531-325 - Drawings-11-P1.pdf

PDF 4 MB Posted

Attached to
Y1DZ--TIERED EVALS - Construct Primary Care/Mental Health Building Minor Construction - Boise 531-325
Solicitation number
36C77624R0096
Issued by

About this file

This document appears to be a set of construction drawings for the Construct Primary Care/Mental Health Building Minor Construction Project (Project 531-325) at the VA Medical Center in Boise, ID. The drawings provide detailed specifications and plans for the plumbing systems, including the domestic water, sanitary sewer, storm drainage, and plumbing fixtures required for the new building. Key details include the size, routing, and connections of the various water supply and waste piping, locations of floor drains, cleanouts, and roof drains, and schedules for plumbing fixtures and equipment such as water heaters, mixing valves, and expansion tanks. The drawings also include details and specifications for items like cleanout covers, roof drain assemblies, and the fire protection system. This comprehensive set of construction documents would be necessary for a contractor to properly install the plumbing systems for this new healthcare facility.

View the file

Other files

File Type Posted
0005 - Tech Questions Tracker - Boise PCMH - 8-7-24.pdf PDF
36C77624R0096 0005.pdf PDF
36C77624R0096 0004.pdf PDF
0004 - Tech Questions Tracker - Boise PCMH - 8-5-24.pdf PDF
0004 - Brand Name Justification.pdf PDF
36C77624R0096 0003.pdf PDF
0003 - Tech Questions Tracker - Boise PCMH - 8-1-24.pdf PDF
36C77624R0096 0002.pdf PDF
0001 - Site Visit Sign-in - 7-16-24.pdf PDF
36C77624R0096 0001.pdf PDF
531-325 - Drawings-14-E3.pdf PDF
531-325 - Drawings-07-A2.pdf PDF
531-325 - SOW 4-15-24.pdf PDF
531-325 - Drawings-05-S1.pdf PDF
531-325 - Specs-Vol-1.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
531-325 - Drawings-09-A4.pdf PDF
531-325 - Drawings-03-C2.pdf PDF
Division Cost Breakdown.xlsx XLSX spreadsheet
531-325 - Drawings-15-E4.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Site Visit Instructions.pdf PDF
531-325 - Drawings-16-E5.pdf PDF
531-325 - Specs-Appx-B.pdf PDF
531-325 - Drawings-04-L1.pdf PDF
531-325 - Specs-Vol-2.pdf PDF
531-325 - Drawings-10-M1.pdf PDF
531-325 - Specs-Appx-A.pdf PDF
Site Visit Map.pdf PDF
531-325 - Drawings-01-G1.pdf PDF
RFP 36C77624R0096.docx DOCX document
531-325 - Drawings-06-A1.pdf PDF
531-325 - Drawings-02-C1.pdf PDF
531-325 - Drawings-13-E2.pdf PDF
531-325 - Drawings-08-A3.pdf PDF
531-325 - Specs-Appx-C.pdf PDF
531-325 - Specs-Appx-E.pdf PDF
DBA Wage Rates - Ada County - 01-12-24.pdf PDF
531-325 - Drawings-12-E1.pdf PDF
531-325 - Specs-Appx-F.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CO

FE

CONCENTRIC REDUCER/INCREASER

ECCENTRIC REDUCER/INCREASER

UNION

TOP CONNECTION, 45° OR 90°

EXTENSION & CONTINUATION

CAPPED OUTLET

POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK

LIMIT OF DEMOLITION

ANCHOR

DIRECTION OF FLOW

DIRECTION OF PIPE PITCH (DOWN)

BOTTOM CONNECTION, 45° OR 90°

PIPE UP

SIDE CONNECTION

RISE OR DROP IN PIPE

PIPE UP

PIPE DOWN

INVERTED BUCKET TRAP SET INCLUDING PIPING ACCESSORIES

FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING ACCESSORIES

STRAINER

PRESSURE GAGE

THERMOMETER

CLEAN-OUT

PTRAP

HOSE BIB

FLOW ELEMENT

PLATE HEAT EXCHANGER SCHEDULE

TAG

MANUF/

MODEL

NUMBER

LOCATION SERVICE TYPE

CAPACITY

(MBH)

QTY

PLATES

PASSES

HOT SIDE COLD SIDE WORKING

PRESSURE

(PSI)

WEIGHT

(LBS)

NOTES

EWT

(°F)

LWT

(°F)

GPM PD (FT) GLYCOL % EWT (°F) LWT (°F) GPM PD (FT) GLYCOL %

AICOO

SAHARA/

LA14DW-40

MECH RM

DOMESTIC WATER

HEATING

BRAZED

PLATE &

FRAME

100 40 1 150 140 10 4.8 0 40 140 2 0.3 0 150 6 1

MIXING VALVE SCHEDULE

TAG MANUFACTURER /MODEL NUMBER LOCATION SERVICE TYPE

CAPACITY

(GPM)

MINIMUM

FLOW

(GPM)

PRESS.

DROP

(PSI)

OUTLET

TEMP.

(°F)

ENCLOSURE

WEIGHT

(LBS)

NOTES

LEONARD / TM-520B-LF-DT MECHANICAL ROOM

DOMESTIC WATER

HEATING

BI-METAL

HI-LOW

FLOW

21 0.5 10 120 NONE 6 1

EXPANSION TANK SCHEDULE

TAG TYPE LOCATION SERVICE

SYSTEM

TEMPERATURES TANK RATED

PRESSURE

(PSI)

MINIMUM TANK

VOLUME

(GALLONS)

MINIMUM TANK

ACCEPTANCE

VOLUME

(GALLONS)

NOTES

MIN (°F) MAX (°F)

DIAPHRAGM MECH RM

BUILDING HEATING

SYSTEM

40 140 150 6.4 0.5 1

NOTES:

1. TANK TO BE ANTIMICROBIAL POLYPROPYLENE WITH ANTI-LEGIONELLA PROTECTION

NOTES:

1. DOUBLE WALL CONSTRUCTION.

HX

NOTES:

1. PROVIDE OUTLET THERMOMETER.

TMV

EXP

PLUMBING FIXTURE SCHEDULE

SYMBOL DESCRIPTION

MANUFACTURER AND CATALOG #

(BASIS OF DESIGN ONLY OTHER

MANUFACTURES THAT MEET THE

SPECIFICATIONS ARE ACCEPTABLE)

FAUCET/FLUSH VALVE

CONNECTIONS

NOTES

HW CW W V

WATER CLOSET, FLOOR

MOUNT, FLUSH VALVE

(ACCESSIBLE)

KOHLER HIGHCLIFF K-96057-0

SLOAN UPPERCUT WES 111-1.6/1.1

(1.6/1.1 GPF) MANUAL DUAL FLUSH

VALVE

- 1" 3" 2" PROVIDE ELONGATED OPEN FRONT SEAT

WALL MOUNT LAVATORY

AMERICAN STANDARD LUCERNE

0355.012

AMERICAN STANDARD,

MONTERREY 6114.114.002, 0.35 BPM

FLOW, SINGLE HANDLE MANUAL

1/2" 1/2" 1-1/2" 1-1/2"

GRID STRAINER, TAIL PIECE, P-TRAP, SUPPLIES, STOPS, INSULATION

ON SUPPLIES AND DRAIN ON ADA FIXTURES, PROVIDE MANUAL MIXING

VALVE TO LIMIT HOT WATER SUPPLY TO 105°F

EXAM ROOM LAV

ELKAY DLR151710, 15"X17"X10",

STAINLESS STEEL

CHCAGO 895-317GN2AE72XKAB, 0.5

GPM, 5-1/4" RIGID GOOSENECK, 4"

WRIST BLADE HANDLES

1/2" 1/2" 1-1/2" 1-1/2"

GRID STRAINER, TAIL PIECE, P-TRAP, SUPPLIES, STOPS, PROVIDE

MANUAL MIXING VALVE TO LIMIT HOT WATER SUPPLY TO 105°F

SERVICE SINK

FIAT TSB100, 24"X24"X12" CORNER

MOUNT

FIAT 830-AA, WALL MOUNTED WITH

SUPPORT AND VACUUM BREAKER

1/2" 1/2" 3" 2"

832AA 4' HOSE & HOSE HANGER, WALL GUARDS FOR TWO WALLS,

STAINLESS STEEL CURB CAPS

SINGLE COMPARTMENT,

COUNTER MOUNT,

STAINLESS STEEL, ADA

SINK

ELKAY

LRAD222255

22"X22"X5.5"

ELKAY LK1001CR, BELOW DECK

MOUNT, SINGLE HANDLE, ADA, 8"

SPOUT, W/HOSE SPRAY

1/2" 1/2" 2" 2"

BASKET STRAINER, TAIL PIECE, P-TRAP, SUPPLIES, STOPS, INSULATION

ON SUPPLIES AND DRAIN ON ADA FIXTURES, PROVIDE MANUAL MIXING

VALVE TO LIMIT HOT WATER SUPPLY TO 105°F

SINGLE COMPARTMENT,

COUNTER MOUNT,

STAINLESS STEEL

ELKAY

DLR222210

22"X22"X10"

CHCAGO 895-317GN8AE67VAB, 0.5

GPM, 8" RIGID GOOSENECK, 4"

WRIST BLADE HANDLES

1/2" 1/2" 2" 2"

BASKET STRAINER, TAIL PIECE, P-TRAP, SUPPLIES, STOPS, INSULATION

ON SUPPLIES AND DRAIN ON ADA FIXTURES, PROVIDE MANUAL MIXING

VALVE TO LIMIT HOT WATER SUPPLY TO 105°F

WATER COOLER

(DUAL HEIGHT)

ELKAY LZSTL8WSLK WITH FILTER

AND BOTTLE FILLER

WALL CARRIER, STOP, SUPPLY,

TAIL PIECE, P-TRAP

- 1/2" 2" 2" 8.0 GPH, 115 V, 1 PH, 3.8 FLA, 260 WATTS

EMERGENCY FACE/EYE

WASH

GUARDIAN G1814-TP

TAIL PIECE AND PTRAP, TMV

G3607LF MIXING VALVE

W/RECESSED ENCLOSURE

1/2" 1/2" 2" 2" -

NON-FREEZE HOSE BIBB JR SMITH 5609QT

VACUUM BREAKER, LOOSE KEY

OPERATOR

- 3/4" - - -

WATER SUPPLY BOX OATEY 39140

WITH WATER HAMMER ARRESTER

AND 1/4 TURN VALVE

- 1/2" - - -

ROOF DRAIN J.R. SMITH FIG 1010

UNDER DECK CLAMP, DOME

STRAINER

- - - - SEE FLOOR PLANS FOR SIZE

OVER FLOW ROOF DRAIN J.R. SMITH FIG 1080

UNDER DECK CLAMP, DOME

STRAINER, 2" DAM

- - - - SEE FLOOR PLANS FOR SIZE

DOWN SPOUT NOZZLE J.R. SMITH FIG 1770 CAST BRONZE BODY AND SPOUT - - - - SEE FLOOR PLANS FOR SIZE

FLOOR DRAIN JR SMITH FIG 2005

ROUND STRAINER, NICKEL BRONZE

STRAINER, TRAP PRIMER

CONNECTION

SEE DRAWINGS FOR DRAIN WASTE AND VENT SIZE, PROVIDE P-TRP

WITH TRAP PRIMER CONNECTION.

FLOOR SINK JR SMITH FIG 9693

12"X12" RECTANGULAR TOP, DOME

BOTTOM STRAINER, TRAP PRIMER

CONNECTION

- - 3" 2"

FLOOR DRAIN JR SMITH FIG 2005

RECTANGULAR STRAINER, NICKEL

BRONZE STRAINER, TRAP PRIMER

CONNECTION, 3581 FUNNEL DRAIN

- - - 2"

SEE FLOOR PLANS FOR DRAIN SIZE. MATCH PIPE SIZE CONNECTED TO

DRAIN

TRAP PRIMER

(ELECTRIC)

PPP MPB-500

WITH DISTRIBUTION UNITS AS

REQUIRED

- 1/2" - - 120V/1PH/60HZ, 12.1 AMPS IN RUSH, 8.8 AMPS HOLDING

TRAP PRIMER

(HYDRAULIC)

PPP P1-500

WITH DISTRIBUTION UNITS AS

REQUIRED

- 1/2" - - -

REDUCED PRESSURE

BACK FLOW PREVENTER

WATTS LF909 NRS (OR EQUAL)

LEAD FREE, NON RISING STEM

VALVES, AIR GAP FITTING

- 2" - - -

REDUCED PRESSURE

BACK FLOW PREVENTER

WATTS LF909 NRS (OR EQUAL)

LEAD FREE, NON RISING STEM

VALVES, AIR GAP FITTING

- 2" - - -

HEATING SYSTEM FILL

REDUCED PRESSURE

BACK FLOW PREVENTER

WATTS LF009M3 QT

LEAD FREE, QUARTER TURN

VALVES AIR GAP FITTING

- 3/4" - - -

GENERAL PLUMBING SYMBOLSPLUMBING PIPING SYMBOLS

DEFINITIONSYMBOL

DOMESTIC COLD WATER, COLD WATER

DOMESTIC HOT WATER, HOT WATER

DOMESTIC HOW WATER RETURN, HOT WATER RETURN

MEDICAL AIR

VENT (SANITARY)

SOIL, WASTE, OR SANITARY SEWER

SANITARY SEWER, BELOW GRADE (SHOWN ON FLOOR PLAN)

MEDICAL VACUUM

LAB AIR

LAB VACUUM

ORAL EXTRACTION

INDUSTRIAL AIR

DRAIN

STORM WATER

STORM WATER, BELOW GRADE (SHOWN ON FLOOR PLAN)

SOFTEN COLD WATER

FILTERED COLD WATER

DRINKING WATER SUPPLY

DRINKING WATER RETURN

TEMPERED WATER SUPPLY

TEMPERED WATER RETURN

NITROUS OXIDE

OXYGEN

NITROGEN

NATURAL GAS

NATURAL GAS, BELOW GRADE

INDIRECT DOMESTIC WATER HEATER STORAGE TANK SCHEDULE

SYMBOL DESCRIPTION SERVICE

TANK SIZE

(GALLONS)

BACKUP ELECTRIC HEATER

NOTES

KW VOLT/PH AMPS

INLET

TEMP.

(°F)

OUTLET

TEMP.

(°F)

GPH CAPACITY

TANK TYPE BUILDING 119 4.5 208/3 12.5 40 140 5.4 1, 2

NOTES:

1. PROVIDE P&T RELIEF VALVE

2. PROVIDE EXPANSION TANK AMTROL ST-12

PLUMBING PUMP SCHEDULE

SYMBOL

MANUFACTURER

/MODEL NUMBER

DESCRIPTION SERVICE

FLOW

(GPM)

HEAD

(FEET)

ELECTRICAL

NOTES

VOLTAGE PHASE HP RPM

ARMSTRONG/

ASTRO 250SS

INLINE

HEAT EXCHANGER

CIRCULATION

2.0 15 115 1 28 WATTS - 1, 2, 3

ARMSTRONG/

ASTRO 250SS

INLINE

HEAT EXCHANGER

CIRCULATION

2.0 15 115 1 28 WATTS - 1, 2, 3

ARMSTRONG/

ASTRO 250SS

INLINE

BUILDING

RECIRCULATION

2.5 35 115 1 28 WATTS - 1, 2, 3, 4

ARMSTRONG/

ASTRO 250SS

INLINE

BUILDING

RECIRCULATION

2.5 35 115 1 28 WATTS - 1, 2, 3, 4

NOTES:

1. PROVIDE ECM MOTOR AND MOTOR SPEED ADJUSTMENT

2. PROVIDE UNION FITTINGS AND BUILT IN CHECK AND STOP VALVES

3. PROVIDE ADJUSTABLE SPEED SWITCH

4. PROVIDE INTEGRAL AQUASTAT CONTROL

PLUMBING ABBREVIATIONS

SS

SS

MA

MV

LV

LA

OA

IA

D

SD

SD

SCW

FCW

DWS

DWR

TWS

TWR

N2O

O

N

NG

NG

WATER BALANCING VALVE

PROJECT NOTES

1. SINCE WORK WILL TAKE PLACE IN A HOSPITAL, THERE IS THE POSSIBILITY OF THE

CONTRACTOR COMING IN CONTRACT WITH BLOOD AND BODY FLUIDS WHENEVER

WORKING ON THE SANITARY SEWER SYSTEM. CONTRACTOR IS REQUIRED TO PROVIDE

AND USE APPROPRIATE PERSONAL PROTECTIVE EQUIPMENT WHENEVER WORKING ON

THE SANITARY SEWER SYSTEM TO PREVENT EXPOSURE TO THEIR

EMPLOYEES

2. WHEN MANUFACTURER AND CATALOG MODEL NUMBERS ARE LISTED THEY ARE

FOR BASIS OF DESIGN ONLY OTHER MANUFACTURES THAT MEET THE

SPECIFICATIONS ARE ACCEPTABLE FOR BIDDING IF THEY MEET THE

SPECIFICATION REQUIREMENTS.

P-401

P-502

P-115

P-413

RD-1

P-708

DSN-1

RD-2

P-528

FD-C

FD-M

TP-1

P-HW

P-HW

P-HW

P-HW

WH

FD-S

P-608

P-812

P-801

BPF-1

BPF-2

TP-2

BPF-3

P-532

A/E ARCHITECT / ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BREAK HORSEPOWER

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C CELSIUS

CA COMPRESSED AIR

CGA COMPRESSED GAS ASSOCIATION

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CO CLEANOUT

CS CLINICAL SINK

CV CONTROL VALVE

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

EL ELEVATION

EMCS ENERGY MONOSERRAT

AND CENTRAL SYSTEM

EPA ENVIROMENTAL PROTECTION

AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT

(HOSE)CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

GAL GALLON

GCO GRADE CLEANOUTS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

H&CW HOT AND COLD WATER

HB HOSE BIBB

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK

(DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

ID INSIDE DIAMETER

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

KW KILOWATT

KWH KILOWATT-HOUR

L/S LITER PER SECOND

LA LABORATORY AIR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT

ROOM

MGDU MEDICAL GAS DISTRIBUTION UNIT

MH MANHOLE

MOU MEMORANDUM OF

UNDERSTADING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N20 NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW LEADER

PA PASCAL

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ATMOSPHERE

PSIG POUNDS PER SQUARE INCH GAGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

PW POTABLE WATER

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RO REVERSE OSMOSIS WATER

SAN SANITARY SEWER

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS

NATIONAL ASSOCIATION

SCFM STANDARD CUBIC FOOT/MINUTE

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF SQUARE FEET

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

TCV TEMPERATURE CONTROL

VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

V VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

YCO YARD CLEANOUT

YH YARD HYDRANT

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

P-001

NOTES, LEGENDS, & SCHEDULES -

PLUMBING

JCJ DLO

Revisions: Date: 146 OF 206

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

2 2.5 3 4A

A.1

B

B.8

C

D

E

F

G

H

I

J

K

L

L.2

M

6"

3"

S S

S S

2"

3"

SD

2"

3"

2"

3"SD UP

(564 SF)

W/WCO

3"SD UP

(722 SF)

W/WCO

3"SD UP

(570 SF)

W/WCO

3"CAMPUS HEATING SUPPLY &

RETURN SEE CIVIL PLANS FOR

CONTINUATION.

3"

SD

(2) 2"CW LINES SEE

CIVIL PLANS FOR

CONTINUATION.

ROUTE TRAP PRIMER

PIPING FROM DRAIN TRAP

UP TO TRAP PRIMER.

6"FIRE LINE SEE

CIVIL PLANS FOR

CONTINUATION.

F

SS

4" 4"

SSSS

4"

4" 3"

S S

S S

2" (TYP)

2" (TYP)

3"3"4"

S S

S S

SS

4"4"

3"

SS

S S4"

S S

2" (TYP)

2" (TYP)

S S

S S

S S

S S

S S

S S

S S

S S

S S

4"

SD

4"

3" 2"

4"SD UP

(3212 SF)

3"SD UP

(2285 SF)

S D

3"

S D

4"

SD

S S

S S

S S

S S

4"SD UP

(5497 SF)

4"SD. IE=2722.25'

(21,183 SQ FT)

SEE CIVIL PLANS

FOR CONTINUATION.

COTG

SS

4" 3"

COTF

2" UP

W/WCO

6"

6"COTF

(FFE=2725.85)

8"

SD

S D

5"

S D

2"

2" UP

W/WCO 3"

4"

3"SD UP

(2171 SF)

SD

SD

SD

2"

3"

3"

2"2" 3"

3"SD UP

(835 SF)

SS

5"

S D

3"

3"SS UP SEE

PL403 FOR

CONTINUATION.

COTF

3"

S D

SDSD

3" 3"

3"SD UP

(835 SF) 3"SD UP

W/WCO

(651 SF)

SS

2"W UP TO EYE

WASH W/2"V

3" 3"

3"SD UP

(2171 SF)

3"SD UP

(835 SF)

S S

S S

S S

S S

3" 3"

2"

3"

3"SD UP

(835 SF)

ROUTE TRAP PRIMER

PIPING FROM DRAIN

TRAP UP TO TRAP

PRIMER (TP-2)

SS

S

SS

S

3"

3"

3"

4"

COTG

6"W. IE=2720.35'

SEE CIVIL PLANS FOR

CONTINUATION.

2 7

5 7

12 7

12 10

2 7

6"

WCO

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PW101

FOUNDATION PLAN - PLUMBING

Checker Author

SCALE: 1/8" = 1'-0"

NORTH

FOUNDATION PLAN - PLUMBING

KEY NOTES

3"W UP TO WATER CLOSET AND 2"V UP IN WALL.

ROUTE 2"W BELOW SLAB TO 1-1/2"W UP TO LAV

ROUTE 2"W BELOW SLAB TO 1-1/2"W UP TO EXAM SINK

3"W WITH P-TRAP UP TO SERVICE SINK AND 2"V UP

2"W UP TO SINK

ROUTE 2"W BELOW SLAB TO 1-1/2" UP TO EXAM SINK. ROUTE

PIPING TO AVOID FOOTINGS. OFFSET PIPE IN WALL ABOVE TO

ALIGN WITH SINK.

ROUTE PIPE FULL SIZE UP TO ABOVE SLAB TO WALL CLEANOUT

3"W WITH P-TRAP UP TO FLOOR DRAIN AND 2"V UP

4"W WITH P-TRAP UP TO FLOOR DRAIN AND 2"V UP

ROUTE WASTE UP TO FLOOR CLEANOUT FLUSH WITH FLOOR

FINISH.

2"W UP TO DRINKING FOUNTAIN WITH WALL CLEANOUT ABOVE

GRADE

2"W WITH P-TRAP UP TO FLOOR SINK OR FLOOR DRAIN AND 2"V

UP

ROUTE 2"W BELOW GRADE STUB UP ABOVE SLAB AND CAP FOR

FUTURE CONNECTION TO EXAM SINK UNDER BASE BID

ROUGH IN 3"W AND 2"V FOR FUTURE FLOOR MOUNTED WATER

CLOSET UNDER BASE BID

ROUTE 2"W BELOW GRADE ROUTE 1-1/2"W UP IN WALL AND

ROUGH IN FOR FUTURE LAV UNDER BASE BID

ROUTE 2"W BELOW GRADE ROUTE 1-1/2"W UP IN WALL AND

ROUGH IN FOR FUTURE EXAM SINK UNDER BASE BID

Revisions: Date: 147 OF 206

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

1 2 2.5 3 4A

A.1

B

B.8

C

D

E

F

G

H

I

J

K

L

L.2

M

ELEC

OIT

SERVER

OFFICE

OFFICE

STAFF TLT

STAFF TLT

SOILED

MED EQUIP

STAFF TLT

STAFF TLT

STAFF

LOUNGE

MECH

CORRIDOR

C15STAFF

LOCKERS

EXAM

ROOM 07

EXAM

ROOM 06

EXAM

ROOM 05

CORRIDOR

C12

EXAM

ROOM 04

PUBLIC

TLT

ALCOVE

EXAM

ROOM 03

EXAM

ROOM 02

EXAM

ROOM 01

WOMEN'S

HEALTH 01

WOMEN'S

HEALTH

TLT

118A

STORAGE

107A

STORAGE

CORRIDOR

C10

PUBLIC

TLT

PUBLIC

TLT

109 MSA &

BUSINESS

SERVICES

HOUSEKEEPING

AND

LADDER

GROUP

ROOM

LOBBY

VESTIBULE

LOBBY

POLICE

FAMILY

TLT

PUBLIC

TLT

LACTATION

CLEAN

SUPPLY

PROCEDURE

ROOM 01

ALCOVE,

H/W

ALCOVE,

H/W

CORRIDOR

C11

PACT

TEAM

PACT

TEAM

SHELL

CORRIDOR

C14

EXAM

ROOM 08

EXAM

ROOM 09

EXAM

ROOM 10

PACT

TEAM

CORRIDOR

C13

EXAM

ROOM 11

EXAM

ROOM 12

EXAM

ROOM 13

EXAM

ROOM 14

PACT

TEAM

SHELL

CORRIDOR

C15

CORRIDOR

C14

STAFF

LOCKERS

STAFF

LOCKERS

P-401

P-115

P-401

P-115

P-401 P-401

P-115P-115

P-528

P-413

P-413

P-413

P-413

P-115

P-401

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-115

P-401

P-413

P-413

P-413

P-413

P-413

P-413

P-115

P-115

P-401

P-401

P-608

P-502

P-708

P-115

P-401

P-115

P-401

P-413

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL102

FLOOR PLAN - PLUMBING

Checker Author

SCALE: 1/8" = 1'-0"

PROJECT

NORTH

FLOOR PLAN - PLUMBING

KEY NOTES

SEE 1/PL401 FOR

PIPING IN THIS AREA

SEE 1/PL402 FOR

PIPING IN THIS AREA

SEE 1/PL403 FOR

PIPING IN THIS AREA

Revisions: Date: 148 OF 206

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

1 2 2.5 3 4

I

J

K

L

L.2

M

3/4"CW DN

2"V DN

FD-M

FD-S

2"V DN

& 3"VTR

P-805

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL103

MECHANICAL ROOM PLAN -

PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

PROJECT

NORTH

MECHANICAL ROOM PLAN - PLUMBING

KEY NOTES

AREA OF WORK

KEY PLAN

Revisions: Date: 149 OF 206

1 2 2.5 3 4

A

A.1

B

B.8

C

D

E

F

G

H

I

J

K

L

L.2

M

RD-2

RD-1

(1155) (1155)

RD-2 RD-1(1155) (1155)

(651) (651)

RD-2 (1155)RD-1(1155)

RD-2

RD-1

(1155) (1155)

(2300)

(2300)

(1757)

(1757) RD-1

RD-2(1757)

(1757)

(570)RD-1

RD-2

RD-1RD-2

RD-1RD-2

(570)

RD-1RD-2

RD-1RD-2

(722) (722) (570)(570)

(2300) RD-1

(2300) RD-2

3" VTR

3" VTR

3" VTR

3" VTR

3" VTR

3" VTR

3" VTR

3" VTR

RD-2

RD-1

3" VTR

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

P-104

ROOF PLAN - PLUMBING

Checker Author

KEY NOTES

SCALE: 1/8" = 1'-0"

PROJECT

NORTH

ROOF PLAN - PLUMBING

Revisions: Date: 150 OF 206

1 2 3 4

B

C

D

E

F

G

H

I

J

K

L

M

N

1.1 3.9

L.2

A.1

2.1 2.92.5

B.8

A

2 1 1 1 1 1

1 1

1 111

3 3

F

F

FFFF

F

F

F

OFFICE

OFFICE

SOILED MED

EQUIP

STAFF LOUNGE

MECH

STAFF LOCKERS

STAFF LOCKERS

STAFF LOCKERS

STAFF LOCKERS

EXAM ROOM 07

EXAM ROOM 06

EXAM ROOM 05

EXAM RM 04

EXAM ROOM 14

EXAM ROOM 13

EXAM ROOM 12

EXAM ROOM 11

EXAM ROOM 21

EXAM ROOM 20

EXAM ROOM 19

EXAM ROOM 18

EXAM ROOM 28

EXAM ROOM 27

EXAM ROOM 26

EXAM ROOM 25

PACT TEAM

EXT TEAM

EQUIP

EXT TEAM

EQUIP

PACT TEAM

P TLT

P TLT

159MED ALCOVE

MED ALCOVE

EXAM ROOM 03

EXAM ROOM 02

EXAM ROOM 01

WOMEN'S

HEALTH 01

EXAM ROOM 10

EXAM ROOM 09

EXAM ROOM 08

PROCEDURE

ROOM 01

WH TLT

118A

PROCEDURE

ROOM 01

EXAM ROOM 15

EXAM ROOM 16

EXAM ROOM 17

PACT TEAM

PACT TEAM

EXAM ROOM 24

EXAM ROOM 23

EXAM ROOM 22

WH TLT

163A

WOMEN'S

HEALTH 02

CLEAN SUPPLY

CLEAN SUPPLY

ALCOVE, H/W

ALCOVE, H/W

STORAGE

STORAGE

114A

GROUP ROOM

TLT PUBLIC

TLT PUBLIC

108 POLICE

FAMILY TLT

TLT PUBLIC

LACTATION

RECEPTION

WAITING

VESTIBULE

WC ALCOVE

101A

WAITING

COFFEE

102D

LOBBY

S TLT

ELEC

170 OIT SERVER

CORRIDOR

C10

MSA & BUSINESS

SERVICES

HOUSEKEEPING

AND LADDER

CORRIDOR

C12

S TLT

S TLT

177 S TLT

CORRIDOR

C15

MED 1

MED 2

CORRIDOR

C11

CORRIDOR

C13 CORRIDOR

C14

6"FIRE LINE SEE

CIVIL PLANS FOR

CONTINUATION

FIRE DEPARTMENT

CONNECTION

FIRE PROTECTION

RISER

P-501

4"

4"

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PF105

FIRE PROTECTION - AUTOMATIC

SPRINKLER SYSTEM - FLOOR PLAN

Checker Author

KEY NOTES

LIGHT HAZARD LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

ORDINARY HAZARD GROUP 1 LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

ORDINARY HAZARD GROUP 2 LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

SCALE: 1/8" = 1'-0"

PROJECT

NORTH

AUTOMATIC SPRINKLER SYSTEM - FIRE PROTECTION - FLOOR PLAN

Revisions: Date: 151 OF 206

1 2 3 4

I

J

K

L

M

N

1.1 3.9

L.2

2.1 2.92.5

1/4" / 1'-0"

/4

1/4" / 1'-0"

/4

1/ 4"

1'

-0 "1/4" / 1'-0"

/4

1/ 4"

1'

-0 " 1/4" / 1'-0"

MECH

PENTHOUSE

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PF106

FIRE PROTECTION - AUTOMATIC

SPRINKLER SYSTEM - PENTHOUSE

PLAN

Checker Author

KEY NOTES

LIGHT HAZARD LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

ORDINARY HAZARD GROUP 1 LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

ORDINARY HAZARD GROUP 2 LEVEL FIRE PROTECTION REQUIRED IN THIS AREA.

SCALE: 1/4" = 1'-0"

PROJECT

NORTH

AUTOMATIC SPRINKLER SYSTEM - PENTHOUSE PLAN

AREA OF WORK

Revisions: Date:

B F

P B

F P

B F

P

2 2.5 3 4

A

A.1

B

B.8

C

D

E

3"SD UP TO RD-1 (564 SF)

3"SD UP TO RD-2 (564 SF) 3"SD DN

3"SD UP TO RD-2 (722 SF)

3"SD UP TO RD-1 (722 SF)

3"SD DN

SD

3"

2"

1" 1"

2"

1-1/2"

1/2"

3/4"

SD

3"

3"

2"

3"VTR 2"

3"SD DN

1/2"

3"SD UP TO RD-1 (570 SF)

3"SD UP TO RD-2 (570 SF)

2" 2"

2"

TMV

2"

WH

P-HW

P-HW

HX

2"V DN

2"V DN

1- 1/4"HW & CW DN

TO MIXING VALVE.

1- 1/2"HW & CW

DN TO WH-1.

P-HWR

P-HWR

EXP

3"VTR

1-1/2"

2-1/2"

2"V DN (TYP 2)

CALIBRATED BALANCE

VALVE SET AT 0.5 GPM

1/2"CW DN TO

TRAP PRIMER

FIRE RISER

2"V DN

(2)2"CW DN. SEE

PW101 FOR

CONTINUATION.

3/4"CW DN TO HEATING

SYSTEM FILL BACK FLOW.

BUILDING HEATING

HEAT EXCHANGER

2-1/2"

1-1/2"1"

3/4"

2"

1-1/4" 2"

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"

SD

SD

S D

S D

3"SD UP TO RD-1 (2285 SF)

3"SD UP TO RD-2 (2285 SF)

3"SD DN TO

DSN-1

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"

4"

CO

4"SD DN

S D

3"

1-1/4" 2"

1-1/2"

1"

1/2"

3"VTR

2"

1/2"

3/4"

2"

2"

2"

1" 3/4"

3"VTR

1-1/2"

3/4"

3/4"

2"

1/2" 3/4"

1/2"

1/2"

3/4"

1-1/2"

1-1/2"

3"

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

SD

SD

S D

SD

S D

S D

3"SD UP TO RD-1 (2285 SF)

3"SD UP TO RD-2 (2285 SF)

3"SD DN TO

DSN-1

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

CO

3"

4"

3"

4"SD DN

2"VDN

& 3"VTR

3"SD DN

2"

1-1/2"

S D

P-115

SD SD

DNS-1

P-4012

P-115 1

P-4012

P-532 3

P-1151 P-812 7

P-115 1

P-528 3 P-4012

P-812 7

P-401 2

BFP-1

BFP-2

FD-M

TP-1

FD-M

FD-E

BFP-3

FD-M

DSN-1

P-501

7 9

WCO

DSN-1

P-501

SD

P-1151

P-1152

1-1/2"

1"

1" 1"

ELEC

OIT

SERVER

OFFICE

OFFICE

STAFF

LOCKERS

CORRIDOR

C15

CORRIDOR

C12

EXAM

ROOM 07

EXAM

ROOM 06

PACT

TEAM

STAFF TLT

174 STAFF TLT

SOILED

MED EQUIP

STAFF TLT

STAFF TLT

STAFF

LOUNGE

MECH

STAFF

LOCKERS

CORRIDOR

C15

CORRIDOR

C14

PACT

TEAM

SHELL

STAFF

LOCKERS

STAFF

LOCKERS

EXAM

ROOM 14

EXAM

ROOM 13

CORRIDOR

C13

EXAM

ROOM 12

EXAM

ROOM 11

EXAM

ROOM 04

ALCOVE

PUBLIC

TLT

CORRIDOR

C12

EXAM

ROOM 03

PACT

TEAM

EXAM

ROOM 10

CORRIDOR

C13

PACT

TEAM

SHELL

PACT

TEAM

SHELL

CORRIDOR

C14

COTF

2"

3"SD PIPING SEE

PL402 FOR

CONTINUATION.

2"CW, 2"V & 3/4"HW

PIPING SEE PL402

FOR CONTINUATION.

1"HW, 1-1/2"V &

3/4"CW PIPING SEE

PL402 FOR

CONTINUATION.

1"CW, 2"V &

3/4"HW PIPING

SEE PL402 FOR

CONTINUATION.

2"CW, 1-1/4"HW

PIPING SEE PL402 FOR

CONTINUATION.

3"SD PIPING SEE

PL402 FOR

CONTINUATION.

FOR CONTINUATION

SEE 1/ PL402

A

FOR CONTINUATION

SEE 1/ PL402

A

P-413

P-413

P-413

P-413

P-413

P-413

4P-413

4P-413

4P-413

FD-M

2"

EXAM

ROOM 05

P-501

P-501

P-501

P-501

P-501

P-501

P-501

P-501

3"VTR STUBBED IN

BELOW CEILING

FOR FUTURE.

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL401

ENLARGED FLOOR PLAN - EAST -

PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

PROJECT

NORTH

ENLARGED FLOOR PLAN - EAST - PLUMBING

KEY NOTES

1"CW WITH BALL VALVE AND 2"V DOWN TO WATER CLOSET

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO

LAVATORY

1/2"HW & CW WITH BALL VALVES AND 2"V DOWN TO SINK

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO EXAM

SINK.

1/2"CW WITH BALL VALVE DN TO REFRIGERATOR ICE MAKER

WATER CONNECTION

CALIBRATED BALANCING VALVES SET AT 1 GPM.

1/2" WATER LINE STUBBED OUT WITH SHUTOFF VALVE FOR

FUTURE SINK AND CAPPED

1-1/2"CW STUBBED OUT WITH SHUTOFF VALVE FOR FUTURE

TOILET ROOM AND CAPPED

1-1/2"V STUBBED OUT AND CAPPED FOR CONNECTION TO

FUTURE EXAM SINK

AREA OF WORK

Revisions: Date: 153 OF 206

F

G

H

3"

1-1/4" 2"

2"

2"

2"

S D

S D

S D

S D

3"

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"SD DN TO

DSN-1

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"

3"SD UP TO RD-2 (2171 SF)

3"SD UP TO RD-1 (2171 SF)

3"

1-1/4"

3"SD DN TO

DSN-1

3"

1-1/4"

2"

DSN-1

P-501

DSN-1

P-501

S D

SD SD

S D

SD

3"

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"SD DN TO

DSN-1

DSN-1

P-501

3"SD DN TO

DSN-1

DSN-1

P-501

3"SD UP TO GUTTER

OUTLET (803 SF). SEE

DETAIL 5/A-504

3"

3"

S D

3/4"

2"

3"SD UP TO RD-2 (2171 SF)

3"SD UP TO RD-1 (2171 SF)

3"SD DN

1-1/2"

1" P-401 2

2"

3/4"

P-1151

P-532 3

1"

P-532 4

1-1/2"

1-1/2"

3/4"

3/4"

1"

3/4"

1"

1"

3/4"

2"

2"

3/4"

3/4"

SDSD

S D

3"SD DN

1"HW PIPING SEE

PL403 FOR

CONTINUATION

2"CW, 1-1/4"HW, &

3"SD PIPING SEE

PL403 FOR

CONTINUATION.

CORRIDOR

C11

WOMEN'S

HEALTH

TLT

118A

WOMEN'S

HEALTH 01

CLEAN

SUPPLY

PACT

TEAM

ALCOVE

CORRIDOR

C12 EXAM

ROOM 03

PACT

TEAM

EXAM

ROOM 02

EXAM

ROOM 01

PACT

TEAM

ALCOVE,

H/W

ALCOVE,

H/W

CORRIDOR

C13

PROCEDURE

ROOM 01

PACT

TEAM

SHELL

EXAM

ROOM 08

EXAM

ROOM 09

EXAM

ROOM 10

PACT

TEAM

SHELL

CORRIDOR

C14

PACT

TEAM

SHELL

CORRIDOR

C14

CORRIDOR

C11

COTF

FOR CONTINUATION

SEE 1/ PL401

A

FOR CONTINUATION

SEE 1/ PL401

A

FOR CONTINUATION

SEE 1/ PL403

B

FOR CONTINUATION

SEE 1/ PL403

B

3"SD PIPING SEE

PL401 FOR

CONTINUATION.

2"CW, 2"V & 3/4"HW

PIPING SEE PL401\

FOR CONTINUATION.

1"HW, 1-1/2"V & 3/4"CW

PIPING SEE PL401 FOR

CONTINUATION.

3"SD PIPING SEE

PL403 FOR

CONTINUATION.

2"CW & 3/4"HW

PIPING SEE PL403

FOR CONTINUATION.

3/4"CW, & 3/4"HW, &

2"V PIPING SEE

PL403 FOR

CONTINUATION

1"CW, 2"V & 3/4"HW

PIPING SEE PL401

FOR CONTINUATION.

2"CW & 1-1/4"HW

PIPING SEE PL401

FOR CONTINUATION.

3"SD PIPING SEE PL401

FOR CONTINUATION.

P-413

4P-413

4P-413

4P-413

4P-413

4P-413

4P-413

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL402

ENLARGED FLOOR PLAN - CENTER -

PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

NORTH

ENLARGED FLOOR PLAN - CENTER - PLUMBING

KEY NOTES

1"CW WITH BALL VALVE AND 2"V DOWN TO WATER CLOSET

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO

LAVATORY

1/2"HW & CW WITH BALL VALVES AND 2"V DOWN TO SINK

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO EXAM

SINK.

NOT USED

NOT USED

1/2" WATER LINE STUBBED OUT WITH SHUTOFF VALVES FOR

FUTURE SINK AND CAPPED

1-1/2"CW STUBBED OUT WITH SHUTOFF VALVE FOR FUTURE

TOILET ROOM AND CAPPED

1-1/2"V STUBBED OUT AND CAPPED FOR CONNECTION TO

FUTURE EXAM SINK

1-1/2"V FROM FIXTURE ROUGH IN UP TO ABOVE 12'-6" AND

CAPPED FOR FUTURE INSTALLATION OF SINK AND CONNECTION

TO VTR.

AREA OF WORK

Revisions: Date: 154 OF 206

I

J

K

L

L.2

M

3"

SD

S D

CO

3"

1-1/2"

3"SD UP TO

RD-2 (835 SF)

3"SD UP TO RD-1 (835 SF)

AND DN IN CHASE

3"VTR

2"V DN

P-115 1

P-4012

P-115 1

P-4012

3/4"

1"

P-608 8

3/4"

3"

3/4"CW UP TO HOSE BIBB

SEE PL103 FOR CONTINUATION.

CO

3"

3"W AND 2"V UP TO

FLOOR DRAIN SEE

PL103 FOR CONT. (TYP 2)

3"W DN SEE PW101

FOR CONTINUATION

1"

2"

1/2"

1-1/4"

P-502 5

3/4"

2"V DN

3/4"

P-708 6

P-502 5

3"SD UP TO RD-2 (835 SF)

3"SD UP TO RD-1 (835 SF)

AND DN IN CHASE

3"VTR

2"V DN

P-1151

P-4012

3"SD DN

2"

P-4012

SDSD

SD

S D

S D

SD

SD

S D

CO

2"

2"

1-1/4"

P-1151 1-1/2"

COTF

FD-C

FD-S

PROVIDE SOLID COVER

UNDER BASE BID

2"V DN

(TYP 3)

COTF

3/4"CW & HW, AND 2"V STUBBED OUT

FOR FUTURE ADD ALT 1 COFFEE SHOP.

CO

3"SD DN TO DSN-1

DSN-1

P-501

3"SD UP TO RD-2 (835 SF)

3"SD UP TO RD-1 (835 SF)

CO

CO

3"SD UP TO RD-2 (651 SF)

3"SD UP TO RD-1 (651 SF)

3"SD DN TO DSN-1

DSN-1

P-501

3"SD UP TO RD-2 (835 SF)

3"SD DN

3"SD UP TO RD-1 (835 SF)

WCO

CORRIDOR

C11

CORRIDOR

C11

STORAGE

CORRIDOR

C10

PUBLIC

TLT

PUBLIC

TLT

CORRIDOR

C11

LOBBY

GROUP

ROOM

LOBBY

LOBBY

MSA &

BUSINESS

SERVICES

HOUSEKEEPING

AND

LADDER

POLICE

FAMILY

TLT

PUBLIC

TLT

LACTATION

LOBBY

VESTIBULE

COTF

FOR CONTINUATION

SEE 1/ PL402

B

FOR CONTINUATION

SEE 1/ PL402

B

3"SD PIPING SEE

PL402 FOR

CONTINUATION.

2"CW & 3/4"HW

PIPING SEE PL402

FOR CONTINUATION.

1"HW PIPING SEE

PL402 FOR

CONTINUATION

3/4"CW, & 3/4"HW, &

2"V PIPING SEE

PL402 FOR

CONTINUATION.

2"CW, 1-1/4"HW, &

3"SD PIPING SEE

PL402 FOR

CONTINUATION.

ACCESS PANEL

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL403

ENLARGED FLOOR PLAN - WEST -

PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

NORTH

ENLARGED FLOOR PLAN - WEST - PLUMBING

KEY NOTES

AREA OF WORK

KEY PLAN

1"CW WITH BALL VALVE AND 2"V DOWN TO WATER CLOSET

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO

LAVATORY

1/2"HW & CW WITH BALL VALVES AND 2"V DOWN TO SINK

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO EXAM

SINK.

