Item 225 SH PLFY P NCMU E OCH410D Parts OCB410D 1.pdf
PDF 6 MB Posted
- Attached to
- TRAINING VESSEL FREEDOM STAR(TVFS) FY25 DRY DOCK
- Solicitation number
- 6933A225Q000001
About this file
This is a technical service manual and parts catalog for Mitsubishi Electric CITY MULTI Series ceiling cassette indoor units, specifically models PLFY-P08/12/15NCMU-E and their variants (E1, ER2, ER3, ER4). The manual covers detailed specifications, installation procedures, refrigerant system diagrams, wiring diagrams, troubleshooting guides, and maintenance procedures for these R410A/R22 split-type heat pump air conditioners.
The units feature a 22-7/16 inch slim profile designed for 2x2 ceiling installations, with cooling capacities ranging from 8,000-15,000 Btu/h and heating capacities from 9,000-17,000 Btu/h. Key components detailed include the indoor controller board, fan motor assemblies, drain pump systems, thermistors, and linear expansion valves. The document provides comprehensive parts lists with RoHS compliance information, detailed disassembly procedures with illustrations, and microprocessor control specifications for operations like cooling, heating, drying and fan modes. The manual includes precise electrical specifications, refrigerant system diagrams, and troubleshooting procedures for service technicians.
View the file
Other files
Show 40 more
Latest 50 of 71 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
INDOOR UNIT
CONTENTS
1. TECHNICAL CHANGES
2. FEATURES
3. PART NAMES AND FUNCTIONS
4. SPECIFICATIONS
5. 4-WAY AIR FLOW SYSTEM
6. OUTLINES AND DIMENSIONS
7. WIRING DIAGRAM
8. REFRIGERANT SYSTEM DIAGRAM
9. MICROPROCESSOR CONTROL
10. TROUBLESHOOTING
11. DISASSEMBLY PROCEDURE
R410A / R22
No. OCH410
REVISED EDITION-D
April 2012
NOTE:
• This manual describes only service data of the indoor units.
PARTS CATALOG (OCB410)
Revision:
• PLFY-P08/12/15NCMU-ER4.TH
have been added in
REVISED EDITION-D.
• Some descriptions have been modified.
• Please void OCH410
REVISED EDITION-C.
Model name indication
[Service Ref.]
PLFY-P08NCMU-E.TH
PLFY-P08NCMU-E1.TH
PLFY-P08NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH
PLFY-P12NCMU-E.TH
PLFY-P12NCMU-E1.TH
PLFY-P12NCMU-ER2.TH
PLFY-P12NCMU-ER3.TH
PLFY-P12NCMU-ER4.TH
PLFY-P15NCMU-E.TH
PLFY-P15NCMU-E1.TH
PLFY-P15NCMU-ER2.TH
PLFY-P15NCMU-ER3.TH
PLFY-P15NCMU-ER4.TH
Indoor unit [Model names]
PLFY-P08NCMU-E
PLFY-P12NCMU-E
PLFY-P15NCMU-E
1 TECHNICAL CHANGES
PLFY-P08NCMU-ER3.TH PLFY-P08NCMU-ER4.TH
PLFY-P12NCMU-ER3.TH PLFY-P12NCMU-ER4.TH
PLFY-P15NCMU-ER3.TH PLFY-P15NCMU-ER4.TH
• INDOOR CONTROLLER BOARD (I.B) has been changed. (S/W version up)
PLFY-P08NCMU-ER2.TH PLFY-P08NCMU-ER3.TH
PLFY-P12NCMU-ER2.TH PLFY-P12NCMU-ER3.TH
PLFY-P15NCMU-ER2.TH PLFY-P15NCMU-ER3.TH
• TURBO FAN and WASHER have been changed.
PLFY-P08NCMU-E1.TH PLFY-P08NCMU-ER2.TH
PLFY-P12NCMU-E1.TH PLFY-P12NCMU-ER2.TH
PLFY-P15NCMU-E1.TH PLFY-P15NCMU-ER2.TH
• The following functions of CONTROLLER BOARD (C.B) have been changed.
* Initial setting of auto restart function Not effective → effective (SW1-9 OFF → ON)
* External heating control change
PLFY-P08NCMU-E.TH PLFY-P08NCMU-E1.TH
PLFY-P12NCMU-E.TH PLFY-P12NCMU-E1.TH
PLFY-P15NCMU-E.TH PLFY-P15NCMU-E1.TH
• PANEL has been changed.
SLP-15AAU (White : 0.70Y 8.59/0.97) → SLP-15AAUW (Pure white : 6.4Y 8.9/0.4)
Use the specifi ed refrigerant only Never use any refrigerant other than that specifi ed.
Doing so may cause a burst, an explosion, or fi re when the unit is being used, serviced, or disposed of.
Correct refrigerant is specifi ed in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
OCH410D
2 FEATURES
1. PERFECT PANEL SIZE
The brand new 22-7/16 inch PLFY-P08/12/15NCMU-E models are slim, attractive, yet powerful units.
PLFY-P08/12/15NCMU-E’s size and shape, which perfectly match 2-by-2 ceilings, and its lighter weight of 34 lbs (PLFY-P08NCMU-E) make installation even easier and more convenient.
2. 29 dB WHISPER-QUIET OPERATION (PLFY-P08NCMU-E) Ideal for cafés, bars, restaurants, and shops. Give all your customers the comfortable environment they deserve.
3. 2,500 HOUR LONG LIFE FILTER
Greatly reduces the frequency the filter needs to be replaced, making maintenance all the easier.
4. FRESH AIR INTAKE
Provides indoor air of the highest quality.
5. SMUDGE-FREE AIRFLOW
Reduces annoying drafts and smudging.
6. SLIM UNIT BODY FOR EASY INSTALLATION
The 22-7/16 inch slim body and octagonal shape, which make the distance between bolts only 16-17/32 inch, help installa-tion easy and maintenance trouble-free.
Models Cooling capacity / Heating capacity PLFY-P08NCMU-E 8,000 / 9,000 Btu/h PLFY-P12NCMU-E 12,000 / 13,500 Btu/h PLFY-P15NCMU-E 15,000 / 17,000 Btu/h
Indoor Unit
Ceiling surface
9- 1/
8- 3/
Unit 22-7/16
T-bar
20-7/8
-1
7/
-7
/1 6Suspension bolt pitch
22-11/16 23-5/8
Unit : inch
Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Grille
Filter Removes dust and pollutants from return air.
Horizontal Air Outlet Sets horizontal airflow automatically during cooling or dehumidifying.
Air Intake Returns air from room.
3 PART NAMES AND FUNCTIONS
Indoor (Main) Unit
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
Temperature setting buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the cover
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilation button ( Operation button)
To go to next operation numberBuilt-in temperature sensor
Wired remote controller Once the controllers are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Note:
The phrase "Wired remote controller" in this manual refers only to the PAR-21MAA.
If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are included in remote controller's box.
Wired remote controller
°F°C °F°C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator Indicates that operation from the remote controller has been prohib-ited by a master controller.
“Timer is Off” indicator Indicates that the timer is off.
