About this file

This document appears to be a set of technical drawings and specifications for a patient lift system to be installed as part of the Construct Primary Care / Mental Health Building project at the Boise VA Medical Center. The key details include:

The system will use Guldmann GH-3 ceiling-mounted patient lifts with a 550 lb capacity. The drawings provide specifications for the lift system layout, attachment to the building's steel web truss structure, power supply, and safety requirements. The system will be installed in multiple patient rooms and other areas across the facility. The drawings indicate the project is part of Project 531-325 "Construct Primary Care/Mental Health Building Minor Construction" at the Boise VA Medical Center. The associated federal contract opportunity is Solicitation Number 36C77624R0096, which seeks construction services for this project.

View the file

Other files

File Type Posted
0005 - Tech Questions Tracker - Boise PCMH - 8-7-24.pdf PDF
36C77624R0096 0005.pdf PDF
36C77624R0096 0004.pdf PDF
0004 - Tech Questions Tracker - Boise PCMH - 8-5-24.pdf PDF
0004 - Brand Name Justification.pdf PDF
36C77624R0096 0003.pdf PDF
0003 - Tech Questions Tracker - Boise PCMH - 8-1-24.pdf PDF
36C77624R0096 0002.pdf PDF
0001 - Site Visit Sign-in - 7-16-24.pdf PDF
36C77624R0096 0001.pdf PDF
531-325 - Drawings-14-E3.pdf PDF
531-325 - Drawings-07-A2.pdf PDF
531-325 - SOW 4-15-24.pdf PDF
531-325 - Drawings-05-S1.pdf PDF
531-325 - Specs-Vol-1.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
531-325 - Drawings-09-A4.pdf PDF
531-325 - Drawings-03-C2.pdf PDF
Division Cost Breakdown.xlsx XLSX spreadsheet
531-325 - Drawings-15-E4.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Site Visit Instructions.pdf PDF
531-325 - Drawings-16-E5.pdf PDF
531-325 - Specs-Appx-B.pdf PDF
531-325 - Drawings-04-L1.pdf PDF
531-325 - Specs-Vol-2.pdf PDF
531-325 - Drawings-10-M1.pdf PDF
531-325 - Specs-Appx-A.pdf PDF
Site Visit Map.pdf PDF
531-325 - Drawings-01-G1.pdf PDF
RFP 36C77624R0096.docx DOCX document
531-325 - Drawings-06-A1.pdf PDF
531-325 - Drawings-02-C1.pdf PDF
531-325 - Drawings-11-P1.pdf PDF
531-325 - Drawings-13-E2.pdf PDF
531-325 - Drawings-08-A3.pdf PDF
531-325 - Specs-Appx-E.pdf PDF
DBA Wage Rates - Ada County - 01-12-24.pdf PDF
531-325 - Drawings-12-E1.pdf PDF
531-325 - Specs-Appx-F.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSTRUCT PRIMARY CARE / MENTAL HEALTH BUILDING PROJECT #: 531-325

BOISE VA MEDICAL CENTER - BOISE, ID CONSTRUCTION DOCUMENTS

APPENDIX C PATIENT LIFT DETAILS

APPENDIX C:

PATIENT LIFT DETAILS

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

SIGNOFF / APPROVAL NOTES

1. The facility structure capacity must be able to support the load specified on the installation drawing.

2. Electrical power source provided by the facility, position to be verified in the field.

3. Guldmann Inc. reserves the right to slightly modify the track layout if necessary without Facility approval.

This includes lowering the system to avoid ceiling objects.

4. Guldmann Inc. will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process of which we have not been advised.

5. Modifications of door headers by the facility.

6. Signed drawings are required prior to ordering and installation of ceiling lifts.

This signature of each drawing confirms agreement of all the conditions listed above.

7. Systems are tested at 1.5 times capacity.

550 lbs. tested at 825 lbs.; 770 lbs. tested at 1155 lbs.; 825 lbs. tested at 1238 lbs.; 1100 lbs. tested at 1650 lbs.