1/2"HW & CW WITH BALL VALVES AND 2"V DOWN TO MOP SINK

1/2"HW & CW WITH BALL VALVES DOWN TO EMERGENCY

FIXTURE, TEMPERING VALVE, AND 1/2" TEMPERED WATER FROM

VALVE TO EYE/FACE WASH.

1/2"CW WITH BALL VALVE DN TO REFRIGERATOR ICE MAKER

WATER CONNECTION

1/2"CW WITH BALL VALVE AND 2"V DN TO WATER COOLER

Revisions: Date: 155 OF 206

PLUMBING FIXTURE SCHEDULE

SYMBOL DESCRIPTION

MANUFACTURER AND CATALOG #

(BASIS OF DESIGN ONLY OTHER

MANUFACTURES THAT MEET THE

SPECIFICATIONS ARE ACCEPTABLE)

FAUCET/FLUSH VALVE

CONNECTIONS

NOTES

HW CW IW V

TRIPLE COMPARTMENT

COUNTER MOUNTED SINK

ELKAY LTR542210

ELKAY LKAV2061 SINGLE HANDLE

WITH SPRAY

1/2" 1/2" 2" - ROUTE INDIRECT WASTE TO NEAREST FLOOR SINK

COUNTER MOUNT HAND

WASH SINK

ELKAY BCR15

15"X15"X6.125"

ELKA LKA2475LF, BELOW DECK

MOUNT, TWO HANDLE, 4" ADA

BLADE, 8" GOOSENECK, W/HOSE

SPRAY

1/2" 1/2" 1-1/2" - ROUTE INDIRECT WASTE TO NEAREST FLOOR SINK

ESPRESSO MACHINE

REDUCED PRESSURE

BACK FLOW DEVICE

WATTS LF009 QT

LEAD FREE, QUARTER TURN

VALVES AIR GAP FITTING

- 1/2" - - ROUTE AIR GAP DRAIN LINE TO NEAREST FLOOR SINK

COFFEE MAKER DOUBLE

CHECK BACK FLOW

DEVICE

WATTS LF007 QT

LEAD FREE, QUARTER TURN

VALVES

- 1/2" - - -

REMOVE SOLID TOP FROM

EXISTING FLOOR SINK

ROUTE 1/2"CW UP TO

COFFEE MAKER

ROUTE 1/2"CW UP TO

ESPRESSO MAKER

1/2"HW & CW UP

TO HAND SINK

BFP-5

BFP-4

P-531

BFP-5

P-524

BFP-4

1/2"

MOUNT BACK FLOW

DEVICES IN CABINET

BELOW SINK. PROVIDE

ACCESS FOR SERVICE

AND TESTING

P-531 P-524

GENERAL NOTES

1. SLOPE ALL SEWERS @ 1/4" PER FOOT UNLESS APPROVED BY LOCAL

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

I

J

K

3"VTR

SDSD

S D

FOR CONTINUATION

SEE 1/ PL402

B

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL404

COFFEE AREA - ADD ALT 1 -

PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

PROJECT

NORTH

COFFEE AREA - ADD ALT 1 - PLUMBING

KEY NOTES

AREA OF WORK

Revisions: Date: 156 OF 206

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

2.5 3 4

E

F

G

H

I

3"

2"

S D

S D

S D

3" 3"

3"SD UP TO RD-2 (2171 SF)

3"SD UP TO RD-1 (2171 SF)

3"

P-115 1

2"

SDSD

S D

S D

3 P-532

P-5323 P-401 2

2"

2"

EXAM

ROOM 17

EXAM

ROOM 16

EXAM

ROOM 15

PROCEDURE

ROOM 01

CORRIDOR

C13

CORRIDOR

C13

CLEAN

SUPPLY

PUBLIC

TLT

EXAM

ROOM 24

EXAM

ROOM 23

EXAM

ROOM 22

WOMEN'S

HEALTH 02

WOMEN'S

HEALTH

TLT

163A

P-413

4P-413

4P-413

P-413

4 P-413

4 P-413

4 P-413

NECIL

CE D

S

T A

T

E I

FO

D A

H O

NOISSEF

O

R P

ENG

NI

E E

R

R

N

E

HCTRAK

KR

A

M

A

A L

P-14003

2-20-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

CONSTRUCT PRIMARY

CARE / MENTAL HEALTH

BUILDING

BOISE VA MEDICAL CENTER - BOISE, ID

531-325

SPEES DESIGN BUILD

625 1ST AVE #301

SEATTLE, WA, 98014

(206) 590-2118

RAY SPEES, PRESIDENT Approved: CHIEF, FACILITY MANAGEMENT SERVICE

07/23/2021

MEDICAL CENTER DIRECTOR

PL405

ENLARGED FLOOR PLAN - PACT

(WEST) - ADD ALT 3 - PLUMBING

Checker Author

SCALE: 1/4" = 1'-0"

NORTH

ENLARGED FLOOR PLAN - PACT (WEST) - ADD ALT 3 - PLUMBING

KEY NOTES

1"CW WITH BALL VALVES AND 2"V DOWN TO WATER CLOSET

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO

LAVATORY

1/2"HW & CW WITH BALL VALVES AND 2"V DOWN TO SINK

1/2"HW & CW WITH BALL VALVES AND 1-1/2"V DOWN TO EXAM

SINK.

AREA OF WORK

Revisions: Date: 157 OF 206

JURISDICTION. LINES 4" AND LARGER MAY BE SLOPED AT 1/8" PER

FOOT UPON APPROVAL OF LOCAL JURISDICTION AND COMPLYING

WITH REDUCED FIXTURE UNIT CAPACITY PER THE UPC.

2. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE

DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. CONTRACTOR MUST

VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE

BEGINNING ANY FABRICATION OR CONSTRUCTION.

3. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE

CURRENT VA GUIDES AND LOCAL PLUMBING CODES AND

ORDINANCES.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.

5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.

6. ALL VENT PIPING SHALL BE ABOVE FLOOD RIM LEVEL OF HIGHEST

FIXTURE BEFORE CONNECTION TO COMMON VENTS.

7. HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A CLEANOUT

AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING, THAT IS MORE

THAN 100' IN TOTAL DEVELOPED LENGTH. CLEANOUTS SHALL BE

PROVIDED IN A DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL

CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY FIVE

DEGREES.

8. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL PIPING

PENETRATIONS OF FIRE RATED ASSEMBLIES OR PROVIDE FIRE RATED

SEALS FOR NON-RATED PLASTIC PIPING PENETRATIONS OF RATED

ASSEMBLIES AS REQUIRED.

2.5 3 4

B

B.8

C

D

E

3"