-REQUEST-FOR-EXIT
AC-MD
M 2.AC-KP ACCESS KEYPAD; LETTER INDICATES AS FOLLOWS:
M = MOUNT
C - CEILING D - DESK F- FLUSH H - HIDDEN M -
MULLION
P - PEDESTAL R - RACK S - SURFACE W - WALL
CCTV 3.
VIDEO SURVEILLANCE CAMERA WITH LENS, WALL
MOUNT OR CEILING MOUNTVS-CM-1
#D
#V
#D#V
#D #V
CEILING INFORMATION OUTLET, COMBINATION
TELEPHONE/DATA COMMUNICATION - EXISTING
N/A
WALL INFORMATION OUTLET, COMBINATION
TELEPHONE/DATA COMMUNICATION - EXISTING
N/A
WALL INFORMATION OUTLET, TELEPHONE
COMMUNICATION - EXISTING
N/A
FLOOR INFORMATION OUTLET, DATA COMMUNICATION
ONLY - EXISTING
N/A
#D-WAP
WIRELESS ACCESS POINT, DATA COMMUNICATION
ONLY - EXISTING
N/A
#D
WALL INFORMATION OUTLET, DATA COMMUNICATION -
EXISTING
N/A
#D-GWAP
GUEST WIRELESS ACCESS POINT, DATA
COMMUNICATION - EXISTING
N/A
#D
CEILING INFORMATION OUTLET, DATA
COMMUNICATION ONLY - EXISTING
N/A
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED
ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
GENERAL NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE
DESCRIPTION AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON
THE SHEET INDEX. REFER TO THE TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE
KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL
INFORMATION.
4. REFER TO RISERS ON SHEET(S): TI404, TI500, TI501, B228-TN400
TECHNOLOGY SYMBOL NOTES:
1. "#D" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO
INFORMATION OUTLET SCHEDULE ON TI600 FOR ADDITIONAL INFORMATION.
2. REFER TO 4/TI400 CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL FOR
ADDITIONAL INFORMATION.
3. "CM-#" ON FLOOR PLANS INDICATES CAMERA TYPE AND IS ASSOCIATED WITH THE
CORRESPONDING "VS-CM-#" EQUIPMENT SCHEDULE ABBREVIATION. "##-##" SUBSCRIPT
INDICATES FLOOR NUMBER-CAMERA NUMBER. REFER TO INDIVIDUAL CAMERA
REQUIREMENT SCHEDULE ON B###-TN400 FOR ADDITIONAL INFORMATION. B###
REPRESENTS BUILDING NUMBER.
CABLE TRAY, CHANNEL TRAY, BASKET
TRAY
LADDER RACK
WIDTH X HEIGHT
WIDTH X HEIGHT
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
CM-#
TECHNOLOGY ABBREVIATION KEY
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS OTHERWISE NOTEDUON
TECHNOLOGY GENERAL NOTES:
1. ###-### INDICATES TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT
LIST ABBREVIATION"
2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
S MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM
OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE
OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING
THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO
ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION
DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN
ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. THE TECHNOLOGY CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
THE CEILINGS, CEILING TILES, AND CEILING GRID ASSOCIATED WITH THE AREAS OF WORK
BY ALL CONTRACTORS.
9. ALL LADDER RACK AND CABLE TRAY SIZES ARE AS DEFINED ON THE DRAWINGS. REFER TO
SPECIFICATION SECTION 27 05 33 FOR APPROVED MANUFACTURERS AND INSTALLATION
REQUIREMENTS.
10. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
11. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES
DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE
RATING, AND FINISH.
12. STAIRWELLS SHALL NOT BE USED FOR ROUTING UTILITIES OR CABLING UNLESS NOTED
OTHERWISE.
13. SCOPE OF WORK INCLUDES RE-USE OF EXISTING TELECOMMUNICATIONS OUTLET ROUGH-
IN FOR NEW CATEGORY 6A CABLING. NEW CATEGORY 6A CABLING AT EXISTING OUTLET
LOCATIONS SHALL BE AS FOLLOWS:
• EXISTING 3/4" CONDUIT ROUGH-IN LOCATIONS TO RECEIVE A MAXIMUM OF TWO (2) CAT
6A CABLES.
• EXISTING 1" CONDUIT ROUGH-IN LOCATIONS TO RECEIVE A MAXIMUM OF FOUR (4) CAT
6A CABLES.
• PROVIDE NEW CONDUIT AND BACKBOX AT LOCATIONS EXCEEDING THE REQUIREMENTS
LISTED ABOVE. NEW CONDUIT SIZE SHALL BE BASED ON 40% FILL, TAKING INTO
CONSIDERATION THE DERATING OF THE CONDUIT CAPACITY FOR EACH 90 DEGREE
BEND.
14. FOR EXISTING ROUGH-IN WITH SHALLOW BACK BOXES: PROVIDE A SURFACE MOUNT
BACKBOX INSTALLED OVER TOP OF EXISTING IN-WALL BACKBOX (LEVITON 42777 OR SIM).
WITH AN ANGLED FACEPLATE (LEVITON 42081 SERIES OR SIM) TO ALLOW FOR BEND RADIUS
OF NEW CAT 6A CABLING.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CABLE LOCATIONS WITHIN FURNITURE
AND WILL BE RESPONSIBLE FOR ALL FURNITURE MOVES TO COMPLETE THE INSTALLATION.
16. SCOPE OF WORK INCLUDES PROVIDING NEW SLEEVES WHERE REQUIRED FOR A
COMPLETE INSTALLATION.
TECHNOLOGY INSTALLATION NOTES:
1. REFER TO SPECIFICATIONS APPENDIX FOR PHASING INFORMATION.
TECHNOLOGY PHASING NOTES
1. THE LOCATION OF THE CONDUIT, HAND HOLES AND/OR MAINTENANCE HOLES SHOWN ARE
APPROXIMATE LOCATIONS. FIELD VERIFY THE LOCATION OF ALL UTILITIES PRIVATE AND/OR
PUBLIC PRIOR TO THE INSTALLATION OF THE COMPONENT. FIELD COORDINATE THE FINAL
LOCATION WITH THE OWNER AND ENGINEER PRIOR TO INSTALLATION.
2. POTHOLING TO LOCATE EXISTING UNDERGROUND UTILITIES, IF APPLICABLE, SHALL BE
INCLUDED IN THE CONTRACTOR'S BID. CONTRACTOR IS RESPONSIBLE FOR FINAL
PLACEMENT OF HAND HOLES AND/OR MAINTENANCE HOLES AND SHALL NOTIFY THE
ENGINEER OF FINAL LOCATIONS PRIOR TO INSTALLATION.
3. HAND HOLES AND/OR MAINTENANCE HOLES SHALL BE CONSTRUCTED SO THAT THE TOP OF
THE FRAME WILL BE FLUSH WITH THE GROUND LINE.
4. REMOVAL AND REPLACEMENT OF THE EXISTING UNDERGROUND UTILITIES THAT ARE
REQUIRED TO COMPLETE THE INSTALLATION SHALL BE INCLUDED IN THE CONTRACTOR'S
BID.
