This solicitation notice provides details for a construction project to build a Clean Core addition to the surgical suite at the Providence, Rhode Island VA Medical Center. The project involves constructing approximately 2,900 gross square feet of new space in an elevated second floor addition and renovating 3,900 gross square feet of existing adjacent space. The work includes building a new surgery suite, relocating the cystoscopy and minor surgery areas, adding an elevated Clean Core with direct sterile supply access to the operating rooms and cystoscopy area, and relocating the surgery locker rooms. The solicitation will be a request for proposal conducted as a total Service-Disabled Veteran-Owned Small Business set-aside, with an estimated value between $5-10 million. The period of performance is approximately 490 calendar days from notice to proceed.
36E77619R0097 Attachment 10 - Electrical Plans.pdf
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REF:
A1
1.
2.
3.
4.
5.
6.
7.
8.
CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY.
INSTALL CONDUIT WITH A MINIMUM OF BENDS IN
THE SHORTEST PRACTICAL DISTANCE
CONSIDERING THE BUILDINGS CONSTRUCTION
AND OBSTRUCTIONS, EXCEPT WHERE OTHERWISE
NOTED.
ALL ENCLOSURES, CONDUIT BODIES AND THEIR
COVERS WHICH CONTAIN FIRE ALARM SYSTEM
CONDUCTORS SHALL BE PAINTED RED.
FLEXIBLE CONNECTIONS TO MOTORS SHALL BE
FLEXIBLE LIQUID TIGHT CONDUIT.
9.
10.
11.
12.
13.
14.
15.
16.
18.
19.
17.
UNLESS OTHERWISE NOTED, ALL WIRING SHALL
BE 600V, COPPER WITH THHN-THWN INSULATION.
ALL GENERAL NOTES, SYMBOLS, LISTS,
ABBREVIATIONS AND DETAILS ARE TO BE
CONSIDERED APPLICABLE TO ALL ELECTRICAL
DRAWINGS FOR THIS PROJECT.
WHERE MATERIAL IS CALLED OUT IN THE
LEGEND BY MANUFACTURER, TYPE OR
CATALOG NUMBER, SUCH DESIGNATIONS
ARE TO ESTABLISH STANDARDS OR
DESIRED QUALITY. ACCEPTANCE OR
REJECTION OF THE PROPOSED
SUBSTITUTIONS SHALL BE SUBJECT TO
THE APPROVAL OF THE OWNER.
REFER TO ARCHITECTURAL DRAWINGS FOR
EXACT LOCATION OF EQUIPMENT, DEVICES, AND
FURNITURE REQUIREMENTS, PRIOR TO ROUGHING
IN FOR SAME.
IN AREAS AFFECTED BY THIS RENOVATION,
THE ELECTRICAL SUBCONTRACTOR SHALL
MAINTAIN CONTINUITY OF EXISTING ELECTRICAL
SERVICE.
PRIOR TO REMOVAL OF EQUIPMENT, THE
OWNER WILL INDICATE WHICH EXISTING DEVICES
OR MATERIALS SHALL BE SALVAGED AND TURNED
OVER FOR STORAGE.
WHERE EXISTING EQUIPMENT AND DEVICES ARE
TO BE RELOCATED, ALL ASSOCIATED WIRING,
CONDUIT AND ACCESSORIES SHALL BE EXTENDED,
RELOCATED OR REPLACED WHERE REQUIRED.
ALL EXIT SIGNS AND NIGHT LIGHT (NL) FIXTURES
ARE TO BE UNSWITCHED.
NOTES
1.
2. THE ELECTRICAL CONTRACTOR SHALL VERIFY
FIXTURE MOUNTING AND LOCATION AGAINST
PLANS, ELEVATIONS, AND DETAIL DRAWINGS.
EXACT LOCATION OF ALL FIXTURES SHALL BE
CONFIRMED WITH THE ARCHITECT PRIOR TO
ROUGHING IN.
THE ELECTRICAL CONTRACTOR SHALL FURNISH
ALL LIGHTING FIXTURES COMPLETE WITH
MOUNTING ACCESSORIES TO MEET JOB REQUIREMENTS.
3.
4.
SERIES FIXTURES SHALL SATISFY LENGTHS AS
SHOWN ON THE DRAWINGS.
FIXTURE LETTERS SHOWN ON A CONTINUOUS ROW
OF FIXTURES SHALL BE TYPICAL FOR THAT ROW
UNLESS OTHERWISE NOTED.
5.
6.
7.
ALL FIXTURES SHALL BE SUPPORTED FROM THE
BUILDING STRUCTURE, INDEPENDENT OF HUNG
CEILINGS.
(EN)
EXISTING TO BE DISCONNECTED AND
RELOCATED
EXISTING IN NEW LOCATION
GENERAL NOTES LIGHTING FIXTURE NOTES
EXISTING
EQUIPMENT LEGEND
REF:
A2
LEGEND
THE ELECTRICAL SUBCONTRACTOR SHALL VISIT
THE SITE AND INSPECT EXISTING CONDITIONS,
SERVICES, CONDUITS, SPATIAL CONSIDERATIONS
AND ALL OTHER PERTINENT CONDITIONS TO FULLY
FAMILIARIZE HIMSELF WITH CONDITIONS TO BE
ENCOUNTERED IN THE PERFORMANCE OF THIS WORK.
THE ELECTRICAL SUBCONTRACTOR SHALL COORDINATE
THIS WORK WITH THE GENERAL CONTRACTOR DURING
CONSTRUCTION. FAILURE TO DO SO WILL NOT RELIEVE
THE ELECTRICAL SUBCONTRACTOR OF THE RESPONSIBILITY
FOR FULL COMPLETION OF THE WORK IN ACCORDANCE
WITH APPLICABLE DRAWINGS AND SPECIFICATIONS.
VERIFY EXISTING SYSTEMS THAT WILL BE UTILIZED FOR
CONNECTION TO THE NEW SYSTEM. IF DISCREPANCIES
EXIST BETWEEN THE CONTRACT DRAWINGS AND THE
ACTUAL EXISTING CONDITIONS, THE ELECTRICAL
SUBCONTRACTOR SHALL NOTIFY THE ENGINEER/OWNER
PRIOR TO PROCEEDING WITH THE INSTALLATION.
ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND
MOTOR STARTERS THAT ARE NOT PROVIDED BY
OTHER DIVISIONS, SHALL BE PROVIDED BY DIVISION 26,
UNLESS SPECIFICALL NOTED OTHERWISE.
ALL PENETRATIONS THROUGH FIRE-RATED FLOORS,
WALLS AND PARTITIONS SHALL BE SEALED WITH
UL APPROVED FIRE SEALANT MATERIAL TO
MAINTAIN THE RATING OF THE SEPARATION.
UNLESS OTHERWISE INDICATED ALL RECEPTACLES
SHALL BE HOSPITAL GRADE.
U.L. LISTED AND LABELED.
APPLICABLE, PROVIDE ONLY MATERIALS THAT ARE
ANSI, IEEE, IES, AND NEMA STANDARDS. WHERE
MATERIALS AND EQUIPMENT THAT COMPLY WITH
STATE, COUNTY, AND CITY AGENCIES. PROVIDE
REGULATIONS OF THE PERTINENT FEDERAL,
OSHA REGULATIONS, AS WELL AS APPLICABLE
NFPA 70, NATIONAL ELECTRICAL CODE(NEC),
ACCORDANCE WITH THE LATEST EDITION OF
ALL WORK SHALL BE PERFORMED IN
1.
PUBLIC ADDRESS SYSTEM NOTES
1.
a.
b.
c.
PROVIDE NEW CARD READERS
WHERE INDICATED.
PROVIDE NEW DOOR CONTACTS
WHERE INDICATED.
PROVIDE NEW REQUEST TO EXIT
DEVICES WHERE INDICATED.
2.
3.
d.
e. PROVIDE NEW ELECTRIC STRIKES
WHERE INDICATED.
CARD ACCESS
SYSTEM NOTES
COORDINATE ALL CARD ACCESS WORK WITH VA
CAMPUS POLICE DEPARTMENT.
