Attachment 42 - Addendum 01.pdf

PDF 2 MB Posted

Attached to
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation Federal contract opportunity
Solicitation number
36C77623B0043
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is for electronic health record modernization infrastructure upgrades at the VA medical center in Hines, Illinois. The solicitation seeks mechanical, electrical, and plumbing construction services to upgrade mechanical infrastructure including HVAC, plumbing, and electrical systems in various areas of the facility. Key work includes installing new HVAC equipment, upgrading mechanical systems in telecom and server rooms, replacing plumbing and adding new drainage systems. The response deadline is August 14, 2023, with construction to be completed by May 31, 2024. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation, newest first.
File Type Posted
Attachment 44 - Technical Questions and Answers Volume 6.pdf PDF
36C77623B0043 0003.pdf PDF
36C77623B0043 0002.pdf PDF
Attachment 39 - Technical Questions and Answers Volume 3.pdf PDF
Attachment 40 - Technical Questions and Answers Volume 4.pdf PDF
Attachment 41 - Technical Questions and Answers Volume 5.pdf PDF
Attachment 43 - Addendum 02.pdf PDF
Presolicitation - Site Walk Sign in Sheet.pdf PDF
Official Site Visit Sign in Sheet - 2.pdf PDF
Official Site Visit Sign in Sheet - 1.pdf PDF
Attachment 37 - Technical Questions and Answers Volume 1.pdf PDF
36C77623B0043 0001.pdf PDF
Attachment 38 - Technical Questions and Answers Volume 2.pdf PDF
S02 - Solicitation - 36C77623B0043.pdf PDF
Attachment 04 - Drawings - 578-701.A.20230531_3.pdf PDF
Attachment 08 - Drawings - 578-701.C.20230531_1.pdf PDF
Attachment 11 - Drawings - 578-701.E.20230531_1.pdf PDF
Attachment 16 - Drawings - 578-701.H.20230531_1.pdf PDF
Attachment 20 - Drawings - 578-701.S.20230531.pdf PDF
Attachment 31 - Facility Technology Needs Report _FTNR_.pdf PDF
Attachment 33 - Equipment Cut Sheets.pdf PDF
Attachment 36 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 13 - Drawings - 578-701.F.20230531_1.pdf PDF
Attachment 19 - Drawings - 578-701.M.20230531_2.pdf PDF
Attachment 24 - Drawings - 578-701.T2.20230531.pdf PDF
Attachment 25 - Site Self Assessment.pdf PDF
Attachment 26 - Basis of Design.pdf PDF
Attachment 30 - Milestone Schedule.pdf PDF
Attachment 34 - Cx Scope Documents.pdf PDF
Attachment 21 - Drawings - 578-701.T.20230531_1.pdf PDF
Attachment 01 - Revised Specifications.pdf PDF
Attachment 02 - Drawings - 578-701.A.20230531_1.pdf PDF
Attachment 10 - Drawings - 578-701.C.20230531_3.pdf PDF
Attachment 14 - Drawings - 578-701.F.20230531_2.pdf PDF
Attachment 15 - Drawings - 578-701.G.20230531.pdf PDF
Attachment 17 - Drawings - 578-701.H.20230531_2.pdf PDF
Attachment 23 - Drawings - 578-701.T.20230531_3.pdf PDF
Attachment 22 - Drawings - 578-701.T.20230531_2.pdf PDF
Attachment 27 - Cook County - Wage Rates.pdf PDF
Attachment 32 - Calculations.pdf PDF
Attachment 03 - Drawings - 578-701.A.20230531_2.pdf PDF
Attachment 05 - Drawings - 578-701.A.20230531_4.pdf PDF
Attachment 06 - Drawings - 578-701.A.20230531_5.pdf PDF
Attachment 07 - Drawings - 578-701.A.20230531_6.pdf PDF
Attachment 09 - Drawings - 578-701.C.20230531_2.pdf PDF
Attachment 12 - Drawings - 578-701.E.20230531_2.pdf PDF
Attachment 18 - Drawings - 578-701.M.20230531_1.pdf PDF
Attachment 28 - QA-QC Plans.pdf PDF
Attachment 29 - Project BIM Execution Plan.pdf PDF
Attachment 35 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 50

36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum 01

Date: 08/14/2023

Project Name: VA Hines EHRM Infrastructure Design Phase II Project #: 21081.001

Telecommunication Specification Items:

1. The following color coding has been added to section 271000 – STRUCTURED CABLING:

A. 2.3 CABLE COLOR CODING

1. Horizontal Cabling:

a. Data Cabling – A side Blue, B side Yellow

b. VA WAP Cabling – Green

c. Analog Voice Cabling – Gray

d. Guest Wifi Cabling – Orange

e. Biomed and Nurse Call – White

f. Surveillance – Purple

g. Access Control

h. Fire Alarm – Red

B. Backbone Cabling:

1. Analog Copper – Gray

2. OM3 Multimode – Aqua

3. OM4 Mutlimode Fiber – Violet

4. OS1 and OS2 Singlemode Fiber – Yellow

Electrical Drawing Items:

1. The following sheet(s) has been modified:

A. Sheet EI402: ELECTRICAL DETAILS

1. Led Luminaire Schedule:

a. Light fixture XM1 is a stand along battery egress light, Lithonia model ELM6L or equal fixture by Sure- Lites or McPhilben.

Mechanical Drawing Items:

2. The following sheets are reissued in their entirety:

A. Sheet B01-M101A: FIRST LEVEL FLOOR PLAN – SECTION A – MECHANICAL

1. Added a thermostat to the UPS room.

B. Sheet B01-M101B: FIRST LEVEL FLOOR PLAN – SECTION B – MECHANICAL

1. Added a thermostat to the UPS room.

www.specializedeng.com

VA Hines EHRM Infrastructure Design Phase II SES Project #21081.001

Addendum 01 Page 2 of 2 08/14/2023

C. Sheet B01-M101D: FIRST LEVEL FLOOR PLAN – SECTION D – MECHANICAL

1. Added a thermostat to the UPS room.

D. Sheet B200-M000B: BASEMENT LEVEL FLOOR PLAN – SECTION B – MECHANICAL

1. Added a thermostat to the UPS room.

E. Sheet M501: MASTER MECHANICAL CONTROLS

1. Clarified Sequence of Controls for TR Racks.

Submitted By: Jeremy Klima jdm

H T

T

B01-M101A

SSCU-1-A217 SSCU-1-A317 SSCU-1-A419

(TYP) 4

TR

A117

B01-M101A

UPS

A113

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

M500

(TYP)

TENANT SPACE

PLAY ROOM

A117

TENANT SPACE

PLAY ROOM

A113

6 7 8

C

D

SS-1-A117

REFS/L UP

TR

A117

UPS

A113

H-1-A1177

12"x8"