5. CONTRACTOR SHALL INCLUDE IN THEIR BID ANY REMOVAL AND REPLACEMENT OF EXISTING
SIDEWALK, PAVEMENT, GRASS, SHRUBS, TREES, ETC. THAT WILL BE IMPACTED BY THE
INSTALLATION OF THE NEW CONDUITS SHOWN ON THE DRAWINGS. IF TREES ARE REQUIRED
TO BE REMOVED THE CONTRACTOR SHALL CONTACT THE OWNER AND DISCUSS OPTIONS
PRIOR TO CUTTING DOWN ANY TREE OR SHRUB OVER 5' IN HEIGHT.
6. NO ADDITIONAL COST SHALL BE APPROVED FOR PLACING CONDUITS DEEPER THAN
REQUIRED MINIMUM DEPTH.
7. PROVIDE A MINIMUM OF 25'-0" SLACK LOOP WITHIN EACH HAND HOLES AND/OR
MAINTENANCE HOLES. SLACK LOOP SHALL BE SECURE SO COPPER OR FIBER IS NOT
RESTING ON EARTH AFTER FINAL INSTALLATION.
TECHNOLOGY OUTSIDE PLANT NOTES
1. THE DRAWINGS INDICATE EXISTING ITEMS TO BE REMOVED. THE DRAWINGS ARE
INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT INDICATE EVERY
BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED. THE CONTRACTOR SHALL VISIT THE
SITE PRIOR TO SUBMITTING A BID AND VERIFY EXISTING CONDITIONS.
2. ITEMS (i.e. SPEAKERS, SWITCHES, ETC.) REMOVED AND NOT RELOCATED REMAIN THE
PROPERTY OF THE OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
DISPOSAL OF MATERIAL THE OWNER DOES NOT WANT TO REUSE OR RETAIN. (i.e., FOR
MAINTENANCE PURPOSES).
3. EXISTING TO REMAIN DEVICES WITHIN OR ADJACENT TO THE PATH OF CONSTRUCTION
SHALL BE PROTECTED IN PLACE. DEVICES THAT MUST BE REMOVED SHALL BE TESTED
PRIOR TO REMOVAL, PROTECTED FROM DAMAGE, AND RE-INSTALLED IN ITS ORIGINAL
LOCATION DURING THE NEW CONSTRUCTION PHASE OF THE PROJECT.
4. OBTAIN APPROVAL FROM THE OWNER BEFORE TURNING OFF THE POWER TO
EQUIPMENT, SYSTEMS, PANELS, ETC. COORDINATE ALL OUTAGES WITH OWNER.
CONDUIT CONCEALED IN WALL CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT
AFFECTED BY OTHER CONSTRUCTION.
5. ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING REMOVED. WHERE
CONDUIT IS IN THE CONCRETE SLAB, CUT OFF FLUSH, PULL OUT WIRE, AND PLUG.
WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED CLAMPS, SUPPORTS, HANGERS,
ETC., SHALL ALSO BE REMOVED.
6. COORDINATE ALL WORK WITH OTHER CONTRACTORS AT THE JOB SITE BEFORE
REMOVING EXISTING EQUIPMENT AND INSTALLING NEW ITEMS.
7. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN PLACE. RELOCATING
EXISTING CONDUIT SHALL NOT BE ALLOWED. BONDING CONDUCTORS SHALL BE
INSTALLED IN ALL REUSED CONDUIT TO ASSURE PROPER GROUND PATH.
8. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS MAY REQUIRE THE INSTALLATION OF A
JUNCTION BOX TO RECONNECT CIRCUITS THAT REMAIN IN OPERATION. EXTEND
CONDUIT AND WIRING AS REQUIRED TO MAINTAIN POWER TO REMAINING EQUIPMENT.
9. DEVICES TO BE REMOVED SHALL HAVE ALL CONNECTED WIRING REMOVED TO THE
SOURCE.
10. DEVICES NOT TO BE REMOVED SHALL BE PROTECTED FROM THE ENVIRONMENT, AND
ALL ASSOCIATED CABLE/RACEWAYS ARE TO REMAIN AND BE PROTECTED. T.C. SHALL BE
RESPONSIBLE FOR REPAIR OF ANY INTERRUPTIONS TO PROTECTED DEVICES.
11. CLAY TILE PARTITIONS - SAW CUT PLASTER AND HOLLOW BUILDING TILE PARTITION AS
REQUIRED FOR MECHANICAL, PLUMBING OR ELECTRICAL WORK. SEE TECHNOLOGY
PLAN(S) FOR ADDITIONAL WORK.
12. GYPSUM BOARD AND METAL STUD PARTITIONS - REMOVE GYP BD ONE SIDE OF
PARTITION AS REQUIRED. SEE TECHNOLOGY PLAN(S) FOR ADDITIONAL WORK.
13. NOTES FOR PATCHING - INFILL GYP WALL OPENING WITH METAL STUDS AND GYP AS
REQUIRED FROM DEMOLITION. PATCH ADJACENT SURFACES WITH MATERIALS TO
MATCH EXISTING, AS REQUIRED. WHERE EXISTING FINISHES ARE DISTURBED PAINT TO
MATCH ADJACENT FINISH, PAINT ENTIRE PARTITION WHERE PATCHING OCCURS.
TECHNOLOGY DEMOLITION NOTES
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
TECHNOLOGY EQUIPMENT SCHEDULE
AND SPECIFICATIONS FOR DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
CABLE TRAY (INCLUDING WIRE BASKET
TRAY) REFER TO SPECIFICATION
SECTION 27 05 28 FOR DEFINITION
T-SERIES E.C. E.C.
LADDER RACK T-SERIES T.C. T.C. 5.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
BONDING SYSTEM FOR TECHNOLOGY
SYSTEM, REFER TO SPECIFICATION
SECTION 27 05 26 FOR DEFINITION
T-SERIES E.C. E.C. 7. 8.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
TECHNOLOGY SERVICE ENTRANCE
CONDUITS, HANDHOLES, AND
MANHOLES
T-SERIES E.C. E.C.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE
BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.
