531-325 - Drawings-15-E4.pdf
PDF 6 MB Posted
- Attached to
- Y1DZ--TIERED EVALS - Construct Primary Care/Mental Health Building Minor Construction - Boise 531-325
- Solicitation number
- 36C77624R0096
About this file
This document appears to be a set of electrical drawings for the Construct Primary Care/Mental Health Building Minor Construction project at the Boise VA Medical Center. The drawings provide detailed information on the layout and specifications for the electrical system, including conduit sizing, cable runs, transformer details, panel schedules, and one-line diagrams. Key details include:
The project involves the installation of new electrical infrastructure, including a 1200A distribution switchboard, 208/120V 3-phase 4-wire service, SPD panels, and emergency power systems. The drawings show the routing of new 12kV and 208V feeders, as well as the reuse of existing equipment like transformers and switchgear. The panel schedules and load calculations indicate the scope of the electrical work required to support the new building. There are also provisions for a future solar photovoltaic system in the one-line diagram.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
#1, 4IN B.67, RM
G02B-67
(E)
FILL TO STATUS CONTENT
PRESERVE
12ST FIBER TO B.122, 12ST FIBER TO B.121,
12ST FIBER TO B.120, 12 ST FIBER TO B.88
12ST FIBER TO G20C-B85, 12ST FIBER TO 130-B85,
12ST FIBER TO 1121-B85,
12ST FIBER TO 232D-B85,
12ST FIBER TO 215E-B85, 12ST FIBER TO 305-B85,
12ST FIBER TO 407-B85
12ST FIBER TO B-85A, 12ST FIBER TO B.77
PRESERVE
#2, 4 IN
#3, 3 IN 0% HH67
(3) 6 PR CU, FIRE ALARM IN BLACK ID, 8 PR DICTATION,
8 PR DICTATION
12ST FIBER TO B.33, 12ST FIBER TO B.54,
12ST FIBER B.124,
12ST FIBER TO B.T123, 12ST FIBER TO B.42
12ST FIBER TO B.4, 12ST FIBER TO B.44
12ST FIBER TO B.6, 12ST FIBER 116-B117,
12ST FIBER 216-B117, (2) 24ST FIBER 171-B127
#4, 3 IN 60% HH67 PRESERVE 27 PR MED GAS ALARMS, (4) SMART METER CABLES
#5, 3 IN 0% HH67
#6, 3 IN 0% HH67
#7, 3 IN 40% PB85-4
#8, 3 IN 30% PB85-3 PRESERVE
#9, 3 IN 10% PB85-4 PRESERVE
#10, 3 IN 5% PB85-3 PRESERVE
#11, 4 IN 30% MH14 PRESERVE
#12, 4 IN 40% MH14 PRESERVE
VACANT
VACANT
VACANT
PB85-1
27 PR MED GAS ALARMS, 8 PR DICTATION, 8 PR
DICTATION
3/8" NEXTEL ANTENNA, 3/8" NEXTEL ANTENNA
FIRE ALARM IN BLACK ID
FIRE ALARM IN BLACK ID, 5/8" TV CABLE
12ST FIBER TO B.33, 12ST FIBER TO B.54,
12ST FIBER B.124,
12ST FIBER TO B.T123, 12ST FIBER TO B.42
12ST FIBER TO B.4, 12ST FIBER TO B.44
12ST FIBER TO B.6, 12ST FIBER 116-B117,
12ST FIBER 216-B117,
PBX
#13, 4 IN 50% MH14 PRESERVE
#14, 4 IN 20% MH14 PRESERVE
#15, 4 IN 100% HH67
12ST FIBER TO B.122, 12ST FIBER TO B.121, 12ST FIBER
TO B.120, 12 ST FIBER TO B.88, 12ST FIBER TO 407-B85
SMART METER CABLES
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO 117-B.115, 12ST
FIBER TO 227-B.115,
12ST FIBER TO B.T110
HH67
HH67
HH67
HH67
HH67
HH67
HH67 HH67
PBX
PB85-1
PB85-1
PB85-1
PB85-4
PB85-4
MH-14
MH-14
PB85-3
PB85-3
MH-14
MH-14
#21, 4 IN 85% PB85-1
#20, 4 IN 40% PB85-1
#17, 4 IN 100% HH67
#18, 4 IN 100% HH67
#16, 4 IN 85% HH67 PRESERVE 3/8" NEXTEL ANTENNA, 3/8" NEXTEL ANTENNA
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116
#19, 4 IN 100% PB85-1 PRESERVE
PRESERVE
VACANT
(2) 6 PR CU
7/8" TV CABLE, (3) SMART METER CABLES
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO 117-B.115,
12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
TO HH67
TO
P
BX
B
LD
G
15%
5/8" TV CABLE, 5/8" TV CABLE, FIRE ALARM IN BLACK ID
10%
SHEET NOTES:
1. STATUS "NEW" REFERS TO NEW CABLING INSTALLED AS PART
OF THIS SOW IN EXISTING DUCTS. ENSURE AS BUILTS OF
BUTTERFLIES ARE PROVIDED TO COR UPON COMPLETION OF
PROJECT. CONTRACTOR SHALL PROVIDE/UPDATE CONDUIT FILL
VALUES FOR ALL NEW CABLE RUNS.
