This document provides details for a federal contract opportunity with the Department of Veterans Affairs Technology Acquisition Center Austin. Solicitation number 36C77623B0043 seeks proposals for EHRM infrastructure upgrades at Hines, Illinois. The related file is a set of drawings with 12MB size for the project's technical requirements. Proposals are due by the date specified in the solicitation for upgrades that include necessary hardware, software, and services to modernize the agency's electronic health records management infrastructure at the specified location.
View the file
Other files for this federal contract opportunity
Show all 50
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS
SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.
WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING
THE NORMAL BRANCH.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
8. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
9. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL
BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
10. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
13. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
15. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 16195 26 05 53 FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
NORMAL BRANCH LUMINAIRE
CRITICAL BRANCH LUMINAIRE
EMERGENCY LIFE SAFETY BRANCH LUMINAIRE
LUMINAIRE SYMBOL KEY
SYMBOL: DESCRIPTION:
DP-# DISTRIBUTION PANEL 26 24 16
26 05 33HH-# HANDHOLE
26 05 37MANHOLE
UPS-# UNINTERRUPTIBLE POWER SUPPLY 26 33 53
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:
RELATED
SPECIFICATION
FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1 V3
V7 VH
FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
V1 V3
V7 VH
FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
A1 A3
A7 AH
FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION
DEVICE - CEILING MOUNTED
A
FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING
MOUNTED
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF
VS
VS
DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT. REFER TO DISC/STA SCHEDULE
AS
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
PANEL '###' 26 24 16 PANELBOARD - SURFACE MOUNT
PANEL '###' 26 24 16 PANELBOARD - RECESS MOUNT
GB 26 05 26 GROUND BUSGB
IBT 26 05 26 INTERSYSTEM BONDING TERMINATIONIBT
EPO 26 09 16 EMERGENCY STOP, N.O. CONTACTEPO
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
TR-# 26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
SW WALL CONTROL STATION26 09 33SW
26 32 13
LINEAR LUMINAIRES
TROFFER
WALL SCONCE LUMINAIRE
DOWNLIGHT LUMINAIRE
AIMABLE OR WALL WASH LUMINAIRE
INDUSTRIAL LUMINAIRE
POLE MOUNTED LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
WALL BRACKET LUMINAIRE
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
WALL/CEILING EMERGENCY EXIT SIGN
REC-SIM-L2120R 26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
REC-SIM-L2130R 26 27 26 RECEPTACLE, LOCKING L21-30R, 120/208V, 3PH
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125V
W
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
REC-QUAD-GFI 26 27 26 QUAD GFI RECEPTACLE, 125V
REFER TO LUMINAIRE
SCHEDULE
S
BLANK - PHOTOELECTRIC
SA - STAND ALONE WITH SOUNDER
REC-SIM-620R 26 27 26 RECEPTACLE, 6-20R,250V
DH DOOR HOLDARCHDH
PP EXISTING PUSH PADARCHPP
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES
ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF
WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH HIS/HER WORK.
6. THE CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,
CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE CONSTRUCTION MANAGER OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
CONSTRUCTION MANAGER'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES
AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS
DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND
TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE
REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED
ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET #/###.
3. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
4. REFER TO SHEET E-XXX FOR LUMINAIRE SCHEDULE.
5. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR
DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER
SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA
OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING
MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC
MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT
DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
FEEDERS: SWITCHBOARDS, DISTRIBUTION PANELS,
PANELBOARDS, MOTOR CONTROL CENTERS, ETC.
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO CONDUIT AND BOXES SPECIFICATION 25 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC IMC EMT PVC PVC
CONCRETE
ENCASED
HDPE
X X
X X
X X
X X
X X
X
X
CORROSIVE LOCATIONS
ELEVATED CONCRETE SLABS (ABOVE GRADE)
XX
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING WHEN PASSING
THROUGH THE PERIMETER OF THE BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
5' OR GREATER FROM THE PERIMETER OF A BUILDING FOUNDATION
WITHIN 5' FROM THE PERIMETER OF A BUILDING FOUNDATION
UNDER ROADS, DRIVES, AND VEHICLE TRAVELED WAYS. WHEN
HDPE DIRECTIONAL BORING IS ALLOWED: PROVIDE PRESSURIZED
GROUT
DUCTBANKS
(REFER TO DUCTBANK DETAILS WHEN APPLICABLE)
BARS SHALL OVERLAP 40 DIAMETERS AND SHALL EXTEND 5' BEYOND
ROADS, DRIVES, TRAVELED WAYS, ETC.
REINFORCING SHALL CONSIST OF ONE-HALF INCH DEFORMED BARS
SPACED 12 INCHES ON CENTER, PARALLELING THE DUCTS ON
BOTTOM, WITH ONE-HALF INCH DEFORMED TIE BARS SPACED
TWELVE INCHES ON CENTERS.
PROVIDE MINIMUM 3" CONCRETE COVER ON ALL SIDES OF
REINFORCING.
ENTIRE DUCTBANK SHALL BE INSTALLED ON PRECAST CONCRETE
PAVERS ON 3’ CENTERS.
CONCRETE ENCASEMENT: CONDUIT WITH A MINIMUM OF 3"
THICKNESS BETWEEN THE SURFACE OF THE CONCRETE AND THE
NEAREST CONDUIT. CONCRETE TO BE DOWELED INTO THE
FOUNDATION.
X
XX
X
X X
XX
X X
XX
X X
X
X
X
X
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
TECHNOLOGY EQUIPMENT SCHEDULE
AND SPECIFICATIONS FOR DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. [T.C] E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
NURSE CALL ROUGH-IN T-SERIES N.C.C. [E.C.] E.C.
NURSE CALL EQUIPMENT, CABLING,
AND TERMINATIONS
T-SERIES N.C.C. [OWNER]
CABLE TRAY (INCLUDING WIRE BASKET
TRAY) REFER TO SPECIFICATION
SECTION 27 05 28 FOR DEFINITION
T-SERIES E.C. E.C.
LADDER RACK T-SERIES T.C. T.C. 5.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
BONDING SYSTEM FOR TECHNOLOGY
SYSTEM, REFER TO SPECIFICATION
SECTION 27 05 26 FOR DEFINITION
T-SERIES E.C. E.C. 7. 8.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
TECHNOLOGY SERVICE ENTRANCE
CONDUITS, HANDHOLES, AND
MANHOLES
[E]T-SERIES E.C. E.C.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE
BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.
8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN
IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .E
R
.r v t
/3
/2
:3
:1
A
M
EI000
ELECTRICAL COVERSHEET ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 MKD UST
100% FINAL STAMPED
BID DOCUMENTS
Revisions: Date:
RESIDENT ENG. (TEMP.)
