531-325 - Drawings-16-E5.pdf

PDF 5 MB Posted

Attached to
Y1DZ--TIERED EVALS - Construct Primary Care/Mental Health Building Minor Construction - Boise 531-325
Solicitation number
36C77624R0096
Issued by

About this file

This document is a set of electrical drawings and specifications for the Construct Primary Care/Mental Health Building Minor Construction project at the Boise VA Medical Center, as part of Federal Contract Opportunity 36C77624R0096. The drawings provide details on the electrical system design, including electrical schedules, legends, one-line diagrams, and roof plans for the photovoltaic (PV) solar system. Key details include:

The PV system will consist of two 14.4 kW, 208V, 3-phase, transformerless inverters with a total capacity of 28.8 kW. The system will utilize 400W monocrystalline PV modules with DC optimizers. The PV system will be interconnected to the facility's electrical distribution system through a dedicated 200A panel. Detailed wiring diagrams, voltage drop calculations, and equipment schedules are provided. The drawings also specify labeling and safety requirements for the PV system.

View the file

Other files

File Type Posted
0005 - Tech Questions Tracker - Boise PCMH - 8-7-24.pdf PDF
36C77624R0096 0005.pdf PDF
36C77624R0096 0004.pdf PDF
0004 - Tech Questions Tracker - Boise PCMH - 8-5-24.pdf PDF
0004 - Brand Name Justification.pdf PDF
36C77624R0096 0003.pdf PDF
0003 - Tech Questions Tracker - Boise PCMH - 8-1-24.pdf PDF
36C77624R0096 0002.pdf PDF
0001 - Site Visit Sign-in - 7-16-24.pdf PDF
36C77624R0096 0001.pdf PDF
531-325 - Drawings-14-E3.pdf PDF
531-325 - Drawings-07-A2.pdf PDF
531-325 - SOW 4-15-24.pdf PDF
531-325 - Drawings-05-S1.pdf PDF
531-325 - Specs-Vol-1.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
531-325 - Drawings-09-A4.pdf PDF
531-325 - Drawings-03-C2.pdf PDF
Division Cost Breakdown.xlsx XLSX spreadsheet
531-325 - Drawings-15-E4.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Site Visit Instructions.pdf PDF
531-325 - Specs-Appx-B.pdf PDF
531-325 - Drawings-04-L1.pdf PDF
531-325 - Specs-Vol-2.pdf PDF
531-325 - Drawings-10-M1.pdf PDF
531-325 - Specs-Appx-A.pdf PDF
Site Visit Map.pdf PDF
531-325 - Drawings-01-G1.pdf PDF
RFP 36C77624R0096.docx DOCX document
531-325 - Drawings-06-A1.pdf PDF
531-325 - Drawings-02-C1.pdf PDF
531-325 - Drawings-11-P1.pdf PDF
531-325 - Drawings-13-E2.pdf PDF
531-325 - Drawings-08-A3.pdf PDF
531-325 - Specs-Appx-C.pdf PDF
531-325 - Specs-Appx-E.pdf PDF
DBA Wage Rates - Ada County - 01-12-24.pdf PDF
531-325 - Drawings-12-E1.pdf PDF
531-325 - Specs-Appx-F.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SCHEDULES

E-603

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021

BOISE VA MEDICAL CENTER - BOISE, ID

531-325 A/E:

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590 - 2118

RAY SPEES, PRESIDENT

Approved:

Approved: CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

LRL / BJR JPS / FEB 201 OF 206

ELECTRICAL SCHEDULES

E-604

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021

BOISE VA MEDICAL CENTER - BOISE, ID

531-325 A/E:

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590 - 2118

RAY SPEES, PRESIDENT

Approved:

Approved: CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

LRL / BJR JPS / FEB 202 OF 206

NOTE: NOT ALL SYMBOLS

OR ABBREVIATIONS IN

LEGENDS ARE NECESSARILY

USED ON THIS PROJECT.

