Attachment 19 - Drawings - 578-701.M.20230531_2.pdf
PDF 19 MB Posted
- Attached to
- 36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation Federal contract opportunity
- Solicitation number
- 36C77623B0043
About this file
This document contains details of a federal contract opportunity for infrastructure upgrades at a Department of Veterans Affairs facility in Hines, Illinois. Solicitation number 36C77623B0043 seeks proposals for EHRM infrastructure upgrades, including drawings provided in the 19MB Attachment 19 file. The opportunity is a special notice posted on the Department of Veterans Affairs Technology Acquisition Center Austin website. Proposals are due based on the response date specified in the full solicitation. The awarded firm will be contracted to provide necessary IT infrastructure upgrade services and support at the Hines VA medical center, replacing or improving existing electronic health records and related systems. The agreement will be managed by the Department of Veterans Affairs Technology Acquisition Center Austin, which currently utilizes an incumbent for these services.
View the file
Other files for this federal contract opportunity
Show all 50
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H T
B100-M101
B100-M101
TR
TR
N
BATH
BATH
BEDROOM
BATH
BATH
BEDROOM
BEDROOM
BEDROOM
BATH
BATH
BEDROOM
BEDROOM
BATH
BATH
BEDROOM
BATH
BATH
BEDROOM
BEDROOM
BEDROOM
BATH
BATH
BEDROOM
BEDROOM
HALL
HALL
OFFICE
MECHANICAL
ELEVATOR EQUIP.
BATH
GUEST TOILET
LAUNDRY
HALL
HALL
LIVING ROOM
DINNING ROOM
FAMILY ROOM
HALL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:4
:3
B100-M101
FIRST LEVEL FLOOR PLAN -
OVERALL - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SCALE: 3/32" = 1'-0"B100-M101
1 FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL
SCALE: 1/4" = 1'-0"B100-M101
2 FIRST LEVEL - ENLARGED DEMO PLAN - MECHANICAL - TR-017
SCALE: 1/4" = 1'-0"B100-M101
3 FIRST LEVEL - ENLARGED FLOOR PLAN - MECHANICAL - TR-017
0' 4' 8' 12'2'
NOT TO SCALE
KEY PLAN
N
0' 4' 8' 16' 32'
0' 4' 8' 12'2'
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
ANCHORING INTO THE BRICK SURFACE IS NOT ALLOWED AT HINES.
Revisions: Date:
H
B113-M101
B113-M101
TR
A138
B1 B2 B3 B4 B5 B6 B7 B8
BF
BE
BD
BC
BB
BA
BEDS BLIND REHAB
PATIENT ROOM
A138
B4 B5
BC
TR
A1388
(TYP)7
SS-113-A138-1
H-113-A1389
6"x6"
D1
B4 B5
BC
CP-113-A138
SS-113-A138-2
(TYP) 7
1 1/4" CD UP
1/2" NPW UP
M500
M500
REFS/L UP
(TYP) 7
3/4" CD
1/2" NPW
N
VERTICAL SPACE
STAIR
RCC112R
EMS TOILET
102B
EMS TOILET
123A
EMS TOILET
120A
EMS TOILET
121A
EMS TOILET
114A
EMS TOILET
117A
EMS TOILET
112A
EMS TOILET
113A
BEDS BLIND
REHAB PATIENT
ROOM
A121
BEDS BLIND
REHAB PATIENT
ROOM
A117
BEDS BLIND
REHAB PATIENT
ROOM
A120
BEDS BLIND
REHAB PATIENT
ROOM
A114
BEDS BLIND
REHAB PATIENT
ROOM
A113
BEDS BLIND
REHAB PATIENT
ROOM
A112
EMS TOILET
116B
EMS TOILET
117B
EMS TOILET
112B
EMS TOILET
108B
BEDS BLIND
REHAB PATIENT
ROOM
B107
EMS TOILET
107B
EMS TOILET
120B
BEDS BLIND
REHAB PATIENT
ROOM
B117
BEDS BLIND
REHAB PATIENT
ROOM
B116
BEDS BLIND
REHAB PATIENT
ROOM
B113
BEDS BLIND
REHAB PATIENT
ROOM
B108
BEDS BLIND
REHAB OFFICE
A143
BEDS BLIND
REHAB OFFICE
A145
BEDS BLIND
REHAB OFFICE
B227
BEDS BLIND
REHAB OFFICE
A148
BEDS BLIND
REHAB OFFICE
A149
BEDS BLIND
REHAB OFFICE
A150
BEDS BLIND
REHAB OFFICE
A151
COMMON SPACE
CORRIDOR
RCC105R
EMS TOILET
105A
BEDS BLIND
REHAB OFFICE
A109
BEDS BLIND
REHAB OFFICE
A115
BEDS BLIND
REHAB SPD
SERVICE
A132
BEDS BLIND
REHAB MEDS
A131
BEDS BLIND
REHAB STUDY
ROOM
A104
BEDS BLIND
REHAB GYM
A106
BEDS BLIND
REHAB OFFICE
A125
BEDS BLIND REHAB
CONFERENCE ROOM
A147
BEDS BLIND
REHAB OFFICE
A141
COMMON SPACE
CORRIDOR
RCC108R
EMS H.A.C.