OIL STORAGE (UNG)
P A R K
IN
G th
S T
G R A V E L
P A R K
IN
G
P A R K
IN
G
PARKING TO 9th AVE.
PARKING
th
S T
S C O T T
D R
IV
E
PARKING
PARKING
42 200 th
S T
MRI
NINTH AVENUE
SCOTT DRIVE
PARKING
HINES BOULEVARD
P A R K
IN
G th S T R E E T
(R O O S E V E
LT
R D
PARKING
L U
E
R A
V
D
H
ENI
OB
S
P A R K
IN
G
W E S T
"B
S T
PARKING
189A
W E S T
"C
S T
TRIPP AVENUE
I
I
SOR
C
AMS
N C c
M
C YO RD
EL
CR
EV
FIFTH AVENUE
PARKING
th
S T
P A R K
IN
G th
S T
PARKING
PARKING
PARKING15
GOLF
COURSE
P A R K
IN
G
SOFTBALL
FIELD
PARKING
P A R K
IN
G
W E S T
"G S T
STORAGE
A
IR
M A
IL
R O A D
SALT
MASONRY
STORAGE
FIRST AVENUE
PARKING
EMERGENCY DRIVE
TO HINES
W E S T
B
S T R E E T
TO HINES
E M E R G E N C Y
D R I V E
FIFTH AVENUE
W E S T
C
S T R E E T
W E S T
D
S T R E E T
132S
134S
134SMT
133S
134N
132N
133N
W E S T
E
S T R E E T
135 143
144 156W
FIFTH AVENUE
W E S T
F
S T R E E T
TO HINES
W E S T
G
S T R E E T
E A S T
B
S T R E E T
FIRST AVENUE
A
FIRST AVENUE
SECOND AVENUE
C
E A S T
E
S T R E E T
131S131N
E
DN
RAMP
F
G
SECOND AVENUE
THIRD AVENUE
E A S T
F
S T R E E T
S E C O N D
A V E N U E
E A S T
G
S T R E E T
TO CERMAK RD.
PARKING
XXX
X X
X
XXXX
X X
X X
X X
XXXXX XXXX XXXX
X
X
X
XXXXX
X
X
X X
X
X
X X
X X X X X X
XXX XXXX
X
X
X
XXXX X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X
X
X
X X
X
X
X
X X
X
X X X X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X X
X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X X
X
X
X
X
X
X X
X
X
X
X
X
B
A
A B
A B
A B
BA
BA
A
B
BA A A
B
A
B
B A
B
B
A
A A A
A
B B
B B
A
A A B
A
B A
B A A
A
B
B
B
B
B A
A
B
A
B
A B
A
B
B LOOP
A LOOP
EXTERNAL A ROUTE
INTERNAL A ROUTE
EXTERNAL B ROUTE
INTERNAL B ROUTE
TO EXISTING
AT&T VAULT
OFFSITE SOURCE
LINES
B A
B
LEGEND
A B
A
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .E
R
.r v t
/3
/2
:3
:1
A
M
EI003
SITE PLAN - ELECTRICAL ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 MKD UST
100% FINAL STAMPED
BID DOCUMENTS
SCALE: 1" = 130'-0"EI003
1 SITE PLAN - ELECTRICAL
STEEL OUTLET BOX, SIZE PER N.E.C. AND
SUPPORT RIGIDLY FROM STRUCTURE
CHAIN HANGER TO STRUCTURE
6'-0" MAXIMUM LENGTH, 3/8" FLEX
CONDUIT WITH 3#18 CONDUCTORS
PENDANT MOUNTED LUMINAIRE
NOTES:
1. SELECT CHAIN LENGTH TO PROVIDE MOUNTING HEIGHT AS REQUIRED ON
DRAWINGS.
2. PROVIDE TWO CHAIN HANGERS FOR EACH LUMINAIRE. ADJUST TO HANG
LUMINAIRE LEVEL.
DEPTH OF
EQUIPMENT
O R
B O
T T
O M
O F
S
T R
U C
T U
R E
W H
IC
H
E V
E R
I S
L E
S S
O R
T O
T O
P O
F E
L E
C T
R
IC
A L E
Q U
IP
M
E N
T W
H
IC
H E
V E
R I S
H
IG
H E
R
36" FOR 208/120 VOLT SYSTEMS
42" FOR 480/277 VOLT SYSTEMS
30" OR WIDTH OF EQUIPMENT
WHICHEVER IS GREATER
GRADE, FLOOR OR PLATFORM GRADE, FLOOR OR PLATFORM
INDICATES ELECTRICAL
EQUIPMENT
WIDTH OF EQUIPMENT
SECTION ELEVATION
INDICATES WORKING SPACE REQUIRED PER LOCAL ELECTRICAL CODE.
ELECTRICAL EQUIPMENT LOCATED ABOVE OR BELOW OTHER RELATED
EQUIPMENT SHALL NOT EXTEND MORE THAN 6" IN FRONT OF SUCH EQUIPMENT.
INDICATES DEDICATED ELECTRICAL SPACE
REQUIRED PER LOCAL ELECTRICAL CODE
#6 COPPER BONDING CONDUCTOR TO
EQUIPMENT RACKS, CABLE TRAYS AND
METALLIC SLEEVES
1/2"Ø (TYP)
GROUND BAR, INSULATORS, BRACKETS
AND BONDING PROVIDED BY E.C.
TWO HOLE COMPRESSION LUG
#6 COPPER GROUND CONDUCTOR
FROM BUILDING SERVICE GROUND
MOLDED POLYESTER -
FIBERGLASS INSULATOR
4"
NOTES:
1. MOUNT BAR AT +6'-6" A.F.F.
2. STANDOFF INSULATORS MUST BE PROVIDED WHEN ZONING THE BAR.
EQUIPMENT GROUND
BONDED TO JUNCTION
BOX BY GROUNDING
SCREW. NEC 250.148
JUNCTION BOX
WIRE NUT OR APPROVED
EQUAL
(1) - STAINLESS
STEEL DRAW BAND
PRE-MOLDED RUBBER
PIPE FLASHING
ROOF INSULATION
CONDUIT,
BY E.C.SEALANT (URETHANE)
ROOF DECK
TOP OF STEEL JOIST
NOTES:
1. CONDUIT SHALL BE SUPPORTED WITHIN 24 INCHES ABOVE AND BELOW ROOF.
2. VERIFY FINAL REQUIREMENTS WITH GENERAL CONTRACTOR (G.C.) AND
ROOFING INSTALLER PRIOR TO INSTALLATION.