ACCESS CONTROL WORK SHALL BE DONE BY
JOHNSON CONTROLS INC. CONTACT CHRIS
DAVID, SECURITY TEAM LEADER; 39 SALEM ST
LYNNFIELD, MA 01940: OFFICE 781-246-5500,
CELL 508-948-7240.
f. PROVIDE RELAYS AND CONNECTIONS
TO MOTORIZED DOOR OPENERS AS REQUIRED.
PROVIDE CONNECTION TO FIRE
ALARM SYSTEM AS REQUIRED.
#10
BRANCH CIRCUIT
VOLTAGE DROP
#8
CONDUCTOR AWG
MAXIMUM CONDUCTOR LENGTH AT 120V
MAXIMUM CONDUCTOR LENGTH AT 277V
GROUND CONDUCTOR AWG
MAXIMUM CONDUCTOR LENGTH AT 480V 1PH.
MAXIMUM CONDUCTOR LENGTH AT 208V 1PH
#10
#12
#12 #10
1.
2.
3.
4.
NOTES:
INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED.
BASED ON 20 AMP CIRCUIT LOADED TO 10 AMP USING
SINGLE PHASE, 2 WIRE CIRCUITS.
SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE
BASED ON LENGTH OF BRANCH CIRCUIT CONDUCTOR
FROM PANEL TO PHYSICAL CENTER OR LOAD TO
OVERCOME VOLTAGE DROP. 3% VOLTAGE DROP
ASSUMED.
TRANSITION FROM LARGER CONDUCTOR SIZE TO #12
FOR FINAL TERMINATION TO OUTLET DEVICE. PROVIDE
JUNCTION BOX WITHIN 10' OF OUTLET. EXTEND #12
CONDUCTOR TO OUTLET DEVICE.
CONDUCTOR INSULATION TYPE SHALL BE THHN/THWN,
75 DEG. C, AND 600V CLASS UNLESS SPECIFIED OTHERWISE.
TELE/DATA SYSTEM NOTES
ALL FIXTURES INDICATED WITH 'NL' ARE TO BE
UNSWITCHED NIGHT LIGHT FIXTURES.
MODIFY THE EXISTING JOHNSON CONTROLS INC.
PEGASYS P2000, VERSION 3.4 CARD ACCESS
SYSTEM PRESENTLY SERVING THE HOSPITAL
BUILDING TO ACCOMMODATE THE NEW
DEVICES INDICATED. PROVIDE EXPANSION CARDS
ADDITIONAL POWER SUPPLIES, CABLES AND
ALL OTHER ACCESSORIES FOR A COMPLETE AND
OPERATIONAL SYSTEM.
CONTRACTOR SHALL PROVIDE ALL PULLBOXES
REQUIRED FOR FEEDERS, SIZE AS REQUIRED.
E L E C T R I C A L L E G E N D
HOMERUN TO PNLBRD - ARROWS INDICATE NUMBER OF CIRCUITS. CROSS LINES INDICATE
NUMBER OF CONDUCTORS OTHER THAN TWO (PROVIDE NUMBER OF WIRES REQUIRED TO ALLOW
SWITCHING SHOWN - E10 SERIES LIGHTING DRAWINGS).
CIRCUIT NUMBER(S)
PANEL DESIGNATION
SINGLE POLE SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER
INDICATES SWITCH CONTROL
THREE-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE
FOUR-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE
WALL MOUNTED OCCUPANCY SENSOR SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE
OC OCCUPANCY SENSOR AND POWER PACK - PROVIDE NUMBER OF POWER PACKS REQUIRED TO
HOSPITAL GRADE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL INTERIOR
GFI HOSPITAL GRADE GFCI DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL INTERIOR
HOSPITAL GRADE DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL
GFI HOSPITAL GRADE GFCI DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL
HOSPITAL GRADE EMERGENCY DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL
HOSPITAL GRADE EMERGENCY GFCI DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL
GFI HOSPITAL GRADE EMERGENCY GFCI DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE
SPECIAL RECEPTACLE - SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS.
VOICE AND DATA OUTLET - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE AND
TWO 1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION SECTION
27 10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS
W
UNLESS NOTED OTHERWISE - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE
AND ONE 1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION
SECTION 27 10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS
V
TV OUTLET - SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS UNLESS
NOTED OTHERWISE - JUNCTION BOX WITH SINGLE GANG RAISED RING/FACEPLATE AND ONE
1" CONDUIT TO ABOVE AN ACCESSIBLE CEILING - REFER TO SPECIFICATION SECTION 27
10 00 STRUCTURED CABLING FOR DATA OUTLET AND CABLING REQUIREMENTS
J JUNCTION BOX
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION DISCONNECT SWITCH & MOTOR STARTER
MOTOR RATED SWITCH
EXISTING PANELBOARD
PANELBOARD
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
GROUND ROD
MOUNTED
MOUNTED DIRECTLY ABOVE DOOR
S PUBLIC ADDRESS SPEAKER - CEILING MOUNTED - "V" INDICATES INTEGRAL VOLUME CONTROL
S PUBLIC ADDRESS SPEAKER - WALL MOUNTED - "V" INDICATES INTEGRAL VOLUME CONTROL
CONTROL PANEL
MOTORIZED DOOR ACTIVATION STATION
CARD READER
DOOR CONTACT/SWITCH
ELECTRIC STRIKE
REQUEST TO EXIT BUTTON
REQUEST TO EXIT SENSOR
## KEYNOTE
EXISTING ITEMS SHOWN DASHED
WP WEATHERPROOF
NL NIGHTLIGHT
EQ
CR CRITICAL PANEL
CB
EQUIPMENT PANEL
EMH ELECTRIC MANHOLE
CIRCUIT BREAKER
ATS AUTOMATIC TRANSFER SWITCH
ALL FIXTURES SHALL MEET UTILITY COMPANY INCENTIVE
REQUIREMENTS. CONTRACTOR SHALL COMPLETE ALL
INCENTIVE APPLICATIONS AND SUBMIT ALL REQUIRED
INFORMATION TO THE UTILITY COMPANY PRIOR TO
ORDERING LIGHT FIXTURES. ALL INCENTIVES SHALL BE
TURNED OVER TO THE VA.
1.
a.
2.
b.
c.
PROVIDE NEW FIRE ALARM
SPEAKER/STROBES WHERE
INDICATED.
PROVIDE NEW FIRE ALARM STROBES
WHERE INDICATED.
FIRE ALARM
SYSTEM NOTES
REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES
AND LOCATIONS OF ALL FIRE ALARM DEVICES
ASSOCIATED WITH FIRE PROTECTION SYSTEMS.
d.
e.
f.
PROVIDE NEW FIRE ALARM DUCT SMOKE
DETECTORS WHERE INDICATED.
PROVIDE NEW FIRE ALARM SMOKE
DETECTORS WHERE INDICATED.
h.
MAKE ALL CONNECTIONS AS REQUIRED.
PROVIDE ALL REQUIRED PROGRAMMING.
RELOCATE EXISTING FIRE ALARM DEVICES
AS INDICATED.
3.
1.
a.
b.
2.
3.
CCTVSYSTEM NOTES
COORDINATE ALL CCTV WORK WITH VA
CAMPUS POLICE DEPARTMENT.
CCTV WORK SHALL BE DONE BY
SHANIX TECHNOLOGY. CONTACT DON T. VOLINO,
GENERAL DIRECTOR; 40 WORTHINGTON
ROAD, CRANSTON, RI, 02920: OFFICE 401-941-4222,
CELL 401-439-7547.
CENTRAK EQUIPMENT LOCATION SENSOR-CEILING MOUNTEDCTR
W
CCTV CAMERA - PELCO FIXED ENDUREA SARIX 3MP
CB CODE BLUE BUTTON
NURSE CALL SYSTEM STAFF STATION
PUBLIC ADDRESS VOLUME CONTROL - WALL MOUNTEDV
NURSE CALL SYSTEM DOME LIGHT
(XRE)
F
AIM
AOM
S
FIRE ALARM MANUAL PULL STATION - MOUNTED C/L UP 48"
FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED
FIRE ALARM ADRESSABLE OUTPUT MODULE
FIRE ALARM ADRESSABLE INPUT MODULE
FIRE ALARM STROBE LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED -
15/75 WHERE NOT OTHERWISE INDICATED ON PLANS - WALL MOUNTED
FIRE ALARM SPEAKER/LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED -
15/75 WHERE NOT OTHERWISE INDICATED ON PLANS - WALL MOUNTED
EQUIPMENT TRACKING
SYSTEM NOTES:
1.
