Item 225 DB PUHY P T Y S KMU A BS U11 E2 3.pdf
PDF 17 MB Posted
- Attached to
- TRAINING VESSEL FREEDOM STAR(TVFS) FY25 DRY DOCK
- Solicitation number
- 6933A225Q000001
About this file
This appears to be a solicitation for dry dock repairs for the Training Vessel Freedom Star (TVFS) for FY25. The Department of Transportation Maritime Administration is seeking industrial support through a firm fixed price purchase order, with work to be performed at the contractor's shipyard. Due to insurance policy restrictions and navigation limits, contractors must be located between Philadelphia, PA and Savannah, GA, within 10 miles offshore.
A site visit is scheduled for December 10, 2024, at 10:00 AM EST at the Seafarers Harry Lundeberg School of Seamanship in Piney Point, Maryland. This will be the only site visit conducted, and attendance is important for understanding the work environment and specific requirements. Quoters must submit pricing for all materials, dry dock services, equipment, and labor using the vendor price sheet (Attachment II), with specifications detailed in the Statement of Work (Attachment I). All documentation should be submitted to Karen.tempest@dot.gov.
View the file
Other files
Show 40 more
Latest 50 of 71 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2 - 175
Y (K) SERIES U11 2nd
MEE15K058
OUTDOOR UNITS
I.Y SERIES
1. SPECIFICATIONS........................................................................................................................................... 2 - 176
2. EXTERNAL DIMENSIONS .............................................................................................................................. 2 - 203
3. CENTER OF GRAVITY ................................................................................................................................... 2 - 234
4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 2 - 235
5. SOUND LEVELS ............................................................................................................................................. 2 - 240
6. VIBRATION LEVEL ......................................................................................................................................... 2 - 247
7. OPERATION TEMPERATURE RANGE.......................................................................................................... 2 - 248
8. CAPACITY TABLES ........................................................................................................................................ 2 - 249
8-1. Selection of Cooling/Heating Units .......................................................................................................... 2 - 250 8-2. Correction by temperature ....................................................................................................................... 2 - 260 8-3. Correction by total indoor......................................................................................................................... 2 - 288 8-4. Correction by refrigerant piping length..................................................................................................... 2 - 295 8-5. Correction at frost and defrost ................................................................................................................. 2 - 298
9. OPTIONAL PARTS.......................................................................................................................................... 2 - 299
9-1. JOINT ...................................................................................................................................................... 2 - 299 9-2. HEADER.................................................................................................................................................. 2 - 300 9-3. OUTDOOR TWINNING KIT..................................................................................................................... 2 - 301
0000002881.BOOK 175 ページ 2016年2月18日 木曜日 午後4時31分
1. SPECIFICATIONS U11 2nd
MEE15K058 2 - 176
Y
K
I.Y SERIES1. SPECIFICATIONS
Outdoor Model PUHY-P72TKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 72,000
(Nominal) kW 21.1
Power input kW 5.06
(208-230) Current input A 15.6-14.1
(Rated) BTU/h 69,000 kW 20.2
Power input kW 4.58 4.79
(208-230) Current input A 14.1-12.7 14.7-13.3
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 80,000
(Nominal) kW 23.4
Power input kW 5.62
(208-230) Current input A 17.3-15.6
(Rated) BTU/h 76,000 kW 22.3
Power input kW 5.04 5.36
(208-230) Current input A 15.5-14.0 16.5-14.9
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P72/1~15
Sound pressure level (measured in anechoic room) dB <A> 58.0
Refrigerant Liquid pipe in. (mm) 3/8 (9.52) Brazed piping diameter Gas pipe in. (mm) 7/8 (22.2) Brazed