REFER TO ARCHITECTURAL
PLANS FOR WALL CONSTRUCTION
PLASTER RING TO COME
WITHIN 1/8" OF FINAL SURFACE
STUD
MOUNTING BRACKET SHALL PROVIDE
SUPPORT FROM STUD AND BACK OF
WALL OR TWO STUDS
NOTES:
1. THE INTENT OF THE DETAIL IS TO ALIGN AND GROUP DEVICE ROUGH-INS FOR POWER
AND LOW VOLTAGE TECHNOLOGY SYSTEMS. SOLIDLY MOUNTED AND THE SURFACE OF
THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL
SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A
MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES THE SAME
RESULTS.
2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE
WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.
3. METAL STUD-TO-STUD MOUNTING BRACKETS FOR MULTIPLE BOXES BETWEEN STUD.
ERICO CADDY RBS## SERIES, EATON B-LINE BB SERIES, OR EQUAL
4. MOUNTING SUPPORT BRACKETS SIZES FOR SINGLE BOXES IN A STUD CAVITY SHALL
MATCH THE STUD DEPTH. ERICO CADDY H## SERIES, EATON B-LINE BB## SERIES, OR
EQUAL.
5. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON
COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE
DEVICES SHALL BE INSTALLED IN THE SAME STUD CAVITY WITH MOUNTING BRACKETS
OR ALIGNED ON OPPOSITE SIDES OF A COMMON STUD WITH SEPARATE SUPPORT.
ALIGNED AND GROUPED
POWER AND LOW
VOLTAGE ROUGH-INS
PLAN VIEW
ADDITIONAL BOX SUPPORT
RATED WALLS: MOLDABLE
FIRE STOP PAD, FIVE SIDES
OF BOX. 3M TAPE MPP-43, UL
R9700
PLASTER RING TO COME
WITHIN 1/8" OF FINAL
SURFACESTUD
ADDITIONAL BOX SUPPORT
REFER TO ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION
NOTES:
1. HORIZONTAL CONDUIT CONNECTION BETWEEN BOXES LESS THAN 2'-0" NOT PERMITTED.
SEE SPECIFICATIONS AND DRAWING NOTES FOR ADDITIONAL SPACE REQUIREMENTS
BETWEEN DEVICES.
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .E
R
.r v t
/3
/2
:3
:1
A
M
EI401
ELECTRICAL DETAILS ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 MKD UST
100% FINAL STAMPED
BID DOCUMENTS
NO SCALE
CHAIN SUSPENDED MOUNTING DETAIL
1 NO SCALE
PANELBOARD EQUIPMENT CLEARANCES
NO SCALE
GROUND BAR (GB) AND INTERSYSTEM BONDING TERMINAL (IBT) DETAIL
NO SCALE
JUNCTION BOX GROUNDING DETAIL
4 NO SCALE
CONDUIT ROOF PENETRATION
5 NO SCALE
BACKBOX MOUNTING DETAIL
Revisions: Date:
NO SCALE
SIDE BY SIDE DEVICE OPENINGS
GALVANIZED STEEL CONDUIT CLAMPS
GALVANIZED STEEL CHANNEL ANCHORED
TO WALL. ANCHORS SHALL BE 1/2"Ø HLC
SLEEVE ANCHOR WITH 1 1/2" EMBEDMENT.
VIEW OF REAR OF RACK
EMT CONDUIT
SUPPORTED TO CEILING
1/2" ALL-THREAD SUPPORT
U-CHANNEL STRUT
RECEPT/E-CONNECTION AS
NOTED ON FLOOR PLANS
BASKET TRAY AS SHOWN
ON TECH DRAWINGS.
INCOMING ELECTRICAL
SERVICE. NO GROUNDING
CONDUCTOR CONSULT
LOCAL UTILITY
MAIN BONDING JUMPER,
PER NEC 250.28 (D) (1) - (D)
(3) INSTALLED AT FACTORY
BONDING BUSHING IF
METALLIC CONDUIT (TYP)
NEUTRAL BUS
EQUIP. GRND. BUS
SERVICE EQUIPMENT
ENCLOSURE (PANELBOARD,
MAIN SWITCHBOARD OR
SWITCHGEAR)
ENCLOSURE
PANELBOARD OR
DISTRIBUTION
PANELBOARD
EQUIPMENT
GROUNDING
CONDUCTOR
NEC 250.122 TABLE
#1/0 CU EQUIP.
BONDING
JUMPER
IF METALLIC
CONDUIT
EQUIP. BONDING
JUMPER PER NEC
250.102(C) OR
INSTALLED AT
FACTORY
TRANSFORMER
#6 BARE CU. (UNO.)
250.94
FEEDERS
FEEDERS
JUNCTION/PULL
BOXES
PANELBOARD W/
ISOLATED GROUND
EQUIP.
GRND.
BUSEQUIP.
GRND.
BUS
NEUTRAL
EQUIP. GROUND.
CONDUCTOR NEC
TABLE 250.122
EQUIPMENT
GROUNDING
CONDUCTORS
BONDED TO BOX
NEUTRAL
GROUNDING BAR GB OR
INTERSYSTEM BONDING
TERMINATION IBT
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V A
H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e I
I/
.7
.C
A M
P U
S .E
R
.r v t
/3
/2
:3
:1
A
M
EI402
ELECTRICAL DETAILS ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
CAMPUS
05/31/2023 Checker Author
100% FINAL STAMPED
BID DOCUMENTS
NO SCALE
CONDUIT WALL SUPPORT
1 NO SCALE
RACK RECEPTACLE DETAIL
NO SCALE
ELECTRICAL SYSTEM GROUNDING DETAIL
Revisions: Date:
REFER TO SPECIFICATION SECTIONS LED LIGHTING 26 51 19 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 3500K COLOR RENDERING INDEX (CRI) AT OR ABOVE 80.UNLESS NOTED OTHERWISE.EXTERIOR CORRELATED COLOR TEMPERATURE 4000K. COLOR RENDING INDEX (CRI) AT OR ABOVE 80,UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF
DESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE
MOUNTING HEIGHTS.
DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)
DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE
0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC
(TYPE) DRIVER:
PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED
P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED
FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER
CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE
CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED
(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP
CFSA - COLOR-FINISH SELECTION BY ARCHITECT [DESIGN SPECIFIC BLANKS]
PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)
FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR
RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC
RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE
FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE
FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR
(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC
LED LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATT LED DRIVER
MANUFACTURER AND MODELL W H DIA.
