Attachment 06 - Drawings - 578-701.A.20230531_5.pdf

PDF 15 MB Posted

Attached to
36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation Federal contract opportunity
Solicitation number
36C77623B0043
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details for a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in Hines, Illinois. The solicitation number is 36C77623B0043 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas as a special notice. The opportunity involves upgrading the EHRM infrastructure at the Hines VA medical center, as outlined in Attachment 06, a 15MB set of technical drawings. Responses to the solicitation are due on May 31, 2023. The award date and any additional requirements or terms were not specified in the provided information.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation, newest first.
File Type Posted
36C77623B0043 0003.pdf PDF
Attachment 44 - Technical Questions and Answers Volume 6.pdf PDF
Attachment 42 - Addendum 01.pdf PDF
Attachment 43 - Addendum 02.pdf PDF
36C77623B0043 0002.pdf PDF
Attachment 39 - Technical Questions and Answers Volume 3.pdf PDF
Attachment 40 - Technical Questions and Answers Volume 4.pdf PDF
Attachment 41 - Technical Questions and Answers Volume 5.pdf PDF
Official Site Visit Sign in Sheet - 1.pdf PDF
Presolicitation - Site Walk Sign in Sheet.pdf PDF
Official Site Visit Sign in Sheet - 2.pdf PDF
Attachment 38 - Technical Questions and Answers Volume 2.pdf PDF
36C77623B0043 0001.pdf PDF
Attachment 37 - Technical Questions and Answers Volume 1.pdf PDF
Attachment 01 - Revised Specifications.pdf PDF
Attachment 02 - Drawings - 578-701.A.20230531_1.pdf PDF
Attachment 10 - Drawings - 578-701.C.20230531_3.pdf PDF
Attachment 14 - Drawings - 578-701.F.20230531_2.pdf PDF
Attachment 15 - Drawings - 578-701.G.20230531.pdf PDF
Attachment 17 - Drawings - 578-701.H.20230531_2.pdf PDF
Attachment 23 - Drawings - 578-701.T.20230531_3.pdf PDF
Attachment 22 - Drawings - 578-701.T.20230531_2.pdf PDF
Attachment 27 - Cook County - Wage Rates.pdf PDF
Attachment 32 - Calculations.pdf PDF
Attachment 13 - Drawings - 578-701.F.20230531_1.pdf PDF
Attachment 19 - Drawings - 578-701.M.20230531_2.pdf PDF
Attachment 24 - Drawings - 578-701.T2.20230531.pdf PDF
Attachment 25 - Site Self Assessment.pdf PDF
Attachment 26 - Basis of Design.pdf PDF
Attachment 30 - Milestone Schedule.pdf PDF
Attachment 34 - Cx Scope Documents.pdf PDF
Attachment 21 - Drawings - 578-701.T.20230531_1.pdf PDF
S02 - Solicitation - 36C77623B0043.pdf PDF
Attachment 04 - Drawings - 578-701.A.20230531_3.pdf PDF
Attachment 08 - Drawings - 578-701.C.20230531_1.pdf PDF
Attachment 11 - Drawings - 578-701.E.20230531_1.pdf PDF
Attachment 16 - Drawings - 578-701.H.20230531_1.pdf PDF
Attachment 20 - Drawings - 578-701.S.20230531.pdf PDF
Attachment 31 - Facility Technology Needs Report _FTNR_.pdf PDF
Attachment 33 - Equipment Cut Sheets.pdf PDF
Attachment 36 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 03 - Drawings - 578-701.A.20230531_2.pdf PDF
Attachment 05 - Drawings - 578-701.A.20230531_4.pdf PDF
Attachment 07 - Drawings - 578-701.A.20230531_6.pdf PDF
Attachment 09 - Drawings - 578-701.C.20230531_2.pdf PDF
Attachment 12 - Drawings - 578-701.E.20230531_2.pdf PDF
Attachment 18 - Drawings - 578-701.M.20230531_1.pdf PDF
Attachment 28 - QA-QC Plans.pdf PDF
Attachment 29 - Project BIM Execution Plan.pdf PDF
Attachment 35 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 50

36C77623B0043 - EHRM Infrastructure Upgrades - Hines, IL - Solicitation has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TR

6' - 7 3/4" 1' - 10" 5' - 0" 3' - 8 3/4"

6'

1/ 2"

1/ 4"

3'

/2

10' - 10 1/2"

953A x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

953A

S3C.GW

S3C.G

IN-03.01

IN-03.01

TR

E 8' - 0" 11

3/ 4"

10' - 5 1/2"

4' - 1" 6' - 4 1/2"

6'

0"

6' - 3 1/2" x9 x8 xK

B 8' - 0"

D 8' - 0"

FLEX

953A

B 8' - 0"

22 9

1'

3' - 8" 4' - 0 1/4"

3'

4'

2 2

6' - 4" 2' - 1 3/4" 5' - 0" 3' - 8 3/4"

6' - 3 1/2"

/2

2'

/4

4' - 6" x9 x8 xK

D 8' - 0"

2' - 2 1/2" 5' - 0" 3' - 8 3/4"

1'

1'

1/ 4"

4" 4'

1/

2" 6'

0" x9 x8 xK

B 8' - 0"

6' - 3 1/4"

TR

6' - 11" 1' - 9 1/4"

5' - 0" 3' - 8 1/4"

6'

/2

3'

/2

10' - 10 1/2"

858A x9 x8 xK

SD-1

RB-1

P-1FEC

FLEX

858A

S3C.GW

S3C.G

IN-03.01

IN-03.01

TR

B 8' - 0"

E 8' - 0" 11

/4

10' - 4 1/4"

6'

6' - 6 3/4" x9 x8 xK

B 8' - 0"

FLEX

858A

B 8' - 0"

22 9

1'

3' - 8" 4' - 0 1/4"

3'

4'

2 2

6' - 7" 2' - 1 1/4" 5' - 0" 4' - 0 1/4"

6' - 6 3/4"

/2

2'

/4 x9 x8 xK

7B 8' - 0"

2' - 1 1/2" 5' - 0" 3' - 8 1/4"

1' x9 x8 xK

B 8' - 0"

B 8' - 0"

8'

/4

6' - 6 3/4"

TR

6' - 7 1/4" 1' - 8" 5' - 0" 3' - 8 3/4"

7'

/4

3'

/2

10' - 8 1/4"

3/ 4"

3 772A x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

772A

S3C.GW

S3C.G

IN-03.01

IN-03.01

TR

E 8' - 5"

D 8' - 5"

10' - 3 1/2"

3' - 6 1/2" 6' - 9"

7'

6' - 3" x9 x8 xK

B 8' - 0"

FLEX

772A

B 8' - 0"

22 9

1'

3' - 8" 4' - 0 1/4"

3'

4'

2 2

6' - 7 1/4" 1' - 8" 5' - 0" 3' - 8 3/4"

/2

5"

3' - 7 3/4" 6' - 9"

6' - 3" x9 x8 xK

D 8' - 5"

2' - 0 1/4" 5' - 0" 3' - 8 3/4"

1'

4' - 0" 6' - 9"

7'

4'

/2

5" 2'

/2 x9 x8 xK

B 8' - 0"

6' - 3"

VERTICAL SPACE

ELEVATOR

RCC729C

VERTICAL SPACE

ELEVATOR

RCC730C

VERTICAL SPACE

CHASE

RCC735C

VERTICAL SPACE

CHASE

773A

COMMON SPACE

CORRIDOR

RCC726R

VERTICAL SPACE

ELEVATOR

RCC729C

VERTICAL SPACE

ELEVATOR

RCC730C

VERTICAL SPACE

CHASE

RCC735C

VERTICAL SPACE

CHASE

773A

VERTICAL SPACE

RC729R

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

ELEVATOR

RCC729C

VERTICAL SPACE

ELEVATOR

RCC730C

VERTICAL SPACE

CHASE

RCC735C

VERTICAL SPACE

CHASE

773A

VERTICAL SPACE

RC729R

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

ELEVATOR

RCC729C

VERTICAL SPACE

ELEVATOR

RCC730C

VERTICAL SPACE

CHASE

RCC735C

VERTICAL SPACE

CHASE

773A

VERTICAL SPACE

CHASE

RCC834C

VERTICAL SPACE

CHASE

838A

VERTICAL SPACE

ELEVATOR

RCC833C

VERTICAL SPACE

ELEVATOR

RCC832C

COMMON SPACE

CORRIDOR

RCC825R

VERTICAL SPACE

CHASE

RCC834C

VERTICAL SPACE

CHASE

838A

VERTICAL SPACE

ELEVATOR

RCC833C

VERTICAL SPACE

ELEVATOR

RCC832C

VERTICAL SPACE

CHASE

RCC823R

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

CHASE

RCC834C

VERTICAL SPACE

CHASE

838A

VERTICAL SPACE

ELEVATOR

RCC833C

VERTICAL SPACE

ELEVATOR

RCC832C

VERTICAL SPACE

CHASE

RCC823R

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

CHASE

RCC834C

VERTICAL SPACE

CHASE

838A

VERTICAL SPACE

ELEVATOR

RCC833C

VERTICAL SPACE

ELEVATOR

RCC832C

VERTICAL SPACE

ELEVATOR

RCC925C

VERTICAL SPACE

ELEVATOR

RCC926C

VERTICAL SPACE

CHASE

RCC920C

VERTICAL SPACE

CHASE

954A

COMMON SPACE

CORRIDOR

RCC903R

VERTICAL SPACE

ELEVATOR

RCC925C

VERTICAL SPACE

ELEVATOR

RCC926C

VERTICAL SPACE

CHASE

RCC920C

VERTICAL SPACE

CHASE

954A

VERTICAL SPACE

ELEVATOR

RCC925C

VERTICAL SPACE

ELEVATOR

RCC926C

VERTICAL SPACE

CHASE

RCC920C

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

RCC904R

VERTICAL SPACE

CHASE

954A

VERTICAL SPACE

ELEVATOR

RCC925C

VERTICAL SPACE

ELEVATOR

RCC926C

VERTICAL SPACE

CHASE

RCC920C

NUTRITION/FOOD

PANTRY

VERTICAL SPACE

RCC904R VERTICAL SPACE

CHASE

954A

A. REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL FOR COORDINATION ITEMS. COORDINATE AS REQUIRED INCLUDING

NECESSARY FRAMING, BLOCKING, ETC.

B. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

C. PATCH EXISTING PARTITIONS WHERE NEW PARTITIONS MEET.

D. PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER ABA REQUIREMENTS.

E. WHERE NO DIMENSION IS INDICATED, FINISH DOORS 6" FROM EDGE OF STUD

FRAMING AT CORNERS UNLESS OTHERWISE NOTED.

F. REFER TO EQUIPMENT SHEETS FOR EQUIPMENT SCHEDULE AND INFORMATION.

G. LEVEL AND INFILL FLOOR SLAB TO RECEIVE NEW FLOORING. REFER TO

SPECIFICATIONS AND FLOORING MANUFACTURE'S TOLERANCES FOR ADDITIONAL

INFORMATION.

H. PROVIDE METAL PLATE ON UNDERSIDE OF FLOOR SLAB WHERE CONCRETE INFILL IS

REQUIRED AND CHIP AWAY CONCRETE AT FLOOR LEVEL TO CREATE A SLOPED

OPENING/LIP TO PATCH PENETRATIONS AND PREVENT CONCRETE INFILL CORE FROM

FALLING THROUGH OPENING TO FLOOR BELOW.

I. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

J. ALL DIMENSIONS SHOWN ARE TO FACE OF WALL FRAMING/ MASONRY UNLESS NOTED

OTHERWISE. DIMENSIONS DESIGNATES AS "CLR" OR "CLEAR" INDICATE A CLEAR

DIMENSION FROM FACE OF FINISH TO FACE OF FINISH.

K. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

L. CONTRACTOR TO MAINTAIN/REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED

BY DEMOLITION/NEW CONSTRUCTION, TYPICAL THROUGHOUT.

M. PROVIDE CONTROL JOINT ON CONTINUOUS GYPSUM BOARD WALLS GREATER THAN

30' LONG.

N. PROVIDE CONTROL JOINTS AT CORNERS OF DOORS OR WINDOWS.

O. ALL NEW PARTITIONS ARE WALL TYPE S3C.G UNLESS NOTED OTHERWISE. REFER TO

WALL TYPE GENERAL NOTES FOR WALL BOARD MATERIAL.

P. NON-RATED WALL CONSTRUCTION THAT FORMS CHASE AREAS DOES NOT REQUIRE

GYPSUM BOARD INSTALLATION ON INTERIOR OF CHASE WALL.

Q. DIMENSIONS INDICATED AS 'VIF' MAY INCREASE OR DECREASE TO MATCH FIELD

CONDITIONS. ALL OTHER DIMENSIONS WITHIN THE DIMENSION STRING MUST BE

MAINTAINED.

R. PROVIDE BLOCKING AND STRAPPING FOR WALL MOUNTED CASEWORK, FURNITURE,

AND ACCESSORIES. COORDINATE WITH FLOOR PLANS, SCHEDULES, ELEVATIONS,

AND ENGINEERING DRAWINGS FOR FULL SCOPE OF WORK.

S. PATCH WALL AREAS ABOVE AND AROUND NEW DOORS TO MATCH EXISTING. SEE

FINISH SHEETS FOR ADDITIONAL INFORMATION.

T. PATCH WALL AREA AROUND NEW FEC LOCATION. SEE FINISH SHEETS.

U. ICRA LOCATIONS SHOWN ON AE100 SERIES SHEETS. SEE SHEET AE001 FOR ICRA

DEALS. FINAL LOCATION OF PARTITIONS TO BE DETERMINED BY THE CONTRACTOR.

ARCHITECTURAL GENERAL NOTES

ARCHITECTURAL PLAN NOTES

1. PARTITION INFILL WITH METAL STUD AT 16" O.C. AND 5/8" THK. GYPSUM BOARD- PRIME

AND PAINT ON EACH SIDE (STAGGER STUD TO ACCOMMODATE EXISTING WALL

THICKNESS WHERE REQUIRED).

2. NEW PARTITION. PRIME AND PAINT.

3. NEW DOOR, FRAME, AND HARDWARE.

4. INFILL EXISTING WINDOW. SEE SHEET AE540.

5. PAINT INTERIOR OF ROOM FROM CORNER TO CORNER, FLOOR TO CEILING. SEE

SHEET AF600.

6. INSTALL NEW FLOORING. SEE SHEET AF600.

7. INSTALL NEW VINYL BASE. SEE SHEET AF600.

8. ALIGN FINISH FACE OF WALL WITH OUTER FINISH FACE OF EXISTING WALL. PROVIDE

SEAMLESS TRANSITION AND NEW FINISH. ALIGN FINISH FACE OF WALL, BOTH SIDES

WHERE APPLICABLE.

9. INFILL PORTION OF EXISTING SLAB. REFERENCE STRUCTURAL.

10. INSTALL SHAFTWALL (UL415).

11. INSTALL WALL TYPE GW (PAINT). ALL WALL MOUNTED PLYWOOD TO HAVE FP-1 WITH

P-1 TOP COAT. SEE SHEET AF600 FOR ALL OTHER WALL SURFACES. SEE AE/540 FOR

DETAILS.

12. INSTALL 24" X 36" ACCESS PANEL 4'-0" A.F.F. (2 HR.).

13. MATCH EXISTING FINISHES; WALLS, FLOORS, BASE, CEILINGS, HAND AND

GUARDRAILS, ETC. SEE SHEET AF600. ANY SPACES LEFT BLANK ARE TO BE

DETERMINED IN THE FIELD. COORDINATE EXACT REQUIREMENTS WITH FACILITY.

14. CLOTHES WASHER, 27" X 42" X 26". VA SUPPLIED.

15. CLOTHES DRYER, 27" X 42" X 28". VA SUPPLIED.

16. INSTALL SALVAGED DOOR IN NEW LOCATION. SEE DOOR SCHEDULE.

17. INSTALL RELOCATED EXISTING SIGNAGE.

18. PATCH AND REPAIR FLOOR. SEE SHEET AF600 FOR FINISHES.

19. INSTALL 5/8" THK. GYPSUM BOARD TO DECK WITH SEALANT. PRIME, PAINT, AND

INSTALL NEW VINYL BASE TO MATCH EXISTING. SEE SHEET AF600.

20. LEAK PREVENTION BARRIER. COORDINATE WITH PLUMBING AND SEE SHEET AE540.

21. PARTITION INFILL WITH CONCRETE MASONRY UNITS. MATCH EXISTING- PRIME AND

PAINT ON EACH SIDE.

22. INSTALL WALL TYPE U415 (PAINT). SEE SHEET AF600 FINISHES. SEE AE/540 FOR

DETAILS.

A. THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL

CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE

ARCHITECTURAL AND ENGINEERING ELEMENTS ARE THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS

ANY DISCREPANCIES TO ARCHITECT AND COR.

B. SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR

REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL INFORMATION.

COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS, UNLESS OTHERWISE

NOTED.

C. ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED TO

ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS AND

BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE LIGHTING LAYOUT.

THE LIGHTING SHALL BE CENTERED IN ROOMS.

D. CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.) SHALL BE

CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.

E. ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE

COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.

F. CEILING TILE REMOVED IN ORDER TO COMPLETE ABOVE CEILING WORK SHALL BE

STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES SHALL BE

REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND NEW FINISH

APPLIED TO MATCH EXISTING.

G. REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON GYPSUM

BOARD PAINT FINISH.

H. CEILINGS AFFECTED BY CONSTRUCTION ARE TO BE REPAIRED AT THE TERMINATION

POINT AND RETURNED TO "AS NEW" CONDITION.

REFLECTED CEILING GENERAL NOTES

REFLECTED CEILING PLAN NOTES

1. NEW CEILING TO MATCH EXISTING IN ADJACENT SPACE.

A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND REPAIR

NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION SHALL BE PROVIDED.