Temperature Setting Shows the target temperature.
Day-of-Week Shows the current day of the week.
Time/Timer Display Shows the current time, unless the simple or Auto Off timer is set.
If the simple or Auto Off timer is set, the time to be switched off is shown.
“Sensor” indication Displays when the remote controller sensor is used.
“Locked” indicator Indicates that remote controller but-tons have been locked.
“Clean The Filter” indicator To be displayed on when it is time to clean the filter.
Timer indicators The indicator comes on if the corre-sponding timer is set.
Up/Down Air Direction indica-tor Shows the direction of the outcoming airflow.
“One Hour Only” indicator
Room Temperature display Shows the room temperature. The room temperature display range is 46~102°F.
The display blinks if the temperature is less than 46°F or 102°F or more.
Louver display Indicates the action of the swing louver.
Does not appear if the louver is not running.
(Power On indicator) Indicates that the power is on.
Fan Speed indicator Shows the selected fan speed.
Ventilation indicator Appears when the unit is running in Ventilation mode.
Displays if the airflow is set to low or downward during COOL or DRY mode. (Operation varies according to model.)
The indicator goes off in one hour, when the airflow direction also changes.
4 SPECIFICATIONS
4-1. SPECIFICATIONS
Note 1. Rating conditions Cooling : Indoor : D.B. 80°F W.B. 67°F outdoor : D.B. 95°F W.B. 75°F Heating : Indoor : D.B. 70°F outdoor : D.B. 47°F W.B. 43°F Note 2. The number indicated in < > is for the grille.
W 3. Air flow and the noise level are indicated as Low - Medium - High.
Item
Btu/h
Btu/h kW kW
A
A in in in
CFM
CFM
Pa kW in in in dB lb
Cooling capacity
Power
Heat exchanger
Insulator
Air filter
Fan × No.
Pipe dimensions
Field drain pipe size
Noise level 3
Product weight
Exterior (munsell symbol)
Fan motor output
External static pressure
Liquid side
Gas side
Heating capacity
Dimensions
Height
Width
Depth
El ec tric ch ar ac ter ist ic
Input Cooling
Heating
Cooling
Heating Current
PLFY-P08NCMU-E.TH
PLFY-P08NCMU-E1.TH
PLFY-P08NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH
8,000
9,000
0.05
0.05
0.23
0.23
280-320-350
250-290-320
0.015
29-32-38
34<7>
15,000
17,000
0.06
0.06
0.28
0.28
31-35-40
12,000
13,500
0.06
0.06
0.28
0.28
30-34-39
Single phase 208/230V 60HzV·Hz
Air flow
DRY
WET
Unit : Galvanized sheets with gray heat insulation
Grilles : ABS resin Munsell<0.7Y 8.59/0.97>(PLFY-P·NCMU-E.TH) / <6.4Y 8.9/0.4>(PLFY-P·NCMU-E1/ER2/ER3/ER4.TH)
22-7/16<25-19/32>
22-7/16<25-19/32>
Cross fin
Turbo fan × 1
Polyethylene sheet
PP honey comb fabric
1/2"
1/4"
O.D1-1/4"
8-3/16<25/32>
320-350-390
290-320-350
0.020
37<7>
F a n
PLFY-P12NCMU-E.TH
PLFY-P12NCMU-E1.TH
PLFY-P12NCMU-ER2.TH
PLFY-P12NCMU-ER3.TH
PLFY-P12NCMU-ER4.TH
PLFY-P15NCMU-E.TH
PLFY-P15NCMU-E1.TH
PLFY-P15NCMU-ER2.TH
PLFY-P15NCMU-ER3.TH
PLFY-P15NCMU-ER4.TH
UNIT
5ft
MICROPHONE
CEILING
4-2. NOISE CRITERION CURVES
63 125 250 500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
O C
TA
VE
B A
N D
S O
U N
D P
R
ES
SU
R
E
LE
VE
L, d B
(0 d
B
.0 μb ar
BAND CENTER FREQUENCIES, Hz
High Medium
SPL(dB)
LINENOTCH
Low 30
PLFY-P12NCMU-E.TH
PLFY-P12NCMU-E1.TH
PLFY-P12NCMU-ER2.TH
PLFY-P12NCMU-ER3.TH
PLFY-P12NCMU-ER4.TH
63 125 250 500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
O C
TA
VE
B A
N D
S O
U N
D P
R
ES
SU
R
E
LE
VE
L, d B
(0 d
B
.0 μb ar
BAND CENTER FREQUENCIES, Hz
High Medium
SPL(dB)
LINENOTCH
Low 31
PLFY-P15NCMU-E.TH
PLFY-P15NCMU-E1.TH
PLFY-P15NCMU-ER2.TH
PLFY-P15NCMU-ER3.TH
PLFY-P15NCMU-ER4.TH
63 125 250 500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
O C
TA
VE
B A
N D
S O
U N
D P
R
ES
SU
R
E
LE
VE
L, d B
(0 d
B
.0 μb ar
BAND CENTER FREQUENCIES, Hz
PLFY-P08NCMU-E.TH
PLFY-P08NCMU-E1.TH
PLFY-P08NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH
High Medium
SPL(dB)
LINENOTCH
Low 29
NOTE: The sound level is measured in an anechoic room where echoes are few, when compres-sor stops. The sound may be bigger than the indicated level in actual use due to surround-ing echoes. The sound level can be higher by about 2 dB than the indicated level during cool-ing and heating operation.
4-3. ELECTRICAL PARTS SPECIFICATIONS
Parts name
Service ref.
Symbol
TH21
TH22
TH23
FUSE
MF
C1
MV
DP
DS
LEV
H2
TB2
TB5
TB15
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
250V 6.3A
PLFY-P08NCMU-E.TH
PLFY-P08NCMU-E1.TH
PLFY-P08NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH
PLFY-P12NCMU-E.TH
PLFY-P12NCMU-E1.TH
PLFY-P12NCMU-ER2.TH
PLFY-P12NCMU-ER3.TH
PLFY-P12NCMU-ER4.TH
PLFY-P15NCMU-E.TH
PLFY-P15NCMU-E1.TH
PLFY-P15NCMU-ER2.TH
PLFY-P15NCMU-ER3.TH
PLFY-P15NCMU-ER4.TH
Thermistor (Room temperature detection) Thermistor (Pipe temperature detection/ Liquid) Thermistor (Pipe temperature detection/ Gas) Fuse (Indoor controller board)
Fan motor (with Thermal fuse)
Electric heater (Condensation proof)
Power supply terminal block
Transmission terminal block
MA remote controller terminal block
6-pole OUTPUT 15W
PK6N15-LA
6-pole OUTPUT 20W
PK6N21-LA
6-pole OUTPUT 20W
PK6N20-LA
Fan motor capacitor
Vane motor
Drain pump
Drain sensor
Linear expansion valve [coil]
Note: Refer to WIRING DIAGRAM for the supplied voltage.