ANSI
WATT
S PER TYPE QTY
DELIVERED
LUMENS (MIN) VOLTS TYPE
F1 4' INDUSTRIAL FIXTURE WITH FROSTED
LENS.MOUNTED AT 6" BELOW FROM THE
BOTTOM OF THE CABLE TRAY. FIXTURE
SHALL BE SUSPENDED USING AIR CRAFT
CABLE.
O SP 4'-0" 6" 4 1/2" 35 W FIX LED 1 5000 120 V EB LITHONIA ZL1N
METALUX SLNED
DAYBRITE CFI FSS
F1A 4' INDUSTRIAL FIXTURE WITH FROSTED
LENS.MOUNTED AT 6" BELOW FROM THE
BOTTOM OF THE CABLE TRAY. FIXTURE
SHALL BE SUSPENDED USING AIR CRAFT
CABLE
O SP 4'-0" 6" 4 1/2" 55 W FIX LED 1 7000 120 V EB LITHONIA ZL1N
METALUX SLNED
DAYBRITE CFI FSS
F2 RECESSED 2'X2' VOLUMETRIC TROFFER. O RE 4'-0" 2'-0" 4 1/2" 38 W FIX LED 1 4800 120 V 0-10V LITHONIA 2VTL4
PHILIPS CLEAR APPEAL
METALUX CRUZ ST
F3 6" RECESSED OPEN LED DOWNLIGHT,
MEDIUM WIDE DISTRIBUTION, GALVANIZED
STEEL HOUSING, SEMI SPECULAR, WHITE
REFLECTOR AND FLANGE.
O RE 4'-0" 1'-0" 9 1/2" 16 W FIX LED 1 1500 120 V EB PRESCOLITE LF6SL
GOTHAM EVO6
NOTES:
1. {L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE.
2. SWITCH DESIGNATION FOR LIGHTING CONTROL.
LIGHTING SEQUENCE OF OPERATION
PLAN ID LIGHTING SWITCHED
{LS1} SEQUENCE: MANUAL SWITCHING WITH NO AUTOMATIC CONTROL.
ON: LIGHTS ARE TURNED ON MANUALLY BY USING WALL CONTROL DEVICE.
OFF: LIGHTS ARE TURNED OFF MANUALLY BY USING THE WALL CONTROL DEVICE.
Checked Drawn
MKD UST
UP
TENANT SPACE
PLAY ROOM
A102
TENANT SPACE
TOILET
A104
TENANT SPACE
PLAY ROOM
A101
TENANT SPACE
PLAY ROOM
A103
TENANT SPACE
OFFICE
A105
TENANT SPACE
TOILET
A107
TENANT SPACE
PLAY ROOM
A109
TENANT SPACE
PLAY ROOM
A113
TENANT SPACE
PLAY ROOM
A117
TENANT SPACE
ELECTRICAL
CLOSET
A119A
TENANT SPACE
PLAYROOM
A119
TENANT SPACE
VESTIBULE
VA1
TENANT SPACE
STORAGE
A125
TENANT SPACE
OFFICE
A129A
TENANT SPACE
OFFICE
A133
TENANT SPACE
OFFICE
A133A
TENANT SPACE
STORAGE
A139
SPACE UNDER
CONSTRUCTION
A141
MEDICAL ADMIN
BENI-TRAVEL
A143
TENANT SPACE
STORAGE
A147
DIRECTOR'S SUITE
OFFICE
A142B
DIRECTOR'S SUITE
OFFICE
A142A
DIRECTOR'S SUITE
COPY ROOM
A148B
DIRECTOR'S SUITE
OFFICE
A148A
VERTICAL SPACE
ELEVATOR
A148B
DIRECTOR'S SUITE
OFFICE
A142
DIRECTOR'S SUITE
OFFICE
A142C
DIRECTOR'S SUITE
OFFICE
A142D
TENANT SPACE
TOILET
A140
TENANT SPACE
TOILET
A138
TENANT SPACE
MECHANICAL ROOM
A134
TENANT SPACE
CHASE
RCC111C
TENANT SPACE
TEACHER'S LOUNGE
A132
TENANT SPACE
PLAY ROOM
A128
VERTICAL SPACE
ELEVATOR
RCC168R
VERTICAL SPACE
STAIR
RCC167R
TENANT SPACE
TOILET
A122
TENANT SPACE
CHASE
RCC105C
TENANT SPACE
PLAY ROOM
A118
TENANT SPACE
KITCHEN
A116
TENANT SPACE
PANTRY
A114
TENANT SPACE
CHASE
RCC104C
TENANT SPACE
CHASE
RCC102C
TENANT SPACE
PLAY ROOM
A110
TENANT SPACE
MECHANICAL ROOM
A106
TENANT SPACE
STORAGE
A108A
COMMON SPACE
CORRIDOR
RCC101R
TENANT SPACE
CHASE
RCC103C
VERTICAL SPACE
CHASE
RCC106C
VERTICAL SPACE
CHASE
RCC110C
TENANT SPACE
MECHANICAL ROOM
A136
DIRECTOR'S SUITE
CHASE
RCC112C
DIRECTOR'S SUITE
CHASE
RCC113C
DIRECTOR'S SUITE
CHASE
RCC114C
TENANT SPACE
STORAGE
A150
TENANT SPACE
CONFERENCE ROOM
B101
COMMON SPACE
CORRIDOR
RCC103R
COMMON SPACE
CORRIDOR
RCC104R
COURTYARD
B -A
E B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
REMOVE EXISTING LIGHTING, FIRE ALARM,
RECEPTACLES, BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW TR ROOM
CONSTRUCTION. MAINTAIN EXISTING
CIRCUITS IN REMAINDER OF ROOM.
1/B01-ED101B
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.E
R
.r v t
/3
/2
:4
:3
A
M
B01-ED101A
FIRST LEVEL DEMO PLAN -
SECTION A - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JFK CVK/KCK
100% FINAL STAMPED
BID DOCUMENTS
ELECTRICAL SHEET NOTES:
1. COORDINATE UTILITY OUTAGES WITH OWNER
A MINIMUM OF 72 HOURS IN ADVANCE.
2. REMOVE ALL WIRING AND CONDUIT FROM
DEMOLISHED CIRCUITS BACK TO PANEL
SERVING AREA, OR LAST ACTIVE JUNCTION
BOX.
3. COORDINATE WITH TECHNOLOGY
CONTRACTOR FOR REMOVAL/REINSTALL
REQURIEMENTS FOR ELECTRICAL DEVICES IN
ANY EXISTING TO REMAIN CEILINGS IN
CORRIDORS OR ROOMS THAT NEED TO BE
RELCOATED TO ALLOW FOR DATA
INFRASTRUCTURE INSTALLATION.