PRESERVE
#7, 4 IN 10% PB85-1
PRESERVE
#8, 4 IN 30% PB85-1
#4, 4 IN 45% PB77-1
DUCT#
SIZE(IN)
(E)
FILL TO STATUS
PRESERVE
#1, 4 IN 80% PB77-1
#2, 4 IN 10% PB77-1
CONTENT
(3)SMART METER CABLES
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116,
12ST FIBER TO B.85A, 12ST FIBER TO B.77
NEW
#3, 4 IN 50% PB77-1 PRESERVE
(2) 24ST FIBER 171-B127
CATV, PHARMACY SECURITY, CAT 3 WIRE,
27PR MED GAS ALARMS, 6PR OXYGEN
ALARMS, 3/8" NEXTEL ANTENNA
7/8" TV CABLE
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126,
12ST FIBER TO 117-B.115,
12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
#5, 4 IN 80% PB85-1
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116,
12ST FIBER TO B.85A, 12ST FIBER TO B.77
#6, 4 IN 100% PB85-1
12ST FIBER TO G20C-B85, 12ST FIBER TO
130-B85, 12ST FIBER TO 1121-B85,
12ST FIBER TO 232D-B85,
12ST FIBER TO 215E-B85,
12ST FIBER TO 305-B85
7/8" TV CABLE, (3)SMART METER CABLES
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
7 6 5
4 3
TO PB77-1
#9, 4 IN 100% G20B-85 PRESERVE
#10, 4 IN 0% G20B-85 PRESERVE
#11, 4 IN 100% -
#12, 4 IN 5% -
#13, 4 IN 50% G20B-85
12ST FIBER TO G20C-B85, 12ST FIBER TO
130-B85, 12ST FIBER TO 1121-B85,
12ST FIBER TO 232D-B85,
12ST FIBER TO 215E-B85,
12ST FIBER TO 305-B85
PHARMACY SECURITY, CAT3 WIRE, 5/8" TV
CABLE
VACANT
VACANT
VACANT
2 1
TO PB85-1/G20B-85
DUCT#
SIZE(IN)
#1, 4 IN 80% PB85-2 PRESERVE
(E)
FILL TO STATUS CONTENT
12ST FIBER TO G20C-B85, 12ST FIBER TO
130-B85, 12ST FIBER TO 1121-B85,
12ST FIBER TO 232D-B85,
12ST FIBER TO 215E-B85,
12ST FIBER TO 305-B85
#2, 4 IN 100% PB85-2
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
#3, 4 IN 10% PB85-2
PRESERVE
#4, 4 IN 30% PB85-2
7/8" TV CABLE, (3)SMART METER CABLES
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116,
12ST FIBER TO B.85A, 12ST FIBER TO B.77
#5, 4 IN 80% MH14A PRESERVE
12ST FIBER TO G20C-B85, 12ST FIBER TO
130-B85, 12ST FIBER TO 1121-B85,
12ST FIBER TO 232D-B85,
12ST FIBER TO 215E-B85,
12ST FIBER TO 305-B85
#6, 4 IN 100% MH14A PRESERVE
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
#7, 4 IN 10% MH14A
TO MH14A
1 2 3 4
#8, 4 IN 40% MH14A
PRESERVE
PRESERVE 7/8" TV CABLE, (3)SMART METER CABLES
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116,
12ST FIBER TO B.85A
TO PB85-2
5 6 7 8
DUCT#
SIZE(IN)
#1, 4 IN 45% PB85-2
(E)
FILL TO STATUS CONTENT
PRESERVE 7/8" TV CABLE
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116,
12ST FIBER TO B.85A, 12ST FIBER TO B.77
PRESERVE
#2, 4 IN 50% PB85-2
CATV, PHARMACY SECURITY, CAT3 WIRE,
27PR MED GAS ALARMS, 6PR OXYGEN
ALARMS, 3/8" NEXTEL ANTENNA
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
#3, 4 IN 10% PB85-2
#4, 4 IN 80% PB85-2
#5, 4 IN 10% MH7 PRESERVE
#6, 4 IN 10% PB77-2
X
7/8" TV CABLE
TO
G01-77
#7, 4 IN 60% PB77-2 PRESERVE
PRESERVE
#8, 4 IN 20% PB77-2
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116
27PR MED GAS ALARM, 6PR OXYGEN
ALARMS
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
TO
PB85A-1
TO
G01-77
TO
PB77-3
PB77-2
TO
MH7
TO
TO
PB77-2
TO
PB77-2
TO
TO
TO
TO
PB85-2 PB85-2 PB85-2 PB85-2
PRESERVE (3)SMART METER CABLES
#9, 2 IN 5% G01-77 PRESERVE
#10, 2 IN 10% G01-77 -
PRESERVE
#11, 4 IN 60% PB77-3
PRESERVE
#12, 4 IN 80% PB85A-1
#13, 1/2 IN 20% G29-85 PRESERVE
12ST FIBER TO B85A
CAT3 WIRE
TO
G29-85
CAT 5 WIRE, CAT 5 WIRE, CAT3 WIRE, DDC
CABLES, CAT 5 DATA FOR DDC