D2

6"x6"

D2

6 7 8

C

D

SS-1-A113

(TYP) 4

LV-1-A113

EF-1-A113

M500

M500

M500

M500

M500

SSCU-1-A117SSCU-1-A113

1 1/2" SAN UP

1/2" NPW UP

2" SAN UP

CP-1-A1173/4" PC

2" SAN

2" STANDPIPE

1 1/2" V

6"x6"

D2

N

A B C D E F G

TENANT

SPACE

PANTRY

A114

TENANT SPACE

STORAGE

A108A

COMMON SPACE

CORRIDOR

RCC101R

DIRECTOR'S

SUITE

OFFICE

A148A

DIRECTOR'S

SUITE

OFFICE

A142C

TENANT

SPACE

MECHANICAL

ROOM

A134

DIRECTOR'S

SUITE

OFFICE

A142D

TENANT

SPACE

TOILET

A104

TENANT

SPACE PLAY

ROOM

A102

TENANT

SPACE PLAY

ROOM

A101

TENANT

SPACE PLAY

ROOM

A103

TENANT

SPACE

OFFICE

A105

TENANT

SPACE PLAY

ROOM

A109

TENANT

SPACE

TOILET

A107

TENANT

SPACE

STORAGE

A147

MEDICAL

ADMIN

BENI-TRAVEL

A143

SPACE

UNDER

CONSTRUCTION

A141

TENANT

SPACE

STORAGE

A139

TENANT

SPACE

OFFICE

A133A

TENANT

SPACE

OFFICE

A133

TENANT

SPACE

OFFICE

A129A

TENANT

SPACE

STORAGE

A125

TENANT

SPACE

VESTIBULE

VA1

VERTICAL

SPACE

ELEVATOR

RCC168R

TENANT

SPACE

PLAYROOM

A119

TENANT

SPACE PLAY

ROOM

A128

TENANT

SPACE

MECHANICAL

ROOM

A106

TENANT

SPACE PLAY

ROOM

A110

TENANT

SPACE

KITCHEN

A116 TENANT

SPACE PLAY

ROOM

A118

TENANT

SPACE

TOILET

A122

VERTICAL SPACE

STAIR

RCC167R

TENANT

SPACE

STORAGE

A150

VERTICAL

SPACE

ELEVATOR

A148B

DIRECTOR'S

SUITE COPY

ROOM

A148B

DIRECTOR'S

SUITE

OFFICE

A142B

DIRECTOR'S

SUITE

OFFICE

A142A

DIRECTOR'S

SUITE

OFFICE

A142

TENANT

SPACE

TOILET

A140

TENANT

SPACE

TOILET

A138

TENANT SPACE

MECHANICAL ROOM

A136

TENANT

SPACE

TEACHER'S

LOUNGE

A132

COMMON SPACE

CORRIDOR

RCC103R

COMMON

SPACE

CORRIDOR

RCC104R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 21081

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 05/31/2023

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e I

I/

-7

.B

.M T

R

.r v t

/1

/2

:4

:4

P

M

B01-M101A

FIRST LEVEL FLOOR PLAN -

SECTION A - MECHANICAL

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JMM RJH

N

SCALE: 1/16" = 1'-0"B01-M101A

1 FIRST LEVEL FLOOR PLAN - SECTION A - MECHANICAL

0' 16' 32'8'4'

SCALE: 1/4" = 1'-0"B01-M101A

2 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - TR-A117

SCALE: 1/4" = 1'-0"B01-M101A

3 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL - TR-A117

0' 4' 8' 12'2'0' 4' 8' 12'2'

NOT TO SCALE

KEY PLAN

SHEET NOTES:

1. REMOVE PLENUM RETURN GRILLE IN ITS ENTIRETY.

2. REMOVE SUPPLY DIFFUSERS AND ASSOCIATED DUCTWORK AS SHOWN.

3. REMOVE RADIATOR AND ASSOCIATED PIPING TO NEAREST ACTIVE MAIN AND CAP.

4. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-

FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL

ACCESSORIES REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM.

5. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.

6. CONTRACTOR TO VERIFY AND MATCH EXISTING SA DUCT SIZE.

7. ROUTE 1-1/4” CONDENSATE DRAIN FROM HUMIDIFIER TO CONDENSATE PUMP.

8. REMOVE SANITARY PIPING TO NEAREST ACTIVE MAIN AND CAP.

9. REMOVE DCW, DHW, AND DHWC PIPING AS SHOWN AND CAP.

10. CONNECT 2" SANITARY INTO EXISTING 4" SANITARY RISER. FIELD CONFIRM LOCATION OF EXISTING RISER.

11. ROUTE 3/4” CD FROM SS-1-A117 AND COMBINE WITH 3/4" CD FROM SS-1-A113. CONTINUE TO 2" STANDPIPE

WITH AIR GAP FITTING.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM

STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.

6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.

ANCHORING INTO THE BRICK SURFACE IS NOT ALLOWED AT HINES.

Revisions: Date:

Addendum 01 08/14/2023

T H

B01-M101B

B01-M101B

(TYP) 5

SSCU-1-B129 SSCU-1-B227 SSCU-1-B323 SSCU-1-B423

TR

B129

UPS

B132

B01-M101B

B01-M101B

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

A

B

C

D

E

SSCU-1-B132

M500

(TYP)

GERIATRICS TOILET

B129

26 27

D

(TYP) 5

REFS/L UP

TR

B129

SS-1-B129

H-1-B1297

REFS/L UP

26 27

D

CP-1-B129

TF-1-B129 75

G1

F-1-B129

24x129

2" SAN UP

M500

M500

M500

M500

3/4" NPW UP

4" SAN UP/DN

2" SAN

3/4" PC

3/4" NPW

1/2" NPW

1 1/2" V UP

3/4" PC8

N

A B C D E F G

FISCAL

STORAGE

B102

TENANT

SPACE

STORAGE

B116A

GERIATRICS

COPY ROOM

B128

VERTICAL

SPACE

ELEVATOR

RCC171R

GERIATRICS

STAFF

ROOM

B146A

MEDICAL

ADMIN

STORAGE

B158

COMMON SPACE

CORRIDOR

RCC109R

GERIATRICS

MECHANICAL

ROOM

B138A GERIATRICS

OFFICE

B140

GERIATRICS

OFFICE

B142

GERIATRICS

CONFERENCE

ROOM

B146

GERIATRICS

STORAGE

B148

GERIATRICS

TOILET

B152

MEDICAL

ADMIN

STORAGE

B158A MEDICAL

ADMIN

OFFICE

B160

MEDICAL

ADMIN

OFFICE

B162

FISCAL

OFFICE

B106

FISCAL

OFFICE

B110

FISCAL

OFFICE

B114

GERIATRICS

OFFICE

B115

TENANT

SPACE

B116

TENANT

SPACE

OFFICE

B118

GERIATRICS

OFFICE

B122

TENANT

SPACE

OFFICE

B103

TENANT

SPACE

OFFICE

B121

TENANT

SPACE

OFFICE

B119

TENANT

SPACE

OFFICE

B117

TENANT

SPACE

OFFICE

B113

TENANT

SPACE

OFFICE

B109

TENANT

SPACE

OFFICE

B107

GERIATRICS

H.A.C.