1.
WIFI SYSTEM NOTES:
WHERE A DISCREPANCY OCCURS BETWEEN THE
DRAWINGS AND THE SPECIFICATIONS, THE MOST
STRINGENT SHALL PREVAIL. CONTACT THE
ENGINEER FOR CLARIFICATION WHEN SUCH A
SITUATION OCCURS.
CONNECT NEW PUBLIC ADDRESS SPEAKERS TO EXISTING
PUBLIC ADDRESS SYSTEM PRESENTLY SERVING THE
HOSPITAL. CONNECT TO EXISTING SYSTEM WIRING
SERVING SPACE OR AS REQUIRED.
WALL MOUNTED SPEAKER: BOGEN # MB8TSL
CEILING MOUNTED SPEAKER: BOGEN # S86T725PG8U
CEILING SPEAKER W/ VOLUME CONTROL: BOGEN # S86T725PG8UVK
CABLE: HONEYWELL/GENESIS #3123
GFI
LP1#3
ALLOW FOR NUMBER OF OCCUPANCY SENSORS AND SWITCHING SHOWN
ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
HOSPITAL GRADE EMERGENCY DOUBLE DUPLEX CONVENIENCE RECEPTACLE - SEE ARCHITECTURAL
INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, MOUNT AT 18"AFF
MOUNT AT 18"AFF
ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS. IF NOT SHOWN ON ELEVATION, EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - CEILING
EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - WALL
2.
(XN) EXISTING TO BE REPLACED WITH NEW
PROVIDE A NEW CCTV SYSTEM TO SERVE THE
CLEAN CORE SPACE. NEW CCTV SYSTEM SHALL
BE COMPLETE WITH CAMERAS, CABLE, CAMERA
HOUSINGS, SPLITTERS, AND ALL OTHER ACCESSORIES
FOR A COMPLETE AND OPERATIONAL SYSTEM.
PROVIDE NEW CCTV CAMERAS WITH
HOUSING WHERE INDICATED.
ALL NEW CLEAN CORE TELE/DATA OUTLETS SHALL BE CONNECTED
TO NEW AND EXISTING TELE/DATA DISTRIBUTION EQUIPMENT
IN O.R. ADDITION, BASEMENT LEVEL, TELE/DATA RM 12L.
PROVIDE AND INSTALL THE FOLLOWING NEW EQUIPMENT IN EXISTING
O.R. ADDITION TELE/DATA ROOM 12L:
-NEW NETWORK RACK - CHATSWORTH CABLE MANAGEMENT
RACK 19" MODEL - 55053703
-NEW 4 X 48 PORT PATCH PANELS - OR-SP6U48 ORTRONICS CAT 6
PATCH PANEL 24 PORT, 568A, 110 FOR PROPOSED CLEAN CORE
DATA OUTLETS
-NEW 4 X HORIZONTAL CABLE MANAGEMENT - OR-808045030 ORTRONICS
CABLE MANAGEMENT HORIZONTAL FOR NEW PATCH PANELS
PRIOR TO DEMOLISHING DATA CABLING, COORDINATE WITH VAMC I.T.
STAFF TO DETERMINE IF EXISTING CABLING CAN BE REUSED. ALL
CABLING THAT CAN NOT BE REUSED SHALL BE DEMOLISHED BACK TO
I.T. CLOSET AND REMOVED FROM PATCH PANELS.
REFERENCE ELECTRICAL SPECIFICATION SECTION 270513 FOR VAMC
PROVIDENCE RI TELE/DATA CABLING STANDARDS.
COORDINATE DATA CABLE CONNECTION POINTS WITH
VA I.T. STAFF.
THE WIRELESS WIFI SYSTEM EQUIPMENT AND CABLING
MUST BE MAINTAINED AND INTACT. ANY EXISTING
CABLING SHALL NOT BE DEMOLISHED AS PART OF THE
PROJECT. VAMC I.T STAFF WILL TEMPORARILY REMOVE
THE ACCESS POINTS WITHIN THE CONSTRUCTION AREA
PRIOR TO THE CONSTRUCTION START DATE. VAMC
INFORMATION TECHNOLOGY DEPARTMENT SHALL
REINSTALL WIRELESS ACCESS POINT DEVICES IN
NEW LOCATIONS.
ABBREVIATIONS
SP
BS
VISIPLEX WIRELESS SPEAKER MODEL#VNS2214-1 WITH WIRELESS RECEIVER
VISIPLEX MODEL#VS4500 BASE STATION WITH INTEGRAL 6 WATT TRANSMITTER MODEL#VTX-6,
HANDHELD MICROPHONE MODEL#VS3005 AND ANTENNA MODEL#VS638
PP
POWER POLE WITH CRITICAL BRANCH QUAD RECEPTACLE AND (2) DATA OUTLETS
WIREMOLD CATALOG #25DTP-4ACT. PROVIDE DATA ADAPTER PLATES AS REQUIRED
SIMPLEX RECEPTACLE ABOVE DROP CEILING FOR VISIPLEX WIRELESS SPEAKER - CRITICAL POWER
1.
2.
3.
PHASING NOTES:
ALL ELECTRICAL UTILITY OUTAGES AND CUTOVERS
SHALL BE SCHEDULED OFF HOURS AND WEEKENDS.
COORDINATE ALL ELECTRICAL OUTAGES AND CUTOVERS
WITH VAMC. CONTRACTOR SHALL CARRY ALL REQUIRED
OVERTIME COST FOR THIS WORK IN BASE BID.
REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2
FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.
OPERATING ROOM (O.R.) AND POST-ANESTHESIA CARE UNIT
(P.A.C.U) SHALL REMAIN OPEN AND ACCESSIBLE AT ALL TIMES
DURING CONSTRUCTION. ANY WORK DONE IN THESE AREAS
SHALL BE PERFORMED ON OFF HOURS AND WEEKENDS ONLY.
COORDINATE ALL PHASING AND CONSTRUCTION WORK WITH
VA CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R) AND
ARCHITECT. IF WORK REQUIRES A SHUTDOWN AND CAN'T
BE PERFORMED OFF HOURS, WEEKENDS OR FEDERAL HOLIDAYS,
A 28 DAY NOTICE IN ADVANCE MUSST BE SUBMITTED TO THE
PROVIDENCE VA MEDICAL CENTER (P.V.A.M.C.), COR AND ARCHITECT.
2.
c.
d.
PROVIDE NEW WORKSTAION AND
DISPLAY IN NURSE MANAGER OFFICE 253.
PROVIDE NEW NETWORK STORAGE
MANAGER FOR RECORDING.
e.
PROVIDE NEW COMPUTER SWITCH
CONNECTING CAMERA VIDEO SIGNAL
TO THE NETWORK.
f. PROGRAM CAMERAS WITH IP ADDRESSES AND
OTHER PROGRAMMING AS REQUIRED.
g.
PROVIDE NEW CCTV CABLING TO
EXISTING RACK IN FIRE COMMAND CENTER.
INSTALL AND TERMINATE RED CATEGORY 6
CABLES FROM CAMERA TO FIRE COMMAND CENTER.
h. RELOCATE EXISTING CCTV CAMERA WHERE INDICATED.
SHANIX BILL OF MATERAL:
(6) PELCO 3MP SARIX CAMERAS, 3-9MM
(6) PELCO SRX ENH+ INDOOR DOME MOUNT
(1) PELCO SARIX IME SERIES VANDAL RESISTANT MINI DOME
(1) CISCO 1000BASE-LX/LH SFP TANSCEIVER MODULE, MMF/SMF, 1310NM
(1) CISCO CATALYST 3850-24P-S LAYER 3 SWITCH-24 POE PORTS IP
(1) CISCO 715W AC CONFIG 1 SECONDARY POWER SUPPLY
(1) CISCO CATALYST 3850 4 X 1GE NETWORK MODULE
(2) CISCO NORTH AMERICAL AC TYPE A POWER CABLE
(1) CISCO 50CM TYPE 1 STACKING CABLE
(1) CISCO UNIVERSAL POWER SUPPLY
(1) VIEWSONIC 43 FULL HD COMMERCIAL DISPLAY, 1920X1080
(1) CHEIF LARGE HEIGHT ADJUSTABLE TILT WALL MOUNT - 37"-63"
(1) PELCO WORKSTATION W/WS5200 SW
(1) PELCO NETWORK STORAGE MANAGER, 24TB
(1) APC 2200VA RM 2U LCD 120V SMART UPS
g.
