This is a technical specification section (28 31 12) detailing requirements for the Fire Alarm System to be installed at the Pueblo Pintado Health Center. The specification requires furnishing and installing a complete addressable 70-volt DC Fire Alarm System including control panels, power supplies, alarm initiating devices, alarm signaling devices, and all necessary components for a fully operational system.
Key requirements include: UL 9th Edition listed control panel with prerecorded voice annunciation capabilities; Class A wiring configuration; battery backup for 24 hours of normal operation plus 5 minutes of alarm operation; photoelectric smoke detectors; heat detectors; duct smoke detectors; manual pull stations; visual and audible alarm devices meeting ADA requirements; remote annunciators with 80-character LCD displays; area indication plaques; and integration with building systems including door holders, smoke dampers, HVAC, sprinkler monitoring, and lighting controls. The system must be installed by NICET Level III certified personnel and comes with a 5-year warranty. The contractor must provide factory-trained service technicians within 50 miles of the site and 24-hour emergency response within 4 hours.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PUEBLO PINTADO HEALTH CENTER FINAL CONSTR. DOCS.
(211015)
HFG Architecture © 2022
FA SYSTEM
28 31 12 - 1
2022 by FEI
SECTION 28 31 12
FIRE ALARM SYSTEM
PART 1 GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 WORK INCLUDED
A. The work covered by this section of the specification includes the furnishing of all labor, equipment, materials and performance of all operations in connection with the installation of an electrically supervised closed loop and addressable 70-volt DC Fire Alarm System as shown on the drawings and as herein specified. The system shall include but not be limited to all control panels, power supplies, alarm initiating devices, alarm signaling devices, conduit, wire, fittings and all auxiliary accessories required to provide a complete and operating system which shall be left in first class operating condition. The system shall be approved by the various regulatory bodies.
B. The requirements of the conditions of the Contract, Supplementary Conditions and General
Requirements, apply to the work specified in this section.
C. The items of equipment furnished under this specification shall be listed as a product of a single
Fire Alarm manufacturer under the appropriate category by Underwriters Laboratories and shall meet the applicable requirements of NFPA Standards, Life Safety Code 101, National Electric
Code Article 760 as well as those standards set by the authorities having jurisdiction. The system controls shall be listed under UL Standard 864 (Control Units). In addition, the system controls shall be UL Listed for Power Limited applications per NEC 760. All circuits must be marked in accordance with NEC Article 760. The Fire Alarm and detection equipment shall not be modified or installed to alter or void the Underwriters Laboratories label or listing. Fire alarm control panel shall be UL 9th Edition listed.
D. All control equipment must have transient protection to comply with UL864 requirements. Where
Fire Alarm circuits leave the building, additional transient protection must be provided for each circuit. Devices must be UL Listed under Standard #497B (Isolated Loop Circuit Protectors).
E. Provide power connections, detection devices, etc., where auxiliary equipment is required, such as remote power supplies, voice annunciation panels, and other equipment necessary for a complete and operating system. Where the Fire Alarm Control Panel is shown connected to an emergency power system, all auxiliary equipment shall also be connected to the emergency power system.
1.03 QUALITY ASSURANCE
A. Submit shop drawings and product data to the Architect-Engineer in accordance with the General
Conditions and General Requirements. Shop drawings shall be prepared by a NICET certified designer, Level III minimum or Fire Protection Engineer. Shop drawings shall include the following:
1. Complete descriptive product data including UL Listing for all system components and detailed manufacturer's drawings on the: Fire Alarm Control Panel, Remote Annunciators, Manual Fire Alarm Station, Automatic Fire Detection Devices, Alarm Signaling Devices, Wiring and Cable.
2. Terminal connection diagram of the Fire Alarm Control Panel showing all wiring connection points including typical field wiring circuit diagrams.