A137
BEDS BLIND
REHAB LOUNGE
A144
EMS TOILET
A102
EMS TOILET
A103
EMS TOILET
A136
EMS TOILET
A135
ENGINEERING
MECHANICAL
ROOM
A139
ENGINEERING
ELECTRICAL
ROOM
A140
EMS TOILET
138B
BEDS BLIND
REHAB PATIENT
ROOM
A134
EMS TOILET
133A
BEDS BLIND
REHAB PATIENT
ROOM
A133
EMS TOILET
134A
EMS TOILET
128A
BEDS BLIND
REHAB PATIENT
ROOM
A128
EMS TOILET
122A
VERTICAL SPACE
ELEVATOR
RCC111R
COMMON SPACE
CORRIDOR
RCC110R
EMS TOILET
129B
BEDS BLIND
REHAB PATIENT
ROOM
B129
EMS TOILET
128B
BEDS BLIND
REHAB PATIENT
ROOM
B128
BEDS BLIND
REHAB PATIENT
ROOM
B124
EMS TOILET
115B
EMS TOILET
110B
EMS TOILET
103B
BEDS BLIND
REHAB PATIENT
ROOM
A122
COMMON SPACE
CORRIDOR
RCC109R
EMS TOILET
113B
BEDS BLIND
REHAB PATIENT
ROOM
B112
BEDS BLIND
REHAB
CONTROL DESK
B123
OI&T
TELEPHONE
A119
BEDS BLIND
REHAB OFFICE
A116
BEDS BLIND
REHAB EXAM
A130
BEDS BLIND
REHAB OFFICE
A127
BEDS BLIND
REHAB WAITING
ROOM
A126
BEDS BLIND REHAB
RECEPTION
A101
COMMON SPACE
CORRIDOR
RCC106R
BEDS BLIND
REHAB INDPNT.
LIVING APT.
A105
NUTRITION/FOOD
KITCHEN
B131
BEDS BLIND
REHAB
STORAGE
A152
ENGINEERING
PUMP ROOM
RCC101R
BEDS BLIND
REHAB
STORAGE
A110
ENGINEERING
ELECTRICAL
ROOM
A108
EMS TOILET
107A
COMMON SPACE
CORRIDOR
RCC107R
BEDS BLIND
REHAB OFFICE
A111
BEDS BLIND
REHAB
STORAGE
A107
EMS TOILET
100B
BEDS BLIND
REHAB PATIENT
ROOM
A123
BEDS BLIND
REHAB LAUNDRY
B106
BEDS BLIND
REHAB PATIENT
ROOM
B104EMS TOILET
104B
BEDS BLIND
REHAB PATIENT
ROOM
B102
BEDS BLIND
REHAB PATIENT
ROOM
B100
BEDS BLIND
REHAB PATIENT
ROOM
B101
EMS TOILET
101B
BEDS BLIND
REHAB PATIENT
ROOM
B103
BEDS BLIND
REHAB PATIENT
ROOM
B105
EMS TOILET
B167
EMS CLEAN
LINEN
B109
VERTICAL SPACE
STAIR
RCC113R
BEDS BLIND
REHAB OFFICE
A142
VERTICAL SPACE
ELEVATOR
RCC114R
COMMON SPACE
CORRIDOR
RCC104R
EMS TOILET
132B
BEDS BLIND
REHAB PATIENT
ROOM
B126
EMS TOILET
126B
ENGINEERING
ELECTRICAL
ROOM
B110
BEDS BLIND
REHAB PATIENT
ROOM
B111
BEDS BLIND
REHAB PATIENT
ROOM
B114
EMS TOILET
114B
BEDS BLIND
REHAB PATIENT
ROOM
B115
BEDS BLIND
REHAB PATIENT
ROOM
B118
EMS TOILET
118B
BEDS BLIND
REHAB LAUNDRY
B121
EMS H.A.C
B125
BEDS BLIND
REHAB DINING
B127
EMS H.A.C.
B122
COMMON SPACE
CORRIDOR
RCC103R
COMMON SPACE
CORRIDOR
RCC102R
BEDS BLIND
REHAB PATIENT
ROOM
B119
EMS TOILET
119B
BEDS BLIND
REHAB PATIENT
ROOM
B120
BEDS BLIND
REHAB PATIENT
ROOM
B132
B1 B2 B3 B4 B5 B6 B7 B8
BF
BE
BD
BC
BB
BA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
/1
/2
:3
:4
A
M
B113-M101
FIRST LEVEL FLOOR PLAN -
MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SHEET NOTES:
1. REMOVE SUPPLY DIFFUSER, VAV, AND ASSOCIATED DUCTWORK TO NEAREST ACTIVE MAIN AND CAP.
2. REMOVE HWS/HWR PIPING TO NEAREST ACTIVE MAIN AND CAP.
3. REMOVE SUPPLY DUCTWORK AS SHOWN. KEEP VAV AND ASSOCIATED VAV BOX PIPING ACCESSORIES AND
CONTROL VALVE FOR REUSE.
4. ROUTE 3/4" PUMPED CONDENSATE LINE AS INDICATED AND DISCHARGE INTO MOP SINK WITH 1 INCH AIR GAP
ABOVE FLOOD LEVEL RIM OF MOP SINK.