8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN
IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
TELECOM ROOM REFERENCES
TELECOM ROOM
DETAIL / SHEET
REFERENCE
FLOOR PLAN
REFERENCE
ARCH ROOM
NUMBER
TR-200-2-1 1/B200-TN303 B200-TN102A D2312A
TR-200-2-2 5/B200-TN303 B200-TN-102C C2216A
TR-200-2-3 1/B200-TN304 B200-TN102D D2463
TR-200-3-1 5/B200-TN304 B200-TN103 3127
TR-200-4-1 1/B200-TN305 B200-TN104 4112
TR-200-5-1 5/B200-TN305 B200-TN105 564
TR-200-6-1 1/B200-TN306 B200-TN106 672
TR-200-7-1 5/B200-TN306 B200-TN107 772
TR-200-8-1 1/B200-TN307 B200-TN108 858
TR-200-9-1 5/B200-TN307 B200-TN109 953
TR-200-10-1 1/B200-TN308 B200-TN110 1072
TR-200-11-1 5/B200-TN308 B200-TN111 1161
TR-200-12-1 1/B200-TN309 B200-TN112 1272
TR-200-13-1 5/B200-TN309 B200-TN113 1372A
TR-200-14-1 1/B200-TN310 B200-TN114 1472
TR-200-15-1 5/B200-TN310 B200-TN115 1572
TR-205-1-1 4/B205-TN300 B205-TN101 118B
TR-217-1-1 4/B217-TN300 B217-TN101B 1A115A
TR-217-2-1 3/B217-TN301 B217-TN102B 2A26A
TR-220-1-1 4/B220-TN300 B220-TN101A 107C
TR-220-2-1 1/B220-TN301 B220-TN102 203A
TR-221-1-1 1/B221-TN300 B221-TN101A A107B
TR-228-0-1 1/B228-TN300 B228-TN100 B1014A
TR-228-1-1 5/B228-TN300 B228-TN101B 1030
TR-228-1-2 1/B228-TN301 B228-TN101C 1088
TR-228-2-1 5/B228-TN301 B228-TN102B 2025
TR-228-2-2 1/B228-TN302 B228-TN102C 2080
TR-228-3-1 5/B228-TN302 B228-TN103B 3025
TR-228-3-2 1/B228-TN303 B228-TN103C 3080
TR-228-4-1 1/B228-TN304 B228-TN104B 4025
TR-228-4-2 5/B228-TN304 B228-TN104C 4080
TR-228-5-1 1/B228-TN305 B228-TN105B 5019B
TR-228-5-2 5/B228-TN305 B228-TN105C 5044A
TR-BJC-0-1 1/BJC-TN300 BJC-TN100 B041A
TR-BJC-1-1 5/BJC-TN300 BJC-TN101 1014
Grand total: 95
TELECOM ROOM REFERENCES
TELECOM ROOM
DETAIL / SHEET
REFERENCE
FLOOR PLAN
REFERENCE
ARCH ROOM
NUMBER
EXISTING TR-48-1-1 1/B48-TN300 B48-TD101
EXISTING TR-113-1-1 1/B113-TN300 B113-TD101 A119
EXISTING TR-113-1-2 3/B113-TN300 B113-TD101 A139
EXISTING TR-113-2-1 1/B113-TN301 B113-TD102 A233A
EXISTING TR-113-2-2 4/B113-TN301 B113-TD102 A234
EXISTING TR-128-1-1 1/B128-TN300 B128-TD101B A147
EXISTING TR-128-1-2 3/B128-TN300 B128-TD101B A151
EXISTING TR-205-1-1 1/B205-TN300 B205-TD101 118B
EXISTING TR-217-1-1 1/B217-TN300 B217-TD101C 1A37
EXISTING TR-217-2-1 1/B217-TN301 B217-TD102A 2A26
EXISTING TR-220-2-1 1/B220-TN300 B220-TD102 RCC201R
TR-01-1-1 1/B01-TN300 B01-TN101A A117
TR-01-1-2 5/B01-TN300 B01-TN101B B129
TR-01-1-3 1/B01-TN301 B01-TN101C C132C
TR-01-1-4 5/B01-TN301 B01-TN101D D146
TR-01-1-5 1/B01-TN302 B01-TN101F F108L
TR-01-1-6 5/B01-TN302 B01-TN101G RCC157R
TR-01-2-1 1/B01-TN303 B01-TN102A A217
TR-01-2-2 5/B01-TN303 B01-TN102B B227
TR-01-2-3 1/B01-TN304 B01-TN102C C228
TR-01-2-4 5/B01-TN304 B01-TN102D D250A
TR-01-2-5 1/B01-TN305 B01-TN102F F225
TR-01-2-6 5/B01-TN305 B01-TN102G G227
TR-01-3-1 1/B01-TN306 B01-TN103A A317
TR-01-3-2 5/B01-TN306 B01-TN103B B323
TR-01-3-3 1/B01-TN307 B01-TN103C C330D
TR-01-3-4 5/B01-TN307 B01-TN103D D351
TR-01-3-5 1/B01-TN308 B01-TN103F F321D
TR-01-3-6 5/B01-TN308 B01-TN103G G327
TR-01-4-1 1/B01-TN309 B01-TN104A A419
TR-01-4-2 5/B01-TN309 B01-TN104B B423
TR-01-4-3 1/B01-TN310 B01-TN104C C420A
TR-01-4-4 5/B01-TN310 B01-TN104D D423A
TR-01-4-5 1/B01-TN311 B01-TN104F F401B
TR-01-4-6 5/B01-TN311 B01-TN104G G422
TR-02-0-1 1/B02-TN300 B02-TN100 022
TR-02-1-1 5/B02-TN300 B02-TN101 106
TR-02-2-1 1/B02-TN301 B02-TN102 210C
TR-03-1-1 1/B03-TN300 B03-TN101 109A
TR-04-1-1 1/B04-TN300 B04-TN101 107
TR-07-2-1 1/B07-TN300 B07-TN102 210B
TR-08-1-1 1/B08-TN300 B08-TN101 109
TR-09-1-1 1/B09-TN300 B09-TN101 101E
TR-12-2-1 1/B12-TN300 B12-TN102 203
TR-13-2-1 1/B13-TN300 B13-TN102 2
TR-16-2-1 1/B16-TN300 B16-TN102 207
TR-17-2-1 1/B17-TN300 B17-TN102 211
TR-18-3-1 1/B18-TN300 B18-TN103 144
TR-45-1-1 1/B45-TN300 B45-TN101 102
TR-48-1-1 3/B48-TN300 B48-TN101 RCC121R
TR-100-1-1 1/B100-TN300 B100-TN101 17
TR-113-1-1 6/B113-TN300 B113-TN101 A138
TR-113-2-1 1/B113-TN302 B113-TN102 A233A
TR-128-1-1 1/B128-TN301 B128-TN101B A151
TR-200-0-1 1/B200-TN300 B200-TN100B B011A
TR-200-0-2 5/B200-TN300 B200-TN100C C032B
TR-200-0-3 1/B200-TN301 B200-TN100D D008
TR-200-1-1 5/B200-TN301 B200-TN101A A123E
TR-200-1-2 1/B200-TN302 B200-TN101C B105A
TR-200-1-3 5/B200-TN302 B200-TN101D D129A
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .T
R
.r v t
/2
/2
:1
:5
P
M
TI000
TELECOMMUNICATIONS SYMBOLS
AND ABBREVIATIONS
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 PDN JFK
100% FINAL STAMPED
BID DOCUMENTS
1. BID TAB
• THE BIDDING CONTRACTOR SHALL PROVIDE THE FOLLOWING
BID BREAKDOWNS FOR THE PROJECT.
• BASE BID: ALL PROJECT SCOPE NOT SPECIFICALLY
IDENTIFIED AS AN ALTERNATE BID ITEM.