0' 8' 16' 32'4'
N
SCALE: 1/8" = 1'-0"B01-ED101A
1 FIRST LEVEL DEMO PLAN - SECTION A - ELECTRICAL
NOT TO SCALE
KEY PLAN
TENANT SPACE
CONFERENCE ROOM
B101
TENANT SPACE
OFFICE
B103
TENANT SPACE
OFFICE
B107
TENANT SPACE
OFFICE
B109 TENANT SPACE
OFFICE
B113
TENANT SPACE
CHASE
RCC117C
FISCAL STORAGE
B102
FISCAL STORAGE
B100
FISCAL OFFICE
B104
FISCAL OFFICE
B106
FISCAL OFFICE
B110
TENANT SPACE
CHASE
RCC119C
COMMON SPACE
CORRIDOR
RCC106R
FISCAL OFFICE
B114
GERIATRICS OFFICE
B115
TENANT SPACE
B116
TENANT SPACE
STORAGE
B116A
TENANT SPACE
OFFICE
B118
GERIATRICS OFFICE
B122
VERTICAL SPACE
CHASE
RCC123C
GERIATRICS CHASE
RCC122C
TENANT SPACE
CHASE
RCC121C
TENANT SPACE
OFFICE
B117
TENANT SPACE
OFFICE
B119
TENANT SPACE
OFFICE
B121
GERIATRICS TOILET
B123
GERIATRICS H.A.C.
B127
GERIATRICS TOILET
B129
VERTICAL SPACE
STAIR
RCC170R
GERIATRICS COPY
ROOM
B128
GERIATRICS OFFICE
B136A
COMMON SPACE
RCC187R
GERIATRICS OFFICE
B134
GERIATRICS OFFICE
B136
GERIATRICS
MECHANICAL ROOM
B132
GERIATRICS
MECHANICAL ROOM
B138A
VERTICAL SPACE
ELEVATOR
RCC171R
GERIATRICS
STORAGE
B138
GERIATRICS OFFICE
B140
COMMON SPACE
RCC102R
GERIATRICS OFFICE
B142
GERIATRICS STAFF
ROOM
B146A
GERIATRICS MAIN
OFFICE
B135
GERIATRICS OFFICE
B135A
GERIATRICS OFFICE
B139
GERIATRICS OFFICE
B141
GERIATRICS OFFICE
B143
GERIATRICS OFFICE
B147
GERIATRICS OFFICE
B145
GERIATRICS OFFICE
B149
GERIATRICS OFFICE
B151
GERIATRICS
STORAGE
B153 DIRECTOR'S SUITE
OFFICE
B155
NUTRITION/FOOD
OFFICE
B159
GERIATRICS
CONFERENCE ROOM
B146
GERIATRICS
STORAGE
B148
GERIATRICS TOILET
B152
MEDICAL ADMIN
STORAGE
B158A
MEDICAL ADMIN
STORAGE
B158
MEDICAL ADMIN
OFFICE
B160
MEDICAL ADMIN
OFFICE
B162
TENANT SPACE
OFFICE
B161A
COMMON SPACE
CORRIDOR
RCC109R
GERIATRICS CHASE
RCC127C
GERIATRICS CHASE
RCC118C
COMMON SPACE
CORRIDOR
RCC107R
COMMON SPACE
CORRIDOR
RCC110R
TENANT SPACE
CHASE
RCC120C
B -A
E A
B -A
E C
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
A
B
C
D
E
REMOVE EXISTING LIGHTING,
FIRE ALARM, RECEPTALCES,
BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW TR
ROOM CONSTRUCTION.
REMOVE EXISTING LIGHTING,
FIRE ALARM, RECEPTALCES,
BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW
UPS ROOM CONSTRUCTION.
1/B01-ED101C
1/B01-ED101A
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.E
R
.r v t
/3
/2
:4
:4
A
M
B01-ED101B
FIRST LEVEL DEMO PLAN -
SECTION B - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JFK CVK/KCK
100% FINAL STAMPED
BID DOCUMENTS
ELECTRICAL SHEET NOTES:
1. COORDINATE UTILITY OUTAGES WITH OWNER
A MINIMUM OF 72 HOURS IN ADVANCE.
2. REMOVE ALL WIRING AND CONDUIT FROM
DEMOLISHED CIRCUITS BACK TO PANEL
SERVING AREA, OR LAST ACTIVE JUNCTION
BOX.
3. COORDINATE WITH TECHNOLOGY
CONTRACTOR FOR REMOVAL/REINSTALL
REQURIEMENTS FOR ELECTRICAL DEVICES IN
ANY EXISTING TO REMAIN CEILING IN
CORRIDORS OR ROOMS THAT NEED TO BE
RELCOATED TO ALLOW FOR DATA
INFRASTRUCTURE INSTALLATION.
0' 8' 16' 32'4'
N
SCALE: 1/8" = 1'-0"B01-ED101B
1 FIRST LEVEL DEMO PLAN - SECTION B - ELECTRICAL
NOT TO SCALE
SOCIAL WORK
OFFICE
C141
SOCIAL WORK
OFFICE
C139
SOCIAL WORK
OFFICE
C137
SOCIAL WORK
OFFICE
C135
SOCIAL WORK
OFFICE
C133
ENVIRONMENTAL
MGMT H.A.C.
