Attachment 20 - Drawings - 578-701.S.20230531.pdf
PDF 1 MB Posted
- Attached to
- 36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation Federal contract opportunity
- Solicitation number
- 36C77623B0043
About this file
This document package includes structural engineering drawings and notes for proposed upgrades to the EHRM infrastructure at the Veterans Affairs hospital located at 5000 5th Ave in Hines, Illinois. The project involves infill of existing openings and installation of new concrete slabs on the first through fifteenth floors of Building 200. Reinforcing details and general notes provide requirements for concrete mix design, reinforcement, welding, structural steel, and decking. Shop drawings must be submitted for review and approval prior to fabrication and installation. The related federal contract opportunity is solicitation number 36C77623B0043 issued by the Department of Veterans Affairs Technology Acquisition Center Austin to upgrade the EHRM infrastructure at the Hines VA medical center located at the above address in Hines, Illinois.
View the file
Other files for this federal contract opportunity
Show all 50
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NON-LOAD-BEARING WALL LINTEL SCHEDULE
OPENING SIZE LINTEL DESCRIPTION DIAGRAM
0' - 0" TO 5' - 0"
GREATER THAN
5' - 0" TO 7' - 0"
L4x4x5/16
L6x4x5/16 (LLV)
GREATER THAN
7' - 0" TO 10' - 0"
L7x4x3/8 (LLV)
NOTES:
1. WHERE LINTELS ARE NOT SPECIFICALLY SHOWN OR NOTED ON THE
STRUCTURAL OR ARCHITECTURAL DRAWINGS, PROVIDE THE FOLLOWING
LINTELS OVER ALL OPENINGS AND RECESSES IN BOTH INTERIOR AND EXTERIOR
NON-LOAD-BEARING WALLS.
2. PROVIDE 1" OF BEARING PER FOOT OF SPAN WITH MINIMUM 8" EACH END OF
BRICK LINTELS, UNLESS NOTED OTHERWISE.
3. ALL EXPOSED STEEL SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH
ASTM A123.
BAR SIZE
TENSION
DEVELOPMENT LENGTH
#3 1' - 3"
#4
#5
#6
#7
#8
#9
CONCRETE CONSTRUCTION DEVELOPMENT AND
CLASS B LAP SPLICE LENGTHS
DEVELOPMENT LENGTH
IN THICK CONCRETE
TYPICAL LAP
SPLICE LENGTH
1' - 7"
2' - 0"
2' - 5"
3' - 6"
4' - 0"
4' - 6"
LAP SPLICE LENGTH IN
THICK CONCRETE
1' - 7"
2' - 1"
2' - 7"
3' - 1"
4' - 6"
5' - 2"
5' - 10"
1' - 7"
2' - 1"
2' - 7"
3' - 1"
4' - 6"
5' - 2"
5' - 10"
2' - 1"
2' - 9"
3' - 5"
4' - 1"
5' - 11"
6' - 9"
8' - 6"
NOTES:
1. THICK CONCRETE IS DEFINED AS HORIZONTAL BAR WITH MORE THAN 12" OF FRESH CONCRETE
CAST BELOW A SLAB, OR WALL, OR OTHER CONCRETE MEMBER.
2. ALL REINFORCING BARS ARE TO BE SPLICED WITH A CLASS B LAP SPLICE, UNO.
3. CONCRETE CLEAR COVER IS GREATER THAN THE NOMINAL BAR DIAMETER.
SECTION
PLAN
E X
. S
TE
E L
B E
A M
/J O
IS
T
C O
O R
D . W
/ G E
N E
R A
L C
O N
TR
NEW L7x4x3/8 (LLV) x 0' - 8" LONG W/
MIN. 3" BRG. ON STEEL BEAM/JOIST
COORD. W/ M.C.
EX. STEEL BEAM/
JOIST TO REMAIN
COORD. W/ M.C.
VERIFY IN FIELD
C6x8.2 FRAME
NEW FLOOR OPENING
NEW FLOOR OPENING
- COORD. SIZE w/
GENERAL CONTR.
NEW C6x8.2 FRAME
E X
. S
TE
E L
B E
A M
/J O
IS
T
EX. CONCRETE
BEAM/JOIST
NEW L4X4X1/4 FRAME
T/FRAME = T/JOIST
NEW DECK
OPENING
NOTE:
1. COORDINATE OPENING SIZE WITH MECHANICAL CONTRACTOR.
2. CONCRETE SLAB NOT SHOWN FOR CLARITY
3. CONTRACTOR TO SAWCUT SLAB FLUSH WITH THE INSIDE FACE OF THE
ANGLE FRAME. PROVIDE 2" CORE DRILL RADIUS AT NEW SLAB CORNERS.
