531-325 - Drawings-05-S1.pdf
PDF 8 MB Posted
- Attached to
- Y1DZ--TIERED EVALS - Construct Primary Care/Mental Health Building Minor Construction - Boise 531-325
- Solicitation number
- 36C77624R0096
About this file
This document contains construction drawings and specifications for the Construct Primary Care/Mental Health Building Minor Construction Project at the VA Medical Center in Boise, ID. The project solicitation number is 36C77624R0096, and the federal agency is the Department of Veterans Affairs Technology Acquisition Center Austin.
The drawings outline the structural, architectural, and MEP requirements for the new building, including foundation, framing, roofing, and exterior wall details. The project involves constructing a primary care and mental health facility with reinforced concrete, steel, and metal stud wall framing. Key details include required concrete strengths, steel member sizes, open-web steel joist specifications, and blast-hardened interior wall construction. The drawings also include design criteria such as seismic, wind, and snow load requirements. The document does not contain a separate Performance Work Statement or Statement of Objectives.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
412 E. Park Center Blvd, Suite 200
Boise, ID 83706
O: 208.336.6985 www.kpff.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
BOISE VA MEDICAL CENTER - BOISE, ID
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(360) 223 - 8994
RAY SPEES, PRESIDENT
07/23/2021
MEDICAL CENTER DIRECTOR
Approved: CHIEF, FACILITY MANAGEMENT SERVICE S-000
TITLE SHEET
CH/JW SG
S-000
ISOMETRIC VIEW1
ARCH ARCHITECTURAL
BM BEAM
BRG BEARING
BTWN BETWEEN
BLKG BLOCKING
BOT BOTTOM
B.O. BOTTOM OF
CTR CENTER
CL CENTERLINE
CLR CLEAR
COL COLUMN
CJP COMPLETE JOINT PENETRATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
DBA DEFORMED BAR ANCHOR
DIA DIAMETER
BN DIAPHRAGM BOUNDARY NAILING
DWG DRAWING
EA EACH
ES EACH SIDE
EW EACH WAY
EL ELEVATION
ELEV ELEVATION
EQ EQUAL
FT FEET
FIN FINISH
FLR FLOOR
FTG FOOTING
FDN FOUNDATION
GA GAUGE
GR GRADE
HSS HOLLOW STRUCTURAL SECTION
HORIZ HORIZONTAL
IN INCH
INFO INFORMATION
INT INTERIOR
IBC INTERNATIONAL BUILDING CODE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OPNG OPENING
EN PANEL EDGE NAILING
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLWD PLYWOOD
PT POST-TENSIONED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
REINF REINFORCING
REQ'D REQUIRED
RTU ROOFTOP MECHANICAL UNIT
RO ROUGH OPENING
SCHED SCHEDULE
SECT SECTION
SHTG SHEATHING
SIM SIMILAR
SOG SLAB-ON-GRADE
SC SLIP CRITICAL
SPEC SPECIFICATION
SQ SQUARE
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STIFF STIFFENER
STIRR STIRRUP
STRUCT STRUCTURAL
SUPP SUPPORT
SYM SYMMETRICAL
TB TABLE
THK THICK(NESS)
THRU THROUGH
T&G TONGUE AND GROOVE
T&B TOP AND BOTTOM
T.O. TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VIF VERIFY IN FIELD
VERT VERTICAL
W W-SHAPE
WHS WELDED HEADED STUD
W/ WITH
W/O WITHOUT
WP WORK POINT
S-000 TITLE SHEET
S-001 GENERAL STRUCTURAL NOTES
S-002 SPECIAL INSPECTIONS 1 OF 2
S-003 SPECIAL INSPECTIONS 2 OF 2
SB201 FOUNDATION PLAN
SF202 FLAT ROOF PLAN
SF203 HIGH ROOF PLAN
SE301 BUILDING ELEVATIONS
SE302 BUILDING ELEVATIONS
SE303 FRAME ELEVATIONS
SE304 FRAME ELEVATIONS
SS311 BUILDING SECTIONS
SS312 BUILDING SECTIONS
SS314 WALL SECTIONS
SS315 WALL SECTIONS
SS316 WALL SECTIONS
SS317 WALL SECTIONS
SD401 CONCRETE DETAILS
SD402 CONCRETE DETAILS
SD501 STEEL DETAILS
SD502 STEEL DETAILS
SD503 STEEL DETAILS
SD504 STEEL DETAILS
SD505 STEEL DETAILS
SD510 METAL DECK DETAILS
SD601 COLD FORMED STEEL DETAILS
SD602 COLD FORMED STEEL DETAILS
DRAWING INDEX
Revisions: Date:
S T A T E O F I D A H O
P R
O
FESS I O NA L ENG I NEER
J UDS E N M . W I L L I A MS
1 2 0 3 3
R
EG I S T ER ED
STRUCTURAL DRAWINGS:
1. STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED WITH OTHER DRAWINGS, SPECIFICATIONS, AND DOCUMENTS ENUMERATED IN THE OWNER/CONTRACTOR AGREEMENT.
2. REVIEW AND COORDINATE THE REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCY IDENTIFIED SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT SO THAT A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS
SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE.
3. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
CODE REQUIREMENTS AND REFERENCED STANDARDS:
1. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING CODES:
2018 INTERNATIONAL BUILDING CODE (IBC), VA HANDBOOK H-18-8 SEISMIC DESIGN REQUIREMENTS AND LATEST REVISIONS REFERRED TO HERE AS “THE CODE”, AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK AND THOSE CODES & STANDARDS LISTED IN THESE NOTES AND
SPECIFICATIONS.
2. ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE THE VERSION REFERENCED IN CHAPTER 35 OF THE CODE OR
AS REFERENCED IN THE APPLICABLE DESIGN STANDARD.
EXISTING CONDITIONS:
1. VERIFY EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIOR TO STARTING CONSTRUCTION. NOTIFY THE
ARCHITECT ANY DISCREPANCIES OR INCONSISTENCIES.
2. INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY SUCH STRUCTURES ARE FOUND, NOTIFY THE ARCHITECT IMMEDIATELY.
TEMPORARY CONDITIONS:
1. THE CONTRACT DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION, INCLUDING BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER DO NOT INCLUDE INSPECTION OF THE ABOVE ITEMS.
2. THE CONTRACT STRUCTURAL DRAWINGS SHOW THE BUILDING IN ITS FINAL INTENDED POSITION. MAKE PROVISIONS IN THE CONSTRUCTION SEQUENCING OF THE BUILDING TO TAKE INTO ACCOUNTS SHRINKAGE, CREEP, SHORTENING, THERMAL EXPANSION, ETC.
3. SPREAD OUT CONSTRUCTION MATERIALS IF PLACED ON FRAMED ROOF OR FLOOR. LOAD SHALL NOT EXCEED THE
DESIGN LIVE LOAD PER SQUARE FOOT.
OTHER DRAWINGS:
1. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
A. SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED
B. SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS UNLESS NOTED AND/OR
DETAILED ON THE STRUCTURAL DRAWINGS
C. SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR DRAINS, SLOPES, DEPRESSED
AREAS, CHANGES IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC
D. SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN
E. FLOOR AND ROOF FINISHES
F. MISCELLANEOUS DRAINAGE AND WATERPROOFING
G. ALL FIREPROOFING REQUIREMENTS INCLUDING FIREPROOFING OF STRUCTURAL STEEL
H. DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS
2. SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
A. PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC., EXCEPT AS SHOWN OR NOTED.
B. ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS.
C. CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES.
D. SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR MOTOR MOUNTS.
GENERAL:
GEOTECHNICAL INVESTIGATION:
1. GEOTECHNICAL INFORMATION AND FOUNDATION DESIGN IS BASED ON THE FOLLOWING GEOTECHNICAL REPORTS AND SUPPLEMENTS/ADDENDUMS. COPIES OF THE REPORTS SHALL BE AVAILABLE AT THE JOBSITE AT ALL TIMES.
ALSO SEE PROJECT SPECIFICATIONS FOR REPORT.
GEOTECHNICAL DESIGN CRITERIA:
1. SPREAD OR CONTINUOUS FOOTINGS:
FOUNDATION REQUIREMENTS:
1. STRUCTURAL FILL: COMPACT ALL SOIL BELOW FOUNDATIONS AND SLABS-ON-GRADE TO MINIMUM 95% OF OPTIMUM
DRY DENSITY PER ASTM D1557.
2. FROST PROTECTION: AT EXTERIOR FOOTINGS, PROVIDE 30 INCHES MINIMUM FROM LOWEST ADJACENT GRADE TO BOTTOM OF FOOTING. VERIFY THAT FOOTING ELEVATIONS AND FINAL GRADES INDICATED WILL PROVIDED THIS MINIMUM DEPTH. NOTIFY ARCHITECT OF ANY LOCATIONS THAT MAY NOT ACHIEVE THIS MINIMUM FROST DEPTH.
3. PROVIDE DE-WATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER AND/OR SEEPAGE.
4. EXCAVATION FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO PLACING
CONCRETE AND REINFORCING.
5. REMOVE ALL ABANDONED FOOTINGS, UTILITIES, ETC. NEW FOOTINGS MUST EXTEND INTO UNDISTURBED SOILS.
6. THE DESIGN GROUNDWATER ELEVATION IS GREATER THAN 16 FEET BELOW EXISTING GRADE PER THE
GEOTECHNICAL INVESTIGATION REPORT.