3. Layout drawings showing the exact location of all Fire Alarm equipment and the interconnection between the devices.
28 31 12 - 2
4. A complete step-by-step description of the operation of the system.
5. A complete sequence of operations matrix, with input/output shown.
6. Certification by the manufacturer that the battery installation meets the operating requirements specified herein.
7. Install Qualifications
a. Personnel must be trained and certified by manufacturer for installation of units required for this Project.
b. Installation must be by personnel certified by NICET.
c. Licensed or certified by authorities having jurisdiction, B. All Submittal data on this system must be approved by the State Fire Marshall and/or the authority having jurisdiction before it is submitted to the Architect for approval.
C. The Contractor shall furnish to the Owner, upon final acceptance of the system, four (4) sets of written Operating and Maintenance Instructions which shall include copies of all designated approved shop drawings, wiring diagrams, layout drawings and installation and operating instructions. The manual shall contain procedures to follow for drills, troubleshooting, resetting the system and other functions normal to, and inherent in, the Fire Alarm and detection system.
1.04 SYSTEM OPERATION
A. Refer to Fire Alarm System Matrix on construction plans for additional detail of operation of system.
B. Fire-alarm signal initiation shall be by one or more of the following devices and systems:
1. Manual stations
2. Smoke detectors
3. Duct mounted smoke detector
4. Heat detector
5. Automatic sprinkler system tamper and waterflow switch
6. Other automatic alarm initiating device
C. Fire-alarm signal shall initiate the following actions:
1. An alarm shall be displayed on the 80 character LCD display. The top line of 40 characters shall be the custom point label and the second line shall be the device type identifier and point status indicator. The custom point label shall identify location of the device. The nomenclature used to describe the device location shall be coordinated with the Owner and shall correspond to zone indication plaque nomenclature. The system alarm red LED shall flash on the Control Panel and remote annunciator until the alarm has been acknowledged at the Control Panel. Once acknowledged, this same LED shall latch on. A subsequent alarm received from another zone shall flash the system alarm LED on the Control Panel. The LCD display shall show the new alarm information.
2. All audible alarm indicating devices shall sound a prerecorded voice message and all visual devices shall activate and have the flash rate synchronized until silenced at the Fire Alarm
Control Panel or remote annunciator. The system will include provisions for silencing the signaling devices, allowing for re-initiation following a subsequent alarm, but only after the signaling devices have operated initially for not less than three (3) minutes. (The inhibit feature shall be adjustable from 0-5 minutes). Systems that do not have resound capabilities will not be acceptable.
3. Continuously operate alarm notification appliances, including voice evacuation notices.
4. Transmit an alarm signal to the remote alarm receiving station.
5. Unlock electric door locks in designated egress paths.
6. Release fire and smoke doors held open by magnetic door holders.
28 31 12 - 3
7. Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode.
8. Close smoke dampers in air ducts of designated air-conditioning duct systems.
9. Recall elevators to primary or alternate recall floors.
a. If the alarm device is on any floor other than the main level of egress, the elevator cabs shall be recalled to the main level of egress.
b. If the alarm device is on the main egress level, the elevator cabs shall be recalled to the predetermined alternate recall level as determined by the local authority having jurisdiction.
10. Activate elevator power shunt trip.
11. Activate emergency lighting control.
12. Activate emergency shutoffs for gas and fuel supplies.
13. Record events in the system memory.
14. Indicate device in alarm on the graphic annunciator.
15. Light an alarm indicator lamp on smoke detectors which have initiated an alarm.
16. The activation of any alarm initiating device shall, in addition to the operations listed above, cause the elevator cabs to be recalled according to the following sequence:
D. Supervisory signal initiation shall be by one or more of the following devices and actions:
1. Valve supervisory switch.
a. Activation of any standpipe or sprinkler valve tamper switch shall activate a distinctive system supervisory audible signal and illuminate a distinctive "Sprinkler Valve
Supervisory Tamper" LED at the Control Panel and the Remote Annunciators.