• ALTERNATE BID #1: ALTERNATE BID #1 INCLUDES THE
FOLLOWING ADDITIONAL SPACES NOT ASSOCIATED WITH
THE EHRM PROJECT:
• BUILDING 200 - BASEMENT NURSE STATION
• BUILDING 200 - BASEMENT BREAK ROOM AND OFFICE
• BUILDING 200 - SECOND LEVEL CENTRAL PROCESSING
• BUILDING 200 - SECOND LEVEL PHARMACY OFFICE
• BUILDING 200 - THIRD LEVEL BREAK ROOM
• BUILDING 200 - FOURTH LEVEL BREAK ROOM
• BUILDING 200 - ELEVENTH LEVEL LAUNDRY
• BUILDING 228 - BASEMENT OPEN OFFICE DOOR
• BUILDING 228 - FIRST LEVEL BREAK ROOM & HAC
• BUILDING 228 - FIFTH LEVEL STORAGE
BIDDING NOTES
Revisions: Date:
1 3
4 3
.3
.7
.4
.4 6 6 .9
.2
.4
.6
.0
.3
.2
.2
.7
.7
.6
.2
.7
.6
.0 6 6 .5
.6
.6
.2
.9
.0
.9 8 12
.1
.2
.3
.8
.5
.8
.6
.9
.8
.6
.7
.6
.6
.1
.6
.8
.8
.5
.2
.9
C P T
T O
E A S T
A C R O S S
F
IR
S T
A V E
.8
.5
.2
.0
AREA UNDER
CONSTRUCTION
A R E A
N O T
A C C E S S
IB
L E
NEW
YORK
LOT
TE
NN
ES
SE
E
LO
T
KENTUCKY LOT
MISSOURI LOT
KANSAS LOT
ILLINOIS
LOT
S H
O P
P A
R K
IN
G
HINES BOULEVARD
L O
T
A L A
B A
M A
S T
O R
A G
E
M A
S O
N R
Y
LO
U
IS
IA
N A
LO
T
F
BLDG.1
D
BLDG. 13
B L D
G
SOUTH
DAKOTA
LOT
IOWA
LOT
OFFICE PARKING
COLORADO LOT
C A
L
IF
O R
N
IA
L O
T
NEBRASKA LOT
BLDG.45 BLDG.9
BLDG. 1E
BLDG.8
BLDG.7
BLDG.33
BLDG.5
C B
BLDG. 1
OKLAHOMA LOT
BLDG. 229
BLDG.3
B L D
G . 4
SHOP PARKING
M
IN
N E
S O
T A
L
O T
WISCONSIN
LOT
BLDG.128
BLDG.228
BLDG.200
BLDG.113
PENNSYLVANIA
LOT
V
IR
G
IN
IA
L
O T
BLDG.53*
5TH AVENUE
B L D
G .2
B L D
G .2
BLDG.28
BLDG.27 BLDG.26
B L D
G .2
B L D
G .3
BLDG. 215 LOT
BLDG.215
B L D
G
BLDG.37*
BLDG.217
BLDG.232*
BLDG.220
T H
S T
T H
S T
T
H S
T
SCOTT DRIVE
NINTH AVENUE
T H
S T
C U
M M
IN
G
S W
A Y
IN
D
IA
N
A L
O T
W E
S T
B
"S T
R E
E T
W E
S T
C
S
T R
E E
T
5TH AVENUE
McCOY DRIVE
SOFTBALL FIELD
5TH AVENUE
W E
S T
'G ' S
T R
E E
T
TO EDWARD HINES JR. VA MEDICAL CENTER
FIRST AVENUE
BLDG. 215
LOT
FEARNS DR
S
T H
A V
E
F L O
R
ID
A L
O T
S C
O T
T D
R S
C O
T T
D R
S. 5TH AVE
S. 5TH AVE
W.
R
OO
SE
VE
LT
R D
TRIPP AVE
TRIPP AVE
C R
O S
S M
A N
C
IR
C L E
C R
O S
S M
A N
C
IR
C L E
TRIPP AVE
TRIPP AVE
TRIPP AVE
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
BDLG.18
B L D
G
BLDG. 16
BLDG.12
BLDG.14
T E X A S L
O T
F R
E E
D O
M 'S
P A
T H
H O
U S
IN
F R
E E
D O
M 'S
P A
T H
H
O U
S
B L D
G
B L D
G
B L D
G
BLDG.205
B L D
G .2
4B L D
G .2
B L D
G .3
BLDG. 2
B L D
G . 1
C R
O S
S M
A N
C
IR
C L E
C R
O S
S M
A N
C
IR
C L E
A
IR
M A
IL
R
D
FEARNS DR
S
T H
A V
E
BDLG.18
B L D
G . 17
BLDG. 16
BLDG. 100
W.
R
OO
SE
VE
LT
RD
FEARNS DR
B
LD
G . 2
B
LD
G . 2
B A
S K
ET
B
A
LL
C O
U R
T
C R
O S
S M
A N
C
IR
C
LE
C R
O S
S M
A N
C
IR
C
LE
S T O R A G E
M A S O N R Y
B
LD
G . 2
BLDG.217
FR
E
ED
O
M 'S
P A
TH
H
O U
SI
N
FR
E
ED
O
M 'S
P A
TH
H O
U S
BLDG. 3
BLDG. 128
BLDG. 113
S C
O T
T D
R
S C
O T
T D
R
S C
O T
T D
R S
C O
T T
D R
HINES BLVD
S. 5TH AVE
TRIPP AVE
S. 5TH AVE
TRIPP AVE
TRIPP AVE
TRIPP AVE
TRIPP AVE
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
A
IR
M A
IL
R
D
IL
L
IN
O
IS
L O T
M O N
IT
O R
IN
G
M H
B E N C H M A R K
N W
B O L T
O N
H Y D R A N T
F
LA
N G E
E L E .2
G A S
V A L V E (4
C H A R G
IN
G
S T A T
IO
N
Y A R D
H Y D R A N T
S T A N D
P
IP
E
B E N C H M A R K
N W
F L A N G E
B O L T
O N
H Y D R A N T
E L E V A T
IO
N .6
B L O C K
W A L L
B L O C K
W A L L
S E C U R
IT
Y
K E Y
P O S T
G A S
P U M P
S E C U R
IT
Y
K E Y
P O S T
G A S
P U M P
C O N C R E T E
W A L L
C O N C R E T E
W A L L
C O N C R E T E
W A L L
G A T E
C O N C R E T E
W A L L
C O N C R E T E
W A L L
S T O N E
W A L L
S T O N E
W A L L
S T O N E
W A L L
B L O C K
W A L L
B L O C K
W A L L
B L O C K
W A L L
C O N C R E T E
W A L L
G A T E
B R
IC
K W A L L
B R
IC
K
W A L L
B R
IC
K
W A L L
B E N C H
C O N C R E T E
W A L L
C O N C R E T E
W A L L
C O N C R E T E
W A L L
C O N C R E T E
W A L L
C O N C R E T E
W A L L
G A T E
B E N C H
BE
NC
H
BENCH
B
EN
CH
P L A S T
IC
F E N C E
C O N C R E T E
W A L K
C O N C R E T E
S T E P S
C O N C R E T E
S T A
IR
S
GATE
GA
TE
C H A
IN
LI
N K
F E N C E
C O N C R E T E
W A L L
C O N C R E T E
S T E P S
C O N C R E T E
W A L L
C O N C R E T E
W A L L
C O N C R E
TE
S T E P
C O N C R E
TE
P A D
C O N C R E
TE
P A D
V A U L T
C O N C R E
TE
S T E P
G R A V E L
B L O C K
W A L L
B U S
S H E
LT
E R
SIG
N
H A N D R A
IL
CO
NC
RE
TE
W
AL
K
C O N C R E
TE
S T E P
S
IG
N
V A U L T
C O N C R E
TE
S T E P
GATEBUS SHELTER
G A T E
S
IG
N
C O N C R E T E
W A L L
C O N C R E T E
S T A
IR
V A U L T
CONC STEPS
C O N C R E T E
S T E P S
B
IK
E
R A C K
C O N C
S T E P
C O N C R E T E
S T E P S
C O N C R E T E
W A L L
V A U L T
C H A
IN
LI
N K
FE
N C E G A T E
V A U L T
V A U L T
G A T
EV
A U L T
S T E A M
V E N T
(2
T R A N S F O R M E R
T R A N S F O R M E R
G R A V E L
TI
M B
ER
W
AL
L
PLA
STIC
FE
NCE
E X E R C
IS
E
B E A M
E X E R C
IS
E