B127

GERIATRICS

TOILET

B123

COMMON

SPACE

CORRIDOR

RCC107R

TENANT

SPACE

OFFICE

B161A

NUTRITION/FOOD

OFFICE

B159

DIRECTOR'S

SUITE

OFFICE

B155

GERIATRICS

STORAGE

B153

GERIATRICS

OFFICE

B151

GERIATRICS

OFFICE

B147

GERIATRICS

OFFICE

B145

GERIATRICS

OFFICE

B143

GERIATRICS

OFFICE

B141

GERIATRICS

OFFICE

B139

GERIATRICS

OFFICE

B135A

GERIATRICS

MAIN

OFFICE

B135

GERIATRICS

OFFICE

B149

TENANT

SPACE

CONFERENCE

ROOM

B101

FISCAL

STORAGE

B100

FISCAL

OFFICE

B104

VERTICAL

SPACE

STAIR

RCC170R

COMMON SPACE

CORRIDOR

RCC106R

GERIATRICS

OFFICE

B136

GERIATRICS

OFFICE

B134

GERIATRICS

STORAGE

B138

GERIATRICS

OFFICE

B136A

COMMON

SPACE

RCC187R

COMMON

SPACE

CORRIDOR

RCC110R

COMMON

SPACE

CORRIDOR

RCC104R

GERIATRICS

MECHANICAL ROOM

B132

28 29

A

B

UPS

B132

28 29

A

B

SS-1-B132

SSCU-1-B132

8 LV-1-B132

EF-1-B132

CP-1-B132

M500

M500

M500

M500

TF-1-B132

G1

24x12 RA

F-1-B132

3/4" CD

3/4" PC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 21081

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 05/31/2023

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e I

I/

-7

.B

.M T

R

.r v t

/1

/2

:4

:4

P

M

B01-M101B

FIRST LEVEL FLOOR PLAN -

SECTION B - MECHANICAL

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JMM RJH

SCALE: 1/16" = 1'-0"B01-M101B

1 FIRST LEVEL FLOOR PLAN - SECTION B - MECHANICAL

SCALE: 1/4" = 1'-0"B01-M101B

2 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - TR-B129

SCALE: 1/4" = 1'-0"B01-M101B

3 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL - TR-B129

N

0' 16' 32'8'4'

0' 4' 8' 12'2'0' 4' 8' 12'2'

NOT TO SCALE

KEY PLAN

SHEET NOTES:

1. DEMO EXHAUST GRILLE AND DUCTWORK AS SHOWN.

2. REMOVE RADIATOR AND ASSOCIATED PIPING TO NEAREST ACTIVE MAIN AND CAP.

3. REMOVE PLUMBING FIXTURE AND ASSOCIATED PIPING TO NEAREST ACTIVE MAIN AND CAP.

4. REMOVE SANITARY PIPING AND CAP AT NEAREST ACTIVE MAIN.

5. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-

FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL

ACCESSORIES REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM.

6. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.

7. ROUTE DRAIN LINE FROM HUMIDIFIER TO CONDENSATE PUMP.

8. ROUTE 1/2" PUMPED CONDENSATE DRAIN LINE AS SHOWN AND CONNECT INTO THE TOP OF THE NEW 2" SAN

LINE.

9. ROUTE 3/4" CONDENSATE DRAIN FROM SPLIT SYSTEM AND CONNECT INTO 1-1/4” DRAIN LINE INTO

CONDENSATE PUMP.

10. PROVIDE NEW 3/4" DCW TAP FROM EXISTING COLD WATER LINE IN SHAFT AND PROVIDE WITH 5 MICRON

INLINE SEDIMENT PREFILTER WITH MINIMUM 5 GPM CAPACITY AND 3/4" DOUBLE CHECK VALVE ASSEMBLY MOUNTED AT 3'-0" ABOVE FINISHED FLOOR. ROUTE 3/4" NCW AS SHOWN TO NEW RISER SERVING HUMIDIFIERS IN TR ROOMS. PREFILTER RATED FOR 125 PSI MAXIMUM PRESSURE, COORDINATE MODEL AND

FILTER TYPE WITH VA HINES CURRENT STOCK UNIT.

11. CONNECT 2" SANITARY LINE INTO EXISTING 4 INCH SANITARY LINE IN WALL.

GENERAL NOTES:

SCALE: 1/4" = 1'-0"B01-M101B

5 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - UPS B132

0' 4' 8' 12'2' SCALE: 1/4" = 1'-0"B01-M101B

6 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL - UPS B132

0' 4' 8' 12'2'

Revisions: Date:

Addendum 01 08/14/2023

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM

STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.

6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.

ANCHORING INTO THE BRICK SURFACE IS NOT ALLOWED AT HINES.

TH

T

T

B01-M101D

B01-M101D

TR

D146

56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73

A

B

C

D

E

UPS

D144

LV-1-D144

8x6 EA

M500

M500

3/4" NPW

67 68

B

C

11 5

TR

D146

H-1-D146

REFS/L UP

SS-1-D146

D19

6"x6"

D2

67 68

B

C

SS-1-D144

EF-1-D144

UPS

D144

M500

M500

M500

M500

RELOCATED

THERMOSTAT

6"x6"

D2

6"x6"

D2

2" SAN UP

2" SAN DN

2" STANDPIPE

N

A B C D E F G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 21081

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 05/31/2023

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e I

I/

-7

.B

.M T

R

.r v t

/1

/2

:4

:4

P

M

B01-M101D

FIRST LEVEL FLOOR PLAN -

SECTION D - MECHANICAL

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JMM RJH

SCALE: 1/16" = 1'-0"B01-M101D

1 FIRST LEVEL FLOOR PLAN - SECTION D - MECHANICAL

SCALE: 1/4" = 1'-0"B01-M101D

2 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - TR-D146 AND UPS D144

SCALE: 1/4" = 1'-0"B01-M101D

3 FIRST LEVEL FLOOR PLAN - ENLARGED MECHANICAL - TR-D146 AND UPS D144

N

0' 16' 32'8'4'

0' 4' 8' 12'2'0' 4' 8' 12'2'

NOT TO SCALE

KEY PLAN

SHEET NOTES:

1. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-

FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL

ACCESSORIES REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM.

2. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.

3. ROUTE DRAIN FROM HUMIDIFIER AND DISCHARGE INTO HUMIDIFIER DRAIN RESERVOIR AS INDICATED IN

DETAIL 5/M500.

4. REMOVE SUPPLY DIFFUSER,ASSOCIATED DUCTWORK, AND EQUIPMENT AS SHOWN.

5. REMOVE RETURN GRILLE AND ASSOCIATED DUCTWORK AS SHOWN.

6. REMOVE SUPPLY DUCTWORK AS SHOWN.

7. ROUTE 3/4” CONDENSATE DRAIN FROM SPLIT SYSTEM, COMBINE WITH HUMIDIFIER AND SPLIT SYSTEM

DRAINS AND CONTINUE AS 1-1/2” LINE TO STANDPIPE WITH AIR GAP FITTING.

8. CONNECT INTO EXISTING DOMESTIC WATER LINE IN HOUSEKEEPING ROOM WITH 3/4" CONNECTION. IN

HOUSEKEEPING ROOM, PROVIDE WITH 5 MICRON INLINE SEDIMENT PREFILTER WITH MINIMUM 5 GPM CAPACITY AND 3/4" DOUBLE CHECK VALVE ASSEMBLY MOUNTED AT 3'-0" ABOVE FINISHED FLOOR. ROUTE 3/4" NCW AS SHOWN TO NEW RISER SERVING HUMIDIFIERS IN TR ROOMS. PREFILTER RATED FOR 125 PSI MAXIMUM PRESSURE, COORDINATE MODEL AND FILTER TYPE WITH VA HINES CURRENT STOCK UNIT.

9. CONTRACTOR TO VALIDATE EXISTING AIRFLOW AND REBALANCE TO MATCH EXISTING AIRFLOW.

10. ROUTE 3/4" CONDENSATE DRAIN FROM SPLIT SYSTEM AND CONNECT INTO 1-1/2” DRAIN LINE TO STANDPIPE

WITH AIR GAP FITTING.

11. REMOVE EXISTING SINK. REMOVE DCW, DHW, AND V PIPING TO NEAREST ACTIVE MAIN AND CAP. REMOVE

SAN TO POINT BELOW FLOOR AND CAP.

12. RELOCATE EXISTING PNEUMATIC THERMOSTAT TO LOCATION INDICATED ON NEW WORK PLAN. MODIFY

EXISTING PNEUMATIC TUBING AS REQUIRED.

13. RELOCATE EXISTING DUAL DUCT BOX AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ACCOMMODATE

NEW WALL. LOCATE TO MAINTAIN ALL REQUIRED ACCESS TO DUAL DUCT BOX.

14. ROUTE 2" SANITARY DOWN. CONNECT TO EXISTING 4" SANITARY IN TUNNEL BELOW.

15. ROUTE 1-1/4” CONDENSATE DRAIN FROM HUMIDIFIER, COMBINE WITH SPLIT SYSTEM DRAINS AND CONTINUE

AS 1-1/2” LINE TO STANDPIPE WITH AIR GAP FITTING.

GENERAL NOTES:

Revisions: Date:

Addendum 01 08/14/2023

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM

STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.

TH

T T

UPS-1

B040-1

B200-M100B

B200-M100B x15 x14 x13 x12 x11 x10 x9 x8 xH xG xF xE xD xC xB xA

B200-M100B

B200-M100B

TR

B011A

N

A

BC

D x8 xC x8 xC

H-200-B011

2" CWR DN

2" CWS DN

TR

B011A

CP-200-B011A

6"x6"

D3

BCU-200-B11A

B200-M600

M500

SURGICAL OFFICE

B019B

SURGICAL OFFICE

B019C

EMS SOILED

UTILITY

B017

EMS TOILET

B016B

SURGICAL

CONFERENCE

ROOM

B018

SURGICAL

PATIENT HOLDING

B016

LINEN SERVICE

B006B

EMS TOILET-1

B014A-1

SURGICAL

LOCKER ROOM

B010

EMS TOILET

B010A

SURGICAL OFFICE

B009

SURGICAL

LOUNGE

B011

COMMON SPACE

CORRIDOR

RCCB12R

EMS TOILET

B020A

SURGICAL EXAM

B022A

SURGICAL

RECEPTION

B020

SURGICAL EXAM

B022C

SURGICAL EXAM

B022B

SURGICAL EXAM

B022D

SURGICAL EXAM

B022E

SURGICAL EXAM

B022F

EMS TOILET

B022I

SURGICAL UTILITY

B023D

SURGICAL

URODYNAMIC LAB

B022H

EMS TOILET

B023C

EMS TOILET

B024A

EMS H.A.C.

B024F

SURGICAL

DECONTAMINATION

ROOM

B025A

SURGICAL

LOCKER ROOM

B024E

SURGICAL

LOCKER ROOM

B024D

SURGICAL

DRESSING ROOM

B024C

SURGICAL

DRESSING ROOM

B024B

SURGICAL

LOCKER ROOM

B024

EMS SOILED

UTILITY

B025B

SURGICAL

PROCEDURE

ROOM

B027

SURGICAL CLEAN

ROOM

B029B

COMMON SPACE

CORRIDOR

RCCB17R

SURGICAL

PROCEDURE

ROOM

B029

SURGICAL

PROCEDURE

ROOM

B028

EMS H.A.C.-1

B030-1

EMS TOILET

B032

OI&T COMPUTER

ROOM

B037B

ENGINEERING

ELECTRICAL

CLOSET

B037D

COMMON SPACE

CORRIDOR

RCCB16R

SURGICAL EXAM

B022G

VESTIBULE

B038G

STAFF LOUNGE

B038H

WORK ROOM

B039F EXAM 3

B039I

EXAM 6

B039L

EKG/HOLTER

B038E

TOILET-1

B138T-1

OFFICE

B039B

EXAM 2

B039H

EXAM 5

B039K

EXAM 4

B039J

EKG/HOLTER

B038F

PASSAGE

B039E

REC

B039A

NURSING SVC

ADMIN WHEEL

CHAIR STORAGE

B031

EMS TOILET

C021

ENGINEERING

ELVATOR

MACHINE ROOM

B033

COMMON SPACE

CORRIDOR

RCCB18R

OI&T

COMMUNICATIONS

B040A

EXAM 1

B039G

OI&T

COMMUNICATIONS

B040

PASSAGE

B038

MUSE

B038D

ENGINEERING ELECTRICAL CLOSET

B037A

VERTICAL SPACE

STAIR

RCCB30C

SURGICAL

ANESTHESIA

STORAGE

B037

EKG

B039D

TOILET

B039C WAITING

B039

COMMON SPACE

CORRIDOR

RCCB21R

SURGICAL

RECOVERY

B023

SURGICAL

STORAGE

B026

EMS TOILET

B023B

SURGICAL

ANESTHESIA

STORAGE

B036

EMS TOILET

B020B

COMMON SPACE

CORRIDOR

RCCB15R

COMMON SPACE

CORRIDOR

RCCB29R

SURGICAL

RCCB28R

SURGICAL OFFICE

B019

SURGICAL

ANESTHESIA

WORK ROOM

B003

EMS H.A.C.