Thermal fuse OFF 284 F 36 F
1.5 × 440V
MSBPC20M13
DC12V 300 /phase
PLD-12230ME-1
INPUT 12/10.8W 24 /Hr
Thermistor resistance 30 F/6.3k , 50 F/3.9k , 70 F/2.5k , 80 F/2.0k , 90 F/1.6k , 100 F/1.3k
DC12V Stepping motor drive, Port dimension 3.2 (0~2000pulse)
EDM-40YGME
240V 15W
(L1, L2,GR) Rated to 330V 30A
(M1, M2, S) Rated to 250V 20A
(1, 2) Rated to 250V 10A
5 4-WAY AIR FLOW SYSTEM
5-3. OPERATION IN CONJUNCTION
WITH DUCT FAN (BOOSTER FAN)
• Whenever the indoor unit is operating, the duct fun also operates.
(1) Connect the optional multiple remote controller adapter (PAC-SA88HA-E) to the connector CN51 on the indoor controller board.
(2) Drive the relay after connecting the 12V DC relay between the Yellow and Orange connector wires.
(*) Use a relay of 1W or smaller.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (For DC 12V, coil rating : 1.0W or below)
5-1. FRESH AIR INTAKE (Location for installation) At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Refrigerant pipe Drain pipeElectrical Box
Fresh air intake Fresh air intake hole diagram (Unit : inch)
3 - 1/8 Burring hole
3-15/16 Burring hole pitch
2-7/8 (Cut out hole)
Ceiling surface
4-
/3
Static pressure : P [in. W.G. 10-2] Air flow : Q [CFM]20
-20
-40
-60
-80
-100
-120
0 20 40 60 80 100 120
PLFY-P08/12/15NCMU-E.TH PLFY-P08/12/15NCMU-E1.TH
PLFY-P08/12/15NCMU-ER2.TH PLFY-P08/12/15NCMU-ER3.TH
PLFY-P08/12/15NCMU-ER4.TH
Taking air into the unit
5-2. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
Q
B
A C
1 Curve in the left graphs
Duct characteristics at site
Q
A E
C
Q Qa
A D
NOTE: Fresh air intake amount should be 20% or less of whole air amount to prevent dew dripping.
CN51
Multiple remote controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor controller board and relay must be within 33ft.
Be sure to secure insulation material by tape, etc.
5 Green
Yellow Orange
Connector (5P)
Indoor unit side Multiple remote controller adapter
PAC-SA88HA-E
Be sure to secure insulation material by tape, etc.
Installation at site
CN51
on indoor unit board
Red Brown
CN51
MB
How to read curves
Q…Designed amount of fresh air intake
<CFM>
A…Static pressure loss of fresh air intake duct system with air flow amount Q <in. W.G.o10-2>
B…Forced static pressure at air condi-tioner inlet with air flow amount Q
<in. W.G.o10-2> C…Static pressure of booster fan with air flow amount Q <in. W.G.o10-2> D…Static pressure loss increase amount of fresh air intake duct sys-tem for air flow amount Q
<in. W.G.o10-2> E…Static pressure of indoor unit with air flow amount Q <in. W.G.o10-2> Qa…Estimated amount of fresh air intake without D <CFM>
5-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure below.
Insulate the disconnected connector with the plastic tape.
Vane motor
Horizontal vane
Connector Unlocking button
Vane motor
3) Set a vertical vane of the air outlet, which is to be fixed by the hand slowly within the range in the table below.
Measured standard position of the grille
Horizontal vane
< Specified range > Up/down airflow direction Horizontal 30° Downward 45° Downward 55° Downward 70°
A 21 mm 13/16 inch
25 mm 31/32 inch
28 mm 1-3/32 inch
30 mm 1-3/16 inch
· The vanes can be set between 21mm, 13/16 inch and 30 mm, 1-3/16 inch.
Caution:
Do not set the up/down vanes passed the specified range. Condensation could form and drop from the ceiling, or the unit could malfunction.
OUTLINES AND DIMENSIONS6
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
Detail drawing of fresh air intake
Ceiling surface
Cut out hole 2-7/8( 73.4)
Burring hole 3- 1/8( 2.8)
3-15/16( 100)
4-
/3 2(
8)
1(25)
+5 0 (2
+3
/1
1- 1/
16 Unit : inch(mm)
19/32~1-15/32(15~37) 19/32~1-15/32(15~37)22-11/16~24-13/32(576~620)
22-7/16(570)
20-7/8(530)
Grille
Fresh air intake
Drain pipe VP-25 connection (O.D. 1-1/4( 32))
Vane motor
Drain hole
Models
Air intake grille
2- 5/
(5
5) 1-
3/ 8(
1-3/8(35) 2-5/32(55)
Auto vane
Grille
Air intake hole
A ir in ta ke h ol e
A ir ou tle t h ol e
Air outlet hole 11-27/32(301)
-2
7/
(3
-2
7/
(3
14-27/32(377)
-1
9/
(6
Suspension bolt M10 or W3/8
Suspension bolt lower edge
9-1/16(230)
7- 5/
(1
1- 7/
8(
Wiring entry
Terminal block Ceiling surface
9- 1/
4(
5) 8-
3/
(2
7-
/3
2(
3)
/3
2(
3-
/3 2(
1- 1/
2~ 2-
9/
(3 8~
2-
/3 2(
4- 3/
4(
1)
21/32(17) 7-15/16(202)
2- 7/
(5
6)
2- 1/
4(
) 3-7 /16
(87 )1-
7/
(3 1)
C ei lin g ho le
S us pe ns io n bo lt pi tc h
/3
2~ 1-
/3
2(
~3 7)
/3
2~ 1-
/3
2(
~3 7)
-1
1/
~2 4-
/3
2(
6~
0)
-1
7/
(4
-7
/1 6(
0)
-3
/1 6(
5)
7-27/32(199)
13-27/32(352) 13-3/16(335)
Suspension bolt pitch
Ceiling hole
25-19/32(650)
PLFY-P08/12/15NCMU-E.TH
PLFY-P08/12/15NCMU-E1.TH
PLFY-P08/12/15NCMU-ER2.TH
PLFY-P08/12/15NCMU-ER3.TH
PLFY-P08/12/15NCMU-ER4.TH
Brand label
Refrigerant pipe (1/2 (12.7) dia.)
flared connection
Refrigerant pipe (1/4 (6.35) dia.)
flared connection
V/M
V/M
V/M
V/M
Unit : inch(mm)
WIRING DIAGRAM7
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
DP
WHT
(DRAIN)
WHT
FAN
(FAN)
See Fig.1
MODELS
P08
P12
P15
<Fig.1>
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
SW2
Power supply for MA-Remote controller on → Lamp is lit.
