Mike Monroney Aeronautical Center (MMAC) Industrial Waste Water Treatment Plant Upgrades
Solicitation number
6973GH-27-R-00005
Issued by

About this file

This is a NESHAP Asbestos Survey Report prepared for the Federal Aviation Administration's Mike Monroney Aeronautical Center (MMAC) facility located at 6620 South Duke Avenue, Oklahoma City, Oklahoma 73159. The survey was conducted on December 16, 2025, by Leidos Corporation under the National Airspace System (NAS) Integration Support Contract (NISC) IV, with field work performed by certified asbestos inspector J. Hunter Henrie (Oklahoma Asbestos Inspector #401011). The inspection included a review of historical documents, visual inspection, and bulk sampling of suspect building materials to identify the presence, type, condition, and percentage of asbestos-containing building materials (ACBM).

The 1,821-square-foot building was constructed in 1992 with steel framework on concrete foundation, metal exterior siding, and metal roof, containing an office, small laboratory, and wastewater treatment area. During the inspection, 25 samples from 11 homogeneous areas were collected and analyzed using Polarized Light Microscopy (PLM) methodology by Pace Analytical and Green Country Testing laboratories. All samples tested negative for asbestos fibers with a reporting limit of 0.10 percent. The survey concluded that no building materials were identified as asbestos-containing via laboratory analysis or presumed to contain asbestos. The report includes appendices containing certifications of the qualified asbestos inspector, photographic documentation of the building exterior, detailed analytical results, and a sample location map with all negative sample identifications marked.

View the file

Other files

File Type Posted
Attachment 13 Key Personnel Experience Form 11.25.26.pdf PDF
QA Log 2 11.25.26.pdf PDF
Amend 0005 6973GH-27-R-00005.pdf PDF
Informational File 2 Asbestos Survey 190-CLS.pdf PDF
Informational File 4 Historic Plans-Information Purposes Only.pdf PDF
Attachment 10 Chapter 33 Construction Safety Rev 11.23.26.pdf PDF
QA Log 1 11.23.26.pdf PDF
Attachment 12 MMAC Delivery Truck Route Roads.pdf PDF
Amend 0004 6973GH-27-R-00005.pdf PDF
Informational File 3 Lead Based Paint Readings 186-IWT XRF.pdf PDF
Amend 0003 6973GH-27-R-00005.pdf PDF
Amend 0002 6973GH-27-R-00005.pdf PDF
Site Visit Attendance Log IWTP 27-R-00005.pdf PDF
Amend 0001 6973GH-27-R-00005.pdf PDF
Attachment 8 Contractor Release.pdf PDF
Attachment 3 SF25A Payment Bond.pdf PDF
Attachment 1b FAA MMAC IWTP_Specifications_IFC Volume II_2026 06 10.pdf PDF
6973GH-27-R-00005.pdf PDF
Attachment 6 Past Performance Experience Form 9.21.26.docx DOCX document
Attachment 1a FAA MMAC IWTP_Specifications_IFC Volume I Rev 2026 09 29.pdf PDF
Attachment 5 Past Performance Survey 9.21.26.docx DOCX document
Attachment 10 Chapter 33 Construction Safety.pdf PDF
Attachment 7 Client Authorization Letter.docx DOCX document
Attachment 11 Davis-Bacon Act WD-OK20260049.pdf PDF
Attachment 4 SF24 Bid Bond.pdf PDF
Attachment 1c FAA MMAC IWTP_Specifications_IFC Volume III_2026 06 10.pdf PDF
Attachment 2 SF25 Performance Bond.pdf PDF
Attachment 9 AMP400-ENV-OC-2.4.3-CC.pdf PDF
Attachment 1d 13289-007_MMAC IWTP Drawings.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NESHAP Asbestos Survey Mike Monroney Aeronautical Center (MMAC)

186-IWT Industrial Water Treatment Plant 6620 South Duke Avenue, Oklahoma City, Oklahoma 73159

Prepared For:

