531-325 - Drawings-16-E5.pdf
PDF 5 MB Posted
- Attached to
- Y1DZ--TIERED EVALS - Construct Primary Care/Mental Health Building Minor Construction - Boise 531-325
- Solicitation number
- 36C77624R0096
About this file
This document is a set of electrical drawings and specifications for the Construct Primary Care/Mental Health Building Minor Construction project at the Boise VA Medical Center, as part of Federal Contract Opportunity 36C77624R0096. The drawings provide details on the electrical system design, including electrical schedules, legends, one-line diagrams, and roof plans for the photovoltaic (PV) solar system. Key details include:
The PV system will consist of two 14.4 kW, 208V, 3-phase, transformerless inverters with a total capacity of 28.8 kW. The system will utilize 400W monocrystalline PV modules with DC optimizers. The PV system will be interconnected to the facility's electrical distribution system through a dedicated 200A panel. Detailed wiring diagrams, voltage drop calculations, and equipment schedules are provided. The drawings also specify labeling and safety requirements for the PV system.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SCHEDULES
E-603
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB 201 OF 206
ELECTRICAL SCHEDULES
E-604
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB 202 OF 206
NOTE: NOT ALL SYMBOLS
OR ABBREVIATIONS IN
LEGENDS ARE NECESSARILY
USED ON THIS PROJECT.
M
DC
AC
DC
DC
DC
AC
DC
AC
DC
AC
SS
XX
XX
XX
XX
XX
XX
GROUND
PHOTOVOLTAIC DEVICE SYMBOLS
DC COMBINER
J-BOX AC
J-BOX DC
METER BASE
MONITOR RECEPTACLE
MICRO INVERTOR WITH TWO INPUTS
MICRO INVERTOR WITH FOUR INPUTS
MODULE
OPTIMIZER
PDU
TL INVERTOR
TL INVERTOR
DISCONNECT
GRA
D
1C
1B
1A
1D E.X
E4.1
E4.2
E6.1
N
E
S
W
POWER SYMBOLS
DUPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON
'A' MOUNTED +4" ABOVE COUNTER BACKSPLASH, TO CENTER
'G' GFI RECEPTACLE
'WP' WEATHERPROOF RECEPTACLE COVER WITH GFCI
RECEPTACLE
'WC' WATER COOLER CONNECTION CONCEALED
BEHIND WATER COOLER
'DW' DISHWASHER CONNECTION BELOW COUNTER
'R' REFRIGERATOR RECEPTACLE, +48" AFF
RELAY
DUPLEX RECEPTACLE, EMERGENCY POWER, NEMA 5-20R, +18" AFF UON
DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER/DISCONNECT SWITCH
MOTOR CONNECTION
ELECTRICAL EQUIPMENT CONNECTION IDENTIFIER, REFERENCE THE
EQUIPMENT SCHEDULE FOR REQUIRED DISCONNECTS AND FEEDERS
QUADRAPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON
POWER POLE
FLUSH FLOOR BOX WITH SINGLE RECEPTACLE, NEMA 5-20R
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE, NEMA 5-20R
SPECIAL RECEPTACLE, NEMA CONFIGURATION AS INDICATED
'M' MICROWAVE RECEPTACLE, +66" AFF
THERMOSTAT, MOUNT +48" UNLESS OTHERWISE NOTED
MECHANICAL OR KITCHEN SCHEDULE EQUIPMENT IDENTIFIER
MANUAL MOTOR STARTERM
'V' VENDING MACHINE RECEPTACLE, +48" AFF
COMBINATION HEAT LAMP AND EXHAUST FAN
ELECTRIC WALL HEATER
INSTANTANEOUS HOT WATER HEATER
ELECTRIC HAND DRYER, MOUNTED +48" TO BOTTOM OF
DESCRIPTION
OTHERWISE +48" AFF TO CENTER WHERE NO COUNTER
'WD' COMBINATION WASHER DRYER RECEPTACLE, +48" AFF
FUSED DISCONNECT SWITCH, SIZE, RATINGS AND FUSING
ISOLATED GROUND RECEPTACLE, NEMA 5-20R, +18" AFF UON
CEILING MOUNTED RECEPTACLE, NEMA 5-20R, UON
IS PRESENT
DUPLEX RECEPTACLE, SPLIT WIRED, NEMA 5-20R, +18" AFF UON
AS INDICATED
OUTLET BOX
ISOLATED GROUND QUADRAPLEX RECEPTACLE, NEMA 5-20R
+18" AFF UON
'GR' GARBAGE DISPOSAL RECEPTACLE
PROVIDE ABOVE COUNTER ON/OFF SWITCH
ELECTRICAL EQUIPMENT CONNECTION POINT, FIELD VERIFY
EXACT LOCATION
ELECTRIC BASEBOARD HEATER
HEAT TAPE IN ROOF DRAIN (BY DIV 16/DIV26) ROUTED TO
BELOW GRADE, OR TO WARM SPACE BELOW.