M

DC

AC

DC

DC

DC

AC

DC

AC

DC

AC

SS

XX

XX

XX

XX

XX

XX

GROUND

PHOTOVOLTAIC DEVICE SYMBOLS

DC COMBINER

J-BOX AC

J-BOX DC

METER BASE

MONITOR RECEPTACLE

MICRO INVERTOR WITH TWO INPUTS

MICRO INVERTOR WITH FOUR INPUTS

MODULE

OPTIMIZER

PDU

TL INVERTOR

TL INVERTOR

DISCONNECT

GRA

D

1C

1B

1A

1D E.X

E4.1

E4.2

E6.1

N

E

S

W

POWER SYMBOLS

DUPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON

'A' MOUNTED +4" ABOVE COUNTER BACKSPLASH, TO CENTER

'G' GFI RECEPTACLE

'WP' WEATHERPROOF RECEPTACLE COVER WITH GFCI

RECEPTACLE

'WC' WATER COOLER CONNECTION CONCEALED

BEHIND WATER COOLER

'DW' DISHWASHER CONNECTION BELOW COUNTER

'R' REFRIGERATOR RECEPTACLE, +48" AFF

RELAY

DUPLEX RECEPTACLE, EMERGENCY POWER, NEMA 5-20R, +18" AFF UON

DISCONNECT SWITCH

COMBINATION MAGNETIC MOTOR STARTER/DISCONNECT SWITCH

MOTOR CONNECTION

ELECTRICAL EQUIPMENT CONNECTION IDENTIFIER, REFERENCE THE

EQUIPMENT SCHEDULE FOR REQUIRED DISCONNECTS AND FEEDERS

QUADRAPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON

POWER POLE

FLUSH FLOOR BOX WITH SINGLE RECEPTACLE, NEMA 5-20R

FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE, NEMA 5-20R

SPECIAL RECEPTACLE, NEMA CONFIGURATION AS INDICATED

'M' MICROWAVE RECEPTACLE, +66" AFF

THERMOSTAT, MOUNT +48" UNLESS OTHERWISE NOTED

MECHANICAL OR KITCHEN SCHEDULE EQUIPMENT IDENTIFIER

MANUAL MOTOR STARTERM

'V' VENDING MACHINE RECEPTACLE, +48" AFF

COMBINATION HEAT LAMP AND EXHAUST FAN

ELECTRIC WALL HEATER

INSTANTANEOUS HOT WATER HEATER

ELECTRIC HAND DRYER, MOUNTED +48" TO BOTTOM OF

DESCRIPTION

OTHERWISE +48" AFF TO CENTER WHERE NO COUNTER

'WD' COMBINATION WASHER DRYER RECEPTACLE, +48" AFF

FUSED DISCONNECT SWITCH, SIZE, RATINGS AND FUSING

ISOLATED GROUND RECEPTACLE, NEMA 5-20R, +18" AFF UON

CEILING MOUNTED RECEPTACLE, NEMA 5-20R, UON

IS PRESENT

DUPLEX RECEPTACLE, SPLIT WIRED, NEMA 5-20R, +18" AFF UON

AS INDICATED

OUTLET BOX

ISOLATED GROUND QUADRAPLEX RECEPTACLE, NEMA 5-20R

+18" AFF UON

'GR' GARBAGE DISPOSAL RECEPTACLE

PROVIDE ABOVE COUNTER ON/OFF SWITCH

ELECTRICAL EQUIPMENT CONNECTION POINT, FIELD VERIFY

EXACT LOCATION

ELECTRIC BASEBOARD HEATER

HEAT TAPE IN ROOF DRAIN (BY DIV 16/DIV26) ROUTED TO

BELOW GRADE, OR TO WARM SPACE BELOW.

'ACLV' AUTOCLAVE RECEPTACLE, +48" AFF

LOW VOLTAGE POWER SUPPLY (BY OTHERS)

5-30R

'USB' RECEPTACLE WITH USB CHARGING PORT

IG

IG

TOGGLE MOTOR STARTER

FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE, EMERGENCY POWER,

CIRCUIT BREAKER CONNECTION

SIMPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON

MOTOR STARTER

SHADE CONTROL

JUNCTION BOX

WITH GFCI RECEPTACLE

'C' MOUNTED +24" AFF IN WALL BEHIND CASEWORK. CUT-OUT IN

CASEWORK FOR ACCESS BY OTHERS

NEMA 5-20R

'LCP' CONTROLLED BY LIGHTING CONTROL SYSTEM FOR ENERGY

CODE COMPLIANCE

GROUND WELL

GENERATOR REMOTE ANNUNCIATER

KEYNOTE IDENTIFIER, REFERENCE THE NUMBERED KEYNOTES

GENERAL SYMBOLS

ON EACH DRAWING.

THE BOTTOM NUMBER INDICATES THE DRAWING REFERENCE.

DETAIL IDENTIFIER, TOP NUMBER INDICATES THE DETAIL REFERENCE,

CONNECTION TO EXISTING ELECTRICAL SYSTEMS

CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-DOWN

CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-UP

ELECTRICAL DEVICE, TO BE REMOVED (DEMOLISHED)

ELECTRICAL DEVICE, EXISTING TO REMAIN

ELEVATION IDENTIFIER, CENTER NUMBER INDICATES THE

REFERENCE DRAWING, LETTERS INDICATE NORTH, SOUTH,

EAST, OR WEST ELEVATION.