FOUNDATION:
REPORT/ADDENDUM TITLE PREPARED BY DATE
ANTICIPATED BEARING MATERIAL ALLOWABLE
BEARING
CAPACITY
ALLOWABLE LATERAL
RESISTANCE
PASSIVE
RESISTANCE
COEFFICIENT
OF FRICTION
MTI FILE NUMBER B201282g NICK STEVENS, G.I.T. AUGUST 28, 2020
FOOTINGS MUST BEAR ON AT LEAST 1.5 FEET OF
COMPACTED STRUCTURAL FILL REINFORCED WITH TWO
LAYERS OF TENSER T160 GEOGRID. GEOGRID REINFORCED
FILL MUST BEAR ON NATIVE CLAYEY SAND OR SILTY SAND
SEDIMENTS. THE EXPOSED SUBGRADE SHOULD BE
PREPARED AS FOLLOWS:
1. SIX INCHES OF STRUCTURAL FILL (ISPWC TYPE 1
CRUSHED AGGREGATE BASE) SHOULD BE PLACED OVER
THE NATIVE CLAYEY SAND/SILTY SAND SEDIMENTS AND
BE COMPACTED TO AT LEAST 95% OF THE MAXIMUM DRY
DENSITY AS DETERMINED BY ASTM D1557.
2. A LAYER OF TENSER TX160 GEOGRID SHOULD BE
PLACED OVER COMPACTED STRUCTURAL FILL
FOLLOWED BY 6 INCHES OF COMPACTED STRUCTURAL
FILL. THIS PROCESS SHOULD BE CONTINUED UNTIL TWO
LAYERS OF GEOGRID ARE IN PLACE. AT LEAST 6 INCHES
OF COMPACTED STRUCTURAL FILL SHOULD BE PLACED
OVER THE TOP LAYER OF GEOGRID.
GEOGRID SHOULD EXTEND A MINIMUM OF 2 FEET BEYOND
FOOTINGS ON ALL SIDES. GEOGRID SHOULD BE
OVERLAPPED A MINIMUM DISTANCE OF 24 INCHES BETWEEN
SPLICES. SEE GEOTECH REPORT "PLATE 3" ATTACHED FILE
FOR GRAPHICAL REPRESENTATION OF THE SYSTEM.
2,000 PSF 349 PSF/FT 0.45
FLOOR LIVE LOADS:
EQUIPMENT ROOMS 150 PSF (N0 REDUCTION)
ROOF LIVE LOADS:
ROOF 20 PSF (REDUCIBLE)
ROOF SNOW LOADS: (SECTION 1603.1.3 OF THE CODE):
GROUND SNOW LOAD: Pg = 15 PSF
FLAT ROOF SNOW LOAD: Pf = 12 PSF
MINIMUM SNOW LOAD: Pm = 25 PSF
SNOW EXPOSURE FACTOR: Ce = 1.0
SNOW LOAD IMPORTANCE FACTOR: Is = 1.1
THERMAL FACTOR: Cf = 1.0
WIND DESIGN DATA:
WIND LOADS ARE IN ACCORDANCE WITH SECTION 1609 OF THE CODE.
RISK CATEGORY: III
BASIC WIND SPEED: V = 110 MPH (3-SECOND GUST)
WIND EXPOSURE: C
INTERNAL PRESSURE COEFFICIENT: GCpi = ± 0.18
EARTHQUAKE DESIGN DATA:
DESIGN CRITERIA:
COMPONENTS & CLADDING WIND PRESSURES (PSF)
LOCATION
ROOF
WALLS
PARAPETS
ZONE 1
COMPONENT TRIBUTARY AREA (SQ FT)
10 50 100
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 4
ZONE 5
SITE AND OCCUPANCY PARAMETERS
RISK CATEGORY
DESIGN SPECTRAL RESPONSE ACCELERATION
PARAMETERS
SEISMIC IMPORTANCE FACTOR
III
Ie = 1.25
SS = 0.312
S1 = 0.111
MAPPED SPECTRAL RESPONSE ACCELERATION
PARAMETERS
SDS = 0.323
SD1 = 0.176
SITE CLASS
BUILDING PARAMETERS
SEISMIC FORCE RESISTING SYSTEM
SYSTEM OVERSTRENGTH FACTOR
CS = 0.135
R = 3
DESIGN BASE SHEAR
Ω0 = 3
Cd = 3
RESPONSE MODIFICATION FACTOR
SEISMIC RESPONSE COEFFICIENTS
DEFLECTION AMPLIFICATION FACTOR
ANALYSIS PROCEDURE USED
D
SEISMIC DESIGN CATEGORY C
EQUIVALENT LATERAL FORCE
V = 199 KIPS
12.0 / -46.8
12.0 / -61.7
12.0 / -84.1
29.4 / -31.9
29.4 / -39.3
91.1 / -61.3
113.5 / -68.7
10.3 / -39.7
10.3 / -52.5
10.3 / -65.7
26.3 / -28.8
26.3 / -33.2
78.8 / -55.1
92.1 / -59.5
9.5 / -36.6
9.5 / -48.6
9.5 / -57.8
25.0 / -27.5
25.0 / -30.5
73.6 / -52.5
82.8 / -55.5
R = 3 BRACE FRAME SYSTEM
GENERAL:
1. COMPLY WITH THE PROVISIONS OF ACI 301 AND ACI 117, EXCEPT AS MODIFIED BY THESE CONTRACT DOCUMENTS.
2. MANUFACTURER QUALIFICATIONS: CERTIFIED ACCORDING TO NRMCA's "CERTIFICATION OF READY MIXED
CONCRETE PRODUCTION FACILITIES.
EXECUTION:
1. OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE SLABS, DECKS, OR WALLS UNLESS SPECIALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE ARCHITECT WHEN DRAWINGS BY OTHERS SHOW OPENINGS, POCKETS, ETC., LARGER THAN 6" NOT SHOWN ON THE STRUCTURAL DRAWINGS.
2. PIPES AND CONDUITS EMBEDDED IN CONCRETE:
A. PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT WHERE
SPECIFICALLY APPROVED BY ARCHITECT.
B. PIPES SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS.
C. DO NOT STACK CONDUITS. SPACE EMBEDDED PIPES AND CONDUITS AT A MINIMUM OF AT A MINIMUM OF 3 DIAMETERS CLEAR FROM OTHER EMBEDDED PIPES/CONDUITS AND 1 1/2" CLEAR FROM REINFORCING BARS.
D. NO CONDUITS SHALL BE PLACED IN CONCRETE FILL OVER METAL DECK.
3. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE PLACING. DO NOT CUT REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE IS NOT PERMITTED WITHOUT ARCHITECT REVIEW AND
APPROVAL.
4. SCREED CONCRETE FILL OVER STEEL DECK TO A CONSTANT THICKNESS AS SPECIFIED IN THE DECKING
SCHEDULE.
5. ALL CONCRETE SURFACES AGAINST WHICH NEW CONCRETE IS TO BE PLACED SHALL BE CLEANED AND
ROUGHENED TO 1/4" AMPLITUDE.
PRODUCTS:
1. CONCRETE MIXTURES: PREPARE DESIGN MIXTURES FOR EACH TYPE AND STRENGTH OF CONCRETE, PROPORTIONED ON THE BASIS OF LABORATORY TRIAL MIXTURES OR FIELD TEST DATA OR BOTH, ACCORDING TO ACI 301.
CONCRETE MIXTURES
LOCATIONS IN STRUCTURE DESIGN
STRENGTH
MAX UNIT
WEIGHT
MAX W/C
RATIO
FOOTINGS AND FOUNDATION WALLS 4,000 PSI 145 PCF 0.45
SLAB ON GRADE 4,000 PSI 145 PCF 0.45
NORMAL WEIGHT CONCRETE DECK 4,000 PSI 145 PCF 0.50
CURBS, PADS, TOPPING SLABS, ETC. 3,000 PSI 145 PCF 0.50
EXPOSURE
CATEGORIES
F1, S0, W0, C1
F0, S0, W0, C0
F1, S0, W0, C1
F1, S0, W0, C1
CONCRETE:
GENERAL:
1. DETAIL, FABRICATE, AND INSTALL REINFORCING IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 301, ACI 117, AND THE "CRSI MANUAL OF STANDARD PRACTICE."
REINFORCING STEEL:
PRODUCTS:
1. REINFORCING STEEL: ASTM A615, GRADE 60, DEFORMED
EXECUTION:
1. PROVIDE THE MINIMUM CONCRETE COVER FOR REINFORCEMENT IN CAST-IN-PLACE CONCRETE (NON-
PRESTRESSED) AS INDICATED IN THE TABLE BELOW.
MINIMUM CONCRETE CLEAR COVER
BAR SIZE
ALL
CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH
LOCATION
#6 & LARGER
CONCRETE EXPOSED TO EARTH OR WEATHER
CLEAR COVER
3"
2"
#5 & SMALLER 1 1/2"
#14 & LARGERSLABS, WALLS, OR JOISTS NOT EXPOSED TO
WEATHER OR IN CONTACT WITH THE GROUND
1 1/2"
#11 & SMALLER 3/4"
ALL
BEAM AND COLUMN TIES & STIRRUPS NOT EXPOSED
TO WEATHER OR IN CONTACT WITH GROUND
1 1/2"
GENERAL:
1. DETAIL, FABRICATE, AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE FOLLOWING PROVISIONS:
A. AISC 303 - "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES"
B. AISC 360 - "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS"
C. RCSC's - "SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS"
2. COMPLY WITH THE FOLLOWING PROVISIONS FOR ALL WELDED JOINTS:
A. AWS D1.1 - "STRUCTURAL STEEL WELDING CODE"
3. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360 SECTION J2.2b.