'ACLV' AUTOCLAVE RECEPTACLE, +48" AFF
LOW VOLTAGE POWER SUPPLY (BY OTHERS)
5-30R
'USB' RECEPTACLE WITH USB CHARGING PORT
IG
IG
TOGGLE MOTOR STARTER
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE, EMERGENCY POWER,
CIRCUIT BREAKER CONNECTION
SIMPLEX RECEPTACLE, NEMA 5-20R, +18" AFF UON
MOTOR STARTER
SHADE CONTROL
JUNCTION BOX
WITH GFCI RECEPTACLE
'C' MOUNTED +24" AFF IN WALL BEHIND CASEWORK. CUT-OUT IN
CASEWORK FOR ACCESS BY OTHERS
NEMA 5-20R
'LCP' CONTROLLED BY LIGHTING CONTROL SYSTEM FOR ENERGY
CODE COMPLIANCE
GROUND WELL
GENERATOR REMOTE ANNUNCIATER
KEYNOTE IDENTIFIER, REFERENCE THE NUMBERED KEYNOTES
GENERAL SYMBOLS
ON EACH DRAWING.
THE BOTTOM NUMBER INDICATES THE DRAWING REFERENCE.
DETAIL IDENTIFIER, TOP NUMBER INDICATES THE DETAIL REFERENCE,
CONNECTION TO EXISTING ELECTRICAL SYSTEMS
CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-DOWN
CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-UP
ELECTRICAL DEVICE, TO BE REMOVED (DEMOLISHED)
ELECTRICAL DEVICE, EXISTING TO REMAIN
ELEVATION IDENTIFIER, CENTER NUMBER INDICATES THE
REFERENCE DRAWING, LETTERS INDICATE NORTH, SOUTH,
EAST, OR WEST ELEVATION.
ELECTRICAL REVISION
ELECTRICAL REVISION NUMBER
MATCHLINE - VIEW CONTINUED ON SAME SHEET -
SHADED SIDE IDENTIFIES CURRENT VIEW
MATCHLINE - VIEW CONTINUED ON NEW SHEET
- SHADED SIDE IDENTIFIES CURRENT SHEET
PHOTO OF EXISTING CONDITIONS
INTERIOR ELEVATION - ELEVATION NUMBER
DENOTED IN ARROW AND SHEET NUMBER
DENOTED IN BOX
COMBINATION MAGNETIC MOTOR STARTER/DISCONNECT SWITCH
MANUAL PUSHBUTTON, NORMALLY CLOSED
MANUAL PUSHBUTTON, NORMALLY OPEN
DISCONNECT SWITCH WITH SEPARATE MOTOR STARTER
'V' DENOTES VOLTMETER
'A' DENOTES AMMETER
METER, 'M' DENOTES ELECTRONIC KWH/KW METER
NORMALLY CLOSED CONTACTOR/RELAY
NORMALLY OPEN CONTACTOR/RELAY
MOTOR CONNECTION
TRANSFORMER
TRANSFER SWITCH, MANUAL OR AUTOMATIC
M
DISCONNECT SWITCH
GROUND ELECTRODE
DIAGRAMATIC SYMBOLS
FEEDER DESIGNATOR, REFERENCE THE FEEDER SCHEDULE
FOR CONDUIT AND RACEWAY REQUIREMENTS
CIRCUIT BREAKER, SIZE AS INDICATED
SWITCH, SIZE AS INDICATED
FUSE, SIZE AS INDICATED
FUSIBLE SWITCH, FUSE AND SWITCH SIZE AS INDICATED
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
CONNECTION TO REMOTE DEVICE
WIRING CONNECTION
MAGNETIC MOTOR STARTER
CIRCUIT BREAKER WITH DRAWOUT FEATURE
GENERATION CONNECTION
SOFT STARTER OR VARIABLE FREQUENCY DRIVE (VFD)
100N
GROUND FAULT INTERRUPT
AUTOMATIC TRANSFER SWITCH
CURRENT TRANSFORMER
FIRE/SMOKE DAMPER
FULL VOLTAGE NON-REVERSING
GROUND
HAND-OFF-AUTOMATIC
INTERMEDIATE DISTRIBUTION FRAME/AREA
INTERMEDIATE METAL CONDUIT