ELECTRICAL REVISION

ELECTRICAL REVISION NUMBER

MATCHLINE - VIEW CONTINUED ON SAME SHEET -

SHADED SIDE IDENTIFIES CURRENT VIEW

MATCHLINE - VIEW CONTINUED ON NEW SHEET

- SHADED SIDE IDENTIFIES CURRENT SHEET

PHOTO OF EXISTING CONDITIONS

INTERIOR ELEVATION - ELEVATION NUMBER

DENOTED IN ARROW AND SHEET NUMBER

DENOTED IN BOX

COMBINATION MAGNETIC MOTOR STARTER/DISCONNECT SWITCH

MANUAL PUSHBUTTON, NORMALLY CLOSED

MANUAL PUSHBUTTON, NORMALLY OPEN

DISCONNECT SWITCH WITH SEPARATE MOTOR STARTER

'V' DENOTES VOLTMETER

'A' DENOTES AMMETER

METER, 'M' DENOTES ELECTRONIC KWH/KW METER

NORMALLY CLOSED CONTACTOR/RELAY

NORMALLY OPEN CONTACTOR/RELAY

MOTOR CONNECTION

TRANSFORMER

TRANSFER SWITCH, MANUAL OR AUTOMATIC

M

DISCONNECT SWITCH

GROUND ELECTRODE

DIAGRAMATIC SYMBOLS

FEEDER DESIGNATOR, REFERENCE THE FEEDER SCHEDULE

FOR CONDUIT AND RACEWAY REQUIREMENTS

CIRCUIT BREAKER, SIZE AS INDICATED

SWITCH, SIZE AS INDICATED

FUSE, SIZE AS INDICATED

FUSIBLE SWITCH, FUSE AND SWITCH SIZE AS INDICATED

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

CONNECTION TO REMOTE DEVICE

WIRING CONNECTION

MAGNETIC MOTOR STARTER

CIRCUIT BREAKER WITH DRAWOUT FEATURE

GENERATION CONNECTION

SOFT STARTER OR VARIABLE FREQUENCY DRIVE (VFD)

100N

GROUND FAULT INTERRUPT

AUTOMATIC TRANSFER SWITCH

CURRENT TRANSFORMER

FIRE/SMOKE DAMPER

FULL VOLTAGE NON-REVERSING

GROUND

HAND-OFF-AUTOMATIC

INTERMEDIATE DISTRIBUTION FRAME/AREA

INTERMEDIATE METAL CONDUIT

MAIN DISTRIBUTION FRAME/AREA

ELECTRICAL ABBREVIATIONS

CONDUIT AND WIRING

CABLE TV

CIRCUIT

CEILING

CONDUIT ONLY

DIAMETER

DISTRIBUTION

ELECTRICAL METALLIC TUBING

FIBER OPTIC

FUSED SWITCH

MAXIMUM

MINIMUM

AS REQUIRED

MIN

MDF/MDA

MAX

IMC

IDF/IDA

HOA

GFI

G, GND

FVNR

FSD

FS

FO

EMT

DIST

DIA

CO

CLG

CT

CKT

CATV

C

ATS

AR

2S2W (R)

(E)

XFMR

W/O W/

WP

VFSC

VFD

UON

UGT

UGP

UG

TYP

TTB

SWBD

SW

ST

SSRV

SPST

SP

SC

REQ'D

PNL

SINGLE POLE, SINGLE THROW

SOLID STATE REDUCED VOLTAGE

TELEPHONE TERMINAL BOARD

UNDERGROUND POWER

UNDERGROUND TELEPHONE

UNLESS OTHERWISE NOTED

VARIABLE FREQUENCY SPEED CONTROLLER

EXISTING TO REMAIN

EXISTING TO BE RELOCATED

TWO-SPEED TWO-WINDING

PANEL

REQUIRED

SCREW COVER

SPARE

SHUNT TRIP

SWITCH

SWITCHBOARD

TYPICAL

UNDERGROUND

WEATHERPROOF

WITH

WITHOUT

TRANSFORMER

OVERHEAD POWEROHP

EUH ELECTRIC UNIT HEATER

ELECTRIC WATER HEATEREWH

OVERHEADOH

NORMALLY OPENNO

LONG TIME, SHORT TIME, INSTANTANEOUSLSI

NIGHTLIGHTNL

PICK UP AND TIME DELAY

LSIG

NORMALLY CLOSED

MANUAL TRANSFER SWITCH

NC

MTS

MMS MANUAL MOTOR STARTER

DDC

OWNER FURNISHED OWNER INSTALLEDOFOI

OWNER FURNISHED CONTRACTOR INSTALLEDOFCI

(D)