E Q U
IP
M E N T
V A U L T
CHAIN LINK FENCE
CHAIN LINK FENCE
S
IG
N
G A T E
G A T E
V A U L T
G A T E
S T A N D
P
IP
E
S
IG
N
SIG
N
S T A N D
P
IP
E
S
IL
L
.4
W E L L
T R A N S F O R M E R
P A D
H A N D R A
IL
C O N C
S T E P S
P O L
IC
E
C A L L
B O X
T R A N S F O R M E R
P A D
C H A
IN
L
IN
K
F E N C E
T R A N S F O R M E R
P A D
C O N C R E
TE
S T E P
S T A
IR
S
C O N C R E T E
W A L L
H A N D R A
IL
S T A
IR
S
H A N D R A
IL
TRANSFORMER PAD
S
IG
N
PLA
NTE
R
PLANTER
PL
AN
TE
R
L A R G E
R O C K
D O W N S P O U T
H A N D R A
IL
S T A N D
P
IP
E
S T A N D
P
IP
E
S T A N D
P
IP
E
SIGN
PL
AN
TE
R
SIGN
P O L
IC
E
C A L L
B O X
B E N C H M A R K
N W
F L A N G E
B O L T
O N
H Y D R A N T
E L E V A T
IO
N .1
T R A N S F O R M E R
P A D
T R A N S F O R M E R
P A D
T R A N S F O R M E R
P A D
S T A N D
P
IP
E
PLANTER
S T A
IR
S T A
IR
S T A N D
P
IP
E
H A N D R A
IL
H A N D R A
IL
S T A
IR
S
H A N D R A
IL
T R A N S F O R M E R
P A D
T R A N S F O R M E R
E M E R G E N C Y
P H O N E
E M E R G E N C Y
P H O N E
B E N C H M A R K
C A L L
B O X
E L E .6
B U S
S H E L T E R
E M E R G E N C Y
P H O N E
E L E C T R
IC
A L
H O U S
IN
G
C O V E R E D
O P E N
IN
G
W A T E R
S P
IG
O T
G A T E
CHAIN LINK FENCE
G A T E
H V A C
P A D
T R A N S F O R M E R
P A D
H V A C
P A D
S T A N D
P
IP
E
H V A C
P A D
CHAIN LINK FENCE
T R A N S F O R M E R
P A D
BENCH
B O U L D E R
M E M O R
IA
L
BEN
CH
B E N C H M A R K
S O U T H E A S T
C O R N E R
O F
S T E P
E L E .6
M E T A L
F E N C E
M E T A L
F E N C E
S
IG
N A L
C O N T R O L
B E N C H
BENCH
P L A S T
IC
F E N C E
B L O C K
W A L L
C H A
IN
LI
N K
F E N C E
C H A
IN
L I N K
FE
N C E
B A S K E T B A L L H O O P
P O L
IC
E
C A L L
B O X
S
IG
N
S
IG
N
SIG
N
S T E P S
V E N T
V E N T
H A N D R A
IL
G U A R D R A
IL
S T E P S
H A N D R A
IL
P L A N T E R
H A N D R A
IL
H A N D R A
IL
P O L
IC
E
C A L L
B O X
PLANTER
P L A N T E R
E M E R G E N C Y
P H O N E
A B A N D O N E D
S T O R M
S T R U C T U R E
B R O K E N
V A L V E
BUS
SHE
LTE
R
C O N C R E T E
ME
TAL
FE
NCE
ME
TA
L
FE
NC
E
C O N C R E T E
W A L L
IN
L E T
O P E N
IN
G
IN
C U R B
IN
L E T
O P E N
IN
G
IN
C U R B
S T E A M
V E N T
S
IG
N
S
IG
N
S
IG
N
SIGN
M O N
IT
O R
IN
G
B E N C H M A R K
S T O P
S
IG
N
E L E .8
B E N C H M A R K
N E
B O L T
O N
H Y D R A N T
F
LA
N G E
E L E .6
SIGN
R A D O N
M
IT
IG
A T
IO
N
C O N C R E T E
C O N C R E T E W A L K
A S P H A
LT
A S P H A
LT
A S P H A
LT
C O N C R E T E W A
LK
C O N C R E T E
W A L K
CONCRETE WALK
CONCRETE WALK
CO
NC
RE
TE
W
AL
K
C O N C R E T E
W A L K
C O N C R E T E W A
LK
A S P H A
LT
A S P H A
LT
A S P H A
LT
G R A V E L
C O N C R E T E
W A L K
CO
NC
RE
TE
W
AL
K
CONCRETE
ASPHALT
A S P H A L T
ASPHALT
A S P H A
LT
C O N C R E T E
CONC WALK
B
RI
C K W
AL
K
CONCRETE WALK
B R
IC
K
A S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
A S P H A L T
ASPHALTASPHALT
CONCRETE
CONCRETE
ASPHALT
CONCRETE
C O N C R
ET
E
C O N C R E T E W A L K
A S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
AS
PH
AL
T
AS
PHA
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
A S
PH
A
LT
A S P H A
LT
C O N C R E T E W A
LK
C O N C R E T E W A
LK
CO
NC
RE
TE
W
AL
K
CO
NC
RE
TE
W
AL
K
CONCRETE WALK
CONCRETE WALKC
O N C R E T E
W A L K
CONCRETE WALK
CONCRETE WALK
CONCRETE WALK
CONCRETE WALK
C O N C R E T E
W A L K
CONCRETE WALK
B R
IC
K
C O N C R E T E
C
ON
C R
ET
E
B R
IC
K
C O N C R E T E W A
LK
GR
AV
EL
GRAVEL
C O N C R E T E
W A L K
A S P H A L T
A S P H A L T
A S P H A
LT
A S P H A
LT
C O N C R
ET
E
W A L K
A S P H A
LT
C O N C R E T E
W A L K
C O N C
W A L K
C O N C R E T E
W A L K
CONCRETE WALK
CONCRETE WALK
C O N C
W A L K
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C
ON
C
C O N C
W A L K
C O N C R E T E
W A L K
CONCRETE WALK
C O N C R E T E
W A L K
C O N C R E T E
W A L K
CONCRETE WALK
C O N C R E T E
W A L K
CONCRETE WALK
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C O N C R E T E
W A L K
CONCRETE WALK
CONCRETE WALK
CONCRETE WALK
C O N C R E T E
W A L K
C O N C R E T E
W A L K
CONCRETE WALK
CONCRETE WALK
CONCRETE WALK
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C O N C R E T E
W A L K
C
ON
CR
ET
E
WA
LK
CONCRETE WALK
CONCRETE WALK
CO
NC
RE
TE
W
AL
K
C O N C R E T E W
A L K
CO
NC
RE
TE
W
AL
K
CONCRETE WAL
K
CONCRETE WAL
K
CONCRETE WALK
C O N C R
ET
E W A
LK
C O N C R E T E
W A L K
A S P H A
LT
BDLG. 1
BDLG. 1
B
LD
G
BLDG. 12
BLDG. 2
(6) 4" C
(4) 4" C
(2) 4" C
8B
(2) 4" C
2B
1A
(2) 4" C
(6) 4" C
(3) 4" C
(6) 4" C
(3) 4" C
(3) 4" C
(2) 4" C
1A
(2) 4" C 1A
(2) 4" C
1A
(2) 4" C
(2) 4" C 1A
3A
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
1A 1B
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
1B
1B
1A
(2) 4"C
(2) 4" C
1A 1B
1B
1B
1B
1A
(2) 4" C
1B
(2) 4" C
PULLBOX
(TYP.)