MAIN DISTRIBUTION FRAME/AREA
ELECTRICAL ABBREVIATIONS
CONDUIT AND WIRING
CABLE TV
CIRCUIT
CEILING
CONDUIT ONLY
DIAMETER
DISTRIBUTION
ELECTRICAL METALLIC TUBING
FIBER OPTIC
FUSED SWITCH
MAXIMUM
MINIMUM
AS REQUIRED
MIN
MDF/MDA
MAX
IMC
IDF/IDA
HOA
GFI
G, GND
FVNR
FSD
FS
FO
EMT
DIST
DIA
CO
CLG
CT
CKT
CATV
C
ATS
AR
2S2W (R)
(E)
XFMR
W/O W/
WP
VFSC
VFD
UON
UGT
UGP
UG
TYP
TTB
SWBD
SW
ST
SSRV
SPST
SP
SC
REQ'D
PNL
SINGLE POLE, SINGLE THROW
SOLID STATE REDUCED VOLTAGE
TELEPHONE TERMINAL BOARD
UNDERGROUND POWER
UNDERGROUND TELEPHONE
UNLESS OTHERWISE NOTED
VARIABLE FREQUENCY SPEED CONTROLLER
EXISTING TO REMAIN
EXISTING TO BE RELOCATED
TWO-SPEED TWO-WINDING
PANEL
REQUIRED
SCREW COVER
SPARE
SHUNT TRIP
SWITCH
SWITCHBOARD
TYPICAL
UNDERGROUND
WEATHERPROOF
WITH
WITHOUT
TRANSFORMER
OVERHEAD POWEROHP
EUH ELECTRIC UNIT HEATER
ELECTRIC WATER HEATEREWH
OVERHEADOH
NORMALLY OPENNO
LONG TIME, SHORT TIME, INSTANTANEOUSLSI
NIGHTLIGHTNL
PICK UP AND TIME DELAY
LSIG
NORMALLY CLOSED
MANUAL TRANSFER SWITCH
NC
MTS
MMS MANUAL MOTOR STARTER
DDC
OWNER FURNISHED OWNER INSTALLEDOFOI
OWNER FURNISHED CONTRACTOR INSTALLEDOFCI
(D)
AFG
AFF ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
REQUEST-TO-EXITREX
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
SILICONE AVALANCHE SURGE SUPPRESSIONSASD
AF AMP FUSE
AMP TRIPAT
MOV METAL OXIDE VARISTOR
INNERDUCTID
UFER CONCRETE ENCASED GROUNDING ELECTRODE
MEDICAL EMERGENCY SYSTEMMES
PNC PATIENT NURSE CALL
REDUCED VOLTAGE NON-REVERSINGRVNR
MOTOR CIRCUIT PROTECTORMCP
BYPASS ISOLATIONBPI
TBD TO BE DETERMINED
1P ONE POLE
2P TWO POLE
3P THREE POLE
2W TWO WIRE
3W THREE WIRE
4W FOUR WIRE
TFCI TENANT FURNISHED CONTRACTOR INSTALLED
(ER) EXISTING TO BE REPLACED
FRACTIONAL HORSEPOWERF
VARIABLE FREQUENCY DRIVE
A, AMP AMPERES
AWG AMERICAN WIRE GAUGE
CCTV
CB
CLOSED CIRCUIT TELEVISION
CIRCUIT BREAKER
DISC DISCONNECT
ELECTRIC OR ELECTRICALELEC
EMERGENCYEM
ELEVATION OR ELEVATORELEV
FULL LOAD AMPERESFLA
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GALVANIZED RIGID CONDUITGRC
HERTZHZ
JUNCTION BOXJ, JB
KILOVOLT AMPERESKVA
KILOWATTKW
LV
LTG
KWH KILOWATT HOUR
LIGHTING
LOW VOLTAGE
NATIONAL ELECTRICAL CODENEC
NOT IN CONTRACTNIC
NONFUSIBLENF
NOT TO SCALENTS
OVERCURRENT PROTECTIONOCP
OVERLOADSOL
POLE,PH OR ∅ PHASEP
PVC POLY VINYL CHLORIDE
RIGID GALVANIZED STEELRGS
SPDT SINGLE POLE, DOUBLE THROW
MOTOR CONTROL CENTERMCC
MAIN CIRCUIT BREAKERMCB
MINIMUM CIRCUIT AMPSMCA
MLO MAIN LUG ONLY
VA VOLT AMPERES
W WATTS OR WIRE
ISOLATED GROUNDIG
INTERNET/CELLULAR FIRE ALARM COMMUNICATORIP-GSM
SPD SURGE PROTECTION DEVICE
LONG TIME, SHORT TIME, INSTANTANEOUS PICK
UP,TIME DELAY AND GROUND FAULT PROTECTION
DIRECT DIGITAL CONTROL (BY MECHANICAL CONTRACTOR)
GROUND FAULT PROTECTIONGFP
MM/MMF MULTIMODE FIBER
SM/SMF SINGLE MODE FIBER
INSULATED CASE CIRCUIT BREAKERICCB
BUILDING MANAGEMENT SYSTEM (BY DIV 23)BMS
LCS LIGHTING CONTROL SYSTEM
STP SHIELDED TWISTED PAIR
UTP UNSHIELDED TWISTED PAIR
(F) FUTURE, NIC
BYPASS ISOLATION BREAKERBIB
MAINTENANCE BYPASS BREAKERMBB
MAINTENANCE BYPASS BREAKERMIB
UGC UNDERGROUND COMMUNICATIONS
UGF UNDERGROUND FIRE ALARM
G
ELECTRICAL LEGEND
KA
KB
PL
S
KIRK-KEY INTERLOCK, KEY "A"
KIRK-KEY INTERLOCK, KEY "B"
KIRK-KEY SOLENOID PILOT LIGHT
KIRK-KEY SOLENOID
EXISTING TO BE REMOVED (DEMOLISHED)
'BMS' CONTROLLED BY BMS SYSTEM FOR ENERGY CODE COMPLIANCE
F L
BB
H
R
SC
RD
P
T
J J
FA
PA
OHP
UGP
UGC
NC
UGF
FO
G
FIRE ALARM WIRING, REFERENCE THE SPECIFICATIONS FOR
NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C
PUBLIC ADDRESS SYSTEM WIRING, REFERENCE THE SPECIFICATIONS
FOR NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C
OVERHEAD POWER WIRING
UNDERGROUND POWER WIRING OR DUCTBANK
UNDERGROUND COMMUNICATIONS WIRING OR DUCTBANK
NURSE CALL SYSTEM WIRING, REFERENCE THE SPECIFICATIONS
FOR NUMBER OF CONDUCTORS AND TYPE, MINIMUM OF 3/4"C
ELECTRICAL SYSTEM WIRING, REFERENCE THE SPECIFICATIONS
FOR NUMBER OF CONDUCTORS AND TYPE; CONDUIT SHALL
BE 3/4" UON.
3/4"C, NO. OF TICK MARKS INDICATES NUMBER OF #12 AWG
PHASE, NEUTRAL, GROUND AND ISOLATED GROUND
CONDUCTORS; FIRST SHORT TICK MARK INDICATES NUMBER
OF PHASE CONDUCTORS, SECOND LONG TICK MARK
INDICATES NUMBER OF NEUTRAL CONDUCTORS, THIRD SHORT
TICK MARK INDICATES NUMBER OF GROUND CONDUCTORS,
FOURTH DOT INDICATES NUMBER OF IG GROUND
CONDUCTORS. EXAMPLE SHOWN 3/4"C-2#12 PHASE, 1#12
NEUTRAL, 1#12 GROUND, 1#12 ISOLATED GROUND.
WIRING DEFINITIONS
CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-DOWN
CONDUIT, FEEDER OR EQUIPMENT CIRCUITING STUB-UP
3/4"C-2#12+1#12 GROUND
CONDUIT STUB, SIZE AS INDICATED OR NOTED
LOW VOLTAGE SYSTEM WIRING, REFERENCE THE RACEWAY AND
WIRING SCHEDULE FOR CONDUCTOR AND CONDUIT SIZE; CONDUIT
SHALL BE 3/4" UON.
CONDUIT RUN IDENTIFIER, REFERENCE THE CONDUIT SCHEDULE#
UNDERGROUND FIBER OPTIC COMMUNICATIONS WIRING OR DUCTBANK
FIBER OPTIC COMMUNICATIONS WIRING OR DUCTBANK
OVERHEAD POWER WIRING
UGPC UNDERGROUND POWER AND COMMUNICATIONS WIRING OR DUCTBANK
F
A
O R
T
RE
B
T C.
E O
S T
A
F O
P R
E
R
ISSE IG S
NO
L
LA
EP
I D
NN
E O
H
E
NE
D
E
ET R
L
NG
I
R E
400 S. Jefferson, Suite 301 Spokane, WA 99204
(T) 509.747.1888 (F) 509.747.1872
Pennell Consulting Inc.