C140
ENVIRONMENTAL
MGMT TOILET
C144
VOLUNTARY
SERVICE VACANT
C142
ENGINEERING
OFFICE
C138
VERTICAL SPACE
ELEVATOR
RCC174R
SOCIAL WORK
OFFICE
C131
SOCIAL WORK
OFFICE
C129
SOCIAL WORK
OFFICE
C134A
SOCIAL WORK
OFFICE
C134
MEDICAL ADMIN
OFFICE
C132A
ENVIRONMENTAL
MGMT LINEN
CLOSET
C136
ENVIRONMENTAL
MGMT STORAGE
C138B
VERTICAL SPACE
CHASE
RCC140C
VOLUNTARY
SERVICE STORAGE
C138A
COMMON SPACE
CORRIDOR
RCC126R
MEDICAL ADMIN
MAIL ROOM
C128
MEDICAL ADMIN TEL
CLOSET
C132B
MEDICAL ADMIN
STORAGE
C126C
MEDICAL ADMIN
TRANSPORT
C130
MEDICAL ADMIN
OFFICE
C125
VERTICAL SPACE
ELEVATOR
RCC173R
VERTICAL SPACE
STAIR
RCC172R
VERTICAL SPACE
CHASE
RCC132C
ENVIRONMENTAL
MGMT TOILET
C121
NURSING SVC
ADMIN
ESCORT/TRANSPORT
C118
ENVIRONMENTAL
MGMT TOILET
C119
DIRECTOR'S SUITE
OFFICE
C117
DIRECTOR'S SUITE
OFFICE
C115
DIRECTOR'S SUITE
OFFICE
C115A
DIRECTOR'S SUITE
OFFICE
C115B
DIRECTOR'S SUITE
OFFICE
C113
NURSING SVC
ADMIN
ESCORT/TRANSPORT
C116
DIRECTOR'S SUITE
OFFICE
C114
MEDICAL ADMIN
ELECTRICAL
CLOSET
C161
NURSING SVC
ADMIN OFFICE
C108E
ENGINEERING
MECHANICAL ROOM
C109
NURSING SVC
ADMIN TOILET
C108F
NURSING SVC
ADMIN BREAK
ROOM
C108D
ENVIRONMENTAL
MGMT TOILET
C112
NURSING SVC
ADMIN OFFICE
C108C
UNASSIGNED
VACANT SPACE
VACANT
C124A
NURSING SVC
ADMIN OFFICE
C108A
NURSING SVC
ADMIN OFFICE
C172
NURSING SVC
ADMIN OFFICE
C108
ENGINEERING
STORAGE
C104
ENGINEERING
STORAGE
C102
UNASSIGNED
VACANT SPACE
STORAGE
C107
MEDICAL ADMIN
OFFICE
C105
NUTRITION/FOOD
OFFICE
C103
COMMON SPACE
RCC186R
MEDICAL ADMIN
BREAK ROOM
C100
COMMON SPACE
RCC185R
ENGINEERING
STORAGE
C124C
TENANT SPACE
TELLER
RCC117R
TENANT SPACE
C124
TENANT SPACE
STORAGE
RCC116R
TENANT SPACE
STORAGE
RCC115R
TENANT SPACE
LOUNGE
RCC114R
TENANT SPACE
STORAGE
RCC113R
TENANT SPACE
STORAGE
RCC112R
TENANT SPACE
OFFICE
RCC111R
COMMON SPACE
CORRIDOR
RCC119R MEDICAL ADMIN
REPRODUCTION
EQPT
C1253
MEDICAL ADMIN
REPRODUCTION
C126A
MEDICAL ADMIN
REPRODUCTION
C126
VERTICAL SPACE
CHASE
RCC135C
MEDICAL ADMIN
CHASE
RCC136C
MEDICAL ADMIN
CHASE
RCC137C
VSO/VET
ASSISTANCE OFFICE
C143
VSO/VET
ASSISTANCE OFFICE
D101
SOCIAL WORK
OFFICE
D102A
SOCIAL WORK
OFFICE
D102B
ENGINEERING
MACHINE SHOP
D122A
COMMON SPACE
CORRIDOR
RCC121R
COMMON SPACE
CORRIDOR
RCC120R
COMMON SPACE
CORRIDOR
RCC118R
MEDICAL ADMIN
CHASE
RCC129C
MEDICAL ADMIN
CHASE
RCC130C
NURSING SVC
ADMIN CHASE
RCC131C
SOCIAL WORK
SUPPLY CLOSET
D102C
COURTYARD
COURTYARD
37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
A
B
C
D
E
REMOVE EXISTING LIGHTING, FIRE ALARM,
RECEPTACLES, BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW TR ROOM
CONSTRUCTION. MAINTAIN EXISTING
CIRCUITS IN REMAINDER OF CORRIDOR.
REMOVE EXISTING LIGHTING, FIRE ALARM,
RECEPTACLES, BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW UPS ROOM
CONSTRUCTION. MAINTAIN EXISTING
CIRCUITS IN REMAINDER OF CORRIDOR.
1/B01-ED101D
1/B01-ED101B
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.E
R
.r v t
/3
/2
:4
:4
A
M
B01-ED101C
FIRST LEVEL DEMO PLAN -
SECTION C - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JFK CVK/KCK
100% FINAL STAMPED
BID DOCUMENTS
ELECTRICAL SHEET NOTES:
1. COORDINATE UTILITY OUTAGES WITH OWNER
A MINIMUM OF 72 HOURS IN ADVANCE.
2. REMOVE ALL WIRING AND CONDUIT FROM
DEMOLISHED CIRCUITS BACK TO PANEL
SERVING AREA, OR LAST ACTIVE JUNCTION
BOX.
3. COORDINATE WITH TECHNOLOGY
CONTRACTOR FOR REMOVAL/REINSTALL
REQURIEMENTS FOR ELECTRICAL DEVICES IN
ANY EXISTING TO REMAIN CEILING IN
CORRIDORS OR ROOMS THAT NEED TO BE
RELCOATED TO ALLOW FOR DATA
INFRASTRUCTURE INSTALLATION.
4. EXISTING
0' 8' 16' 32'4'
N
SCALE: 1/8" = 1'-0"B01-ED101C
1 FIRST LEVEL DEMO PLAN - SECTION C - ELECTRICAL
NOT TO SCALE
KEY PLAN
KEYNOTES:
1. EXISTING LIGHT SWITCH TO BE REMOVED AND
RELOCATED TO NEW LOCATION.
SOCIAL WORK
OFFICE
D102E
SOCIAL WORK
OFFICE
D102D
VSO/VET
ASSISTANCE OFFICE
D103
VSO/VET
ASSISTANCE OFFICE
D105
VSO/VET
ASSISTANCE OFFICE
D107
VSO/VET
ASSISTANCE OFFICE
D109
ENGINEERING
MECHANICAL ROOM
D100A
ENVIRONMENTAL
MGMT TOILET
D104
ENVIRONMENTAL
MGMT TOILET
D106
ENVIRONMENTAL
MGMT TOILET
D108
MEDICAL
RESEARCH/DEV
STORAGE
D110
VSO/VET
ASSISTANCE OFFICE
D113
MEDICAL
RESEARCH/DEV
OFFICE
D115
MEDICAL
RESEARCH/DEV
STORAGE
D112A
MEDICAL
RESEARCH/DEV
STORAGE
D112B
MEDICAL
RESEARCH/DEV
STORAGE
D112C
MEDICAL
RESEARCH/DEV
STORAGE
D112D
MEDICAL
RESEARCH/DEV
STORAGE
D112E
MEDICAL
RESEARCH/DEV
STORAGE
RCC123R
MEDICAL
RESEARCH/DEV
OFFICE
D114
MEDICAL
RESEARCH/DEV
OFFICE
D117
MEDICAL
RESEARCH/DEV
OFFICE
C459
MEDICAL
RESEARCH/DEV
OFFICE
C460
MEDICAL
RESEARCH/DEV
OFFICE
D123
MEDICAL
RESEARCH/DEV
OFFICE
D125
VERTICAL SPACE
CHASE
RCC145C
MEDICAL
RESEARCH/DEV
CORRIDOR
RCC124R
MEDICAL
RESEARCH/DEV
STORAGE
D116
VERTICAL SPACE
STAIR
RCC175R
VERTICAL SPACE
ELEVATOR
RCC176R
VERTICAL SPACE
CHASE
RCC148C
ENVIRONMENTAL
MGMT H.A.C.