STRUCTURAL STEEL:
EXECUTION:
1. DO NOT CUT OR DAMAGE EXISTING REINFORCEMENT. PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED TO REINFORCED CONCRETE USING POST-INSTALLED ANCHORS, LOCATE ALL REINFORCEMENT AND CONFIRM CONTRACTIBILITY OF ANCHOR LOCATIONS. SHOULD CONFLICTS WITH REINFORCEMENT OCCUR, SUBMIT ALTERNATE ANCHOR LOCATIONS AND REVISED STEEL FABRICATIONS TO
ARCHITECT FOR REVIEW AND APPROVAL.
PRODUCTS:
1. ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED BELOW (UNO):
W SHAPES AND WT SHAPES A992, GR 50 (S75)
TYPE ASTM SPECIFICATION
ANGLES & CHANNELS A36
PLATES & BARS
A36
A572, GR 50 (WHERE INDICATED)
HSS SECTIONS A500 GR B
HIGH STRENGTH BOLTS
(AS INDICATED IN DETAILS)
A325 OR F1582 (TWIST-OFF TYPE)
ANCHOR RODS F1554 GR 36
F1554 GR 55 (WHERE INDICATED)
COMMON/MACHINE BOLTS A307, GR A
GENERAL
1. FABRICATE AND INSTALL STEEL DECK ACCORDING TO THE FOLLOWING PROVISIONS:
A. ROOF DECK: ANSI/SDI RD-2017, "STANDARDS FOR STEEL ROOF DECK."
B. COMPOSITE FLOOR DECK: ANSI/SDI C-2017, "STANDARDS FOR COMPOSITE STEEL FLOOR DECK-SLAB."
C. WELDING OF STEEL DECK: AWS D1.3, "SPECIFICATIONS FOR WELDING SHEET STEEL IN STRUCTURES."
STEEL DECK:
PRODUCTS
1. STEEL ROOF DECK: PROVIDE AND INSTALL ROOF AS NOTED ON THE STEEL DECK SCHEDULE. SUBSTITUTIONS MUST BE EQUAL OR BETTER TO THE PRODUCT SPECIFIED, AND MUST BE SUBMITTED TO THE DESIGN TEAM FOR
APPROVAL.
EXECUTION
1. EXAMINE SUPPORTING FRAME AND FIELD CONDITIONS FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE. PROCEED WITH INSTALLATION ONLY AFTER
UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
A. RUN UNITS CONTINUOUS OVER THREE OR MORE SPANS.
B. PROVIDE 2" MINIMUM DECK BEARING AT ALL SUPPORTS.
2. INSTALL DECK PANELS AND ACCESSORIES ACCORDING TO ANSI/SDI STANDARDS AND MANUFACTURER'S WRITTEN
INSTRUCTIONS.
3. INSTALL TEMPORARY SHORING BEFORE PLACING DECK PANELS AS REQUIRED TO MEET DEFLECTION LIMITATIONS.
GENERAL
1. FABRICATE AND INSTALL COLD-FORMED METAL FRAMING ACCORDING TO THE FOLLOWING PROVISIONS:
A. AISI S100, "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS".
B. AISI S200, "NORTH AMERICAN STANDARD FOR COLD-FORMED STEEL FRAMING".
C. WELDING OF COLD-FORMED METAL FRAMING: AWS D1.3, "SPECIFICATIONS FOR WELDING SHEET STEEL IN
STRUCTURES."
COLD-FORMED METAL FRAMING:
PRODUCTS
1. PROVIDE GALVANIZED COLD-FORMED STEEL STUDS, TRACKS, AND FURRING CHANNELS CONFORMING WITH ICC-ES #3064P, "PRODUCT TECHNICAL GUIDE" BY THE STEEL STUD MANUFACTURERS ASSOCIATION AND THE FOLLOWING:
A. MATERIAL SPECIFICATION:
a. 16 GAGE AND THICKER: ASTM A653, GRADE 50 OR ASTM A1003, GRADE 50, TYPE H
b. 18 GAGE AND THINNER: ASTM A653, GRADE 33 OR ASTM A1003, GRADE 33, TYPE H
B. MINIMUM SECTION PROPERTIES: BASED ON ICC-ES #3064P, "PRODUCT TECHNICAL GUIDE" BY THE STEEL STUD
MANUFACTURERS ASSOCIATION.
EXECUTION
1. INSTALL COLD-FORMED STEEL FRAMING ACCORDING TO AISI S200 AND TO MANUFACTURER'S WRITTEN
INSTRUCTIONS.
OPEN WEB STEEL JOISTS:
1. DESIGN, DETAILING, FABRICATION, AND ERECTION OF OPEN-WEB STEEL JOIST SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. DESIGN SHALL COMPLY WITH THE CURRENT BUILDING CODE AND WITH LOADS SHOWN ON
THE GENERAL NOTES AND ON THE LOADING PLANS.
2. SHOP DRAWINGS (STAMPED AND SIGNED BY A LICENSED STRUCTURAL OR CIVIL ENGINEER IN THE STATE OF IDAHO) AND CALCULATIONS FOR OPEN-WEB STEEL JOISTS SHALL BE SUBMITTED FOR APPROVAL TO THE ARCHITECT OR
STRUCTURAL ENGINEER PRIOR TO FABRICATION.
3. NON-COMPOSITE LONGSPAN STEEL JOISTS, NOTED AS TYPE "LH", SHALL COMPLY WITH SJI-LH/DLH-2015 STANDARD
SPECIFICATION FOR LONGSPAN STEEL JOISTS, 2015.
4. NON-COMPOSITE K-SERIES STEEL JOISTS, NOTED AS TYPE "K", SHALL COMPLY WITH SJI 100-2015 STANDARD
SPECIFICATION FOR K-SERIES.
5. BEARING SEAT DEPTH TO BE DETERMINED BY THE CONTRACTOR AND COORDINATED WITH THE STEEL, CMU AND BEARING METAL STUD SUBCONTRACTORS TO DETERMINE TOP OF STEEL ELEVATIONS FOR STRUCTURE
SUPPORTING OPEN WEB STEEL JOISTS.
6. DESIGN ALL OWSJ FOR THE FOLLOWINGS MAXIMUM DEFLECTIONS:
A. TOTAL DEFLECTION < L/240
B. LIVE LOAD / SNOW LOAD DEFLECTION < L/360
7. STEEL JOIST SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO FABRICATION AND SHALL INDICATE NUMBER, TYPE, LOCATION, SPACING AND ANCHORAGE OF ALL STEEL
JOISTS. SHOP DRAWINGS MUST ALSO INCLUDE THE PROPOSED CAMBER OF ALL JOISTS.
8. PROVIDE MEP PIPE SUPPORT LOCATION AND ATTACHMENT SUBMITAL TO SEOR IF ATTACHED TO OWSJ.
P d
DRIFT LENGTH
DEAD LOAD
LIVE / FLAT ROOF SNOW LOAD / MINIMUM SNOW LOAD
SNOW DRIFT
WIND UPLIFT
BEND-CHECK
OR ADD-LOAD
AXIAL LOAD AXIAL LOAD
JOIST SCHEDULE (ASD)
JOIST TYPE
JOIST
DEPTH
DESIGN LOADS, PLF CONCENTRATED DESIGN LOAD, LB
DEAD
LOAD
ROOF
LIVE
LOADS
SNOW LOAD NET
WIND
UPLIFT
(ASD)
BEND-
CHECK
ADD-
LOAD
AXIAL
P f
P d
DRIFT
LENGTH
JOIST
DESIGNATION
OWSJ-01
OWSJ-02
JOIST
SPACING
1. DEAD LOADS LISTED ARE SUPERIMPOSED LOADS. SELF-WEIGHT OF JOISTS ARE NOT INCLUDED
2. WIND UPLIFT VALUES PROVIDED ARE SERVICE-LEVEL (ASD) NET WIND UPLIFTS (PLF) FROM ASCE 7-16, SECTION 30.4.
3. FOR ADD-LOAD, DESIGN JOIST FOR CONCENTRATED LOADS LOCATED AT ANY ONE PANEL POINT ALONG THE
JOIST. ADD LOADS SHOULD BE CONSIDERED AS DEAD LOADS.
4. FOR BEND-CHECK, DESIGN JOIST TOP CHORD FOR ADDITIONAL BENDING STRESSES RESULTING FROM
CONCENTRATED LOADS LOCATED AT ANY LOCATION ALONG CHORD.
6. COMBINE FLAT ROOF SNOW LOAD (Pf) AND DRIFT LOAD (Pd). DRIFT LOADS INDICATED SHOULD BE APPLIED
TO BOTH ENDS OF JOIST U.N.O.
8. BEARING SEAT NOTED IS NOMINAL AND DOES NOT ACCOUNT FOR SLOPED SEAT
REQUIREMENTS. COORDINATE FINAL BEARING SEAT DEPTH WITH STEEL FABRICATOR.
5. AXIAL LOADS PROVIDED ARE FROM WIND PRESSURE OR SEISMIC COLLECTOR FORCES THAT ARE ALREADY
FACTORED TO ASD OMEGA (Ω) LEVEL.
9. POINT LOADS SHOWN ON PLANS ARE VERTICAL SERVICE LEVEL (ASD) LOADS. THEY ARE
SHOWN AS TOTAL LOAD/LIVE LOAD.
12. VENDOR SHALL DETAIL BRIDGING AND WEB COMPONENTS OF JOISTS TO ENFORCE YIELDING OF THE
TOP AND BOTTOM CHORDS FOR LOADING IN THE UPWARD AND DOWNWARD DIRECTIONS.
10. SEE PLAN FOR ADDITIONAL LOADING APPLIED TO SPECIFIC JOISTS.
K-SERIES
P min
7. MINIMUM ROOF SNOW LOAD (P
min
) IS A SEPARATE UNIFORM LOAD CASE. IT NEED NOT BE USED IN DETERMINING
OR IN COMBINATION WITH DRIFT,UNBALANCED, OR PARTIAL LOADS.