VACANT
CAT 5 WIRE, CAT 5 WIRE, CAT3 WIRE, DDC
CABLES, CAT 5 DATA FOR DDC, 3/8" NEXTEL
ANTENNA, (3)SMART METER CABLES
12ST FIBER TO B77
PHARMACY SECURITY, CATV
TO PB85-2
TO
A-
/8
5A
TO
M
H 7/
G
-7 7/
PB
-2
DUCT#
SIZE(IN)
13 14
PRESERVE
ADD
NEW
CABELING
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
#22, 4 IN 10% PB85-1 NEW (2) 24ST FIBER 171-B127
- VACANT
NEW (2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLINGNEW CABLING
NEW CABLING
B.67, RM
G02B-67
ELECTRICAL DETAILS
E-504
SCALE: NTS1 BUTTERFLY VIEW DETAIL - MANHOLE MH14A
SCALE: NTS2 BUTTERFLY VIEW DETAIL - PULLBOX PB 85-1
SCALE: NTS3 BUTTERFLY VIEW DETAIL - PULLBOX 85-2
SCALE: NTS4 BUTTERFLY VIEW DETAIL - PULLBOX 77-1
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB 195 OF 206
#4, 4 IN 20% PB77-1
#5, 4 IN 60% PB77-1 PRESERVE
#3, 4 IN 10% MH7 NEW
PRESERVE
#2, 4 IN 60% MH7 PRESERVE
#1, 4 IN 20% MH7
DUCT#
SIZE(IN)
(E)
FILL TO STATUS
PRESERVE
CONTENT
27PR MED GAS ALARMS, 6PR OXYGEN
ALARMS
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER TO B.23, 12ST FIBER TO B.45
12ST FIBER TO B.123, 12ST FIBER B.114,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111,12ST FIBER TO B.116
(2) 24ST FIBER 171-B127
27PR MED GAS ALARMS, 6PR OXYGEN
ALARMS
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER TO B.23, 12ST FIBER TO B.45
12ST FIBER TO B.123, 12ST FIBER B.114,
12ST FIBER TO B.126, 12ST FIBER TO
117-B.115, 12ST FIBER TO 227-B.115, 12ST
FIBER TO BT110
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8, 12ST
FIBER TO B.T111, ,12ST FIBER TO B.116
#6, 4 IN 10% PB77-1
TO
P
B7 7-
TO
M
H
DUCT#
SIZE(IN)
G07-
PB77-
PB77-
MH10
PB27-1
#13, 4 IN 10% MH6
#14, 4 IN 100% MH6
#15, 3 IN 0% MH10
#16, 3 IN 10% MH10 PRESERVE
MH6
400PR
VACANT
(1) DDC CONTROLS
#17, 3 IN 20% MH10 PRESERVE FIRE ALARM IN BLACK ID, FIRE ALARM IN BLACK ID
MH6
50,200PR
X
X
X
#11, 3 IN 5% MH6
#12, 3 IN 30% MH6 PRESERVE
#1, 3IN
#2, 3 IN
#3, 3 IN
75% G07-27 -
0% -
20% PB27-1
#4, 1.5 IN 0%
#5, 1.5 IN 0%
#6, 1.5 IN 0%
#7, 4 IN
#8, 4 IN 100% MH10 PRESERVE
#9, 3 IN
#10, 3 IN 0%
25% G07-27
MH6
PRESERVE
PRESERVE
CONTENT
VACANT
VACANT
FIRE ALARM IN BLACK ID, 1/4" CATV, (2) DDC
CONTROLS, FIRE ALARM IN BLACK ID, (4) 12 AWG
FIRE ALARM
12 ST FIBER TO B.116
NOT USABLE
NOT USABLE
NOT USABLE
60% MH10
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO 117-B.115,
12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
1/4" CATV, (1) DDC CONTROLS
VACANT
(2) DDC CONTROLS, (4) 12 AWG FIRE ALARM
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116
MH6
7/8" TV CABLE, 27 PR MED GAS ALARMS G07-27
MH6
X
MH10
MH10 MH10
#20, 4 IN 10% PB77-2 NEW
#21, 4 IN 10% PB77-1 PRESERVE
#22, 3/4 IN 50% OP PRESERVE
#19, 4 IN 60% PB77-2 PRESERVE
#18, 4 IN 20% PB77-2
PRESERVE 27 PR MED GAS ALARMS, 6 PR OXYGEN ALARMS
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111, 12ST FIBER TO B.116
12ST FIBER TO B.1, 12ST FIBER TO B.24,
12ST FIBER B.114, 12ST FIBER TO B.23,
12ST FIBER TO B.45, 12ST FIBER TO B.123,
12ST FIBER TO B.126, 12ST FIBER TO 117-B.115,
12ST FIBER TO 227-B.115,
12ST FIBER TO B.T110
7/8" TV CABLE
6 PR OXYGEN ALARMS (OXYGEN PAD)
TO MH 10
MH10
TO BLDG 27/PB77-1
TO
M
H
0P
R O
XY
G
EN
PA
D
PB
2 PB
TO
M
H
/ B
LD
G
9-
9-
9-
#7, 4 IN
#8, 3 IN
#9, 3 IN
10%
5%
#10, 3 IN 10%
#11, 3 IN 0%
#12, 2 IN 10%
#13, 2 IN 0%
MH5
MH5 -
MH5 PRESERVE
NA -
NA PRESERVE
NA -
VACANT.
