This is a detailed technical specifications document for Mitsubishi HVAC equipment, specifically the PURY-P72-288T(S)KMU-A and PURY-P72-288Y(S)KMU-A air conditioning systems. The document provides comprehensive specifications for R2-series heat recovery outdoor units in both 208-230V and 460V configurations, with cooling capacities ranging from 72,000 to 288,000 BTU/h.

The specifications include detailed performance data, physical dimensions, electrical requirements, operating conditions, and refrigerant information for each model. Key features include inverter scroll hermetic compressors, propeller fans with brushless DC motors, and R410A refrigerant. The units operate in cooling mode between 59-75°F indoor and 23-115°F outdoor temperatures, and in heating mode between 59-81°F indoor and -13-60°F outdoor temperatures. The document includes installation requirements, piping specifications, and optional parts information such as twinning kits and BC controllers. All units feature salt-resistant cross fin and copper tube heat exchangers, auto-defrost capability, and various protection devices including high pressure sensors and overcurrent protection.

View the file

Other files

File Type Posted
Crane rope cert.pdf PDF
1547 4411 Rev 5 Machinery Arrgmt.pdf PDF
Tow Winch Pic 2.jpg JPG image
1547L F 54 Rev 4 Barge Towing Arr and Det.pdf PDF
Sullair Compressor Pic.jpg JPG image
1547L P72 Rev 2 Towing winch Power and controls.pdf PDF
AMD 0002 Drydock 2025 Questions and Answers 2.pdf PDF
P00002 6933A225Q000001 .pdf PDF
crane cab rough dimensions.pdf PDF
Tow Winch Pic 1.jpg JPG image
AMD0001 6933A225Q000001 .pdf PDF
Item 225 Photo.jpg JPG image
Item 226 Fassmer FRB.pdf PDF
Item 225 SH PLFY P NCMU E OCH410D Parts OCB410D 1.pdf PDF
AMD 00001 TSFS Drydock 2025 Questions and Answers.pdf PDF
Item 226 Global Davit Catalogue 2016.pdf PDF
Item 225 DB PUHY P T Y S KMU A BS U11 E2 3.pdf PDF
FREEDOM STAR ON 629627 Trim and Stability Booklet Rev D.pdf PDF
1547 4411 Rev 5 Machinery Arrgmt.pdf PDF
1547-4701 Rev 3 Rudder Arr 3.pdf PDF
MA-57 Dry dock Report 3.pdf PDF
1547-4420 Rev 3 Bow Thruster Arr 3.pdf PDF
FREEDOM STAR ON 629627 Trim and Stability Booklet Rev D 1.pdf PDF
Stern Thruster Mechanical manual G569W G570W 32HJP 4.pdf PDF
TSFS 2023 Anchor Chain Gauging Report 2.pdf PDF
Shaft Liners 2.pdf PDF
TSFS Wartsila Tailshaft Parts 2024 1.pdf PDF
Stern Thruster 2768WG-D 32HJP SECTIONAL ARRANGEMENET 1.pdf PDF
TSFS 2023 Motor Megger Report 3.pdf PDF
Sherwin Williams Coating Spec 04-12-2024 2.pdf PDF
1316-901 Kings Pointer Docking Plan 3.pdf PDF
FREEDOM STAR MEGGER READINGS blank 1.docx DOCX document
2018 Bow Thruster Maintenance - Final Service Report 1.pdf PDF
1780-4419 Stern Thruster Compt Arrangement1of1 3.pdf PDF
TV KINGS POINTER Docking Calculations 2.pdf PDF
Crane Diesel Manual 1.pdf PDF
TSFS FY25 CSS 6933A225Q000001 FINAL.pdf PDF
1547-1420 Docking Plan 3.pdf PDF
1547-2510 Rev 7 Long l Struct Sections 3.pdf PDF
Sullair ES6 2.pdf PDF
1547-4801 Rev 4 Shafting Arr and Det 2.pdf PDF
2020 Bow Thruster Maintenance Report 1.pdf PDF
ABS Rules Part 7 Chapter 6 4.pdf PDF
TSFS 2023 Anode Locations 2.pdf PDF
TS FREEDOM STAR - Signed CFR 014 Tailshaft Bearing Clearances WI 202 1.pdf PDF
2023 Freedom Star Gauge Calibration List 1.xls XLS spreadsheet
4163B-M20 Bow Thruster Arrangement Omega OCP-400 1.pdf PDF
TSFS Gauge Calibration Final Report 2023 1.pdf PDF
Attmt II TSFS VENDOR PRICE SHEET (SECTION B) .xlsx XLSX spreadsheet
ABS Rules Part 7 Chapter 5 Sections 1 and 2 3.pdf PDF
Show 40 more