CONTRACTOR SHALL REMOVE EXISTING IMPROVEMENTS WHETHER OR NOT

SPECIFICALLY INDICATED ON THE DRAWINGS TO FACILITATE THE COMPLETION OF ALL

REQUIRED WORK. CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES

AND ITEMS REQUIRED TO BE REMOVED.

B. REFER TO ARCHITECTURAL SYMBOLS SHEET FOR DEMOLITION SYSTEMS AND

DRAWING NOMENCLATURE.

C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN UNLESS

OTHERWISE NOTED.

D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE

PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO VERIFY

NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH CONDITIONS SHALL BE

RECTIFIED BEFORE WORK MAY PROCEED.

E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE ARCHITECTURAL FLOOR

PLAN AND ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.

F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED ARE

APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF WORK TO BE

REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE NEW CONSTRUCTION.

COORDINATE DEMOLITION WORK WITH DESIGN INTENT OF NEW CONSTRUCTION TO

PROVIDE ADEQUATE AREA FOR THIS WORK.

G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION

ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHERWISE NOTED, TO ACCOMMODATE

NEW CONSTRUCTION.

H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE NEW

FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH THAT THE

CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE SMOOTH AND

UNDETECTABLE.

I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE

REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES CAN BE

REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY

CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED AND PAINTED TO

SEAMLESSLY MATCH EXISTING CEILING COLOR FOLLOWING ABOVE CEILING

DEMOLITION ACTIVITY. THIS SHALL INCLUDE REPAIR TO THE CEILING GRID,

SUSPENSION SYSTEM AND ALL ASSOCIATED ASSEMBLIES AS WELL AS THE

REPLACEMENT OF DAMAGED CEILING PANELS, WITHIN AND BEYOND PROJECT LIMITS.

J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND VENDOR

DRAWINGS.

K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE SHALL BE

REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL BE FILLED/

LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING MANUFACTURES

RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.

L. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

M. AREAS ADJACENT TO DEMOLITION AND NEW CONSTRUCTION TO BE REPAIRED TO "AS

NEW" CONDITION.

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1. REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

2. REMOVE PORTION OF EXISTING PARTITION IN ITS ENTIRETY.

3. REMOVE EXISTING DOOR, FRAME, HARDWARE, AND PORTION OF EXISTING PARTITION

TO ACCOMMODATE NEW WORK.

4. REMOVE EXISTING WINDOW IN IT'S ENTIRETY, AND PREPARE FOR RELOCATION.

5. REMOVE EXISTING WINDOW AND FRAME.

6. RELOCATE EXISTING EQUIPMENT, COORDINATE WITH FACILITY FOR FINAL LOCATION.

7. PORTION OF EXISTING CEILING TO BE REMOVED / MODIFIED AS REQUIRED FOR NEW

CEILING LAYOUT. SEE PLANS. MAINTAIN SURROUNDING CEILINGS.

8. REMOVE EXISTING FINISH FLOORING MATERIAL IN ITS ENTIRETY AND PREPARE AREA

FOR NEW VINYL TILE.

9. REMOVE EXISTING FLOOR BASE.

10. REMOVE EXISTING WALL FINISHES TO STRUCTURE. PREPARE FOR NEW WALL TYPE.

11. PREPARE EXISTING CONCRETE FLOOR FOR NEW VINYL TILE.

12. PREPARE EXISTING MASONRY WALL FOR NEW PLYWOOD FINISH.

13. REMOVE EXISTING MILLWORK CABINETS AND SHELVING.

14. REMOVE EXISTING COUNTER TOP.

15. REMOVE EXISTING HANDRAIL AND CRASHRAIL.

16. REMOVE EXISTING PLUMBING FIXTURES AND CAP UTILITIES ON FLOOR BELOW. SEE

PLUMBING DEMO SHEETS.

17. REMOVE EXISTING RAILING IN ITS ENTIRETY.

18. NOT USED.

19. REMOVE EXISTING CEILING IN ITS ENTIRETY.

20. REMOVE EXISTING BASE-BOARD HEATER.

21. PATCH AND REPAIR EXTERIOR WALL WITH EXISTING DAMAGE TO AS-NEW CONDITION.

22. REMOVE PORTION OF EXISTING FLOOR IN ITS ENTIRETY AND PREPARE AREA FOR

NEW VINYL TILE.

23. REMOVE PORTION OF EXISTING WALL FOR FIRE EXTINGUISHER CABINET. SEE SHEET

AE540 FOR CABINET DETAIL.

24. REMOVE EXISTING DOOR, FRAME, AND HARDWARE FOR SALVAGE AND REUSE. SEE

DOOR SCHEDULE.

25. REMOVE EXISTING SIGNAGE FOR SALVAGE AND REUSE.

A

REFLECTED CEILING TYPE LEGEND

TYPE GRAPHIC DESCRIPTION

B

C

D

8x8 ACOUSTICAL CEILING TILE (AT-1)

2x2 ACOUSTICAL CEILING TILE (AT-2)

2x4 ACOUSTICAL CEILING TILE (AT-3)

GYPSUM BOARD CEILING. CEILING PAINT.

E NO CEILING / EXISTING

CEILING TO REMAIN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project :

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e

I I/

-7

.B

.A

R

.r v t

/2

/2

:4

:2

A

M

B200-AE406

ENLARGED FLOOR PLANS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 LNS

SCALE: 1/4" = 1'-0"B200-AE406

9 NINTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE406

10 NINTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE406

11 NINTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE406

12 NINTH LEVEL - ENLARGED CEILING DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE406

5 EIGHTH LEVEL -ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE406

6 EIGHTH LEVEL -ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE406

7 EIGHTH LEVEL -ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE406

8 EIGHTH LEVEL -ENLARGED CEILING DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE406

1 SEVENTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE406

2 SEVENTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE406

3 SEVENTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE406

4 SEVENTH LEVEL - ENLARGED CEILING DEMO PLAN

0' 4' 8' 12'2'

Revisions: Date: JG

NOT F

OR

CONSTRUCTIO

N

6' - 7 3/4"

1' - 10 1/4"

5' - 0" 3' - 7 1/2"

7'

3'

10' - 9 1/4"

/2

1272A x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

1272A

IN-03.01

S3C.G

S3C.GW

IN-03.01

TR

E 8' - 0"

/4

10' - 4 1/2"6' - 3 1/2"

7'

/2 x9 x8 xK

B 8' - 0"

FLEX

1272A

D 8' - 0"

B 8' - 0" 7'

/4

22 9

1'

3' - 8" 1' - 4"

3'

4'

2 2

9' - 1" 5' - 0" 3' - 7 1/2"

6' - 3 1/2"

10' - 10" x9 x8 xK

D 8' - 0"

2' - 2 1/2" 5' - 0" 3' - 7 1/2"

1'

6' - 3 1/2" 10' - 10"

7'

/2

4'

1/ 2"

2' x9 x8 xK

B 8' - 0"

TR

1' - 11 3/4" 7' - 1 3/4"

1' - 9 1/2" 5' - 0" 3' - 3 3/4"

3'

10' - 6 1/4"

5'

/2

9'

/4

1161A x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

1161A

IN-03.01

11S3C.GWS3C.G

TR

B 8' - 5"

E 8' - 0"

9' - 11 3/4"6' - 9 1/2"

5'

/4 x9 x8 xK

B 8' - 0"

B 8' - 5"

FLEX

1161A

8' - 8 1/2"

8'

3/ 4"

6'

/4

22 9

1'

3' - 8" 3' - 8"

3'

4'

2 2

6' - 9 1/2" 2' - 1 3/4" 5' - 0" 3' - 3 3/4"

5' - 0 3/4"

/4

10' - 5 1/2" x9 x8 xK

6'

/4

B 8' - 5"

2' - 1 3/4" 5' - 0" 3' - 3 3/4"

1'

10' - 5 1/2"

/4

4'

/4 x9 x8 xK

B 8' - 0"

9'

/4

1' - 6"

D 8' - 0"

TR

6' - 7 3/4" 1' - 10 1/4"

5' - 0" 3' - 8 1/2"

7'

/4

3'

/2

10' - 10 1/4"

1072A x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

1072A

S3C.GW

S3C.G

IN-03.01

IN-03.01

TR

E 8' - 0"

10' - 5 1/2"

7'

/4

6' - 3 1/2"

3' - 7 1/2" 6' - 10"

1" x9 x8 xK

B 8' - 0"

D 8' - 0"

FLEX

1072A

B 8' - 0"

22 9

1'

3' - 8" 4' - 0"

3'

4'

2 2

6' - 4 1/4" 2' - 1 3/4" 5' - 0" 3' - 8 1/2"

/4

4"

6' - 3 1/2"

4' - 0 1/2" 6' - 10" x9 x8 xK

7D 8' - 0"

5' - 0" 3' - 8 1/2"

1'

7'

/4

4'

/2

4" 2'

6' - 3 1/2" 4' - 1" 6' - 10" x9 x8 xK

B 8' - 0"