Main power supply(Indoor unit:208-230V) power on → Lamp is lit.Main power supply
Power supply for MA-Remote controllerLED2
LED1
Mark Meaning LED on indoor controller board for service
Function
CN32
(REM
OTE SW
ITCH)
W
HT
DC24-30V
CONTROLLER
TO NEXT INDOOR UNIT
PULL BOX
FUSE(15A)
BREAKER
(15A)
60Hz
HA
WHT
CN41 CN51
WHT
(CENTRALLY
CONTROL)
5 4 3 2 1
CN52
(REMOTE
INDICATION)
GRN
12345
REMOTE SWITCHCN32
X7 FAN MOTOR (Me) X6 FAN MOTOR (Hi) X5 FAN MOTOR (Lo)
SW1 SWITCH MODE SELECTION
CONNECTION No.SW14
SW12
SW11 ADDRESS SETTING 1ST DIGIT
ADDRESS SETTING 2ND DIGIT
MODEL SELECTION
MODE SELECTION
CAPACITY CODE
SW4
SW3
SW2
(32 F/15kΩ 77 F/5.4kΩ)
(32 F/15kΩ 77 F/5.4kΩ)
DP DRAIN PUMP
DS DRAIN SENSOR
H2 DEW PREVENTION HEATER
FAN MOTOR (LL)
DRAIN PUMP/DEW PREVENTION HEATERX1 AUX. RELAY
SYMBOL NAME
VARISTOR
INDOOR POWER BOARDP.B
ZNR
X4
I.B
CN41
CN51
CN52
FUSE FUSE (6.3A/250V)
REMOTE INDICATION
CENTRALLY CONTROL
HA TERMINAL-A
CONNECTOR
INDOOR CONTROLLER BOARD
[LEGEND]
NAMESYMBOL
PIPE TEMPERATURE DETECTION/GASTH23
TRANSMISSION
TERMINAL
BLOCK
POWER SUPPLY
TB5
TB15
TB2
(32 F/15kΩ 77 F/5.4kΩ)
THERMISTOR ROOM TEMPERATURE DETECTION
TH22
TH21
LEV LINEAR EXPANSION VALVE
MV
MF
VANE MOTOR
FAN MOTOR (WITH THERMAL FUSE)
CAPACITOR (FAN MOTOR)C1
PIPE TEMPERATURE DETECTION/LIQUID
MA-REMOTE CONTROLLER
LED2
LED1
31 1 3
CND
(POWER)
YLW
YLW
1 3
BLU
(D•U•M)
CNC
(D•HEATER)
RED ORN
FUSE
ZNR
CNP
X1
RED
ORN
GRILLE
BL
U
WHT
BLU
RED
ORN
YLW
RED
RED
C1
1 5
BL
K
YLW W
HTBR
N
7 9
X6 X5 X4 X7
X4 X7X5X6
MF
I.B
CN20
CN31
BL
U
WH
T
OR
N
RE
D
YLW 6
6 5 4 3 2 1
(VANE)
CN6V
GRN
RE
D
OR
N
BL
U
6 5 4 3 2 1
(LEV)
CN60
WHT
WH
T
YLWBR
N
BLK
2 2 11
(LIQUID)(INTAKE)
CN21
RED WHT
2 1
(GAS)
CN29
(R
EM
OC
ON
W
HT
RE
D
P.B
RED
CNDK
(POWER
BORD)
AC208-230V
CNSK(RED)
TB2 L1
L2
GR
RED
BLU
GRN/YLW
~/N 208-230V
POWER SUPPLY
TRANS DC13.1V
CN2S(WHT)
(P
OW
ER
B
O
RD
CN
2D
W
HT WHT
BLK
M1
2 CONTROLLER
DC8.7-13V
TO MA-REMOTE
CN
2M
(M -N
ET
) 1
CN
3A
BL
U
BL
U
M2
TB15
S(SHIELD)
M-NET REMOTE
TO OUTDOOR UNIT
BC CONTROLLERTB5
X1
TH23TH22TH21DS
LEV
3RD
DIGIT
O
0N
0FF
SW1
1 2 3 4 5 6 7 8 9 10
SW12 SW11
1ST
DIGIT
2ND
DIGIT
SW14
CONNECTION
No.
1 2 3 4 5
0FF
0N
SW4SW2
654321 10987654321
0FF
0N
SW3
MV
H2
MV
MV
MV
Notes:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmisson wire is non-polar.)
4. Symbol[S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, :terminal block, :connecter.
6. The setting of the SW2 dip switch differs in the capacity. For the detail, refer to Fig.1.
7. Use copper supply wire.
The black square (■) indicates a switch position.
(RED)
(RED)
MODELS
P08
P12
P15
<Fig.1>
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
SW2
Power supply for MA-Remote controller on → Lamp is lit.
Main power supply(Indoor unit:208-230V) power on → Lamp is lit.Main power supply
Power supply for MA-Remote controller
LED2
(RED)
LED1
(RED)
Mark Meaning LED on indoor controller board for service
Function
Notes:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmisson wire is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, :connecter.
6. The setting of the SW2 dip switch differs in the capacity. For the detail, refer to Fig.1.
7. Use copper supply wire.
The black square (■) indicates a switch position.
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
SYMBOL NAME
I.B INDOOR CONTROLLER BOARD
CN32
CN41
CN51
CONNECTOR
REMOTE SWITCH
CN24 EXTERNAL HEATER
P.B INDOOR POWER BOARD
HA TERMINAL-A
CENTRALLY CONTROL
CN52 REMOTE INDICATION
X1 X4 X5 X6 X7
AUX.
RELAY
FUSE FUSE(T6.3AL 250V)
SYMBOL NAME
TH21
DS
THERMISTOR ROOM TEMP. DETECTION
(32°F/15k ,77°F/5.4k )
PIPE TEMP. DETECTION / LIQUID
(32°F/15k ,77°F/5.4k )
PIPE TEMP. DETECTION / GAS
(32°F/15k ,77°F/5.4k )
DRAIN PUMP(TEST MODE)
TH22
TH23
DRAIN SENSOR
H2 DEW PREVENTION HEATER
DRAIN PUMP/DEW PREVENTION HEATER
FAN MOTOR(LL)
FAN MOTOR(Lo) FAN MOTOR(Hi) FAN MOTOR(Me)
MF
MV
LEV LINEAR EXPANSION VALVE
FAN MOTOR(WITH THERMAL FUSE)
VANE MOTOR
TB2
TB5
TB15
TRANSMISSION
MA-REMOTE CONTROLLER
TERMINAL
BLOCK
POWER SUPPLY
SW4
SW11
SW12
SW14
SWE
ADDRESS SETTING 1s DIGIT ADDRESS SETTING 10ths DIGIT BRANCH No.
SW1
SW2
SW3
CAPACITY CODE
MODE SELECTION
MODE SELECTION
MODEL SELECTION
SWITCH
<fig:*1>
MODELS SW2
P08 123456
ON
OFF
P12 123456
ON
OFF
P15 123456
ON
OFF
Notes:
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S]of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are, : terminal block, : connecter.
6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to the fig:*1.
7.Use copper supply wire.