5. PROVIDE 1/2" DCW CONNECTION FROM WATER LINE SERVING MOP SINK. 5 MICRON INLINE SEDIMENT
PREFILTER WITH MINIMUM 2 GPM CAPACITY AND 1/2" DOUBLE CHECK VALVE ASSEMBLY MOUNTED AT 3 FOOT ABOVE FINISHED FLOOR. ROUTE 1/2" NPW AS SHOWN TO SERVE HUMIDIFIERS IN TR ROOMS. PREFILTER RATED FOR 125 PSI MAXIMUM PRESSURE, COORDINATE MODEL AND FILTER TYPE WITH VA HINES CURRENT
STOCK UNIT.
6. REUSE EXISTING VAV BOX AND RECONNECT INTO EXISTING SUPPLY DUCTWORK AND PIPING AS SHOWN.
REBALANCE OUTLETS DOWNSTREAM OF VAV BOX.
7. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-
FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL
ACCESSORIES REQUIRED FOR A COMPLETE AND COMPARABLE SYSTEM.
8. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.
9. ROUTE 1-1/4” CONDENSATE DRAIN FROM HUMIDIFIER, COMBINE WITH SPLIT SYSTEM DRAIN AND CONTINUE
AS 1-1/2” LINE DOWN TO CONDENSATE PUMP.
10. EXTEND 1/2" NPW TO HUMIDIFIER.
11. ROUTE 3/4” CONDENSATE DRAIN FROM SPLIT SYSTEM, COMBINE WITH HUMIDIFIER DRAIN AND CONTINUE AS
1-1/4” LINE DOWN TO CONDENSATE PUMP.
12. CONNECT 3/4” PUMPED CONDENSATE LINE INTO TOP OF 1-1/4” CONDENSATE DRAIN. CONTINUE COMBINED
LINE AS INDICATED AND DISCHARGE INTO MOP SINK WITH AIR GAP.
13. TAP OFF EXISTING DCW LINE SERVING MOP SINK WITH NEW ½” LINE. PROVIDE 5 MICRON INLINE SEDIMENT
PREFILTER WITH MINIMUM 2 GPM CAPACITY AND 1/2" DOUBLE CHECK VALVE ASSEMBLY MOUNTED AT 3 FOOT ABOVE FINISHED FLOOR. ROUTE 1/2” NPW AS SHOWN TO HUMIDIFIERS IN TR ROOMS. PREFILTER RATED FOR 125 PSI MAXIMUM PRESSURE, COORDINATE MODEL AND FILTER TYPE WITH VA HINES CURRENT STOCK UNIT.
GENERAL NOTES:
SCALE: 1/16" = 1'-0"B113-M101
1 FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL
SCALE: 1/4" = 1'-0"B113-M101
2 FIRST LEVEL - ENLARGED DEMO PLAN - MECHANICAL
SCALE: 1/4" = 1'-0"B113-M101
3 FIRST LEVEL - ENLARGED FLOOR PLAN - MECHANICAL
NOT TO SCALE
KEY PLAN
0' 8' 16' 32'4'
N
0' 4' 8' 12'2' 0' 4' 8' 12'2'
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
B113-M102
B113-M102
TR
A233A
B1 B2 B3 B4 B5 B6 B7 B8
BF
BE
BD
BC
BB
BA
REFS/L UP
BEDS BLIND REHAB
OFFICE
A233
B5
BC
TR
A233A
(TYP) 3
6"x6"
D1
SS-113-A233A-1
H-113-A233A 5
B5
BC
SS-113-A233A-28
M500
M500
REFS/L DN
1/2" NPW DN
1 1/4" CD UP
N
ENGINEERING
ELECTRICAL
ROOM
B213
BED BLIND
REHAB EXAM
B211
BED BLIND
REHAB OFFICE
B210
BED BLIND
REHAB COMP.
ACCESS
TRAINING
B207
BED BLIND
REHAB COMP.
ACCESS
TRAINING
B206
BED BLIND
REHAB COMP.
ACCESS
TRAINING
B203
BED BLIND
REHAB COMP.
ACCESS
TRAINING
B202
BED BLIND
REHAB COMP.
ACCESS
TRAINING
B200
BED BLIND
REHAB COMP.
ACCESS
TRAINING
A229
BED BLIND
REHAB COMP.
ACCESS
TRAINING
A228
BED BLIND
REHAB COMP.
ACCESS
TRAINING
A227
BED BLIND
REHAB OFFICE
A225
BED BLIND
REHAB
ORIENTATION &
MOBILITY RM.
A223
BED BLIND
REHAB OFFICE
A221
BED BLIND
REHAB LIVING
SKILLS
CLASSROOM
A220
BED BLIND
REHAB OFFICE
A219
BEDS BLIND
REHAB LIVING
SKILLS
CLASSROOM
A218
EMS TOILET
A217
ENGINEERING
ELECTRICAL
ROOM
A215
BEDS BLIND
REHAB LIVING
SKILLS
CLASSROOM
A213
BEDS BLIND
REHAB LIVING
SKILLS
CLASSROOM
A210
BEDS BLIND
REHAB LOCKER
ROOM
A208
BEDS BLIND
REHAB LIVING
SKILLS KITCHEN
A207
BEDS BLIND
REHAB
TUTORING ROOM
A205
BEDS BLIND
REHAB LIVING
SKILLS KITCHEN
A204
BEDS BLIND
REHAB LIVING
SKILLS KITCHEN
A203
VERTICAL SPACE
STAIR
RCC204R
VERTICAL SPACE
ELEVATOR
RCC206R
VERTICAL SPACE
ELEVATOR
RCC207R
BEDS BLIND
REHAB KILN
B236B
BEDS BLIND
REHAB HOME
MECH.