MY SIGNATURE BELOW VERIFIES THAT I HAVE:

Reviewed all _____ pages, with a total quantity of _____ room(s), _____ system(s) for the approbation of layout for each room and the approbation of structure for each room.

CUSTOMER

APPROVAL: _____________________________________ DATE: _______________

DATE: DRAWN BY:

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise VA Boise PCMH

500 W Fort St.

Boise, ID 83702

PROJECT ID:102460

Boise PCMH

FACILITY SIGNOFF

GUL101

TRC04/19/2021

7 2 2

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

Revision Schedule

Date Issued by Letter Description

05/28/2021 TRC A RM. 118 RE-CONFIGURED / RMS 163 & 145 REMOVED AND SET TO ALT

06/14/2021 CML B NEW BACKGROUNDS / RM 136 REPLACED WITH RM 163

06/18/2021 CML C ROOMS 136 & 145 READDED / PROJECT SPLIT IN TWO

EACH FIXED RAIL TO

HAVE x1 PARALLEL & x2 PERPENDICULAR

STABILIZERS

ALL JOINTS MUST HAVE x1 PARALLEL & x1

PERPENDICULAR STABILIZER

SEE SPAN CHART

S E

E S

P A

N C

H A

R T

SEE SPAN CHART

± 22°

STABILIZERS CAN BE ROTATED 180°

Fixed rail systems Fixed rail systems must be connected by Guldmann Service Team or by a qualified installer.

A Guldmann class I transformer must be used.

Installation to follow existing rules for authorized electricians and according to IEC/UL 60601-1.

Terminals on transformers Class I Double-insulated UL approved cable must be used (Cable specification: UL category: AVLV2, min.300V, min.

80° C, min. 18AWG (1 mm2 )) Transformer DK-13991 In:

Terminal 1 = N Terminal 2 = 100-115V AC Terminal 3 = 230V AC Terminal 4 = Protective ground Out:

Terminal 5 = 33V AC Terminal 6 = 33V AC

POWER TO BE WITHIN 15 FT OF END OF FIXED RAIL

Guldmann permanent mounted ceiling aluminium rail

Hoist with trolleys movable in rail

Protective Plast Enclosure

UL approved 400V cable, green, min. 14 AWG

Protective Ground

M1

UL approved 400V double isolated cable, min. 18 AWG

ON/OFF

UL approved 400V double isolated cable, min. 18 AWG

T ra n s fo rm e r

D K

-1

Main power Permanent installation Specification of breaker:

> 1 Amp capacity Line must always be broken

L1

AC/DC charger

Main Motor Control

Emergency Stop

Safety Circuit Emergency down

Motor Function Selector Switch0 1

V A

C

U S

V

A C

P ro te c ti ve

G ro u n d

V

A C

V

A C1 A

T

.5

A T

Green Light ON (or ON / OFF - sign)

MAX

PROJECTION

MAX DISTANCE BETWEEN VERTICAL SUPPORTS

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

X

X

X

RAIL

RAIL

RAIL

RAIL

RAIL

RAIL

INCH

METER

,23

,7

1,2

39 49 59 68 78 118 137 147 157 177 187 206 215 236 246 264

1,0 1,25 1,5 1,75 2,0 3,0 3,5 3,75 4,0 4,5 4,75 5,25 5,5 6,0 6,25 6,75

MAX. 175 KG (385 LBS.)

MAX. 205 KG (450 LBS.)

MAX. 255 KG (560 LBS.)

MAX. 300 KG (660 LBS.)

MAX. 350 KG (770 LBS.)

MAX. 375 KG (825 LBS.)

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

A-RAIL

WEIGHT: 2.6 KG/M

(1.75 LBS/FT)

B-RAIL

WEIGHT: 5.0 KG/M

(3.36 LBS/FT)

C-RAIL

WEIGHT: 6.0 KG/M

(4.03 LBS/FT)

(2 1/2")

62 mm.

(2

/4

,5 m m

(2 1/2")

62 mm.

(5 m m

(2 1/2")

62 mm.