Minimum Circuit Ampacity A 25-23
Maximum Overcurrent Protection A 42-38
FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175
L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor
Motor output kW 0.92
*3 External static press. 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 5.5 x 1
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 mm 1,650 x 920 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection
Fan motor Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R319
Wiring KE94C645
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 176 ページ 2016年2月18日 木曜日 午後4時31分
2 - 177
Y (K
MEE15K058
Outdoor Model PUHY-P96TKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 96,000
(Nominal) kW 28.1
Power input kW 7.00
(208-230) Current input A 21.5-19.5
(Rated) BTU/h 92,000 kW 27.0
Power input kW 6.35 6.62
(208-230) Current input A 19.5-17.7 20.4-18.4
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 108,000
(Nominal) kW 31.7
Power input kW 7.47
(208-230) Current input A 23.0-20.8
(Rated) BTU/h 103,000 kW 30.2
Power input kW 6.79 7.04
(208-230) Current input A 20.9-18.9 21.7-19.6
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/1~20
Sound pressure level (measured in anechoic room) dB <A> 58.0
Refrigerant Liquid pipe in. (mm) 3/8 (9.52) Brazed (1/2 (12.7) Brazed, the farthest pipe length >= 90 m) piping diameter Gas pipe in. (mm) 7/8 (22.2) Brazed
Minimum Circuit Ampacity A 34-31
Maximum Overcurrent Protection A 57-52
FAN Type x Quantity Propeller fan x 1
Airflow rate cfm 6,200 m3/min 175
L/s 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor
Motor output kW 0.92
*3 External static press. 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 7.1 x 1
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection
Fan motor Thermal switch
Refrigerant Type x original charge R410A x 25 lbs + 6 oz (11.5 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 532 (241)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R320
Wiring KE94C647
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 177 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 178
Y
K
Outdoor Model PUHY-P120TKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 120,000
(Nominal) kW 35.2
Power input kW 9.09
(208-230) Current input A 28.0-25.3
(Rated) BTU/h 114,000 kW 33.4
Power input kW 8.56 8.27
(208-230) Current input A 26.4-23.8 25.5-23.0
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 135,000
(Nominal) kW 39.6
Power input kW 10.28
(208-230) Current input A 31.7-28.6
(Rated) BTU/h 129,000 kW 37.8
Power input kW 9.46 9.57
(208-230) Current input A 29.1-26.3 29.5-26.6
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/1~26
Sound pressure level (measured in anechoic room) dB <A> 60.0
Refrigerant Liquid pipe in. (mm) 3/8 (9.52) Brazed (1/2 (12.7) Brazed, the farthest pipe length >= 40 m) piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Minimum Circuit Ampacity A 45-42
Maximum Overcurrent Protection A 73-67
FAN Type x Quantity Propeller fan x 2
Airflow rate cfm 11,300 m3/min 320
L/s 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor
Motor output kW 0.92+0.92
*3 External static press. 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 8.1 x 1
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection
Fan motor Thermal switch
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R321
Wiring KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 178 ページ 2016年2月18日 木曜日 午後4時31分
2 - 179
Y (K
MEE15K058
Outdoor Model PUHY-P144TKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 144,000
(Nominal) kW 42.2
Power input kW 11.84
(208-230) Current input A 36.5-33.0
(Rated) BTU/h 137,000 kW 40.2
Power input kW 11.13 10.79
(208-230) Current input A 34.3-31.0 33.2-30.0
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 160,000
(Nominal) kW 46.9
Power input kW 12.47
(208-230) Current input A 38.4-34.7
(Rated) BTU/h 152,000 kW 44.5
Power input kW 11.49 11.61
(208-230) Current input A 35.4-32.0 35.8-32.3
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/1~31
Sound pressure level (measured in anechoic room) dB <A> 61.0
Refrigerant Liquid pipe in. (mm) 1/2 (12.7) Brazed piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Minimum Circuit Ampacity A 53-49
Maximum Overcurrent Protection A 88-80
FAN Type x Quantity Propeller fan x 2
Airflow rate cfm 11,300 m3/min 320
L/s 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor
Motor output kW 0.92+0.92
*3 External static press. 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 10.6 x 1
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection
Fan motor Thermal switch
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R321
Wiring KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 179 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 180
Y
K