B235
BEDS BLIND
REHAB EXAM
B209
BEDS BLIND
REHAB LOW
VISION THERAPY
OFFICE
B208
BEDS BLIND
REHAB COMP.
ACCESS
TRAINING
B205
BEDS BLIND
REHAB COMP.
ACCESS
TRAINING
B204
BEDS BLIND
REHAB LOUNGE
B201
VERTICAL SPACE
STAIR
RCC205R
BEDS BLIND
REHAB FINISH
ROOM
B234B
BEDS BLIND
REHAB
RESOURCE
ROOM
A200
BEDS BLIND
REHAB
ACTIVITIES
LIVING LOUNGE
A214
BEDS BLIND
REHAB OFFICE
A209
OI&T
TELEPHONE
A233A
BEDS BLIND
REHAB OFFICE
B229
BEDS BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B227
BEDS BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B226
BEDS BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B225
BEDS BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B222
BED BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B219
BED BLIND
REHAB VISUAL
SKILL
CLASSROOM
B217
BED BLIND
REHAB OFFICE
B216
BED BLIND
REHAB VISUAL
SKILLS
CLASSROOM
B215
BEDS BLIND
REHAB OFFICE
A233
OI&T CLOSET
A234
ELECTRICAL
ROOM
A235
BEDS BLIND
REHAB LEATHER
SHOP
B236BEDS BLIND
REHAB PREP
ROOM
B236A
BEDS BLIND
REHAB OFFICE
B230
BEDS BLIND
REHAB
STORAGE
B234A
BEDS BLIND
REHAB
WOODSHOP
B234
EMS H.A.C.
B232
BEDS BLIND
REHAB SMALL
ENGINE REPAIR
B231
BEDS BLIND
REHAB MANUAL
SKILLS ASSES.
B233
BEDS BLIND
REHAB EXAM
B214
BEDS BLIND
REHAB OFFICE
B218
BEDS BLIND
REHAB OFFICE
B220
BEDS BLIND
REHAB OFFICE
B221
BEDS BLIND
REHAB OFFICE
B223
BEDS BLIND
REHAB OFFICE
B224
COMMON SPACE
CORRIDOR
RCC202R
BEDS BLIND
REHAB
STORAGE
B228
COMMON SPACE
CORRIDOR
RCC203R
BEDS BLIND
REHAB
STORAGE
A230
COMMON SPACE
CORRIDOR
RCC201R
BEDS BLIND
REHAB
STORAGE
A206A
BEDS BLIND
REHAB LIVING
SKILLS
CLASSROOM
A212
BEDS BLIND
REHAB
STORAGE
A232
EMS TOILET
A222
BEDS BLIND
REHAB
STORAGE
A226
EMS H.A.C.
A231
EMS TOILET
A224
BEDS BLIND
REHAB LIVING
SKILLS
CLASSROOM
A211
BEDS BLIND
REHAB
MULTIPURPOSE
ROOM
A206
EMS TOILET
A201
EMS TOILET
A202
B1 B2 B3 B4 B5 B6 B7 B8
BF
BE
BD
BC
BB
BA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:4
:2
B113-M102
SECOND LEVEL FLOOR PLAN -
MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SHEET NOTES:
1. REMOVE SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK AS SHOWN.
2. REMOVE RETURN GRILLE AND ASSOCIATED DUCTWORK TO NEAREST ACTIVE MAIN AND CAP.
3. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-
FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL
ACCESSORIES REQUIRED FOR A COMPLETE AND COMPARABLE SYSTEM.
4. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.
5. ROUTE 1-1/8” CONDENSATE DRAIN FROM HUMIDIFIER, COMBINE WITH SPLIT SYSTEM DRAIN AND CONTINUE
AS 1-1/2” LINE.
6. TAP OFF EXISTING DCW LINE . EXTEND 1/2" TO HUMIDIFIER.
7. ROUTE 3/4” CONDENSATE DRAIN FROM SPLIT SYSTEM, COMBINE WITH HUMIDIFER DRAIN AND CONTINUE AS
1-1/2” LINE.
8. MOUNT COOLING UNITS AT 8’-0” ABOVE FINISHED FLOOR.
GENERAL NOTES:
SCALE: 1/16" = 1'-0"B113-M102
1 SECOND LEVEL FLOOR PLAN - OVERALL - MECHANICAL
SCALE: 1/4" = 1'-0"B113-M102
2 SECOND LEVEL - ENLARGED DEMO PLAN - MECHANICAL
SCALE: 1/4" = 1'-0"B113-M102
3 SECOND LEVEL - ENLARGED FLOOR PLAN - MECHANICAL
NOT TO SCALE
KEY PLAN
0' 8' 16' 32'4'
N
0' 4' 8' 12'2' 0' 4' 8' 12'2'
Revisions: Date:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
B1 B2 B3 B4 B5 B6 B7 B8
BF
BE
BD
BC
BB
BA
SSCU-113-A138-2
SSCU-113-A138-1
SSCU-113-A233A-1
SSCU-113-A233A-2
REFS/L DN
(TYP)1
B113-M103
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
/1
/2
:3
:4
A
M
B113-M103
ROOF PLAN - MECHANICAL ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SCALE: 1/16" = 1'-0"B113-M103
1 PENTHOUSE LEVEL FLOOR PLAN - MECHANICAL
0' 8' 16' 32'4'
N
SHEET NOTES:
1. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-
FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL
ACCESSORIES REQUIRED FOR A COMPLETE AND COMPARABLE SYSTEM.