VERTICAL SPACE

CHASE

RCC1021C

VERTICAL SPACE

ELEVATOR

RCC1031C

VERTICAL SPACE

ELEVATOR

RCC1032C

VERTICAL SPACE

CHASE

1073A

COMMON SPACE

CORRIDOR

RCC1007R

VERTICAL SPACE

CHASE

RCC1021C

VERTICAL SPACE

ELEVATOR

RCC1031C

VERTICAL SPACE

ELEVATOR

RCC1032C

VERTICAL SPACE

CHASE

1073A

VERTICAL SPACE

RCC1010R

UNASSIGNED VACANT

SPACE PANTRY

VERTICAL SPACE

CHASE

RCC1021C

VERTICAL SPACE

ELEVATOR

RCC1031C

VERTICAL SPACE

ELEVATOR

RCC1032C

VERTICAL SPACE

CHASE

1073A

VERTICAL SPACE

CHASE

1073A

VERTICAL SPACE

RCC1010R

UNASSIGNED VACANT

SPACE PANTRY

VERTICAL SPACE

CHASE

RCC1021C

VERTICAL SPACE

ELEVATOR

RCC1031C

VERTICAL SPACE

ELEVATOR

RCC1032C

VERTICAL SPACE

CHASE

1073A

BEDS REHAB

RCC1103R

BEDS REHAB PT/OT/KT

ROOM

BEDS REHAB PT/OT/KT

ROOM

BEDS REHAB PANTRY

ADL/KITCHEN

BEDS REHAB PT/OT/KT

ROOM

VERTICAL SPACE

CHASE

RCC1127C

BEDS REHAB PANTRY

ADL/KITCHEN

BEDS REHAB PT/OT/KT

ROOM

VERTICAL SPACE

CHASE

RCC1127C

BEDS REHAB PANTRY

ADL/KITCHEN

BEDS REHAB PT/OT/KT

ROOM

VERTICAL SPACE

ELEVATOR

RCC1222C

VERTICAL SPACE

ELEVATOR

RCC1221C

VERTICAL SPACE

CHASE

RCC1228C

VERTICAL SPACE

CHASE

1273A

COMMON SPACE

CORRIDOR

RCC1201R

VERTICAL SPACE

ELEVATOR

RCC1222C

VERTICAL SPACE

ELEVATOR

RCC1221C

ACS-PRIMARY CARE

STORAGE

VERTICAL SPACE

CHASE

RCC1228C

VERTICAL SPACE

CHASE

1273A

VERTICAL SPACE

CHASE

RCC1206R

VERTICAL SPACE

ELEVATOR

RCC1222C

VERTICAL SPACE

ELEVATOR

RCC1221C

ACS-PRIMARY CARE

STORAGE

VERTICAL SPACE

CHASE

RCC1228C

VERTICAL SPACE

CHASE

1273A

VERTICAL SPACE

CHASE

RCC1206R

VERTICAL SPACE

ELEVATOR

RCC1222C

VERTICAL SPACE

ELEVATOR

RCC1221C

ACS-PRIMARY CARE

STORAGE

VERTICAL SPACE

CHASE

RCC1228C

VERTICAL SPACE

CHASE

1273A

A. REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL FOR COORDINATION ITEMS. COORDINATE AS REQUIRED INCLUDING

NECESSARY FRAMING, BLOCKING, ETC.

B. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

C. PATCH EXISTING PARTITIONS WHERE NEW PARTITIONS MEET.

D. PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER ABA REQUIREMENTS.

E. WHERE NO DIMENSION IS INDICATED, FINISH DOORS 6" FROM EDGE OF STUD

FRAMING AT CORNERS UNLESS OTHERWISE NOTED.

F. REFER TO EQUIPMENT SHEETS FOR EQUIPMENT SCHEDULE AND INFORMATION.

G. LEVEL AND INFILL FLOOR SLAB TO RECEIVE NEW FLOORING. REFER TO

SPECIFICATIONS AND FLOORING MANUFACTURE'S TOLERANCES FOR ADDITIONAL

INFORMATION.

H. PROVIDE METAL PLATE ON UNDERSIDE OF FLOOR SLAB WHERE CONCRETE INFILL IS

REQUIRED AND CHIP AWAY CONCRETE AT FLOOR LEVEL TO CREATE A SLOPED

OPENING/LIP TO PATCH PENETRATIONS AND PREVENT CONCRETE INFILL CORE FROM

FALLING THROUGH OPENING TO FLOOR BELOW.

I. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

J. ALL DIMENSIONS SHOWN ARE TO FACE OF WALL FRAMING/ MASONRY UNLESS NOTED

OTHERWISE. DIMENSIONS DESIGNATES AS "CLR" OR "CLEAR" INDICATE A CLEAR

DIMENSION FROM FACE OF FINISH TO FACE OF FINISH.

K. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

L. CONTRACTOR TO MAINTAIN/REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED

BY DEMOLITION/NEW CONSTRUCTION, TYPICAL THROUGHOUT.

M. PROVIDE CONTROL JOINT ON CONTINUOUS GYPSUM BOARD WALLS GREATER THAN

30' LONG.

N. PROVIDE CONTROL JOINTS AT CORNERS OF DOORS OR WINDOWS.

O. ALL NEW PARTITIONS ARE WALL TYPE S3C.G UNLESS NOTED OTHERWISE. REFER TO

WALL TYPE GENERAL NOTES FOR WALL BOARD MATERIAL.

P. NON-RATED WALL CONSTRUCTION THAT FORMS CHASE AREAS DOES NOT REQUIRE

GYPSUM BOARD INSTALLATION ON INTERIOR OF CHASE WALL.

Q. DIMENSIONS INDICATED AS 'VIF' MAY INCREASE OR DECREASE TO MATCH FIELD

CONDITIONS. ALL OTHER DIMENSIONS WITHIN THE DIMENSION STRING MUST BE

MAINTAINED.

R. PROVIDE BLOCKING AND STRAPPING FOR WALL MOUNTED CASEWORK, FURNITURE,

AND ACCESSORIES. COORDINATE WITH FLOOR PLANS, SCHEDULES, ELEVATIONS,

AND ENGINEERING DRAWINGS FOR FULL SCOPE OF WORK.

S. PATCH WALL AREAS ABOVE AND AROUND NEW DOORS TO MATCH EXISTING. SEE

FINISH SHEETS FOR ADDITIONAL INFORMATION.

T. PATCH WALL AREA AROUND NEW FEC LOCATION. SEE FINISH SHEETS.

U. ICRA LOCATIONS SHOWN ON AE100 SERIES SHEETS. SEE SHEET AE001 FOR ICRA

DEALS. FINAL LOCATION OF PARTITIONS TO BE DETERMINED BY THE CONTRACTOR.

ARCHITECTURAL GENERAL NOTES

ARCHITECTURAL PLAN NOTES

1. PARTITION INFILL WITH METAL STUD AT 16" O.C. AND 5/8" THK. GYPSUM BOARD- PRIME

AND PAINT ON EACH SIDE (STAGGER STUD TO ACCOMMODATE EXISTING WALL

THICKNESS WHERE REQUIRED).

2. NEW PARTITION. PRIME AND PAINT.

3. NEW DOOR, FRAME, AND HARDWARE.

4. INFILL EXISTING WINDOW. SEE SHEET AE540.

5. PAINT INTERIOR OF ROOM FROM CORNER TO CORNER, FLOOR TO CEILING. SEE

SHEET AF600.

6. INSTALL NEW FLOORING. SEE SHEET AF600.

7. INSTALL NEW VINYL BASE. SEE SHEET AF600.

8. ALIGN FINISH FACE OF WALL WITH OUTER FINISH FACE OF EXISTING WALL. PROVIDE

SEAMLESS TRANSITION AND NEW FINISH. ALIGN FINISH FACE OF WALL, BOTH SIDES

WHERE APPLICABLE.

9. INFILL PORTION OF EXISTING SLAB. REFERENCE STRUCTURAL.

10. INSTALL SHAFTWALL (UL415).

11. INSTALL WALL TYPE GW (PAINT). ALL WALL MOUNTED PLYWOOD TO HAVE FP-1 WITH

P-1 TOP COAT. SEE SHEET AF600 FOR ALL OTHER WALL SURFACES. SEE AE/540 FOR

DETAILS.

12. INSTALL 24" X 36" ACCESS PANEL 4'-0" A.F.F. (2 HR.).

13. MATCH EXISTING FINISHES; WALLS, FLOORS, BASE, CEILINGS, HAND AND

GUARDRAILS, ETC. SEE SHEET AF600. ANY SPACES LEFT BLANK ARE TO BE

DETERMINED IN THE FIELD. COORDINATE EXACT REQUIREMENTS WITH FACILITY.

14. CLOTHES WASHER, 27" X 42" X 26". VA SUPPLIED.

15. CLOTHES DRYER, 27" X 42" X 28". VA SUPPLIED.

16. INSTALL SALVAGED DOOR IN NEW LOCATION. SEE DOOR SCHEDULE.

17. INSTALL RELOCATED EXISTING SIGNAGE.

18. PATCH AND REPAIR FLOOR. SEE SHEET AF600 FOR FINISHES.

19. INSTALL 5/8" THK. GYPSUM BOARD TO DECK WITH SEALANT. PRIME, PAINT, AND

INSTALL NEW VINYL BASE TO MATCH EXISTING. SEE SHEET AF600.