Federal Aviation Administration Mike Monroney Aeronautical Center

Environmental, Occupational, Safety and Health AMP100

December 24, 2025

Prepared By:

Leidos Corporation

NISC IV

6128 S.W. 68th Street, BMB Rm. 145

(405) 954-1185

Prepared By:

J. Hunter Henrie

Oklahoma Asbestos Inspector #401011

NESHAP Asbestos Survey Report Mike Monroney Aeronautical Center 186-IWT Industrial Water Treatment Plant

Introduction

At the request of the Mike Monroney Aeronautical Center (MMAC), Environmental Occupational Safety and Health department Leidos National Airspace System (NAS) Integration Support Contract (NISC) personnel conducted an Asbestos Survey on 12-16-25 at the Building # 186-IWT located at 6620 South Duke Avenue, Oklahoma City, Oklahoma 73159.

The initial field work was performed on December 16, 2025, by Leidos asbestos inspector J.

Hunter Henrie (Oklahoma Asbestos Inspector # 401011).

This Asbestos Inspection included a review of any historical documents available, a visual inspection, and bulk sampling (if necessary) of suspect building materials to determine the presence, type, condition, and percentage of asbestos containing building materials (ACBM).

The review of historical data included Google Earth™, Aerial photos of MMAC site, Archibus® and information provided by the Federal Aviation Administration (FAA) organization representative.

Facility Description

The building encompasses approximately 1,821 square feet (SF) and, according to Archibus®, was constructed in 1992. It is supported by a steel framework on a concrete foundation, with a metal exterior siding and a metal roof. The interior layout includes a single office, a small laboratory, and a wastewater treatment area which encompasses roughly half of the total building space.

Results & Recommendations

During the onsite visual and physical inspection of the structure, 25 samples from 11 homogeneous areas were identified and sampled. All the samples tested negative for asbestos fibers.

Subsequently, no building materials were identified as asbestos containing via laboratory analysis or are assumed to contain asbestos.

Appendix A

Certifications

Appendix B

Photographic Log

PHOTOGRAPHIC LOG: 186-IWT – Industrial Water Treatment Plant

West view of the building. (Photograph taken facing towards the east)

South view of the building. (Photograph taken facing towards the north)

East view of the building. (Photograph taken facing towards the west)

Appendix C

Analytical Results

Date Received: 12/17/2025

Project: Omega COCID 3101

Pace Set ID 500148

Analyzed By: Tanner Smith

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: N/A

Project Number: 2512277

Account Number: 69-000076

Received By: Baylie Puga

Date Analyzed: 12/23/2025

Pace

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Green Country Testing

6825 E. 38th St.

Tulsa, OK 74145

Non Fibrous

001 2512277-001A Homogeneous Glue

Paint

Asbestos Not Present NA

Caulk

Gray

002 2512277-002A Homogeneous GlueAsbestos Not Present NA

Caulk

Clear

003 2512277-003A Homogeneous Glue

Paint

Asbestos Not Present NA

Caulk

Gray

Date of Report

12/26/2025

Tanner Smith, Laboratory Analyst

Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis. Pace Analytical is a NVLAP accredited Testing PLM laboratory (Lab Code:

101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA—40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples; and EPA/600/R-93/116: Method for the Determination of Asbestos in Bulk

Building Materials. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory. If submitted samples are inhomogeneous in nature, then subsamples of the components will be analyzed separately. Samples determined to contain asbestos fibers, will have the following acceptable error ranges (1% = 0-3%, 5% = 1-9%, 10% = 5-15%, 20% = 10-30%, 50%

= 40-60%, etc.) as specified per EPA Method 600/R-93/116, Table 2-1.

December 29, 2025

Federal Aviation Administration

Vicki Ray

Dear Vicki Ray:

RE: 190-CLS

Order No.: 2512277

FAX

TEL:

6500 S MacArthur Blvd, MAP-100A

Oklahoma City, OK 73169

Green Country Testing, Inc.