HAND HOLE
(TYP.)
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
3B
2A
2B
2B
1B
1A
2A
2B
4A
2A
2A
1A
1B
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4"C(2) 4"C
(2) 4"C
(6) 4" C
(3) 4" C
(3) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C (2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
(2) 4" C
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .T
R
.r v t
/2
/2
:1
:0
P
M
TI002
SITE PLAN -
TELECOMMUNICATIONS
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 PDN JFK
100% FINAL STAMPED
BID DOCUMENTS
SCALE: 1" = 130'-0"TI002
1 SITE PLAN - TELECOMMUNICATIONS
0 130' 260'65'
SHEET NOTES:
1. REFER TO CIVIL PLANS FOR EXACT CONDUIT
ROUTING AND QUANTITIES.
2. REFER TO 1/TI401 EXTERIOR HAND HOLE
DETAIL FOR ADDITIONAL INFORMATION.
3. REFER TO 3/TI401 EXTERIOR WALL
PENETRATION DETAIL FOR ADDITIONAL
INFORMATION.
4. CONTRACTOR TO COORDINATE ALL CONDUITS
WITH ALL TRADES AND THE OWNER PRIOR TO
INSTALLATION.
5. REFER TO INDIVIDUAL BUILDINGS FOR
INTERNAL CONDUIT ROUTES.
6. ALL EXTERIOR ANCHORS FASTENED TO THE
BUILDING SHALL BE LOCATED AT THE MORTAR
JOINTS. ANCHORING INTO THE BRICK
SURFACE IS NOT PERMITTED
KEYNOTES:
1. ROUTE "A" LEG FIBERS TO EACH BUILDING.
REFER TO INDIVIDUAL BUILDING FLOOR PLANS
FOR CONTINUATION. REFER TO TI501 FOR
ADDITIONAL INFORMATION.
2. ROUTE "B" LEG FIBERS TO EACH BUILDING.
REFER TO INDIVIDUAL BUILDING FLOOR PLANS
FOR CONTINUATION. REFER TO TI502 FOR
ADDITIONAL INFORMATION.
3. ALL UNDERGROUND CONDUITS SHALL BE
INSTALLED IN CONCRETE ENCASED DUCT
BANK. REFER TO CIVIL DRAWINGS FOR DUCT
BANK AND HAND HOLE DETAILS.
4. ROUTE CONDUITS UP ON THE EXTERIOR SIDE
OF BUILDING 1 TO ABOVE FIRST FLOOR
CEILING. REFER TO B01-TN101G FOR THE
CONTINUATION.
5. ROUTE CONDUITS IN CEILING OF 2ND FLOOR
WALKWAY.
6. ROUTE CONDUITS PAST EXISTING COOLING
TOWER PIPING DOWN TO SUB-BASEMENT 0F
BUILDING 200.
SC-GND-1
NEAREST
ELECTRICAL
PANEL
EQUIPMENT
RACK(S)
SURGE
SUPPRESSION
DEVICE(S)
BUILDING
STEEL
LADDER RACK
(CONTINUOUS
BOND)
METALLIC
CONDUITS
AND SLEEVES
MOLDED POLYESTER -
FIBERGLASS INSULATOR
COPPER GROUND CONDUCTOR FROM
BUILDING SERVICE GROUND. REFER
TO SPECIFICATIONS FOR DETAILS
TWO HOLE
COMPRESSION LUG
NOTES:
1. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE SC-GND-1 FOR
WIDTH REQUIREMENTS.
2. REFER TO 2/TI400 FOR TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
COPPER BONDING CONDUCTOR TO
EQUIPMENT RACKS, CABLE TRAYS
& METALLIC SLEEVES. REFER TO
SPECIFICATIONS FOR DETAILS
BARE COPPER GROUND BAR,
INSULATORS, BRACKETS AND
BONDING PROVIDED BY E.C.
REFER TO TECHNOLOGY
EQUIPMENT SCHEDULE SC-GND-1
5/16" Ø
(TYP)
7/16" Ø
(TYP)
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
TELECOMMUNICATIONS ROOM TR-#, (TYP.) 1
TELECOMMUNICATIONS
BONDING JUMPER (TBJ)
NOTES:
1. THIS FLOW DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS FLOW DIAGRAM IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION.
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM SHALL BE MINIMUM SIZE OF 3/0 AWG PLENUM RATED COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR) UNLESS CONDUCTOR LENGTH IS LESS THAN 66 FEET. REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS LESS THAN 66 FEET IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
3. ALL BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED BY COMPRESSION LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION CONNECTORS. SOLDER IS NOT AN ACCEPTABLE MEANS OF CONNECTION. SHEET METAL SCREWS SHALL NOT BE USED TO CONNECT COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT. WHERE NECESSARY, REMOVE PAINT AND/OR USE PAINT-PIERCING WASHERS TO PROVIDE PROPER ELECTRICAL BOND AT ALL CONNECTIONS.
4. REFER TO 1/TI400 FOR BONDING BUS BAR DETAIL AND ADDITIONAL INFORMATION AND REQUIREMENTS FOR SC-GND-1.
5. REFER TO 2/TI403 PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENT FOR ADDITIONAL INFORMATION.
KEYNOTES:
1. REFER TO TELECOM ROOM REFERENCES SCHEDULE ON DRAWING TI000 FOR TELECOMMUNICATIONS ROOM NUMBER AND
LOCATION INFORMATION.
2. INCLUDES HORIZONTAL AND VERTICAL CONDUIT SLEEVES FOR TECHNOLOGY CABLING.
3. TELECOMMUNICATIONS BONDING BACKBONE (TBB). REFER TO 1/B###-TN400 FOR TELECOMMUNICATIONS BONDING RISER
DIAGRAM. "B###" REPRESENTS BUILDING NUMBER.
4. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT), TO ELECTRICAL ENTRANCE INTERSYSTEM BONDING TERMINATION.
REFER TO 1/B###-TN400 FOR TELECOMMUNICATIONS BONDING RISER DIAGRAM FOR CONTINUATION AND ADDITIONAL
INFORMATION AND REQUIREMENTS. WHERE "B###" REPRESENTS BUILDING NUMBER.
5. REFER TO THE ELECTRICAL DRAWINGS FOR LOCATION.
6. PROVIDE SC-GND-2 RACK MOUNT TELECOMMUNICATIONS BONDING BUSBAR AT EACH EQUIPMENT RACK. INSTALL ON BACK OF
EQUIPMENT RACK AT THE RU45 POSITION.
5/16" (TYP)
BARE COPPER GROUND BAR. INSULATORS,
BRACKETS AND BONDING PROVIDED BY E.C.
REFER TO TECHNOLOGY EQUIPMENT
SCHEDULE SC-GND-2
TWO HOLE COMPRESSION LUG
COPPER GROUND CONDUCTOR
FROM BUILDING SERVICE GROUND.
REFER TO SPECIFICATIONS FOR
DETAILS
NOTES:
1. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE SC-GND-2 FOR WIDTH REQUIREMENTS.
NOTES:
1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN
REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS
FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.
2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND
CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.