27PR MED GAS ALARMS
VACANT
CATV
VACANT
MH5 MH5
MH5 MH5
MH5
TO MH5
75% MH5
#6, 4 IN 60% MH5 PRESERVE
#4, 4 IN 10% MH7
x x
#5, 4 IN 100% MH7 PRESERVE
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111
7/8" TV CABLE
x
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8, 12ST
FIBER TO B.T111
MH7
MH7
400PR
#2, 3 IN
#3, 3 IN
30%
0%
MH7 PRESERVE
MH7 PRESERVE
7/8" TV CABLE, 27 PR MED GAS ALARMS
12ST FIBER TO B.116
DUCT#
SIZE(IN)
#1, 3 IN 15%
CONTENT
MH7 PRESERVE (4)12AWG FIRE ALARM, (2) DDC CONTROLS
#16, 2.5 IN 5% 119-116
#14, 2.5 IN 5% 119-116
#15, 2.5 IN 0% 119-116
PRESERVE (4)12AWG FIRE ALARM, (2) DDC CONTROLS
12ST FIBER TO B.116
VACANT
VACANT
TO
M
H
MH7
MH7
MH7
TO
M
H
MH7
MH7
MH7
TO
M
H 4/
BL
D
G T
1/
T1
TO
M
H 6/
BL
D
G
/B
LD
G
DUCT#
SIZE(IN)
#1, 4 IN
(E)
FILL TO STATUS CONTENT
75% MH6
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
12ST FIBER TO B.T111
#2, 4 IN
#3, 2 IN
#4, 2.5 IN
#5, 3 IN
#6, 3 IN
#7, 3 IN
#8, 3 IN
#9, 4 IN
#10, 2 IN
#11, 4 IN
60% MH6 PRESERVE
10% PB29-1 PRESERVE
0% PB29-2 PRESERVE
5% PB110-1 -
20% PB110-1 PRESERVE
0% PB110-1
0% UK
60% 104-T111
0% 50%
AB
MH4
7/8" TV CABLE
FIRE ALARM IN BLACK ID, TV CABLE?, 1PR DDC
CONTROLS
VACANT
VACANT.
TO MH6
7/8" TV CABLE, 7/8" TV CABLE, 5/8" TV CABLE
VACANT
VACANT
PRESERVE 1PR DDC CONTROLS, FIRE ALARM IN BLACK ID
12ST FIBER TO B.T111
PRESERVE
#12, 4 IN 60% MH4
#13, 3 IN
#14, 3 IN
#15, 3 IN
15%
25%
10%
MH4
MH4
#16, 1.5 IN 0% UN
#17, 1.5 IN 0% UN
#18, 3 IN
MH4 PRESERVE
10% MH6 PRESERVE
UNUSABLE
VACANT.
7/8" TV CABLE, 5/8" TV CABLE
12ST FIBER TO B.34, 12ST FIBER TO B.43,
12ST FIBER TO B.50, 12ST FIBER TO B.82,
12ST FIBER TO B.48, 12ST FIBER TO B.28,
12ST FIBER TO B.46, 12ST FIBER TO B.8,
VACANT.
VACANT.
27PR MED GAS ALARMS
UNUSABLE
ABANDONED LEAD - UNUSABLE
27PR MED GAS ALARMS
200PR
200PR
400PR
#19, 3 IN 80% MH6
#20, 1.25 IN 0% UK
#21, 3 IN 10% MH6
#22, 1.25 IN 0% UK
#23, 1.5 IN 0% PB29-2
VACANT.
VACANT
VACANT
VACANT
(E)
FILL TO STATUS
(E)
FILL TO STATUS
SHEET NOTES:
1. STATUS "NEW" REFERS TO NEW CABLING INSTALLED AS PART
OF THIS SOW IN EXISTING DUCTS. ENSURE AS BUILTS OF
BUTTERFLIES ARE PROVIDED TO COR UPON COMPLETION OF
PROJECT. CONTRACTOR SHALL PROVIDE/UPDATE CONDUIT FILL
VALUES FOR ALL NEW CABLE RUNS.