20. LEAK PREVENTION BARRIER. COORDINATE WITH PLUMBING AND SEE SHEET AE540.

21. PARTITION INFILL WITH CONCRETE MASONRY UNITS. MATCH EXISTING- PRIME AND

PAINT ON EACH SIDE.

22. INSTALL WALL TYPE U415 (PAINT). SEE SHEET AF600 FINISHES. SEE AE/540 FOR

DETAILS.

A. THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL

CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE

ARCHITECTURAL AND ENGINEERING ELEMENTS ARE THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS

ANY DISCREPANCIES TO ARCHITECT AND COR.

B. SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR

REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL INFORMATION.

COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS, UNLESS OTHERWISE

NOTED.

C. ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED TO

ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS AND

BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE LIGHTING LAYOUT.

THE LIGHTING SHALL BE CENTERED IN ROOMS.

D. CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.) SHALL BE

CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.

E. ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE

COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.

F. CEILING TILE REMOVED IN ORDER TO COMPLETE ABOVE CEILING WORK SHALL BE

STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES SHALL BE

REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND NEW FINISH

APPLIED TO MATCH EXISTING.

G. REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON GYPSUM

BOARD PAINT FINISH.

H. CEILINGS AFFECTED BY CONSTRUCTION ARE TO BE REPAIRED AT THE TERMINATION

POINT AND RETURNED TO "AS NEW" CONDITION.

REFLECTED CEILING GENERAL NOTES

REFLECTED CEILING PLAN NOTES

1. NEW CEILING TO MATCH EXISTING IN ADJACENT SPACE.

A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND REPAIR

NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION SHALL BE PROVIDED.

CONTRACTOR SHALL REMOVE EXISTING IMPROVEMENTS WHETHER OR NOT

SPECIFICALLY INDICATED ON THE DRAWINGS TO FACILITATE THE COMPLETION OF ALL

REQUIRED WORK. CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES

AND ITEMS REQUIRED TO BE REMOVED.

B. REFER TO ARCHITECTURAL SYMBOLS SHEET FOR DEMOLITION SYSTEMS AND

DRAWING NOMENCLATURE.

C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN UNLESS

OTHERWISE NOTED.

D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE

PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO VERIFY

NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH CONDITIONS SHALL BE

RECTIFIED BEFORE WORK MAY PROCEED.

E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE ARCHITECTURAL FLOOR

PLAN AND ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.

F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED ARE

APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF WORK TO BE

REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE NEW CONSTRUCTION.

COORDINATE DEMOLITION WORK WITH DESIGN INTENT OF NEW CONSTRUCTION TO

PROVIDE ADEQUATE AREA FOR THIS WORK.

G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION

ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHERWISE NOTED, TO ACCOMMODATE

NEW CONSTRUCTION.

H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE NEW

FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH THAT THE

CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE SMOOTH AND

UNDETECTABLE.

I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE

REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES CAN BE

REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY

CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED AND PAINTED TO

SEAMLESSLY MATCH EXISTING CEILING COLOR FOLLOWING ABOVE CEILING

DEMOLITION ACTIVITY. THIS SHALL INCLUDE REPAIR TO THE CEILING GRID,

SUSPENSION SYSTEM AND ALL ASSOCIATED ASSEMBLIES AS WELL AS THE

REPLACEMENT OF DAMAGED CEILING PANELS, WITHIN AND BEYOND PROJECT LIMITS.

J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND VENDOR

DRAWINGS.

K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE SHALL BE

REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL BE FILLED/

LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING MANUFACTURES

RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.

L. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

M. AREAS ADJACENT TO DEMOLITION AND NEW CONSTRUCTION TO BE REPAIRED TO "AS

NEW" CONDITION.

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1. REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

2. REMOVE PORTION OF EXISTING PARTITION IN ITS ENTIRETY.

3. REMOVE EXISTING DOOR, FRAME, HARDWARE, AND PORTION OF EXISTING PARTITION

TO ACCOMMODATE NEW WORK.

4. REMOVE EXISTING WINDOW IN IT'S ENTIRETY, AND PREPARE FOR RELOCATION.

5. REMOVE EXISTING WINDOW AND FRAME.

6. RELOCATE EXISTING EQUIPMENT, COORDINATE WITH FACILITY FOR FINAL LOCATION.

7. PORTION OF EXISTING CEILING TO BE REMOVED / MODIFIED AS REQUIRED FOR NEW

CEILING LAYOUT. SEE PLANS. MAINTAIN SURROUNDING CEILINGS.

8. REMOVE EXISTING FINISH FLOORING MATERIAL IN ITS ENTIRETY AND PREPARE AREA

FOR NEW VINYL TILE.

9. REMOVE EXISTING FLOOR BASE.

10. REMOVE EXISTING WALL FINISHES TO STRUCTURE. PREPARE FOR NEW WALL TYPE.

11. PREPARE EXISTING CONCRETE FLOOR FOR NEW VINYL TILE.

12. PREPARE EXISTING MASONRY WALL FOR NEW PLYWOOD FINISH.

13. REMOVE EXISTING MILLWORK CABINETS AND SHELVING.

14. REMOVE EXISTING COUNTER TOP.

15. REMOVE EXISTING HANDRAIL AND CRASHRAIL.

16. REMOVE EXISTING PLUMBING FIXTURES AND CAP UTILITIES ON FLOOR BELOW. SEE

PLUMBING DEMO SHEETS.

17. REMOVE EXISTING RAILING IN ITS ENTIRETY.

18. NOT USED.

19. REMOVE EXISTING CEILING IN ITS ENTIRETY.

20. REMOVE EXISTING BASE-BOARD HEATER.

21. PATCH AND REPAIR EXTERIOR WALL WITH EXISTING DAMAGE TO AS-NEW CONDITION.

22. REMOVE PORTION OF EXISTING FLOOR IN ITS ENTIRETY AND PREPARE AREA FOR

NEW VINYL TILE.

23. REMOVE PORTION OF EXISTING WALL FOR FIRE EXTINGUISHER CABINET. SEE SHEET

AE540 FOR CABINET DETAIL.

24. REMOVE EXISTING DOOR, FRAME, AND HARDWARE FOR SALVAGE AND REUSE. SEE

DOOR SCHEDULE.

25. REMOVE EXISTING SIGNAGE FOR SALVAGE AND REUSE.

A

REFLECTED CEILING TYPE LEGEND

TYPE GRAPHIC DESCRIPTION

B

C

D

8x8 ACOUSTICAL CEILING TILE (AT-1)

2x2 ACOUSTICAL CEILING TILE (AT-2)

2x4 ACOUSTICAL CEILING TILE (AT-3)

GYPSUM BOARD CEILING. CEILING PAINT.

E NO CEILING / EXISTING

CEILING TO REMAIN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project :

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e

I I/

-7

.B

.A

R

.r v t

/2

/2

:4

:3

A

M

B200-AE407

ENLARGED FLOOR PLANS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JG LNS

SCALE: 1/4" = 1'-0"B200-AE407

9 TWELFTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE407

10 TWELFTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE407

11 TWELFTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE407

12 TWELFTH LEVEL - ENLARGED CEILING DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE407

5 ELEVENTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE407

6 ELEVENTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE407

7 ELEVENTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE407

8 ELEVENTH LEVEL - ENLARGED CEILING DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE407

1 TENTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE407

2 TENTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE407

3 TENTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE407

4 TENTH LEVEL - ENLARGED CEILING DEMO PLAN

0' 4' 8' 12'2'

Revisions: Date:

NOT F

OR

1372A

1372A

6' - 9 3/4" 1' - 10 1/4"

5' - 0" 3' - 7 1/2"

3'

10' - 9 1/4"

/2 x9 x8 xK

SD-1

RB-1

P-1

FEC

FLEX

1372B

IN-03.01

S3C.GW

TR

1372A

E 8' - 0"

3/ 4"

10' - 4 1/2"

3' - 11 1/2" 6' - 5"

/4 x9 x8 xK

B 8' - 1"

B 8' - 0"

FLEX

1372B

B 8' - 0"

B 8' - 0"

1'

3' - 8" 1' - 4"

3'

4'

2 2

6' - 6 1/4" 2' - 1 3/4" 5' - 0" 3' - 7 1/2"

6' - 5 1/2"

6'

1/ 2"

4" 2'

/4

4'

/2

4' - 5 3/4" 6' - 3 3/4" x9 x8 xK

B 8' - 0"

5' - 0" 3' - 7 1/2"

1'

6'

1/ 2"

4" 2'

/4

17' - 3 1/2"

4'

/2 x9 x8 xK

B 8' - 1"

TR

6' - 7 1/4" 1' - 8 1/4"

5' - 0" 3' - 8 1/2"

3'

/2

10' - 9"

/4

5'

1/ 4"

1472A x9 x8 xK

VDT-1

RB-1

P-1

FEC

FLEX

1472A

IN-03.01

S3C.G

S3C.GW

IN-03.01

TR

E 8' - 0"