AFG

AFF ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

REQUEST-TO-EXITREX

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

SILICONE AVALANCHE SURGE SUPPRESSIONSASD

AF AMP FUSE

AMP TRIPAT

MOV METAL OXIDE VARISTOR

INNERDUCTID

UFER CONCRETE ENCASED GROUNDING ELECTRODE

MEDICAL EMERGENCY SYSTEMMES

PNC PATIENT NURSE CALL

REDUCED VOLTAGE NON-REVERSINGRVNR

MOTOR CIRCUIT PROTECTORMCP

BYPASS ISOLATIONBPI

TBD TO BE DETERMINED

1P ONE POLE

2P TWO POLE

3P THREE POLE

2W TWO WIRE

3W THREE WIRE

4W FOUR WIRE

TFCI TENANT FURNISHED CONTRACTOR INSTALLED

(ER) EXISTING TO BE REPLACED

FRACTIONAL HORSEPOWERF

VARIABLE FREQUENCY DRIVE

A, AMP AMPERES

AWG AMERICAN WIRE GAUGE

CCTV

CB

CLOSED CIRCUIT TELEVISION

CIRCUIT BREAKER

DISC DISCONNECT

ELECTRIC OR ELECTRICALELEC

EMERGENCYEM

ELEVATION OR ELEVATORELEV

FULL LOAD AMPERESFLA

GROUND FAULT CIRCUIT INTERRUPTERGFCI

GALVANIZED RIGID CONDUITGRC

HERTZHZ

JUNCTION BOXJ, JB

KILOVOLT AMPERESKVA

KILOWATTKW

LV

LTG

KWH KILOWATT HOUR

LIGHTING

LOW VOLTAGE

NATIONAL ELECTRICAL CODENEC

NOT IN CONTRACTNIC

NONFUSIBLENF

NOT TO SCALENTS

OVERCURRENT PROTECTIONOCP

OVERLOADSOL

POLE,PH OR ∅ PHASEP

PVC POLY VINYL CHLORIDE

RIGID GALVANIZED STEELRGS

SPDT SINGLE POLE, DOUBLE THROW

MOTOR CONTROL CENTERMCC

MAIN CIRCUIT BREAKERMCB

MINIMUM CIRCUIT AMPSMCA

MLO MAIN LUG ONLY

VA VOLT AMPERES

W WATTS OR WIRE

ISOLATED GROUNDIG

INTERNET/CELLULAR FIRE ALARM COMMUNICATORIP-GSM

SPD SURGE PROTECTION DEVICE

LONG TIME, SHORT TIME, INSTANTANEOUS PICK

UP,TIME DELAY AND GROUND FAULT PROTECTION

DIRECT DIGITAL CONTROL (BY MECHANICAL CONTRACTOR)

GROUND FAULT PROTECTIONGFP

MM/MMF MULTIMODE FIBER

SM/SMF SINGLE MODE FIBER

INSULATED CASE CIRCUIT BREAKERICCB

BUILDING MANAGEMENT SYSTEM (BY DIV 23)BMS

LCS LIGHTING CONTROL SYSTEM

STP SHIELDED TWISTED PAIR

UTP UNSHIELDED TWISTED PAIR

(F) FUTURE, NIC

BYPASS ISOLATION BREAKERBIB

MAINTENANCE BYPASS BREAKERMBB

MAINTENANCE BYPASS BREAKERMIB

UGC UNDERGROUND COMMUNICATIONS

UGF UNDERGROUND FIRE ALARM

G

ELECTRICAL LEGEND

KA

KB

PL

S

KIRK-KEY INTERLOCK, KEY "A"

KIRK-KEY INTERLOCK, KEY "B"

KIRK-KEY SOLENOID PILOT LIGHT

KIRK-KEY SOLENOID

EXISTING TO BE REMOVED (DEMOLISHED)

'BMS' CONTROLLED BY BMS SYSTEM FOR ENERGY CODE COMPLIANCE

F L

BB

H

R

SC

RD

P

T

J J

FA

PA

OHP

UGP

UGC

NC

UGF

FO

G

FIRE ALARM WIRING, REFERENCE THE SPECIFICATIONS FOR

NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C

PUBLIC ADDRESS SYSTEM WIRING, REFERENCE THE SPECIFICATIONS

FOR NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C

OVERHEAD POWER WIRING

UNDERGROUND POWER WIRING OR DUCTBANK

UNDERGROUND COMMUNICATIONS WIRING OR DUCTBANK

NURSE CALL SYSTEM WIRING, REFERENCE THE SPECIFICATIONS

FOR NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C

ELECTRICAL SYSTEM WIRING, REFERENCE THE SPECIFICATIONS

FOR NUMBER OF CONDUCTORS AND TYPE; CONDUIT SHALL

BE 3/4" UON.

3/4"C, NO. OF TICK MARKS INDICATES NUMBER OF #12 AWG

PHASE, NEUTRAL, GROUND AND ISOLATED GROUND

CONDUCTORS; FIRST SHORT TICK MARK INDICATES NUMBER

OF PHASE CONDUCTORS, SECOND LONG TICK MARK

INDICATES NUMBER OF NEUTRAL CONDUCTORS, THIRD SHORT

TICK MARK INDICATES NUMBER OF GROUND CONDUCTORS,

FOURTH DOT INDICATES NUMBER OF IG GROUND

CONDUCTORS. EXAMPLE SHOWN 3/4"C-2#12 PHASE, 1#12

NEUTRAL, 1#12 GROUND, 1#12 ISOLATED GROUND.

WIRING DEFINITIONS

CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-DOWN

CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-UP

3/4"C-2#12+1#12 GROUND

CONDUIT STUB, SIZE AS INDICATED OR NOTED

LOW VOLTAGE SYSTEM WIRING, REFERENCE THE RACEWAY AND

WIRING SCHEDULE FOR CONDUCTOR AND CONDUIT SIZE; CONDUIT

SHALL BE 3/4" UON.

CONDUIT RUN IDENTIFIER, REFERENCE THE CONDUIT SCHEDULE#

UNDERGROUND FIBER OPTIC COMMUNICATIONS WIRING OR DUCTBANK

FIBER OPTIC COMMUNICATIONS WIRING OR DUCTBANK

OVERHEAD POWER WIRING

UGPC UNDERGROUND POWER AND COMMUNICATIONS WIRING OR DUCTBANK

F

A

O R

T

RE

B

T C.