B006

COMMON SPACE

CORRIDOR

RCCB11R

SURGICAL BLOOD

GAS ANALYSIS

B008A

SURGICAL

LOCKER ROOM

B014

COMMON SPACE

CORRIDOR

RCCB14R

SURGICAL COPY

ROOM

B012

SURGICAL OFFICE

B036A

UPS-1

B040-1 x12 xF xE

2" CWR UP/DN

2" CWS UP/DN

BCU-200-B040-1B200-M600

10"x6"

D3

6"x10"

GE7

x12 xF xE x9 x8 xB

150150

175 175 x9 x8 xB

6"x6"

D3

175175

B200-M600

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 21081

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 05/31/2023

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e

I I/

-7

.B

.M

T

R

.r v t

/1

/2

:4

:2

P

M

B200-M100B

BASEMENT LEVEL FLOOR PLAN -

SECTION B - MECHANICAL

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JMM RJH

SCALE: 1/16" = 1'-0"B200-M100B

1 BASEMENT LEVEL FLOOR PLAN - SECTION B - MECHANICAL

NOT TO SCALE

KEY PLAN

N

0' 4' 8' 12'2'SCALE: 1/4" = 1'-0"B200-M100B

2 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - TR-B011

SCALE: 1/4" = 1'-0"B200-M100B

3 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL - TR-B011

0' 4' 8' 12'2'

SHEET NOTES:

1. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.

2. REMOVE SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK AS SHOWN.

3. REMOVE RETURN GRILLE AND ASSOCIATED DUCTWORK TO MAIN.

4. BOTTOM OF NEW EQUIPMENT SHALL BE 1'-4" AFF. PROVIDE BASIS OF DESIGN CLEARANCES PER

MANUFACTURER RECOMMENDATIONS.

5. ROUTE 1" PUMPED CONDENSATE DRAIN LINES TO LOCATION SHOWN. TERMINATE WITH AIR GAP.

6. TAP OFF EXISTING DCW LINE WITH 1/2" RPZ BACKFLOW PREVENTER. EXTEND 1/2" DCW DOWNSTREAM OF

BACKFLOW PREVENTER TO HUMIDIFIER. PROVIDE AIR GAP FITTING ON BACKFLOW PREVENTER AND ROUTE

TO DRAIN.

7. ROUTE 3/4” GRAVITY CONDENSATE DRAIN LINE FROM SS-200-B011. CONTINUE DRAIN LINE AS SHOWN ON PLANS, COMBINE WITH HUMIDIFIER DRAIN AND CONTINUE AS 1” CONDENSATE DRAIN LINE DOWN TO CP-200- B011.

8. REMOVE VENT PIPING AS SHOWN.

9. REMOVE DCW PIPING AS SHOWN.

10. REBALANCE DIFFUSER/GRILLE TO CFM INDICATED.

GENERAL NOTES:

0' 8' 16'4' 32'

SCALE: 1/4" = 1'-0"B200-M100B

5 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL - UPS-B040-1

SCALE: 1/4" = 1'-0"B200-M100B

6 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - UPS-B040-1

0' 4' 8' 12'2'0' 4' 8' 12'2'

SCALE: 1/4" = 1'-0"B200-M100B

7 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL DEMOLITION - LOCKER ROOM

0' 4' 8' 12'2' SCALE: 1/4" = 1'-0"B200-M100B

8 BASEMENT LEVEL FLOOR PLAN - ENLARGED MECHANICAL - LOCKER ROOM

0' 4' 8' 12'2'

Revisions: Date:

Addendum 03 07/14/2023

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM

STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.

FANMOTOR

CONTROLLER

TEMPERATURE

CONTROL WIRING

(TYP)

01 02

SEQUENCE OF OPERATION

TRANSFER FANS (TF-##-####)

EACH FAN HAS A CURRENT STATUS SWITCH TO PROVE FAN OPERATION. IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, SEND AND ALARM TO

THE USER INTERFACE.

FAN SHALL RUN CONTINUOUSLY TO PRESSURIZE THE TELECOM ROOM.

PROVIDE DIFFERENTIAL PRESSURE SENSOR ACROSS FILTER BANK. ALARM USER INTERFACE WHEN PRESSURE DROP EXCEEDS 0.2" W.C. (ADJUSTABLE).

GENERAL NOTES

1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.

2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES.

REMARKS:

1. E = ELECTRIC P = PNEUMATIC O = BY OTHERS S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK

2. A = ANALOG B = BINARY

3. I = INPUT O = OUTPUT

4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE

5. T = TRENDING E = EVENT HISTORY A = ARCHIVE TT = TOTALIZATION G = GRAPHICAL POINT

DP

C

C

C W

R

C W

S

CONTROLLER

MOTOR

FAN

SPACE BOUNDARY

TEMPERATURE

CONTROL WIRING

(TYP)

01 02

03 04

T

SEQUENCE OF OPERATION

EACH ZONE HAS A FAN COIL UNIT WITH A CHILLED WATER COOLING COIL, COOLING COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 75°F (ADJUSTABLE). SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.

ABOVE SETPOINT, THE FAN COIL UNIT FAN SHALL RUN CONTINUOUSLY AND THE COOLING COIL CONTROL VALVE SHALL BE FULLY OPEN.

ON A FALL IN SPACE TEMPERATURE THE FAN COIL UNIT SHALL CYCLE OFF AND THE COOLING COIL CONTROL VALVE SHALL CLOSE. IF SPACE TEMPERATURE RISES ABOVE

90°F (ADJUSTABLE), SEND ALARM TO THE OPERATOR INTERFACE.

GENERAL NOTES

1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.

2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES.

3. MOUNT ALL ROOM SENSORS AT 48" ABOVE FINISHED FLOOR. COORDINATE LOCATION WITH NEARBY DEVICES SUCH AS LIGHT SWITCHES.

REMARKS:

1. E = ELECTRIC P = PNEUMATIC O = BY OTHERS S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK

2. A = ANALOG B = BINARY

3. I = INPUT O = OUTPUT

4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE

5. T = TRENDING E = EVENT HISTORY A = ARCHIVE TT = TOTALIZATION G = GRAPHICAL POINT

01 02

SS-#-####-1 SS-#-####-2

T TELECOM ROOM / UPS ROOM

03 04

SPLIT SYSTEM DX AIR:

• CONSISTS OF WALL MOUNTED BLOWER EVAPORATOR UNIT, ROOF/GRADE MOUNTED

CONDENSING UNIT, THERMOSTAT PROVIDED BY MANUFACTURER, AND TEMPERATURE SENSOR

PROVIDED BY CONTROLS CONTRACTOR.