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
PRESERVE
12 13 14 15 16
8 9
10 6 7
1 3
PRESERVE
PRESERVE
PRESERVE
NEW (2) 24ST FIBER 171-B127 NEW (2) 24ST FIBER 171-B127
(2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
NEW (2) 24ST FIBER 171-B127
16 17
MH6
10 11
S
9 22 18 19 20 21
1 2
NEW (2) 24ST FIBER 171-B127
#24, 4 IN 10% B127
#25, 4 IN 0% B127
#26, 4 IN 0% B127
NEW (2) 24ST FIBER 171-B127
NEW
NEW VACANT
24 25 26
222018
19 21
9 11
S
NEW
CABLING/CONDUIT
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING
VACANT
ELECTRICAL DETAILS
E-505
SCALE: NTS1 BUTTERFLY VIEW DETAIL-PULLBOX 77-2
SCALE: NTS2 BUTTERFLY VIEW DETAIL - MANHOLE MH7
SCALE: NTS3 BUTTERFLY VIEW DETAIL - MANHOLE MH6
SCALE: NTS4 BUTTERFLY VIEW DETAIL - MANHOLE MH5
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
LRL / BJR JPS / FEB 196 OF 206
LEGEND
SPLICE
CONDUIT
AC ARMORED CABLE
G GROUNDING CONDUCTOR
LEGEND
SPLICE
CONDUIT
AC ARMORED CABLE
G GROUNDING CONDUCTOR
LEGEND
SPLICE
CONDUIT
AC ARMORED CABLE
G GROUNDING CONDUCTOR
LEGEND
SPLICE
CONDUIT
AC ARMORED CABLE
G GROUNDING CONDUCTOR
NORTH
EASTWEST
SOUTH
G
G
G
NORTH
EASTWEST
SOUTH
G
G
G
WEST
NORTH
SOUTH
EAST
8 1
G
11 5
G
G
WEST
NORTH
SOUTH
EAST
G
G 4 2 3 1
2 4
1 3DESTINATIONCABLEFILL
%DUCT
SIZEDUCT ID
-G - - MH4A
FACE
E -
1 5" MH4AE -
1-4/0 AC (E102)2 5" 100 MH4AE -
DUCT
TYPE
PVC
PVC
3 2" MH4AE -PVC
PLC CONTROLS4 2" 20 MH4AE -PVC
-G - - MH2W --
-G - - B.83-GRND-BUSW --
-1 5" - MH2W -PVC
-2 5" - MH2W -PVC
1-4/0AC (E101)3 5" 100 MH2W -PVC
-4 5" - MH2W -PVC
-5 4" - B.83-SECTION-6W -PVC
1-4/0 AC (E101)6 4" 100 B.83-SECTION-6W -PVC
1-4/0 AC (T1N)7 5" 100 T1NW -PVC
PLC CONTROLS8 2" 20 MH2W -PVC
9 2" - MH2W -PVC
PLC CONTROLS10 2" 20 HH8W -PVC
-11 2" - HH8W -PVC
PLC CONTROLS12 2" 20W -PVC
-13 2" -W -PVC
DESTINATIONCABLEFILL
%DUCT
SIZEDUCT ID
-G - - MH2
FACE
N -
1 5" 100 MH2N -
1-4/0 AC (N101)2 5" 100 MH2N -
DUCT
TYPE
PVC
PVC
3 5" MH2N -PVC
4 5" MH2N -PVC
-G - - MH4AE --
-5" - MH4AE -PVC
5" 100 MH4AE -PVC2
5" MH4AE -PVC
1-4/0 AC (N102)
5" 100 MH4AE -PVC
FILLED IN WITH GROUT
2" - -E -PVC
FILLED IN WITH GROUT
2" - -E -PVC
1-4/0 AC
5" 100 T1NW -PVC7
DESTINATIONCABLEFILL
%DUCT
SIZEDUCT ID
-G - - S2E
FACE
N -
-1 5" - S2EN -
1-4/0 AC (E102)2 5" 100 S2EN -
DUCT
TYPE
PVC
PVC
3 5"N -PVC
4 5"N -PVC
1-4/0 AC (T5N)5 5" 100 S2NN -PVC
1-4/0 AC (N102)5" 100 S2NN -PVC
PLC CONTROLS
2" 20 S2EN -PVC
2" - S2EN -PVC
- - MH4E --
G
5" - MH4E -PVC
5" - MH4E -PVC
1-4/0 AC (N103)
5" 100 MH4E -PVC3
DESTINATIONCABLEFILL
%DUCT
SIZEDUCT ID
-G - - MH4A
FACE
N -
1 5" MH4AN -
1-4/0 AC (E102)2 5" 100 MH4AN -
DUCT
TYPE
PVC
PVC
3 5" MH4AN -PVC
1-4/0 AC (N103)4 5" 100 MH4AN -PVC
PLC CONTROLS5 2" 20 MH4AN -PVC
-2" - MH4AN -PVC
- - S5NE --
G
5" - S5NE -PVC
5" - S5NE -PVC
1-4/0 AC (N103)
5" 100 S5NE -PVC
1-4/0 AC (N104)
5" 100 S5NE -PVC
PLC CONTROLS
2" 20 S5NE -PVC5
-5" - MH4E -PVC4