E O

S T

A

F O

P R

E

R

ISSE IG S

NO

L

LA

EP

I D

NN

E O

H

E

NE

D

E

ET R

L

NG

I

R E

400 S. Jefferson, Suite 301 Spokane, WA 99204

(T) 509.747.1888 (F) 509.747.1872

Pennell Consulting Inc.

Electrical and Electronics

System Design www.pennellconsulting.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT

Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY001

ADDITIVE ALTERNATE 2

ELECTRICAL LEGEND

BOISE VA MEDICAL CENTER - BOISE, ID

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021 RCP KVT

CONSTRUCTION

DOCUMENTS

PANEL KEYNOTES:

BALANCED THREE PHASE AMPS: 79.94 A 99.93 A

TOTAL KVA 28.8 kVA 36 kVA

COOLING MOTOR NONCOIN/DIVERSE

HEATING KITCHEN EQUIP

RECEPTACLES NONCONTINUOUS

MOTOR CONTINUOUS 28.8 kVA 36 kVA

LIGHTING EXISTING DEMAND

LOAD CLASSIFICATION CONNECTED LOAD CALCULATED LOAD LOAD CLASSIFICATION CONNECTED LOAD CALCULATED LOAD

TOTAL AMPS: 80 A 80 A 80 A

TOTAL LOAD: 9.6 kVA 9.6 kVA 9.6 kVA

29 -- -- 1 -- -- 1 -- -- 30

27 -- -- 1 -- -- 1 -- -- 28

25 -- -- 1 -- -- 1 -- -- 26

23 -- -- 1 -- -- 1 -- -- 24

21 -- -- 1 -- -- 1 -- -- 22

19 -- -- 1 -- -- 1 -- -- 20

17 -- -- 1 -- -- 1 -- -- 18

15 -- -- 1 -- -- 1 -- -- 16

13 -- -- 1 -- -- 1 -- -- 14

11 -- -- 1 -- -- 1 -- -- 12

9 -- -- 1 -- -- 1 -- -- 10

7 -- -- 1 -- -- 1 -- -- 8

5 -- -- -- 4.8 4.8 -- -- -- 6

3 -- -- -- 4.8 4.8 -- -- -- 4

1 INVERTER 'A' 50 A 3 4.8 4.8 3 50 A INVERTER 'B' 2

CKT CIRCUIT DESCRIPTION NOTE BKR P A B C P BKR NOTE CIRCUIT DESCRIPTION CKT

NOTE:

FEEDER: 2"C,4#1/0,#6EGC,CU NEUTRAL: 100.00% LUGS: STANDARD

MOUNTING: SURFACE WIRES: 4 BUS AMPS: 125 A

FED FROM: DISC-PV PHASE: 3 MAIN BKR: MLO

ROOM: MECH PENTHOUSE 201 VOLTS: 120/208 WYE AIC: 22KA

PV1

Revisions: Date: 203 OF 206

1 2 3 4

B

C

D

E

F

G

H

I

J

K

L M

1.1 3.9

L.2

A.1

2.1 2.9

2.5

B.8

A

8:12 SLOPE8:12 SLOPE 8:12 SLOPE8:12 SLOPE

EY501

STRING A1

IN

V

E R

T E

R B

P V

IN

V

E R

T E

R A

4' - 0"

5' - 4"

STRING A2

STRING A3

STRING B2

STRING B1

4' - 6"

5' - 4"

4' - 6"

3TYP OF 26

4 TYP OF 8

4 TYP OF 14

4 TYP OF 16

0 8 164

1/8" = 1'-0"

ROOF PLAN - ELECTRICAL

A. CONTRACTOR TO VERIFY LAYOUT AND DIMENSIONS ON ROOF PRIOR

TO INSTALLATION. SYSTEM LAYOUT SHALL BE INSTALLED IN

ACCORDANCE WITH 2018 IFC SECTION 1204 AND 2017 NEC.

B. CONTRACTOR SHALL FIELD VERIFY ROUTING DC STRINGS FROM

ARRAYS TO INVERTERS.

C. RACKING LAYOUT AND ENGINEERING BY MANUFACTURER. A SHARED

RAIL SYSTEM MAY BE REQUIRED FOR ORIENTATION OF MODULES.

D. ALL WIRING LEAVING THE ARRAY AREA SHALL BE INSTALLED IN

CONDUIT.

E. MATERIALS SHALL BE UL LISTED AND LABELED.

1. PROVIDE CONDUIT AND WIRE TO CONNECT STRINGS BETWEEN ARRAYS.

2. MINIMUM 4'-0" SET BACK FROM ROOF EDGES, EVES, RIDGES, AND ROOF

MOUNTED EQUIPMENT PER IFC.

3. AWNING MOUNTED SOLAR PANELS, MOUNT 12" BELOW ROOF EDGE.

4. FLAT ROOF MOUNTED SOLAR PANELS.

5. PITCHED ROOF MOUNTED SOLAR PANELS. TYPICAL UON.

KEYPLAN

F

A

O R

T

RE

B

T C.