3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY.
CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING
ENVIRONMENT.
4. THE ELECTRICAL OR SECURITY CONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING
JURISDICTION (AHJ).
5. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
6. REFER TO THE CONTROLLED SECURITY SCHEME WIRING DIAGRAM ON 5/TI400 FOR CABLING REQUIREMENTS AND THE CONTROLLED SECURITY SCHEME SCHEDULE ON B###-TN400 FOR ADDITIONAL INFORMATION. "B###" REPRESENTS BUILDING NUMBER.
7. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE
RESPONSIBILITY FOR ADDITIONAL INFORMATION.
KEYNOTES:
1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.
2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN
ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.
3. 4" SQUARE BACKBOX WITH SINGLE GANG PLASTER RING. PROVIDE 2 1/2" DEEP MASONRY BOX WHERE APPLICABLE. REFER TO FLOOR PLAN(S) FOR
ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.
4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURE SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST TELECOM
ROOM. PROVIDE A NYLON BUSHING ON CONDUIT END.
5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES.
MAINTAIN ACCESS TO THE JUNCTION BOX.
6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY SCHEME SCHEDULE ON B###-TN400 FOR DOORS THAT REQUIRE THIS ROUGH-IN. "B###" REPRESENTS BUILDING NUMBER.
7. CONDUIT SHALL ROUTE TO THE NEAREST TELECOM ROOM. PROVIDE A NYLON BUSHING ON CONDUIT END.
DOOR FRAME ROUGH-IN DIAGRAM
(ALL SINGLE DOORS)
DOOR FRAME ROUGH-IN DIAGRAM
(ALL DOUBLE DOORS WITH OR WITHOUT MULLION)
FINISHED ACCESSIBLE
CEILING
3/4" EMT CONDUIT
MINIMUM TO ABOVE THE
ACCESSIBLE CEILING
FINISHED FLOOR
CREDENTIAL READER
ROUGH-IN 3
DOOR
CONTACT
ROUGH-IN
1" EMT CONDUIT
MINIMUM
REQUEST TO
EXIT DEVICE
ROUGH-IN
FOR DOOR
HARDWARE
POWER
SUPPLIES
1/2" EMT CONDUIT
MINIMUM (TYP.)
1" EMT CONDUIT
MINIMUM FOR DOOR
HARDWARE
POWER
SUPPLIES
3/4" EMT CONDUIT
MINIMUM TO ABOVE THE
ACCESSIBLE CEILING
CREDENTIAL READER
ROUGH-IN 3
REQUEST TO
EXIT DEVICE
ROUGH-IN
DOOR CONTACT
ROUGH-IN
4" 4" 4"
7 7
SECURITY
LAN
TYPICAL OF SINGLE
DOORS
WIRING KEY:
22 AWG (2) TWO CONDUCTOR STRANDED
18 AWG (4) FOUR CONDUCTOR STRANDED
14 AWG (2) TWO CONDUCTOR STRANDED
22 AWG (6) SIX CONDUCTOR STRANDED
A
B
C
D
TELECOM ROOM
C
E
C
AC-PSP-1
AC-SCP-1
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND NOT INTENDED TO SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS
RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE.
2. ALL CABLING SHALL BE PLENUM RATED.
3. REFER TO TI600 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES:
1. CONTRACTOR SHALL SUPPLY MOTION REQUEST TO EXIT DEVICES AT DOORS INDICATED ON ACCESS CONTROL SCHEDULE.
REFER TO ACCESS CONTROL SCHEDULE FOR QUANTITIES AND LOCATIONS. ALL OTHER MOTION DETECTORS FOR AUTOMATIC DOOR CONTROL ARE EXISTING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING CABLING FROM ACCESS CONTROL PANEL TO
EACH EXISTING AUTOMATIC DOOR CONTROL INTERFACE WITH ACCESS CONTROL SYSTEM.
D
A
B
CATEGORY 6A CABLEE
CSS
M
T
M
T
M
T
M
NOTES:
1. COORDINATE EXACT LOCATION ON SITE WITH WORK BY OTHER TRADES TO ENSURE DESIRED VIEWING AREA AND SERVICE ACCESS AFTER COMPLETION OF PROJECT AND TO MINIMIZE ANY POSSIBLE DAMAGE TO INSTALLED CAMERA OR ASSOCIATED CABLING.
2. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR CAMERA ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO
SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.
3. PROVIDE CAMERA MOUNTING ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION FROM THE SAME MANUFACTURER OF THE CAMERA AND APPROVED BY THE MANUFACTURER FOR USE WITH THE SPECIFIC MODEL NUMBER OF CAMERA INSTALLED.
SCHEDULED CEILING
1" FLEXIBLE METALLIC CONDUIT
FROM JUNCTION BOX TO
ENCLOSURE. FLEX CONDUIT SHALL
ONLY BE USED FOR MAXIMUM OF 10'
4-SQUARE OR OCTAGON JUNCTION
BOX AS REQUIRED FOR CAMERA
CAMERA AS SPECIFIED
1" EMT CONDUIT ROUTE TO NEAREST CABLE TRAY
IF REQUIRED, PROVIDE TRIM RING TO ENSURE
BACK BOX IS COMPLETELY COVERED
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .T
R
.r v t
/2
/2
:1
:0
P
M
TI400
TELECOMMUNICATIONS DETAILS ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 PDN JFK
100% FINAL STAMPED
BID DOCUMENTS
NO SCALETI400
1 BONDING BUS BAR DETAIL
NO SCALETI400
2 TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM
NO SCALETI400
3 RACK MOUNT GROUND BAR DETAIL
NO SCALETI400
4 CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL
NO SCALETI400
5 CONTROLLED SECURITY SCHEME WIRING DIAGRAM
NO SCALETI400
6 INACCESSIBLE CEILING CAMERA MOUNT AND ROUGH-IN DETAIL
LID SHALL BE MARKED
"TELECOMMUNICATIONS"
MOUSE HOLES - (4).
CONDUIT ENTRY PENETRATION NOT TO
EXCEED 25 PERCENT OF SIDE WALL AREA
STAINLESS STEEL HEX
HEAD BOLT W/WASHER
PULL SLOT
SKID RESISTANT SURFACE
EXTENSIONS AS
REQUIRED BY
CONDUIT DEPTH
KNOCKOUTS - (8)
SLOPE GRADE AWAY
FROM COVER 1" IN 3'
GRAVEL DRAINAGE BED MINIMUM 6"
DEPTH. MINIMUM SIZE GRAVEL 1"
NOTES:
1. ALL DIMENSIONS ARE NOMINAL INSIDE CLEARANCES.
2. ANY SPLICES OR DEVICES IN HANDHOLE SHALL BE SUBMERGIBLE.
3. PROVIDE LOCKABLE COVER FOR A COMPLETE SYSTEM.
8" E
XTENSIO
N
LOG
O
LENGTH
W
IDTH
DEPTH
BELOW GRADE CONCRETE WALL OR FLOOR
HYDROSTATIC SEAL ASSEMBLY. INSTALL
ASSEMBLY SO BOLT HEADS ARE ACCESSIBLE
FROM INTERIOR FOR DISASSEMBLY.
"LINK-SEAL", OZ-GEDNEY "CSM" SERIES,
CROUSE-HINDS "TW" SERIES, REFER TO NOTE #1
DUCT SEALING COMPOUND IN INTERIOR OF CONDUIT.