DP
C1 CAPACITOR(FAN MOTOR)
DRAIN PUMP
Mark Meaning Function
Power supply for MA-Remote controller
Main power supply (Indoor unit) Power on → Iamp is lit
LED on indoor board for service
Main power supply
Power supply for MA-Remote controller on → Iamp is lit
LED1
(RED)
LED2
(RED)
1 3 5 7 9
5 14 1 6 19 1
L1 L2
GR
LED1
(RED)
LED2
(RED)
FAN
(WHT) 1 131 31 3
1 3
CNP
(BLU)
1 2345
SW3
SW2
ON
OFF
ON
OFF
SW4
ON
OFF
12345678910
SW1
12345678910
M 1~M
1~
RED
RE
D
ORN
BL
U
YL
W
YL
W
YL
W
BL
K
W
HT
W
HT
BR
N
MF DP
BLU
TB2
RED
GRN/YLW
P.B
I.B
GRILLE PULL
BOX
FUSE
(16A)
BREAKER
(16A)
TO NEXT
INDOOR
UNIT
POWER SUPPLY
208-230V 60Hz
CNSK
(RED)
CNDK
(RED)
CND
(ORN)
C1
CNC
(RED)
CN3A
(BLU)
CN2M
(BLU)
See fig:*1
TB5
M1 M2
TB15
S
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TO OUTDOOR UNIT
BC CONTROLLER
M-NET REMOTE
CONTROLLER
DC24-30V
DC13.1V
CN2S
(WHT)
CN2D
(WHT)
CN24
(YLW)
TRANS
CN32
(WHT)
1 CN31
(WHT)CN41
(WHT)
CN51
(WHT)
CN60
(WHT)
CN90
(WHT)
3 1
FUSE
WHT
BLK
TH23
TH22
TH21DS
6 1
CN6V
(GRN)
5 1
CN52
(GRN) 0 1
SW12
0 1
SW11SW14
10ths
DIGIT
1s
DIGIT
BRANCH
No.
M
LEV
RE
D
YL
W
W
HT
O
RN
BL
U
BR
N
M
MV RED
RED
RED
YLW
H2
WHT
ORN
BLU
5M
MV
5 6
5M
MV
5M
MV
CN20
(RED)
CN21
(WHT)
CN29
(BLK)
X7X4 X1X5X6
0 1234
6789AB
C
D E F
SWE
OFF ON
LEGEND
t° t° t° t°
The black square (■) indicates a switch position.
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
REFRIGERANT SYSTEM DIAGRAM8
Strainer (#50mesh)
Strainer (#100 mesh)
Strainer1 (#50 mesh) Strainer2 (#100 mesh)
Heat exchanger
Room temperature thermistor TH21
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Liquid pipe
Flare connection
Gas pipe
Liquid pipe
1/2
1/4
Refrigerant flow in cooling Refrigerant flow in heating
Unit : inch
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
MICROPROCESSOR CONTROL9
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ûFûC °F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
INDOOR UNIT CONTROL
9-1. COOL OPERATION
Control modes Control details
1-1. Thermostat function (Function to prevent restarting for 3 minutes)
• Room temperature desired temperature + 2°F ···Thermo ON
• Room temperature desired temperature ···Thermo OFF
1-2. Anti-freezing control Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16 minutes from compressor's start up, anti-freezing control starts and the thermo OFF.
Released condition : The timer which prevents reactivating is set for 3 minutes, and anti-freezing control is cancelled when any one of the following conditions is satisfied.
Liquid pipe temp. (TH22) turns 50°F or above.
The condition of the thermo OFF has completed by thermostat, etc.
The operation modes became mode other than COOL.
The operation stopped.
By the remote controller setting (switch of 3 speeds)2. Fan
1. Thermostat function
Remarks
Type Fan speed notch
[Low], [Med], [High]3 speeds type
Continued to the next page
<How to operate> 1 Press POWER ON/OFF button.
2 Press the operation MODE button to display COOL.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°F(2°F) when the or button is pressed once. Cooling 67 to 87°F
Variable range of the set temperature depends on the remote control-ler which is applied.
1→
Control modes Control details
3-1. Drain pump control
• Always drain pump ON during the COOL and DRY mode operation.
(Regardless of the thermo ON/ OFF)
• When the operation mode has changed from the COOL or DRY to the others (including Stop), OFF the control after the drain pump ON for 3 minutes.
Drain sensor function
• Energize drain sensor at a fixed voltage for a fixed duration. After energizing, compare the drain sensor’s temperature to the one before energizing, and judge whether the sensor is in the air or in the water.
Basic control system
• While drain pump is turned on, repeat the following control system and judge whether the sensor is in the air or in the water.
• Drain sensor temperature rise (∆t)
• Temperature of drain sensor before current is applied (T0)
• Temperature of drain sensor after current is applied (T1)
[ ∆t = T1 – T0 ]
(1) Initial setting : Start at COOL mode and horizontal vane.
(2) Vane position : Horizontal →Downward A →Downward B →Downward C→Swing
(3) Restriction of the downward vane setting When setting the downward vane A, B or C in [Med] or [Low] of the fan speed notch, the vane changes to horizontal position after 1 hour.
4. Vane (up/down vane change)
3. Drain pump
Remarks
Drain sensor Indoor control P.C. board
CN31
"Only 1 Hr" appears on the wired remote controller.
Timing of energizing drain sensor
ON
OFF
Stand by for a minute sec.
sec.
Detect the temperature before energizing (T0)
Detect the temperature after energizing (T1)
Judge whether the sensor is in the air or in the water.
Stand by for a minute
·······Repeat
From the preceding page
Control modes Control details
1-1. Thermostat function (Function to prevent restarting for 3 minutes) Setting the Dry thermo by the thermostat signal and the room temperature (TH21).
Dry thermo ON Room temperature desired temperature + 2°F Dry thermo OFF Room temperature desired temperature
1-2. Freeze prevention control No control function
Indoor fan operation controll depends on the compressor conditions.
3. Drain pump
1. Thermostat function
Remarks
Room temperature
3 min. passed since starting operation
Thermostat signal Room temperature (T1)
Dry thermo
ON
time (min)
Dry thermo
OFF
time (min)
Less than 64°F
Over 64°F
ON
OFF
T1 83°F 83°F > T1 79°F 79°F > T1 75°F 75°F > T1
Unconditional
9 3 7 3 5 3 3 3
Dry thermo OFF
2. Fan
Note: Remote controller setting is not acceptable.
Dry thermo Fan speed notch
ON
OFF
[Low]
Stop
4. Vane (up/down vane change)
Same control as COOL operation
Same control as COOL operation
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ûFûC °F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
9-2. DRY OPERATION
<How to operate> 1 Press POWER ON/OFF button.
2 Press the operation MODE button to display DRY.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°F(2°F) when the or button is pressed once. Dry 67 to 87°F
Variable range of the set temperature depends on the remote control-ler which is applied.
Set by remote controller.
2. Drain pump
Remarks
1. Fan Type Fan speed notch
3 speeds type [Low], [Med], [High]
3. Vane (up/down vane change)
2-1. Drain pump control The drain pump turns ON for the specified amount of time when any of the following conditions is met:
ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
ON for 6 minutes after the drain sensor is determined to be submerged using the liquid level detection method given below.
ON for 6 minutes after indoor piping (liquid piping) temperature – indoor intake temperature -18°F, AND the drain sensor input is at the short or open level.
(If condition or is still being met after the drain pump has been turned ON for 6 minutes, the drain pump is kept ON for further 6 minutes.)