EX. CONCRETE
BEAM/JOIST
DRILL AND EPOXY (2) 3/8" HILTI
HIT-Z ANCHORS WITH HIT-HY
200 EPOXY (OR APPROVED
EQUAL). MIN EMBED 4 1/2", TYP
M
IN3"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .A
R
.r v t
/2
/2
:1
:0
P
M
SF-001
STRUCTURAL GENERAL NOTES &
TYPICAL DETAILS
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 ADK LKB
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER OF RECORD A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD DEVIATION"
DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER OF RECORD.
DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE MIX DESIGN(S)
2. REINFORCING STEEL
3. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE
WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS)
4. STEEL DECK
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER OF RECORD AND COR FOR REVIEW.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE REINFORCEMENT
3. WELDED WIRE FABRIC (WWF) FOR CONCRETE
4. CONCRETE CURING COMPOUND
5. CONCRETE JOINT SEALANT
6. MASONRY JOINT REINFORCEMENT
7. EXPANSION ANCHORS
8. ADHESIVE ANCHORS
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A
DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY WEIGHT) OF FLY ASH TO TOTAL
CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER OF RECORD FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL HAVE THE PROPERTIES AS SHOWN BELOW:
CONCRETE SLABS & FOUNDATION WALLS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 4 TO 6 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.50
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 0 - 3%
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS TAKEN FROM DRAWINGS THAT WERE PREPARED FOR THE VETERANS ADMINISTRATION HOSPITAL, BUILDING 200, DATED 10-29-1965. THERE WERE NOT ANY OTHER ORIGINAL EXISTING
DRAWINGS AVAILABLE FOR ANY OF THE OTHER BUILDINGS WITHIN THIS SET.
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE STRUCTURAL ENGINEER OF RECORD IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK ALL DIMENSIONS, ELEVATIONS, ETC. NECESSARY FOR THE PROPER CONSTRUCTION AND ALIGNMENT. THE CONTRACTOR SHALL MAKE ALL NECESSARY MEASUREMENTS FOR FABRICATION AND ERECTION OF THE STRUCTURAL MEMBERS. ANY ERRORS OR DISCREPANCIES SHALL BE REPORTED TO THE STRUCTURAL ENGINEER OF RECORD PRIOR TO THE FABRICATION AND ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THE PROJECT, THAT BECOME DAMAGED, SHALL BE REPLACED
WITH NEW MATERIAL OF EQUAL QUALITY AND APPEARANCE, AT THE CONTRACTORS EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK. ADJACENT EXISTING CONSTRUCTION SHALL BE
PROTECTED FROM DUST, DIRT, AND DEBRIS ACCUMULATION AT ALL TIMES.
ALL CORNERS OF NEW RECTANGULAR OPENINGS IN EXISTING CONCRETE SLABS OR WALLS MUST BE CORE DRILLED.
WHERE ORIGINAL EXISTING DRAWINGS WERE NOT AVAILABLE, THE CONTRACTOR MUST VERIFY THE EXISTING STRUCTURE (DETERMINE DISTANCES BETWEEN MEMBERS, SLAB & DECK THICKNESSES, FRAMING MEMBER SIZES, LOCATION OF REINFORCING IN SLABS AND FRAMING MEMBERS, ETC) IN AREAS WHERE NEW LOADS (EX. DATA RACKS, ETC) ARE TO BE SUPPORTED BY THE EXISTING STRUCTURE OR NEW OPENINGS (EX. CONDUIT, PIPING, ETC) ARE TO BE ADDED TO EXISTING FLOORS OR WALLS AND COORDINATE
WITH THE STRUCTURAL ENGINEER OF RECORD BEFORE PROCEEDING.
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING CODE.
DEAD LOAD = COMPUTED FOR THE MATERIALS OF CONSTRUCTION INCORPORATED INTO THE BUILDING, INCLUDING BUT NOT LIMITED TO FLOORS, CEILINGS, FINISHES, AND OTHER SIMILAR ARCHITECTURAL AND STRUCTURAL ITEMS, AS WELL AS MECHANICAL, ELECTRICAL, PLUMBING, AND TECHNOLOGY EQUPIMENT AND FIXTURES.
LIVE LOAD FOR SLAB INFILLS = 60 PSF
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000
PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING STANDARDS:
ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER
OVER REINFORCEMENT AS FOLLOWS:
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 1 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR
APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP PER TABLE THIS SHEET.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED OTHERWISE.
ELEVATED CONCRETE SLABS
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN
A CONSTANT SLAB [THICKNESS].
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING, INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD OF ANY DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.) IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE
STRUCTURAL ENGINEER OF RECORD.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS; CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF RECORD IMMEDIATELY AND SHALL NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT
PRIOR REVIEW BY THE STRUCTURAL ENGINEER OF RECORD.
ELEVATED SLABS SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER
CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND
LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED 3/4 INCH DOWN FROM TOP OF SLABS ON METAL DECK, UNLESS NOTED OTHERWISE.