(6

/3 m m

A

B

C

RAIL MAX. 400 KG (880 LBS.)

X

X

X

A

B

C

RAIL MAX. 500 KG (1100 LBS.)

X

X

X

7,25

8,0

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X m m

/2 m m

/4

,5 m m

M

IN

m m

/4

DEPTH = 205 mm (8 1/4")

345 mm (13 3/4")

A

B

C

D

E

F

G

H

I

J

K

Ceiling bracket standard

A / B / C

Basic High M

Basic High M

Dimensions

205 mm

580 mm

345 mm

24 mm

58.5 / 125 / 170 mm

156 mm

184 mm

284 mm

2500 mm

970 mm

340 mm

8"

22.8"

13.5"

1.5"

2.2 / 4.9 / 6.6"

6.29"

7.2"

11.38"

98"

38"

13.3"

H

A

E D

F

C

G I

B

K J

SPRING PLATE

AVAILABLE FOR A & B RAIL

FLUSH CEILING PROFILE LIP IS 7/16" X 3/8"

CUT 12 - 15 MM OF THE 2 LONGITUDE

SCREW FOR

PROFILE END

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

Boise PCMH

GEN. INFO

GUL102

TRC04/19/2021

PROJECT ID:102460

NTS

BRACING + SUPPORT

NTS

GH3 TRANSFORMER

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

NTS

RAIL SPAN CHART

Revision Schedule

Date Issued by Number

SPAN = 5' - 4 1/4"

NTS

GH3 HOIST DIMS

NTS

GH3 PATIENT SLING DIMS

NTS

FLUSH CEILING PROFILE

DRAWINGS APPROVED FOR THE GULDMANN

GH-3 LIFTER SYSTEM STANDARD INSTALLATION

OF SUPPORT AND CONNECTION TO STEEL WEB

TRUSS.

SYSTEMS INSTALLED FOR 1100 POUNDS WILL BE

TESTED AT 1650 POUNDS.

SYSTEMS INSTALLED FOR 770 POUNDS WILL BE

TESTED AT 1155 POUNDS.

SYSTEMS INSTALLED FOR 550 POUNDS WILL BE

TESTED AT 825 POUNDS.

STEEL WEB TRUSS

TAG ITEM NUMBER DESCRIPTION

10 113024 3/8" NYLOCK NUT

6,7,12

A

GULDMANN RAIL

EXISTING STEEL TRUSS

M A

X

V A

R

IE

S

40° TO 90°

9 P2787 8-1/4" BEAM CLAMP

8 11101273 3/8" X 1-1/4" X 1/8" WASHER (THICK)

7 411764 3/8" X 1-1/4" BOLT

6 377882 MQM-F WINGNUT 3/8"

5 550435 CEILING BRACKET KIT - GULDMANN

4 550481-US 1" Ø-6013-T6 AL TUBE - GULDMANN

3 550439 STABILIZER BRACKET KIT - GULDMANN

2 HTHR037 12B7 3/8" B7 THREADED ROD

1 3584301 2-7/16" X 10' B2B STRUT SLOTTED

0º

90º

HVAC / MECH

BASEPLATE x4

STABILIZERS x3

STABILIZERS

± 22°

BRIDGE SECTION

BRIDGE / RAIL TOP

8,10

11 411752 3/8" HEX NUT

SPAN

12 370632 MQZ-L BASE PLATE 3/8"

OPTIONAL A

DETAIL A

OPTIONAL

ATTACHMENT

12 10

TRUSS

13 377885 MQA-F SADDLE NUT 3/8" (OPTIONAL A)

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Boise PCMH

ATTACHMENT

GUL103

TRC04/19/2021

PROJECT ID:102460

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

Revision Schedule

Date Issued by Number

SPAN = 5' - 4 1/4"

GUL104

/8

H

O

IS

T

/2

T R

A V

E R

S E

C E

IL

IN

G

8" MIN.1

/8

/2

/8

27" MAX.

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Boise PCMH

PROJECT DETAILS

GUL104

TRC04/19/2021

PROJECT ID:102460

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

Revision Schedule

Date Issued by Number

06/14/2021 CML B

06/18/2021 CML C

SPAN = 5' - 4 1/4"

1" = 1'-0"

SYSTEM ELEVATION

1 1/2" = 1'-0"

SYSTEM / CEILING

/8

6' - 2 1/2" 3' - 1 5/8"

9' - 10 1/8"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

PROCEDURE RM 01 - 136

GUL105

TRC04/19/2021

PROJECT ID:102460

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

3/4" = 1'-0"

PROCEDURE RM 01 - 136

Revision Schedule

Date Issued by Number

06/14/2021 CML B

06/18/2021 CML C

10' - 4"

/4

/2

8' - 2 1/8" 2' - 1 1/2"

GUL104

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

WOMENS HEALTH 01 - 118

GUL106

TRC04/19/2021

PROJECT ID:102460

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

3/4" = 1'-0"

WOMENS HEALTH 01 - 118

Revision Schedule

Date Issued by Number

A B C D E F G H I J K L M

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

OVERALL

GUL107

TRC04/19/2021

PROJECT ID:102460

3/32" = 1'-0"

OVERALL

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

Revision Schedule

Date Issued by Number

05/28/2021 TRC A

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

SIGNOFF / APPROVAL NOTES

1. The facility structure capacity must be able to support the load specified on the installation drawing.

2. Electrical power source provided by the facility, position to be verified in the field.

3. Guldmann Inc. reserves the right to slightly modify the track layout if necessary without Facility approval.

This includes lowering the system to avoid ceiling objects.

4. Guldmann Inc. will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process of which we have not been advised.

5. Modifications of door headers by the facility.

6. Signed drawings are required prior to ordering and installation of ceiling lifts.

This signature of each drawing confirms agreement of all the conditions listed above.

7. Systems are tested at 1.5 times capacity.

550 lbs. tested at 825 lbs.; 770 lbs. tested at 1155 lbs.; 825 lbs. tested at 1238 lbs.; 1100 lbs. tested at 1650 lbs.

MY SIGNATURE BELOW VERIFIES THAT I HAVE:

Reviewed all _____ pages, with a total quantity of _____ room(s), _____ system(s) for the approbation of layout for each room and the approbation of structure for each room.

CUSTOMER

APPROVAL: _____________________________________ DATE: _______________

DATE: DRAWN BY:

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise VA Boise PCMH

500 W Fort St.

Boise, ID 83702

PROJECT ID:102460.1

Boise PCMH

FACILITY SIGNOFF

GUL101

TRC04/19/2021

7 2 2

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

Revision Schedule

Date Issued by Letter Description

05/28/2021 TRC A RM. 118 RE-CONFIGURED / RMS 163 & 145 REMOVED AND SET TO ALT

06/14/2021 CML B NEW BACKGROUNDS / RM 136 REPLACED WITH RM 163

06/18/2021 CML C ROOMS 136 & 145 READDED / PROJECT SPLIT IN TWO

EACH FIXED RAIL TO

HAVE x1 PARALLEL & x2 PERPENDICULAR

STABILIZERS

ALL JOINTS MUST HAVE x1 PARALLEL & x1

PERPENDICULAR STABILIZER

SEE SPAN CHART

S E

E S

P A

N C

H A

R T

SEE SPAN CHART

± 22°

STABILIZERS CAN BE ROTATED 180°

Fixed rail systems Fixed rail systems must be connected by Guldmann Service Team or by a qualified installer.

A Guldmann class I transformer must be used.

Installation to follow existing rules for authorized electricians and according to IEC/UL 60601-1.

Terminals on transformers Class I Double-insulated UL approved cable must be used (Cable specification: UL category: AVLV2, min.300V, min.

80° C, min. 18AWG (1 mm2 )) Transformer DK-13991 In:

Terminal 1 = N Terminal 2 = 100-115V AC Terminal 3 = 230V AC Terminal 4 = Protective ground Out:

Terminal 5 = 33V AC Terminal 6 = 33V AC

POWER TO BE WITHIN 15 FT OF END OF FIXED RAIL

Guldmann permanent mounted ceiling aluminium rail

Hoist with trolleys movable in rail

Protective Plast Enclosure

UL approved 400V cable, green, min. 14 AWG

Protective Ground

M1

UL approved 400V double isolated cable, min. 18 AWG

ON/OFF

UL approved 400V double isolated cable, min. 18 AWG

T ra n s fo rm e r

D K

-1

Main power Permanent installation Specification of breaker:

> 1 Amp capacity Line must always be broken

L1

AC/DC charger

Main Motor Control

Emergency Stop

Safety Circuit Emergency down

Motor Function Selector Switch0 1

V A

C

U S

V

A C

P ro te c ti ve

G ro u n d

V

A C

V

A C1 A

T

.5

A T

Green Light ON (or ON / OFF - sign)

MAX

PROJECTION

MAX DISTANCE BETWEEN VERTICAL SUPPORTS

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

X

X

X

RAIL

RAIL

RAIL

RAIL

RAIL

RAIL

INCH

METER

,23

,7

1,2

39 49 59 68 78 118 137 147 157 177 187 206 215 236 246 264

1,0 1,25 1,5 1,75 2,0 3,0 3,5 3,75 4,0 4,5 4,75 5,25 5,5 6,0 6,25 6,75

MAX. 175 KG (385 LBS.)

MAX. 205 KG (450 LBS.)

MAX. 255 KG (560 LBS.)

MAX. 300 KG (660 LBS.)

MAX. 350 KG (770 LBS.)

MAX. 375 KG (825 LBS.)

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

A-RAIL

WEIGHT: 2.6 KG/M

(1.75 LBS/FT)

B-RAIL

WEIGHT: 5.0 KG/M

(3.36 LBS/FT)

C-RAIL

WEIGHT: 6.0 KG/M

(4.03 LBS/FT)

(2 1/2")

62 mm.

(2

/4

,5 m m

(2 1/2")

62 mm.

(5 m m

(2 1/2")

62 mm.

(6

/3 m m

A

B

C

RAIL MAX. 400 KG (880 LBS.)

X

X

X

A

B

C

RAIL MAX. 500 KG (1100 LBS.)

X

X

X

7,25

8,0

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X m m

/2 m m

/4

,5 m m

M

IN

m m

/4

DEPTH = 205 mm (8 1/4")

345 mm (13 3/4")

A

B

C

D

E

F

G

H

I

J

K

Ceiling bracket standard

A / B / C

Basic High M

Basic High M

Dimensions

205 mm

580 mm

345 mm

24 mm

58.5 / 125 / 170 mm

156 mm

184 mm

284 mm

2500 mm

970 mm

340 mm

8"

22.8"

13.5"

1.5"

2.2 / 4.9 / 6.6"

6.29"

7.2"

11.38"

98"

38"

13.3"

H

A

E D

F

C

G I

B

K J

SPRING PLATE

AVAILABLE FOR A & B RAIL

FLUSH CEILING PROFILE LIP IS 7/16" X 3/8"

CUT 12 - 15 MM OF THE 2 LONGITUDE

SCREW FOR

PROFILE END

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

Boise PCMH

GEN. INFO

GUL102

TRC04/19/2021

PROJECT ID:102460.1

NTS

BRACING + SUPPORT

NTS

GH3 TRANSFORMER

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

NTS

RAIL SPAN CHART

Revision Schedule

Date Issued by Number

06/18/2021 CML C

SPAN = 5' - 4 1/4"

NTS

GH3 HOIST DIMS

NTS

GH3 PATIENT SLING DIMS

NTS

FLUSH CEILING PROFILE

DRAWINGS APPROVED FOR THE GULDMANN

GH-3 LIFTER SYSTEM STANDARD INSTALLATION

OF SUPPORT AND CONNECTION TO STEEL WEB

TRUSS.

SYSTEMS INSTALLED FOR 1100 POUNDS WILL BE

TESTED AT 1650 POUNDS.