Outdoor Model PUHY-P168TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 168,000
(Nominal) kW 49.2
Power input kW 12.71
(208-230) Current input A 39.1-35.4
(Rated) BTU/h 161,000 kW 47.2
Power input kW 11.95 11.58
(208-230) Current input A 36.8-33.3 35.7-32.2
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 188,000
(Nominal) kW 55.1
Power input kW 14.02
(208-230) Current input A 43.2-39.1
(Rated) BTU/h 179,000 kW 52.5
Power input kW 13.16 12.80
(208-230) Current input A 40.5-36.7 39.4-35.7
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/1~36
Sound pressure level (measured in anechoic room) dB <A> 61.0
Refrigerant Liquid pipe in. (mm) 5/8 (15.88) Brazed piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Set Model
Model PUHY-P72TKMU-A (-BS) PUHY-P96TKMU-A (-BS)
Minimum Circuit Ampacity A 25-23 34-31
Maximum Overcurrent Protection A 42-38 57-52
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Airflow rate cfm 6,200 6,200 m3/min 175 175
L/s 2,920 2,920
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 5.5 x 1 7.1 x 1
Case heater kW - -
Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type) Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 mm 1,650 x 920 x 740 1,650 x 1,220 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg) R410A x 25 lbs + 6 oz (11.5 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195) 532 (241)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 3/8 (9.52) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 7/8 (22.2) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R325
Wiring KE94C645 KE94C647
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y100CBK3 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 180 ページ 2016年2月18日 木曜日 午後4時31分
2 - 181
Y (K
MEE15K058
Outdoor Model PUHY-P192TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 192,000
(Nominal) kW 56.3
Power input kW 14.81
(208-230) Current input A 45.6-41.3
(Rated) BTU/h 183,000 kW 53.6
Power input kW 14.04 13.39
(208-230) Current input A 43.3-39.1 41.2-37.3
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 215,000
(Nominal) kW 63.0
Power input kW 16.91
(208-230) Current input A 52.1-47.1
(Rated) BTU/h 205,000 kW 60.1
Power input kW 16.00 15.31
(208-230) Current input A 49.3-44.6 47.2-42.7
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/1~41
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe in. (mm) 5/8 (15.88) Brazed piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Set Model
Model PUHY-P72TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 25-23 45-42
Maximum Overcurrent Protection A 42-38 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2
Airflow rate cfm 6,200 11,300 m3/min 175 320
L/s 2,920 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 5.5 x 1 8.1 x 1
Case heater kW - -
Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type) Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 920 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R326
Wiring KE94C645 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y100CBK3 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2,CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 181 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 182
Y
K
Outdoor Model PUHY-P216TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 216,000
(Nominal) kW 63.3
Power input kW 16.90
(208-230) Current input A 52.1-47.1
(Rated) BTU/h 206,000 kW 60.4
Power input kW 16.09 15.21
(208-230) Current input A 49.6-44.8 46.9-42.4
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 243,000
(Nominal) kW 71.2
Power input kW 19.26
(208-230) Current input A 59.4-53.7
(Rated) BTU/h 232,000 kW 68.0
Power input kW 18.40 17.27
(208-230) Current input A 56.7-51.3 53.2-48.1
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~46
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe in. (mm) 5/8 (15.88) Brazed piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Set Model
Model PUHY-P96TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 34-31 45-42
Maximum Overcurrent Protection A 57-52 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2
Airflow rate cfm 6,200 11,300 m3/min 175 320
L/s 2,920 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 7.1 x 1 8.1 x 1
Case heater kW - -
Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type) Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 25 lbs + 6 oz (11.5 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 532 (241) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R327
Wiring KE94C647 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y100CBK3 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2,CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 182 ページ 2016年2月18日 木曜日 午後4時31分
2 - 183
Y (K
MEE15K058
Outdoor Model PUHY-P240TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 240,000
(Nominal) kW 70.3
Power input kW 19.12