Differentiation between valve tamper activation opens and/or grounds on fire alarm initiation circuit wiring shall be provided. Activating the Alarm Silence Switch will silence the supervisory audible signal while maintaining the "Sprinkler Valve Supervisory
Tamper" LED on indicating that the tamper contact is still in the off-normal state.
Restoring the valve to the normal position shall cause the "Sprinkler Supervisory
Tamper" LED to extinguish thus indicating restoration to normal position.
2. Elevator shunt-trip supervision.
3. Independent fire-detection and -suppression systems.
4. User disabling of zones or individual devices.
5. Loss of communication with any panel on the network
E. System trouble signal initiation shall be by one or more of the following devices and actions:
1. Open circuits, shorts, and grounds in designated circuits.
2. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices.
3. Loss of communication with any addressable sensor, input module, relay, control module, remote annunciator, printer interface, or Ethernet module.
4. Loss of primary power at fire-alarm control unit.
5. Ground or a single break in internal circuits of fire-alarm control unit.
6. Abnormal ac voltage at fire-alarm control unit.
7. Break in standby battery circuitry.
8. Failure of battery charging.
9. Abnormal position of any switch at fire-alarm control unit or annunciator.
10. Voice signal amplifier failure.
F. System Supervisory Signal Actions:
1. Initiate notification appliances.
2. Identify specific device initiating the event at fire-alarm control unit, connected network control panels, off-premises network control panels and remote annunciators.
28 31 12 - 4
3. After a time delay of 200 seconds, transmit a trouble or supervisory signal to the remote alarm receiving station.
4. Transmit system status to building management system.
5. Display system status on graphic annunciator.
G. The System Control Panel must be capable of communicating with the types of addressable devices specified below. The location of addressable devices will be selected along with conventional devices to optimize the system layout in order to provide the level of protection, zone identification and control as shown on the drawings.
H. The system shall have provisions for disabling and enabling all addressable devices, monitoring, signaling and control circuits individually for maintenance and testing purposes.
I. Alarm and trouble conditions shall be immediately displayed on the Control Panel from
Alphanumeric LCD display. If more than one (1) alarm or trouble is in the system, the operator may scroll to display new alarms.
J. A manual evacuation (drill) switch shall be provided to operate the systems alarm indicating devices. Other control circuits shall not be activated. However, an alarm shall be processed as described previously.
K. The Control Panel shall include a system testing capability to help ensure that zoning and supervision have been maintained throughout the system. The actuation of the enable walk test program at the Control Panel shall activate the "Walk-Test" mode of the system which shall cause the following to occur:
1. The city connection circuit shall be disconnected.
2. Control relay functions shall be bypassed.
3. The Control Panel shall show a trouble condition.
4. The alarm activation of any initiation device shall cause the audible signals to code a number of pulses to match the zone number.
5. The panel shall automatically reset itself after code is complete.
6. Any momentary opening of alarm initiating or alarm indicating circuit wiring shall cause the audible signals to sound continuously for four (4) seconds to indicate the trouble condition.
L. The system shall be capable of logging and storing 300 events in an alarm log and 300 events in a trouble log. These events shall be stored in a battery protected random access memory. Each recorded event shall include the time and date of that event's occurrence. The system shall have the capability of recalling alarms, trouble conditions, acknowledgements, silencing and reset activities in chronological order for the purpose of recreating an event history.
M. Smoke detectors shall have a smoke density measuring device having no self contained alarm set-point. The alarm decision for each sensor shall be determined by the control panel. The control panel shall determine the condition of each sensor by comparing the sensor value to the stored values. The control panel shall maintain a moving average of the sensors smoke chamber value. Systems that do not automatically maintain a constant smoke obscuration sensitivity for each detector by compensating for environmental factors are deemed not acceptable.
