DB Design PURY P T Y S KMU A BS MEES17K096 201802.pdf
PDF 5 MB Posted
- Attached to
- TRAINING VESSEL FREEDOM STAR(TVFS) FY25 DRY DOCK
- Solicitation number
- 6933A225Q000001
About this file
This is a detailed technical specifications document for Mitsubishi HVAC equipment, specifically the PURY-P72-288T(S)KMU-A and PURY-P72-288Y(S)KMU-A air conditioning systems. The document provides comprehensive specifications for R2-series heat recovery outdoor units in both 208-230V and 460V configurations, with cooling capacities ranging from 72,000 to 288,000 BTU/h.
The specifications include detailed performance data, physical dimensions, electrical requirements, operating conditions, and refrigerant information for each model. Key features include inverter scroll hermetic compressors, propeller fans with brushless DC motors, and R410A refrigerant. The units operate in cooling mode between 59-75°F indoor and 23-115°F outdoor temperatures, and in heating mode between 59-81°F indoor and -13-60°F outdoor temperatures. The document includes installation requirements, piping specifications, and optional parts information such as twinning kits and BC controllers. All units feature salt-resistant cross fin and copper tube heat exchangers, auto-defrost capability, and various protection devices including high pressure sensors and overcurrent protection.
View the file
Other files
Show 40 more
Latest 50 of 71 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR CONDITIONING SYSTEMS
MODEL
PURY-P72-288T(S)KMU-A (-BS)
PURY-P72-288Y(S)KMU-A (-BS)
GENERAL LINE-UP Outdoor units
I.GENERAL LINE-UP
216K
PURY-P216YSKMU-A
Type(BTU/h)
Model Name
72K
PURY-P72TΚMU-A
96K
PURY-P96TΚMU-A
120K
PURY-P120TΚMU-A
144K
PURY-P144TΚMU-A
168K
PURY-P168TSKMU-A
192K
PURY-P192TSKMU-A
216K
PURY-P216TSKMU-A
Type(BTU/h)
Model Name
Type(BTU/h)
Model Name
240K
PURY-P240TSKMU-A
264K
PURY-P264TSKMU-A
288K
PURY-P288TSKMU-A
Type(BTU/h)
Model Name
72K
PURY-P72YΚMU-A
96K
PURY-P96YΚMU-A
120K
PURY-P120YΚMU-A
144K
PURY-P144YΚMU-A
144K
PURY-P144YSKMU-A
168K
PURY-P168YSKMU-A
192K
PURY-P192YSKMU-A
Type(BTU/h)
Model Name
Type(BTU/h)
Model Name
240K
PURY-P240YSKMU-A
264K
PURY-P264YSKMU-A
288K
PURY-P288YSKMU-A
Type(BTU/h)
Model Name
Heat Recovery R2-Series (K) - 208-230 V Heat Recovery R2-Series (K) - 460 V
R2-SERIES (K) Outdoor units
OUTDOOR UNITS
I.R2 SERIES
1. SPECIFICATIONS........................................................................................................................................... OUg-2-2
2. EXTERNAL DIMENSIONS .............................................................................................................................. OUg-2-23
3. CENTER OF GRAVITY ................................................................................................................................... OUg-2-37
4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ OUg-2-38
5. SOUND LEVELS ............................................................................................................................................. OUg-2-44
6. VIBRATION LEVEL ......................................................................................................................................... OUg-2-48
7. OPERATION TEMPERATURE RANGE.......................................................................................................... OUg-2-49
8. CAPACITY TABLES ........................................................................................................................................ OUg-2-50 8-1. Selection of Cooling/Heating Units .......................................................................................................... OUg-2-50 8-2. Correction by temperature ....................................................................................................................... OUg-2-60 8-3. Correction by total indoor......................................................................................................................... OUg-2-84 8-4. Correction by refrigerant piping length..................................................................................................... OUg-2-90 8-5. Correction at frost and defrost ................................................................................................................. OUg-2-94
9. OPTIONAL PARTS.......................................................................................................................................... OUg-2-95 9-1. JOINT ...................................................................................................................................................... OUg-2-95 9-2. OUTDOOR TWINNING KIT..................................................................................................................... OUg-2-96 9-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER ............................................................................. OUg-2-97 9-4. RELAY BOX ............................................................................................................................................ OUg-2-98 9-5. BASE HEATER........................................................................................................................................ OUg-2-99