24"
24"
7'-6" MAX
7'-6" MAX
LH-SERIES
OWSJ-03 LH-SERIES 24" 3'-10" MAX
4,000
4,000
2,000
2,000
2,000
2,000
1,000
1,000
1,000
11. ALL OWSJ TO HAVE 5" BEARING SEATS. EXCEPT AS INDICATED IN NOTE 8.
OWSJ-04 K-SERIES 18" 7'-0" MAX245 175 4,000140 3,0001,000
MIN
PANEL
POINTS
PER PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
BLAST
UPLIFT (AT
CONNECTION)
23,300
18,000
17,900
11,600
412 E. Park Center Blvd, Suite 200
Boise, ID 83706
O: 208.336.6985 www.kpff.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
BOISE VA MEDICAL CENTER - BOISE, ID
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(360) 223 - 8994
RAY SPEES, PRESIDENT
07/23/2021
MEDICAL CENTER DIRECTOR
Approved: CHIEF, FACILITY MANAGEMENT SERVICE S-001
GENERAL STRUCTURAL NOTES
CH/JW SG
R
O
FESS I O NA L ENG I NEER
J UDS E N M . W I L L I A MS
1 2 0 3 3
R
STRUCTURAL OBSERVATIONS:
1. KPFF WILL PERFORM STRUCTURAL OBSERVATION BASED ON THE REQUIREMENTS OF CHAPTER 17 OF THE CODE AT THE STAGES OF CONSTRUCTION LISTED BELOW. CONTRACTOR SHALL NOTIFY ARCHITECT AND PROVIDE ACCESS FOR KPFF TO PERFORM THESE OBSERVATIONS.
2. KPFF WILL ISSUE AN OBSERVATION REPORT TO ARCHITECT FOR DISTRIBUTION TO THE OWNER AND CONTRACTOR. OBSERVATION REPORT WILL IDENTIFY
WORK OBSERVED AND ANY WORK NOT IN CONFORMANCE WITH CONTRACT DOCUMENTS.
3. STRUCTURAL OBSERVATION IS TO VERIFY GENERAL CONFORMANCE WITH THE STRUCTURAL DRAWINGS. STRUCTURAL OBSERVATIONS DO NOT REPLACE THE
NEED FOR SPECIAL INSPECTION AS REQUIRED BY CHAPTER 17 OF THE CODE.
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION WILL BE PROVIDED BY A THIRD-PARTY TESTING AGENCY, RETAINED BY THE OWNER TO VERIFY COMPLIANCE WITH ITEMS SUMMARICED IN
THE STATEMENT OF SPECIAL INSPECTION.
2. CONTRACTOR SHALL PROVIDE SUFFICIENT NOTICE AND ACCESS FOR THE SPECIAL INSPECTOR TO PERFORM THESE INSPECTIONS.
STRUCTURAL OBSERVATIONS
ITEM
A. FOUNDATIONS
B. CONCRETE WALLS
C. STEEL FRAME
D. LATERAL FORC RESISTING SYSTEM
E. STEEL DECK DIAPHRAGMS
TIMING/FREQUENCY OF OBSERVATION
PRIOR TO FIRST CONCRETE PLACEMENT, AFTER REINFORCING IS
INSTALLED AND TIED.
PRIOR TO FIRST CONCRETE WALL PLACEMENT. AFTER REINFORCING
IS INSTALLED AND TIED.
AFTER EACH LEVEL OF STEEL IS ERECTED, PRIOR TO
APPLICATION OF FIRE PROOFING.
AFTER STTL DECK IS INSTALLED AND ATTACHED TO STRUCTURE.
PRIOR TO ROOFING ISTALLATION.
AFTER EACH LEVEL OF STEEL IS ERECTED PRIOR TO APPLICATION OF
FIRE PROOFING.
412 E. Park Center Blvd, Suite 200
Boise, ID 83706
O: 208.336.6985 www.kpff.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
BOISE VA MEDICAL CENTER - BOISE, ID
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(360) 223 - 8994
RAY SPEES, PRESIDENT
07/23/2021
MEDICAL CENTER DIRECTOR
Approved: CHIEF, FACILITY MANAGEMENT SERVICE S-002
SPECIAL INSPECTIONS 1 OF 2
CH/JW SG
STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING
VERIFYING WELDER QUALIFICATIONS - X COPY OF QUALIFICATION CARDS
VERIFYING USE OF PROPER WELDING
PROCEDURE SPECIFICATIONS
- X
COPY OF WELDING PROCEDURE
SPECIFICATIONS
MATERIAL VERIFICATION OF WELD FILLER
METALS
1705.3.1
- X MANUFACTURER'S CERTIFIED TEST REPORTS
INSPECTION OF REINFORCING STEEL WELDING
TB 1705.3(2)
1705.3.1
ACI 318: 26.6.4
AWS D1.4: 7
- - EXCEPT AS NOTED OTHERWISE
INSPECT REINFORCEMENT, INCLUDING
EMBEDMENTS AND PRESTRESSING TENDONS,
AND VERIFY PLACEMENT.
TB 1705.3(1)
1705.3 1908.4
ACI 318: 20, 25.2-25.3,
26.6.1-26.6.3, 26.8, 26.13.3
- X
TOLERANCE AND REINFORCING PLACEMENT
PER ACI 318: 26.6
CONCRETE
INSPECTION IN FABRICATION SHOP 1704.2.5 - - -
WHERE FABRICATION OF STRUCTURAL,
LOAD-BEARING OR LATERAL LOAD-RESISTING
MEMBERS OR ASSEMBLIES IS BEING
PERFORMED ON THE PREMISES OF A
FABRICATOR'S SHOP, SPECIAL INSPECTION OF
THE FABRICATED ITEMS SHALL BE AS
REQUIRED BY TABLE 2 AND AS REQUIRED
ELSEWHERE IN THE STATEMENT OF SPECIAL
INSPECTIONS. REFERENCE SECTION 1704.2.5.1
FOR APPROVED FABRICATOR EXCEPTION.
FABRICATION
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY (NOTE 6)SYSTEM OR MATERIAL
INSPECTION
REMARKS
TABLE 2 - REQUIRED STRUCTURAL SPECIAL INSPECTIONS
VERIFY USE OF PROPER MATERIALS, DENSITIES
AND LIFT THICKNESSES DURING PLACEMENT
AND COMPACTION OF COMPACTED FILL.
X -
PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS.
- X
VERIFY EXCAVATIONS ARE EXTENDED TO
PROPER DEPTH AND HAVE REACHED PROPER
MATERIAL.
- X
VERIFY MATERIALS BELOW SHALLOW
FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
TB 1705.6
1705.6
GEOTECHNICAL
REPORT
- X
BY THE CONTRACTOR
SOILS
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY (NOTE 6)SYSTEM OR MATERIAL
INSPECTION
REMARKS
TABLE 1 - REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS
INSPECT REINFORCING STEEL MECHANICAL
COUPLERS, TERMINATORS AND FORM SAVERS
ICC/IAPMO
EVALUATION
REPORTS
- X
VISUALLY INSPECT FOR CORRECT ASSEMBLY
AND LOCATION
INSPECT FORMWORK FOR SHAPE, LOCATION
AND DIMENSIONS OF THE CONCRETE MEMBER
BEING FORMED.
TB 1705.3(12)
1705.3
ACI 318: 26.11.1.2(b) - X -
VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES.
TB 1705.3(8)
1705.3 1908.9
ACI 318: 26.5.3-26.5.5,
26.13.3
- X -
VERIFY CURING METHOD AND DURATION OF
CURING FOR EACH MEMBER.
- ACI 318: 26.13.3.3(b) - X -
PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE
CONCRETE.
TB 1705.3(6)
1908.10
ASTM C 172
ASTM C 31
ACI 318: 26.4, 26.12
X - -
VERIFY USE OF REQUIRED DESIGN MIX.
TB 1705.3(5)
1705.3 1908.2 1908.3
ACI 318: 19,
26.4.3-26.4.4, 26.13.3
- X -
MECHANICAL ANCHORS, ADHESIVE
ANCHORS, AND ADHESIVE REINFORCING
DOWELS NOT DEFINED ABOVE.
TB 1705.3 (4.b)
ACI 355.4
ICC/IAPMO
EVALUATION REPORT
ACI 318: 17.8.2, 26.13.3
X
(NOTE 7)
ALL ANCHORS SHALL BE VISUALLY INSPECTED
ADHESIVE ANCHORS AND ADHESIVE
REINFORCING DOWELS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
TB 1705.3 (4.a)
ACI 355.4
ICC/IAPMO
EVALUATION REPORT
ACI 318: 17.8.2.4,
26.13.3
X -
REFER TO ANCHOR CALLOUTS FOR
SUSTAINED TENSION (ST) DESIGNATION
INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS:
INSPECT ANCHORS CAST IN CONCRETE WAC 51-50-1705 ACI 318 17.8.2 - X ALL ANCHORS SHALL BE VISUALLY INSPECTED
INSPECT ALL OTHER WELDS
TB 1705.3
(2.c)
X -
ALL WELDS VISUALLY INSPECTED PER AWS
D1.4: 7.5
INSPECT SINGLE PASS FILLET WELDS,
MAXIMUM 5/16"
TB 1705.3
(2.b)
- X -
VERIFY WELDABILITY OF REINFORCING
STEEL OTHER THAN ASTM A 706.