2-2. Liquid level detection method The liquid level is detected by determining whether or not the drain sensor is submerged, based on the amount the temperature rises after self-heating the sensor. This process is performed if any of the following conditions is met:
Drain pump is ON.
Indoor piping (liquid piping) temperature – indoor intake temperature -18°F Indoor piping (liquid piping) temperature or indoor intake temperature is at the short or open level temperature.
Every 1 hour after the drain pump has been switched from ON to OFF and 1 hour have passed.
Same as the control performed during the COOL operation, but no restriction on the vane's downward blow setting
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ûFûC °F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
9-3. FAN OPERATION
<How to operate> 1 Press POWER ON/OFF button.
2 Press the operation MODE button to display FAN.
1-1. Thermostat function (Function to prevent restarting for 3 minutes)
• Room temperature desired temperature -2°F ···Thermo ON
• Room temperature desired temperature ···Thermo OFF
1. Thermostat function
Remarks
Controlled by the remote controller (3-speed) Give priority to controlled mode mentioned below.
2-1. Hot adjust mode 2-2. Residual heat exclusion mode 2-3. Thermo OFF mode (When the compressor off by the thermostat) 2-4. Cool air prevention mode (Defrosting mode) 2-5. Capacity increasing mode
2-1. Hot adjust mode The fan controller becomes the hot adjust mode for the following conditions.
When starting the HEAT operation When the thermostat function changes from OFF to ON.
When release the HEAT defrosting operation
2. Fan
A: Hot adjust mode start B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more C: 2 minutes have passed since the condition A (Terminating the hot adjust mode)
A CB
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode 1
2-2. Residual heat exclusion mode When the condition changes the auxiliary heater ON to OFF (thermostat or operation stop, etc), the indoor fan operates in [Low] mode for 1 minute.
This control is same for the model without auxiliary heater.
"STAND BY" will be displayed during the hot adjust mode.
Continued to the next page
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ûFûC °F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
9-4. HEAT OPERATION
<How to operate> 1 Press POWER ON/OFF button.
2 Press the operation MODE button to display HEAT.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°F(2°F) when the or button is pressed once. Heating 63 to 83°F
Variable range of the set temperature depends on the remote controller which is applied.
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed during hot adjust mode.
Control modes Control details
2. Fan
Remarks
2-3. Thermo OFF mode When the thermostat function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode The indoor fan stops.
No drain pump operation However, when the control changes from COOL or DRY operation, the drain pump operates for 3 minutes.
(1) Initial setting : OFF → HEAT···[last setting] When changing the mode from exception of HEAT to HEAT operation ···[Downward C]
(2) Vane position :
Horizontal →Downward A →Downward B →Downward C→Swing
(3) Restriction of vane position The vane is horizontally fixed for the following modes.
(The setting by the remote controller is temporarily invalidated and vane control is set by the unit controller.)
• Thermo OFF
• Hot adjust [Extra low] mode
• Heat defrost mode
3. Drain pump
4. Vane control (Up/down vane change)
From the preceding page
1. Drain pump
Control modes Control details
HEAT mode for room temperature < Desired temperature COOL mode for room temperature Desired temperature
(1) HEAT mode → COOL mode Room temperature Desired temperature + 3°F or 3 minutes has passed
(2) COOL mode → HEAT mode Room temperature Desired temperature - 3°F or 3 minutes has passed
1. Initial value of operation mode
Remarks
2. Mode change
Same control as cool operation3. COOL mode
Same control as heat operation4. HEAT mode
Control modes Control details
1-1. Drain pump control The drain pump turns ON for the specified amount of time when any of the following conditions is met (regardless of whether the compressor is ON or OFF)
ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (HEAT mode).
ON for 6 minutes after the drain sensor is determined to be submerged using the liquid level detection method given below.
ON for 6 minutes after indoor piping (liquid piping) temperature – indoor intake temperature 14°F, and the drain sensor input is at the short or open level.
(If condition or is still being met after the drain pump has been turned ON for 6 minutes, the drain pump is kept ON for a further 6 minutes.)
1-2. Liquid level detection method The liquid level is detected by determining whether or not the drain sensor is submerged, based on the amount the temperature rises after self-heating the sensor.
This process is performed if any of the following conditions is met:
Drain pump is ON.
Indoor piping (liquid piping) temperature – indoor intake temperature 14°F
(except during defrosting) Indoor piping (liquid piping) temperature or indoor intake temperature is at the short or open level temperature.
Every 1 hour after the drain pump has been switched from ON to OFF.
Remarks
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ûFûC °F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
9-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
<How to operate> 1 Press POWER ON/OFF button.
2 Press the operation MODE button to display AUTO.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°F(2°F) when the or button is pressed once. Automatic 67 to 83°F
Variable range of the set temperature depends on the remote controller which is applied.
“AUTO” works to change the operation mode either to cooling or heat-ing according to the room temperature.
9-6. WHEN UNIT IS STOPPED CONTROL MODE
10 TROUBLESHOOTING
10-1. HOW TO CHECK THE PARTS
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
Parts name Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50 F~86 F)
Disconnect the connector then measure the resistance valve with a tester.
Measure the resistance between the terminals with a tester. (At the ambient temperature 68 F~86 F)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 68 F~86 F)
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(At the ambient temperature 32 F~140 F)
Vane motor (MV)
Linear expansion valve (LEV)
Drain pump (DP)
Drain sensor (DS)
Refer to the next page for the details.
Refer to the next page for the details.
Thermistor (TH21) (Room temperature detection) Thermistor (TH22) (Pipe temperature detection/ Liquid) Thermistor (TH23) (Pipe temperature detection/ Gas)
Yellow
Relay connector
Yellow
Normal 4.3k ~9.6k
Abnormal Open or short
Abnormal Open or short
Normal 0.6k ~6.0k
Abnormal
Open or short
Normal
200 10%
White-Red Yellow-Brown Orange-Red Blue-Brown
NormalConnector Abnormal
300 Open or short
Normal Abnormal 290 Open or short
OrangeRedWhite
Blue
Brown
Yellow
M
Orange Red
White Red — Yellow Red — Blue Red — Orange Red — WhiteBlue Yellow
Fan motor (MF)
M
Refer to the next page for the details.