N. An operator at the control panel, having a proper access level, shall have the capability to manually access the following information for each sensor:
1. Primary status.
2. Device type.
3. Present average value.
4. Present sensitivity selected *
5. Peak detection values *
6. Sensor range (normal, dirty, etc.
28 31 12 - 5
O. An operator at the control panel, having a proper access level, shall have the capability to manually control the following for each sensor:
1. Clear peak detection values.
2. Enable or disable the point.
3. Clear verification tally.
4. Control a sensor's relay driver output.
1.05 SUPERVISION
A. When a trouble of any nature is detected, an audible trouble signal shall sound at the Fire Alarm
Control Panel until the trouble is corrected or until it is manually silenced. In addition a "System
Trouble" LED shall be illuminated and shall remain "On" until the trouble condition is corrected. A subsequent trouble condition received after manually silencing shall cause the audible trouble signal to "resound". Each independently supervised circuit shall include a discreet LCD readout to indicate disarrangement condition in that circuit.
B. Should a trouble condition be present within the system and the audible trouble signal silenced, the trouble signal shall resound at preprogrammed time intervals to act as reminder that the Fire
Alarm System is not 100% operational. Both the time interval and the trouble reminder signal shall be programmable to suit the Owner's application.
C. The system shall contain independently supervised initiating circuits so that a fault in any one (1) zone shall not affect any other zone. The alarm activation of any initiation circuit shall not prevent the subsequent alarm operation of any other initiation circuit.
D. The alarm indicating device circuits shall be independently supervised and fused so that disarrangement of any circuit shall not affect the operation of the other circuits.
E. The system shall annunciate, at the Control Panel, the following trouble conditions for each addressable point within the system: open, short and device failed/missing. Should a device fail it will not hinder the operation of other system devices.
F. All auxiliary manual controls shall be supervised so that all switches must be returned to the normal automatic position to clear system trouble.
G. The power supply for the system shall be supervised so that loss of the incoming power, a low battery voltage condition or a battery disconnection will cause a trouble condition in the system. A green "power on" LED shall be displayed continuously while incoming power is present.
H. Wiring to the remote annunciator(s) shall be supervised for open and ground conditions.
I. The system shall automatically indicate when an individual sensor needs cleaning. When a sensor's average value reaches a predetermined value, a "Dirty Sensor" trouble condition shall be audibly and visually indicated at the control panel for the individual sensor. Additionally, the LED on the sensor base shall glow steady giving a visible indication at the sensor location. If a "Dirty
Sensor" is left unattended and its average value increases to a second predetermined value, an
"Excessively Dirty Sensor" trouble condition shall be indicated at the control panel for the individual sensor. It shall be possible, at the control panel, to determine if any sensors are "Almost
Dirty" to aid in maintenance of the system.
J. The control panel shall automatically perform a daily self-test on each sensor. Checking the electronics in the sensor's base ensures the accuracy of the values being transmitted to the control panel. A sensor which fails the self-test will cause a "Self Test Abnormal" trouble condition at the control panel. A sensor self-test which must be manually initiated by the operator shall not be acceptable.
28 31 12 - 6
1.06 POWER REQUIREMENTS
A. The Control panel shall receive 120 VAC power (as noted on the plans) via a dedicated circuit. An approved earth ground connection to the Control Panel shall also be provided.
B. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal 120 VAC power in a normal supervisory mode for a period of 24 hours with five (5) minutes of alarm operation at the end of this period. The system shall automatically transfer to the standby batteries upon power failure. All battery charging and recharging operations shall be automatic.
C. All circuits requiring system operating power shall be 70 VDC and shall be individually fused at the
Control Panel.
1.07 WARRANTY
A. Manufacturer agrees to repair or replace fire-alarm system equipment and components that fail in materials or workmanship within specified warranty period of five years from data of Substation
Completion.
PART 2 PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. The equipment furnished under this specification shall be of one manufacturer’s noncoded, UL-certified addressable system, with multiplexed signal transmission and voice/strobe evacuation. All components provided shall be listed for use with the selected system. Electrical components, devices, and accessories shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Similar equipment as manufactured by Johnson Controls/Simplex, Honeywell/Notifier, Edwards or
Siemens subject to compliance with these specifications may be considered as equal.