(208-230) Current input A 58.9-53.3
(Rated) BTU/h 228,000 kW 66.8
Power input kW 18.28 17.13
(208-230) Current input A 56.3-50.9 52.8-47.7
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 270,000
(Nominal) kW 79.1
Power input kW 21.86
(208-230) Current input A 67.4-60.9
(Rated) BTU/h 258,000 kW 75.6
Power input kW 20.70 19.78
(208-230) Current input A 63.8-57.7 61.0-55.1
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 63.0
Refrigerant Liquid pipe in. (mm) 5/8 (15.88) Brazed piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Set Model
Model PUHY-P120TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 45-42 45-42
Maximum Overcurrent Protection A 73-67 73-67
FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 11,300 11,300 m3/min 320 320
L/s 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92+0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.1 x 1 8.1 x 1
Case heater kW - -
Lubricant MEL32 MEL32
External finish Pre-coated galvanized steel sheet (+powder coating for -BS type) Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 697 (316) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 1/2 (12.7) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 1-1/8 (28.58) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R328
Wiring KE94C649 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y100CBK3 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2,CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 183 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 184
Y
K
Outdoor Model PUHY-P264TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 264,000
(Nominal) kW 77.4
Power input kW 20.35
(208-230) Current input A 62.7-56.7
(Rated) BTU/h 252,000 kW 73.9
Power input kW 19.39 18.29
(208-230) Current input A 59.8-54.0 56.4-51.0
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 295,000
(Nominal) kW 86.5
Power input kW 23.11
(208-230) Current input A 71.2-64.4
(Rated) BTU/h 281,000 kW 82.4
Power input kW 22.07 20.72
(208-230) Current input A 68.0-61.5 63.9-57.7
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 63.5
Refrigerant Liquid pipe in. (mm) 3/4 (19.05) Brazed piping diameter Gas pipe in. (mm) 1-3/8 (34.93) Brazed
Set Model
Model PUHY-P72TKMU-A (-BS) PUHY-P72TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 25-23 25-23 45-42
Maximum Overcurrent Protection A 42-38 42-38 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 2
Airflow rate cfm 6,200 6,200 11,300 m3/min 175 175 320
L/s 2,920 2,920 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 5.5 x 1 5.5 x 1 8.1 x 1
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
External finish Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg) R410A x 19 lbs + 13 oz (9.0 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195) 430 (195) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 3/8 (9.52) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R329
Wiring KE94C645 KE94C645 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y300CBK2 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2,CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 184 ページ 2016年2月18日 木曜日 午後4時31分
2 - 185
Y (K
MEE15K058
Outdoor Model PUHY-P288TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 288,000
(Nominal) kW 84.4
Power input kW 22.39
(208-230) Current input A 69.0-62.4
(Rated) BTU/h 275,000 kW 80.6
Power input kW 21.33 20.13
(208-230) Current input A 65.7-59.4 62.0-56.1
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 323,000
(Nominal) kW 94.7
Power input kW 25.36
(208-230) Current input A 78.2-70.7
(Rated) BTU/h 308,000 kW 90.3
Power input kW 24.27 22.69
(208-230) Current input A 74.8-67.6 69.9-63.2
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 64.0
Refrigerant Liquid pipe in. (mm) 3/4 (19.05) Brazed piping diameter Gas pipe in. (mm) 1-3/8 (34.93) Brazed
Set Model
Model PUHY-P72TKMU-A (-BS) PUHY-P96TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 25-23 34-31 45-42
Maximum Overcurrent Protection A 42-38 57-52 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 2
Airflow rate cfm 6,200 6,200 11,300 m3/min 175 175 320
L/s 2,920 2,920 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 5.5 x 1 7.1 x 1 8.1 x 1
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
External finish Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 920 x 740 1,650 x 1,220 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg) R410A x 25 lbs + 6 oz (11.5 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195) 532 (241) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 3/8 (9.52) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R330
Wiring KE94C645 KE94C647 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y300CBK2 joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2,CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 185 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 186