JM CLIPPER DUXSEAL OR EQUIVALENT PULL BOX, CONDUIT
FITTING OR AUXILIARY
GUTTER, REFER TO
NOTE #2
APPLY CAULK FLUSH WITH SURFACE AND PROVIDE
CHROME ESCUTCHEON RING FOR FINISHED WALLS
CAST OR MALLEABLE IRON SLEEVE WITH WATER
STOP, IF NOT CORE DRILLED
IF APPLICABLE, DOWEL DUCT BANK TO CONCRETE
WALL WITH MINIMUM OF (4) #4 EMBEDDED
MINIMUM OF 4" AND EPOXY ANCHORED
NOTES:
1. HYDROSTATIC SEAL SELECTION BASED ON OUTSIDE DIAMETER OF CONDUIT AND INSIDE
DIAMETER OF SLEEVE OR BORE.
2. PROVIDE PULL BOX, CONDUIT FITTING OR AUXILIARY GUTTER, SIZED PER N.E.C. WITHIN 5' OF
CONDUIT ENTER TO ALLOW SEALING OF CONDUITS. BOX ORIENTATION IS DIAGRAMMATIC
SEALING COMPOUND SHALL BE NON-HARDENING MATERIAL FOR WATERSTOP AND MOISTURE
BARRIER, OZ/GEDNEY "DUX" OR APPROVED EQUIVALENT SEAL BOTH ENDS OF EXTERIOR
CONDUITS.
3. THIS DETAIL APPLIES TO ALL BELOW GRADE WALL AND FLOOR CONDUIT ENTRIES INTO
BUILDING.
RIGID METAL CONDUIT THRU WALL
GROUND
EXTERIOR WALL. REFER TO ARCHITECTURAL
DRAWINGS FOR ADDITIONAL INFORMATION.
NOTES:
1. REFER TO CIVIL DRAWINGS FOR EXACT LOCATION OF SC-HH-1.
2. REFER TO TI600 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES:
1. CONTRACTOR TO COORDINATE JUNCTION BOX ELEVATIONS WITH OWNER.
2. ROUTE 4" CONDUIT TO TELECOM ROOM. COORDINATE ROUTE WITH OWNER.
3. REFER TO 1/TI401 EXTERIOR HAND HOLE DETAIL FOR ADDITIONAL INFORMATION.
SC-HH-1
5'-0"
(18" X 18" X 6")
JUNCTION BOX
(2) 4" CONDUITS
(2) 4" CONDUITS TO TELECOM ROOM
COORDINATE EXACT LOCATION
WITH CIVIL DRAWINGS
(18" X 18" X 6")
JUNCTION BOX
REFER TO ARCHITECTURAL
PLANS FOR WALL CONSTRUCTION
SINGLE GANG PLASTER RING
TO COME WITHIN 1/8" OF FINAL
SURFACE
STUD
1" EMT CONDUIT UNLESS
OTHERWISE NOTED. REFER TO
DETAIL NOTES FOR ADDITIONAL
REQUIREMENTS
NYLON BUSHING
J-HOOK
NOTES:
1. 1" EMT CONDUIT SHALL STUB UP TO NEAREST ACCESSIBLE CEILING AND TERMINATE ORIENTED HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED J-HOOK ROUTE. CONDUIT RUN SHALL NOT CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR BETWEEN JUNCTION BOX AND END OF
CONDUIT.
2. WHERE CONDUIT STUB IS LOCATED IN A ROOM WITH AN ACCESSIBLE CEILING AND IS NOT REQUIRED TO RUN TO CABLE ROUTE LOCATED OUTSIDE THE ROOM, STUB MUST TERMINATE ABOVE THE ACCESSIBLE CEILING WITH A 90-DEGREE BEND AT THE TOP ORIENTED IN TO THE ROOM AT THE HEIGHT OF THE ASSOCIATED J-HOOK ROUTE
IN THE ROOM.
3. ALL STUBS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.
4. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR TECHNOLOGY ROUGH-INS
PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.
VELCRO CABLE
STRAP
CABLE EXTENDS TO
THE NEAREST
TELECOMMUNICATIONS
ROOM
COILED
CATEGORY
SLACKLOOP
KEYNOTES:
1. MOUNT A DEDICATED J-HOOK TO THE NEAREST CEILING SUBSTRUCTURE, COLUMN, JOIST, OR WALL ABOVE THE CEILING AS SHOWN ON THE DRAWINGS. PROVIDE THE PROPER SUPPORT WHEN HANGING FROM THE CEILING SUBSTRUCTURE OR COLUMN WALL OR JOIST. REFER TO SPECIFICATION SECTION 27 05 28 FOR ADDITIONAL
REQUIREMENTS.
2. REFER TO SECTION 27 10 00 FOR SLACKLOOP LENGTH. MAINTAIN THE MANUFACTURERS BEND RADIUS FOR
SLACKLOOP SIZE.
3. PROVIDE AND INSTALL A VELCRO CABLE STRAP ON THE SLACKLOOP APPROXIMATELY EVERY 6" ALONG THE SLACKLOOP. FOR SLACKLOOPS GREATER THAN 3' A MINIMUM OF (4) STRAPS WILL BE INSTALLED.
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .T
R
.r v t
/2
/2
:1
:0
P
M
TI401
TELECOMMUNICATIONS DETAILS ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 PDN JFK
100% FINAL STAMPED
BID DOCUMENTS
NO SCALETI401
1 EXTERIOR HAND HOLE DETAIL
NO SCALETI401
3 EXTERIOR WALL PENETRATION DETAIL
NO SCALETI401
4 EXTERIOR PATHWAY DETAIL (LOW HEIGHT)
NO SCALETI401
2 TECHNOLOGY ROUGH-IN TO J-HOOK DETAIL
B A B A
ANGLED PANEL COVER
e2XHD Angled Panel - 1 RU
Rear Cable Manager
16.37"
.3
.3
.3
.0
.1 e2XHD High-Density Angled Panel - Top View
1 RU Panel - Front View
19.00"
18.31"
HDX1A-144 E2XHD-CMB SPLCH-12X
.1
.9
" 1
.5
.3
8.39"
.4
16.90"
.2
19.15"
.7
ONE CATEGORY 6A 8P8C OUTLET
ACTIVE FOR TELEPHONY
MINIMUM OF FOUR CATEGORY 6A 8P8C
OUTLETS FOR DATA OR TELEPHONY
TYPICAL WALL MOUNT PHONE
VOIP OUTLET
TYPICAL WORK FLOOR MOUNT OUTLET
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASIS.
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
TYPICAL HIGH DENSITY WALL
MOUNTED WORK AREA OUTLET
CONFIGURATION
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASIS.
TWO CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
STANDARD DENSITY WALL
MOUNTED WORK AREA OUTLET
CONFIGURATION
FRONT VIEW REAR VIEW SIDE VIEW ISOMETRIC VIEW
.2
.0
.0
.0
TOP VIEW
6.4 5"
10.26"
.9
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .T
R
.r v t
/2
/2
:1
:0
P
M
TI402
TELECOMMUNICATIONS DETAILS ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 PDN JFK
100% FINAL STAMPED
BID DOCUMENTS
NO SCALETI402
1 UTP PATCH PANEL
NO SCALETI402
2 FIBER DISTRIBUTION…
This is the start of the file's text. The full file is on GovTribe.