PROVIDE NEW ADDRESSABLE OUTPUT
MODULES WHERE INDICATED.
1.
a.
2.
b.
c.
d.
e.
f.
MAKE ALL CONNECTIONS AS REQUIRED.
PROVIDE ALL REQUIRED PROGRAMMING.
REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES
AND LOCATIONS OF WIRELESS PUBLIC ADDRESS
DEVICES.
VISIPLEX WIRELESS
PUBLIC ADDRESS
SYSTEM NOTES
MODIFY THE EXISTING VISIPLEX WIRELESS
PUBLIC ADRESS SYSTEM TO ACCOMMODATE
THE NEW DEVICES INDICATED. PROVIDE ALL
POWER SUPPLIES AND OTHER ACCESSORIES
FOR A COMPLETE AND OPERATIONAL SYSTEM.
PROVIDE NEW BASE STATIONS WITH
HANDSET, INTEGRAL 6 WATT TRANSMITTER
AND ANTENNA WHERE INDICATED.
PROVIDE NEW CEILING MOUNTED
WIRELESS SPEAKERS WITH RECEIVER
AND POWER CORD WHERE INDICATED.
PROVIDE ABOVE CEILING POWER OUTLETS
WHERE INDICATED.
PROVIDE NEC COMPLIANT CLASS 2, 12V DC
POWER SUPPLIES COMPATIBLE WITH SPEAKER
RECEIVER AT EACH SPEAKER LOCATION.
NACP FIRE ALARM NOTIFICATION APPLIANCE CONTROL PANEL (N.A.C. PANEL)
a DIMMER SWITCH - 3 INDICATES 3-WAY - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE -
SUBLETTER INDICATES SWITCH CONTROL
WIRELESS ACCESS POINT (WIFI)
WALL PHONE OUTLET - MOUNTED 5' AFF.
CONTRACTOR SHALL PROVIDE AND INSTALL FIVE
24-PORT PATCH PANELS IN EXISTING RACK IN EXISTING
O.R. ADDITION TELE/DATA ROOM 12L. pATCH PANELS
SHALL BE ORTRONICS CATALOG #PHD66U24.
CONTRACTOR SHALL PROVIDE, INSTALL AND TERMINATE
(1) CAT 6 CABLE FROM WIRELESS ACCESS POINT TO
PATCH PANEL IN O.R. ADDITION, BASEMENT LEVEL,
TELE/DATA RM 12L. PROVIDE AND INSTALL (1) BISCUIT
JACK IN CEIILING AT EACH WIRELESS ACCESS POINT.
CAT 6 CABLE SHALL BE CERTIFIED BY CONTRACTOR.
COORDINATE EXACT MOUNTING REQUIREMENTS WITH
VAMC I.T. STAFF. VAMC WILL PROVIDE WIRELESS
ACCESS POINTS.
MODIFY THE EXISTING NOTIFIER NFS2-3030 MAIN FIRE
ALARM CONTROL PANEL TO ACCOMMODATE THE NEW
DEVICES INDICATED. NEW CONTACTS, NOTIFICATION
APPLIANCE CIRCUIT POWER SUPPLY CABINETS AND ALL
OTHER ACCESSORIES FOR A COMPLETE AND
OPERATIONAL SYSTEM.
4.
ALL FIRE ALARM DEVICES SHALL BE PURCHASED FROM
FSI, FIRE SYSTEMS INC.. CONTACT PAULA CASEY. PHONE
NUMBER (508) 999-4444 EXT. 204.
ALL WORK ON THE NEW AND EXISTING FIRE ALARM
SYSTEM SHALL BE DONE BY WYMAN & SONS ELECTRIC.
CONTACT DAVID WYMAN (401) 737-0032. THIS
CONTRACTOR SHALL CONTRACT WITH WYMAN &
SONS ELECTRIC FOR ALL REQUIRED FIRE ALARM
SYSTEM WORK.
NO NEW CENTRAK DEVICES SHALL BE INSTALLED AS PART
OF THIS PROJECT.
EXISTING CENTRAK TRACKING EQUIPMENT INDICATED TO
REMAIN SHALL BE MAINTAINED AND KEPT INTACT. ALL
EXISTING CENTRAK EQUIPMENT CABLING SHALL NOT BE
DEMOLISHED AS PART OF THIS PROJECT. ALL CENTRAK
DEVICES INDICATED TO BE DEMOLISHED SHALL BE REMOVED
BY VAMC CLINICAL ENGINEERING DEPARTMENT PRIOR TO
DEMOLITION. COORDINATE DEMOLITION SCHEDULE WITH
VAMC CLINICAL ENGINEERING DEPARTMENT AS REQUIRED.
EXISTING CENTRAK CABLING SHALL BE TAGGED/
MARKED AND PROTECTED DURING DEMOLITION AND
CONTRUCTION OF CLEAN CORE SCOPE OF WORK.
COORDINATE CENTRAK CABLE MARKING/TAGGING AND
PROTECTION WITH VAMC CLINICAL ENGIEERING DEPARTMENT
AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E00.1
JWT APG
AND NOTES
ELECTRICAL LEGEND
LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION
ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. MTG. VOLT
NO. WATT
LAMPS
TYPE
REMARKS/BALLAST INFORMATION
LEDUNVR
A
LED
LEDUNVF
K
32.2LEDUNVR
B1
12.5LEDUNVS
F
LED LITHONIA
1LED120/277R
E
TLE-2-RLITHONIA
LED PROVIDE FACES AND CHEVRONS AS INDICATEDTLE-1-RLITHONIA
RECESSED MOUNT SINGLE OR DOUBLE FACED LED EXIT SIGN
24.9LEDUNVF
150LED120R
C
LED120R
D
KENALL
2'x2' LED RECESSED OPERATING ROOM LIGHT FIXTURE
KENALL M4SEDI-22-76LL-40K8-DCC-120-2F-2H-SYM
LITHONIA
LITHONIA
LITHONIA
LITHONIA
LITHONIA
28LEDF
G LED
M4DL4-DCFW-28L-40K9-FW-RIS4-120-DIM1
L
150LED120R
C1
LED KENALL
2'x4' LED RECESSED OPERATING ROOM LIGHT FIXTURE WITH EMERGENCY BATTERY PACK
24.9LEDUNVF
LED LITHONIAL1
M4SEDI-24-150L-40K8-DCC-120-2F-2H-SYM-2C
M4SEDI-24-150L-40K8-DCC-120-2F-2H-SYM-2C-LEL
2'x4' LED RECESSED OPERATING ROOM LIGHT FIXTURE, 2-CIRCUIT
K1
LEDR
H LED
6" LED DOWNLIGHT
18.5
EVO-40-15-6AR-LSS-PPC-MVOLT-GZ10GOTHAM
GRADE
TAPE 12" BELOW GRADE
PLASTIC "ELECTRIC" MARKER
CONCRETE ENCASEMENT
A B
TYPICAL DUCTBANK CONSTRUCTION
SCALE: NO SCALE
DUCTBANK SECTION
SCALE: NO SCALE
* CABLE AMPACITIES ARE BASED ON A MAXIMUM BURIAL DEPTH OF 30" UNLESS
OTHERWISE INDICATED, EXCEPT THAT 25% OF THE LENGTH MAY BE DEEPER TO AVOID
OBSTRUCTIONS OR ENTER A STRUCTURE. ELECTRICAL CONTRACTOR SHALL CONSTRUCT
DUCTBANK TO MEET THESE CONDITIONS. WHERE CONDITIONS DO NOT ALLOW, ELECTRICAL
CONTRACTOR SHALL DE-RATE CONDUCTORS FOR DEEPER BURIAL DEPTHS PER NEC.