• CYCLE CONDENSING UNIT AND INDOOR UNIT IN UNISON TO MAINTAIN SPACE TEMPERATURE

SETPOINT OF 75 DEF °F (ADJUSTABLE). SPACE TEMPERATURE SHALL BE MONITORED THROUGH

DDC. SEND AN ALARM TO THE OPERATOR INTERFACE IF THE SPACE TEMPERATURE EXCEEDS 90°F

(ADJUSTABLE).

• WHERE TWO SPLIT SYSTEMS SERVE THE SAME TELECOM ROOM, THE TEMPERATURE SETPOINT

FOR EACH UNIT SHALL BE CYCLED WEEKLY.

1. WEEK 1:

A. UNIT "1" SHALL BE SET TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75° F

(ADJUSTABLE).

B. UNIT "2" SHALL BE SET TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 80° F

(ADJUSTABLE).

2. WEEK 2:

A. UNIT "1" SHALL BE SET TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 80° F

(ADJUSTABLE).

B. UNIT "2" SHALL BE SET TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75° F

(ADJUSTABLE).

06 07

HUMIDIFIER

H TELECOM ROOM / UPS ROOM

TELECOM ROOMS WITH STAND ALONE HUMIDIFIERS CONTROL:

• HUMIDIFIER TO OPERATE TO MAINTAIN ROOM HUMIDISTAT (HUMIDISTAT AND HUMIDIFIER

CONTROL PROVIDED BY THE HUMIDIFIER MANUFACTURER) SETPOINT. PROVIDE A ROOM

HUMIDITY SENSOR (BY CONTROLS CONTRACTOR) TO MONITOR ROOM HUMIDITY. IF ROOM

HUMIDITY FALLS BELOW 20% RH OR RISES ABOVE 70% RH FOR MORE THAN THIRTY MINUTES,

SEND AN ALARM THROUGH DDC SYSTEM.

• EACH HUMIDIFIER TO BE PROVIDED WITH MEANS AND CONTROL TO COOL CONDENSATE TO A

MAXIMUM OF 140°F. CONDENSATE COOLER AND CONTROL TO BE PROVIDED AS PART OF

HUMIDIFIER EQUIPMENT. PROVIDE A TEMPERATURE SENSOR IN THE DISCHARGE DRAIN LINE

DOWNSTREAM OF THE HUMIDIFIER. WHERE HUMIDIFIERS HAVE A CONDENSATE RETURN PUMP

LOCATE THE SENSOR IN THE CONDENSATE SUMP. PROVIDE A CONTACT SWITCH INTEGRATED

WITH THE TEMPERATURE SENSOR AND HUMIDIFIER CONTROLS TO SHUT DOWN HUMIDIFIER

OPERATION AND ALARM THROUGH THE DDC SYSTEM IF TEMPERATURE IN THE DISCHARGE LINE

OR SUMP EXCEEDS 140°F.

• WHERE HUMIDIFIERS ARE SERVED BY A CONDENSATE RETURN PUMP, THE CONDENSATE PUMP IS

TO HAVE A HIGH-LEVEL SWITCH PROVIDED BY THE CONDENSATE PUMP MANUFACTURER.

PROVIDE A CONTACT TO INTEGRATE THE HIGH-LEVEL SWITCH WITH THE DDC SYSTEM AS WELL AS THE HUMIDIFIER CONTROLLER. IF THE HIGH-LEVEL SWITCH IS ACTIVATED THE HUMIDIFIER SHALL

SHUT DOWN AND AN ALARM SHALL BE SENT THROUGH THE DDC SYSTEM.

TO DRAIN

08 10

SS-#-####-1 SS-#-####-2

TELECOM ROOM / UPS ROOM

CONDENSATE RETURN PUMPS SERVING TR ROOM COOLING UNITS:

• THE CONDENSATE PUMP IS TO HAVE A HIGH-LEVEL SWITCH PROVIDED BY THE CONDENSATE

PUMP MANUFACTURER. PROVIDE A CONTACT TO INTEGRATE THE HIGH-LEVEL SWITCH WITH THE

DDC SYSTEM AS WELL AS THE COOLING UNIT (COOLING UNITS IF THE CONDENSATE PUMP SERVES

MORE THAN ONE UNIT) CONTROLS. IF THE HIGH-LEVEL SWITCH IS ACTIVATED THE COOLING

UNIT(S) SHALL SHUT DOWN AND AN ALARM SHALL BE SENT THROUGH DDC SYSTEM.

WATER BUG ALARMS:

• WATER BUG ALARMS ARE TO BE PLACED AT THE FLOOR LEVEL OF ALL TELECOM ROOMS AND

ENTRANCE ROOMS.

• WITH THE EXCEPTION OF FIRE PROTECTION PIPING, WATER BUG ALARMS ARE TO ALSO BE

PLACED IN DRAIN PANS INSTALLED BELOW HORIZONTAL PIPING WITHIN THE CONFINES OF THE

VARIOUS ROOMS.

• WHEN WATER IS SENSED BY A WATER BUG AN ALARM IS TO BE SENT THROUGH THE DDC SYSTEM.

• REFER TO PLANS AND ASSOCIATED PLAN NOTES FOR ADDITIONAL INFORMATION TO CONFIRM

WATER BUG QUANTITIES.

CONDENSATE PUMP 11

REMARKS:

1. E = ELECTRIC P = PNEUMATIC O = BY OTHERS S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK

2. A = ANALOG B = BINARY

3. I = INPUT O = OUTPUT

4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE

5. T = TRENDING E = EVENT HISTORY A = ARCHIVE TT = TOTALIZATION G = GRAPHICAL POINT

RACK MONITORING SYSTEM

CONNECTED TO

DDC SYSTEM

SN

RACK

TH

T

T

1 FT MAX FROM

TOP OF RACK

APPROXIMATE

CENTER OF RACK

1 FT MAX FROM

BOTTOM OF RACK

(3) TEMPERATURE PROBES,

AND (1) HUMIDITY PROBE

PER SENSOR. LOCATED AT

TOP, MIDDLE, AND BOTTOM

OF FRONT FACE OF RACK.