TB 1705.3
(2.a)
AWS D1.4
ACI 318: 26.6.4
- X CERTIFIED MILL TEST REPORTS
FASTENERS ARE PRETENSIONED IN
ACCORDANCE WITH THE RCSC
SPECIFICATION, PROGRESSING
SYSTEMATICALLY FROM THE MOST RIGID
POINT TOWARD THE FREE EDGES
X - -
FASTENER COMPONENT NOT TURNED BY
THE WRENCH PREVENTED FROM
ROTATING
X - -
JOINT BROUGHT TO SNUG-TIGHT
CONDITION PRIOR TO THE
PRETENSIONING OPERATION
X - -
FASTENER ASSEMBLIES, OF SUITABLE
CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED
AS REQUIRED
1705.2
AISC 360: TB N5.6-2
AISC 360: N5.6
X - -
INSPECTION TASKS DURING BOLTING:
PROPER STORAGE PROVIDED FOR BOLTS,
NUTS, WASHERS AND OTHER FASTENER
COMPONENTS
X - -
PRE-INSTALLATION VERIFICATION TESTING
BY INSTALLATION PERSONNEL OBSERVED
AND DOCUMENTED FOR FASTENER
ASSEMBLIES AND METHODS USED
X - -
CONNECTING ELEMENTS, INCLUDING THE
APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF
SPECIFIED, MEET APPLICABLE
REQUIREMENTS
X - -
PROPER BOLTING PROCEDURE FOR JOINT
DETAIL
X - -
PROPER FASTENERS SELECTED FOR THE
JOINT DETAIL (GRADE, TYPE, BOLT LENGTH
IF THREADS ARE TO BE EXCLUDED FROM
SHEAR PLANE)
X - -
FASTENERS MARKED IN ACCORDANCE
WITH ASTM REQUIREMENTS
X - -
MANUFACTURER'S CERTIFICATIONS
AVAILABLE FOR FASTENER MATERIALS
1705.2
AISC 360: TB N5.6-1
AISC 360: N5.6
- X -
INSPECTION TASKS PRIOR TO BOLTING:
DOCUMENT ACCEPTANCE OR REJECTION
OF WELDED JOINT OR MEMBER
- X -
REPAIR ACTIVITIES - X -
BACKING REMOVED AND WELD TABS
REMOVED (IF REQUIRED)
- X -
K-AREA - X -
ARC STRIKES - X -
WELDS MEET VISUAL ACCEPTANCE
CRITERIA: CRACK PROHIBITION,
WELD/BASE-METAL FUSION, CRATER
CROSS SECTION, WELD PROFILES, WELD
SIZE, UNDERCUT, POROSITY
- X -
SIZE, LENGTH AND LOCATION OF WELDS - X -
WELDS CLEANED
1705.2
AISC 360: TB N5.4-3
AISC 360: N5.4
X - -
INSPECTION TASKS AFTER WELDING:
WELDING TECHNIQUES: INTERPASS AND
FINAL CLEANING, EACH PASS WITHIN
PROFILE LIMITATIONS, EACH PASS MEETS
QUALITY REQUIREMENTS
X - -
WPS FOLLOWED: SETTINGS ON WELDING
EQUIPMENT, TRAVEL SPEED, SELECTED
WELDING MATERIALS, SHIELDING GAS
TYPE/FLOW RATE, PREHEAT APPLIED,
INTERPASS TEMPERATURE MAINTAINED
(MIN./MAX.), PROPER POSITION (F, V, H, OH)
X - -
ENVIRONMENTAL CONDITIONS: WIND
SPEED WITHIN LIMITS, PRECIPITATION AND
TEMPERATURE
X - -
NO WELDING OVER CRACKED TACK WELDS X - -
CONTROL AND HANDLING OF WELDING
CONSUMABLES: PACKAGING, EXPOSURE
CONTROL
X - -
USE OF QUALIFIED WELDERS
1705.2
AISC 360: TB N5.4-2
AISC 360: N5.4
X - -
INSPECTION TASKS DURING WELDING:
CHECK WELDING EQUIPMENT - - FABRICATOR OR ERECTOR SHALL OBSERVE
FIT-UP OF FILLET WELDS: DIMENSIONS
(ALIGNMENT, GAPS AT ROOT),
CLEANLINESS (CONDITION OF STEEL
SURFACES), TACKING (TACK WELD
QUALITY AND LOCATION), BACKING TYPE
AND FIT (IF APPLICABLE)
X - -
CONFIGURATION AND FINISH OF ACCESS
HOLES
X - -
FIT-UP OF GROOVE WELDS (INCLUDING
JOINT GEOMETRY): JOINT PREPARATION,
DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL), CLEANLINESS
(CONDITION OF STEEL SURFACES),
TACKING (TACK WELD QUALITY AND
LOCATION), BACKING TYPE AND FIT (IF
APPLICABLE)
X - -
WELDER IDENTIFICATION SYSTEM X - -
MATERIAL IDENTIFICATION (TYPE/GRADE) X - -
MANUFACTURER CERTIFICATIONS FOR
WELDING CONSUMABLES AVAILABLE
- X -
WELDING PROCEDURE SPECIFICATIONS
(WPS) AVAILABLE
1705.2
AISC 360: TB N5.4-1
AISC 360: N5.4
- X -
INSPECTION TASKS PRIOR TO WELDING:
STEEL
OBSERVE PERFORM
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY (NOTE 8)SYSTEM OR MATERIAL
INSPECTION
REMARKS
4. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S) EXERCISING SUCH CONTROL AND THEIR POSITION(S) IN THE ORGANIZATION.
3. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S ORGANIZATION, THE METHOD AND FREQUENCY OF REPORTING AND DISTRIBUTION
OF THE REPORTS.
2. ACKNOWLEDGEMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS APPROVED BY THE
BUILDING OFFICIAL.
1. ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS.
FOR SEISMIC DESIGN CATEGORY C, D, E AND F STRUCTURES, THE CONTRACTOR IS RESPONSIBLE FOR THE CONSTRUCTION OF THE MAIN WIND OR SEISMIC FORCE-RESISTING SYSTEM, OR A WIND OR SEISMIC FORCE-RESISTING COMPONENT LISTED IN TABLES 2C, 3 AND 4. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE
CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN THE FOLLOWING:
CONTRACTOR RESPONSIBILITY:
10. THE SPECIAL INSPECTION SCHEDULE AND PROCUREMENT IS THE RESPONSIBILITY OF THE CONTRACTOR AND NOT THE VA.
9. INDICATED CONCRETE TESTING MEETS MINIMUM REQUIREMENTS FOR STRUCTURAL TESTING TO BE PROVIDED BY THE APPROVED QUALIFIED TESTING AND INSPECTING AGENCY. ADDITIONAL TESTING FOR CONSTRUCTION CONSIDERATIONS ARE NOT INDICATED AND SHALL BE DETERMINED BY THE
CONTRACTOR AND PROVIDED AT CONTRACTOR'S EXPENSE.
8. OBSERVE: OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
PERFORM: PERFORM THESE TASKS FOR EACH ELEMENT.
- SPECIAL INSPECTOR SHALL PROVIDE DOCUMENTATION AT THE END OF ANCHOR INSTALLATIONS STATING THAT THE MINIMUM NUMBER OF ANCHORS
WERE INSPECTED.
- INSPECTION REPORTS SHALL IDENTIFY NAMES OF INSTALLERS.
- FOR EACH ANCHOR TYPE AND SIZE, INSPECTOR SHALL BE ONSITE TO CONTINUOUSLY INSPECT A MINIMUM OF THE FIRST 10 ANCHORS INSTALLED BY EACH INSTALLER FOR CONFORMANCE WITH ICC/IAPMO EVALUATION REPORT. PROVIDED ALL ANCHORS ARE INSTALLED CORRECTLY PER MANUFACTURER'S INSTRUCTIONS, PROVIDE PERIODIC INSPECTION ON A MINIMUM OF 10% OF THE NEXT 1000 ANCHORS BY EACH INSTALLER AND A MINIMUM OF 5% OF THE REMAINING ANCHORS BY EACH INSTALLER. INSPECTIONS SHALL OCCUR A MINIMUM OF ONCE PER WEEK AT A RANDOM TIME WHILE ANCHOR INSTALLATION IS ONGOING. ANY NON-COMPLIANCE ISSUES SHALL RESET THE INSPECTION REQUIREMENTS TO TEN (10) CONTINUOUS INSPECTIONS. NON-COMPLIANT ANCHORS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD FOR REVIEW AND
SHALL BE BROUGHT INTO COMPLIANCE BY EITHER TESTING OR RE-INSTALLATION.
- FOR ALL ANCHORS, PRIOR TO CONCEALMENT, VERIFY: ANCHOR TYPE, ANCHOR DIMENSIONS, ANCHOR SPACING AND EDGE DISTANCE.
7. WHERE PERIODIC INSPECTION IS ALLOWED IN ACCORDANCE WITH THE ANCHOR ICC/IAPMO EVALUATION REPORT, INSPECTIONS SHALL BE AS FOLLOWS:
6. CONTINUOUS SPECIAL INSPECTION: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED. PERIODIC SPECIAL INSPECTION: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE
WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED.
5. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS FOR EACH INSPECTION TO THE BUILDING OFFICIAL, STRUCTURAL ENGINEER, ARCHITECT, CONTRACTOR, AND OWNER. THE TESTING AND INSPECTING AGENCY SHALL SUBMIT A FINAL REPORT STATING THAT THE WORK REQUIRING SPECIAL INSPECTION WAS INSPECTED AND IS IN CONFORMANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS AND THAT ALL DISCREPANCIES NOTED IN THE
INSPECTION REPORTS HAVE BEEN CORRECTED.