GENERAL NOTES:
NO SCALEB113-M103
2 ROOF PHOTO
Revisions: Date:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.
3. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, AND WIND BAFFLES FOR COOLING OPERATION DOWN TO -40°F AMBIENT.
4. INDOOR UNIT POWERED THROUGH ASSOCIATED OUTDOOR UNIT. REFER TO ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.
2. PROVIDE REMOTE DAMPER ACTUATION IN HARD CEILINGS.
3. COORDINATE LOCATION OF GRILLES WITH ARCHITECTURAL CEILING PLANS AND ELEVATIONS.
4. COORDINATE LOCATION OF GRILLES WITH EXISTING CEILING/WALL ELEMENTS WHERE LOCATED IN
EXISTING CEILING/WALL.
5. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES
ARE HORIZONTAL (PARALLEL TO THE FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE PARALLEL TO THE LONG DIMENSION OF THE
GRILLE.
REMARKS:
1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC
EXTERNAL ALARM.
3. PROVIDE WITH 14’, 3-CONDUCTOR CABLE WITH GROUNDED 3-PRONGE PLUG.
4. PROVIDE WITH BRASS CHECK VALVES.
REMARKS:
1. PROVIDE WITH THE FOLLOWING ACCESSORIES: WALL MOUNT BRACKET, INTEGRAL DRAIN COOLER TO LIMIT DRAIN WATER TEMPERATURE TO 140°F MAXIMUM, AND STEAM BLOWER ASSEMBLY. REFER TO PLANS FOR LOCATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:4
:2
B113-M600
MECHANICAL SCHEDULES ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
DUCT FREE SYSTEM / SPLIT SYSTEM / DX FAN COIL UNIT / COMPUTER ROOM AIR CONDITIONER SCHEDULE
MARK
NOMINAL
CAPACITY
[TONS]
TOTAL
COOLING
CAPACITY
[MBH]
INDOOR UNIT OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKS
DIMENSIONS [IN] EAT
(DB / WB)
[°F] MODEL
DIMENSIONS [IN] SUMMER
AMBIENT AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT LENGTH WIDTH HEIGHT SS-113-A138-1 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SS-113-A138-2 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SS-113-A233A-1 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SS-113-A233A-2 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SSCU-113-A138-1 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
SSCU-113-A138-2 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
SSCU-113-A233A-1 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
SSCU-113-A233A-2 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH
FACE SIZE
NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH
D1 DOUBLE DEFLECTION
SUPPLY GRILLE
0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS
KRUEGER
PRICE
300RL/SL
(1)(2)(3)(4)(5)
PUMP SCHEDULE
MARK
FLOW
[GPM]
TOTAL
HEAD
[FT]
SHUT-OFF
HEAD
[FT]
SUCTION /
DISCHARGE
SIZE
[IN]
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSHP FLA VOLTAGE
CP-113-A138 225 20 32 3/8" 0.125 1.4 115 V LITTLE GIANT HT-VCL-30-P (1)(2)(3)(4)
HUMIDIFIER SCHEDULE
MARK SERVICE
MAKE UP WATER
CONNECTION
SIZE KW
ELECTRICAL DATA STEAM
CAPACITY
[LB / HR] REMARKSVOLTAGE PHASE MANUFACTURER MODEL
H-113-A138 TR-A138 1/2" 1.9 120 V 1 DRISTEEM XTR 5 (1)
H-113-A233A TR-A233A 1/2" 1.9 120 V 1 DRISTEEM XTR 5
H T
T
B128-M101
B128-M101
S1 S2 S3 S4 S5 S6 S7 S8 S9
S10
S11 S12S13S14 S15 S16 S17 S18
S19
S20
S21
S22 S23
SA
SA.2
SB
SB.7
SC
SD
SF
SG
SH
M500
S12
SC
SD
SS-128-A151-2
H-128-A151
S12
SC
SD
CP-128-A151
SS-128-A151-1
TR
A151
6"x6"
D1
(TYP) 1
M500
M500
M500
REFS/L UP
N
A B
EMS TOILET
B127
BEDS SCID
OFFICE
A149
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:3
:4
B128-M101
FIRST LEVEL FLOOR PLAN -
MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SCALE: 1" = 30'-0"B128-M101
1 FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL
SCALE: 1/4" = 1'-0"B128-M101
2 FIRST LEVEL - ENLARGED DEMO PLAN - MECHANICAL
SCALE: 1/4" = 1'-0"B128-M101
3 FIRST LEVEL - ENLARGED FLOOR PLAN - MECHANICAL
NOT TO SCALE
KEY PLAN
N
0' 15' 30' 60'
0' 4' 8' 12'2' 0' 4' 8' 12'2'
SHEET NOTES:
1. ROUTE REFRIGERANT SUCTION AND LIQUID LINES FROM CONDENSING UNIT TO CORRESPONDING DUCT-
FREE SYSTEM. SIZE LINES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL
ACCESSORIES REQUIRED FOR A COMPLETE AND COMPARABLE SYSTEM.
2. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.
3. ROUTE 1-1/4” CONDENSATE DRAIN FROM HUMIDIFIER, COMBINE WITH SPLIT SYSTEM DRAIN AND CONTINUE
AS 1-1/4” LINE TO CONDENSATE PUMP.
4. ROUTE 3/4” PUMPED CONDENSATE LINE AS INDICATED AND DISCHARGE INTO MOP SINK WITH 1 INCH AIR GAP
ABOVE FLOOD LEVEL RIM OF MOP SINK.
5. PROVIDE 1/2” DCW CONNECTION FROM WATER LINE SERVING MOP SINK. 5 MICRON INLINE SEDIMENT
PREFILTER WITH MINIMUM 2 GPM CAPACITY AND 1/2" DOUBLE CHECK VALVE ASSEMBLY MOUNTED AT 3 FOOT ABOVE FINISHED FLOOR. ROUTE 1/2” NPW AS SHOWN TO SERVE HUMIDIFIERS IN TR ROOMS. PREFILTER RATED FOR 125 PSI MAXIMUM PRESSURE, COORDINATE MODEL AND FILTER TYPE WITH VA HINES CURRENT
STOCK UNIT.
6. REMOVE RETURN GRILLE AND ASSOCIATED DUCTWORK AS SHOWN.
7. REMOVE SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK AS SHOWN.
8. REMOVE HWS/R PIPING AS SHOWN.
9. RELOCATE THERMOSTAT AND ASSOCIATED CONTROLS AS SHOWN.
10. RELOCATED VAV AS SHOWN.
11. ROUTE 3/4” CONDENSATE DRAIN FROM SPLIT SYSTEM, COMBINE WITH HUMIDIFER DRAIN AND CONTINUE AS
1-1/4” LINE DOWN TO CONDENSATE PUMP.
12. CONTRACTOR TO VERIFY EXISTING SUPPLY DUCTWORK SIZE. SIZE NEW DUCTWORK TO MATCH EXISTING
DUCT SIZES.
13. REBALANCE EXISTING TO REMAIN DIFFUSERS TO EXISTING CFM.
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
N
A B
SSCU-128-A151-2
S1S2 S3 S4 S5 S6 S7 S8 S9
S10
S11 S12S13S14 S15 S16 S17 S18
S19
S20
S21
S22 S23
SA
SA.2
SB
SB.7
SC
SD
SF
SG
SH
SSCU-128-A151-2
REFS/L DN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:3
:4
B128-M102
ROOF FLOOR PLAN - MECHANICAL ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 Checker Author
NOT TO SCALE
KEY PLAN
N
0' 15' 30' 60'
GENERAL NOTES:
SCALE: 1" = 30'-0"B128-M102
1 ROOF PLAN - MECHANICAL
Revisions: Date:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.
3. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, AND WIND BAFFLES FOR COOLING OPERATION DOWN TO -40°F AMBIENT.
4. INDOOR UNIT POWERED THROUGH ASSOCIATED OUTDOOR UNIT. REFER TO ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PROVIDE WITH THE FOLLOWING ACCESSORIES: WALL MOUNT BRACKET, INTEGRAL DRAIN COOLER TO LIMIT DRAIN WATER TEMPERATURE TO 140°F MAXIMUM, AND STEAM BLOWER ASSEMBLY. REFER TO PLANS FOR LOCATION.
REMARKS:
1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC
EXTERNAL ALARM.
3. PROVIDE WITH 14’, 3-CONDUCTOR CABLE WITH GROUNDED 3-PRONGE PLUG.
4. PROVIDE WITH BRASS CHECK VALVES.
REMARKS:
1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.