E O

S T

A

F O

P R

E

R

ISSE IG S

NO

L

LA

EP

I D

NN

E O

H

E

NE

D

E

ET R

L

NG

I

R E

400 S. Jefferson, Suite 301 Spokane, WA 99204

(T) 509.747.1888 (F) 509.747.1872

Pennell Consulting Inc.

Electrical and Electronics

System Design www.pennellconsulting.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT

Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY104

ADDITIVE ALTERNATE 2

ROOF PLAN - ELECTRICAL

BOISE VA MEDICAL CENTER - BOISE, ID

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021 RCP KVT

CONSTRUCTION

DOCUMENTS

GENERAL SHEET NOTES

KEY PLAN

KEY NOTES (THIS SHEET ONLY)

N

NOT TO SCALE

ROOF PLAN ISOMETRIC - PV SYSTEM

Revisions: Date:

NOT TO SCALE

SOLAR PANEL - ISOMETRIC VIEW

2 32.1 2.92.5

CONDUIT TO ELECTRICAL RM 170

CONDUIT TO EXTERIOR PV PANELS

PV1

INVERTER 'A' INVERTER 'B'

2 3

I

J

2.1 2.92.5

EY501

MECH

PENTHOUSE

P V

IN

V

E R

T E

R A

IN

V

E R

T E

R B

B

A

ELEC

C B

-N M

D P

C

B -E

M D

P

E M

D P

N M

D P

EXG MCP1

EXG PNL 1

1 2 3

DISC-PV

F

A

O R

T

RE

B

T C.

E O

S T

A

F O

P R

E

R

ISSE IG S

NO

L

LA

EP

I D

NN

E O

H

E

NE

D

E

ET R

L

NG

I

R E

400 S. Jefferson, Suite 301 Spokane, WA 99204

(T) 509.747.1888 (F) 509.747.1872

Pennell Consulting Inc.

Electrical and Electronics

System Design www.pennellconsulting.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT

Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY501

ADDITIVE ALTERNATE 2

SOLAR DETAILS

BOISE VA MEDICAL CENTER - BOISE, ID

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021 RCP KVT

CONSTRUCTION

DOCUMENTS

SCALE: 1/2" = 1'-0"

MECH PENTHOUSE 201 - EAST ELEVATION

SCALE: 1/4" = 1'-0"

MECH PENTHOUSE 201 - ENLARGED PLAN

SCALE: 1/4" = 1'-0"

ELEC 170 - ENLARGED PLAN

A. COORDINATE EXACT LOCATIONS OF EQUIPMENT WITH MEP TRADES

PRIOR TO ROUGH-IN.

1. PROVIDE THE FOLLOWING PHENOLIC LABEL ON DISCONNECT

'DISC-PV'

PHOTOVOLTAIC SYSTEM AC DISCONNECT

MAX AC OPERATING CURRENT: 80 A

NOM AC OPERATING VOLTAGE: 208 V

2. PROVIDE THE FOLLOWING STICKER LABEL:

SOLAR PV SYSTEM IS EQUIPPED

WITH RAPID SHUTDOWN

TURN RAPID SHUTDOWN

SWITCH TO THE

"OFF" POSITION TO

SHUTDOWN PV SYSTEM

AND REDUCE

SHOCK HAZARD

IN ARRAY

3. PROVIDE THE FOLLOWING STICKER LABEL:

RAPID SHUTDOWN

SWITCH FOR

SOLAR PV SYSTEM

4. PROVIDE 3/4"C WITH ONE (1) CAT5E TO OIT ROOM 402 FOR TCP/IP

COMMUNICATIONS TO INVERTER 'A'..

5. DISCONNECT 'DISC-PV' FOR INTERCONNECT WITH ELECTRICAL

SYSTEM. REFER TO ELECTRICAL ONE-LINE DIAGRAM SHEET E601.

GENERAL SHEET NOTES

KEY PLAN

KEY NOTES (THIS SHEET ONLY)

N

KEYPLAN

EY501

EY501

Revisions: Date: 205 OF 206

VOLTAGE DROP SCHEDULE

DC STRINGS ON RACKS DC HOMRUNS FROM STRING TO COMBINER AC INVERTER TO PV1 PV1 TO EQUIPMENT BUILDING

STRING

DISTANCE

(FT)

VOLTS AMPS WIRE R (Ω/1kft)

I(2)R

(WATTS)

VD

(Volts)

VD

STRING DISTANCE (FT) VOLTS AMPS WIRE R (Ω/1kft)

I(2)R

(WATTS)

VD (Volts)

VD

DC VD

VOLTS

VD (%) INVERTER DISTANCE (FT) VOLTS AMPS WIRE R (Ω/1kft)

VD

(Volts)

VD (%) PANEL

DISTANCE

(FT)

VOLTS AMPS WIRE R (Ω/1kft)

VD

(Volts)

VD (%)