2.02 FIRE ALARM CONTROL PANEL
A. Where shown on the plans, provide and install Fire Alarm Control Panel. Panel shall be field-programmable, microprocessor-based modular, power limited design with electronic modules complying with UL 864. An 80 character LCD display shall indicate alarms, supervisory service conditions and any troubles. Keyboards or keypads shall not be required to operate the system during fire alarm conditions. The Fire Alarm Control Panel shall be in an enclosed metal surface-mounted cabinet specifically designed for public areas. It shall have a locked, hinged front door with two (2) master keys that also fit all other fire alarm apparatus utilizing keys for access.
B. The Control Panel shall be provided with alarm initiating circuits as required. Trouble and alarm conditions shall be indicated on the LCD display.
C. All fire alarm components and wiring systems shall be Class A. All circuits shall be installed such that the outgoing and returning conductors are routed in separate raceways in accordance with
NFPA 72.
D. The Control Panel shall provide communication with individually addressable initiating and control devices as indicated on the drawings. All of these devices will be individually annunciated at the
Control Panel. There shall be no limit to the number of detectors, stations or Zone Adapter
Modules, which may be activated or "in alarm" simultaneously.
E. Alarm signaling circuits shall be provided as required. Each circuit shall be separately fused and indicated on the LCD display. The number of circuits required shall be determined by a method which ensures that the end device received no less than 63 VDC operating power and in no case shall the circuit be initially loaded in excess of 80% of it's rated capacity.
F. The Fire Alarm Control Panel shall have prerecorded voice annunciation capabilities including digitally recorded voice messages and speaker annunciation. Prerecorded messages shall be
28 31 12 - 7 coordinate with Owner and AHJ. A built-in microphone shall be provided to allow pang through speaker circuits and shall have priority over the alarm message. System amplifiers shall have a minimum of 25% spare capacity.
G. Provide a remote microphone and audio controls cabinet in Entry Vestibule 1E-042 adjacent to the remote annunciator. It shall be permitted to combine the microphone, controls, and remote annunciator into a single cabinet.
H. Control panels shall have digital alarm communicating transmitter for central station monitoring of alarms, troubles and supervisory conditions with specific point identification. Also provide contact closure digital communicating transmitter for off-site monitoring. Provide wiring to closest telephone termination board for off-site annunciation. The selection of a central monitoring agency, its fees and the fees for the leased lines are the responsibility of the Owner.
I. The Fire Alarm Control Panel shall allow for loading or editing special instructions and operating sequences as required. The system shall be capable of on site programming to accommodate and facilitate expansion, building parameter changes or changes as required by local codes. All software operations shall be stored in a non-volatile programmable memory within the Fire Alarm
Control Panel. Loss of primary and secondary power shall not erase the instructions stored in memory. Systems that require factory reprogramming to add or delete addressable devices are unacceptable.
J. The Fire Alarm Control Panel shall include a multi-level password protection capability which can be applied to various system functions such as; alarm silence, alarm reset, manual control, disable/enable and walk test. Access to a level will only allow the operator to perform all actions within that level plus all actions of lower levels, not higher levels. The access level shall be in effect until the operator manually logs out or the keypad has been inactive for 10 minutes at which time the access level returns to its lowest level.
K. The "Control" module for the Fire Alarm System shall include annunciator supervision circuitry, earth ground detection, low or no battery voltage trouble monitoring and reporting and adjustable alarm silence inhibit capability as well as the reset, alarm silence, trouble silence switches and audible and visual trouble indicators. The Control Panel shall electrically supervise facilities for automatic Fire Department notification. Relays shall be provided to accomplish the various control functions as specified in the system operation section and shall be capable of being bypassed for testing purpose.