2. PROVIDE REMOTE DAMPER ACTUATION IN HARD CEILINGS.
3. COORDINATE LOCATION OF GRILLES WITH ARCHITECTURAL CEILING PLANS AND ELEVATIONS.
4. COORDINATE LOCATION OF GRILLES WITH EXISTING WALL ELEMENTS WHERE LOCATED IN EXISTING WALL.
5. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES
ARE HORIZONTAL (PARALLEL TO THE FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE PARALLEL TO THE LONG DIMENSION OF THE
GRILLE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:3
:4
B128-M600
MECHANICAL SCHEDULES ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
SPLIT SYSTEM SCHEDULE
MARK
NOMINAL
CAPACITY
[TONS]
TOTAL
COOLING
CAPACITY
[MBH]
INDOOR UNIT OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKS
DIMENSIONS [IN] EAT
(DB / WB)
[°F] MODEL
DIMENSIONS [IN] SUMMER
AMBIENT AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT LENGTH WIDTH HEIGHT SS-128-A151-1 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SS-128-A151-2 2.5 30 50 3/8" 13 9/16" 9 15/16" 80/67 AC030BNTDCH/AA 41 - 208 V 1 0 0 MECH 5 SAMSUNG (1)(3)(4)
SSCU-128-A151-2 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
SSCU-128-A151-2 2.5 30 80/67 - 37" 13" 39 5/16" 95 157 AC030DXSCCC/AA 208 V 1 23.5 20.2 MECH 5 SAMSUNG (1)(2)(3)(5)
HUMIDIFIER SCHEDULE
MARK SERVICE
MAKE UP WATER
CONNECTION
SIZE
ELECTRICAL DATA STEAM
CAPACITY
[LB / HR] REMARKSKW VOLTAGE PHASE MANUFACTURER MODEL
H-128-A151 TR C107 1/2" 1.9 120 V 1 DRISTEEM XTR 5 (1)
PUMP SCHEDULE
MARK
FLOW
[GPH]
TOTAL
HEAD
[FT]
SHUT-OFF
HEAD
[FT]
SUCTION /
DISCHARGE
SIZE
[IN]
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSHP FLA VOLTAGE
CP-128-A151 225 20 32 3/8" 0.125 1.4 115 V LITTLE GIANT HT-VCL-30-P (1)(2)(3)(4)
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH
FACE SIZE
NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH
D1 DOUBLE DEFLECTION
SUPPLY GRILLE
0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS
KRUEGER
PRICE
300RL/SL
(1)(2)(3)(4)(5)
SDFS
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:3
B200-M000
BASEMENT PIPE SPACE FLOOR
PLAN - OVERALL - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
ANCHORING INTO THE BRICK SURFACE IS NOT ALLOWED AT HINES.
NOT TO SCALE
KEY PLAN
N
0' 16' 32' 48' 96'
Revisions: Date:
SCALE: 1/32" = 1'-0"B200-M000
1 BASEMENT PIPE SPACE FLOOR PLAN - OVERALL - MECHANICAL
xH xG xF xE xD xC xB xA x7 x6 x5 x4 x3 x2 x1
2" CWS UP
2" CWR UP
N
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:4
B200-M000A
BASEMENT PIPE SPACE FLOOR
PLAN - SECTION A - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
6. ALL EXTERIOR ANCHORS FASTENED TO THE BUILDING SHALL BE LOCATED AT THE MORTAR JOINTS.
ANCHORING INTO THE BRICK SURFACE IS NOT ALLOWED AT HINES.
SCALE: 1/16" = 1'-0"B200-M000A
1 BASEMENT PIPE SPACE FLOOR PLAN - SECTION A - MECHANICAL
NOT TO SCALE
KEY PLAN
Revisions: Date:
0' 16' 32'8'4' x15 x14 x13 x12 x11 x10 x9 x8 xH xG xF xE xD xC xB xA
2" CWR
2" CWR UP
2" CWS UP
2" CWR UP
2" CWS UP
2" CWS
2" CWR
2" CWS
CONNECT TO EXISTING
SANITARY STACK IN THIS
APPROXIMATE LOCATION
N
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:4
B200-M000B
BASEMENT PIPE SPACE FLOOR
PLAN - SECTION B - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
SCALE: 1/16" = 1'-0"B200-M000B
1 BASEMENT PIPE SPACE FLOOR PLAN - SECTION B - MECHANICAL
NOT TO SCALE
KEY PLAN
N
0' 8' 16' 32'4'
Revisions: Date:
N
0' 16' 32'8'4'
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
x15 xS x14 x13 x12 x11 x10 x9 x8 xR xQ xP xN xM xL xK xJ
4" CWS
4" CWR
PROVIDE END OF MAIN DRIP
TRAP AT BASE OF TEAM RISER
1 1/4" LPS
3/4" LPC
3" LPC
3" RELIEF VENT UP
3" SAN UP
4" CWS UP
4" CWR UP
3/4" LPC UP
1 1/4" LPS UP
PRV-1
2" STEAM VENT
12" CWS
12" CWR 4" CWS
4" CWR
2" CWS
2" CWR
2" CWS
2" CWR
CONNECT TO EXISTING
SANITARY STACK IN THIS
APPROXIMATE LOCATION
TO MECHANICAL ROOM
PRV-2
3/4" HPS 1 1/4" LPS
LOCATE PRV STATION IN READILY ACCESSIBLE
LOCATION WITHIN PIPE BASEMENT -
APPROXIMATE LOCATION SHOWN
3/4" LPC
PROVIDE END OF MAIN DRIP
TRAP AT LOW POINT OF PIPING
N
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:4
B200-M000C
BASEMENT PIPE SPACE FLOOR
PLAN - SECTION C - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
SCALE: 1/16" = 1'-0"B200-M000C
1 BASEMENT PIPE SPACE FLOOR PLAN - SECTION C - MECHANICAL
NOT TO SCALE
KEY PLAN
Revisions: Date:
N
0' 16' 32'8'4'
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
xS xR xQ xP xN xM xL xK xJ x7 x6 x5 x4 x3 x2 x1
2" CWS UP
2" CWR UP
2" CWS UP
2" CWR UP
N
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:4
B200-M000D
BASEMENT PIPE SPACE FLOOR
PLAN - SECTION D - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
SCALE: 1/16" = 1'-0"B200-M000D
1 BASEMENT PIPE SPACE FLOOR PLAN - SECTION D - MECHANICAL
NOT TO SCALE
KEY PLAN
Revisions: Date:
N
0' 16' 32'8'4'
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
A
BC
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.M
T
R
.r v t
-0
-2
:1
:4
B200-M100
BASEMENT LEVEL FLOOR PLAN -
OVERALL - MECHANICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JMM RJH
GENERAL NOTES:
SCALE: 1/32" = 1'-0"B200-M100
1 BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL
NOT TO SCALE
KEY PLAN
N
0' 16' 32' 48' 96'
Revisions: Date:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
DRAIN PANS ARE NOT REQUIRED UNDER REFRIGERANT PIPING. DRAIN PANS TO BE SUPPORTED FROM
STRUCTURE. SUSPENDING DRAIN PANS FROM OTHER BUILDING SYSTEMS IS NOT ALLOWED.