VD

INV

VD INV

A1 86 400 15.0 #10 1.24 23.99 3.20 0.80% A1 90 400 15.0 #8 0.778 15.75 2.10 0.53% 5.30 1.32%

A 5 208 40 #6 0.491 0.1700 0.08%

PV1 200 208 80 #1/0 0.122 3.38 1.62%

3.55 1.71%A2 135 400 15.0 #10 1.24 37.53 5.00 1.25% A2 80 400 15.0 #8 0.778 14.00 1.87 0.47% 6.87 1.72%

A2 96 400 15.0 #10 1.24 26.78 3.57 0.89% A2 110 400 15.0 #8 0.778 19.26 2.57 0.64% 6.14 1.53%

B1 116 400 15.0 #10 1.24 32.36 4.32 1.08% B1 115 400 15.0 #8 0.778 20.13 2.68 0.67% 7.00 1.75% B 7 208 40 #6 0.491 0.2379 0.11% 3.62 1.74%

B2 65 400 15.0 #10 1.24 18.14 2.42 0.60% B2 75 400 15.0 #8 0.778 13.13 1.75 0.44% 4.17 1.04%

TOTAL I(2)R LOSSES DC STRINGS 138.80 WATTS TOTAL I(2)R LOSSES DC HOMERUNS 82.27 WATTS 221.08 WATTS DC TOTAL I(2)R LOSSES INVERTERS TO PV1 28.24 WATTS TOTAL I(2)R LOSSES PV1 TO SERVICE 467.79 WATTS 0.50 kW AC

NEC 702.12(B)(2)(3)(b) COMPLIANCE

PV total kVA AC Output 28800

PV Power Source Amps 80

MCB Rating 1200

Sum of PV & MCB 1280

Busbar Rating 1200

120% Basbar Rating 1440

NEC 702.12(B)(2)(3)(b) 1440A > 1280A

VOLTAGE DROP GROUND SIZE

100 Amps #1 83690

VD Wire Size #1/0 105600

Ratio 1.261799

100A EGC #8 16510

Min Gnd 20840

VD Gnd #6 26240

MAX PV MODULE VOLTAGE CALCULATION

OPEN CIRCUIT VOLTAGE VOC 48.96 V

TEMPERATURE COEFFICIENT OF VOC β -0.27 %/K

STC TEMPERATURE T 25 °C

BOISE, IDAHO LOW TEMP T -17.00 °C

TEMPERATURE DELTA Δ 42 °C

42°C x -0.27%/K = -0.1134 %

VDELTA = 0.1134% x 48.96 V = 5.55 V

VMAX = VOC + V DELTA = 54.51 V

P401 MAX VOC INPUT = 60 V

3P-50A

3P-50A

AC

DC

AC

DC

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

D C

2"C,4#1/0,#6EGC,CU

1"C,3#6,1#6N, 1#10EGC,CU

40A X 1.25 = 50A

3/4"C,2#8,1#10G,CU

16 X 400W = 6.4KW

6.4kW / 400V = 16A

1.56 X 16A = 24.96A

(TYPICAL ALL STRINGS)

200A PANEL 'PV1'

NEMA 3R

TYP.

STRING

'A1'

PITCHED

ROOF

STRING

'A2'

FLAT

ROOF

TYP.

208Y/120V, 3 Ø, 4W 22kAIC

3/4"C,2#8,1#10G,CU

20 X 400W = 8KW

8kW / 400V = 20A

1.56 X 16A = 31.2A

(TYPICAL ALL STRINGS)

TYP.

STRING

'B1'

FLAT ROOF

STRING

'B2'

AWNING

c9 b9 d d e fa7 e

MECH PENTHOUSE

MECH PENTHOUSE

MECH PENTHOUSE

INVERTER 'B'

INVERTER 'A'

STRING

'A3'

FLAT

ROOF

STRING

'B1'

AWNING

STRING

'A2'

PITCHED

ROOF

TYP. 7

TYP.

TYP.

TYP.

TYP.

TYP.

10 TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

g h i j k

NOT TO SCALE

PV SYSTEM ONELINE DIAGRAM

F

A

O R

T

RE

B

T C.

E O

S T

A

F O

P R

E

R

ISSE IG S

NO

L

LA

EP

I D

NN

E O

H

E

NE

D

E

ET R

L

NG

I R

E

400 S. Jefferson, Suite 301 Spokane, WA 99204

(T) 509.747.1888 (F) 509.747.1872

Pennell Consulting Inc.

Electrical and Electronics

System Design www.pennellconsulting.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT

Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY601

ADDITIVE ALTERNATE 2

PV ONE-LINE DIAGRAM

BOISE VA MEDICAL CENTER - BOISE, ID

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

07/23/2021 RCP KVT

CONSTRUCTION

DOCUMENTS

GENERAL SHEET NOTES

PV SYSTEM LABELING

KEY NOTES (THIS SHEET ONLY)

1. 16 MODULES AND 16 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.

2. 20 MODULES AND 20 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.

3. 8 MODULES AND 8 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.

4. 14 MODULES AND 14 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.

5. 6 MODULES AND 6 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.