L. The communication format to the addressable devices must be a completely digital poll-response protocol to allow t-tapping of the circuit wiring. Each addressable device must be uniquely identified by an address code entered on each device at time of installation. The system must verify that proper type device is in place and matches the desired software configuration.
M. Standby power for the system shall be provided by low maintenance sealed lead acid batteries specifically designed for Fire Alarm use and shall be kept fully charged by an automatic battery charger. Automotive type construction wet cell storage batteries or other non-fire alarm type batteries will NOT be acceptable.
2.03 ALARM INITIATING DEVICES
A. Manual stations shall be dual action, addressable stations. Manual stations shall be constructed of high impact, red lexan with raised white lettering and a smooth high gloss finish. Stations shall be keyed alike with the Fire Alarm Control Panel. When the station is operated, the handle shall lock in a protruding manner to facilitate quick visual identification of the activated station. Addressable stations shall contain electronics that communicate the device status to the Control Panel over two
(2) wires which also provide power to the station. The address location of the station will be field programmed at the station via a dip switch.
28 31 12 - 8
B. Furnish and install where indicated on the plans, Photoelectric smoke sensor with addressable sensor base. The sensors shall communicate the actual smoke chamber values to the system control panel. The sensors shall be listed to UL Standard 268 for both ceiling and wall mount applications and shall be documented compatible with the control equipment to which it is connected. Each sensor base shall contain an LED that will flash each time it is scanned by the control panel (once every four (4) seconds). When the control panel determines that a sensor is in an alarm or a trouble condition, the control panel shall command the LED on that sensor's base to turn on steady indicating the abnormal condition. Sensors which do not provide a visible indication of an abnormal condition at the sensor location shall not be acceptable. Sensor bases, as shown on the plans, shall be provided with a relay driver output that is to be controlled either automatically or manually from the control panel. Each sensor shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location. Each sensor shall be scanned by the control panel for its type identification to prevent inadvertent substitution of another sensor type. The control panel shall operate with the installed device but shall initiate a "wrong device" trouble condition until the proper type is installed or the programmed sensor type is changed. The sensor's electronics shall be immune from false alarms caused by EMI or RFI.
C. Automatic heat detectors shall be combination rate-of-rise and fixed-temperature type addressable detectors. In high hazard areas with high temperature, furnish fixed temperature detector with the appropriate Zone Adapter Module. Detectors shall be of the replaceable element type and shall visually indicate an alarm condition when operated.
D. Duct smoke detectors shall include Photoelectric smoke sensor operating on the light scattering photodiode principle. No radioactive materials shall be used. Detector construction shall be of the split type that is, mounting base with twist-lock detecting sensor. Contacts between the base and sensor shall be of the bifurcated type using spring-type, self-wiping contacts. The sensor base shall contain an LED that will flash each time it is scanned by the control panel (once every four (4) seconds). When the control panel determines that a sensor is in an alarm or a trouble condition, the control panel shall command the LED on that sensor's base to turn on steady indicating the abnormal condition. Removal of the sensor shall cause a trouble signal at the Control Panel.
Duct housing couplings shall be slotted to insure proper alignment of the sampling and exhaust tubes. Detector shall have an alarm LED visible through the front cover. Installation must comply with NFPA-90A.
1. Remote alarm LED indicators shall be provided for each Duct Smoke Detector. Indicators shall be mounted in an easily accessible location such as near the doors of Mechanical
Rooms or flush-mounted in the ceiling located directly below the unit when the detector is above the ceiling. Each indicator shall identify the unit it serves and also indicate supply or return.
E. Resident Smoke Detectors: Smoke detectors in Sleeping/Staff Bedrooms shall operate on 120
VAC and be provided with 9 VDC battery backup to operate the detector in the case of loss of main operating power. Smoke detectors shall have the following features and functions:
1. Supervise backup battery and provide indication of low battery power or missing battery.
2. Provide a solid state piezo alarm rated at 90dB at 10-feet.
3. Provide a visual LED monitor that pulses slow in normal operation and fast in alarm condition.
4. Detectors shall have Form A and Form C contacts.
5. Detectors shall have tandem interconnect capability.
6. Detectors shall be self-restoring when conditions causing the alarm clear.
28 31 12 - 9
2.04 ALARM SIGNALING DEVICES
A. Alarm speakers and combination alarm speakers/visual devices shall produce a prerecorded voice message. Devices shall have white color finish with red lettering. Refer to drawings for ceiling or wall mounted locations.
1. Alarm annunciation dB levels shall meet the Americans with Disabilities Act (ADA), UL, NFPA and local codes.
2. Contractor shall coordinate exact prerecorded voice messages with Owner and AHJ.
3. Voice alarm intelligibility testing shall be completed in accordance with IEC 60849.
B. Visible alarm indicating devices shall be entirely solid state and comprised of Xenon flashtube.
Visual alarm units shall meet the photometric requirements of the Americans with Disabilities
(ADA), UL, NFPA and local codes. The unit shall be complete with a tamper-resistant Lexan lens with a white finish and red lettering. Refer to drawings for ceiling or wall mounted locations.
1. The drawings indicate areas requiring visual devices. The intensity level of each device, exact quantity and location per area shall be determined by manufacturer and devices provided accordingly.
2.05 REMOTE ANNUNCIATOR
A. Provide a flush-mounted remote annunciator at each location shown on the drawings.
B. Annunciator(s) shall have 80 character LCD display (two (2) lines, each line 40 characters) with control switches for System Acknowledgements, Alarm Silence and System Reset. There shall be
Lamp/LCD test and four (4) programmable control switches with windows for "slip-in" labels.
Mounting screws shall be tamperproof.
C. A key switch activated "ENABLE" feature shall be provided. All switches on the annunciator shall be inoperable without the "ENABLE" switch activated. The key shall be removable in the disabled position only.
D. The display shall provide clear English language information to include point status, type of alarm
(smoke detector, manual station, etc.), number of alarms, supervisory conditions, troubles in the system and a custom location label.
2.06 AREA INDICATION PLAQUE
A. Provide an area indication plaque wall mounted adjacent to each remote annunciator and also at the Fire Alarm Control Panel. The display shall be a scaled representation of the facility with each area/room in the facility shown on the plaque and labeled accordingly. Coordinate size and nomenclature of areas with Owner and program control panel and annunciator displays to correspond with nomenclature of plaque. The plaque shall be approximately 18-inch square
(exact quantity and size of plaque(s) shall be determined by size of Project) with stainless steel or anodized aluminum frame and plexiglass cover over display. The plaque itself shall be reverse-engraved silk-screened plastic sheet of 3/16-inch minimum thickness or CADD generated on
Mylar.
2.07 MISCELLANEOUS DEVICES
A. Door holders shall be provided as work of Section 08 71 00 “Door Hardware” coordinate with door hardware supplier. Electrical connections to door holders shall be provided as work of this section.
B. Provide connection to smoke and combination fire/smoke dampers.
C. Fan shutdown relays shall be provided as required and shall be compatible with the unit being controlled.
D. Provide connection to sprinkler system flow and tamper switches.
E. Zone Adapter Modules shall be used for monitoring of waterflow, valve tamper, non-addressable detectors and devices and for control of evacuation indicating appliances and AHU Systems.
28 31 12 - 10
ZAMs will be capable of mounting in a standard electric outlet box. ZAMs will include cover plates to allow surface- or flush-mounting. ZAMs will receive their 70VDC power from a separate two (2) wire pair running from an appropriate power supply. The ZAM shall be capable of being programmed for its "address" location on the addressable device initiating circuit. The ZAM shall be compatible with addressable manual stations and addressable detectors, etc. on the same addressable initiating circuit.