1-4/0 AC (T5N)5" 100 MH4E -PVC5
1-4/0 AC (N102)5" 100 MH4E -PVC6
-- - MH5BS --G
5" MH5BS -PVC1
1-4/0 AC (N103)5" 100 MH5BS -PVC2
5" MH5BS -PVC3
1-4/0 AC (E102)5" 100 MH5BS -PVC4
PLC CONTROLS2" 20 MH5BS -PVC5
-2" - MH5BS -PVC6
S
S
S
S
-2" - S5NE -PVC6
-- - MH5CS --G
1-4/0 AC (N104)5" 100 MH5CS -PVC1
1-4/0 AC (E102)5" 100 MH5CS -PVC2
-5" - MH5CS -PVC3
-5" - MH5CS -PVC4
PLC CONTROLS2" 20 MH5CS -PVC5
-2" - MH5CS -PVC6
-1
- -2
-3
- -4
- -5
- -6
NEW CABLING FROM
SECTIONALIZER "S2E"
NEW CABLING
NEW CABLING
NEW CABLING
SHEET NOTES:
NEW
CONDUIT &
CABLING
NEW CABLING
NEW CONDUIT
AND CABLING
NEW CABLING FROM
SECTIONALIZER "S2N"
NEW CABLING FROM
SECTIONALIZER "S2E"
NEW CABLING
NEW CABLING
NEW CABLING
NEW CABLING FROM
SECTIONALIZER "S2N"
NEW CABLING FROM
SECTIONALIZER "S2E"
1-4/0 AC (S2E-3)100
S2E
S2E
100 1-4/0 AC (S2N-3)
1-4/0 AC (S2N-3)
1-4/0 AC (S2E-3)
S2N100
100 S2E
1-4/0 AC (S2N-4)
1-4/0 AC (S2E-4)
1-4/0 AC (S2N-4)
1-4/0 AC (S2E-4)
W
W
W
W
W
W
5"
5"
5"
5"
5"
5"
PVC
PVC
PVC
PVC
PVC
PVC
1-4/0 AC (S2N-5)
SPARE (RN-001)
SPARE (RN-002)
1-4/0 AC (S2E-5)
SPARE (RN-001)
SPARE (RN-002)
SC58N
SC58N
SC58N
SC58E
SC58E
SC58E
1. STATUS "NEW" REFERS TO NEW CABLING INSTALLED AS PART OF THIS SOW IN EXISTING DUCTS.
ENSURE AS BUILTS OF BUTTERFLIES ARE PROVIDED TO COR UPON COMPLETION OF PROJECT.
CONTRACTOR SHALL PROVIDE/UPDATE CONDUIT FILL VALUES FOR ALL NEW CABLE RUNS.
NEW CABLING
NEW CABLING
NEW CABLING
ELECTRICAL DETAILS
E-506
1-4/0 AC (2N3)
SCALE: NTS1 POWER MANHOLE "S2E"
SCALE: NTS2 POWER MANHOLE "S2N"
SCALE: NTS3 POWER MANHOLE "MH5B"
SCALE: NTS4 POWER MANHOLE "MH4A"
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
LRL / BJR JPS / FEB 197 OF 206
ONE-LINE DIAGRAM
SPD
PANEL 11
200A 208/120V
3PH 4W
42KAIC
SPD
DISTRIBUTION SWITCHBOARD - NMDP1
1200A 208/120V 3PH 4W 42KAIC
E-601
EXISTING MV SWITCH S2N
SW-2N-5
EXISTING VAULT - MH5B
EXISTING MV SWITCH S2E
TRANSFORMER
"T34E"
75KVA
12.47KV-208/120V 3P
Z = 5%MIN
SW-2E-5
EXISTING
BLDG 79
PNL1
60A 480/277V
3PH 4W
EXISTING
LIGHTING
CONTACTOR
EXISTING TRANSFORMER
T1
150KVA
12.47kV-480/277V Z=2.7%
EXISTING CB N1EXISTING CB N1
SW-2E-1SW-2N-2
1200/3
TIE-BREAKER SECTIONNORMAL POWER BUS 83N
1200A
EMERGENCY POWER BUS
83E
1200A
EXISTING CB U1 EXISTING CB 52-E2
EXISTING BUS 82G
1200A
EXISTING CB G1 EXISTING CB G2
EXISTING
GEN2
1500KW
EXISTING
GEN1
1500KW
EXISTING VAULT - MH4B
TRANSFORMER
"T34N"
500KVA
12.47KV-208/120V 3PH
Z = 5%MIN
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
KEY NOTES (THIS SHEET ONLY)
TO BUILDING GROUNDING ELECTRODE SYSTEM.
REFERENCE SHEET EG101 FOR ADDITIONAL INFORMATION.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL CIRCUITING INFORMATION.
CONTRACTOR SHALL PROVIDE SMART METER INTEGRAL TO
PANELBOARD PER MANUFACTURER'S REQUIREMENTS AND
PROVIDE INTEGRATION AS REQUIRED FOR OWNER
MONITORING. METER SHALL HAVE BAC NET AND DDC
CAPABILITY.