6. 400 WATT MONO-CRYSTALLINE PV MODULE, Q-CELLS Q.PEAK DUO L-G7 400:

PMAX = 400 Wdc VMAX = 41.04 Vdc IMAX = 9.75 Idc VOC = 49.00 Vdc ISC = 10.24 Adc

7. 400 WATT OPTIMIZER FOR EACH PV MODULE. SOLAREDGE P401.

MAX INPUT POWER = 400 Wdc MAX INPUT VOLTAGE = 60.0 Vdc MAX OUTPUT VOLTAGE = 60.0 Vdc MAX OUTPUT CURRENT = 15.0 Adc

8. WP JUNCTION BOX TO TRANSITION FROM #10 PV WIRE TO USE CABLE OR

CONDUIT AND WIRE.

9. 14.4 kW, 208Y/120V, 3∅, 4W TRANFORMERLESS (NON-ISOLATED) INVERTER

WITH INTEGRAL DC DISCONNECT SWITCH AND GROUND FAULT

DETECTION INTERRUPTER. SOLAREDGE SE #14.4K-US:

RATED AC OUTPUT = 14400 VAac MAXIMUM CONTINUOUS CURRENT (PER PHASE) = 40 Aac AC OUTPUT VOLTAGE = 208Y/120V Vac MAX DC POWER INPUT = 19400 Wdc NOMINAL INPUT VOLTAGE DC + TO DC - = 400 Vdc

10. INSTALL MANUFACTURER FURNISHED #10 PV WIRE PER MANUFACTURER'S

RECOMMENDATION. ALL WIRING SHALL BE SECURED TO RACKING AND/OR

MODULE FRAMES.

11. BOND ALUMINUM FRAME OF PV MODULE BY GROUNDING CLAMPS PROVIDED

BY RACK MANUFACTURER. BONDING OF OPTIMIZERS SHALL BE MADE WITH

WEEBS. REFER TO MANUFACTURER'S INSTALLATION MANUAL FOR MORE

INFORMATION.

12. #6 BARE, CU WIRE FOR BONDING OF ALL EXPOSED METAL WITHIN THE ARRAY

AREA.

13. TO DISCONNECT 'DISC-PV'. REFERENCE SHEET E-501 FOR CONTINUATION.

14. PROVIDE 3/4"C WITH ONE (1) CAT5E CONFIGURED FOR RS-485

COMMUNICATIONS BETWEEN INVERTERS 'A', AND 'B'.

15. PROVIDE 3/4"C WITH ONE (1) CAT5E TO OIT ROOM 170 FOR TCP/IP

COMMUNICATIONS TO INVERTER 'A'.

16. PROVIDE 3/4"C WITH 2#10, 1#10EGC,CU TO CONNECT STRINGS BETWEEN

DIFFERENT ARRAYS.

a. PROVIDE THE FOLLOWING PHENOLIC LABEL:

SOLAR PV SYSTEM EQUIPPED

WITH AUTOMATIC RAPID SHUTDOWN

b. PROVIDE THE FOLLOWING PHENOLIC LABEL:

PHOTOVOLTAIC DC DISCONNECT

MAX DC CURRENT: 48 Adc NOM DC VOLTAGE: 400 Vdc

c. PROVIDE THE FOLLOWING PHENOLIC LABEL:

PHOTOVOLTAIC DC DISCONNECT

MAX DC CURRENT: 40 Adc NOM DC VOLTAGE: 400 Vdc

d. PROVIDE THE FOLLOWING STICKER LABEL TO CONDUITS:

PHOTOVOLTAIC POWER SOURCE

e. PROVIDE THE FOLLOWING STICKER LABEL TO CONDUITS:

CAUTION SOLAR CIRCUIT

f. PROVIDE THE FOLLOWING PHENOLIC LABEL:

PANEL 'PV1'

SOLAR PV CIRCUITS ONLY.

DO NOT ADD ADDITIONAL

CIRCUITS TO THIS PANEL.

g. PROVIDE THE FOLLOWING SITCKER LABEL TO 'NMDP1':

CAUTION SOLAR ELECTRIC SYSTEM CONNECTED

h. PROVIDE THE FOLLOWING PHENOLIC LABEL TO 'CB-PV':

PHOTOVOLTAIC SYSTEM AC DISCONNECT

MAX AC OPERATING CURRENT: 80 AMPS

MAX AC OPERATING VOLTAGE: 208 VOLTS

I. PROVIDE THE FOLLOWING STICKER LABEL TO 'CB-PV'::

SOLAR PV SYSTEM IS EQUIPED WITH RAPID

SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO

THE "OFF" POSITION TO SHUTDOWN PV SYSTEM

AND REDUCE SHOCK HAZARD IN ARRAY

j. PROVIDE THE FOLLING STICKER LABEL TO 'CB-PV':

RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM

k. PROVIDE THE FOLLOWING PHENOLIC LABLE TO PV BACK-

FEED CIRCUIT BREAKER IN 'NMDP1':

WARNING: POWER SOURCE OUTPUT CONNECTION.

DO NOT RELOCATE THIS OVERCURRENT DEVICE

A. MATERIALS SHALL BE UL LISTED AND LABELED.

Revisions: Date: 206 OF 206