BLK RED ORNYLWBLU BRN
WHT
P
Measure the resistance between the terminals with a tester. (Coil wiring temperature 50 F~86 F)
Normal
WHT-BLK
BLK-BLU
BLU-YLW
YLW-RED
RED-BRN
303 ~328 105 ~114 39 ~42
235 ~254
272 ~295 79 ~85 37 ~40
191 ~206
PLFY-P08NCMU-E
PLFY-P08NCMU-E1
PLFY-P08NCMU-ER2
PLFY-P08NCMU-ER3
PLFY-P08NCMU-ER4
387 ~418 77 ~83 19 ~21
179 ~193
Abnormal
Opened or short-circuited
: Thermal fuse 284°F±36 F
PLFY-P12NCMU-E
PLFY-P12NCMU-E1
PLFY-P12NCMU-ER2
PLFY-P12NCMU-ER3
PLFY-P12NCMU-ER4
PLFY-P15NCMU-E
PLFY-P15NCMU-E1
PLFY-P15NCMU-ER2
PLFY-P15NCMU-ER3
PLFY-P15NCMU-ER4
4 4
2 2
1 1
Controller board
Drive circuit
Connector (CN60)
DC12V
Brown
Red
Blue
Orange
Yellow
White
M
Blue
Brown
Yellow
OrangeRedWhite
Linear expansion valve
<Thermistor characteristic graph>
Room temperature thermistor(TH21) Liquid pipe temperature thermistor(TH22) Gas pipe temperature thermistor(TH23)
Thermistor R0=15k' ± 3% Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
30_F 15.8k' 50_F 9.6k' 70_F 6.0k' 80_F 4.8k' 90_F 3.9k' 100_F 3.2k'
Thermistor R0=6.0k' ±5% Fixed number of B=3390 ± 2%
Rt=6exp { 3390( ) }
30_F 6.3k' 50_F 3.9k' 70_F 2.5k' 80_F 2.0k' 90_F 1.6k' 100_F 1.3k'
Thermistor for lower temperature
Linear expansion valve 1 Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
273+(t-32)/1.8
273+(t-32)/1.8
Thermistor for drain sensor
0-20 20 40 60 80 100 120
< Thermistor for lower temperature >
Temperature (°F)
R es is ta nc e
(k
20 40 60 80 100 120 140 170
< Thermistor for drain sensor >
Temperature (°F)
R es is ta nc e
(k
Output (Phase)
Output
{1
ON
{2 ON
{3 OFF
{4 OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
<Output pulse signal and the valve operation>
2 Linear expansion valve operation
3 Troubleshooting
D
A
E
B
C
Open
Extra tightening (80~100pulse)
Pulse number
2000 pulse Opening a valve all the way
Close
Va lv e po si tio n (c ap ac ity
LED1k
Symptom Check points
Operation circuit failure of the micro processor
Disconnect the connector on the controller board, then con-nect LED for checking.
Pulse signal will be sent out for 10 seconds as soon as the main switch is turned on. If there is LED with lights on or lights off, it means the operation circuit is abnormal.
Countermeasures
Exchange the indoor con-troller board at drive circuit failure.
Linear expansion valve mechanism is locked.
Valve does not close completely (thermis-tor leaking).
Wrong connection of the connector or contact failure
To check the linear expansion valve, operate the indoor unit in fan mode and at the same time operate other indoor units in cooling mode, then check the pipe temperature <liquid pipe temperature> of the indoor unit by the out-door multi controller board operation moni-tor. During fan operation, linear expansion valve is closed completely and if there are some leaking, detecting temperature of the thermistor will go lower. If the detected temperature is much lower than the tem-perature indicated in the remote controller, it means the valve is not closed all the way. It is not necessary to exchange the linear expansion valve, if the leakage is small and not making any trouble.
Thermistor (Liquid pipe)
Linear expansion valve
Motor will idle and make ticking noise when motor is operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality.
Check the color of lead wire and missing terminal of the con-nector.
Exchange the linear expan-sion valve.
Exchange the linear expan-sion valve.
If a large amount of refrig-erant is leaked, exchange the linear expansion valve.
Disconnect the connector at the controller board, then check the continuity.
Measure the resistance between the each coil (red-white, red-orange, brown-yellow, brown-blue) with a tester. It is nor-mal if the resistance is in the range of 200 i 10%
Short or breakage of the motor coil of the linear expansion valve
Closing a valve : 1 → 2 → 3 → 4 → 1 Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phases become OFF.
• At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will lock and vibrate.
• When the switch is turned on, 2200 pulse closing valve signal will be sent till it goes to A point in order to define the valve position.
• When the valve moves smoothly, there is no sound or vibration occurring from the linear expansion valve; however, when the pulse number moves from E to A or when the valve is locked, more sound can be heard than normal situation.
• Sound can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion valve.
10-2. FUNCTION OF DIP SWITCH
Switch Function RemarksEffective timing
Under suspension
Under suspension
Before power supply
ON
Before power supply
ON
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Operation by switch
ON OFF
Pole
Built-in remote controller
Provided
2,500h
Effective
Thermo ON signal indication
Fan operation at Heating mode
Low 1
Setting air flow 1
Effective
Effective
Filter clogging detection
Filter cleaning
Fresh air intake
Remote indication switching
Humidifier control
Airflow setting during thermo OFF in heating mode
Auto restart function
Power ON/OFF
Indoor unit
Not provided
100h
Not effective
Fan output indication Thermo ON operation at heating mode
Extra low 1
Depends on SW1-7
Not effective
Not effective
Cooling only
Available
Available
Available
Second setting 5
Horizontal angle
Effective
Not effective
Heat pump / Cooling only
Louver
Vane
Vane swing function
Vane horizontal angle
Vane cooling limit angle setting 3
Heat 4degrees up
Superheat setting temperature 4
Sub cool setting temperature 4
Heat pump
Not available
Not available
Not available
First setting
Down B, C
Not effective
Effective
SW2
Capacity code setting
1~6
1~5
SW3
Function setting
Thermistor <Room temperature detection> position
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Indoor controller board
Note :
3 At cooling mode, each angle can be used only 1 hour.
4 Do not use SW3-9, 10 as trouble might be caused by the usage condition.
5 Second setting is same as first setting
Indoor controller board
<Initial setting>
Set while the unit is off.
Set for each capacity.
Indoor controller board
Indoor controller board
ON
OFF
1 2 3 4 5
Capacity
P12
P08 P15
SW 2 Capacity SW 2
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
SW1
Function Selection
SW4
Unit
Selection
Indoor linear expansion valve opening
In case of replacing the indoor controller board, make sure to set the switch to the initial setting, which is shown below.
SW 1-7
OFF
ON
OFF
ON
SW 1-8
OFF
OFF
ON
ON
Fan speed
Extra low
Low
Setting air flow stop
2 SW1-9 setting
PLFY-P·NCMU-E(1) :OFF
PLFY-P·NCMU-ER2/ER3/ER4:ON
The black square ( ) indicates a switch position.
8 37
1 0
8 37
8 37
1 0
8 37
F
E
D 5C
B
A
F
E
D 5C
B
A
R ot ar y sw itc h R ot ar y sw itc h
SW14
Connection
No.
setting
SW11
1s digit address setting
SW12
10ths digit address setting
Pole Operation by switch
How to set addresses Example: If address is "3", remain SW12 (for over 10) at "0", and match SW11 (for 1 to 9) with "3".
How to set branch numbers SW14 (Series R2 only) Match the indoor unit’s refrigerant pipe with the BC controller’s end connection number.
Remain other than series R2 at "0".