6825 E 38th Street

Tulsa, OK 74145

Website: www.greencountrytesting.com

TEL: 918-828-9977 FAX: 918-828-7756

Susie Southwell

In accordance with your instructions, Green Country Testing conducted the analysis shown on the following pages on samples submitted by your company. The results relate only to the items tested. Unless otherwise noted, all analysis were conducted using EPA approved methodologies. Test reports meet all the NELAC requirements. All relevant sampling information is on the attached chain-of-custody form. The initials SUB as the analyst designate any testing sub-contracted by Green Country Testing.

Certifications/Accreditation: OK - 9953 ; 7604

A scope of Certified/Accredited parameters is available upon request. If you have any questions regarding these tests results, please feel free to call.

Sincerely, Green Country Testing, Inc. received 3 sample(s) on 12/16/2025 for the analyses presented in the following report.

Original

Project: 190-CLS

CLIENT: Federal Aviation Administration Lab Order: 2512277

12/29/2025

Analytical Report

2512277

Date Reported:

WO#:

(continuous)

Green Country Testing, Inc.

6825 E 38th Street

Tulsa, OK 74145

Website: www.greencountrytesting.com

TEL: 918-828-9977 FAX: 918-828-7756

Client Sample ID: 190-1216-CLK-01A Exterior Caulking-Louver Vent-E.Si

Lab ID: 2512277-001 Collection Date: 12/16/2025

Matrix: MISCELLANEOUS SOLID MA

Analyses Result Qual Units Date AnalyzedDFRL

ASBESTOS - N PLM Analyst: 8727

Asbestos 12/23/20250.10 % 1Asbestos Not Present

Client Sample ID: 190-1216-CLK-01B Exterior Caulking-Waste water pipe

Lab ID: 2512277-002 Collection Date: 12/16/2025

Matrix: MISCELLANEOUS SOLID MA

Analyses Result Qual Units Date AnalyzedDFRL

ASBESTOS - N PLM Analyst: 8727

Asbestos 12/23/20250.10 % 1Asbestos Not Present

Client Sample ID: 190-1216-CLK-01C Exterior Caulking-West Entrance D

Lab ID: 2512277-003 Collection Date: 12/16/2025

Matrix: MISCELLANEOUS SOLID MA

Analyses Result Qual Units Date AnalyzedDFRL

ASBESTOS - N PLM Analyst: 8727

Asbestos 12/23/20250.10 % 1Asbestos Not Present

Qualifiers:

Original

H Holding times for preparation or analysis exceeded M Manual Integration used to determine area response

ND Not Detected at the Reporting Limit PL Permit Limit

RL Reporting Detection Limit W Sample container temperature is out of limit as specified at testcode

Appendix D

ACM & Sample Location Map

Building 186-IWT Industrial Water Treatment Plant Known ACM Locations (None Identified)

*No asbestos containing materials were identified during the inspection.

= Positive Sample ID (No Positive Samples Present)

= Negative Sample ID

186-1216-XXXX-00A

186-1216-XXXX-00A

Sample Collection Date: 12/16/25 Green Country Testing Lab Order #: 2512277 All samples collected were non-detect

001-MMDD-MAT-00A

Building Number Identifier Month and Day of Collection

Building Material Description Identifier Homogeneous Area Number Identifier

Sample Identifier

186-1216-DWGB-01A

186-1216-DWGB-01B

186-1216-DWJC-02A

186-1216-DWJC-02B

186-1216-FT-06A

186-1216-FTM-07A

186-1216-CB-04B

186-1216-CBM-05B

186-1216-SAT-03A

186-1216-SAT-03B

186-1216-DM-10A

186-1216-DM-10B

186-1216-CLK-11A

186-1216-CLK-11B

186-1216-CB-04A

186-1216-CBM-05A

186-1216-FT-06B

186-1216-FTM-07B

186-1216-FT-08A

186-1216-FTM-09A186-1216-FT-08B

186-1216-FTM-09B

186-1216-CLK-12B

186-1216-CLK-12C

186-1216-CLK-12A

File details come from the government source that posted it. Updated .