D122
PROSTHETICS
RCC131.3R
ENGINEERING
SOILED UTILITY
RCC129R
ENVIRONMENTAL
MGMT TOILET
D129 ENVIRONMENTAL
MGMT TOILET
D133
MED SERVICE
ADMIN OFFICE
D135 MED SERVICE
ADMIN OFFICE
D137
MED SERVICE
ADMIN OFFICE
D139
MEDICAL
RESEARCH/DEV
ELECTRICAL
CLOSET
D121a
VERTICAL SPACE
CHASE
RCC150C
MED SERVICE
ADMIN OFFICE
D141
MED SERVICE
ADMIN OFFICE
D143
MED SERVICE
ADMIN OFFICE
D145
MED SERVICE
ADMIN OFFICE
D147 MED SERVICE
ADMIN
CONFERENCE ROOM
D149
ENVIRONMENTAL
MGMT TOILET
RCC134R
MED SERVICE
ADMIN OFFICE
E101
NURSING SVC
ADMIN OFFICE
E101A
MED SERICE ADMIN
OFFICE
E103
MED SERVICE
ADMIN ADMIN PIV
BADGING
E105
MED SERVICE
ADMIN STORAGE
E102C
MED SERVICE
ADMIN OFFICE
E102D
MED SERVICE
ADMIN OFFICE
E102E
MED SERVICE
ADMIN OFFICE
E104A
MED SERVICE
ADMIN OFFICE
E104D
MED SERVICE
ADMIN STORAGE
E104E
COMMON SPACE
MECHANICAL ROOM
D108A
ENVIRONMENTAL
MGMT
RCC131.2R
COMMON SPACE
CORRIDOR
RCC125R
COMMON SPACE
CORRIDOR
RCC128R
VERTICAL SPACE
CHASE
RCC144C
COMMON SPACE
LOBBY
DLOBBY
B -A
E C
B -A
E E
56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73
A
B
C
D
E
EXISTING MSB-1-D
TO REMAIN
REMOVE EXISTING LIGHTING, FIRE
ALARM, RECEPTACLES, BACK BOXES,
ETC IN THIS AREA TO ALLOW THE NEW
TR ROOM CONSTRUCTION. MAINTAIN
EXISTING CIRCUITS IN REMAINDER OF
CORRIDOR.
1/zZB01-ED101E
1/B01-ED101C
3 2
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.E
R
.r v t
/3
/2
:4
:5
A
M
B01-ED101D
FIRST LEVEL DEMO PLAN -
SECTION D - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JFK CVK/KCK
100% FINAL STAMPED
BID DOCUMENTS
ELECTRICAL SHEET NOTES:
1. COORDINATE UTILITY OUTAGES WITH OWNER
A MINIMUM OF 72 HOURS IN ADVANCE.
2. REMOVE ALL WIRING AND CONDUIT FROM
DEMOLISHED CIRCUITS BACK TO PANEL
SERVING AREA, OR LAST ACTIVE JUNCTION
BOX.
3. COORDINATE WITH TECHNOLOGY
CONTRACTOR FOR REMOVAL/REINSTALL
REQURIEMENTS FOR ELECTRICAL DEVICES IN
ANY EXISTING TO REMAIN CEILINGS IN
CORRIDORS OR ROOMS THAT NEED TO BE
RELCOATED TO ALLOW FOR DATA
INFRASTRUCTURE INSTALLATION.
0' 8' 16' 32'4'
N
SCALE: 1/8" = 1'-0"B01-ED101D
1 FIRST LEVEL DEMO PLAN - SECTION D - ELECTRICAL
NOT TO SCALE
KEY PLAN
KEYNOTES:
1. EXISTING FOUR WAY SWITCH TO BE REMOVED.
REVISE EXISTING 3-WAY SWITCHES AS
REQUIRED TO MAINTAIN FUNCTIONALITY OF
ROOM SWITCHING.
2. EXISTING 3-WAY SWITCHES TO BE REMOVED,
REFER TO B01-EP101D FOR ADDITIONAL
WORK.
TOILET ROOM
G102-A
CHANGING ROOM
G102-B
WAITING
G100-B
SPD SERVICE
RCC150R
POLICE SECURITY
LOCKERS
F115C
POLICE SECURITY
VACANT
F108H
POLICE/SECURITY
VACANT
F108Q
POLICE/SECURITY
CORRIDOR
RCC143R
POLICE/SECURITY
LOCKERS
F115A
POLICE/SECURITY
BOOKING
F117F
POLICE/SECURITY
JAIL CELL
F117E
POLICE/SECURITY
TOILET
F117D
POLICE/SECURITY
EVIDENCE ROOM
F115Q
POLICE/SECURITY
OFFICE
F117B
POLICE/SECURITY
STORAGE
RCC152R
POLICE/SECURITY
OFFICE
F117A
POLICE/SECURITY
CORRIDOR
RCC145R
POLICE/SECURITY
CORRIDOR
RCC144R
POLICE/SECURITY
VACANT
E108J
POLICE/SECURITY
VACANT
F108L
VERTICAL SPACE
ELEVATOR
RCC179R
COMMON SPACE
RCC189R
POLICE/SECURITY
VACANT
F108I
POLICE/SECURITY
VACANT
F108K
POLICE/SECURITY
MECHANICAL ROOM
F108M
POLICE/SECURITY
TOILET
F108N
VERTICAL SPACE
CHASE
RCC165C
POLICE/SECURITY
POLICE STATION
F117
VERTICAL SPACE
STAIR
RCC180R
POLICE/SECURITY
EVIDENCE
ROOM-STORAGE
F133A
POLICE/SECURITY
STORAGE
F133
COMMON SPACE
RCC151R
COMMON SPACE
LOBBY
POLICE/SECURITY
STORAGE
F137
VERTICAL SPACE
ELEVATOR
RCC181R
COMMON SPACE
CORRIDOR
RCC147R
POLICE/SECURITY
OFFICE
F115OO
MEDICAL ADMIN
OFFICE
F140A
FISCAL STORAGE
F148A
FISCAL CHASIER
F148
LIBRARY OFFICE
F145
LIBRARY OFFICE
F145A
LIBRARY OFFICE
F145B
ENVIRONMENTAL
MGMT TOILET
F147
COMMON SPACE
CORRIDOR
RCC148R
COMMON SPACE
ENGINEERING
EQUIPMENT
F151
LIBRARY
F155A
LIBRARY
F155
SOCIAL WORK
OFFICE
F152
CANTEEN SERVICE
TELEPHONE
F135
COMMON SPACE
MECHANICAL ROOM
F158
LIBRARY
F159A
LIBRARY
F159B
VERTICAL SPACE
PIPE CHASE
RCC160C
ENVIRONMENTAL
MGMT TOILET
F162
VERTICAL SPACE
PIPE CHASE
RCC159C
ENVIRONMENTAL
MGMT H.A.C.