BURIAL DEPTHS
MINIMUM - PER NEC TABLE 300.50
MAXIMUM - 30 INCHES (SEE BELOW)
CSP
P P
REF:
A2
LIGHT FIXTURE SCHEDULE DETAILS
LEGEND:
SP - 4" SPARE CONDUIT
P - 4" POWER CONDUIT
C - 4" COMMUNICATION CONDUIT - GENERATOR START AND ANNUNCIATOR CIRCUITING
CONCRETE ENCASED
P P
P P
E00.2 E00.2
LEDC
J LED
LITHONIA
1'x4' LED INDUSTRIAL STRIP LIGHT WITH LENS - CHAIN HUNG
ZL1N-L48-3000LM-FST-MVOLT-40K-80CRI-WH-HC36
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
4000K COLOR TEMPERATURE
2'x2' LED RECESSED LIGHT FIXTURE - FLANGE MOUNT
2'x2' LED RECESSED LIGHT FIXTURE WITH BATTERY PACK- FLANGE MOUNT
2'x4' LED RECESSED LIGHT FIXTURE - FLANGE MOUNT
SAME AS TYPE A2 EXCEPT WITH EMERGENCY BATTERY PACK - FLANGE MOUNT
2'x2' LED RECESSED LIGHT FIXTURE WITH BATTERY PACK
32.2LEDUNVR
B
2'x2' LED RECESSED LIGHT FIXTURE
2TL2-33L-FW-A12-EZ1-LP840-ABC GASKET-DGA22
2TL2-33L-FW-A12-EZ1-LP840-EL14L-ABC GASKET-DGA22
LEDUNVR
A2
SURGICAL LED DOWNLIGHT - FLANGE MOUNT
2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE
2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE - FLANGE MOUNT
2'x4' LED RECESSED FLAT PANEL LIGHT FIXTURE
EPANL-2X4-4000LM-80CRI-40K-MIN10-2T-MVOLT- DGA24
EPANL-2X2-3400LM-80CRI-35K-MIN10-2T-MVOLT- E10WCP
UCLD-24IN-40K-90CRI-WH-UCD JB-UC PIR M12
UNDER-CABINET LIGHT FIXTURE WITH MOTION SENSOR SWITCHING
EPANL-2X4-4000LM-80CRI-40K-MIN10-2T-MVOLT
EPANL-2X4-4000LM-80CRI-35K-MIN10-2T-MVOLT
EPANL-2X2-3400LM-80CRI-35K-MIN10-2T-MVOLT
2TL4-60L-FW-A12-EZ1-LP840-EL14L-ABC GASKET-DGA24
2TL4-60L-FW-A12-EZ1-LP840-ABC GASKET - DGA24
KENALL
4000K COLOR TEMPERATURE
CONTRACTOR TO PROVIDE NEOPRENE
GASKETING BETWEEN FIXTURE AND CEILING
GASKETING BETWEEN FIXTURE AND CEILING
CONTRACTOR TO PROVIDE NEOPRENE
4000K COLOR TEMPERATURE
GASKETING BETWEEN FIXTURE AND CEILING
CONTRACTOR TO PROVIDE NEOPRENE
3500K COLOR TEMPERATURE
GASKETING BETWEEN FIXTURE AND CEILING
CONTRACTOR TO PROVIDE NEOPRENE
3500K COLOR TEMPERATURE
GASKETING BETWEEN FIXTURE AND CEILING
CONTRACTOR TO PROVIDE NEOPRENE
3500K COLOR TEMPERATURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E00.2
JWT APG
FIXTURE SCHEDULE AND DETAILS
ELECTRICAL LIGHTING
DP-N-OR
EQ-2-OR
LS-2-OR
CB-2A-OR
DP-CB-OR-2
DP-CB-OR-1
CB-2B-OR
C R
W
C T R
OC OC
WP
G F I
G F I
G F I
G F I
OC
CTR
CTR
CTR
CTR
CTR
OC OC
J
POWERED FURNITURE
OC
W
OC
G F I
GFI
GFI
C T R
C T R
C T R
C T R
R E X
OC
S
S
V
J
DOOR
C T
R
OC
S
J
DOOR
R E X
MGAP
C T R
IPU-E-CYSTO
C B
C R
C T R
C T R
ENCLOSED BREAKER
J
SINK
CEILING MTD.
J
TIMER
TIMER RESET STATION
EQUIPMENT WHIP CONNECTIONS
NURSE CALL C.P.
(XRE)(XRE)(XRE) (XRE)
LEGEND:
EXISTING EQUIPMENT TO BE DEMOLISHED IS INDICATED AS BOLD AND DASHED:
EXISTING EQUIPMENT TO REMAIN IS INDICATED AS LIGHT AND DASHED:
EXISTING EQUIPMENT TO BE BE MODIFIED IS INDICATED AS BOLD AND DASHED WITH TEXT ADJACENT:
(XRE)
(XRE)
(XRE)DEMOLITION NOTES:
VISIPLEX BASE STATION
N-L-2-OR
S
S
S
S
(XRE)
(XRE)
S
OC
S
SECURITY SYSTEM CONTROL PANEL
BSSP
(XRE)
C R
BOOM WITH POWER, AND DATA OUTLETS
J
DOOR
CTR
F
W
S
REX
CTR
J
DOOR
S
W
PHASE 2A
DEMOLISH EXISTING ELECTRICAL DEVICES IN THIS AREA UNDER PHASE 2B
REFER TO ARCHITECTURAL DRAWINGS FOR TEMPORARY WALL LOCATIONS
TEMPORARY WALLS TO BE CONSTRUCTED DURING PHASE 2A
ELECTRICAL DEVICES IN THIS AREA TO REMAIN IN PLACE DURING PHASE 2A
1. ELECTRICAL INDICATED IS AS GENERALLY FOUND (APRIL
2017). THE INTENT OF THE EXISTING CONDITIONS PLAN(S) IS TO
DOCUMENT EXISTING CONDITIONS. HOWEVER, ALL ELECTRICAL
DEVICES MAY NOT NECESSARILY BE INDICATED ON THE
DRAWINGS. FIELD VERIFY AND ADJUST WORK TO SUIT ALL FOUND.
2. REFER TO THIS EXISTING CONDITION PLAN AND LIGHTING
POWER, AND SIGNAL PLAN TO DETERMINE EXTENT OF WORK
IN EACH AREA, INCLUDING WHETHER DEVICES ARE TO REMAIN,
BE REMOVED, REPLACED, ETC... EXCEPT AS NOTED, GENERALLY
THE INTENT IS THAT IF EXISTING DEVICES ARE SHOWN ON THE EXISTING
CONDITIONS PLANS AND NEW DEVICES ARE SHOWN ON THE FLOOR
PLANS THEN EXISTING DEVICES ARE TO BE REMOVED. IF EXISTING
DEVICES ARE SHOWN ON BOTH THEN DEVICES ARE TO REMAIN.
3. ALL EXISTING ITEMS INTENDED FOR REMOVAL SHALL BE REMOVED
WITH ALL ASSOCIATED HARDWARE INCLUDING, BUT NOT LIMITED TO:
CONDUIT, BOXES, WIRING, CABLES, HANGERS, ETC...
4. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR
MECHANICAL AND PLUMBING EQUIPMENT TO BE REMOVED. REMOVE
ALL ASSOCIATED CONDUIT, BOXES, WIRING, ETC...
5. CONDUIT IN GOOD CONDITION AND PROPERLY LOCATED MAY BE
REUSED WHERE APPLICABLE, UNLESS NOTED OTHERWISE.
6. IN AREAS NOT RENOVATED BY THIS CONTRACT VERIFY THAT
ELECTRICAL POWER, LIGHTING AND SYSTEMS ARE NOT AFFECTED
BY THE ALTERATIONS. PROVIDE ALL WORK AS REQUIRED TO
MAINTAIN POWER AND PROPER OPERATION OF SYSTEMS.