1. SPECIFICATIONS Outdoor units
R
(K
I.R2 SERIES1. SPECIFICATIONS
Outdoor Model PURY-P72TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 72,000 (Nominal) kW 21.1
Power input kW 4.40 (208-230) Current input A 13.5-12.2
(Rated) BTU/h 69,000 kW 20.2
Power input kW 4.10 4.05 (208-230) Current input A 12.6-11.4 12.4-11.2
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 80,000 (Nominal) kW 23.4
Power input kW 5.92 (208-230) Current input A 18.2-16.5
(Rated) BTU/h 76,000 kW 22.3
Power input kW 5.79 5.37 (208-230) Current input A 17.8-16.1 16.5-14.9
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~18 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 5/8 (15.88) Brazed piping diameter Low pressure in. (mm) 3/4 (19.05) Brazed Minimum Circuit Ampacity A 23-21 Maximum Overcurrent Protection A 38-35 FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175 L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 4.7 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 503 (228) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R359
Wiring KE94C646 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
1. SPECIFICATIONS
2 (K
Outdoor units
Outdoor Model PURY-P96TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 96,000 (Nominal) kW 28.1
Power input kW 7.05 (208-230) Current input A 21.7-19.6
(Rated) BTU/h 92,000 kW 27.0
Power input kW 6.24 6.81 (208-230) Current input A 19.2-17.4 21.0-18.9
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 108,000 (Nominal) kW 31.7
Power input kW 8.28 (208-230) Current input A 25.5-23.0
(Rated) BTU/h 103,000 kW 30.2
Power input kW 7.80 7.75 (208-230) Current input A 24.0-21.7 23.9-21.6
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~24 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 7/8 (22.2) Brazed Minimum Circuit Ampacity A 34-31 Maximum Overcurrent Protection A 57-52 FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175 L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 6.7 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R359
Wiring KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
(K
Outdoor Model PURY-P120TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 120,000 (Nominal) kW 35.2
Power input kW 9.44 (208-230) Current input A 29.1-26.3
(Rated) BTU/h 114,000 kW 33.4
Power input kW 8.78 8.71 (208-230) Current input A 27.0-24.4 26.8-24.2
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 135,000 (Nominal) kW 39.6
Power input kW 10.86 (208-230) Current input A 33.4-30.2
(Rated) BTU/h 129,000 kW 37.8
Power input kW 10.10 10.23 (208-230) Current input A 31.1-28.1 31.5-28.5
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~30 Sound pressure level (measured in anechoic room) dB <A> 60.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Minimum Circuit Ampacity A 45-42 Maximum Overcurrent Protection A 74-68 FAN Type x Quantity Propeller fan x 2
Airflow rate cfm 11,300 m3/min 320 L/s 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92+0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 8.2 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R360
Wiring KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
2 (K
Outdoor units
Outdoor Model PURY-P144TKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 144,000 (Nominal) kW 42.2
Power input kW 11.20 (208-230) Current input A 34.5-31.2
(Rated) BTU/h 137,000 kW 40.2
Power input kW 10.14 10.60 (208-230) Current input A 31.2-28.2 32.6-29.5
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 160,000 (Nominal) kW 46.9
Power input kW 13.54 (208-230) Current input A 41.7-37.7
(Rated) BTU/h 152,000 kW 44.5
Power input kW 13.13 12.22 (208-230) Current input A 40.4-36.6 37.6-34.0
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~36 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Minimum Circuit Ampacity A 53-48 Maximum Overcurrent Protection A 87-80 FAN Type x Quantity Propeller fan x 2
Airflow rate cfm 11,300 m3/min 320 L/s 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92+0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 9.5 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R360
Wiring KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1 Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
(K
Outdoor Model PURY-P168TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 168,000 (Nominal) kW 49.2
Power input kW 12.80 (208-230) Current input A 39.4-35.7
(Rated) BTU/h 161,000 kW 47.2
Power input kW 11.80 11.90 (208-230) Current input A 36.3-32.9 36.7-33.1
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 188,000 (Nominal) kW 55.1
Power input kW 14.91 (208-230) Current input A 45.9-41.5
(Rated) BTU/h 179,000 kW 52.5
Power input kW 14.43 13.44 (208-230) Current input A 44.5-40.2 41.4-37.4
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~42 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P96TKMU-A(-BS) PURY-P72TKMU-A(-BS) Minimum Circuit Ampacity A 34-31 23-21 Maximum Overcurrent Protection A 57-52 38-35 FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Airflow rate cfm 6,200 6,200 m3/min 175 175 L/s 2,920 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92 0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 6.7 4.7 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 538 (244) 503 (228) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 5/8 (15.88) Brazed distributor Low pressure in. (mm) - 3/4 (19.05) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R352