1/ 2"

5'

1/ 2"

4'

1/ 2"

6' - 3" 10' - 3 1/2"

3' - 11 1/2" 6' - 4" x9 x8 xK

B 8' - 0"

FLEX

1472A

D 8' - 0"

B 8' - 0"

1'

3' - 8" 4' - 0"

3'

4'

2 2

6' - 3 3/4" 1' - 11 3/4" 5' - 0" 3' - 8 1/2"

6' - 3"

4' - 5" 6' - 4"

5" 3'

/4 x9 x8 xK

D 8' - 0"

5' - 0" 3' - 8 1/2"

1'

5'

1/ 2"

4'

1/ 2"

5" 3'

/4

6' - 3" 4' - 5" 6' - 4" x9 x8 xK

B 8' - 0"

VERTICAL SPACE

ELEVATOR

RCC1334C

VERTICAL SPACE

ELEVATOR

RCC1335C

VERTICAL SPACE

CHASE

RCC1323C

VERTICAL SPACE

CHASE

1373A

COMMON SPACE

CORRIDOR

RCC1310R

VERTICAL SPACE

ELEVATOR

RCC1334C

VERTICAL SPACE

ELEVATOR

RCC1335C

VERTICAL SPACE

CHASE

RCC1323C

VERTICAL SPACE

CHASE

1373A

VERTICAL SPACE

CHASE

RCC1318R

VERTICAL SPACE

ELEVATOR

RCC1334C

VERTICAL SPACE

ELEVATOR

RCC1335C

VERTICAL SPACE

CHASE

RCC1323C

VERTICAL SPACE

CHASE

1373A

VERTICAL SPACE

CHASE

RCC1318R

VERTICAL SPACE

ELEVATOR

RCC1334C

VERTICAL SPACE

ELEVATOR

RCC1335C

VERTICAL SPACE

CHASE

RCC1323C

VERTICAL SPACE

CHASE

1373A

VERTICAL SPACE

ELEVATOR

RCC1435C

VERTICAL SPACE

ELEVATOR

RCC1436C

VERTICAL SPACE

CHASE

RCC1425C

VERTICAL SPACE

CHASE

1473A

COMMON SPACE

CORRIDOR

RCC1427R

VERTICAL SPACE

ELEVATOR

RCC1435C

VERTICAL SPACE

ELEVATOR

RCC1436C

VERTICAL SPACE

CHASE

RCC1425C

VERTICAL SPACE

CHASE

1473A

VERTICAL SPACE

RCC1423R

VERTICAL SPACE

ELEVATOR

RCC1435C

VERTICAL SPACE

ELEVATOR

RCC1436C

VERTICAL SPACE

CHASE

RCC1425C

VERTICAL SPACE

CHASE

1473A

VERTICAL SPACE

RCC1423R

VERTICAL SPACE

ELEVATOR

RCC1435C

VERTICAL SPACE

ELEVATOR

RCC1436C

VERTICAL SPACE

CHASE

RCC1425C

VERTICAL SPACE

CHASE

1473A

A. REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL FOR COORDINATION ITEMS. COORDINATE AS REQUIRED INCLUDING

NECESSARY FRAMING, BLOCKING, ETC.

B. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

C. PATCH EXISTING PARTITIONS WHERE NEW PARTITIONS MEET.

D. PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER ABA REQUIREMENTS.

E. WHERE NO DIMENSION IS INDICATED, FINISH DOORS 6" FROM EDGE OF STUD

FRAMING AT CORNERS UNLESS OTHERWISE NOTED.

F. REFER TO EQUIPMENT SHEETS FOR EQUIPMENT SCHEDULE AND INFORMATION.

G. LEVEL AND INFILL FLOOR SLAB TO RECEIVE NEW FLOORING. REFER TO

SPECIFICATIONS AND FLOORING MANUFACTURE'S TOLERANCES FOR ADDITIONAL

INFORMATION.

H. PROVIDE METAL PLATE ON UNDERSIDE OF FLOOR SLAB WHERE CONCRETE INFILL IS

REQUIRED AND CHIP AWAY CONCRETE AT FLOOR LEVEL TO CREATE A SLOPED

OPENING/LIP TO PATCH PENETRATIONS AND PREVENT CONCRETE INFILL CORE FROM

FALLING THROUGH OPENING TO FLOOR BELOW.

I. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

J. ALL DIMENSIONS SHOWN ARE TO FACE OF WALL FRAMING/ MASONRY UNLESS NOTED

OTHERWISE. DIMENSIONS DESIGNATES AS "CLR" OR "CLEAR" INDICATE A CLEAR

DIMENSION FROM FACE OF FINISH TO FACE OF FINISH.

K. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

L. CONTRACTOR TO MAINTAIN/REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED

BY DEMOLITION/NEW CONSTRUCTION, TYPICAL THROUGHOUT.

M. PROVIDE CONTROL JOINT ON CONTINUOUS GYPSUM BOARD WALLS GREATER THAN

30' LONG.

N. PROVIDE CONTROL JOINTS AT CORNERS OF DOORS OR WINDOWS.

O. ALL NEW PARTITIONS ARE WALL TYPE S3C.G UNLESS NOTED OTHERWISE. REFER TO

WALL TYPE GENERAL NOTES FOR WALL BOARD MATERIAL.

P. NON-RATED WALL CONSTRUCTION THAT FORMS CHASE AREAS DOES NOT REQUIRE

GYPSUM BOARD INSTALLATION ON INTERIOR OF CHASE WALL.

Q. DIMENSIONS INDICATED AS 'VIF' MAY INCREASE OR DECREASE TO MATCH FIELD

CONDITIONS. ALL OTHER DIMENSIONS WITHIN THE DIMENSION STRING MUST BE

MAINTAINED.

R. PROVIDE BLOCKING AND STRAPPING FOR WALL MOUNTED CASEWORK, FURNITURE,

AND ACCESSORIES. COORDINATE WITH FLOOR PLANS, SCHEDULES, ELEVATIONS,

AND ENGINEERING DRAWINGS FOR FULL SCOPE OF WORK.

S. PATCH WALL AREAS ABOVE AND AROUND NEW DOORS TO MATCH EXISTING. SEE

FINISH SHEETS FOR ADDITIONAL INFORMATION.

T. PATCH WALL AREA AROUND NEW FEC LOCATION. SEE FINISH SHEETS.

U. ICRA LOCATIONS SHOWN ON AE100 SERIES SHEETS. SEE SHEET AE001 FOR ICRA

DEALS. FINAL LOCATION OF PARTITIONS TO BE DETERMINED BY THE CONTRACTOR.

ARCHITECTURAL GENERAL NOTES

ARCHITECTURAL PLAN NOTES

1. PARTITION INFILL WITH METAL STUD AT 16" O.C. AND 5/8" THK. GYPSUM BOARD- PRIME

AND PAINT ON EACH SIDE (STAGGER STUD TO ACCOMMODATE EXISTING WALL

THICKNESS WHERE REQUIRED).

2. NEW PARTITION. PRIME AND PAINT.

3. NEW DOOR, FRAME, AND HARDWARE.

4. INFILL EXISTING WINDOW. SEE SHEET AE540.

5. PAINT INTERIOR OF ROOM FROM CORNER TO CORNER, FLOOR TO CEILING. SEE

SHEET AF600.

6. INSTALL NEW FLOORING. SEE SHEET AF600.

7. INSTALL NEW VINYL BASE. SEE SHEET AF600.

8. ALIGN FINISH FACE OF WALL WITH OUTER FINISH FACE OF EXISTING WALL. PROVIDE

SEAMLESS TRANSITION AND NEW FINISH. ALIGN FINISH FACE OF WALL, BOTH SIDES

WHERE APPLICABLE.

9. INFILL PORTION OF EXISTING SLAB. REFERENCE STRUCTURAL.

10. INSTALL SHAFTWALL (UL415).

11. INSTALL WALL TYPE GW (PAINT). ALL WALL MOUNTED PLYWOOD TO HAVE FP-1 WITH

P-1 TOP COAT. SEE SHEET AF600 FOR ALL OTHER WALL SURFACES. SEE AE/540 FOR

DETAILS.

12. INSTALL 24" X 36" ACCESS PANEL 4'-0" A.F.F. (2 HR.).

13. MATCH EXISTING FINISHES; WALLS, FLOORS, BASE, CEILINGS, HAND AND

GUARDRAILS, ETC. SEE SHEET AF600. ANY SPACES LEFT BLANK ARE TO BE

DETERMINED IN THE FIELD. COORDINATE EXACT REQUIREMENTS WITH FACILITY.

14. CLOTHES WASHER, 27" X 42" X 26". VA SUPPLIED.

15. CLOTHES DRYER, 27" X 42" X 28". VA SUPPLIED.

16. INSTALL SALVAGED DOOR IN NEW LOCATION. SEE DOOR SCHEDULE.

17. INSTALL RELOCATED EXISTING SIGNAGE.

18. PATCH AND REPAIR FLOOR. SEE SHEET AF600 FOR FINISHES.

19. INSTALL 5/8" THK. GYPSUM BOARD TO DECK WITH SEALANT. PRIME, PAINT, AND

INSTALL NEW VINYL BASE TO MATCH EXISTING. SEE SHEET AF600.