7. EXISTING CENTRAK TRACKING EQUIPMENT INDICATED TO
REMAIN SHALL BE MAINTAINED AND KEPT INTACT. ALL
EXISTING CENTRAK EQUIPMENT CABLING SHALL NOT BE
DEMOLISHED AS PART OF THIS PROJECT. ALL CENTRAK
DEVICES INDICATED TO BE DEMOLISHED SHALL BE REMOVED
BY VAMC CLINICAL ENGINEERING DEPARTMENT PRIOR TO
DEMOLITION. COORDINATE DEMOLITION SCHEDULE WITH
VAMC CLINICAL ENGINEERING DEPARTMENT AS REQUIRED.
EXISTING CENTRAK CABLING SHALL BE TAGGED/
MARKED AND PROTECTED DURING DEMOLITION AND
CONTRUCTION OF CLEAN CORE SCOPE OF WORK.
COORDINATE CENTRAK CABLE MARKING/TAGGING AND
PROTECTION WITH VAMC CLINICAL ENGIEERING DEPARTMENT
AS REQUIRED.
8. WIRELESS ACCESS POINT DEVICES SHALL BE REMOVED AND STORED BY VAMC INFORMATION
TECHNOLOGY DEPARTMENT. CLEAN CORE RENOVATION PROJECT SHALL PROVIDE AND INSTALL
NEW CAT 6 CABLING TO ALL NEW WIRELESS ACCESS POINT EQUIPMENT LOCATIONS. VAMC INFORMATION
TECHNOLOGY DEPARTMENT SHALL INSTALL WIRELESS ACCESS POINT DEVICES IN NEW LOCATIONS.
9. PRIOR TO DEMOLISHING DATA CABLING, COORDINATE WITH VAMC I.T. STAFF TO DETERMINE IF
EXISTING CABLING CAN BE REUSED. ALL CABLING THAT CAN NOT BE REUSED SHALL BE DEMOLISHED
BACK TO I.T. CLOSET AND REMOVEDFROM PATCH PANELS. ALL NEW CABLING SHALL MEET REQUIREMENTS
OF ELECTRICAL SPECIFICATION SECTION 270513, VAMC PROVIDENCE RI TELE/DATA CABLING STANDARDS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E05.1
APGJWT
EXISTING CONDITIONS
SECOND FLOOR PART PLAN
1/8" = 1'-0"
0 4' 8' 12'
0.5
1.8 2.2 2.5 3 4 5 6 7
G.4'
E4.8
E5
ED
A.5
A.5'
A
3'
B
C.3
D.3
C.5
B' C' D' E' F'
F
F.7' G'
H
D
E E.1
E4
G.3'
4.8'
C
G.5'
4.75'
4.7'
4.5'
4' 4'
4.3' 4.3'
L
EA.1
K
J
EBB
G
F.9
2'
A.6'
1'
252632
52 53
SEE A72.4 FOR EQUIPMENT SCHEDULE.
18 15 28 27 45 16
5'
CLEAN AND STERILE
SUPPLY
EQUIPMENT STORAGE
MECHANICAL
CYSTOSCOPY
SEMI RESTRICTED
CORRIDOR
CLEAN CORE
FUTURE CLEAN EL.
A-EL-3
FUTURE CLEAN EL.
A-EL-2
CLEAN AND STERILE
SUPPLY
CC STORAGE
255A
NURSE MANAGER
OFFICE
ELEC. CL.
SOILED UTILITY
IUSS
ANESTHESIA
WORKROOM
EQUIPMENT STORAGE
WORK AREA
CONTROL STATION
MALE LOCKERS
ANGIOPLASTY
OR-1
OR-2
OR-3
HOUSE KEEPING
215G
FEMALE LOCKERS
CONSULT ROOM
TOILET
202A
MINOR PROCEDURE
OR STORAGE
PATIENT TOILET
215F
PATIENT LOCKERS
215E
VESTIBULE
215D
CLEAN UTILITIES
215C
SOILED UTILITIES
215B
SEMI RESTRICTED
CORRIDOR
STAIR WELL
A-2
ELECTRICAL CLOSET
HOUSE KEEPING
232A
ELEC
232C
ELEC
232D
INTERVENTIONAL PAIN
MANAGEMENT
233A
ELECTRICAL ROOM
201C
EMERGENCY
ELECTRICAL ROOM
201B
ELEVATOR LOBBY
L23
LINEN CHUTE
IT CLOSET
229A
ELECTRICAL CLOSET
CORRIDOR
2-DC-1A
SEMI RESTRICTED
CORRIDOR
EXAM-1
E205
EXAM-2
E206
OFFICE
CORRIDOR
BRONCHOSCOPY
Room
4ZZ
Room
4AAA
Room
4BBB
Room
4CCC
Room
4DDD
SCRUB
210A
SCRUB
210B
OR ACCESS VESTIBULE
OR ACCESS VESTIBULE
OBSERVATION ROOM
PACU
NURSE STATION
PATIENT TOILET
215A
CORRIDOR
C223
STAIR-K
K-2
STAFF TOILET/SHOWER
SEMI RESTRICTED
CORRIDOR
LINK CORRIDOR
L24
MICROSCOPE
E207
EXAM-3
E208
CAST ROOM
E204
CORRIDOR
C22
ELEVATOR LOBBY
L21
CORRIDOR
C21
LOBBY
L22
ELEVATOR
E-EL-2
ELEVATOR
E-EL-1
OR RECEPTION
WAITING ROOM
OFFICE
201A
FUTURE SOILED
ELEVATOR
A-EL-1
DP-N-OR
EQ-2-OR
LS-2-OR
CB-2A-OR
DP-CB-OR-2
DP-CB-OR-1
CB-2B-OR
OC OC
OC
OC
OC
N-L-2-OR
OC
A
3'
2'
MALE LOCKERS
CORRIDOR
C223
SEE DRAWING E40.1 FOR
1/4" SCALE CYSTOSCOPY
PART PLAN
K1
K
K1
K
L1
G
G
G
G a b a a b a
A
A
A
A AL1 L1 L1
J
OC
B
A
A
A1 A1A1A1A1A1A1
A2
A2
OC
A
A
OC
OC
A
OC
A1
A1
A1
OCOC
OCOC
OC
A1 A1A1 A1
A1
A1
A1
A1
A1
OC
OC
A1A1
OC
F
A1 A1
OC
A
A
OC
OC
A
A
A
OC
OC
B
A2 A2
A2
A
OC
(EN)
OC
(EN)
E E
E
E
E
E
E
E
E
E
E
E
E
E
21 21 21 21
NLNL
NL
NLNL
NL
NL
NL
NL
NL
NL
NL
E
E
LS-2-OR#21
L01 PROVIDE AND INSTALL (1) 20A, 1-POLE BREAKER IN EXISTING SPACE 21.
NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING AIC RATING.
L01
1 1
1 1
21 1 21 1
1 21 21
4 4 4
OC
OC
OC
OC A
A
A
A2
A2
B1
A1
A1 A1A1
A
21NL
1 ab a a a bb b
L
L02 RECIRCUIT EXISTING LIGHT FIXTURE TO BE CONTROLLED ONLY BY EXISTING OCCUPANCY SENSOR.
L02 L02
NL
B1 B1
B1B1B1
N-2-CC#3
N-2-CC
L03 CIRCUIT LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT SERVING THE CORRIDOR.
L03 L03
OC
N-2-CC#3
CB-2-CC#2
b b b a a a
CB-2-CC#4
OC
B1 B1
B1B1
B1B1
4 4
PHASE 5
PHASE 7
DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.L04
L04
H H
(UNISTRUT MOUNTED)
CB-2-CC
PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2
FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.
J J J
JJJJ
F
F
F
F a aac c c a a a b b bb b b d c c d d d d c c
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E10.1
APGJWT
LIGHTING
SECOND FLOOR PART PLAN
1.8 2.2 2.5 3 4 5 6 7
G.4'
E4.8
E5
ED
A.5
A.5'
A
3'
B
C.3
D.3
C.5
B' C' D' E' F'
F
F.7' G'
H
D
E E.1
E4
G.3'
4.8'
C
G.5'
4.75'
4.7'
4.5'
4' 4'
4.3' 4.3'
L
EA.1
K
J
EBB
G
F.9
2'
A.6'
1'
5'
CLEAN AND STERILE
SUPPLY
EQUIPMENT STORAGE
MECHANICAL
CYSTOSCOPY
SEMI RESTRICTED
CORRIDOR
CLEAN CORE
FUTURE CLEAN EL.