4. THE SPECIAL INSPECTOR SHALL OBSERVE THE INDICATED WORK FOR COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION AND NOTED IN THE INSPECTION REPORTS. ISSUES REQUIRING IMMEDIATE CORRECTIVE ACTIONS OR ENGINEERING INPUT ARE TO BE BROUGHT TO THE ENGINEER'S ATTENTION IMMEDIATELY UPON
DISCOVERY.
3. SPECIAL INSPECTIONS AND ASSOCIATED TESTING SHALL BE PERFORMED BY A QUALIFIED TESTING AND INSPECTING AGENCY MEETING THE REQUIREMENTS OF ASTM E 329 (MATERIALS), ASTM D 3740 (SOILS), ASTM C 1077 (CONCRETE), AND ASTM E 543 (NON-DESTRUCTIVE). THE TESTING AND INSPECTING AGENCY SHALL FURNISH TO THE COR A COPY OF THEIR SCOPE OF ACCREDITATION. SPECIAL INSPECTORS SHALL BE CERTIFIED BY THE BUILDING OFFICIAL. WELDING INSPECTORS SHALL BE QUALIFIED PER SECTION 6.1.4.1.1 OF AWS D1.1.
SDI QA/QC-2011
TMS 402-13, 602-13
RCSC 2009
341-10
AISC 360-10
ASTM CURRENT EDITION
AWS CURRENT EDITION
AWC SDPWS 2015
ACI 318-14
IBC 2018
2. REFERENCE CODES AND STANDARDS ARE AS FOLLOWS:
1. SPECIAL INSPECTIONS SHALL CONFORM TO CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE (IBC) AND THE REFERENCE CODES AND STANDARDS LISTED IN NOTE 2. REFER TO TABLES 1 AND 2 FOR SPECIAL INSPECTION AND TABLES 3 AND 4 FOR TESTING REQUIREMENTS.
STATEMENT OF SPECIAL INSPECTION AND TESTING NOTES:
CONTINUE ON SHEET S-003
R
O
FESS I O NA L ENG I NEER
J UDS E N M . W I L L I A MS
1 2 0 3 3
R
412 E. Park Center Blvd, Suite 200
Boise, ID 83706
O: 208.336.6985 www.kpff.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
BOISE VA MEDICAL CENTER - BOISE, ID
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(360) 223 - 8994
RAY SPEES, PRESIDENT
07/23/2021
MEDICAL CENTER DIRECTOR
Approved: CHIEF, FACILITY MANAGEMENT SERVICE S-003
SPECIAL INSPECTIONS 2 OF 2
CH/JW SG
STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING - CONTINUED
INSTALLATION OF VIBRATION ISOLATION
SYSTEMS IN STRUCTURES ASSIGNED TO SEISMIC
DESIGN CATEGORY C, D, E OR F WHERE THE
CONSTRUCTION DOCUMENTS REQUIRE A
NOMINAL CLEARANCE OF 0.25 INCHES OR LESS
BETWEEN THE EQUIPMENT SUPPORT FRAME
AND RESTRAINT
1705.12.6 - - X
INSTALLATION OF OTHER SEISMIC SUPPORTS
FOR DESIGNATED MECHANICAL SYSTEMS AND
THEIR COMPONENTS
- - X
INSTALLATION OF EQUIPMENT USING
COMBUSTIBLE ENERGY SOURCES
1705.12.4
- - X
INSTALLATION OF FIRE PROTECTION SPRINKLER
SYSTEM
1705.12 - - X
INSTALLATION AND ANCHORAGE OF HVAC
DUCTWORK DESIGNED TO CARRY HAZARDOUS
MATERIALS
1704.3.2 1705.12.6
- - X
SEISMIC RESTRAINT OF BUILDING
MECHANICAL COMPONENTS IS A CONTRACTOR
RESPONSIBILITY AND IS LISTED HERE FOR
INFORMATION ONLY. REFERENCE
MECHANICAL FOR FURTHER INFORMATION.
BUILDING MECHANICAL AND PLUMBING
INSTALLATION OF OTHER SEISMIC SUPPORTS
FOR DESIGNATED MECHANICAL SYSTEMS AND
THEIR COMPONENTS
- - X
INSTALLATION OF EQUIPMENT USING
COMBUSTIBLE ENERGY SOURCES
1705.12.4
- - X
INSTALLATION AND ANCHORAGE OF PIPING
SYSTEMS DESIGNED TO CARRY HAZARDOUS
MATERIALS AND ASSOCIATED MECHANICAL
UNITS
1704.3.2 1705.12.6
- - X
SEISMIC RESTRAINT OF PROCESS
MECHANICAL COMPONENTS IS A CONTRACTOR
RESPONSIBILITY AND IS LISTED HERE FOR
INFORMATION ONLY. REFERENCE
MECHANICAL FOR FURTHER INFORMATION.
PROCESS MECHANICAL AND PLUMBING
INSTALLATION OF OTHER SEISMIC SUPPORTS
FOR DESIGNATED ELECTRICAL SYSTEMS AND
THEIR COMPONENTS
1705.12.6 - - X
INSTALLATION OF VIBRATION ISOLATION
SYSTEMS IN STRUCTURES ASSIGNED TO SEISMIC
DESIGN CATEGORY C, D, E OR F WHERE THE
CONSTRUCTION DOCUMENTS REQUIRE A
NOMINAL CLEARANCE OF 0.25 INCHES OR LESS
BETWEEN THE EQUIPMENT SUPPORT FRAME
AND RESTRAINT
1705.12.6 1705.12.8
- - X
ANCHORAGE OF ALL ELECTRICAL EQUIPMENT IN
SEISMIC DESIGN CATEGORY E OR F ONLY
- - X
ANCHORAGE OF ELECTRICAL EQUIPMENT FOR
EMERGENCY OR STANDBY POWER SYSTEMS 1704.3.2
1705.12.6
- - X
SEISMIC RESTRAINT OF ELECTRICAL
COMPONENTS IS A CONTRACTOR
RESPONSIBILITY AND IS LISTED HERE FOR
INFORMATION ONLY. REFERENCE ELECTRICAL
FOR FURTHER INFORMATION.
ELECTRICAL
INSTALLATION OF OTHER SEISMIC SUPPORTS
FOR DESIGNATED ARCHITECTURAL SYSTEMS
AND THEIR COMPONENTS
1704.3.2 1705.12.5
- - X
REFERENCE ARCHITECTURAL FOR
INFORMATION
INSTALLATION AND ANCHORAGE OF STORAGE
RACKS
1704.3.2 1705.12.7
ASCE 7: 15.5.3 - X FOR RACKS OVER 8 FEET IN HEIGHT
ERECTION AND FASTENING OF EXTERIOR
NONBEARING WALLS IN BUILDINGS MORE THAN
30 FEET IN HEIGHT
- - X
ERECTION AND FASTENING OF INTERIOR
NONBEARING WALLS WEIGHING MORE THAN 15
PSF IN BUILDINGS MORE THAN 30 FEET IN
HEIGHT
- - X
INSTALLATION AND ANCHORAGE OF CLADDING
AND INTERIOR/EXTERIOR VENEER WEIGHING
MORE THAN 5 PSF IN BUILDINGS MORE THAN 30
FEET IN HEIGHT
1704.3.2 1705.12.5
- - X
INSTALLATION AND ANCHORAGE OF ACCESS
FLOORS
1704.3.2 1705.12.5.1
- - X
REFERENCE ARCHITECTURAL FOR
INFORMATION
ARCHITECTURAL
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCYSYSTEM OR MATERIAL
TESTING
REMARKS
* TABLE N2 - REQUIRED NONSTRUCTURAL SPECIAL INSPECTIONS
FOR SEISMIC RESISTANCE
INSTALLATION 1705.18 - - X RECORD DEVICE LOCATION(S)
SMOKE CONTROL SYSTEMS
INSTALLATION 1705.17 - - X -
FIRE-RESISTANT PENETRATIONS AND JOINTS
INSTALLATION 1705.16 - X - -
EXTERIOR INSULATION AND FINISH SYSTEMS
APPLICATION - X
SURFACE CONDITIONS
1705.14 1705.15
ICC/IAPMO
EVALUATION
REPORT
- X
SPECIAL INSPECTIONS APPLY TO
CLEANLINESS OF STEEL, PRODUCT NAME AND
TYPE, MATERIAL EXPIRATION DATE, AMBIENT
CONDITIONS, APPLICATION PROCEDURES, AND
MATERIAL THICKNESS, DENSITY AND BOND
STRENGTH
SPRAYED FIRE-RESISTANT MATERIALS AND INTUMESCENT FIRE-RESISTANT COATINGS
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCYSYSTEM OR MATERIAL
TESTING
REMARKS
TABLE N1 - REQUIRED ARCHITECTURAL SPECIAL INSPECTIONS
MT OF THE ENDS OF FLANGE WELDS FROM
WHICH WELD TABS HAVE BEEN REMOVED
AISC 341: J6.2f
AWS D1.1: 6.14.4
EACH LOCATION -
MT OF THE WELD AND ADJACENT AREA IN A
REDUCED BEAM SECTION (RBS) PLASTIC HINGE
REGION REPAIRED BY WELDING
AISC 341: J6.2e
AWS D1.1: 6.14.4
EACH LOCATION -
MT OF THERMALLY CUT SURFACES OF BEAM
COPES AND ACCESS HOLES AT WELDED SPLICES
AND CONNECTIONS WHEN THE FLANGE
THICKNESS EXCEEDS 1-1/2" FOR ROLLED
SHAPES OR THE WEB THICKNESS EXCEEDS 1-1/2"
FOR BUILT-UP SHAPES
AISC 341: J6.2d
AWS D1.1: 6.14.4
EACH LOCATION -
UT OF BASE METAL THICKER THAN 1-1/2"
SUBJECT TO THROUGH-THICKNESS WELD
SHRINKAGE STRAINS
AISC 341: J6.2c
AWS D1.1: 6.13 &
6.14.3
BEHIND AND ADJACENT
TO EACH WELD
MAGNETIC PARTICLE (MT) AND ULTRASONIC (UT)
TESTING OF COMPLETE JOINT PENETRATION
GROOVE (CJP) WELDS IN MATERIALS 5/16" THICK
AND GREATER
AISC 341: J6.2b
MT - AWS D1.1: 6.14.4
UT - AWS D1.1: 6.13 &
6.14.3
UT 100% OF WELDS
MT 25% OF WELDS
REFER TO DRAWINGS FOR LOCATIONS
MT OF K-AREA OF ROLLED WIDE FLANGE
COLUMN WEBS ADJACENT TO
DOUBLER/CONTINUITY PLATE WELDS
1705.13.1
AISC 341: J6.2a
AWS D1.1: 6.14.4
EACH PLATE LOCATION -
STEEL
COMPONENT TESTING INCLUDING MOUNTING
SYSTEMS OR ANCHORAGE IF CERTIFICATES OF
COMPLIANCE ARE NOT AVAILABLE
1705.13 1705.13.2 1705.13.3
ASCE 7: 13.2 - X
SEISMIC RESTRAINT OF MECHANICAL AND
ELECTRICAL COMPONENTS IS A CONTRACTOR
RESPONSIBILITY AND IS LISTED HERE FOR
INFORMATION ONLY. REFERENCE
MECHANICAL AND ELECTRICAL FOR FURTHER
INFORMATION.
MECHANICAL AND ELECTRICAL
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY
SYSTEM OR MATERIAL
TESTING
REMARKS
TABLE N4 - REQUIRED NONSTRUCTURAL TESTING FOR SEISMIC
RESISTANCE
LEAKAGE, PRESSURE DIFFERENTIAL, FLOW
MEASUREMENT AND DETECTION AND CONTROL
VERIFICATION
1705.18 -
DETERMINED BY
JURISDICTION
SMOKE CONTROL SYSTEMS
THICKNESS 1705.15
AWCI TECHNICAL
MANUAL 12-B
ASTM D1182
REFERENCE ARCHITECTURAL FOR ADDITIONAL
INFORMATION
INTUMESCENT FIRE-RESISTANT COATINGS
BOND STRENGTH AT STRUCTURAL FRAMING
MEMBERS
1705.14.6.2
EACH TYPE OF
STRUCTURAL MEMBER
FOR EACH 2500 SQ FT OF
FLOOR AREA EACH FLOOR
LEVEL
BOND STRENGTH AT FLOOR, ROOF, AND WALL
ASSEMBLIES
1705.14.6.1
ASTM E 736
EACH 2500 SQ FT OF
SPRAYED AREA EACH
FLOOR LEVEL
REFERENCE ARCHITECTURAL FOR ADDITIONAL
INFORMATION
DENSITY 1705.14.5 -
THICKNESS AT STRUCTURAL FRAMING MEMBERS
TEST A MINIMUM OF 25%
OF THE STRUCTURAL
MEMBERS AT EACH LEVEL
THICKNESS AT FLOOR, ROOF, AND WALL
ASSEMBLIES
1705.14.4
ASTM E 605
NOT LESS THAN (4)
MEASUREMENTS FOR
EACH 1000 SQ FT OF
SPRAYED AREA EACH
FLOOR LEVEL
REFERENCE ARCHITECTURAL FOR ADDITIONAL
INFORMATION
SPRAYED FIRE-RESISTANT MATERIALS
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY
SYSTEM OR MATERIAL
TESTING
REMARKS
TABLE N3 - NONSTRUCTURAL TESTING
R
O
FESS I O NA L ENG I NEER
J UDS E N M . W I L L I A MS
1 2 0 3 3
R
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
T.O. SOG
EL XXX'-XX"
T.O.F.
EL XXX'-XX"
S S
A
B
C
D
E
F
G
H
I
J
K
L
2 3 4 6" 44'-3"
9" 15'-7 1/2" 15'-7 1/2"
9"
44'-3" 6"
SS311
M
SE303
H SS6x6x1/4
H SS6x6x1/4
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 5/
H SS6x
6x 5/
H SS6x
6x 5/
H SS6x
6x 5/
H SS6x
6x 1/
H SS6x
6x 5/
H SS6x
6x 5/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x6x1/2
H SS6x6x1/2
4" SOG W/ #4 @ 1'-6" OC
EA WAY PER .
PROVIDE CONTROL
JOINTS PER .
SS311
SS312
CONC STEM
WALL, TYP
SE303
SE303
SE304
SE304
SE304
SE304
SE301
F6.0
(97'-0")
F6.0
(97'-0")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(98'-6")
F6.0
(95'-6")
F9.0
(99'-0")
F10.5
(99'-0")
F10.5
(99'-0")
F9.0
(99'-0")
F10.5
(98'-6")
F10.5
(98'-6")
F10.5
(99'-0")
F10.5
(99'-0")
F9.0
(99'-0")
F9.0
(99'-0")
BLAST HARDENED
METAL STUD PARTITION
WALL PER
CONC STEM
WALL, TYP
CONC STEM
WALL, TYP
2'-9" 2'-9"
#7 @ 12" OC
TOP & BOT
#7 @ 12" OC
TOP & BOT
2'-9" 2'-9"
2'-0" THICK
CONC FTG
2'-0" THICK
CONC FTG
(6) #7 TOP &
BOT
(6) #7 TOP
& BOT
4'-0" 4'-0"
#8 @ 12" OC TOP
& BOT
2'-8" THICK
CONC FTG
(8) #8 BOT & (8) #8 TOP
BARS
SD402
TYP BTWN
COL FTGS
CONT FTG BTWN PAD FTGS
PER . TOP OF FTG
ELEV = 98'-6", TYP UNO
5/SD402
CONT FTG BTWN PAD FTGS
PER . TOP OF FTG
ELEV = 98'-6", TYP UNO
5/SD402
CONT FTG BTWN PAD FTGS
PER . TOP OF FTG
ELEV = 98'-6", TYP UNO
5/SD402
CONT FTG BTWN PAD FTGS
PER . TOP OF FTG
ELEV = 98'-6", TYP UNO
5/SD402
SD402
TYP UNO
T.O. SOG
EL = 100'-0"
(7) #7 TOP & BOT
#7 @ 12" OC
TOP & BOT
2'-0" THICK
CONC FTG
SD402
TYP BTWN
COL FTGS
(7) #7 TOP & BOT
#7 @ 12" OC
TOP & BOT
2'-0" THICK
CONC FTG
4'-0" 4'-0"
(7) #7 TOP & BOT
#7 @ 12" OC
TOP & BOT
2'-0" THICK
CONC FTG
(7) #7 TOP & BOT
#7 @ 12" OC
TOP & BOT
2'-0" THICK
CONC FTG
4'-0" 4'-0"
(98'-6")
(98'-6")
(98'-6")
(98'-6")
(98'-6")
(99'-0") (99'-0")
(98'-6")
(98'-6")
5'-0"
5'-6" 5'-6"
2'-8" THICK
CONC FTG
(10) #8 BOT
& (12) #6
TOP BARS
#8 @ 12" OC TOP
& BOT
#8 @ 12" OC TOP &
BOT(10) #8 BOT & (10) #7
TOP BARS
4'-0"4'-0"
(6) #8 BOT &
(6) #5 TOP
BARS
2'-0" THICK
CONC FTG
#8 @ 12" OC
TOP & BOT
SD401
L.2
2.1 2.92.51.1 3.9
TYP
B.8
/2 SB201
MATCH LINE
SS312
A.1
4'-0" 4'-0"
4'-0" 4'-0"
14'-0"
T.O.F.
EL = 95'-6"
T.O.F.
EL = 95'-6"2
T.O.F.
EL = 97'-0"
3'-0"
T.O.F.
EL = 97'-0"
COORDINATE
LOCATION OF UTILITY
WITH PLUMBING
T.O.F.
EL = 97'-0"
T.O.F.
EL = 95'-6"
T.O.F.
EL = 97'-0"
COORDINATE LOCATION OF
UTILITY WITH PLUMBING
CSW-12
CSW-12
CSW-12
CSW-12
C S
W -1
C S
W -1
C
S W
-1
CSW-12CSW-16CSW-12
C S
W -1
C
S W
-1
SE302
10'-0"
H SS6x6x1/4
F4.0
(99'-0")
UTILITY TO GO UNDER FTG PER
DETAIL AT THIS LOCATION.
COORDINATE LOCATION OF UTILITY
WITH PLUMBING.
/3 SD401
SD402
SD402
TYP
UNO
SD402
TYP
UNOSD401
TYP
SD402
SE302
HSS JAMB PER
ELEVATION
HSS JAMB PER
ELEVATION
/1 SD402
/4 SD402
SD402
TYP
SD402
TYP
UNO
SD401
SD401
TYP
HSS JAMB PER
ELEVATION
HSS JAMB PER
ELEVATION
HSS JAMB PER
ELEVATION
HSS JAMB PER
ELEVATION
HSS JAMB PER
ELEVATION
SS313
SD402
COORDINATE WITH
ELECTRICAL DRAWINGS
LOCATION AND ELEVATIONS
OF ELECTRICAL CONDUIT
/1 SD601
B -S
T U
D -6
B -S
T U
D -6
B -S
T U
D -6
B -S
T U
D -6
B -S
T U
D -8
B -S
T U
D -8
B -S
T U
D -6
B-STUD-6
B-STUD-6
B-STUD-6
B-STUD-8
B-STUD-6
B-STUD-6
B-STUD-6
B-STUD-6
T.O.F.