Remarks
<Initial setting>
SW12
SW11
SW12 SW11
SW14
SW14
<Initial setting>
Effective timing
Before power supply ON Indoor controller board
Indoor controller board
10-3. TEST POINT DIAGRAM
10-3-1. Indoor power board
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
CNSK
Connect to the indoor controller board (CNDK) Between 1 to 3 208-230V AC
CN2S
Connect to the indoor controller board (CN2D) Between 1 to 3 12.5-13.7V DC (Pin1 (+))
LED1
Main power supply (Indoor unit : 208-230V)
CND
Power supply for indoor controller board Between 1 to 3
208-230V AC
CNP
Drain pump output (DP) Between 1 to 3
208-230V AC
FUSE
6.3A 250V
CNDK
Connect to the indoor power board (CNSK) Between 1 to 3
208-230V AC
FAN
Fan motor output (MF)
CN2D
Connect to the indoor power board (CN2S) 12.5-13.7V DC (Pin1 (+))
CN2M
Connect to the terminal block (TB5) (M-NET transmission connecting wire) 24-30V DC (non-polar)
CN3A
Connect to the terminal block (TB15) (MA-Remote controller connecting wire) Between 1 to 3 8.7-13V DC (Pin1 (+))
CN29
Pipe temperature detection/Gas (TH23)
CN21
Pipe temperature detection/Liquid (TH22)
LED2
Power supply for MA-Remote controller
SW4
Model selection
CN60
Linear expansion valve output (LEV) 12VDC pulse output
CN31
Drain sensor (DS)
SW3
Function setting
SW2
Capacity setting
CN6V
Vane motor output (MV) 12VDC pulse output
CN20
Room temperature detection (TH21)
CN32
Connector (Remote switch)
CN27
Connector (Damper)
10-3-2. Indoor controller board
PLFY-P08NCMU-E.TH PLFY-P12NCMU-E.TH PLFY-P15NCMU-E.TH
PLFY-P08NCMU-E1.TH PLFY-P12NCMU-E1.TH PLFY-P15NCMU-E1.TH
SW11
Address setting 1s DIGIT
SW12
Address setting 10ths DIGIT
SW14
Branch No.
SW1
Function setting
CN51
Centrally control 1-2: Control signal
12VDC pulse input (1: +) 3-4: Operation indicator
12VDC (3: +)
3-5: Malfunction indicator
12VDC (3: +)
CN52
Remote indicator 1-2: Status lamp 12VDC (1 : +) Fan motor output (SW1-5 OFF) Thermostat ON (SW1-5 ON) 1-3: Cooling/Dry status lamp
12VDC (1 : +)
1-4: Heating status lamp
12VDC (1 : +)
CNC
Dew prevention heater Between 1 to 3
208-230V AC
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH PLFY-P15NCMU-ER2.TH
PLFY-P08NCMU-ER3.TH PLFY-P12NCMU-ER3.TH PLFY-P15NCMU-ER3.TH
PLFY-P08NCMU-ER4.TH PLFY-P12NCMU-ER4.TH PLFY-P15NCMU-ER4.TH
LED1
Main power supply (Indoor unit : 220-240V)
CND
Power supply for indoor controller board Between 1 to 3
208-230V AC
CNP
Drain pump output (DP) Between 1 to 3
208-230V AC
FUSE
6.3A 250V
CNDK
Connect to the indoor power board (CNSK) Between 1 to 3
208-230V AC
FAN
Fan motor output (MF)
CN2D
Connect to the indoor power board (CN2S) 12.5-13.7V DC (Pin1 (+))
CN2M
Connect to the terminal block (TB5) (M-NET transmission connecting wire) 24-30V DC (non-polar)
CN3A
Connect to the terminal block (TB15) (MA-Remote controller connecting wire) Between 1 to 3 8.7-13V DC (Pin1 (+))
CN29
Pipe temperature detection/Gas (TH23)
CN21
Pipe temperature detection/Liquid (TH22)
LED2
Power supply for MA-Remote controller
SW4
Model selection
CN60
Linear expansion valve output (LEV) 12VDC pulse output
CN31
Drain sensor (DS)
SW3
Function setting
CN51
Centrally control 1-2: Control signal
12VDC pulse input (1: +) 3-4: Operation indicator
12VDC (3: +)
3-5: Malfunction indicator
12VDC (3: +)
SW2
Capacity setting
CN6V
Vane motor output (MV) 12VDC pulse output
CN20
Room temperature detection (TH21)
CN32
Connector (Remote switch)
CN27
Connector (Damper)
12VDC (1: +)
SW11
Address setting 1s DIGIT
SW12
Address setting 10ths DIGIT
SW14
Branch No.
CN90
Connect to the wireless junction cable
SW1
Model selection
Jumper wire J41, J42 Pair No. setting for wireless remote controller
CN24
External heater
12VDC (1: +)
CN52
Remote indicator 1-2: Status lamp 12VDC (1 : +) Fan motor output (SW1-5 OFF) Thermostat ON (SW1-5 ON) 1-3: Cooling/Dry status lamp
12VDC (1 : +)
1-4: Heating status lamp
12VDC (1 : +)
CNC
Dew prevention heater Between 1 to 3
208-230V AC
DISASSEMBLY PROCEDURE11
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to prevent the grille from dropping.
(3) Slide the hinge of the intake grille to the direction of the arrow 2 and remove the air intake grille.
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Indoor power board (P.B)
• Fan motor capacitor (C1)
• Fuse (FUSE)
• Varistor (ZNR)
• Terminal block (TB)
Be careful when removing heavy parts.
Photo 3
Figure 1 Air intake grille
Grille
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
Air intake grille knob
3. Removing the panel
(1) Remove the air intake grille. (Refer to 1) Corner panel (See Figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow 3, and remove the corner panel.
Panel (See Photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose other
2 screws, which are fixed to the oval hole, have different diameter.
(3) Rotate the panel a little to remove the screws. (Slide the panel so that the screw comes to a larger diameter of the oval hole, which has two different diameters.)
Photo 1
Screws
Air intake grille
Photo 2
Figure 2
Corner panel
Screw Corner panel Panel
Panel Screws
Connector Screws
Fan guard
Indoor controller board (I.B)
Fuse
(FUSE)
Indoor power board (P.B)
Terminal block (TB2)
Indoor controller box
PLFY-P08/12/15NCMU-E.TH PLFY-P08/12/15NCMU-E1.TH
PLFY-P08/12/15NCMU-ER2.TH PLFY-P08/12/15NCMU-ER3.TH
PLFY-P08/12/15NCMU-ER4.TH
Terminal block (TB5)
Varistor
(ZNR)
Fan motor Capacitor (C1)
Terminal block
(TB15)
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
7. Removing the pipe temperature detection/liquid (TH22) and pipe temperature detection/gas (TH23)
(1) Remove the panel. (Refer to procedure 3)
(2) Remove the drain pan. (Refer to procedure 6)
(3) Disconnect the liquid or gas from the holder.
(4) Remove the 3 screws fixed to the piping cover, and remove the piping cover. (See Photo 9)
(5) Remove the 2 screws fixed to the control box cover, and remove the control box cover.
Pipe temperature detection/liquid (TH22)
(6) Remove the connector (CN21) from the indoor controller board, and disconnect the pipe temperature detection/Liquid.
Pipe temperature detection/gas (TH23)
(6) Remove the connector (CN29) from the indoor controller board, and disconnect the pipe temperature detection/Gas with its holder.
8. Removing the fan motor (MF)
(1) Remove the panel.