TH
T T
UPS-1
B040-1
B200-M100B
B200-M100B x15 x14 x13 x12 x11 x10 x9 x8 xH xG xF xE xD xC xB xA
B200-M100B
B200-M100B
TR
B011A
N
A
BC
D x8 xC x8 xC
H-200-B011
2" CWR DN
2" CWS DN
TR
B011A
CP-200-B011A
6"x6"
D3
BCU-200-B11A
B200-M600
M500
SURGICAL OFFICE
B019B
SURGICAL OFFICE
B019C
EMS SOILED
UTILITY
B017
EMS TOILET
B016B
SURGICAL
CONFERENCE
ROOM
B018
SURGICAL
PATIENT HOLDING
B016
LINEN SERVICE
B006B
EMS TOILET-1
B014A-1
SURGICAL
LOCKER ROOM
B010
EMS TOILET
B010A
SURGICAL OFFICE
B009
SURGICAL
LOUNGE
B011
COMMON SPACE
CORRIDOR
RCCB12R
EMS TOILET
B020A
SURGICAL EXAM
B022A
SURGICAL
RECEPTION
B020
SURGICAL EXAM
B022C
SURGICAL EXAM
B022B
SURGICAL EXAM
B022D
SURGICAL EXAM
B022E
SURGICAL EXAM
B022F
EMS TOILET
B022I
SURGICAL UTILITY
B023D
SURGICAL
URODYNAMIC LAB
B022H
EMS TOILET
B023C
EMS TOILET
B024A
EMS H.A.C.
B024F
SURGICAL
DECONTAMINATION
ROOM
B025A
SURGICAL
LOCKER ROOM
B024E
SURGICAL
LOCKER ROOM
B024D
SURGICAL
DRESSING ROOM
B024C
SURGICAL
DRESSING ROOM
B024B
SURGICAL
LOCKER ROOM
B024
EMS SOILED
UTILITY
B025B
SURGICAL
PROCEDURE
ROOM
B027
SURGICAL CLEAN
ROOM
B029B
COMMON SPACE
CORRIDOR
RCCB17R
SURGICAL
PROCEDURE
ROOM
B029
SURGICAL
PROCEDURE
ROOM
B028
EMS H.A.C.-1
B030-1
EMS TOILET
B032
OI&T COMPUTER
ROOM
B037B
ENGINEERING
ELECTRICAL
CLOSET
B037D
COMMON SPACE
CORRIDOR
RCCB16R
SURGICAL EXAM
B022G
VESTIBULE
B038G
STAFF LOUNGE
B038H
WORK ROOM
B039F EXAM 3
B039I
EXAM 6
B039L
EKG/HOLTER
B038E
TOILET-1
B138T-1
OFFICE
B039B
EXAM 2
B039H
EXAM 5
B039K
EXAM 4
B039J
EKG/HOLTER
B038F
PASSAGE
B039E
REC
B039A
NURSING SVC
ADMIN WHEEL
CHAIR STORAGE
B031
EMS TOILET
C021
ENGINEERING
ELVATOR
MACHINE ROOM
B033
COMMON SPACE
CORRIDOR
RCCB18R
OI&T
COMMUNICATIONS
B040A
EXAM 1
B039G
OI&T
COMMUNICATIONS
B040
PASSAGE
B038
MUSE
B038D
ENGINEERING ELECTRICAL CLOSET
B037A
VERTICAL SPACE
STAIR
RCCB30C
SURGICAL
ANESTHESIA
STORAGE
B037
EKG
B039D
TOILET
B039C WAITING
B039
COMMON SPACE
CORRIDOR
RCCB21R
SURGICAL
RECOVERY
B023
SURGICAL
STORAGE
B026
EMS TOILET
B023B
SURGICAL
ANESTHESIA
STORAGE
B036
EMS TOILET
B020B
COMMON SPACE
CORRIDOR
RCCB15R
COMMON SPACE
CORRIDOR
RCCB29R
SURGICAL
RCCB28R
SURGICAL OFFICE
B019
SURGICAL
ANESTHESIA
WORK ROOM
B003
EMS H.A.C.
B006
COMMON SPACE
CORRIDOR
RCCB11R
SURGICAL BLOOD
GAS ANALYSIS
B008A
SURGICAL
LOCKER ROOM
B014
COMMON SPACE
CORRIDOR
RCCB14R
SURGICAL COPY
ROOM
B012
SURGICAL OFFICE
B036A
UPS-1
B040-1 x12 xF xE
2" CWR UP/DN
2" CWS UP/DN
BCU-200-B040-1B200-M600
10"x6"
D3
6"x10"
GE7
x12 xF xE x9 x8 xB
150150
175 175 x9 x8 xB
6"x6"
D3
175175
B200-M600
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 21081
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project : 05/31/2023
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .