7-7. IFB 043-26-RM PS-12-182 PLANS Redundant Power - Final Plans SS.pdf
PDF 25 MB Posted
- Attached to
- Re-Bid Pump Station 182 Redundant Power
- Solicitation number
- IFB-043-26-RM
- Issued by
- Leon County, Florida
About this file
File Summary
This is a 100% construction plans document for the Pump Station 182 Redundant Power Project prepared by the City of Tallahassee Underground Utilities and Public Infrastructure Department, Water Resources Engineering Division, with plans designed by Kimley-Horn and Associates, Inc. The project involves construction of a redundant underground power supply system from the City of Tallahassee Electric Department's distribution system to Pump Station 182. The contractor's primary scope of work includes supplying and installing two 4-inch HDPE DR11 conduits via horizontal directional drilling from an existing termination cabinet on Engineering Way to the Pump Station 182 site, with conduit routing distances varying by location (ranging from approximately 150 to 460 linear feet across multiple routes). Additional work includes installation of termination cabinets supplied by the City of Tallahassee Electric Department along the conduit route, coordination with the Electric Utility for pad-mounted transformer and primary conductor installation, and supply and installation of a 2000-amp main breaker and automatic transfer switch with associated conduit and cable work. The plans establish a project datum of NAVD 88 and include detailed electrical conduit routing plans, existing conditions surveys, construction profiles, and technical specifications conforming to Florida Department of Transportation standards and City of Tallahassee technical specifications for water and sewer construction.
The construction plans require contractors to maintain minimum 42-inch cover between electrical conduits and existing grade, repair all damaged curb, gutter, and asphalt, and coordinate with multiple utility companies with 48 hours minimum notice before commencing work. The contractor bears full responsibility for locating and preserving underground utilities, obtaining all required construction permits and bonds, submitting certified record surveys, and maintaining as-built documentation. Plans indicate multiple directional bore pit locations with 375 square feet of silt fence-defined limits of disturbance at each site. Environmental compliance requirements include implementation of best management practices, erosion and sediment control measures, stormwater pollution prevention, turbidity barriers, and coordination with Leon County Environmental Inspector. The contractor must provide a certified Florida professional land surveyor for record drawings and as-built documentation and must ensure a foreman or supervisor certified under the Florida Stormwater, Erosion and Sedimentation Control Inspector Training Program is available during all construction activities.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
PR
O
PO
SED
TER
M
IN
ATIO
N C
ABIN
ET
TR
AN
SFO
R
M
ER
Springsax Park
Leon County Jail
ROBERTS AVE
R
AN
KIN
AVE
W PENSACOLA ST
W
AH
N
IS
H W
AY
RIDGE RD
JACKSON BLUFF RD
LEVY AVE
M
ABR
Y ST
SA
XO
N S
T
ORANGE AVE W
H O
LTO
N
ST
W GAINES ST
GAMBLE ST
BRAGG DR
BELLE VUE WAY
OSCEOLA ST
M
IL
L
ST
KEITH
ST
PEPPER DR
EISEN
H
O W
ER
ST
PLANT ST
N R
ID
G
E R D
AU
SLEY R
D
W JEFFERSON ST
LAKE BRADFORD RD
PAU
L D
IR
AC
D R
LAKE AVE
CALLEN ST
AIRPORT DR
PER
R
Y ST
TYSON RD
PO
TT
SD
AM
ER
S
T
KISSIMMEE ST
SPRINGSAX RD
MAYHEW ST EUGENIA ST
D U
PR
EE ST
ATKAMIRE DR
COLEMAN ST
ELBERTA DR
CAMPBELL ST
STUCKEY AVE
G
AY ST
TUCKER ST
W MADISON ST
W ST AUGUSTINE ST
MCELROY ST
W COLLEGE AVE
OKALOOSA ST
H
AYD
EN
R
D
HERNANDO DR
DANIELS ST
MCCASKILL AVE
H
AR
R
IS ST
RIDGEWAY ST
MUNICIPAL WAY
CARVER ST
ESSEX D
R
EPPES DR E
KAREN LN
D
AISY ST
TR
O
PI
C
AI
R
E
ST
FLORAL ST
PENNELL
CIR
GORE AVE
PRO
G
RESS DR
PO
PPY ST
N O
TR
E D
AM
E ST
M U
R
AT ST
IAM
O
N
IA ST
JOES RD
R
AI
LR
O
AD
A
VE
BLISS DR
NASSAU ST
LIBERTY ST
G U
N N
S T
OXFORD RD
VAN FLEET ST
MAUDE ST
FL
EE
TW
O
O D
S T
YU
LE
E
ST
SHARKEY ST
C H
IPLEY ST
S W
O O
D W
AR
D
A
VE
PA
TR
IC
K
AV
E
E PAUL DIRAC DR
TANNER DR
SATU
R
D
AY R
D
MANATEE ST
ROSWELL DR
FAMCEE AVE
ESTATES R
D
CATES AVE
STEAR
N
S ST
BLU
E JAY D
R
W LAFAYETTE ST
HOWARD AVE
MARCIA
A
VE
VICTORIA ST
HAM
ILTO
N PARK DR
H O
LM
ES
S T
FA
M
U /F
SU
W
AY
LEISU
R
E LN
MOSLEY ST
SYKES DR
HAMPTON AVE
D
ISSTO
N
ST
ED
W
AR
D
S ST
AVIATIO
N
AVE
MELANIE DR
H
ER
LO
N
G D
R
W
AR
W
IC
K
ST
KE
N
N
ED
Y D
R
PALM BEACH ST
TO
U
C
AN
D R
WIES ST
R
AC
KLEY D
R
W BLOXHAM ST
W H
EA
TL
EY
R
D
R
ID
G E
H
AV
EN
R
D
GLENDA DR
CHAMPIO
NS W
AY
D
AY ST
CALDWELL DR
CENTURY PARK DR
RYCO DR
HUTCHINSON AVE
CYPRESS COVE DR
BROOK ST
SAYERS DR
GAITHER DR
SUNRIDGE RD
TOMAHAWK TRL
SUNDOWN RD
LO
R
EN
E
ST
BOB WHITE DR
G
ALIM
O R
E D R
G
LY
N W
O O
D D
R
IN
D
IAN
R
IVER
ST
YORKSHIRE DR
G
EN
E ST
TYNDALL DR
KINGFORD AVE
C
LA
R A
ST
TUSKEGEE ST
O
LIVER
ST
PR
IN
C
E ST
CRATE DR
HAWKINS ST
G R
AY ST
BARBARA ST
ENTREPOT CT
BROOKRIDGE DR
EMORY CT
KEATOR ST
SAWMILL RD
GEORGETOWN DR
PI
N
EL
LA
S
ST
SNELLINGS DR
AIR
PO
R T C
O M
M
ER
C
E BLVD
DON PRICE WAY
MCARTHUR ST
BR
U
C E
LN
LENORA DR
CRENSHAW
CT
PASC
O
ST
KE
IT
H S
T
SPRINGHILL RD
W PENSACOLA ST
VILLAMORE AVE
SP
RI
NG
HI
LL
R
D
KISSIMMEE ST
JAM
ES ST
C
LE
VE
LA
N D
S T
ORANGE AVE W
M
IL
L
ST
LA
KE
B R
AD
FO
R D
R D
JACKSON BLUFF RD
Amtrak Station
Bragg Memorial StadiumInnovation
Park
Doak Campbell Stadium
Palmer Munroe Center
Walker Ford Center & Pool
James Messer Fields
Tallahassee Skate Park
Bellaire Wetland Preserve
Jake Gaither Municipal Golf Course
NIMS JUNIOR
HIGH SCHOOL
PINEVIEW
SCHOOL
BOND
SCHOOL
FLORIDA A AND
M UNIVERSITY
UNIVERSITY
HIGH SCHOOL
BELLE VUE SCHOOL
LEWIS M LIVELY AREA
TECHNICAL-
VOCATIONAL SCHOOL
SABAL
PALM
SCHOOL
SOUTHSIDE
CEMETERY
BLACK
SWAMP
BLACK SWAMP
GRASSY
LAKE
LAKE
BRADFORD
LAKEVIEW DR
LA
KE BRADFORD RD
R O
BI
N
R D
LONGLEAF RD
GERALD DR
SEASONS LN
LONG PINE DR
AUTUMN LN
WINDY PINE WAY
CATHEDRAL DR
BA
R
K D
R W
M
AR
IS
E
ST
BL
U
E
BI
R D
R D
TALL TOP DR
EN
TR
EP
O
T
BL
VD
LONGLEAF CT
JEWELL DR
PINENOLL DR
SA
N
D P
IN
E
D R
SL
O
E D
R
SP
R
IN
IL
R D
CROWN RIDGE RD
PARTRIDGE DR
EC
H
O P
O
IN
T
LN
ARROWWOOD LN
FLA
STACOWO R
D
BI
G
P
IN
E D
R
G
EO
R G
E
ST
EAGLE RD
SPR
IN
G
VIEW
TR
L
AU
TU
M N
C T
WINDY PINE CT
CONE DR
ROBIN CT
BIG LIMB CT
SP
RIN
IL
RD
WATER RESOURCES ENGINEERING DIVISION
WATER UTILITY ENGINEERING
WATER RESOURCES ENGINEERING DIVISION
WATER UTILITY ENGINEERING
300 S. Adams Street, B-26 ~ Tallahassee, FL 32301 Phone: 850-891-4968 ~ www.talgov.com/you
CIVIL ENGINEER
KIMLEY-HORN AND ASSOCIATES, INC.
2619 CENTENNIAL BLVD., SUITE 200
TALLAHASSEE, FL 32308
PHONE: (850) 553-3500
INDEX OF SHEETS
SHEET No. SHEET DESCRIPTION
C000 COVER SHEET
C100 GENERAL NOTES
C101 KEY SHEET
C200 EXISTING CONDITIONS
C201 EXISTING CONDITIONS
C202 EXISTING CONDITIONS
C203 EXISTING CONDITIONS
C300 ELECTRICAL CONDUIT ROUTING PLAN
C301 ELECTRICAL CONDUIT ROUTING PLAN
C302 ELECTRICAL CONDUIT ROUTING PLAN
C303 ELECTRICAL CONDUIT ROUTING PLAN
C400 PROFILE OF CONDUIT
C600 CONSTRUCTION DETAILS
E-01 ELECTRICAL SITE PLAN
E-02 ELECTRICAL RISER PLAN
E-03 ELECTRICAL CT/PT ENVLOSURES
PLANS PREPARED BY:
LOCATION MAP
UNDERGROUND UTILITIES & PUBLIC
INFRASTRUCTURE DEPARTMENT
No.
R E V I S I O N S
BY DATEDESCRIPTION
Know what'sbelow.
Callbefore you dig.
CALL 2 BUSINESS
DAYS BEFORE
YOU DIG
IT'S THE LAW!
DIAL 811
SUNSHINE STATE ONE CALL OF FLORIDA, INC.
PROJECT LOCATION
PROJECT LOCATION
FELICITY JOY APPEL, P.E.
ENGINEER OF RECORD
FL P.E. No. 87780 C I T Y O F T A L L A H A S S E E
UNDERGROUND UTILITIES DEPARTMENT
WATER RESOURCES ENGINEERING DIVISION
300 S. Adams Street, B-26 ~ Tallahassee, FL 32301 Phone: 850-891-0000 ~ www.talgov.com/you
SHEET
LEON COUNTY, FLORIDA
General Highway Map
APALACHEE PKWY
CAPITAL CIR SE
LA
KE
B
RA
DF
OR
D
RD
PENSACOLA ST
CA
PI
TA
L C
IR
N
W
CAPITAL CIR SW
MO
NR
OE
S
T
ORANGE AVE
THARPE ST
MONROE ST
CRAW
FO
RDVIL
LE
RD
W
OO
DV
ILL
E
HW
Y
BLOXHAM CUTOFF SP
RI
NG
HI
LL
R
D
CA
PI
TA
L C
IR
N
E
CENTE
RVILL
E RD
MICCOSUKEE RD
MAHAN DR
INTERSTATE 10
TRAM RD
INTERSTATE 10
TH
OMAS
VIL
LE
RD
ME
RI
DI
AN
R D
TENNESSEE ST
BLOUNTSTOWN HWY
MA
GN
OL
IA
D R
BL
AI
R
ST
ON
E
RD
PLANS PREPARED FOR:
GOVERNING STANDARDS AND SPECIFICATIONS:
PLANS PREPARED BY:
LOCATION MAP
APPROVED FOR CONSTRUCTION
CITY OF TALLAHASSEE UNDERGROUND UTILITIES &
PUBLIC INFRASTRUCTURE DEPARTMENT
WATER RESOURCES ENGINEERING DIVISION
DATE: ______________ SET No. __________
U se r:
Ju lia n.
M cN ei lJ on es
K:
\ta l_ ci vi l\1
- c ity o f t al la ha ss ee
\0
- p s a nd re du nd an t p ow er
\D es ig n\
C
AD
D \p la ns he et s\ C
C O
VE
R
S H
EE
T.
dw g
6/
/2
9:
:2
AM
Proj/CIP-WTR/File Tracker No.:
Project No.:
IFB No.:
of
PUMP STATION 182 REDUNDANT POWER
100% CONSTRUCTION PLANS
JUNE 2025
1" = 2000'
144124091
Florida Department of Transportation Standard Plans, Current Edition Standard Specifications for Road and Bridge Construction, Current Edition City of Tallahassee Technical Specifications for Water and Sewer Construction, Current Edition
AS AMENDED BY CONTRACT DOCUMENTS
Attention is directed to the fact that these plans may have been altered in size by reproduction. this must be considered when obtaining scaled data.
ENGINEER OF RECORD IS RESPONSIBLE FOR ALL SHEETS LISTED IN THE
ABOVE INDEX EXCEPT FOR SHEETS C200 TO C203 AND E-01 TO E-03.
This item has been digitally signed and sealed by Felicity Joy Appel on the date adjacent to the seal.
Signature must be verified on any electronic copies
Digitally signed by Felicity J Appel DN: CN=Felicity J Appel, dnQualifier=A01410C000001948F8D53B1000333DD, O=KIMLEY-HORN AND ASSOCIATES, C=US
Date: 2025.07.10 08:03:16-04'00'
G
EN
ER
AL
N O
TE
S
C100
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
GENERAL CONSTRUCTION NOTES
1. THE CONTRACTOR AND SUBCONTRACTORS SHALL OBTAIN A COPY OF THE FLORIDA DEPARTMENT OF TRANSPORTATION
"STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION" (LATEST EDITION) AND BECOME FAMILIAR WITH THE CONTENTS PRIOR TO COMMENCING WORK, AND, UNLESS OTHERWISE NOTED, ALL WORK SHALL CONFORM AS APPLICABLE TO
THESE STANDARDS AND SPECIFICATIONS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING ALL MATERIAL AND LABOR TO CONSTRUCT THE FACILITY AS SHOWN AND DESCRIBED IN THE CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH THE APPROPRIATE APPROVING AUTHORITIES, SPECIFICATIONS AND REQUIREMENTS. CONTRACTOR SHALL CLEAR AND GRUB ALL AREAS UNLESS OTHERWISE INDICATED, REMOVING TREES, STUMPS, ROOTS, MUCK, EXISTING PAVEMENT AND ALL OTHER DELETERIOUS MATERIAL.
3. EXISTING UTILITIES SHOWN ARE LOCATED ACCORDING TO THE INFORMATION AVAILABLE TO THE ENGINEER AT THE TIME OF THE TOPOGRAPHIC SURVEY AND HAVE NOT BEEN INDEPENDENTLY VERIFIED BY THE OWNER OR THE ENGINEER. GUARANTEE IS NOT MADE THAT ALL EXISTING UNDERGROUND UTILITIES ARE SHOWN OR THAT THE LOCATION OF THOSE SHOWN ARE ENTIRELY ACCURATE. FINDING THE ACTUAL LOCATION OF ANY EXISTING UTILITIES IS THE CONTRACTOR'S RESPONSIBILITY AND SHALL BE DONE BEFORE COMMENCING ANY WORK IN THE VICINITY. FURTHERMORE, THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES DUE TO THE CONTRACTOR'S FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES. THE OWNER OR ENGINEER WILL ASSUME NO LIABILITY FOR ANY DAMAGES SUSTAINED OR COST INCURRED BECAUSE OF THE OPERATIONS IN THE VICINITY OF EXISTING UTILITIES OR STRUCTURES, NOR FOR TEMPORARY BRACING AND SHORING OF SAME. IF IT IS NECESSARY TO SHORE, BRACE, SWING OR RELOCATE A UTILITY, THE UTILITY COMPANY OR DEPARTMENT AFFECTED SHALL BE CONTACTED AND THEIR PERMISSION OBTAINED REGARDING THE
METHOD TO USE FOR SUCH WORK.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE VARIOUS UTILITY COMPANIES WHICH MAY HAVE BURIED OR AERIAL UTILITIES WITHIN OR NEAR THE CONSTRUCTION AREA BEFORE COMMENCING WORK. THE CONTRACTOR SHALL PROVIDE 48 HOURS MINIMUM NOTICE TO ALL UTILITY COMPANIES PRIOR TO BEGINNING CONSTRUCTION. AN APPROXIMATE LIST OF THE UTILITY COMPANIES WHICH THE CONTRACTOR MUST CALL BEFORE COMMENCING WORK IS PROVIDED ON THE COVER SHEET OF THESE CONSTRUCTION PLANS. THIS LIST SERVES AS A GUIDE ONLY AND IS NOT INTENDED TO LIMIT THE
UTILITY COMPANIES WHICH THE CONTRACTOR MAY WISH TO NOTIFY.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED CONSTRUCTION PERMITS AND BONDS IF
REQUIRED PRIOR TO CONSTRUCTION.
6. THE CONTRACTOR SHALL HAVE AVAILABLE AT THE JOB SITE AT ALL TIMES ONE COPY OF THE CONSTRUCTION DOCUMENTS INCLUDING PLANS, SPECIFICATIONS, GEOTECHNICAL REPORT AND SPECIAL CONDITIONS AND COPIES OF ANY REQUIRED
CONSTRUCTION PERMITS.
7. ANY DISCREPANCIES ON THE DRAWINGS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE OWNER AND ENGINEER BEFORE COMMENCING WORK. NO FIELD CHANGES OR DEVIATIONS FROM DESIGN ARE TO BE MADE WITHOUT
PRIOR WRITTEN APPROVAL OF THE OWNER AND NOTIFICATION TO THE ENGINEER.
8. ALL COPIES OF COMPACTION, CONCRETE AND OTHER REQUIRED TEST RESULTS ARE TO BE SENT TO THE OWNER AND DESIGN
ENGINEER OF RECORD DIRECTLY FROM THE TESTING AGENCY.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING TO THE ENGINEER A CERTIFIED RECORD SURVEY SIGNED AND SEALED BY A PROFESSIONAL LAND SURVEYOR REGISTERED IN THE STATE OF FLORIDA DEPICTING THE ACTUAL FIELD LOCATION OF ALL CONSTRUCTED IMPROVEMENTS THAT ARE REQUIRED BY THE JURISDICTIONAL AGENCIES FOR THE
CERTIFICATION PROCESS. ALL SURVEY COSTS WILL BE THE CONTRACTORS RESPONSIBILITY.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DOCUMENTING AND MAINTAINING AS-BUILT INFORMATION WHICH SHALL BE RECORDED AS CONSTRUCTION PROGRESSES OR AT THE COMPLETION OF APPROPRIATE CONSTRUCTION INTERVALS AND SHALL BE RESPONSIBLE FOR PROVIDING AS-BUILT DRAWINGS TO THE OWNER FOR THE PURPOSE OF CERTIFICATION TO JURISDICTIONAL AGENCIES AS REQUIRED. ALL AS-BUILT DATA SHALL BE COLLECTED BY A STATE OF FLORIDA PROFESSIONAL
LAND SURVEYOR WHOSE SERVICES ARE ENGAGED BY THE CONTRACTOR.
11. ANY WELLS DISCOVERED ON SITE THAT WILL HAVE NO USE MUST BE PROPERLY ABANDONED BY A LICENSED WELL DRILLING CONTRACTOR IN A MANNER APPROVED BY ALL JURISDICTIONAL AGENCIES. CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING ANY WELL ABANDONMENT PERMITS REQUIRED.
12. ANY WELL DISCOVERED DURING EARTH MOVING OR EXCAVATION SHALL BE REPORTED TO THE APPROPRIATE JURISDICTIONAL
AGENCIES WITHIN 24 HOURS AFTER DISCOVERY IS MADE.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE PROPOSED IMPROVEMENTS SHOWN ON THE PLANS DO NOT CONFLICT WITH ANY KNOWN EXISTING OR OTHER PROPOSED IMPROVEMENTS. IF ANY CONFLICTS ARE DISCOVERED, THE CONTRACTOR SHALL NOTIFY THE OWNER PRIOR TO INSTALLATION OF ANY PORTION OF THE SITE WORK THAT WOULD BE AFFECTED. FAILURE TO NOTIFY OWNER OF AN IDENTIFIABLE CONFLICT PRIOR TO PROCEEDING WITH INSTALLATION RELIEVES
OWNER OF ANY OBLIGATION TO PAY FOR A RELATED CHANGE ORDER.
14. ANY CONSTRUCTION ADJACENT TO A WETLAND AREA SHALL BE PERFORMED FROM THE UPLAND SIDE OF THE AREA.
CONSTRUCTION ENCROACHMENT INTO A WETLAND AREA IS NOT ALLOWED UNLESS PERMITTED BY THE JURISDICTIONAL
AGENCY.
15. TRAFFIC CONTROL SHALL BE IN ACCORDANCE WITH THE CURRENT FDOT DESIGN STANDARD INDEX (SERIES 600) AND THE
MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
DEMOLITION NOTES
1. ALL MATERIAL REMOVED FROM THIS SITE BY THE CONTRACTOR SHALL BE DISPOSED OF BY THE CONTRACTOR IN A LEGAL
MANNER.
2. REFER TO THE TOPOGRAPHIC SURVEY FOR ADDITIONAL DETAILS OF EXISTING STRUCTURES, ETC., LOCATED WITHIN THE PROJECT SITE. UNLESS OTHERWISE NOTED, ALL EXISTING BUILDINGS, STRUCTURES, SLABS, CONCRETE, ASPHALT, DEBRIS PILES, SIGNS, AND ALL APPURTENANCES ARE TO BE REMOVED FROM THE SITE BY THE CONTRACTOR AND PROPERLY DISPOSED OF IN A LEGAL MANNER AS PART OF THIS CONTRACT. SOME ITEMS TO BE REMOVED MAY NOT BE DEPICTED ON THE TOPOGRAPHIC SURVEY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VISIT THE SITE AND DETERMINE THE FULL EXTENT OF ITEMS TO BE REMOVED. IF ANY ITEMS ARE IN QUESTION, THE CONTRACTOR SHALL CONTACT THE OWNER PRIOR TO REMOVAL
OF SAID ITEMS.
3. THE CONTRACTOR SHALL REFER TO THE DEMOLITION PLAN AND TREE INVENTORY PLAN FOR DEMOLITION/PRESERVATION OF EXISTING TREES. ALL TREES NOT SPECIFICALLY SHOWN TO BE PRESERVED OR RELOCATED SHALL BE REMOVED AS A PART OF THIS CONTRACT. TREE PROTECTION FENCING SHALL BE INSTALLED PRIOR TO ANY DEMOLITION.
4. CONTRACTOR SHALL ADJUST GRADE OF ANY EXISTING UTILITIES TO REMAIN.
5. CONTRACTOR IS REQUIRED TO OBTAIN ALL DEMOLITION PERMITS.
RECORD DRAWINGS
1. CONTRACTOR SHALL PROVIDE TO THE ENGINEER AND OWNER A MINIMUM OF 10 HARD COPIES OF A PAVING, GRADING AND
DRAINAGE RECORD DRAWING AND A SEPARATE UTILITY RECORD DRAWING, AS WELL AS BOTH IN AUTOCAD 2015 OR LATER, BOTH PREPARED BY A FLORIDA REGISTERED SURVEYOR. THE RECORD DRAWINGS SHALL VERIFY ALL DESIGN INFORMATION
INCLUDED ON THE DESIGN PLANS OF THE SAME NAME.
PAVING, GRADING AND DRAINAGE NOTES
1. ALL PAVING, CONSTRUCTION, MATERIALS, AND WORKMANSHIP WITHIN JURISDICTION'S RIGHT-OF-WAY SHALL BE IN
ACCORDANCE WITH LOCAL OR COUNTY SPECIFICATIONS AND STANDARDS (LATEST EDITION) OR FDOT SPECIFICATIONS AND
STANDARD PLANS (LATEST EDITION) IF NOT COVERED BY LOCAL OR COUNTY REGULATIONS.
2. ALL UNPAVED AREAS IN EXISTING RIGHTS-OF-WAY DISTURBED BY CONSTRUCTION SHALL BE REGRADED AND SODDED.
3. TRAFFIC CONTROL ON ALL FDOT, LOCAL AND COUNTY RIGHTS-OF-WAY SHALL MEET THE REQUIREMENTS OF THE MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES (U.S. DOT/FHA) AND THE REQUIREMENTS OF THE STATE AND ANY LOCAL AGENCY HAVING JURISDICTION. IN THE EVENT THAT THE CONTRACT DOCUMENTS AND THE JURISDICTIONAL AGENCY REQUIREMENTS
ARE NOT IN AGREEMENT, THE MOST STRINGENT SHALL GOVERN.
4. THE CONTRACTOR SHALL GRADE THE SITE TO THE ELEVATIONS INDICATED AND SHALL REGRADE WASHOUTS WHERE THEY OCCUR AFTER EVERY RAINFALL UNTIL A GRASS STAND IS WELL ESTABLISHED OR ADEQUATE STABILIZATION OCCURS.
5. WHERE NEW PAVEMENT MEETS THE EXISTING PAVEMENT, THE CONTRACTOR SHALL SAW CUT THE EXISTING PAVEMENT A MINIMUM 2" DEEP FOR A SMOOTH AND STRAIGHT JOINT AND MATCH THE EXISTING PAVEMENT ELEVATION WITH THE
PROPOSED PAVEMENT UNLESS OTHERWISE INDICATED.
6. THE CONTRACTOR SHALL INSTALL FILTER FABRIC OVER ALL DRAINAGE STRUCTURES FOR THE DURATION OF CONSTRUCTION AND UNTIL ACCEPTANCE OF THE PROJECT BY THE OWNER. ALL DRAINAGE STRUCTURES SHALL BE CLEANED OF SILT AND DEBRIS AS REQUIRED DURING AND AT THE END OF CONSTRUCTION TO PROVIDE POSITIVE DRAINAGE FLOWS.
7. IF DEWATERING IS REQUIRED, THE CONTRACTOR SHALL OBTAIN ANY APPLICABLE REQUIRED PERMITS. THE CONTRACTOR IS
TO COORDINATE WITH THE OWNER AND THE DESIGN ENGINEER PRIOR TO ANY EXCAVATION.
8. STRIP TOPSOIL AND ORGANIC MATTER FROM ALL AREAS OF THE SITE AS REQUIRED. IN SOME CASES TOPSOIL MAY BE STOCKPILED ON SITE FOR PLACEMENT WITHIN LANDSCAPED AREAS BUT ONLY AS DIRECTED BY THE OWNER AND APPROVED
BY THE LEON COUNTY ENVIRONMENTAL INSPECTOR.
9. FIELD DENSITY TESTS SHALL BE TAKEN AT INTERVALS IN ACCORDANCE WITH THE LOCAL JURISDICTIONAL AGENCY OR TO FDOT STANDARDS. IN THE EVENT THAT THE CONTRACT DOCUMENTS AND THE JURISDICTIONAL AGENCY REQUIREMENTS ARE
NOT IN AGREEMENT, THE MOST STRINGENT SHALL GOVERN.
10. ALL SLOPES AND AREAS DISTURBED BY CONSTRUCTION SHALL BE SODDED OR SEEDED AS SPECIFIED IN THE PLANS, FERTILIZED, MULCHED, WATERED AND MAINTAINED UNTIL HARDY GRASS GROWTH IS ESTABLISHED IN ALL AREAS. ANY AREAS DISTURBED FOR ANY REASON PRIOR TO FINAL ACCEPTANCE OF THE JOB SHALL BE CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. ALL EARTHEN AREAS WILL BE SODDED OR SEEDED AND MULCHED AS SHOWN ON THE
LANDSCAPING PLAN.
11. ALL CUT OR FILL SLOPES SHALL BE 3 (HORIZONTAL) :1 (VERTICAL) OR FLATTER UNLESS OTHERWISE SHOWN.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF DUST AND DIRT RISING AND SCATTERING IN THE AIR DURING CONSTRUCTION AND SHALL PROVIDE WATER SPRINKLING OR OTHER SUITABLE METHODS OF CONTROL. THE
CONTRACTOR SHALL COMPLY WITH ALL GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION.
13. THE CONTRACTOR SHALL TAKE ALL REQUIRED MEASURES TO CONTROL TURBIDITY, INCLUDING BUT NOT LIMITED TO THE INSTALLATION OF TURBIDITY BARRIERS AT ALL LOCATIONS WHERE THE POSSIBILITY OF TRANSFERRING SUSPENDED SOLIDS INTO THE RECEIVING WATER BODY EXISTS DUE TO THE PROPOSED WORK OR ANY OTHER AREAS AS INDICATED BY THE LEON COUNTY ENVIRONMENTAL INSPECTOR. TURBIDITY BARRIERS MUST BE MAINTAINED IN EFFECTIVE CONDITION AT ALL LOCATIONS UNTIL CONSTRUCTION IS COMPLETED AND DISTURBED SOIL AREAS ARE STABILIZED. THEREAFTER, THE CONTRACTOR MUST REMOVE THE BARRIERS. AT NO TIME SHALL THERE BE ANY OFF-SITE DISCHARGE WHICH VIOLATES THE
WATER QUALITY STANDARDS IN CHAPTER 17-302, FLORIDA ADMINISTRATIVE CODE.
14. SOD, WHERE CALLED FOR, MUST BE INSTALLED AND MAINTAINED ON EXPOSED SLOPES WITHIN 48 HOURS OF COMPLETING FINAL GRADING, AND AT ANY OTHER TIME AS NECESSARY, TO PREVENT EROSION, SEDIMENTATION OR TURBID DISCHARGES.
15. THE CONTRACTOR MUST REVIEW AND MAINTAIN A COPY OF THE ENVIRONMENTAL RESOURCE PERMIT COMPLETE WITH ALL CONDITIONS, ATTACHMENTS, EXHIBITS, AND PERMIT MODIFICATIONS IN GOOD CONDITION AT THE CONSTRUCTION SITE. THE COMPLETE PERMIT MUST BE AVAILABLE FOR REVIEW UPON REQUEST BY WATER MANAGEMENT DISTRICT REPRESENTATIVES, OR ANY OTHER REGULATORY AGENCY WHOSE JURISDICTION COVERS THIS PROJECT SITE.
16. THE CONTRACTOR SHALL ENSURE THAT ISLAND PLANTING AREAS AND OTHER PLANTING AREAS ARE NOT COMPACTED AND DO NOT CONTAIN ROAD BASE MATERIALS. THE CONTRACTOR SHALL ALSO EXCAVATE AND REMOVE ALL UNDESIRABLE MATERIAL FROM ALL AREAS ON THE SITE TO BE PLANTED AND PROPERLY DISPOSED OF IN A LEGAL MANNER.
17. THE CONTRACTOR SHALL INSTALL ALL UNDERGROUND STORMWATER PIPING PER MANUFACTURER'S RECOMMENDATIONS.
MAINTENANCE
ALL MEASURES STATED ON THE EROSION AND SEDIMENT CONTROL PLAN, AND IN THE STORM WATER POLLUTION PREVENTION PLAN, SHALL BE MAINTAINED IN FULLY FUNCTIONAL CONDITION UNTIL NO LONGER REQUIRED FOR A COMPLETED PHASE OF WORK OR FINAL STABILIZATION OF THE SITE. ALL EROSION AND SEDIMENTATION CONTROL MEASURES SHALL BE CHECKED BY A QUALIFIED PERSON AT LEAST ONCE EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS OF THE END OF A 0.5" RAINFALL EVENT
OR GREATER, AND CLEANED AND REPAIRED IN ACCORDANCE WITH THE FOLLOWING:
1. INLET PROTECTION DEVICES AND BARRIERS SHALL BE REPAIRED OR REPLACED IF THEY SHOW SIGNS OF UNDERMINING, OR
DETERIORATION.
2. ALL SEEDED AREAS SHALL BE CHECKED REGULARLY TO SEE THAT A GOOD STAND IS MAINTAINED. AREAS SHOULD BE FERTILIZED, WATERED AND RESEEDED AS NEEDED. FOR MAINTENANCE REQUIREMENTS REFER TO SECTION 981 OF THE
STANDARD SPECIFICATIONS.
3. SILT FENCES SHALL BE REPAIRED TO THEIR ORIGINAL CONDITIONS IF DAMAGED. SEDIMENT SHALL BE REMOVED FROM THE
SILT FENCES WHEN IT REACHES ONE-HALF THE HEIGHT OF THE SILT FENCE.
4. THE CONSTRUCTION ENTRANCES SHALL BE MAINTAINED IN A CONDITION WHICH WILL PREVENT TRACKING OR FLOW OF MUD ONTO PUBLIC RIGHTS-OF-WAY. THIS MAY REQUIRE PERIODIC TOP DRESSING OF THE CONSTRUCTION ENTRANCES AS
CONDITIONS DEMAND.
5. THE TEMPORARY PARKING AND STORAGE AREA SHALL BE KEPT IN GOOD CONDITION (SUITABLE FOR PARKING AND STORAGE).
THIS MAY REQUIRE PERIODIC TOP DRESSING OF THE TEMPORARY PARKING AS CONDITIONS DEMAND.
6. OUTLET STRUCTURES IN THE SEDIMENTATION BASINS SHALL BE MAINTAINED IN OPERATIONAL CONDITIONS AT ALL TIMES.
SEDIMENT SHALL BE REMOVED FROM SEDIMENT BASINS OR TRAPS WHEN THE DESIGN CAPACITY HAS BEEN REDUCED BY 55
CUBIC YARDS / ACRE.
7. ALL MAINTENANCE OPERATIONS SHALL BE DONE IN A TIMELY MANNER BUT IN NO CASE LATER THAN 2 CALENDAR DAYS
FOLLOWING THE INSPECTION.
WATER AND SEWER UTILITY NOTES
1. ALL EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE THE CONTRACTOR SHALL COMPLY WITH ALL
REQUIREMENTS FOR UTILITY LOCATION AND COORDINATION IN ACCORDANCE WITH THE NOTES CONTAINED IN THE GENERAL
CONSTRUCTION SECTION OF THIS SHEET.
2. THE CONTRACTOR SHALL RESTORE ALL DISTURBED VEGETATION IN KIND, UNLESS SHOWN OTHERWISE.
3. WATER FOR FIRE FIGHTING SHALL BE AVAILABLE FOR USE PRIOR TO COMBUSTIBLES BEING BROUGHT ON SITE.
4. CONTRACTOR SHALL PERFORM, AT HIS OWN EXPENSE, ANY AND ALL TESTS REQUIRED BY THE SPECIFICATIONS AND/OR ANY AGENCY HAVING JURISDICTION. THESE TESTS MAY INCLUDE, BUT MAY NOT BE LIMITED TO, INFILTRATION AND EXFILTRATION, TELEVISION INSPECTION AND A MANDREL TEST ON GRAVITY SEWER. A COPY OF THE TEST RESULTS SHALL BE PROVIDED TO
THE UTILITY PROVIDER, OWNER AND JURISDICTIONAL AGENCY AS REQUIRED.
EROSION CONTROL NOTES
1. THE STORM WATER POLLUTION PREVENTION PLAN ("SWPPP") IS COMPRISED OF THIS EROSION CONTROL PLAN, THE
STANDARD DETAILS, THE PLAN NARRATIVE, ATTACHMENTS INCLUDED IN SPECIFICATIONS OF THE SWPPP, PLUS THE PERMIT
AND ALL SUBSEQUENT REPORTS AND RELATED DOCUMENTS.
2. ALL CONTRACTORS AND SUBCONTRACTORS INVOLVED WITH STORM WATER POLLUTION PREVENTION SHALL OBTAIN A COPY OF THE STORM WATER POLLUTION PREVENTION PLAN AND THE STATE OF FLORIDA NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM GENERAL PERMIT (NPDES PERMIT) AND BECOME FAMILIAR WITH THEIR CONTENTS.
3. THE CONTRACTOR SHALL IMPLEMENT BEST MANAGEMENT PRACTICES AS REQUIRED BY THE SWPPP. ADDITIONAL BEST MANAGEMENT PRACTICES SHALL BE IMPLEMENTED AS DICTATED BY CONDITIONS AT NO ADDITIONAL COST TO THE OWNER
THROUGHOUT ALL PHASES OF CONSTRUCTION.
4. BEST MANAGEMENT PRACTICES (BMP'S) AND CONTROLS SHALL CONFORM TO FEDERAL, STATE, OR LOCAL REQUIREMENTS OR MANUAL OF PRACTICE, AS APPLICABLE. THE CONTRACTOR SHALL IMPLEMENT ADDITIONAL CONTROLS AS DIRECTED BY THE
PERMITTING AGENCY OR OWNER.
5. PERMITS FOR ANY CONSTRUCTION ACTIVITY IMPACTING STATE WATERS OR REGULATED WETLANDS MUST BE MAINTAINED ON
SITE AT ALL TIMES.
6. THE CONTRACTOR SHALL MINIMIZE CLEARING TO THE MAXIMUM EXTENT PRACTICAL OR AS REQUIRED BY THE GENERAL
PERMIT.
7. CONTRACTOR SHALL DENOTE ON PLAN THE TEMPORARY PARKING AND STORAGE AREA WHICH SHALL ALSO BE USED AS THE EQUIPMENT MAINTENANCE AND CLEANING AREA, EMPLOYEE PARKING AREA, AND AREA FOR LOCATING PORTABLE FACILITIES, OFFICE TRAILERS, AND TOILET FACILITIES.
8. ALL WASH WATER (CONCRETE TRUCKS, VEHICLE CLEANING, EQUIPMENT CLEANING, ETC.) SHALL BE DETAINED AND PROPERLY
TREATED OR DISPOSED.
9. SUFFICIENT OIL AND GREASE ABSORBING MATERIALS AND FLOTATION BOOMS SHALL BE MAINTAINED ON SITE OR READILY
AVAILABLE TO CONTAIN AND CLEAN-UP FUEL OR CHEMICAL SPILLS AND LEAKS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DUST CONTROL ON SITE. THE USE OF MOTOR OILS AND OTHER PETROLEUM
BASED OR TOXIC LIQUIDS FOR DUST SUPPRESSION OPERATIONS IS PROHIBITED.
11. RUBBISH, TRASH, GARBAGE, LITTER, OR OTHER SUCH MATERIALS SHALL BE DEPOSITED INTO SEALED CONTAINERS.
MATERIALS SHALL BE PREVENTED FROM LEAVING THE PREMISES THROUGH THE ACTION OF WIND OR STORM WATER
DISCHARGE INTO DRAINAGE DITCHES OR WATERS OF THE STATE.
12. ALL STORM WATER POLLUTION PREVENTION MEASURES PRESENTED ON THE PLAN, SHALL BE INITIATED AS SOON AS
PRACTICABLE.
13. STABILIZATION PRACTICES SHOULD BE INITIATED AS SOON AS PRACTICAL, BUT IN NO
CASE MORE THAN 7 DAYS WHERE CONSTRUCTION HAS TEMPORARILY CEASED.
14. DISTURBED PORTIONS OF THE SITE WHERE CONSTRUCTION ACTIVITY HAS PERMANENTLY STOPPED SHALL BE PERMANENTLY SEEDED. THESE AREAS SHALL BE SEEDED NO LATER THAN 7 DAYS AFTER THE LAST CONSTRUCTION ACTIVITY OCCURRED IN THESE AREAS. REFER TO SECTION 981 OF THE STANDARD SPECIFICATIONS FOR SEEDING AND MAINTENANCE REQUIREMENTS.
15. IF THE ACTION OF VEHICLES TRAVELING OVER THE GRAVEL CONSTRUCTION ENTRANCES IS NOT SUFFICIENT TO REMOVE THE MAJORITY OF DIRT OR MUD, THEN THE TIRES MUST BE WASHED BEFORE THE VEHICLES ENTER A PUBLIC ROAD. IF WASHING IS USED, PROVISIONS MUST BE MADE TO INTERCEPT THE WASH WATER AND TRAP THE SEDIMENT BEFORE IT IS CARRIED OFF
THE SITE.
16. ALL MATERIALS SPILLED, DROPPED, WASHED, OR TRACKED FROM VEHICLES ONTO ROADWAYS OR INTO STORM DRAINS MUST
BE REMOVED AS SOON AS POSSIBLE.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING SEDIMENT IN THE DETENTION POND AND ANY SEDIMENT THAT MAY HAVE COLLECTED IN THE STORM SEWER DRAINAGE SYSTEMS IN CONJUNCTION WITH THE STABILIZATION OF THE SITE.
18. ON-SITE & OFF SITE SOIL STOCKPILE AND BORROW AREAS SHALL BE PROTECTED FROM EROSION AND SEDIMENTATION THROUGH IMPLEMENTATION OF BEST MANAGEMENT PRACTICES. STOCKPILE AND BORROW AREA LOCATIONS SHALL BE NOTED ON THE EROSION CONTROL PLAN AND PERMITTED IN ACCORDANCE WITH GENERAL PERMIT REQUIREMENTS.
19. SLOPES SHALL BE LEFT IN A ROUGHENED CONDITION DURING THE GRADING PHASE TO REDUCE RUNOFF VELOCITIES AND
EROSION.
20. DUE TO GRADE CHANGES DURING THE DEVELOPMENT OF THE PROJECT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ADJUSTING THE EROSION CONTROL MEASURES (SILT FENCES, ETC.) TO PREVENT EROSION.
21. ALL CONSTRUCTION SHALL BE STABILIZED AT THE END OF EACH WORKING DAY, THIS INCLUDES BACK FILLING OF TRENCHES FOR UTILITY CONSTRUCTION AND PLACEMENT OF GRAVEL OR BITUMINOUS PAVING FOR ROAD CONSTRUCTION.
BEST MANAGEMENT PRACTICES (BMP) NOTES
1. CONTRACTOR SHALL COORDINATE WITH THE ENVIRONMENTAL INSPECTOR.
2. ADDITIONAL SEDIMENT AND EROSION CONTROL MEASURES MAY BE REQUIRED, DURING ANY PHASE OF DEVELOPMENT, AT
THE DISCRETION ENVIRONMENTAL INSPECTOR.
3. THE CONTRACTOR SHALL ENSURE THAT A FOREMAN OR SUPERVISOR WHO HAS BEEN CERTIFIED UNDER THE FLORIDA STORMWATER, EROSION AND SEDIMENTATION CONTROL INSPECTOR TRAINING PROGRAM IS AVAILABLE IN PERSON OR BY PHONE AT ALL TIMES DURING CONSTRUCTION ACTIVITIES. INSPECTOR TO BE DESIGNATED AND AVAILABLE AT THE
PRE-CONSTRUCTION MEETING.
4. SILT FENCE SHOWN ON THESE PLANS SHALL BE INSTALLED GENERALLY IN THE LOCATIONS INDICATED, ADJUSTED FOR FIELD
CONSTRAINTS.
5. CONTRACTOR SHALL INSPECT AND REPAIR ALL BMP's AT LEAST ONCE A WEEK, AND AFTER EVERY SIGNIFICANT RAIN EVENT (>
2" OF RAINFALL.) A LOG OF SUCH INSPECTIONS SHALL BE MAINTAINED AT THE SITE.
6. ANY BMP IN NEED OF REPAIR OR REINSTALLATION SHALL BE CORRECTED BY THE CONTRACTOR WITHIN 24 HOURS OF
IDENTIFICATION OF THE NEED FOR SUCH ORRECTION.
7. ADDITIONAL BMP MEASURES MAY BE NECESSARY TO ENSURE THAT TURBID WATER IS NOT DISCHARGED FROM THE CONSTRUCTION SITE. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE STORMWATER POLLUTION PREVENTION PLAN, THE N.P.D.E.S. PERMIT AND THE CONDITIONS OF THE APPLICABLE NWFWMD ENVIRONMENTAL
RESOURCE PERMIT.
9. ALL DISTURBED AREAS TO BE LEFT IDLE LONGER THAN 14 DAYS MUST BE STABILIZED WITH QUICK GROW GRASS SEED AND
MULCH.
10. IMPROVEMENTS SHOWN FOR REFERENCE ONLY.
11. COORDINATE DISPOSAL OF EXCAVATED MATERIAL WITH OWNER.
12. CONTRACTOR IS RESPONSIBLE FOR SODDING ALL DISTURBED AREAS.
PROJECT SPECIFIC NOTES
1. CONTRACTOR TO SUBMIT BORING PLAN FOR APPROVAL PRIOR TO START OF CONSTRUCTION.
CC
T
T T
(R
IG
H T
O F
W A
Y V
A
RI
ES
(RIGHT OF WAY VARIES)
APPROX. ROW
APPROX. ROW
A
PP
RO
X.
R O
W
FT 00
FT 00
ZS 00
ZS 00
ZS 00
ZS 00
PT 00
PT 00
AT 00
(1
' R
IG
H T
O F
W A
Y)
F
F
W F
A
PP
R O
X.
R
O W
A
PP
R O
X.
R
O W
KE
Y
SH
EE
T
C101
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
N O
R
TH
GRAPHIC SCALE IN FEET
50 100 200
GRAPHIC SCALE IN FEET
50 100 200
SHEET C300
SHEET C300 SHEET C301 SHEET C301
SHEET C302 SHEET C302
M A
TC
H
LI
N
E A
M A
TC
H
LI
N
E A
COLLEGE OF ENGINEERING
SHEET C303 SHEET C303
PROJECT DATUM NAVD 88
LEGEND:
CC
A
PP
RO
X.
R O
W
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
C200
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
NORTH
GRAPHIC SCALE IN FEET
10 20 40
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
B E
LO
W
MATCHLINE SEE ABOVE
M A
TC
H
LI
N
E S
E E
S H
E E
T C
(R
IG
H T
O F
W A
Y V
A
RI
ES
A
PP
RO
X.
R O
W
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
C201
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
M A
TC
H
LI
N
E S
E E
S H
E E
T C
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
C202
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
M A
TC
H
LI
N
E S
E E
S H
E E
T C
F
W F
A
PP
R O
X.
R
O W
A
PP
R O
X.
R
O W
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
C203
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE
OE
OE
OE
OE
OE
OE
OE
OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
A
PP
RO
X.
R O
W
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
S F
SF
S F
PROPOSED TERMINATION CABINET
285 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT 2 - 4" HDPE DR11 CONDUIT
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
CONTRACTOR TO STUB UP CONDUIT AT EXISTING OVERHEAD UTILITY POLE.
CITY OF TALLAHASSEE ELECTRIC TO RUN CABLE AND MAKE CONNECTIONS.
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
285 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
LP
LP
x x x x x x x
OEOE
OEOE
O E
O E
O E
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE OE OE OE OE OE OE OE OE OE OE
O E
O E
O E
O E
O E
O E
O E
O E
OE OE OE OE OE OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE OE OE OE OE OE OE OE OE OE OE OE
x x x x x x x x x x x x x x xxxx x x x
S F
S F
S F
U G
-E U
G -E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
PROPOSED TERMINATION CABINET
397 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
LP
EL
EC
TR
IC
AL
C
O N
D U
IT
R
O U
TI
N
G
PL
AN
C300
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
NORTH
GRAPHIC SCALE IN FEET
10 20 40
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
NOTES:
1. CONTRACTOR SHALL REPAIR ALL
CURB, GUTTER, AND ASPHALT
DAMAGED OR REMOVED DURING
CONSTRUCTION.
2. 42" MINIMUM COVER BETWEEN
ELECTRICAL CONDUIT AND
EXISTING GRADE.
M A
TC
H
LI
N
E S
E E
B E
LO
W
MATCHLINE SEE ABOVE
x x x x
OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
T T
OE OE OE OE OE OE OE
OE
OE OE OE OE OE OE OE
(R
IG
H T
O F
W A
Y V
A
RI
ES
A
PP
RO
X.
R O
W
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
SF
S F
S F
PROPOSED TERMINATION CABINET
2 - 4" HDPE DR11 CONDUIT
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
355 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
264 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
LP
LP
LP
LP
LP
LP
x x x x x x x
O E
O E x
OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE
OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE x x x x x x x x x x x x
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
337 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
S F
SF
S F S
F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
281 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
LP
EL
EC
TR
IC
AL
C
O N
D U
IT
R
O U
TI
N
G
PL
AN
C301
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
M A
TC
H
LI
N
E S
E E
S H
E E
T C
NOTES:
1. CONTRACTOR SHALL REPAIR ALL
CURB, GUTTER, AND ASPHALT
DAMAGED OR REMOVED DURING
CONSTRUCTION.
2. 42" MINIMUM COVER BETWEEN
ELECTRICAL CONDUIT AND
EXISTING GRADE.
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
UG-E UG-E UG-E
SF
S F
S F
PROPOSED TERMINATION CABINET
382 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
UG-E
UG-E
UG-E
UG-E
UG-E
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
150 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
23.8'
.1'
26.0'
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
x x x x x x x x xx
O E
O E
O E
52545658
62646668
2 - 4" HDPE DR11 CONDUIT
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
460 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUITE UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
UG-E
UG-E
SF
S F
S F
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
PROPOSED TERMINATION CABINET
.6
48.9'
60.4'
EL
EC
TR
IC
AL
C
O N
D U
IT
R
O U
TI
N
G
PL
AN
C302
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
M A
TC
H
LI
N
E S
E E
S H
E E
T C
NOTES:
1. CONTRACTOR SHALL REPAIR ALL
CURB, GUTTER, AND ASPHALT
DAMAGED OR REMOVED DURING
CONSTRUCTION.
2. 42" MINIMUM COVER BETWEEN
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
U G
-E U
G
- E
U G
-E
UG-E U
SF
S F
S F
353 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
PROPOSED TERMINATION CABINET
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
2 - 4" HDPE DR11 CONDUIT
UG-E
UG-E
UG-E
UG-E
SF
S F
S F
AREA OF DIRECTIONAL BORE PIT.
SILT FENCE TO DEFINE LOD AREA = 375 SQFT
433 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
140 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
FT 00
AT 00
OE
OE OE OE OE OE OE OE
OE OE OE OE OE OE OE
W F
OE OE OE OE OE OE OE OE OE OE OE OE OE
OE OE OE OE OE OE OE OE OE OE OE OE OE
x x x x x x x x x x x x x x x x x
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
OE OE OE OE OE OE OE OE OE OE
G G
G
W W
W W
W W
W W
W W
W W
WW WW
W W
W W
W
W
A
PP
R O
X.
R
O W
A
PP
R O
X.
R
O W
W W
WW
W W
E UG-E UG-E UG-E UG-E UG-E UG-E
PROPOSED TERMINATION CABINET
SEE ELECTRICAL PLANS FOR DETAILS
277 LF OF PROPOSED
2 - 4" HDPE DR11 CONDUIT
.5'
.5
EL
EC
TR
IC
AL
C
O N
D U
IT
R
O U
TI
N
G
PL
AN
C303
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
N O
R
TH
GRAPHIC SCALE IN FEET
10 20 40
M A
TC
H
LI
N
E S
E E
S H
E E
T C
M A
TC
H
LI
N
E S
E E
B E
LO
W
M A
TC
H
LI
N
E S
E E
A B
O V
E
NOTES:
1. CONTRACTOR SHALL REPAIR ALL
CURB, GUTTER, AND ASPHALT
DAMAGED OR REMOVED DURING
CONSTRUCTION.
2. 42" MINIMUM COVER BETWEEN
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N
W W
W W
W W
W W
W W
F
PROPOSED TERMINATION CABINET
SEE ELECTRICAL PLANS FOR DETAILS
UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E UG-E
0+00 0+05 0+10 0+15 0+20 0+25 0+30 0+35 0+40 0+45 0+50 0+55 0+60 0+65 0+70 0+75 0+80 0+85 0+90 0+95 1+00 1+05 1+10 1+15
EXISTING GRADE
EXISTING 4" WATER
INVERT ELEV: 38.016'
EXISTING 8" GRAVITY SEWER
INVERT ELEV: 35.060'
2-4" HDPE
DR11 CONDUITS
LIMITS OF ORANGE AVENUE SEE ELECTRICAL PLANS
FOR CONTINUATION
0+05
.4
0+10
.5
0+15
.3
0+20
.4
0+25
.0
0+30
.1
0+35
.3
0+40
.5
0+45
.6
0+50
.7
0+55
.6
0+60
.6
0+65
.4
0+70
.3
0+75
.1
0+80
.1
0+85
.2
0+90
.5
0+95
.8
1+00
.0
1+05
.0
1+10
.0
EXISTING 4" WATER
INVERT ELEV: 36.606'
EXISTING 8" SANITARY SEWER
INVERT ELEV: 29.613'
EXISTING 12"x18" RCP
INVERT ELEV: 38.330'
EXISTING 18" FORCE MAIN
INVERT ELEV: 36.793'
EXISTING 30" FORCE MAIN
INVERT ELEV: 36.325'
PR
O
FI
LE
O F
C O
N D
U
IT
C400
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
N O
R
TH
GRAPHIC SCALE IN FEET
2.5 5 10
GRAPHIC SCALE IN FEET
HORIZONTAL
VERTICAL
2.5 5 10
31.3 5
C O
N
ST
R U
C
TI
O N
D
ET
AI
LS
C600
PS
R
ED
U
N D
AN
T
PO
W
ER
PR
EP
AR
ED
F
O R
C
IT
Y O
F
TA
LL
AH
AS
SE
E
PIPE TRENCH AND ASPHALT PATCH
N.T.S.
Notes:
1. CONDUITS MUST BE PLACED 4" FROM BOTTOM FRONT CABINET BASE.
2. 4" CONDUITS ARE PLACED NEAR THE CENTER OF THE CABINET. DO NOT "CROSS CONDUITS.
3. THE TOP OF THE CABINET BASE MUST BE SET BETWEEN 2" & 4" ABOVE FINAL GRADE AND
LOCATED AT A MIN. OF 12" FROM SIDEWALKS OR WALKING PATHS AND 24" FROM BACK OF
CURBS.
4. 1" GRD. ROD SLEEVE MUST BE INSTALLED DEEPER THAN THE OTHER CONDUITS.
5. SOIL MUST BE WELL COMPACTED UNDER THE CABINETS.
6. FOR CURB REPAIR, REFER TO FDOT STANDARD PLAN SPECIFICATION 520-001.
FT
FT
002 3/4" CONDUIT
1/P #16 SHLD
(PT002)
ZS
ZS
ZS
ZS
3/4" CONDUIT
(2)1/P #16 SHLD (FT002,PT002)
3/4" CONDUIT
3/C #14-POWER TO FT002 (120VAC)
12"x10"x8" ENCLOSURE
NEMA 4X STAINLESS STEEL
FOR FLOATS & LEVEL XMTR
NOTE 1
(4) 1 14" CONDUIT
PUMP MONITOR
CABLE EXTENSION
12/C #14
(1) 1 1/4" CONDUIT
(7) 1/P #16 SHLD
+3 1/P SHLD (SPARE)
(1) 1 1/4" CONDUIT
FLOAT CABLES
ZS CABLES
(1) 1 1/4" CONDUIT 120VAC
RECEPTACLE CKT. &
POWER CIRCUITS TO
FTOO1 AND FT002
(1) 1 14" CONDUIT SPARE
400AMP NON-FUSED
DISCONNECT
NEMA 4X STAINLESS STEEL
(SEE DETAIL ON SHEET 33)
24"x18"x8" NEMA 4x SS, HINGED
DOOR, WITH BACK PANEL.
INSTALL CONDUIT SEALS IN
CONDUITS ROUTED TO WET WELL.
INSTALL 20A SPEC GRADE
RECEPTACLE IN WP CAST BOX W/
LOCKABLE COVER ON PANEL
STRUCTURE (LEVITON IUM1V-KBG
OR EQUAL)
3/4"C 2-3/C#14
TC
1 14" CONDUIT
(3) 1/P #16 SHLD. (LEVEL XMTR)
& H2S MONITOR.
(2) HIGH LEVEL FLOAT SWITCH
CABLE
NOTE 2
BELOW GRADE PULL
BOX 24"x18x24" (OPEN
BOTTOM)
BELOW GRADE PULL
BOX 48"x48"x24" (OPEN
BOTTOM) TRAFFIC
RATED COVER
NOTE 4
GENERATOR
WITH SOUND ATTENUATING
ENCLOSURE AND SUB BASE
FUEL TANK
NOTE 5
POLE MOUNTED
FLOOD LIGHT RAB -
FFLED - 80
20' POLE (TYP. OF 4)
PT
PT
400AMP NON-FUSED
DISCONNECT
NEMA 4X STAINLESS STEEL
(SEE DETAIL ON SHEET 33)
2-4" CONDUITS (PENETRATE P/S LID)
2 VENDOR PUMP CABLES (ROUTED
TO PUMP VIA CABLE SUPPORTS)
2"C (PENETRATE P/SLID) FOR MOTOR
PILOT CABLE.
(TYPICAL OF 4).
4" CONDUIT 3 500 MCM XHHW 1 #2
GND IN EACH (TYP. OF 4 - FROM
PULL-BOX TO SWITCH).
(SEE DETAIL ON E-107 TYP.)
120VAC CIRCUIT TO
PANEL BOARD IN
CONTROL BUILDING
36" CABLE TRAY W/DIVIDER 24" POWER, 12"
INSTRUMENT AND CONTROLS) INTERIOR
CABLE TRAY AND PENETRATION THROUGH
BUILDING WALL SHALL BE BY BUILDING
SUPPLIER
(8)1 1/4 " CONDUIT
(1 SPARE)
1-2" CONDUIT
PUMP CONTROL / MONITOR PILOT
CABLE FROM PUMP TO
INSTRUMENT PANEL
(TYPICAL OF 4)
STUB-UP & CAP.
SPARE CONDUIT
AT FIRST SWITCH
WP
GFI
WP
GFI
NOTE 3
3/4" CONDUIT
(4)1/P #16 SHLD (FT001,FT002,PT001,
PT002)
3/4" CONDUIT
6/C #14-POWER TO FT001 AND FT002
(4) 4" CONDUITS
3 500 MCM XHHW
1 #2 GND IN EACH
(1) 4" CONDUIT SPARE W/ PULL
STRING
(1) 1 1/4" CONDUIT
NOTE 3
AT
4" CONDUIT
(1) 1/P #16 SHLD
(H2S XMTR)
H2S MONITOR
(NOTE 8)
GROUNDING
NOTE 10
SCADA POLE/ANTENNA.
NOTE 9
(5) 4" CONDUITS
4/C #500 kCM
PADMOUNT
TRANSFORMER
NO.1
PADMOUNT
TRANSFORMER
NO.2
2-4"
CONDUITS
FROM
PRIMARY
CIRCUIT NO.2
(SEE NOTE 2)
2-4"
CONDUITS
FROM
PRIMARY
CIRCUIT NO.1
JOB No.
DRAWN
DESIGNED
CHECKED
DATE
SHEET
SH
EE
T
PR
EP
AR
ED
B
Y of
PU
M
P
ST
A
TI
O N
A N
D
R
ED
U
N D
A N
T
PO
W
ER
S
YS
TE
M
PU
M
P
ST
A
TI
O N
A N
D
R
ED
U
N D
A N
T
PO
W
ER
EL
EC
TR
IC
A L
SI
TE
P
LA
N
1 3
AUG 2022
DK
JAL
JAL
PR
OJ
EC
T
EN
GI
NE
ER
O F
RE
CO
RD
1 2 3 4 5
FL
P
.E . N o.
Si gn atu re
Da te
DE
SC
RI
PT
IO
N
DA
TE
BY
UP
DA
TE
D
PE
R
PS
C
ON
ST
RU
CT
IO
N
4- 9-
R
A
JO
SE
PH
L
AN
E, P .E
RE
VI
SI
ON
S
Joseph A. Lane Digitally signed by Joseph A. Lane DN: C=US, E=jlane@nhwl.com, O="NHWL Engineering, Inc.", CN=Joseph A. Lane Reason: I attest to the accuracy and integrity of this document Date: 2025.04.09 08:51:23-04'00'
JOB No.
DRAWN
DESIGNED
CHECKED
DATE
SHEET
SH
EE
T
PR
EP
AR
ED
B
Y of
PU
M
P
ST
A
TI
O N an d
R
ED
U N
D A
N T
PO
W
ER
S
YS
TE
M
PU
M
P
ST
A
TI
O N
A N
D
O
R A
N G
E A
VE
N
U E
M C
C P
LA
N
A N
D R
IS
ER
D
IA
G R
A M
2 3
JAL
JAL
PR
OJ
EC
T
EN
GI
NE
ER
O F
RE
CO
RD
1 2 3 4 5
FL
P
.E . N o.
Si gn atu re
Da te
DE
SC
RI
PT
IO
N
DA
TE
BY
UP
DA
TE
D
PE
R
PS
C
ON
ST
RU
CT
IO
N
4- 9-
R
A
JO
SE
PH
L
AN
E, P .E
RE
VI
SI
ON
S
REVISED SUBMITTAL - APRIL 2025
Joseph A. Lane Digitally signed by Joseph A. Lane DN: C=US, E=jlane@nhwl.com, O="NHWL Engineering, Inc.", CN=Joseph A. Lane Reason: I attest to the accuracy and integrity of this document Date: 2025.04.09 08:50:38-04'00'
JOB No.
DRAWN
DESIGNED
CHECKED
DATE
SHEET
SH
EE
T
PR
EP
AR
ED
B
Y of
PU
M
P
ST
A
TI
O N
O
R A
N G
E A
VE
N
U E
Q U
A D
R U
PL
EX
L
IF
T
ST
A
TI
O N
PU
M
P
ST
A
TI
O N an d
R
ED
U N
D A
N T
PO
W
ER
EL
EC
TR
IC
A
L C
T/
PT
E N
C
LO
SU
R
ES
3 3
APR 2025
JAL
JAL
PR
OJ
EC
T
EN
GI
NE
ER
O F
RE
CO
RD
1 2 3 4 5
FL
P
.E . N o.
Si gn atu re
Da te
DE
SC
RI
PT
IO
N
DA
TE
BY
UP
DA
TE
D
PE
R
PS
2 C
ON
ST
RU
CT
IO
N 4-
9-
R A
RE
VI
SI
ON
S
EN
GI
NE
ER
O
F
RE
CO
RD
FL
P
.E . N o.
Si gn atu re
Da te
JO
SE
PH
L
AN
E, P .E
REVISED SUBMITTAL - APRIL 2025
Joseph A. Lane Digitally signed by Joseph A. Lane DN: C=US, E=jlane@nhwl.com, O="NHWL Engineering, Inc.", CN=Joseph A. Lane Reason: I attest to the accuracy and integrity of this document Date: 2025.04.09 08:49:38-04'00'
| _Revised Redundant Power Electrical Plan_ss.pdf |
| _E-01 Overall Plan - REVISED SUBMITTAL - S&S.pdf |
| _E-02 Riser Diagram - REVISED SUBMITTAL - S&S.pdf |
| _E-03 CT and PT Enclosures - REVISED SUBMITTAL - S&S.pdf |
File details come from the government source that posted it. Updated .