F164
LIBRARY STORAGE
F161
COMMON SPACE
CORRIDOR
RCC155R
POLICE/SECURITY
CHASE
RCC164C
VERTICAL SPACE
CHASE
RCC149C
MEDICAL MEDIA
THEATER
F157
MEDICAL MEDIA
CHASE
RCC146C
COMMON SPACE
CORRIDOR
RCC156R
COMMON SPACE
CORRIDOR
RCC153R
COMMON SPACE
CORRIDOR
RCC154R
MEDICAL MEDIA
CHASE
RCC141C
SPD SERVICE
RCC149R
RECEPTION
G100-A
B -A
E E
B -A
E G
93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110
A
B
C
D
E
REMOVE EXISTING LIGHTING, FIRE ALARM,
RECEPTALCES, BACK BOXES, ETC IN THIS
AREA TO ALLOW THE NEW TR ROOM
CONSTRUCTION. MAINTAIN EXISTING
CIRCUITS IN REMAINDER OF ROOM.
1/B01-ED101G
1/zZB01-ED101E
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project :
B
IM
/2
V
A H in e s E
H R
M I n fr a s tr u c tu re D e s ig n P h a s e
I I/
-7
.B
.E
R
.r v t
/3
/2
:4
:5
A
M
B01-ED101F
FIRST LEVEL DEMO PLAN -
SECTION F - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADE
5000 5TH AVE, HINES, IL 60141
578-21-701
05/31/2023 JFK CVK/KCK
100% FINAL STAMPED
BID DOCUMENTS
ELECTRICAL SHEET NOTES:
1. COORDINATE UTILITY OUTAGES WITH OWNER
A MINIMUM OF 72 HOURS IN ADVANCE.
2. REMOVE ALL WIRING AND CONDUIT FROM
DEMOLISHED CIRCUITS BACK TO PANEL
SERVING AREA, OR LAST ACTIVE JUNCTION
BOX.
3. COORDINATE WITH TECHNOLOGY
CONTRACTOR FOR REMOVAL/REINSTALL
REQURIEMENTS FOR ELECTRICAL DEVICES IN
ANY EXISTING TO REMAIN CEILINGS IN
CORRIDORS OR ROOMS THAT NEED TO BE
RELCOATED TO ALLOW FOR DATA
INFRASTRUCTURE INSTALLATION.
0' 8' 16' 32'4'
N
SCALE: 1/8" = 1'-0"B01-ED101F
1 FIRST LEVEL DEMO PLAN - SECTION F - ELECTRICAL
NOT TO SCALE
J
S
TOILET ROOM
G102-C
MECH ROOM
G102-D
CALL CENTER
G101-A
SPACE UNDER
CONSTRUCTION
CHASE
RCC125C
SPACE UNDER
CONSTRUCTION
CHASE
RCC134C
PANTRY
G100-M
ADMIN
WORKSTATION
G100-O
CONFERENCE ROOM
G100-R
VERTICAL SPACE
CHASE
RCC108C
VERTICAL SPACE
ELEVATOR
RCC182R
SPACE UNDER
CONSTRUCTION
STORAGE
RCC157R
VERTICAL SPACE
STAIR
RCC183R
ENGINEERING
ELECTRICAL
CLOSET
RCC158R
COMMON SPACE
CORRIDOR
RCC162R
COPY/ MAIL ROOM
G100-T
TENANT SPACE
OFFICE
G130
TENANT SPACE
COPY ROOM
G132
TENANT SPACE
OFFICE
G133
TENANT SPACE
OFFICE
G134
COMMON SPACE
CORRIDOR
RCC163R
TENANT SPACE
OFFICE
G131A
TENANT SPACE
OFFICE
G136
TENANT SPACE
CONFERENCE ROOM
G138
TENANT SPACE
OFFICE
G140
TENANT SPACE
OFFICE
G142B
TENANT SPACE
STORAGE
G142
TENANT SPACE
OFFICE
G135
TENANT SPACE
OFFICE
G137
TENANT SPACE
OFFICE
G139
TENANT SPACE
OFFICE
G141
TENANT SPACE
STORAGE
RCC165R
TENANT SPACE
TOILET
G143
TENANT SPACE
H.A.C.
RCC164R
TENANT SPACE
TOILET
G144
TENANT SPACE
OFFICE
G142A
TENANT SPACE
OFFICE
G142C
COMMON SPACE
MECHANICAL ROOM
G146
COMMON SPACE
CHASE
RCC107C
VERTICAL SPACE
STAIR
RCC184R
COMMON SPACE
CORRIDOR
RCC166R
TENANT SPACE
H.A.C.
G145
TENANT SPACE
LOUNGE
G147
TENANT SPACE FILE
ROOM
G148B
TENANT SPACE
CHASE
RCC115C
DIRECTOR'S SUITE
COPY ROOM
G01-C
UNASSIGNED
VACANT SPACE
STORAGE
G148C
ENGINEERING
STORAGE
RCC161R
COMMON SPACE
CORRIDOR
RCC159R
B -A
E F
111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126
A
B
C
D
E
REMOVE EXISTING LIGHTING, FIRE
ALARM, RECEPTACLES, BACK
BOXES, ETC IN THIS AREA TO
ALLOW THE NEW TR ROOM
CONSTRUCTION.
1/B01-ED101F
EXISTING ATS TO REMAIN
EXISTING PANEL 1G-ICCP TO REMAIN
EXISTING UPS AND BATTERY
CABINET TO REMAIN, EC TO SLIDE
UPS TO SOUTH AS NEEDED TO
ACCOMODATE TR ROOM WALL
CONSTRUCTION
EXISTING PANEL 1G-ICCP-2 TO REMAIN
EXISTING SIMPLEX FIRE ALARM
PANEL ANS SPLICE BOX TO BE
REMOVED. 2
E
N
A B C D E F G
263 SHUMAN BOULEVARD
SUITE 550
NAPERVILLE, IL 60563
P: 630.527.2320 www.imegcorp.com
PROJECT #21003861.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6…