Electrical and Electronics
System Design www.pennellconsulting.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY001
ADDITIVE ALTERNATE 2
ELECTRICAL LEGEND
BOISE VA MEDICAL CENTER - BOISE, ID
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021 RCP KVT
CONSTRUCTION
DOCUMENTS
PANEL KEYNOTES:
BALANCED THREE PHASE AMPS: 79.94 A 99.93 A
TOTAL KVA 28.8 kVA 36 kVA
COOLING MOTOR NONCOIN/DIVERSE
HEATING KITCHEN EQUIP
RECEPTACLES NONCONTINUOUS
MOTOR CONTINUOUS 28.8 kVA 36 kVA
LIGHTING EXISTING DEMAND
LOAD CLASSIFICATION CONNECTED LOAD CALCULATED LOAD LOAD CLASSIFICATION CONNECTED LOAD CALCULATED LOAD
TOTAL AMPS: 80 A 80 A 80 A
TOTAL LOAD: 9.6 kVA 9.6 kVA 9.6 kVA
29 -- -- 1 -- -- 1 -- -- 30
27 -- -- 1 -- -- 1 -- -- 28
25 -- -- 1 -- -- 1 -- -- 26
23 -- -- 1 -- -- 1 -- -- 24
21 -- -- 1 -- -- 1 -- -- 22
19 -- -- 1 -- -- 1 -- -- 20
17 -- -- 1 -- -- 1 -- -- 18
15 -- -- 1 -- -- 1 -- -- 16
13 -- -- 1 -- -- 1 -- -- 14
11 -- -- 1 -- -- 1 -- -- 12
9 -- -- 1 -- -- 1 -- -- 10
7 -- -- 1 -- -- 1 -- -- 8
5 -- -- -- 4.8 4.8 -- -- -- 6
3 -- -- -- 4.8 4.8 -- -- -- 4
1 INVERTER 'A' 50 A 3 4.8 4.8 3 50 A INVERTER 'B' 2
CKT CIRCUIT DESCRIPTION NOTE BKR P A B C P BKR NOTE CIRCUIT DESCRIPTION CKT
NOTE:
FEEDER: 2"C,4#1/0,#6EGC,CU NEUTRAL: 100.00% LUGS: STANDARD
MOUNTING: SURFACE WIRES: 4 BUS AMPS: 125 A
FED FROM: DISC-PV PHASE: 3 MAIN BKR: MLO
ROOM: MECH PENTHOUSE 201 VOLTS: 120/208 WYE AIC: 22KA
PV1
Revisions: Date: 203 OF 206
1 2 3 4
B
C
D
E
F
G
H
I
J
K
L M
1.1 3.9
L.2
A.1
2.1 2.9
2.5
B.8
A
8:12 SLOPE8:12 SLOPE 8:12 SLOPE8:12 SLOPE
EY501
STRING A1
IN
V
E R
T E
R B
P V
IN
V
E R
T E
R A
4' - 0"
5' - 4"
STRING A2
STRING A3
STRING B2
STRING B1
4' - 6"
5' - 4"
4' - 6"
3TYP OF 26
4 TYP OF 8
4 TYP OF 14
4 TYP OF 16
0 8 164
1/8" = 1'-0"
ROOF PLAN - ELECTRICAL
A. CONTRACTOR TO VERIFY LAYOUT AND DIMENSIONS ON ROOF PRIOR
TO INSTALLATION. SYSTEM LAYOUT SHALL BE INSTALLED IN
ACCORDANCE WITH 2018 IFC SECTION 1204 AND 2017 NEC.
B. CONTRACTOR SHALL FIELD VERIFY ROUTING DC STRINGS FROM
ARRAYS TO INVERTERS.
C. RACKING LAYOUT AND ENGINEERING BY MANUFACTURER. A SHARED
RAIL SYSTEM MAY BE REQUIRED FOR ORIENTATION OF MODULES.
D. ALL WIRING LEAVING THE ARRAY AREA SHALL BE INSTALLED IN
CONDUIT.
E. MATERIALS SHALL BE UL LISTED AND LABELED.
1. PROVIDE CONDUIT AND WIRE TO CONNECT STRINGS BETWEEN ARRAYS.
2. MINIMUM 4'-0" SET BACK FROM ROOF EDGES, EVES, RIDGES, AND ROOF
MOUNTED EQUIPMENT PER IFC.
3. AWNING MOUNTED SOLAR PANELS, MOUNT 12" BELOW ROOF EDGE.
4. FLAT ROOF MOUNTED SOLAR PANELS.
5. PITCHED ROOF MOUNTED SOLAR PANELS. TYPICAL UON.
KEYPLAN
F
A
O R
T
RE
B
T C.
E O
S T
A
F O
P R
E
R
ISSE IG S
NO
L
LA
EP
I D
NN
E O
H
E
NE
D
E
ET R
L
NG
I
R E
400 S. Jefferson, Suite 301 Spokane, WA 99204
(T) 509.747.1888 (F) 509.747.1872
Pennell Consulting Inc.
Electrical and Electronics
System Design www.pennellconsulting.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY104
ADDITIVE ALTERNATE 2
ROOF PLAN - ELECTRICAL
BOISE VA MEDICAL CENTER - BOISE, ID
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021 RCP KVT
CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEY PLAN
KEY NOTES (THIS SHEET ONLY)
N
NOT TO SCALE
ROOF PLAN ISOMETRIC - PV SYSTEM
Revisions: Date:
NOT TO SCALE
SOLAR PANEL - ISOMETRIC VIEW
2 32.1 2.92.5
CONDUIT TO ELECTRICAL RM 170
CONDUIT TO EXTERIOR PV PANELS
PV1
INVERTER 'A' INVERTER 'B'
2 3
I
J
2.1 2.92.5
EY501
MECH
PENTHOUSE
P V
IN
V
E R
T E
R A
IN
V
E R
T E
R B
B
A
ELEC
C B
-N M
D P
C
B -E
M D
P
E M
D P
N M
D P
EXG MCP1
EXG PNL 1
1 2 3
DISC-PV
F
A
O R
T
RE
B
T C.
E O
S T
A
F O
P R
E
R
ISSE IG S
NO
L
LA
EP
I D
NN
E O
H
E
NE
D
E
ET R
L
NG
I
R E
400 S. Jefferson, Suite 301 Spokane, WA 99204
(T) 509.747.1888 (F) 509.747.1872
Pennell Consulting Inc.
Electrical and Electronics
System Design www.pennellconsulting.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY501
ADDITIVE ALTERNATE 2
SOLAR DETAILS
BOISE VA MEDICAL CENTER - BOISE, ID
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021 RCP KVT
CONSTRUCTION
DOCUMENTS
SCALE: 1/2" = 1'-0"
MECH PENTHOUSE 201 - EAST ELEVATION
SCALE: 1/4" = 1'-0"
MECH PENTHOUSE 201 - ENLARGED PLAN
SCALE: 1/4" = 1'-0"
ELEC 170 - ENLARGED PLAN
A. COORDINATE EXACT LOCATIONS OF EQUIPMENT WITH MEP TRADES
PRIOR TO ROUGH-IN.
1. PROVIDE THE FOLLOWING PHENOLIC LABEL ON DISCONNECT
'DISC-PV'
PHOTOVOLTAIC SYSTEM AC DISCONNECT
MAX AC OPERATING CURRENT: 80 A
NOM AC OPERATING VOLTAGE: 208 V
2. PROVIDE THE FOLLOWING STICKER LABEL:
SOLAR PV SYSTEM IS EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
3. PROVIDE THE FOLLOWING STICKER LABEL:
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
4. PROVIDE 3/4"C WITH ONE (1) CAT5E TO OIT ROOM 402 FOR TCP/IP
COMMUNICATIONS TO INVERTER 'A'..
5. DISCONNECT 'DISC-PV' FOR INTERCONNECT WITH ELECTRICAL
SYSTEM. REFER TO ELECTRICAL ONE-LINE DIAGRAM SHEET E601.
GENERAL SHEET NOTES
KEY PLAN
KEY NOTES (THIS SHEET ONLY)
N
KEYPLAN
EY501
EY501
Revisions: Date: 205 OF 206
VOLTAGE DROP SCHEDULE
DC STRINGS ON RACKS DC HOMRUNS FROM STRING TO COMBINER AC INVERTER TO PV1 PV1 TO EQUIPMENT BUILDING
STRING
DISTANCE
(FT)
VOLTS AMPS WIRE R (Ω/1kft)
I(2)R
(WATTS)
VD
(Volts)
VD
STRING DISTANCE (FT) VOLTS AMPS WIRE R (Ω/1kft)
I(2)R
(WATTS)
VD (Volts)
VD
DC VD
VOLTS
VD (%) INVERTER DISTANCE (FT) VOLTS AMPS WIRE R (Ω/1kft)
VD
(Volts)
VD (%) PANEL
DISTANCE
(FT)
VOLTS AMPS WIRE R (Ω/1kft)
VD
(Volts)
VD (%)
VD
INV
VD INV
A1 86 400 15.0 #10 1.24 23.99 3.20 0.80% A1 90 400 15.0 #8 0.778 15.75 2.10 0.53% 5.30 1.32%
A 5 208 40 #6 0.491 0.1700 0.08%
PV1 200 208 80 #1/0 0.122 3.38 1.62%
3.55 1.71%A2 135 400 15.0 #10 1.24 37.53 5.00 1.25% A2 80 400 15.0 #8 0.778 14.00 1.87 0.47% 6.87 1.72%
A2 96 400 15.0 #10 1.24 26.78 3.57 0.89% A2 110 400 15.0 #8 0.778 19.26 2.57 0.64% 6.14 1.53%
B1 116 400 15.0 #10 1.24 32.36 4.32 1.08% B1 115 400 15.0 #8 0.778 20.13 2.68 0.67% 7.00 1.75% B 7 208 40 #6 0.491 0.2379 0.11% 3.62 1.74%
B2 65 400 15.0 #10 1.24 18.14 2.42 0.60% B2 75 400 15.0 #8 0.778 13.13 1.75 0.44% 4.17 1.04%
TOTAL I(2)R LOSSES DC STRINGS 138.80 WATTS TOTAL I(2)R LOSSES DC HOMERUNS 82.27 WATTS 221.08 WATTS DC TOTAL I(2)R LOSSES INVERTERS TO PV1 28.24 WATTS TOTAL I(2)R LOSSES PV1 TO SERVICE 467.79 WATTS 0.50 kW AC
NEC 702.12(B)(2)(3)(b) COMPLIANCE
PV total kVA AC Output 28800
PV Power Source Amps 80
MCB Rating 1200
Sum of PV & MCB 1280
Busbar Rating 1200
120% Basbar Rating 1440
NEC 702.12(B)(2)(3)(b) 1440A > 1280A
VOLTAGE DROP GROUND SIZE
100 Amps #1 83690
VD Wire Size #1/0 105600
Ratio 1.261799
100A EGC #8 16510
Min Gnd 20840
VD Gnd #6 26240
MAX PV MODULE VOLTAGE CALCULATION
OPEN CIRCUIT VOLTAGE VOC 48.96 V
TEMPERATURE COEFFICIENT OF VOC β -0.27 %/K
STC TEMPERATURE T 25 °C
BOISE, IDAHO LOW TEMP T -17.00 °C
TEMPERATURE DELTA Δ 42 °C
42°C x -0.27%/K = -0.1134 %
VDELTA = 0.1134% x 48.96 V = 5.55 V
VMAX = VOC + V DELTA = 54.51 V
P401 MAX VOC INPUT = 60 V
3P-50A
3P-50A
AC
DC
AC
DC
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
D C
2"C,4#1/0,#6EGC,CU
1"C,3#6,1#6N, 1#10EGC,CU
40A X 1.25 = 50A
3/4"C,2#8,1#10G,CU
16 X 400W = 6.4KW
6.4kW / 400V = 16A
1.56 X 16A = 24.96A
(TYPICAL ALL STRINGS)
200A PANEL 'PV1'
NEMA 3R
TYP.
STRING
'A1'
PITCHED
ROOF
STRING
'A2'
FLAT
ROOF
TYP.
208Y/120V, 3 Ø, 4W 22kAIC
3/4"C,2#8,1#10G,CU
20 X 400W = 8KW
8kW / 400V = 20A
1.56 X 16A = 31.2A
(TYPICAL ALL STRINGS)
TYP.
STRING
'B1'
FLAT ROOF
STRING
'B2'
AWNING
c9 b9 d d e fa7 e
MECH PENTHOUSE
MECH PENTHOUSE
MECH PENTHOUSE
INVERTER 'B'
INVERTER 'A'
STRING
'A3'
FLAT
ROOF
STRING
'B1'
AWNING
STRING
'A2'
PITCHED
ROOF
TYP. 7
TYP.
TYP.
TYP.
TYP.
TYP.
10 TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
g h i j k
NOT TO SCALE
PV SYSTEM ONELINE DIAGRAM
F
A
O R
T
RE
B
T C.
E O
S T
A
F O
P R
E
R
ISSE IG S
NO
L
LA
EP
I D
NN
E O
H
E
NE
D
E
ET R
L
NG
I R
E
400 S. Jefferson, Suite 301 Spokane, WA 99204
(T) 509.747.1888 (F) 509.747.1872
Pennell Consulting Inc.
Electrical and Electronics
System Design www.pennellconsulting.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
Approved: CHIEF, FACILTY MANAGEMENT SERVICE EY601
ADDITIVE ALTERNATE 2
PV ONE-LINE DIAGRAM
BOISE VA MEDICAL CENTER - BOISE, ID
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021 RCP KVT
CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
PV SYSTEM LABELING
KEY NOTES (THIS SHEET ONLY)
1. 16 MODULES AND 16 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.
2. 20 MODULES AND 20 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.
3. 8 MODULES AND 8 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.
4. 14 MODULES AND 14 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.
5. 6 MODULES AND 6 OPTIMIZERS IN STRING, NOT SHOWN FOR CLARITY.
6. 400 WATT MONO-CRYSTALLINE PV MODULE, Q-CELLS Q.PEAK DUO L-G7 400:
PMAX = 400 Wdc VMAX = 41.04 Vdc IMAX = 9.75 Idc VOC = 49.00 Vdc ISC = 10.24 Adc
7. 400 WATT OPTIMIZER FOR EACH PV MODULE. SOLAREDGE P401.
MAX INPUT POWER = 400 Wdc MAX INPUT VOLTAGE = 60.0 Vdc MAX OUTPUT VOLTAGE = 60.0 Vdc MAX OUTPUT CURRENT = 15.0 Adc
8. WP JUNCTION BOX TO TRANSITION FROM #10 PV WIRE TO USE CABLE OR
CONDUIT AND WIRE.
9. 14.4 kW, 208Y/120V, 3∅, 4W TRANFORMERLESS (NON-ISOLATED) INVERTER
WITH INTEGRAL DC DISCONNECT SWITCH AND GROUND FAULT
DETECTION INTERRUPTER. SOLAREDGE SE #14.4K-US:
RATED AC OUTPUT = 14400 VAac MAXIMUM CONTINUOUS CURRENT (PER PHASE) = 40 Aac AC OUTPUT VOLTAGE = 208Y/120V Vac MAX DC POWER INPUT = 19400 Wdc NOMINAL INPUT VOLTAGE DC + TO DC - = 400 Vdc
10. INSTALL MANUFACTURER FURNISHED #10 PV WIRE PER MANUFACTURER'S
RECOMMENDATION. ALL WIRING SHALL BE SECURED TO RACKING AND/OR
MODULE FRAMES.
11. BOND ALUMINUM FRAME OF PV MODULE BY GROUNDING CLAMPS PROVIDED
BY RACK MANUFACTURER. BONDING OF OPTIMIZERS SHALL BE MADE WITH
WEEBS. REFER TO MANUFACTURER'S INSTALLATION MANUAL FOR MORE
INFORMATION.
12. #6 BARE, CU WIRE FOR BONDING OF ALL EXPOSED METAL WITHIN THE ARRAY
AREA.
13. TO DISCONNECT 'DISC-PV'. REFERENCE SHEET E-501 FOR CONTINUATION.
14. PROVIDE 3/4"C WITH ONE (1) CAT5E CONFIGURED FOR RS-485
COMMUNICATIONS BETWEEN INVERTERS 'A', AND 'B'.
15. PROVIDE 3/4"C WITH ONE (1) CAT5E TO OIT ROOM 170 FOR TCP/IP
COMMUNICATIONS TO INVERTER 'A'.
16. PROVIDE 3/4"C WITH 2#10, 1#10EGC,CU TO CONNECT STRINGS BETWEEN
DIFFERENT ARRAYS.
a. PROVIDE THE FOLLOWING PHENOLIC LABEL:
SOLAR PV SYSTEM EQUIPPED
WITH AUTOMATIC RAPID SHUTDOWN
b. PROVIDE THE FOLLOWING PHENOLIC LABEL:
PHOTOVOLTAIC DC DISCONNECT
MAX DC CURRENT: 48 Adc NOM DC VOLTAGE: 400 Vdc
c. PROVIDE THE FOLLOWING PHENOLIC LABEL:
PHOTOVOLTAIC DC DISCONNECT
MAX DC CURRENT: 40 Adc NOM DC VOLTAGE: 400 Vdc
d. PROVIDE THE FOLLOWING STICKER LABEL TO CONDUITS:
PHOTOVOLTAIC POWER SOURCE
e. PROVIDE THE FOLLOWING STICKER LABEL TO CONDUITS:
CAUTION SOLAR CIRCUIT
f. PROVIDE THE FOLLOWING PHENOLIC LABEL:
PANEL 'PV1'
SOLAR PV CIRCUITS ONLY.
DO NOT ADD ADDITIONAL
CIRCUITS TO THIS PANEL.
g. PROVIDE THE FOLLOWING SITCKER LABEL TO 'NMDP1':
CAUTION SOLAR ELECTRIC SYSTEM CONNECTED
h. PROVIDE THE FOLLOWING PHENOLIC LABEL TO 'CB-PV':
PHOTOVOLTAIC SYSTEM AC DISCONNECT
MAX AC OPERATING CURRENT: 80 AMPS
MAX AC OPERATING VOLTAGE: 208 VOLTS
I. PROVIDE THE FOLLOWING STICKER LABEL TO 'CB-PV'::
SOLAR PV SYSTEM IS EQUIPED WITH RAPID
SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO
THE "OFF" POSITION TO SHUTDOWN PV SYSTEM
AND REDUCE SHOCK HAZARD IN ARRAY
j. PROVIDE THE FOLLING STICKER LABEL TO 'CB-PV':
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
k. PROVIDE THE FOLLOWING PHENOLIC LABLE TO PV BACK-
FEED CIRCUIT BREAKER IN 'NMDP1':
WARNING: POWER SOURCE OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT DEVICE
A. MATERIALS SHALL BE UL LISTED AND LABELED.
Revisions: Date: 206 OF 206
File details come from the government source that posted it. Updated .