A-EL-3
FUTURE CLEAN EL.
A-EL-2
CLEAN AND STERILE
SUPPLY
CC STORAGE
255A
NURSE MANAGER
OFFICE
ELEC. CL.
SOILED UTILITY
IUSS
ANESTHESIA
WORKROOM
EQUIPMENT STORAGE
WORK AREA
CONTROL STATION
MALE LOCKERS
ANGIOPLASTY
OR-1
OR-2
OR-3
HOUSE KEEPING
215G
FEMALE LOCKERS
CONSULT ROOM
TOILET
202A
MINOR PROCEDURE
OR STORAGE
PATIENT TOILET
215F
PATIENT LOCKERS
215E
VESTIBULE
215D
CLEAN UTILITIES
215C
SOILED UTILITIES
215B
SEMI RESTRICTED
CORRIDOR
STAIR WELL
A-2
ELECTRICAL CLOSET
HOUSE KEEPING
232A
ELEC
232C
ELEC
232D
INTERVENTIONAL PAIN
MANAGEMENT
233A
ELECTRICAL ROOM
201C
EMERGENCY
ELECTRICAL ROOM
201B
ELEVATOR LOBBY
L23
LINEN CHUTE
IT CLOSET
229A
ELECTRICAL CLOSET
CORRIDOR
2-DC-1A
SEMI RESTRICTED
CORRIDOR
EXAM-1
E205
EXAM-2
E206
OFFICE
CORRIDOR
BRONCHOSCOPY
Room
4ZZ
Room
4AAA
Room
4BBB
Room
4CCC
Room
4DDD
SCRUB
210A
SCRUB
210B
OR ACCESS VESTIBULE
OR ACCESS VESTIBULE
OBSERVATION ROOM
PACU
NURSE STATION
PATIENT TOILET
215A
CORRIDOR
C223
STAIR-K
K-2
STAFF TOILET/SHOWER
SEMI RESTRICTED
CORRIDOR
LINK CORRIDOR
L24
MICROSCOPE
E207
EXAM-3
E208
CAST ROOM
E204
CORRIDOR
C22
ELEVATOR LOBBY
L21
CORRIDOR
C21
LOBBY
L22
ELEVATOR
E-EL-2
ELEVATOR
E-EL-1
OR RECEPTION
WAITING ROOM
OFFICE
201A
FUTURE SOILED
ELEVATOR
A-EL-1
DP-N-OR
EQ-2-OR
LS-2-OR
CB-2A-OR
DP-CB-OR-2
DP-CB-OR-1
CB-2B-OR
G F I
G F I
G F I
G F I
J
DOOR
N-L-2-OR
J
DOOR
J
DOOR
PHASE 2A
DEMOLISH EXISTING ELECTRICAL DEVICES IN THIS AREA UNDER PHASE 2B
REFER TO ARCHITECTURAL DRAWINGS FOR TEMPORARY WALL LOCATIONS
TEMPORARY WALLS TO BE CONSTRUCTED DURING PHASE 2A
ELECTRICAL DEVICES IN THIS AREA TO REMAIN IN PLACE DURING PHASE 2A
MALE LOCKERS
SEE DRAWING E40.1 FOR
1/4" SCALE CYSTOSCOPY
PART PLAN
(EN)
(EN)
(EN)
(EN)
J
MGAP
G F
ISINK
SINK
SINK
SINK
G
F I
W
J
J
P01
P01
J JRCPTS.
GROUNDING LOOP.
TO LIGHTING PROTECTION SYSTEM
FROM BOTTOM OF STRUCTURAL COLUMN
PROVIDE LIGHTNING PROTECTION SYSTEM
GROUND ROD
GROUND RODGROUND ROD
GROUND ROD
GROUND ROD
GROUNDING LOOP.
TO LIGHTING PROTECTION SYSTEM
FROM BOTTOM OF STRUCTURAL COLUMN
PROVIDE LIGHTNING PROTECTION SYSTEM
GROUNDING LOOP.
TO LIGHTING PROTECTION SYSTEM
FROM BOTTOM OF STRUCTURAL COLUMN
PROVIDE LIGHTNING PROTECTION SYSTEM
SYSTEM GROUNDING LOOP.
TO LIGHTING PROTECTION
STRUCTURAL COLUMN
FROM BOTTOM OF
PROTECTION SYSTEM
PROVIDE LIGHTNING
SYSTEM GROUNDING LOOP.
TO LIGHTING PROTECTION
STRUCTURAL COLUMN
FROM BOTTOM OF
PROTECTION SYSTEM
PROVIDE LIGHTNING
BUILDING ADDITION.
SYSTEM GROUNDING LOOP AROUND
EXTEND EXISTING LIGHTNING PROTECTION
CONDUCTOR SIZE AND MATERIAL
SHALL MATCH EXISTING GROUND LOOP
NEW GROUND LOOP CONDUCTOR
PROTECTION SYSTEM GROUNDING LOOP.
CONNECT TO EXISTING LIGHTNING
PROTECTION SYSTEM GROUNDING LOOP.
CONNECT TO EXISTING LIGHTNING
G F I
GFI
G F I
J
DOOR
J
DOOR
J
DOOR
IPU-N-CYSTO
NEW PANEL
IPU-E-CYSTO1
NEW PANEL CRASH CART
P03
P03
LS-2-OR#23
LS-2-OR#25
LIGHTS
P02 CIRCUIT TO NORMAL LIGHTING CIRCUIT SERVING THE ROOM.
P02
TEMPORARY LIGHTNING PROTECTION SYSTEM GROUND ROD DURING CONSTRUCTION.
EXTEND EXISTING DOWN CONDUCTORS FROM WING A AND O.R. ADDITION AS REQUIRED.
P04
P05
P04 P04
IPU-E-CYSTO2
NEW PANEL
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
MGAP
J
FREEZER
SPEAKER
SPEAKER SPEAKER
P06 PROVIDE CONNECTION TO EXISTING PEGASYS SYSTEM FOR TEMPERATURE ALARM.
P06
J
DOOR
J
DOOR
PP
PP
PP
PP
PP
SPEAKER
1 1 1
3 3 3
CB-2-CC#1
CB-2-CC#3
N-2-CC#2
PHASE 7
PHASE 5N-2-CC#2
CB-2-CC#1
CB-2-CC#3
P07 DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.
P07
CB-2-CC#5
N-2-CC#5
7 7 7 79 9 9 911 13 11 13 11 13 11 13 7
N-2-CC#9
N-2-CC#7
N-2-CC#13
N-2-CC#11
N-2-CC#15
N-2-CC#4
N-2-CC#6
N-2-CC#8
N-2-CC#10
STERILIZER
12 N-2-CC#12
G F I
CB-2-CC#7
N-2-CC
G F I
G F I
CB-2-CC#9
CB-2-CC#13
CB-2-CC#15
CB-2-CC#17
PUMP
PUMP
G F I
J
CB-2-CC#18
N-2-CC#19
CB-2-CC#16
CB-2-CC#14
CB-2-CC#6,8
CB-2-CC#10,12
N-2-CC#23,25
N-2-CC#21
LS-2-OR#27
P08
P09
MONITOR BOOM WITH (2) VIDEO MONITORS, (2) VIDEO OUTLETS AND (2) DUPLEX OUTLETS.
P08
P09
11 11
11 CB-2-CC#11
11 11
N-2-CC#14
N-2-CC#16
N-2-CC#18
(UNISTRUT MOUNTED)
CB-2-CC
PROVIDE AND INSTALL (3) 20A, 1-POLE BREAKERS IN EXISTING SPACE 23,25 FOR MOTORIZED DOORS AND 27 FOR (2) MGAP.
NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING AIC RATING.
PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2
FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.
G F I
G F I
G F I 9
G F I
DP1-EQ-CC#13,15,17 DP1-EQ-CC#7,9,11
REFER TO RISER DIAGRAM ON DRAWING E50.1 FOR FEEDER SIZE.
7.5 5
7.5 5
J
J
J
J
J
J
J
N-2-CC#24
SMOKE DAMPER
SMOKE DAMPER
SMOKE DAMPER
UTILITY BOOM WITH (2) CRITICAL QUAD OUTLETS, (2) NORMAL QUAD OUTLETS AND (2) DATA QUAD OUTLETS.