TR RACKS:

• PROVIDE DEWPOINT SENSORS AT THE ENTRANCE OF EACH TR OR TE ROOM RACK. ALARM TO

BUILDING MANAGEMENT SYSTEM IF DEWPOINT TEMPERATURE EXCEEDS 82 DEGF (ADJUSTABLE).

• HUMIDITY SENSOR AND MIDDLE TEMPERATURE SENSOR MOUNTED ON INSIDE OF FRONT CABINET

DOOR.

• HIGH AND LOW TEMPERATURE SENSORS TO BE LOCATED ON INSIDE OF REAR CABINET DOOR.

FANMOTOR

CONTROLLER

ACTUATOR

TEMPERATURE

CONTROL WIRING

(TYP)

01 02

03 04

SEQUENCE OF OPERATION

EACH FAN HAS AN ISOLATION DAMPER WITH END SWITCH AND CURRENT STATUS SWITCH TO PROVE FAN OPERATION. IF THE ISOLATION DAMPER DOES NOT PROVE OPEN, SEND AN ALARM TO THE USER INTERFACE. IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, SEND AND ALARM TO THE USER

INTERFACE.

FAN SHALL RUN CONTINUOUSLY TO MAINTAIN MINIMUM 1 CFM/SF EXHAUST FROM UPS ROOM. DAMPER SHALL CLOSE UPON LOSS OF POWER TO THE FAN.

GENERAL NOTES

1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.

2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES.

REMARKS:

1. E = ELECTRIC P = PNEUMATIC O = BY OTHERS S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK

2. A = ANALOG B = BINARY

3. I = INPUT O = OUTPUT

4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE

5. T = TRENDING E = EVENT HISTORY A = ARCHIVE TT = TOTALIZATION G = GRAPHICAL POINT

01 02

EXISTING CRAC

T MCR G225-2

04 05

MCR – CONTROLS UPGRADE (PLAN NAME: NUCLEAR MEDICINE OFFICE G225-2)

THE EXISTING MCR ROOM IS COMPOSED OF THREE LIEBERT MODEL DS070 CRAC UNITS WITH

INDIVIDUAL CONTROLS. PROVIDE LIBERT ICOM CONTROLS UPGRADE FOR THESE UNITS TO ALLOW

PARALLEL OPERATION AND CONTROL OF THESE UNITS. ICOM CONTROLS TO COMMUNICATE WITH

EXISTING BUILDING MANAGEMENT SYSTEM AND VA HINES OIT FOR REMOTE MONITORING AND

ALARMS.

THE UNITS SHALL BE STAGED IN OPERATION. RETURN ISOLATION DAMPERS ON RETURN DUCTS TO

CRAC UNITS SHALL OPEN UPON CALL FOR CRAC UNIT OPERATION. PROVIDE END SWITCH ON

DAMPERS. WHEN END SWITCH PROVES DAMPER OPEN THE CRAC UNIT SHALL BE ALLOWED TO

START. IF END SWITCH DOES NOT CONTACT ON A CALL TO OPEN, SEND AN ALARM.

THE CRAC UNITS SHALL OPERATE IN A LEAD LAG FASHION. CRAC UNITS 1 AND 2 SHALL BE STAGED ON FIRST AS LEAD UNITS, AND SHALL OPERATE IN PARALLEL TO MEET LOAD CONDITIONS. UNIT FANS

AND COMPRESSORS SHALL MODULATE TO MEET DESIGN LOAD. IF LOAD CANNOT BE MET BY THE

TWO ON LINE UNITS LAG CRAC UNIT 3 SHALL COME ON LINE AND THE THREE CRAC UNITS SHALL

OPERATE IN PARALLEL TO MEET THE LOAD.

EVERY TWO WEEKS (ADJUSTABLE) THE UNITS SHALL CYCLE THROUGH LEAD- LAG UNITS. AFTER TWO

WEEKS CRAC UNITS 2 AND 3 WILL BE LEAD AND CRAC UNIT ONE WILL BE LAG AND SO ON.

PROVIDE ALARM IF RETURN AIR TEMPERATURE TO AN ON-LINE CRAC UNIT EXCEEDS 85 DEF °F

(ADJUSTABLE)

REMARKS:

1. E = ELECTRIC P = PNEUMATIC O = BY OTHERS S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK

2. A = ANALOG B = BINARY

3. I = INPUT O = OUTPUT

4. G = GENERAL C = CRITICAL H = HIGH LIMIT L = LOW LIMIT F = FAILURE

5. T = TRENDING E = EVENT HISTORY A = ARCHIVE TT = TOTALIZATION G = GRAPHICAL POINT

EXISTING CRAC

E X

IS

T

IN

G

C R

A C

03 06

11 12

EXISTING CRAC

T MAIN SERVER ROOM G301A

14 15

MAIN SERVER ROOM G301A CONTROLS UPGRADE

THE EXISTING MCR ROOM IS COMPOSED OF TWO LIEBERT MODEL DS035 CRAC UNITS WITH

INDIVIDUAL CONTROLS. PROVIDE LIBERT ICOM CONTROLS UPGRADE FOR THESE UNITS TO ALLOW

PARALLEL OPERATION AND CONTROL OF THESE UNITS. ICOM CONTROLS TO COMMUNICATE WITH

EXISTING BUILDING MANAGEMENT SYSTEM AND VA HINES OIT FOR REMOTE MONITORING AND

ALARMS.

THE UNITS SHALL BE STAGED IN OPERATION. RETURN ISOLATION DAMPERS ON RETURN DUCTS TO

CRAC UNITS SHALL OPEN UPON CALL FOR CRAC UNIT OPERATION. PROVIDE END SWITCH ON

DAMPERS. WHEN END SWITCH PROVES DAMPER OPEN THE CRAC UNIT SHALL BE ALLOWED TO

START. IF END SWITCH DOES NOT CONTACT ON A CALL TO OPEN, SEND AN ALARM.

THE CRAC UNITS SHALL OPERATE IN A LEAD LAG FASHION. CRAC UNIT 4 SHALL BE STAGED ON FIRST AS LEAD UNIT. UNIT FANS AND COMPRESSORS SHALL MODULATE TO MEET DESIGN LOAD. IF LOAD CANNOT BE MET BY THE LEAD UNIT, LAG CRAC UNIT 5 SHALL COME ON LINE AND THE TWO CRAC

UNITS SHALL OPERATE IN PARALLEL TO MEET THE LOAD.

EVERY TWO WEEKS (ADJUSTABLE) THE UNITS SHALL CYCLE THROUGH LEAD- LAG UNITS. AFTER TWO

WEEKS CRAC UNITS 5 WILL BE LEAD AND CRAC UNIT 4 WILL BE LAG.