20. LEAK PREVENTION BARRIER. COORDINATE WITH PLUMBING AND SEE SHEET AE540.

21. PARTITION INFILL WITH CONCRETE MASONRY UNITS. MATCH EXISTING- PRIME AND

PAINT ON EACH SIDE.

22. INSTALL WALL TYPE U415 (PAINT). SEE SHEET AF600 FINISHES. SEE AE/540 FOR

DETAILS.

A. THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL

CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE

ARCHITECTURAL AND ENGINEERING ELEMENTS ARE THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS

ANY DISCREPANCIES TO ARCHITECT AND COR.

B. SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR

REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL INFORMATION.

COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS, UNLESS OTHERWISE

NOTED.

C. ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED TO

ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS AND

BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE LIGHTING LAYOUT.

THE LIGHTING SHALL BE CENTERED IN ROOMS.

D. CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.) SHALL BE

CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.

E. ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE

COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.

F. CEILING TILE REMOVED IN ORDER TO COMPLETE ABOVE CEILING WORK SHALL BE

STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES SHALL BE

REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND NEW FINISH

APPLIED TO MATCH EXISTING.

G. REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON GYPSUM

BOARD PAINT FINISH.

H. CEILINGS AFFECTED BY CONSTRUCTION ARE TO BE REPAIRED AT THE TERMINATION

POINT AND RETURNED TO "AS NEW" CONDITION.

REFLECTED CEILING GENERAL NOTES

REFLECTED CEILING PLAN NOTES

1. NEW CEILING TO MATCH EXISTING IN ADJACENT SPACE.

A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND REPAIR

NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION SHALL BE PROVIDED.

CONTRACTOR SHALL REMOVE EXISTING IMPROVEMENTS WHETHER OR NOT

SPECIFICALLY INDICATED ON THE DRAWINGS TO FACILITATE THE COMPLETION OF ALL

REQUIRED WORK. CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES

AND ITEMS REQUIRED TO BE REMOVED.

B. REFER TO ARCHITECTURAL SYMBOLS SHEET FOR DEMOLITION SYSTEMS AND

DRAWING NOMENCLATURE.

C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN UNLESS

OTHERWISE NOTED.

D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE

PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO VERIFY

NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH CONDITIONS SHALL BE

RECTIFIED BEFORE WORK MAY PROCEED.

E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE ARCHITECTURAL FLOOR

PLAN AND ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.

F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED ARE

APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF WORK TO BE

REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE NEW CONSTRUCTION.

COORDINATE DEMOLITION WORK WITH DESIGN INTENT OF NEW CONSTRUCTION TO

PROVIDE ADEQUATE AREA FOR THIS WORK.

G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION

ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHERWISE NOTED, TO ACCOMMODATE

NEW CONSTRUCTION.

H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE NEW

FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH THAT THE

CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE SMOOTH AND

UNDETECTABLE.

I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE

REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES CAN BE

REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY

CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED AND PAINTED TO

SEAMLESSLY MATCH EXISTING CEILING COLOR FOLLOWING ABOVE CEILING

DEMOLITION ACTIVITY. THIS SHALL INCLUDE REPAIR TO THE CEILING GRID,

SUSPENSION SYSTEM AND ALL ASSOCIATED ASSEMBLIES AS WELL AS THE

REPLACEMENT OF DAMAGED CEILING PANELS, WITHIN AND BEYOND PROJECT LIMITS.

J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND VENDOR

DRAWINGS.

K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE SHALL BE

REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL BE FILLED/

LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING MANUFACTURES

RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.

L. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

M. AREAS ADJACENT TO DEMOLITION AND NEW CONSTRUCTION TO BE REPAIRED TO "AS

NEW" CONDITION.

DEMOLITION GENERAL NOTES

DEMOLITION PLAN NOTES

1. REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

2. REMOVE PORTION OF EXISTING PARTITION IN ITS ENTIRETY.

3. REMOVE EXISTING DOOR, FRAME, HARDWARE, AND PORTION OF EXISTING PARTITION

TO ACCOMMODATE NEW WORK.

4. REMOVE EXISTING WINDOW IN IT'S ENTIRETY, AND PREPARE FOR RELOCATION.

5. REMOVE EXISTING WINDOW AND FRAME.

6. RELOCATE EXISTING EQUIPMENT, COORDINATE WITH FACILITY FOR FINAL LOCATION.

7. PORTION OF EXISTING CEILING TO BE REMOVED / MODIFIED AS REQUIRED FOR NEW

CEILING LAYOUT. SEE PLANS. MAINTAIN SURROUNDING CEILINGS.

8. REMOVE EXISTING FINISH FLOORING MATERIAL IN ITS ENTIRETY AND PREPARE AREA

FOR NEW VINYL TILE.

9. REMOVE EXISTING FLOOR BASE.

10. REMOVE EXISTING WALL FINISHES TO STRUCTURE. PREPARE FOR NEW WALL TYPE.

11. PREPARE EXISTING CONCRETE FLOOR FOR NEW VINYL TILE.

12. PREPARE EXISTING MASONRY WALL FOR NEW PLYWOOD FINISH.

13. REMOVE EXISTING MILLWORK CABINETS AND SHELVING.

14. REMOVE EXISTING COUNTER TOP.

15. REMOVE EXISTING HANDRAIL AND CRASHRAIL.

16. REMOVE EXISTING PLUMBING FIXTURES AND CAP UTILITIES ON FLOOR BELOW. SEE

PLUMBING DEMO SHEETS.

17. REMOVE EXISTING RAILING IN ITS ENTIRETY.

18. NOT USED.

19. REMOVE EXISTING CEILING IN ITS ENTIRETY.

20. REMOVE EXISTING BASE-BOARD HEATER.

21. PATCH AND REPAIR EXTERIOR WALL WITH EXISTING DAMAGE TO AS-NEW CONDITION.

22. REMOVE PORTION OF EXISTING FLOOR IN ITS ENTIRETY AND PREPARE AREA FOR

NEW VINYL TILE.

23. REMOVE PORTION OF EXISTING WALL FOR FIRE EXTINGUISHER CABINET. SEE SHEET

AE540 FOR CABINET DETAIL.

24. REMOVE EXISTING DOOR, FRAME, AND HARDWARE FOR SALVAGE AND REUSE. SEE

DOOR SCHEDULE.

25. REMOVE EXISTING SIGNAGE FOR SALVAGE AND REUSE.

A

REFLECTED CEILING TYPE LEGEND

TYPE GRAPHIC DESCRIPTION

B

C

D

8x8 ACOUSTICAL CEILING TILE (AT-1)

2x2 ACOUSTICAL CEILING TILE (AT-2)

2x4 ACOUSTICAL CEILING TILE (AT-3)

GYPSUM BOARD CEILING. CEILING PAINT.

E NO CEILING / EXISTING

CEILING TO REMAIN

xP x2

6' - 8 1/2"

NURSE STATION

D010H xP x2

6' - 9 1/4" xP x2

C 8' - 5"

6' - 9 1/4"

NURSE STATION

D010H xP x2

6' - 9 1/4"

C 8' - 5"

COMMON SPACE

CORRIDOR

RCCB38R

COMMON SPACE

CORRIDOR

RCCB38R

COMMON SPACE

CORRIDOR

RCCB38R

COMMON SPACE

CORRIDOR

RCCB38R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project :

B

IM

/2

V

A H in e s E

H R

M I n fr a s tr u c tu re D e s ig n P h a s e

I I/

-7

.B

.A

R

.r v t

/2

/2

:4

:4

A

M

B200-AE408

ENLARGED FLOOR PLANS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

5000 5TH AVE, HINES, IL 60141

578-21-701

05/31/2023 JG LNS

SCALE: 1/4" = 1'-0"B200-AE408

1 THIRTEENTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE408

2 THIRTEENTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE408

3 THIRTEENTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE408

4 THIRTEENTH LEVEL - ENLARGED CEILING DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE408

5 FOURTEENTH LEVEL - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE408

6 FOURTEENTH LEVEL - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE408

7 FOURTEENTH LEVEL - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE408

8 FOURTEENTH LEVEL - ENLARGED CEILING DEMO PLAN

0' 4' 8' 12'2'

SCALE: 1/4" = 1'-0"B200-AE408

9 BASEMENT LEVEL - SECTION D - ENLARGED FLOOR PLAN

SCALE: 1/4" = 1'-0"B200-AE408

11 BASEMENT LEVEL - SECTION D - ENLARGED DEMO PLAN

SCALE: 1/4" = 1'-0"B200-AE408

10 BASEMENT LEVEL - SECTION D - ENLARGED CEILING PLAN

SCALE: 1/4" = 1'-0"B200-AE408

12 BASEMENT LEVEL - SECTION D - ENLARGED CEILING DEMO PLAN

Revisions: Date:

NOT F

OR

UPS

8'