Latest 50 of 71 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR CONDITIONING SYSTEMS

MODEL

PURY-P72-288T(S)KMU-A (-BS)

PURY-P72-288Y(S)KMU-A (-BS)

GENERAL LINE-UP Outdoor units

I.GENERAL LINE-UP

216K

PURY-P216YSKMU-A

Type(BTU/h)

Model Name

72K

PURY-P72TΚMU-A

96K

PURY-P96TΚMU-A

120K

PURY-P120TΚMU-A

144K

PURY-P144TΚMU-A

168K

PURY-P168TSKMU-A

192K

PURY-P192TSKMU-A

216K

PURY-P216TSKMU-A

Type(BTU/h)

Model Name

Type(BTU/h)

Model Name

240K

PURY-P240TSKMU-A

264K

PURY-P264TSKMU-A

288K

PURY-P288TSKMU-A

Type(BTU/h)

Model Name

72K

PURY-P72YΚMU-A

96K

PURY-P96YΚMU-A

120K

PURY-P120YΚMU-A

144K

PURY-P144YΚMU-A

144K

PURY-P144YSKMU-A

168K

PURY-P168YSKMU-A

192K

PURY-P192YSKMU-A

Type(BTU/h)

Model Name

Type(BTU/h)

Model Name

240K

PURY-P240YSKMU-A

264K

PURY-P264YSKMU-A

288K

PURY-P288YSKMU-A

Type(BTU/h)

Model Name

Heat Recovery R2-Series (K) - 208-230 V Heat Recovery R2-Series (K) - 460 V

R2-SERIES (K) Outdoor units

OUTDOOR UNITS

I.R2 SERIES

1. SPECIFICATIONS........................................................................................................................................... OUg-2-2

2. EXTERNAL DIMENSIONS .............................................................................................................................. OUg-2-23

3. CENTER OF GRAVITY ................................................................................................................................... OUg-2-37

4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ OUg-2-38

5. SOUND LEVELS ............................................................................................................................................. OUg-2-44

6. VIBRATION LEVEL ......................................................................................................................................... OUg-2-48

7. OPERATION TEMPERATURE RANGE.......................................................................................................... OUg-2-49

8. CAPACITY TABLES ........................................................................................................................................ OUg-2-50 8-1. Selection of Cooling/Heating Units .......................................................................................................... OUg-2-50 8-2. Correction by temperature ....................................................................................................................... OUg-2-60 8-3. Correction by total indoor......................................................................................................................... OUg-2-84 8-4. Correction by refrigerant piping length..................................................................................................... OUg-2-90 8-5. Correction at frost and defrost ................................................................................................................. OUg-2-94

9. OPTIONAL PARTS.......................................................................................................................................... OUg-2-95 9-1. JOINT ...................................................................................................................................................... OUg-2-95 9-2. OUTDOOR TWINNING KIT..................................................................................................................... OUg-2-96 9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER ............................................................................. OUg-2-97 9-4. RELAY BOX ............................................................................................................................................ OUg-2-98 9-5. BASE HEATER........................................................................................................................................ OUg-2-99

1. SPECIFICATIONS Outdoor units

R

(K

I.R2 SERIES1. SPECIFICATIONS

Outdoor Model PURY-P72TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 72,000 (Nominal) kW 21.1