F. Provide connection to kitchen hood extinguishing system.
G. Provide connection to dry pipe sprinkler monitoring system.
H. Provide connection to lighting control system and program system so emergency lighting is automatically turned on when fire alarm system is activated.
I. Provide relays and/or auxiliary control modules for connection to paging system and program system to override paging system to be muted when fire alarm system is activated. The mute condition shall be self-restoring after alarm reset.
2.08 WIRE
A. All wire and wiring shall be in strict compliance with all of the provisions of the National Electrical
Code, Article 760, the manufacturer's recommendations and requirements.
2.09 NETWORK
A. Provide network communications for fire-alarm system according to fire-alarm manufacturer’s written requirements.
B. Provide network communications pathway per manufacturer’s written requirements and requirements in NFPA 72 and NFPA 70.
C. Provide integration gateway for connection to building automation system. Coordinate with BAS.
PART 3 EXECUTION
3.01 INSTALLATION
A. The entire system shall be installed in a workmanlike manner in accordance with approved manufacturer's wiring diagrams and per NFPA 72, NFPA 101 and requirements of AHJ. The
Contractor shall furnish all conduit, wiring, outlet boxes, junction boxes, cabinets and similar devices necessary for a complete installation. All wiring shall be of the type recommended by the manufacturer and approved by the local authority having jurisdiction and shall be installed in conduit throughout. All junction boxes shall be sprayed red and labeled "FIRE ALARM". Wiring color code shall be maintained throughout the installation.
B. Installation of equipment and devices that pertain to other work in the Contract shall be closely coordinated with the appropriate Subcontractors. All ceiling mounted devices shall be coordinate with reflected ceiling plan and all other ceiling devices.
C. Cover all smoke detection devices with plastic bags immediately after installation to maintain cleanliness, if field conditions so require.
D. The Contractor shall clean all dirt and debris from the inside and the outside of the fire alarm equipment after completion of the installation.
3.02 FINAL CONNECTIONS, TESTING, INSPECTION AND ACCEPTANCE
A. The Contractor shall, under this Contract, obtain the services of a factory trained representative of the system manufacturer to supervise the installation and its progress, supervise final connections to the equipment and provide testing to assure that the system is in proper operating condition and is in compliance with all applicable regulations. A complete functional test of the system in accordance with NFPA 72 chapter 14 and voice alarm intelligibility testing in accordance with IEC
60849 shall be performed and a written report shall be submitted to the Contractor attesting to the
28 31 12 - 11 proper operation of the completed system. The Contractor shall have present representatives of the manufacturer of the Fire Alarm System, authorities having jurisdiction and the Architect during final inspection. The Contractor shall demonstrate to the satisfaction of all parties that the system installed meets the specification requirements. All changes, modifications and adjustments to the installed system needed to meet the specification requirements will be made at no additional cost to the Owner.
B. Upon completion of the installation, printed system operating instructions and as-built wiring and layout drawings will be furnished to the Owner.
C. The manufacturer will provide an authorized representative to instruct and train the Fire
Department and the Owner's personnel in the operation of the system. This service will be made available for two (2) one (1) hour sessions as scheduled by the Owner.
3.03 GUARANTEE AND AFTER SERVICE
A. The Contractor shall warrant the completed Fire Alarm System wiring and equipment to be free from inherent mechanical and electrical defects for a period of one (1) year from the date of the completed and certified test or from the date of first beneficial use.
B. Upon satisfactory completion of all tests, the manufacturer's representative will present to the
Owner a proposal to provide inspections and testing of the system in compliance with the requirements of the state and local fire codes.
C. The system's vendor must employ factory trained technicians and maintain a service organization within 50 miles of the Job Site. This organization must have a minimum of 10 years experience servicing Fire Alarm Systems and provide 24 hour emergency service.
D. The vendor shall provide a maximum of four (4) hour response to the Owner's request for service.
The vendor will demonstrate this capability to the Owner and will provide this minimum response under all reasonable circumstances.
END OF SECTION