PROVIDE ALARM IF RETURN AIR TEMPERATURE TO AN ON-LINE CRAC UNIT EXCEEDS 85 DEF °F

(ADJUSTABLE)

EXISTING CRAC

13 16

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 21081

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project : 05/31/2023

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e I

I/

-7

.B

.M T

R

.r v t

/1

/2

:0

:4

P

M

M501

MASTER MECHANICAL CONTROLS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JMM RJH

SCALE: NO SCALEM501

1 TRANSFER FAN CONTROL (TF-##-####)

SCALE: NO SCALEM501

2 FAN COIL UNIT - 2 PIPE COOLING ONLY - CYCLED FAN OPERATION

DIRECT DIGITAL CONTROL POINTS LIST - FAN COIL UNIT - 2 PIPE COOLING ONLY - CYCLED FAN

OPERATION

POINT

ID POINT DESCRIPTION

SOURCE

(1)

TYPE

(2)

I/O (3)

SETPOINT

ADJUSTMENT

ALARMS

(4)

APPLICATIONS

(5) UNITS

01 FAN COIL UNIT FAN STATUS E B I NO - T, A, G ON / OFF

02 FAN COIL UNIT FAN START/STOP E B O NO - - -

03 SPACE TEMPERATURE SETPOINT E A I YES - T, A, G DEGREES F

04 SPACE TEMPERATURE E A I NO G, H, L T, A, G DEGREES F

05 HEATING COIL CONTROL VALVE E A O NO - - -

SCALE: NO SCALEM501

3 TELECOM ROOM / UPS ROOM CONTROLS

DIRECT DIGITAL CONTROL POINTS LIST - TELECOM ROOM / UPS ROOM

POINT

ID POINT DESCRIPTION

SOURCE

(1)

TYPE

(2) I/O (3)

SETPOINT

ADJUSTMENT

ALARMS

(4)

APPLICATIONS

(5) UNITS

01 SPLIT SYSTEM DX AIR CONDITIONING SYSTEMS STATUS E B I NO G E, A ON / OFF

02 SPLIT SYSTEM DX AIR CONDITIONING SYSTEMS CONDENSATE ALARM E B I NO G E, A NORMAL / ALARM

03 SPLIT SYSTEM DX AIR CONDITIONING SYSTEMS STATUS E B I NO G E, A ON / OFF

04 SPLIT SYSTEM DX AIR CONDITIONING SYSTEMS CONDENSATE ALARM E B I NO G E, A NORMAL / ALARM

05 SPACE TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

06 HUMIDIFIER STATUS E B I NO G E, A ON / OFF

07 HUMIDIFIER FAULT ALARM E B I NO G E, A NORMAL / ALARM

08 DRAIN WATER TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

09 SPACE RELATIVE HUMIDITY E A I NO H T, A, G % RELATIVE HUMIDITY

10 CONDENSATE HIGH LIMIT SWITCH E B I NO G E, A NORMAL / ALARM

11 WATER BUG ALARM E B I NO G E, A NORMAL / ALARM

12 RACK TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

13 RACK RELATIVE HUMIDITY E A I NO H T, A, G % RELATIVE HUMIDITY

14 RACK TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

15 RACK TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

SCALE: NO SCALEM501

4 UPS ROOM EXHAUST FAN CONTROL (EF-##-####)

DIRECT DIGITAL CONTROL POINTS LIST - UPS ROOM EXHAUST FAN CONTROL

POINT

ID POINT DESCRIPTION

SOURCE

(1)

TYPE

(2) I/O (3)

SETPOINT

ADJUSTMENT

ALARMS

(4)

APPLICATIONS

(5) UNITS

01 EXHAUST FAN STATUS E B I NO G, F E, A, G ON / OFF

02 EXHAUST FAN START/STOP E B O NO - - -

03 EXHAUST FAN ISOLATION DAMPER ACTUATOR E A O NO - T, A, G -

04 EXHAUST FAN ISOLATION DAMPER POSITION E B I NO F T, A, G OPEN / CLOSED

DIRECT DIGITAL CONTROL POINTS LIST - TRANSFER FAN CONTROL

POINT

ID POINT DESCRIPTION

SOURCE

(1)

TYPE

(2) I/O (3)

SETPOINT

ADJUSTMENT

ALARMS

(4)

APPLICATIONS

(5) UNITS

01 EXHAUST FAN STATUS E B I NO G, F E, A, G ON / OFF

02 EXHAUST FAN START/STOP E B O NO - - -

03 FILTER DIFFERENTIAL PRESSURE E A I NO F T, A, G INCHES W.C.

Revisions: Date:

Addendum 01 08/14/2023

SCALE: NO SCALEM501

5 EXISTING SERVER ROOM CONTROL UPGRADES

DIRECT DIGITAL CONTROL POINTS LIST - EXISTING SERVER ROOMS

POINT

ID POINT DESCRIPTION

SOURCE

(1)

TYPE

(2) I/O (3)

SETPOINT

ADJUSTMENT

ALARMS

(4)

APPLICATIONS

(5) UNITS

01 CRAC SYSTEM STATUS E B I NO G E, A ON / OFF

02 CRAC SYSTEM ICOM CONTROLS E A I NO G E, A -

03 RETURN AIR DAMPER POSITION E B I NO G E, A OPEN / CLOSED

04 CRAC SYSTEM STATUS E B I NO G E, A ON / OFF

05 CRAC SYSTEM ICOM CONTROLS E A I NO G E, A -

06 RETURN AIR DAMPER POSITION E B I NO G E, A OPEN / CLOSED

07 CRAC SYSTEM STATUS E B I NO G E, A ON / OFF

08 CRAC SYSTEM ICOM CONTROLS E A I NO G E, A -

09 RETURN AIR DAMPER POSITION E B I NO G E, A OPEN / CLOSED

10 EXISTING SPACE TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

11 CRAC SYSTEM STATUS E B I NO G E, A ON / OFF

12 CRAC SYSTEM ICOM CONTROLS E A I NO G E, A -

13 RETURN AIR DAMPER POSITION E B I NO G E, A OPEN / CLOSED

14 CRAC SYSTEM STATUS E B I NO G E, A ON / OFF

15 CRAC SYSTEM ICOM CONTROLS E A I NO G E, A -

16 RETURN AIR DAMPER POSITION E B I NO G E, A OPEN / CLOSED

17 EXISTING SPACE TEMPERATURE SENSOR E A I NO H T, A, G DEGREES F

2023-08-14 Addendum #1 MECH
B01-M101A - FIRST LEVEL FLOOR PLAN - SECTION A - MECHANICAL
B01-M101B - FIRST LEVEL FLOOR PLAN - SECTION B - MECHANICAL
B01-M101D - FIRST LEVEL FLOOR PLAN - SECTION D - MECHANICAL

2023-08-09 - Addendum 01

File details come from the government source that posted it. Updated .