8' - 0 3/4" 11' - 0"

6' - 7 1/4" 1' - 8 1/4"

5' - 0" 3' - 8 1/2"

3'

/2

10' - 9"

/4

5'

1/ 4"

1572A x10 x9 x8 xK

SD-1

RB-1

P-1

SD-1

RB-1

P-1

10 1/2" 3' - 11"

FEC

FLEX

1572A

U415

S3C.GW

S3C.G

IN-03.01

1571A

IN-03.01

TR

E 8' - 0"

1/ 2"

10' - 3 1/2"6' - 3"

5'

1/ 2"

3'

1/ 2"

5" 4'

/4

3' - 11 1/2" 6' - 4"

7' - 8 1/2" 10' - 11"

8' x10 x9 x8 xK

B 8' - 0"

FLEX

1572A

D 8' - 0"

1'

3' - 8"

3'

4'

2 2

6' - 3" 2' - 0 1/2" 5' - 0" 3' - 8 1/2"

4' - 5" 6' - 4"

3'

/4

5" x10 x9 x8 xK

D 8' - 0"

5' - 0" 3' - 8 1/2"

1'

6' - 3" 4' - 5" 6' - 4"

5'

1/ 2"

4'

1/ 2"

5" 3'

/4 x10 x9 x8 xK

B 8' - 0"

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

ELEVATOR

RCC1531C

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE CORRIDOR

RCC1519R

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE CORRIDOR

RCC1521R

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

ELEVATOR

RCC1531C

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE CORRIDOR

RCC1519R

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

CHASE

RCC1523R

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

ELEVATOR

RCC1531C

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE CORRIDOR

RCC1519R

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

CHASE

RCC1523R

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE

VERTICAL SPACE

ELEVATOR

RCC1531C

UNASSIGNED VACANT

SPACE

UNASSIGNED VACANT

SPACE CORRIDOR

RCC1519R

UNASSIGNED VACANT

SPACE

1530 #

A. REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL FOR COORDINATION ITEMS. COORDINATE AS REQUIRED INCLUDING

NECESSARY FRAMING, BLOCKING, ETC.

B. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

C. PATCH EXISTING PARTITIONS WHERE NEW PARTITIONS MEET.

D. PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER ABA REQUIREMENTS.

E. WHERE NO DIMENSION IS INDICATED, FINISH DOORS 6" FROM EDGE OF STUD

FRAMING AT CORNERS UNLESS OTHERWISE NOTED.

F. REFER TO EQUIPMENT SHEETS FOR EQUIPMENT SCHEDULE AND INFORMATION.

G. LEVEL AND INFILL FLOOR SLAB TO RECEIVE NEW FLOORING. REFER TO

SPECIFICATIONS AND FLOORING MANUFACTURE'S TOLERANCES FOR ADDITIONAL

INFORMATION.

H. PROVIDE METAL PLATE ON UNDERSIDE OF FLOOR SLAB WHERE CONCRETE INFILL IS

REQUIRED AND CHIP AWAY CONCRETE AT FLOOR LEVEL TO CREATE A SLOPED

OPENING/LIP TO PATCH PENETRATIONS AND PREVENT CONCRETE INFILL CORE FROM

FALLING THROUGH OPENING TO FLOOR BELOW.

I. ALL KEYNOTES MAY NOT BE APPLICABLE TO EACH SHEET - CONTRACTOR SHALL

VERIFY.

J. ALL DIMENSIONS SHOWN ARE TO FACE OF WALL FRAMING/ MASONRY UNLESS NOTED

OTHERWISE. DIMENSIONS DESIGNATES AS "CLR" OR "CLEAR" INDICATE A CLEAR

DIMENSION FROM FACE OF FINISH TO FACE OF FINISH.

K. VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT

DISCREPANCIES IMMEDIATELY TO ARCHITECT FOR CLARIFICATION.

L. CONTRACTOR TO MAINTAIN/REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED

BY DEMOLITION/NEW CONSTRUCTION, TYPICAL THROUGHOUT.

M. PROVIDE CONTROL JOINT ON CONTINUOUS GYPSUM BOARD WALLS GREATER THAN

30' LONG.

N. PROVIDE CONTROL JOINTS AT CORNERS OF DOORS OR WINDOWS.

O. ALL NEW PARTITIONS ARE WALL TYPE S3C.G UNLESS NOTED OTHERWISE. REFER TO

WALL TYPE GENERAL NOTES FOR WALL BOARD MATERIAL.

P. NON-RATED WALL CONSTRUCTION THAT FORMS CHASE AREAS DOES NOT REQUIRE

GYPSUM BOARD INSTALLATION ON INTERIOR OF CHASE WALL.

Q. DIMENSIONS INDICATED AS 'VIF' MAY INCREASE OR DECREASE TO MATCH FIELD

CONDITIONS. ALL OTHER DIMENSIONS WITHIN THE DIMENSION STRING MUST BE

MAINTAINED.

R. PROVIDE BLOCKING AND STRAPPING FOR WALL MOUNTED CASEWORK, FURNITURE,

AND ACCESSORIES. COORDINATE WITH FLOOR PLANS, SCHEDULES, ELEVATIONS,

AND ENGINEERING DRAWINGS FOR FULL SCOPE OF WORK.

S. PATCH WALL AREAS ABOVE AND AROUND NEW DOORS TO MATCH EXISTING. SEE

FINISH SHEETS FOR ADDITIONAL INFORMATION.

T. PATCH WALL AREA AROUND NEW FEC LOCATION. SEE FINISH SHEETS.

U. ICRA LOCATIONS SHOWN ON AE100 SERIES SHEETS. SEE SHEET AE001 FOR ICRA

DEALS. FINAL LOCATION OF PARTITIONS TO BE DETERMINED BY THE CONTRACTOR.

ARCHITECTURAL GENERAL NOTES

ARCHITECTURAL PLAN NOTES

1. PARTITION INFILL WITH METAL STUD AT 16" O.C. AND 5/8" THK. GYPSUM BOARD- PRIME

AND PAINT ON EACH SIDE (STAGGER STUD TO ACCOMMODATE EXISTING WALL

THICKNESS WHERE REQUIRED).

2. NEW PARTITION. PRIME AND PAINT.

3. NEW DOOR, FRAME, AND HARDWARE.

4. INFILL EXISTING WINDOW. SEE SHEET AE540.

5. PAINT INTERIOR OF ROOM FROM CORNER TO CORNER, FLOOR TO CEILING. SEE

SHEET AF600.

6. INSTALL NEW FLOORING. SEE SHEET AF600.

7. INSTALL NEW VINYL BASE. SEE SHEET AF600.

8. ALIGN FINISH FACE OF WALL WITH OUTER FINISH FACE OF EXISTING WALL. PROVIDE

SEAMLESS TRANSITION AND NEW FINISH. ALIGN FINISH FACE OF WALL, BOTH SIDES

WHERE APPLICABLE.

9. INFILL PORTION OF EXISTING SLAB. REFERENCE STRUCTURAL.

10. INSTALL SHAFTWALL (UL415).

11. INSTALL WALL TYPE GW (PAINT). ALL WALL MOUNTED PLYWOOD TO HAVE FP-1 WITH

P-1 TOP COAT. SEE SHEET AF600 FOR ALL OTHER WALL SURFACES. SEE AE/540 FOR

DETAILS.

12. INSTALL 24" X 36" ACCESS PANEL 4'-0" A.F.F. (2 HR.).

13. MATCH EXISTING FINISHES; WALLS, FLOORS, BASE, CEILINGS, HAND AND

GUARDRAILS, ETC. SEE SHEET AF600. ANY SPACES LEFT BLANK ARE TO BE

DETERMINED IN THE FIELD. COORDINATE EXACT REQUIREMENTS WITH FACILITY.

14. CLOTHES WASHER, 27" X 42" X 26". VA SUPPLIED.

15. CLOTHES DRYER, 27" X 42" X 28". VA SUPPLIED.

16. INSTALL SALVAGED DOOR IN NEW LOCATION. SEE DOOR SCHEDULE.

17. INSTALL RELOCATED EXISTING SIGNAGE.

18. PATCH AND REPAIR FLOOR. SEE SHEET AF600 FOR FINISHES.

19. INSTALL 5/8" THK. GYPSUM BOARD TO DECK WITH SEALANT. PRIME, PAINT, AND

INSTALL NEW VINYL BASE TO MATCH EXISTING. SEE SHEET AF600.

20. LEAK PREVENTION BARRIER. COORDINATE WITH PLUMBING AND SEE SHEET AE540.

21. PARTITION INFILL WITH CONCRETE MASONRY UNITS. MATCH EXISTING- PRIME AND

PAINT ON EACH SIDE.

22. INSTALL WALL TYPE U415 (PAINT). SEE SHEET AF600 FINISHES. SEE AE/540 FOR

DETAILS.

A. THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL

CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE

ARCHITECTURAL AND ENGINEERING ELEMENTS ARE THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS

ANY DISCREPANCIES TO ARCHITECT AND COR.

B. SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR

REFERENCE ONLY. REFER TO ENGINEERING PLANS…