EXISTING UNDERGROUND CONDUIT/CONTROLLED SITE
LIGHTING CIRCUIT ROUTED THROUGH EXISTING
HANDHOLES TO PROVIDE POWER FOR NEW SITE LIGHTING
POLE FIXTURES. REFERENCE SITE PLANS ES100 AND ES101
FOR ADDITIONAL INFORMATION.
PRIMARY FUSES PROVIDED AND SIZED PER TRANSFORMER
MANUFACTURER.
COORDINATE WITH MANUFACTURER FOR CIRCUIT BREAKER
SIZING REQUIREMENTS.
CONTRACTOR SHALL PROVIDE PLACARD INDICATING
MAXIMUM AVAILABLE FAULT CURRENT. COORDINATE WITH
ENGINEER DURING CONSTRUCTION AS REQUIRED.
GENERAL SHEET NOTES
1. REFERENCE CONDUIT AND WIRE SCHEDULE ON SHEET E-603
FOR ADDITIONAL CIRCUITING INFORMATION.
EXISTING UTILITY
TRANSFORMER
EXISTING
UTILITY
SYSTEM
G G
SECTIONALIZER "SC5BN"
12.47KV 3PH
200A 42KAIC
SECTIONALIZER "SC5BE"
12.47KV 3PH
200A 42KAIC
SPD
1200A 3P
LSI
N G
DISTRIBUTION PANELBOARD - EMDP1
225A, 208/120V 3PH 4W, 22 KAIC
CB-NMDP1
SERVICE ENTRANCE RATED
SWITCH
208/120V 3PH 4W 42KAIC
100% RATED
SPD
PANEL 12
200A 208/120V
3PH 4W
42KAIC
CB-EMDP1
SERVICE ENTRANCE RATED
SWITCH
208/120V 3PH 4W 22KAIC
N G
SPD
PANEL 13
200A 208/120V
3PH 4W
42KAIC
SPD
PANEL 21
200A 208/120V
3PH 4W
42KAIC
A
PRIMARY CARE/MENTAL HEALTH BUILDING #127
SPARE SPARE SPARE SPARE
AHU-1
0A
/3 P
N G
N G
EXISTING
MDP1
480/277V
3PH 4W
BUILDING 79
60A 3P
SM SM
60A 3P
S2N-6
PN-002 PE-002
PN-005
S2E-6
PN-001
PN-010
EXISTING ELECTRICAL
STORAGE BUILDING #79
S2E-3
S2E-4
S2E-5
PE-001
MAX AFC= 4.2KA
PN-006 PN-007 PN-008 PN-009
225A 3P
LSI
MAX AFC= 27.8KA
S2N-3
S2N-4
S2N-5
200A 3P
LSI
200A 3P
LSI
200A 3P
LSI
200A 3P
LSI
600A 3P
LSI
6 6
5 5
SCALE: NTS1 ONE-LINE DIAGRAM
SPARE
200A 3P
LSI
G-004 G-005
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB
ONE-LINE DIAGRAM
(ADD ALT #2)
SPD
PANEL 11
200A 208/120V
3PH 4W
42KAIC
SPD
DISTRIBUTION SWITCHBOARD - NMDP1
1200A 208/120V 3PH 4W 42KAIC
E-601A
EXISTING MV SWITCH S2N
SW-2N-5
EXISTING VAULT - MH5B
EXISTING MV SWITCH S2E
TRANSFORMER
"T34E"
75KVA
12.47KV-208/120V 3P
Z = 5%MIN
SW-2E-5
EXISTING
BLDG 79
PNL1
60A 480/277V
3PH 4W
EXISTING
LIGHTING
CONTACTOR
EXISTING TRANSFORMER
T1
150KVA
12.47kV-480/277V Z=2.7%
AUTOMATIC
DISCONNECT SWITCH
'DISC-PV'
200A, 208V 3P
200A 3P
LSI
EXISTING CB N1EXISTING CB N1
SW-2E-1SW-2N-2
1200/3
TIE-BREAKER SECTIONNORMAL POWER BUS 83N
1200A
EMERGENCY POWER BUS
83E
1200A
EXISTING CB U1 EXISTING CB 52-E2
EXISTING BUS 82G
1200A
EXISTING CB G1 EXISTING CB G2
EXISTING
GEN2
1500KW
EXISTING
GEN1
1500KW
EXISTING VAULT - MH4B
TRANSFORMER
"T34N"
500KVA
12.47KV-208/120V 3PH
Z = 5%MIN
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
1200AT
1200AF
0/
KEY NOTES (THIS SHEET ONLY)
TO BUILDING GROUNDING ELECTRODE SYSTEM.
REFERENCE SHEET EG101 FOR ADDITIONAL INFORMATION.
FEEDER TO SOLAR PV SYSTEM. REFERENCE SHEET EY601
FOR CONTINUATION.
AUTOMATIC DISCONNECT SWITCH WITH MANUAL RESET.