Power input kW 4.40 (208-230) Current input A 13.5-12.2

(Rated) BTU/h 69,000 kW 20.2

Power input kW 4.10 4.05 (208-230) Current input A 12.6-11.4 12.4-11.2

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 80,000 (Nominal) kW 23.4

Power input kW 5.92 (208-230) Current input A 18.2-16.5

(Rated) BTU/h 76,000 kW 22.3

Power input kW 5.79 5.37 (208-230) Current input A 17.8-16.1 16.5-14.9

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~18 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 5/8 (15.88) Brazed piping diameter Low pressure in. (mm) 3/4 (19.05) Brazed Minimum Circuit Ampacity A 23-21 Maximum Overcurrent Protection A 38-35 FAN Type x Quantity Propeller fan x 1

Airflow rate cfm 6,200 m3/min 175 L/s 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 4.7 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 503 (228) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R359

Wiring KE94C646 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

*Above specification data is

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

1. SPECIFICATIONS

2 (K

Outdoor units

Outdoor Model PURY-P96TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 96,000 (Nominal) kW 28.1

Power input kW 7.05 (208-230) Current input A 21.7-19.6

(Rated) BTU/h 92,000 kW 27.0

Power input kW 6.24 6.81 (208-230) Current input A 19.2-17.4 21.0-18.9

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 108,000 (Nominal) kW 31.7

Power input kW 8.28 (208-230) Current input A 25.5-23.0

(Rated) BTU/h 103,000 kW 30.2

Power input kW 7.80 7.75 (208-230) Current input A 24.0-21.7 23.9-21.6

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~24 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 7/8 (22.2) Brazed Minimum Circuit Ampacity A 34-31 Maximum Overcurrent Protection A 57-52 FAN Type x Quantity Propeller fan x 1

Airflow rate cfm 6,200 m3/min 175 L/s 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 6.7 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R359

Wiring KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

(K

Outdoor Model PURY-P120TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 120,000 (Nominal) kW 35.2

Power input kW 9.44 (208-230) Current input A 29.1-26.3

(Rated) BTU/h 114,000 kW 33.4

Power input kW 8.78 8.71 (208-230) Current input A 27.0-24.4 26.8-24.2

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 135,000 (Nominal) kW 39.6

Power input kW 10.86 (208-230) Current input A 33.4-30.2

(Rated) BTU/h 129,000 kW 37.8

Power input kW 10.10 10.23 (208-230) Current input A 31.1-28.1 31.5-28.5

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~30 Sound pressure level (measured in anechoic room) dB <A> 60.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Minimum Circuit Ampacity A 45-42 Maximum Overcurrent Protection A 74-68 FAN Type x Quantity Propeller fan x 2

Airflow rate cfm 11,300 m3/min 320 L/s 5,330

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92+0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 8.2 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R360

Wiring KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

2 (K

Outdoor units

Outdoor Model PURY-P144TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 144,000 (Nominal) kW 42.2

Power input kW 11.20 (208-230) Current input A 34.5-31.2

(Rated) BTU/h 137,000 kW 40.2

Power input kW 10.14 10.60 (208-230) Current input A 31.2-28.2 32.6-29.5

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 160,000 (Nominal) kW 46.9

Power input kW 13.54 (208-230) Current input A 41.7-37.7

(Rated) BTU/h 152,000 kW 44.5

Power input kW 13.13 12.22 (208-230) Current input A 40.4-36.6 37.6-34.0

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~36 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Minimum Circuit Ampacity A 53-48 Maximum Overcurrent Protection A 87-80 FAN Type x Quantity Propeller fan x 2

Airflow rate cfm 11,300 m3/min 320 L/s 5,330

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92+0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 9.5 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R360

Wiring KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1 Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1

Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

(K

Outdoor Model PURY-P168TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 168,000 (Nominal) kW 49.2

Power input kW 12.80 (208-230) Current input A 39.4-35.7

(Rated) BTU/h 161,000 kW 47.2

Power input kW 11.80 11.90 (208-230) Current input A 36.3-32.9 36.7-33.1

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 188,000 (Nominal) kW 55.1

Power input kW 14.91 (208-230) Current input A 45.9-41.5

(Rated) BTU/h 179,000 kW 52.5

Power input kW 14.43 13.44 (208-230) Current input A 44.5-40.2 41.4-37.4

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~42 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P96TKMU-A(-BS) PURY-P72TKMU-A(-BS) Minimum Circuit Ampacity A 34-31 23-21 Maximum Overcurrent Protection A 57-52 38-35 FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Airflow rate cfm 6,200 6,200 m3/min 175 175 L/s 2,920 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92 0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 6.7 4.7 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 538 (244) 503 (228) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 5/8 (15.88) Brazed distributor Low pressure in. (mm) - 3/4 (19.05) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R352

Wiring KE94C648 KE94C646 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100CBK2 joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement above specifications may be subject to change without notice subject to rounding variation

2 (K

Outdoor units

Outdoor Model PURY-P192TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 192,000 (Nominal) kW 56.3

Power input kW 15.61 (208-230) Current input A 48.1-43.5

(Rated) BTU/h 183,000 kW 53.6

Power input kW 14.61 14.30 (208-230) Current input A 45.0-40.7 44.1-39.8

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 215,000 (Nominal) kW 63.0

Power input kW 17.20 (208-230) Current input A 53.0-47.9

(Rated) BTU/h 205,000 kW 60.1

Power input kW 16.73 15.34 (208-230) Current input A 51.5-46.6 47.3-42.7

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~48 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P96TKMU-A(-BS) PURY-P96TKMU-A(-BS) Minimum Circuit Ampacity A 34-31 34-31 Maximum Overcurrent Protection A 57-52 57-52 FAN Type x Quantity Propeller fan x 1 Propeller fan x 1

Airflow rate cfm 6,200 6,200 m3/min 175 175 L/s 2,920 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92 0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 6.7 6.7 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 538 (244) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 7/8 (22.2) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R352

Wiring KE94C648 KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100CBK2 joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

(K

Outdoor Model PURY-P216TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 216,000 (Nominal) kW 63.3

Power input kW 18.22 (208-230) Current input A 56.1-50.8

(Rated) BTU/h 206,000 kW 60.4

Power input kW 17.43 16.31 (208-230) Current input A 53.7-48.6 50.3-45.4

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 243,000 (Nominal) kW 71.2

Power input kW 19.89 (208-230) Current input A 61.3-55.4

(Rated) BTU/h 232,000 kW 68.0

Power input kW 19.20 17.86 (208-230) Current input A 59.2-53.5 55.0-49.8

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)

Sound pressure level (measured in anechoic room) dB <A> 62.5 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P120TKMU-A(-BS) PURY-P96TKMU-A(-BS) Minimum Circuit Ampacity A 45-42 34-31 Maximum Overcurrent Protection A 74-68 57-52 FAN Type x Quantity Propeller fan x 2 Propeller fan x 1

Airflow rate cfm 11,300 6,200 m3/min 320 175 L/s 5,330 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 8.2 6.7 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 7/8 (22.2) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R353

Wiring KE94C650 KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

2 (K

Outdoor units

Outdoor Model PURY-P240TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 240,000 (Nominal) kW 70.3

Power input kW 21.11 (208-230) Current input A 65.1-58.8

(Rated) BTU/h 228,000 kW 66.8

Power input kW 20.03 19.06 (208-230) Current input A 61.7-55.8 58.7-53.1

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 270,000 (Nominal) kW 79.1

Power input kW 22.73 (208-230) Current input A 70.1-63.3

(Rated) BTU/h 258,000 kW 75.6

Power input kW 21.43 20.92 (208-230) Current input A 66.0-59.7 64.5-58.3

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)

Sound pressure level (measured in anechoic room) dB <A> 63.0 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P120TKMU-A(-BS) PURY-P120TKMU-A(-BS) Minimum Circuit Ampacity A 45-42 45-42 Maximum Overcurrent Protection A 74-68 74-68 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2

Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 8.2 8.2 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354

Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement above specifications may be subject to change without notice subject to rounding variation

(K

Outdoor Model PURY-P264TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 264,000 (Nominal) kW 77.4

Power input kW 23.05 (208-230) Current input A 71.0-64.2

(Rated) BTU/h 251,000 kW 73.6

Power input kW 21.89 20.79 (208-230) Current input A 67.5-61.0 64.1-57.9

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 295,000 (Nominal) kW 86.5

Power input kW 25.37 (208-230) Current input A 78.2-70.7

(Rated) BTU/h 281,000 kW 82.4

Power input kW 24.65 22.64 (208-230) Current input A 76.0-68.7 69.8-63.1

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)

Sound pressure level (measured in anechoic room) dB <A> 63.5 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P144TKMU-A(-BS) PURY-P120TKMU-A(-BS) Minimum Circuit Ampacity A 53-48 45-42 Maximum Overcurrent Protection A 87-80 74-68 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2

Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 9.5 8.2 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 7/8 (22.2) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354

Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

2 (K

Outdoor units

Outdoor Model PURY-P288TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 288,000 (Nominal) kW 84.4

Power input kW 24.57 (208-230) Current input A 75.7-68.5

(Rated) BTU/h 274,000 kW 80.3

Power input kW 23.24 22.26 (208-230) Current input A 71.6-64.8 68.6-62.0

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 320,000 (Nominal) kW 93.8

Power input kW 27.62 (208-230) Current input A 85.1-77.0

(Rated) BTU/h 304,000 kW 89.1

Power input kW 26.83 24.40 (208-230) Current input A 82.7-74.8 75.2-68.0

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)

Sound pressure level (measured in anechoic room) dB <A> 64.0 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P144TKMU-A(-BS) PURY-P144TKMU-A(-BS) Minimum Circuit Ampacity A 53-48 53-48 Maximum Overcurrent Protection A 87-80 87-80 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2

Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330

Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92

*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 9.5 9.5 Case heater kW - - Lubricant MEL32 MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

High pressure sensor, High pressure switch at 4.15 MPa (601 psi)

Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 7/8 (22.2) Brazed 7/8 (22.2) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354

Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.

The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

(K

Outdoor Model PURY-P72YKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 460 V ±10% 60 Hz Cooling capacity *1 BTU/h 72,000 (Nominal) kW 21.1

Power input kW 4.40

(460) Current input A 6.1

(Rated) BTU/h 69,000 kW 20.2

Power input kW 4.10 4.05

(460) Current input A 5.7 5.6

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 80,000 (Nominal) kW 23.4

Power input kW 5.92

(460) Current input A 8.2

(Rated) BTU/h 76,000 kW 22.3

Power input kW 5.79 5.37

(460) Current input A 8.0 7.4

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~18 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 5/8 (15.88) Brazed piping diameter Low pressure in. (mm) 3/4 (19.05) Brazed Minimum Circuit Ampacity A 11 Maximum Overcurrent Protection A 17 FAN Type x Quantity Propeller fan x 1

Airflow rate cfm 6,200 m3/min 175 L/s 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 4.7 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 534 (242) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R361

Wiring KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1

BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1

Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.

Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)

2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)

3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.

4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).

BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536

* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.

2 (K

Outdoor units

Outdoor Model PURY-P96YKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 460 V ±10% 60 Hz Cooling capacity *1 BTU/h 96,000 (Nominal) kW 28.1

Power input kW 7.05

(460) Current input A 9.8

(Rated) BTU/h 92,000 kW 27.0

Power input kW 6.24 6.81

(460) Current input A 8.7 9.4

Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 108,000 (Nominal) kW 31.7

Power input kW 8.28

(460) Current input A 11.5

(Rated) BTU/h 103,000 kW 30.2

Power input kW 7.80 7.75

(460) Current input A 10.8 10.8

Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity

Model/Quantity P06~P96/1~24 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 7/8 (22.2) Brazed Minimum Circuit Ampacity A 15 Maximum Overcurrent Protection A 26 FAN Type x Quantity Propeller fan x 1

Airflow rate cfm 6,200 m3/min 175 L/s 2,920

Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92

*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1

Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 6.7 Case heater kW - Lubricant MEL32

External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

<MUNSELL 5Y 8/1>

External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740

Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -

Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller

Net weight lbs (kg) 574 (260) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R361

Wiring KE94C642 Standard…