EL = 97'-0"
16'-6"
T.O.F.
EL = 97'-0"
SS313
PROJECT
NORTH
TYP @
ENTRY/DOOR
T.O.F.
EL = 98'-6"
SD401
8 TYP @ COL IN
STEM WALL
SD401
8 TYP @ COL IN
STEM WALL
TYP @
ENTRY/DOOR
T.O.F.
EL = 98'-6"
T.O.F.
EL = 98'-6"
SD602
3 SD602
3"
3"
3"
3"
3"
3"
3"
3"
3"
2"
3"
3"
19'-6 3/4" 8'-6" 8'-6"
" 2
1'-2 1/2" 8'-5" 8'-6" 4'-5"
" 2
" 2
3"
3"
3"
3"
3"
3"
3"
3"
3"
2"
3"
3"
13'-6" 13'-9 1/2"
13'-9 1/2" 13'-6"
4"
4"
4"
4"
2'-8"
3"3
6'-9 1/2"
3"
6'-9 1/2" 3'-0"
3" 3"
3"3"
3" 3"
3"
3"
3" 3"3
"3
2"
HSS JAMB PER ELEVATION
FOUNDATION PLAN NOTES
1. FOR TYPICAL CONCRETE DETAILS SEE SHEET &
2. FOR OPENINGS IN SLAB ON GRADE SEE
3. WHERE BELOW GRADE UTILITIES RUN ABOVE OR BELOW FOOTING SEE .
UTILITIES MUST GO ABOVE OR BELOW FOOTINGS AND NOT THROUGH THE
FOOTINGS.
4. INDICATES FOOTING TYPE PER FOOTING SCHEDULE AND PER
5. (XXX'-XX") INDICATES TOP OF FOOTING ELEVATION
OR
6. INDICATES TOP OF SLAB ON GRADE ELEVATION
100'-0" = 2,725.85 FT MSL ELEVATION PER CIVIL
7. INDICATES HSS COLUMN
8. INDICATES FRAME BRACE.
INDICATES FRAME BRACE BELOW.
9. INDICATES STEP IN FOOTING PER DETAIL
10. FOR TYPICAL EXTERIOR WALL FRAMING SEE
11. CSW-X INDICATES CONCRETE STEM WALL SIZE AND REINFORCEMENT PER SCHEDULE
IN DETAIL . SEE ARCHITECTURAL DRAWINGS FOR EXTENTS OF STEM
WALL TYPES.
12. B-STUD-X INIDICATES INTERIOR BLAST METAL STUD WALL TYPE PER SCHDULE IN DETAIL
13. SEE LANDSCAPE DRAWINGS FOR LIGHT POLE LOCATIONS. FOR LIGHT POLE
FOUNDATION REQUIREMENTS SEE DETAIL
F#
FOOTING SCHEDULE
DIMENSIONS
TYPE MARK REINFORCING
WIDTHLENGTH DEPTH
F6.0
F9.0
6'-0"
9'-0"
6'-0"
9'-0"
1'-0"
1'-2"
(6) - #5 EW
(8) - #6 EW
3/SD402
3/SD401
9/SD401
1/SD601
SD401 SD402
/5 SD402
F4.0 4'-0" 4'-0" 1'-0" (4) - #5 EW
F10.5 10'-6" 1'-4" (8) - #7 EW10'-6"
4/SD401
1/SD601
8/SD402
L
2 3
M
N
L.2
2.1 2.92.5
H SS6x
6x 1/
H SS6x
6x 1/
H SS6x6x1/2
H SS6x6x1/2
4" SOG W/ #4 @ 1'-6" OC
EA WAY
(98'-6")
(98'-6")
(98'-6")
F6.0 (98'-6")
F6.0
MATCH LINE
/1 SB201
CSW-8
C S
W -8
C S
W -8
SD402
SD402
SD402
SD402
3"
3"
412 E. Park Center Blvd, Suite 200
Boise, ID 83706
O: 208.336.6985 www.kpff.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
BOISE VA MEDICAL CENTER - BOISE, ID
531-325
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(360) 223 - 8994
RAY SPEES, PRESIDENT
07/23/2021
MEDICAL CENTER DIRECTOR
Approved: CHIEF, FACILITY MANAGEMENT SERVICE SB201
FOUNDATION PLAN
CH/JW SG
1/8" = 1'-0"1
FOUNDATION PLAN
1/8" = 1'-0"2
VESTIBULE PARTIAL FOUNDATION PLAN
R
O
FESS I O NA L ENG I NEER
J UDS E N M . W I L L I A MS
1 2 0 3 3
R
B.O. DECK
EL = X'-X"
A
B
C
D
E
F
G
H
I
J
K
L
2 3 4
SS311
M
SE303
OWSJ 01 OWSJ 02 OWSJ 01
W21x93 W21x44 W21x50
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
W24x94 (LFRS)
OWSJ 01
OWSJ 02
OWSJ 02
OWSJ 02
OWSJ 02
OWSJ 02
OWSJ 02
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
OWSJ 01
W24x94 (LFRS)
OWSJ 01
W21x44 (LFRS)
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W21x44 (LFRS)
W x
L F
R S
W x
L F
R S
W x
L F
R S
W21x44 (LFRS)
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x (L
F R
S
W10x12
W x
W x
W18x35
W x
W x
L F
R S
W21x44 (LFRS)
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
W x
L F
R S
D1
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
OWSJ 03
D2
22'-0"
D1
D2
W18x35
MECH UNIT
MECHANICAL. MAX
WEIGHT = 28,000 LBS
SS311
SS312
6" 44'-3" 9" 15'-7 1/2" 15'-7 1/2" 9" 44'-3" 6"
W14x22
OWSJ 03
SE303
SE303
SE304
SE304
SE304
SE304
W21x44 (LOW) W21x44 (LOW) W16x26 (LOW)
SE301
W x
W x
BLAST HARDENED
PARTITION WALL
BELOW. FOR TOP OF
WALL CONN SEE
DETAIL
EQ EQ EQ EQ
EQ EQ EQ EQ
W x
EQ EQ EQ EQ
SD502
TYP BTWN
OWSJ CONN
SD502
TYP OWSJ
TO HSS COL
NOTE WF BEAMS ARE 5"
BELOW B.O. DECK ELEVATION,
TYP WHERE OWSJ BEARS ON
BEAM
SD502
TYP OWSJ TO WF
@ PERIMETER
NOTE WF BEAMS ARE 5" BELOW
B.O. DECK ELEVATION, TYP
WHERE OWSJ BEARS ON BEAM
B.O. DECK
EL = 113'-7 1/2"
B.O. DECK
EL = 113'-7 1/2"
B.O. DECK
EL = 113'-7 1/2"
B.O. DECK
EL = 113'-7 1/2"
B.O. DECK
EL = 116'-6"
TYP UNO
B.O. DECK
EL = 116'-6"
TYP UNO
B.O. DECK
EL = 114'-6"
B.O. DECK
EL = 114'-6"
SD502
TYP OWSJ TO
WF @ INT
SD502
TYP OWSJ TO WF
@ PERIMETER
W x
W x
OWSJ 01 OWSJ 01
W x
G A
P
S
E
IS
M
IC
W x
L F
R S
OWSJ 01
B .F
B
.F
B.F. B.F.
B .F
B .F
B.F.
B .F
B
.F
B.F. B.F.
W x
L F
R S
W x
L F
R S
L.2
2.1 2.92.51.1 3.9
B.8
OWSJ 01
SS312
MATCH LINE
/2 SF202
A.1
OWSJ 01OWSJ 01
B.O. DECK
EL = 114'-6"
B.O. DECK
EL = 114'-6"
B.O. DECK
EL = 114'-6"
EQ EQ EQ EQ EQ EQ EQ EQ
W14x22 W14x22
W16x40 (LFRS)
W x
W18x35
W18x35
W18x35 W18x35
W x
W x
W x
W x
W x
W x
SD502
SD502
W x
L F
R S
W16x40 (LFRS)
(L F
R S
(L
F R
S
W x
W x
W10x12
W10x12
W x
W x
W10x12
W x
W x
W10x12
W10x12 W x
W x
W10x12
W10x12
W x 2W x
SKYLIGHT PER ARCH
LOCATE PER ARCH
DRAWINGS, TYP
W x
W10x12
W x
W x
W10x12
W x 2 W10x12 W10x12W x
W10x12
W x
W x
W10x12W x
W10x12
W x
W x
W10x12
W10x12
SE302
SE302
SD505
W12x14 (LOW)
W21x44
SD504
OWSJ 01 OWSJ 02 OWSJ 01
OWSJ 01
OWSJ 03 OWSJ 03
OWSJ 03 OWSJ 03
SD504
SD504
WELDED DRAG
CONNECTION
PER /3 SD503
SD504
SD504
B.O. DECK
EL = 116'-6" 1
SS313
____ W12x14
W x
W x 4W12x14
OWSJ 01
SD504
TYP @
WF TO
OWSJ
W12x14
W x
W x
W12x14
B.O. DECK
EL = 116'-6"
W14x22
W14x22
W x
L F
R S
W x
L F
R S
OWSJ 01
W x
W x
W x
W x
TYP UNO
B.O. DECK
EL = 116'-6"
B.O. DECK
EL = 116'-6"
SD502
BLAST HARDENED METAL
STUD WALL BELOW
7'-9"
7'-9"
7'-9" 7'-9"
" 1
M
IN
M
IN
MIN
6'-0"
MIN
6'-0"
LINE INDICATES EDGE
OF METAL STUD TRUSS
OVERBUILD, TYP
25'-5 11/16"
Pd = 31 psf
P d p s f
P d p s f
P d…