05120-qrs.doc

DOC document 45 KB Posted

Attached to
CONSTRUCT HEAVY TIMBER LOG RECREATION SHELTER AT AMOLE CANYON Federal contract opportunity
Solicitation number
AG-83A7-10-S-0013
Issued by
Department of Agriculture Forest Service R3-Southwestern Region

About this file

Attachment - Specification

View the file

Other files for this federal contract opportunity

Other files attached to CONSTRUCT HEAVY TIMBER LOG RECREATION SHELTER AT AMOLE CANYON, newest first.
File Type Posted
SF 30.pdf PDF
Sf 30 modification 1.docx DOCX document
02336-imported_fill.docx DOCX document
09900.doc DOC document
01410-Testing_Quality.doc DOC document
03-SiteDetails 11X17(2) —
06100-carpentry.rtf RTF text file
01200_Mobilization.doc DOC document
07-Shelter2 11X17(2) —
03200-qrs.doc DOC document
02310_Grading.doc DOC document
02230_Clearing_ _Grubbing.doc DOC document
CONSTRUCTION rfq amole canyon.docx DOCX document
05-ShelterDetails 11X17(2) —
06-Shelter 11X17(2) —
Wage Det NM100001 6-4-10 NM1.docx DOCX document
02725_agg_base_surface.rtf RTF text file
02-SitePlan 11X17(2) —
07900_-_joint_sealers.docx DOCX document
07410-metal_roofing.rtf RTF text file
Response Pkg Amole Canyon.docx DOCX document
07130_-_underlaymentr.rtf RTF text file
01-TitleSheet 11X17(2) —
03300-qrs.doc DOC document
01330-submittal_procedure.rtf RTF text file
03100-qrs.doc DOC document
04-Sections Dtls 11X17(2) —
02317_Excavation_ _Backfill_Structures.doc DOC document
01101-Abbrevaitions.doc DOC document
02845-wheel_stops.docx DOCX document
06131-Log_Shelter.doc DOC document
03350_Concrete_Finishing.docx DOCX document
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 05120PRIVATE

STRUCTURAL STEEL

PART 1 -

GENERAL

1.01

SECTION INCLUDES

A.

Structural steel framing members, and support members.

B.

Base plates.

C.

Grouting under base plates.

1.02

REFERENCES

A. AISC ‑ Code of Standard Practice ‑ Manual of Steel Construction – Allowable

Stress Design (ASD).

ASTM A36/A36M ‑ Structural Steel.

ASTM A53 ‑ Hot‑Dipped, Zinc‑coated Welded and Seamless Steel Pipe.

D.

ASTM A123 ‑ Zinc (Hot Dipped Galvanized) Coatings on Iron and Steel Products.

E.

ASTM A307 ‑ Carbon Steel Externally Threaded Standard Fasteners.

F.

ASTM A325 ‑ High Strength Bolts for Structural Steel Joints.

G.

ASTM A500 ‑ Cold‑Formed Welded and Seamless Carbon Steel Structural Tubing in Round and Shapes.

H.

ASTM A563 ‑ Carbon and Alloy Steel Nuts.

I.

AWS A2.4 ‑ Symbols for Welding, Brazing, and Nondestructive Examination.

J.

AWS D1.1 ‑ Structural Welding Code.

K.

SSPC (Steel Structures Painting Council) ‑ Painting Manual.

1.03

SUBMITTALS FOR REVIEW

Section 01300 – Submittals

1.

Connections not detailed on the drawings.

2.

Indicate welded connections with AWS A2.0 welding symbols. Indicate net weld lengths.

1.04

QUALITY ASSURANCE

A. Fabricate structural steel members in accordance with AISC Code of Standard

Practice.

Perform Work in accordance with AISC Section 10.

PART 2 -seq level1 \h \r0 seq level2 \h \r0 seq level3 \h \r0

PRODUCTS

2.01

MATERIALS

Structural Steel Members: ASTM A36/A36M.

Structural Tubing: ASTM A500, Grade B.

Pipe: ASTM A53, Grade B.

Bolts, Nuts, and Washers: ASTM A325 bolts, ASTM A563 nuts, galvanized to ASTM A123 for galvanized structural members.

Anchor Bolts: ASTM A307.

F.

Welding Materials: AWS D1.1; type required for materials being welded.

G.

Grout: Non‑shrink type, pre‑mixed compound consisting of non‑metallic aggregate, cement, water reducing and plasticizing additives, capable of developing a minimum compressive strength of 7,000 psi at 28 days.

H.

Shop and Touch‑Up Primer: SSPC 15, Type 1, red oxide.

2.02

FABRICATION

Continuously seal joined members by continuous welds. Grind exposed welds smooth.

Fabricate connections for bolt, nut, and washer connectors.

Develop required camber for members.

2.03

FINISH

Prepare structural component surfaces in accordance with SSPC SP 3.

Shop prime structural steel members. Do not prime surfaces that will be field welded, in contact with concrete, and high strength bolts.

PART 3 -seq level1 \h \r0 seq level2 \h \r0

EXECUTION

3.01

ERECTION

Allow for erection loads, and for sufficient temporary bracing to maintain structure safe, plumb, and in true alignment until completion of erection and installation of permanent bracing.

Field weld components indicated on Drawings.

Field connect members with threaded fasteners; torque to required resistance.

Do not field cut or alter structural members without approval of Architect/Engineer.

After erection, prime welds, abrasions, and surfaces not shop primed, except surfaces to be in contact with concrete.

Grout under base plates in accordance with Section 3300. Trowel grouted surface smooth, splay neatly to 45 degrees.

3.03

ERECTION TOLERANCES

Maximum Variation From Plumb: 1/4 inch per story, non‑cumulative.

Maximum Offset From True Alignment: 1/4 inch.

PART 4 - MEASUREMENT AND PAYMENT

4.01

MEASUREMENT

A.

The work specified herein will not be measured for payment.

4.02

PAYMENT

This work is incidental to other items in this contract and direct separate item payment will not be made.

END OF SECTION

05120-3

File details come from the government source that posted it. Updated .