Y
K
Outdoor Model PUHY-P312TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 312,000
(Nominal) kW 91.4
Power input kW 24.87
(208-230) Current input A 76.7-69.3
(Rated) BTU/h 297,000 kW 87.0
Power input kW 23.70 22.36
(208-230) Current input A 73.0-66.1 68.9-62.3
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 350,000
(Nominal) kW 102.6
Power input kW 28.71
(208-230) Current input A 88.5-80.0
(Rated) BTU/h 334,000 kW 97.9
Power input kW 27.53 25.64
(208-230) Current input A 84.9-76.7 79.0-71.5
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 64.5
Refrigerant Liquid pipe in. (mm) 3/4 (19.05) Brazed piping diameter Gas pipe in. (mm) 1-3/8 (34.93) Brazed
Set Model
Model PUHY-P72TKMU-A (-BS) PUHY-P120TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 25-23 45-42 45-42
Maximum Overcurrent Protection A 42-38 73-67 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 6,200 11,300 11,300 m3/min 175 320 320
L/s 2,920 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92+0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 5.5 x 1 8.1 x 1 8.1 x 1
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
External finish Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 36-1/4 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 920 x 740 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 19 lbs + 13 oz (9.0 kg) R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 430 (195) 697 (316) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R331
Wiring KE94C645 KE94C649 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y300CBK2 joint: CMY-Y102SS/LS-G2,CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 186 ページ 2016年2月18日 木曜日 午後4時31分
2 - 187
Y (K
MEE15K058
Outdoor Model PUHY-P336TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 336,000
(Nominal) kW 98.5
Power input kW 27.21
(208-230) Current input A 83.9-75.8
(Rated) BTU/h 320,000 kW 93.8
Power input kW 25.82 24.57
(208-230) Current input A 79.6-72.0 75.7-68.5
Temp. range of Indoor W.B. 59~75°F (15~24°C) cooling Outdoor D.B. 23~115°F (-5~46°C)
Heating capacity *2 BTU/h 378,000
(Nominal) kW 110.8
Power input kW 31.73
(208-230) Current input A 97.8-88.4
(Rated) BTU/h 361,000 kW 105.8
Power input kW 30.61 28.14
(208-230) Current input A 94.4-85.3 86.7-78.4
Temp. range of Indoor D.B. 59~81°F (15~27°C) heating Outdoor W.B. -4~60°F (-20~15.5°C)
Indoor unit Total capacity 50~130% of outdoor unit capacity
Model/Quantity P06~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 64.5
Refrigerant Liquid pipe in. (mm) 3/4 (19.05) Brazed piping diameter Gas pipe in. (mm) 1-5/8 (41.28) Brazed
Set Model
Model PUHY-P96TKMU-A (-BS) PUHY-P120TKMU-A (-BS) PUHY-P120TKMU-A (-BS)
Minimum Circuit Ampacity A 34-31 45-42 45-42
Maximum Overcurrent Protection A 57-52 73-67 73-67
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 6,200 11,300 11,300 m3/min 175 320 320
L/s 2,920 5,330 5,330
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.92 0.92+0.92 0.92+0.92
*3 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 7.1 x 1 8.1 x 1 8.1 x 1
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
External finish Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type) Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension H x W x D in. 64-31/32 x 48-1/16 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 64-31/32 x 68-29/32 x 29-5/32 mm 1,650 x 1,220 x 740 1,650 x 1,750 x 740 1,650 x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-current protection Over-current protection Over-current protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 25 lbs + 6 oz (11.5 kg) R410A x 26 lbs + 1 oz (11.8 kg) R410A x 26 lbs + 1 oz (11.8 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 532 (241) 697 (316) 697 (316)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe in. (mm) 3/8 (9.52) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed distributor Gas pipe in. (mm) 7/8 (22.2) Brazed 1-1/8 (28.58) Brazed 1-1/8 (28.58) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94R332
Wiring KE94C647 KE94C649 KE94C649
Standard Document Installation Manual attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-Y300CBK2 joint: CMY-Y102SS/LS-G2,CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Notes: Unit converter
1.Cooling conditions (Test conditions are based on AHRI 1230) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.External static pressure option is available (0.12 in.WG, 0.24 in.WG/30 Pa, 60 Pa).
BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg /0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000002881.BOOK 187 ページ 2016年2月18日 木曜日 午後4時31分
MEE15K058 2 - 188
Y
K
Outdoor Model PUHY-P360TSKMU-A (-BS)
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 360,000
(Nominal) kW 105.5
Power input kW 29.65
(…