Wiring KE94C648 KE94C646 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100CBK2 joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement above specifications may be subject to change without notice subject to rounding variation
2 (K
Outdoor units
Outdoor Model PURY-P192TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 192,000 (Nominal) kW 56.3
Power input kW 15.61 (208-230) Current input A 48.1-43.5
(Rated) BTU/h 183,000 kW 53.6
Power input kW 14.61 14.30 (208-230) Current input A 45.0-40.7 44.1-39.8
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 215,000 (Nominal) kW 63.0
Power input kW 17.20 (208-230) Current input A 53.0-47.9
(Rated) BTU/h 205,000 kW 60.1
Power input kW 16.73 15.34 (208-230) Current input A 51.5-46.6 47.3-42.7
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~48 Sound pressure level (measured in anechoic room) dB <A> 61.0 Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P96TKMU-A(-BS) PURY-P96TKMU-A(-BS) Minimum Circuit Ampacity A 34-31 34-31 Maximum Overcurrent Protection A 57-52 57-52 FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Airflow rate cfm 6,200 6,200 m3/min 175 175 L/s 2,920 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92 0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 6.7 6.7 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 538 (244) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 7/8 (22.2) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R352
Wiring KE94C648 KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100CBK2 joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
(K
Outdoor Model PURY-P216TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 216,000 (Nominal) kW 63.3
Power input kW 18.22 (208-230) Current input A 56.1-50.8
(Rated) BTU/h 206,000 kW 60.4
Power input kW 17.43 16.31 (208-230) Current input A 53.7-48.6 50.3-45.4
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 243,000 (Nominal) kW 71.2
Power input kW 19.89 (208-230) Current input A 61.3-55.4
(Rated) BTU/h 232,000 kW 68.0
Power input kW 19.20 17.86 (208-230) Current input A 59.2-53.5 55.0-49.8
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room) dB <A> 62.5 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed Set Model Model PURY-P120TKMU-A(-BS) PURY-P96TKMU-A(-BS) Minimum Circuit Ampacity A 45-42 34-31 Maximum Overcurrent Protection A 74-68 57-52 FAN Type x Quantity Propeller fan x 2 Propeller fan x 1
Airflow rate cfm 11,300 6,200 m3/min 320 175 L/s 5,330 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 8.2 6.7 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) 538 (244) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 7/8 (22.2) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R353
Wiring KE94C650 KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
2 (K
Outdoor units
Outdoor Model PURY-P240TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 240,000 (Nominal) kW 70.3
Power input kW 21.11 (208-230) Current input A 65.1-58.8
(Rated) BTU/h 228,000 kW 66.8
Power input kW 20.03 19.06 (208-230) Current input A 61.7-55.8 58.7-53.1
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 270,000 (Nominal) kW 79.1
Power input kW 22.73 (208-230) Current input A 70.1-63.3
(Rated) BTU/h 258,000 kW 75.6
Power input kW 21.43 20.92 (208-230) Current input A 66.0-59.7 64.5-58.3
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room) dB <A> 63.0 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P120TKMU-A(-BS) PURY-P120TKMU-A(-BS) Minimum Circuit Ampacity A 45-42 45-42 Maximum Overcurrent Protection A 74-68 74-68 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 8.2 8.2 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354
Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement above specifications may be subject to change without notice subject to rounding variation
(K
Outdoor Model PURY-P264TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 264,000 (Nominal) kW 77.4
Power input kW 23.05 (208-230) Current input A 71.0-64.2
(Rated) BTU/h 251,000 kW 73.6
Power input kW 21.89 20.79 (208-230) Current input A 67.5-61.0 64.1-57.9
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 295,000 (Nominal) kW 86.5
Power input kW 25.37 (208-230) Current input A 78.2-70.7
(Rated) BTU/h 281,000 kW 82.4
Power input kW 24.65 22.64 (208-230) Current input A 76.0-68.7 69.8-63.1
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room) dB <A> 63.5 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P144TKMU-A(-BS) PURY-P120TKMU-A(-BS) Minimum Circuit Ampacity A 53-48 45-42 Maximum Overcurrent Protection A 87-80 74-68 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 9.5 8.2 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 7/8 (22.2) Brazed 3/4 (19.05) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354
Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
2 (K
Outdoor units
Outdoor Model PURY-P288TSKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 208-230 V ±10% 60 Hz Cooling capacity *1 BTU/h 288,000 (Nominal) kW 84.4
Power input kW 24.57 (208-230) Current input A 75.7-68.5
(Rated) BTU/h 274,000 kW 80.3
Power input kW 23.24 22.26 (208-230) Current input A 71.6-64.8 68.6-62.0
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 320,000 (Nominal) kW 93.8
Power input kW 27.62 (208-230) Current input A 85.1-77.0
(Rated) BTU/h 304,000 kW 89.1
Power input kW 26.83 24.40 (208-230) Current input A 82.7-74.8 75.2-68.0
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room) dB <A> 64.0 Refrigerant High pressure in. (mm) 1-1/8 (28.58) Brazed piping diameter Low pressure in. (mm) 1-3/8 (34.93) Brazed Set Model Model PURY-P144TKMU-A(-BS) PURY-P144TKMU-A(-BS) Minimum Circuit Ampacity A 53-48 53-48 Maximum Overcurrent Protection A 87-80 87-80 FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 11,300 11,300 m3/min 320 320 L/s 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Motor output kW 0.92+0.92 0.92+0.92
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Motor output kW 9.5 9.5 Case heater kW - - Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Over heat protection, Over-current protection Fan motor - -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 715 (324) 715 (324) Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure in. (mm) 7/8 (22.2) Brazed 7/8 (22.2) Brazed distributor Low pressure in. (mm) - 1-1/8 (28.58) Brazed Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R354
Wiring KE94C650 KE94C650 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts Outdoor Twinning kit: CMY-R100XLCBK joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1 Main BC controller: CMB-P108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Systems with considerably long pipe runs, in heating mode, may be subject to slightly louder than normal noise from the out-door unit/s.
The outdoor twinning kit (low pressure) should be connected to the low pressure side of the outdoor unit. If the connected units are of different capacities, the outdoor twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
(K
Outdoor Model PURY-P72YKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 460 V ±10% 60 Hz Cooling capacity *1 BTU/h 72,000 (Nominal) kW 21.1
Power input kW 4.40
(460) Current input A 6.1
(Rated) BTU/h 69,000 kW 20.2
Power input kW 4.10 4.05
(460) Current input A 5.7 5.6
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 80,000 (Nominal) kW 23.4
Power input kW 5.92
(460) Current input A 8.2
(Rated) BTU/h 76,000 kW 22.3
Power input kW 5.79 5.37
(460) Current input A 8.0 7.4
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~18 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 5/8 (15.88) Brazed piping diameter Low pressure in. (mm) 3/4 (19.05) Brazed Minimum Circuit Ampacity A 11 Maximum Overcurrent Protection A 17 FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175 L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 4.7 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 534 (242) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R361
Wiring KE94C648 Standard Document Installation Manual attachment Accessory Details refer to External Drw Optional parts joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G1 Main BC controller: CMB-P108,1010,1013,1016NU-GA1,108,1010,1016NU-HA1
Sub BC controller: CMB-P104,108NU-GB1,CMB-P1016NU-HB1 Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter 1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating.
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
2 (K
Outdoor units
Outdoor Model PURY-P96YKMU-A (-BS) Indoor Model Non-Ducted Ducted Power source 3-phase 3-wire 460 V ±10% 60 Hz Cooling capacity *1 BTU/h 96,000 (Nominal) kW 28.1
Power input kW 7.05
(460) Current input A 9.8
(Rated) BTU/h 92,000 kW 27.0
Power input kW 6.24 6.81
(460) Current input A 8.7 9.4
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C) Heating capacity *2 BTU/h 108,000 (Nominal) kW 31.7
Power input kW 8.28
(460) Current input A 11.5
(Rated) BTU/h 103,000 kW 30.2
Power input kW 7.80 7.75
(460) Current input A 10.8 10.8
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating *3 Outdoor W.B. -13~60°F (-25~15.5°C) Indoor unit Total capacity 50~150% of outdoor unit capacity
Model/Quantity P06~P96/1~24 Sound pressure level (measured in anechoic room) dB <A> 58.0 Refrigerant High pressure in. (mm) 3/4 (19.05) Brazed piping diameter Low pressure in. (mm) 7/8 (22.2) Brazed Minimum Circuit Ampacity A 15 Maximum Overcurrent Protection A 26 FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175 L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Motor output kW 0.92
*4 External static press. 0 in.WG (0 Pa) Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output kW 6.7 Case heater kW - Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) Inverter circuit (COMP./FAN) Over heat protection, Over-current protection Fan motor -
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) Control Indoor LEV and BC controller
Net weight lbs (kg) 574 (260) Heat exchanger Salt-resistant cross fin & copper tube HIC circuit (HIC: Heat Inter-Changer) - Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Drawing External KD94R361
Wiring KE94C642 Standard…