DISCONNECT SHALL BE NORMALLY CLOSED. DISCONNECT
SHALL OPEN WHEN POWER IS LOST; MANUAL RESET SHALL
BE REQUIRED TO RECONNECT TO ELECTRICAL SYSTEM.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL CIRCUITING INFORMATION.
CONTRACTOR SHALL PROVIDE SMART METER INTEGRAL TO
PANELBOARD PER MANUFACTURER'S REQUIREMENTS AND
PROVIDE INTEGRATION AS REQUIRED FOR OWNER
MONITORING. METER SHALL HAVE BAC NET AND DDC
CAPABILITY.
PROVIDE INDICATION LAMP FOR OPEN DISCONNECT OR
CLOSED DISCONNECT. PROVIDE AUX CONTACTS FOR
ALARM.
EXISTING UNDERGROUND CONDUIT/CONTROLLED SITE
LIGHTING CIRCUIT ROUTED THROUGH EXISTING
HANDHOLES TO PROVIDE POWER FOR NEW SITE LIGHTING
POLE FIXTURES. REFERENCE SITE PLANS ES100 AND ES101
FOR ADDITIONAL INFORMATION.
PRIMARY FUSES PROVIDED AND SIZED PER TRANSFORMER
MANUFACTURER.
COORDINATE WITH MANUFACTURER FOR CIRCUIT BREAKER
SIZING REQUIREMENTS.
CONTRACTOR SHALL PROVIDE PLACARD INDICATING
MAXIMUM AVAILABLE FAULT CURRENT. COORDINATE WITH
ENGINEER DURING CONSTRUCTION AS REQUIRED.
PROVIDE PV WARNING PLACARD PER NEC.
GENERAL SHEET NOTES
1. REFERENCE CONDUIT AND WIRE SCHEDULE ON SHEET E-603
FOR ADDITIONAL CIRCUITING INFORMATION.
EXISTING UTILITY
TRANSFORMER
EXISTING
UTILITY
SYSTEM
G G
SECTIONALIZER "SC5BN"
12.47KV 3PH
200A 42KAIC
SECTIONALIZER "SC5BE"
12.47KV 3PH
200A 42KAIC
SPD
1200A 3P
LSI
N G
DISTRIBUTION PANELBOARD - EMDP1
225A, 208/120V 3PH 4W, 22 KAIC
CB-NMDP1
SERVICE ENTRANCE RATED
SWITCH
208/120V 3PH 4W 42KAIC
100% RATED
4 4
SPD
PANEL 12
200A 208/120V
3PH 4W
42KAIC
CB-EMDP1
SERVICE ENTRANCE RATED
SWITCH
208/120V 3PH 4W 22KAICN
G
SPD
PANEL 13
200A 208/120V
3PH 4W
42KAIC
SPD
PANEL 21
200A 208/120V
3PH 4W
42KAIC
A
PRIMARY CARE/MENTAL HEALTH BUILDING #127
SPARE SPARE
SPARE SPARE
AHU-1
0A
/3 P
N G
N G
EXISTING
MDP1
480/277V
3PH 4W
BUILDING 79
60A 3P
SM SM
60A 3P
S2N-6
PN-002 PE-002
PN-005PN-003
PN-004
S2E-6
PN-001
PN-010
EXISTING ELECTRICAL
STORAGE BUILDING #79
S2E-3
S2E-4
S2E-5
PE-001
MAX AFC= 4.2KA
PN-006 PN-007 PN-008 PN-009
225A 3P
LSI
MAX AFC= 27.8KA
S2N-3
S2N-4
S2N-5
200A 3P
LSI
200A 3P
LSI
200A 3P
LSI
200A 3P
LSI
600A 3P
LSI
9 9
8 8
ADD ALT 2
SCALE: NTS1 ONE-LINE DIAGRAM (ADD ALT #2)
G-004 G-005
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB
ELECTRICAL SCHEDULES
E-602
KEY NOTES (THIS SHEET ONLY)
NEW PARKING LOT LIGHTING SHALL BE TIED INTO EXISTING CIRCUIT '1'.
PANEL SCHEDULE IS INCLUDED TO CONFIRM BRANCH CIRCUIT BREAKERS SERVING
NEW LIGHTING IS NOT OVERLOADED. CONTRACTOR SHALL UPDATE PANEL DIRECTORY
TO INCLUDE NEW B127 AREA LIGHTING.
LOAD SCHEDULE IS INCLUDED TO CONFIRM THAT THE EXISTING PANEL WITH ADDED
LOAD IS NOT OVERLOADED. THIS SCHEDULE SHALL BE USED FOR INFORMATION
PURPOSES ONLY.
CIRCUIT CONTROLLED VIA ROOF MOUNTED PHOTOCELL AND ASSOCIATED LIGHTING
CONTACTOR LOCATED IN ELECTRICAL ROOM 170.
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
CONSTRUCT PRIMARY
CARE / MENTAL HEALTH
BUILDING
07/23/2021
BOISE VA MEDICAL CENTER - BOISE, ID
531-325 A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590 - 2118
RAY SPEES, PRESIDENT
Approved:
Approved: CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
LRL / BJR JPS / FEB