SYSTEMS INSTALLED FOR 770 POUNDS WILL BE

TESTED AT 1155 POUNDS.

SYSTEMS INSTALLED FOR 550 POUNDS WILL BE

TESTED AT 825 POUNDS.

STEEL WEB TRUSS

TAG ITEM NUMBER DESCRIPTION

10 113024 3/8" NYLOCK NUT

6,7,12

A

GULDMANN RAIL

EXISTING STEEL TRUSS

M A

X

V A

R

IE

S

40° TO 90°

9 P2787 8-1/4" BEAM CLAMP

8 11101273 3/8" X 1-1/4" X 1/8" WASHER (THICK)

7 411764 3/8" X 1-1/4" BOLT

6 377882 MQM-F WINGNUT 3/8"

5 550435 CEILING BRACKET KIT - GULDMANN

4 550481-US 1" Ø-6013-T6 AL TUBE - GULDMANN

3 550439 STABILIZER BRACKET KIT - GULDMANN

2 HTHR037 12B7 3/8" B7 THREADED ROD

1 3584301 2-7/16" X 10' B2B STRUT SLOTTED

0º

90º

HVAC / MECH

BASEPLATE x4

STABILIZERS x3

STABILIZERS

± 22°

BRIDGE SECTION

BRIDGE / RAIL TOP

8,10

11 411752 3/8" HEX NUT

SPAN

12 370632 MQZ-L BASE PLATE 3/8"

OPTIONAL A

DETAIL A

OPTIONAL

ATTACHMENT

12 10

TRUSS

13 377885 MQA-F SADDLE NUT 3/8" (OPTIONAL A)

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Boise PCMH

ATTACHMENT

GUL103

TRC04/19/2021

PROJECT ID:102460.1

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

Revision Schedule

Date Issued by Number

SPAN = 5' - 4 1/4"

C E

IL

IN

G

/2

T R

A V

E R

S E

/8

H

O

IS

T 1

/8

/2

/8

8" MIN.

27" MAX.

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

Boise PCMH

PROJECT DETAILS

GUL104

TRC04/19/2021

PROJECT ID:102460.1

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

Revision Schedule

Date Issued by Number

06/14/2021 CML B

06/18/2021 CML C

SPAN = 5' - 4 1/4"

1" = 1'-0"

SYSTEM ELEVATION

1 1/2" = 1'-0"

SYSTEM / CEILING

/8

9' - 10 1/8"

3' - 1 7/8" 6' - 2 1/2"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

PROCEDURE RM 01 - 145

GUL105

TRC04/19/2021

PROJECT ID:102460.1

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

3/4" = 1'-0"

PROCEDURE RM 01 - 145

Revision Schedule

Date Issued by Number

05/28/2021 TRC A

1' - 10 3/8" 8' - 2 1/2"

10' - 4 1/8"

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

WOMENS HEALTH 02 - 163

GUL106

TRC04/19/2021

PROJECT ID:102460.1

3/4" = 1'-0"

WOMENS HEALTH 02 - 163

B rail

Ceiling bracket, Extended

Hoist

Stabilizers

KEY

Hoist Transformer

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

Revision Schedule

Date Issued by Number

A B C D E F G H I J K L M

Guldmann Inc.

14401 McCormick Drive Tampa FL, 33626 Unit A

Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558

Email: Info@Guldmann.net

NOTES

APPROVED BY:

PROJECT NAME:

SHEET DESCRIPTION:

SHEET NO:

DATE: DRAWN BY:

SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS

ACCURATE TO 4" BASED

ON PDF CONVERSION

Boise PCMH

OVERALL

GUL107

TRC04/19/2021

PROJECT ID:102460.1

3/32" = 1'-0"

OVERALL

HOIST = 550 LBS1.

FLUSH RECESSED / TYPE G2.

CEILING HEIGHT = 9' - 0"3.

AFF TO B.O.S = 14' - 6"

ATTACHMENT TYPE = WEB TRUSS4.

SPAN = 5' - 4 1/4"

Revision Schedule

Date Issued by Number

05/28/2021 TRC A