FIBER REINFORCEMENT
SUBSTITUTION OF FIBER SECONDARY REINFORCEMENT FOR WELDED WIRE FABRIC ON SUPPORTED SLABS IS PROHIBITED.
FIBER REINFORCEMENT SHALL BE VIRGIN (NON-RECYCLED) NYLON OR POLYPROPYLENE FIBERS, INTRODUCED INTO THE CONCRETE MIX AT THE BATCH PLANT, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND DOSAGE.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER OF RECORD. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING UNLESS DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE PROTECTED
AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL
CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER OF RECORD, READY-MIX SUPPLIER AND
CONTRACTOR WITHIN 24 HOURS AFTER TESTING.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER OF RECORD AND SHALL BE INSTALLED IN CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI HIT-HY 200 FOR SOLID SUBSTRATE AND HILTI HIT-HY 270 FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER OF RECORD, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE
MANUFACTURER'S REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 15 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE C.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A29.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE ELEMENTS
ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
STRUCTURAL STEEL SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE ARCHITECT. COORDINATE FINISH
PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE
A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
GALVANIZE ALL EXPOSED STEEL.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS AND
CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE WET WEIGHT OF
CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION WHERE POSSIBLE.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN ACCORDANCE WITH ASTM A924 G90.
NO SCALESF-001
4 TYPICAL SLAB ON METAL DECK OPENING FRAME DETAIL
NO SCALESF-001
3 TYPICAL CONCRETE FLOOR OPENING FRAME
Revisions: Date:
N
A
BC
D x15 xS x14 x13 x12 x11 x10 x9 x8 xR xQ xP xN xM xL xK xJ
B200-SF101
(F V
(F
V
(F V
(F
V
(F V
(F
V
(F V
21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) 21' - 8" (FV) x8 x9 xK x9 x8 xK x9 x8 xK
1'
3'
1'
1' - 7 3/4"
1' - 1"
3' - 8" 8" 3' - 8"
1'
3'
EX. CONC. BEAM
TO REMAIN
(F V
EX. 5 ½" CONC.
SLAB TO REMAIN
DIAGONAL HATCH DENOTES:
NEW 5 ½" CONC. SLAB W/ #4 EA. WAY
@ 8" OC. W/ FIBER REINFORCING.
SEE DETAIL 3/B200-SF101.
EX. CONC. COLUMN
TO REMAIN
TEMPORARY FORM
AS REQUIRED
EX. CONC. SLAB PER
PLAN TO REMAIN
#4 x 1' - 5" LONG @ 4" O.C. MAX., STAGGERED
HIGH & LOW, FULL PERIMETER OF OPENING.
DRILL INTO EX. CONC. SLAB & SET W/ 2-PART
CHEMICAL ADHESIVE SYSTEM. IF UNABLE TO
ACHIEVE FULL DEVELOPMENT LENGTH, 90
DEG. HOOKED BARS MAY BE USED.
#4 EA. WAY @ 8" OC
MAX. TOP & BOTTOM
EX. CONC. SLAB PER
PLAN TO REMAIN, TYP
T/EX. SLAB
T/NEW SLAB TO
MATCH T/EX. SLAB
MIN.
4 ½" 1' - 0" MIN.
T Y
P 1"
C
LR
T Y
P 1"
C
LR
DASHED LINE INDICATES
REINF. BEYOND, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.A
R
.r v t
/2
/2
:4
:0
P
M
B200-SF101
FIRST-FIFTEENTH FLOOR
FRAMING PLAN
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 LKL LKB
NOT TO SCALE
KEY PLANSCALE: 1/16" = 1'-0"B200-SF101
1 FIRST-FIFTEENTH FLOOR FRAMING PLAN
SCALE: 1/4" = 1'-0"B200-SF101
2 ENLARGED FLOOR 1-15 FRAMING PLAN
SCALE: 1" = 1'-0"B200-SF101
3 INFILL OF EXISTING OPENING
SHEET NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS NOT SHOWN. CONTRACTOR SHALL
VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION & IMMEDIATELY NOTIFY ARCHITECT &
ENGINEER OF ANY DISCREPANCIES.
2. ALL EX. CONSTRUCTION SHOWN IN PLAN AND/OR SECTION WAS DERIVED FROM EXISTING
DRAWINGS & MUST BE FIELD VERIFIED (FV). IF ANY DISCREPANCIES ARE DISCOVERED
BETWEEN THE INFORMATION SHOWN ON THE DRAWINGS & ACTUAL CONDITIONS, IMMEDIATELY
CONTACT ARCHITECT & ENGINEER FOR DIRECTION BEFORE PROCEEDING WITH THE WORK.
N
0' 8' 16'4' 32'
N
Revisions: Date:
| SF-001 - STRUCTURAL GENERAL NOTES & TYPICAL DETAILS |
| B200-SF101 - FIRST-FIFTEENTH FLOOR FRAMING PLAN |
File details come from the government source that posted it. Updated .