ALL POWER OUTLETS IN EQUIPMENT STORAGE ROOM 254 SHALL BE MOUNTED AT 36" AFF.
P05
P05
P10 MOUNT POWER OUTLET AT 30" AFF.
P10
P11 MOUNT POWER OUTLET AT 6" ABOVE COUNTER HEIGHT.
P10 P10 P10 P10 P10 P10 P10 P10
P11
P11
P11
P12 MOUNT POWER OUTLET AND DATA OUTLET AT AT 4'-6" AFF..
P12
P12
P12
P10
P10P10P10P10P10P10P10
N-2-CC#2424
SINK
SINK
AIR HANDLER 12B001
J
NAC PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E20.1
APGJWT
POWER
SECOND FLOOR PART PLAN
1.5
1.5
1.8 2.2 4 5 6 7 8
G.4'
E4.8
E5
ED
EB.3
A.5
A
3'
B
C.3
D.3
C.5
B' C' D' E' F'
F
F.7' G'
H
D
E
E.1
G.3'
4.8'
C
G.5'
4.75'
4.75'
4.7' 4.7'
4.5'
4.5'
4'
4'
4.3'
L
EA.1
K
J
EBB
G
F.9
2'
A.6'
1'
5'
N
LIGHTINING PROTECTION SYSTEM PRESENTLY INSTALLED ON THE O.R. ADDITION
CONNECT NEW LIGHTNING PROTECTION SYSTEM AIR TERMINALS TO EXISTING
W P
G F I
B-EQ-CC#13
N-2-CC#20
J
2#10+1#10G
IN 3/4"C
EF-13B001
EXHAUST FAN
BRONCOSCOPY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E20.2
APGJWT
POWER
ROOF PART PLAN
1.8 2.2 2.5 3 4 5 6 7
G.4'
E4.8
E5
ED
A.5
A.5'
A.5'
A
3'
B
A' A.2'
C.3
D.3
C.5
B' C' D' E' F'
F
F.7' G'
H
D
E E.1
E4
G.3'
4.8'
C
G.5'
4.75'
4.7'
4.5'
4' 4'
4.3' 4.3'
L
EA.1
J
EBB
G
F.9
2'
A.6'
1'
252632
52 53
SEE A72.4 FOR EQUIPMENT SCHEDULE.
18 15 28 27 45 16
5'
CLEAN AND STERILE
SUPPLY
EQUIPMENT STORAGE
MECHANICAL
CYSTOSCOPY
SEMI RESTRICTED
CORRIDOR
CLEAN CORE
FUTURE CLEAN EL.
A-EL-3
FUTURE CLEAN EL.
A-EL-2
CLEAN AND STERILE
SUPPLY
CC STORAGE
255A
NURSE MANAGER
OFFICE
ELEC. CL.
SOILED UTILITY
IUSS
ANESTHESIA
WORKROOM
EQUIPMENT STORAGE
WORK AREA
CONTROL STATION
MALE LOCKERS
ANGIOPLASTY
OR-1
OR-2
OR-3
HOUSE KEEPING
215G
FEMALE LOCKERS
CONSULT ROOM
TOILET
202A
MINOR PROCEDURE
OR STORAGE
PATIENT TOILET
215F
PATIENT LOCKERS
215E
VESTIBULE
215D
CLEAN UTILITIES
215C
SOILED UTILITIES
215B
SEMI RESTRICTED
CORRIDOR
STAIR WELL
A-2
ELECTRICAL CLOSET
HOUSE KEEPING
232A
ELEC
232C
ELEC
232D
INTERVENTIONAL PAIN
MANAGEMENT
233A
ELECTRICAL ROOM
201C
EMERGENCY
ELECTRICAL ROOM
201B
ELEVATOR LOBBY
L23
LINEN CHUTE
IT CLOSET
229A
ELECTRICAL CLOSET
CORRIDOR
2-DC-1A
SEMI RESTRICTED
CORRIDOR
EXAM-1
E205
EXAM-2
E206
OFFICE
CORRIDOR
BRONCHOSCOPY
Room
4ZZ
Room
4AAA
Room
4BBB
Room
4CCC
Room
4DDD
SCRUB
210A
SCRUB
210B
OR ACCESS VESTIBULE
OR ACCESS VESTIBULE
OBSERVATION ROOM
PACU
NURSE STATION
PATIENT TOILET
215A
CORRIDOR
C223
STAIR-K
K-2
STAFF TOILET/SHOWER
SEMI RESTRICTED
CORRIDOR
LINK CORRIDOR
L24
MICROSCOPE
E207
EXAM-3
E208
CAST ROOM
E204
CORRIDOR
C22
ELEVATOR LOBBY
L21
CORRIDOR
C21
LOBBY
L22
ELEVATOR
E-EL-2
ELEVATOR
E-EL-1
OR RECEPTION
WAITING ROOM
OFFICE
201A
FUTURE SOILED
ELEVATOR
A-EL-1
DP-N-OR
EQ-2-OR
LS-2-OR
CB-2A-OR
DP-CB-OR-2
DP-CB-OR-1
CB-2B-OR
C R
W
C T R
CTR
CTR
CTR
CTR
W
C T
R
S
NURSE CALL C.P.
VISIPLEX BASE STATION
N-L-2-OR
S
S
S
S
S
S
SECURITY SYSTEM CONTROL PANEL
BS
CTR
F
W
S
REX
CTR
S
W
A
B
B
A
M D O
FFIC
E
O
FFIC
E
TO
ILET
M
EN
S
TO
ILET
W O
M
EN
S C O N
FER
EN
C E
A
Z
R
EC
EP
TIO
N
A D
M
IN
IS
TR
A
TO
R
S
EC
R
ETA
R Y
C H
IEF
C O R R
ID
O R
ELEV
A
TO
R
LO
B B Y
L-
P
P
P
S
A
A
TC
A
B R
EA
K R
O O
M
C
H
F
G
FILE R
O O
M
O
FFIC
E
LA
B
B
LO
O D
A R
TER
IA
L
ELEV
A
TO
R
L-
C
C H A S E
R
EC
P T
P H A R
M A C Y
ELEV
A
TO
R
TC
1L
TELEP
H O N E
C
LO
S
ET
ELEV
A
TO
R
C
LO
S
ET
C
LO
S
ET
D W 1C
W A
ITER
P H A R
M A C Y
C L2
C H A S E
C 1L
C H A S E
C B
C H A S E
R O O
M
P A S S
EN
G
ER
S
TA
IR
ELEC
TR
IC
A L
FU
TU
R E
P H A R
M A C Y
O
FFIC
E
IN
P A
TIEN
T
P H A R
M A C Y
IN
P A
TIEN
T
P H A R
M A C Y
IN
P A
TIEN
T
D U
M B
C O
M M U N
IC
A
TIO
N
S
ER
V
IC
E
ELEC
TR
IC
A L
P A S S
EN
G
ER
ELEV
A
TO
R
P A S S
EN
G
ER TO
ILET
TO
ILET
R O O
M
ELEC
TR
IC
A L
FU
TU
R E
MALE LOCKERS
CORRIDOR
C223
SEE DRAWING E40.1 FOR
1/4" SCALE CYSTOSCOPY
PART PLAN
C B
SSSSS
S
S
S
SS
W
S
S
S
S
V
S
CLEAN CORE AIR HANDLER
S
15cd
15cd 15cd
S
15cd
15cd
S
15cd
15cd
S
15cd
S
15cd
S
15cd
15cd
S
15cd
(EN)
WP
S
15cd
S
S
S
15cd
15cd
15cd
S
15cd
15cd
S
15cd
15cd
1.
WIFI SYSTEM NOTES:
THE WIRELESS WIFI SYSTEM EQUIPMENT AND CABLING
MUST BE MAINTAINED AND INTACT. ANY EXISTING
CABLING SHALL NOT BE DEMOLISHED AS PART OF THE
PROJECT. VAMC I.T STAFF WILL TEMPORARILY REMOVE
THE ACCESS POINTS WITHIN THE CONSTRUCTION AREA
PRIOR TO THE CONSTRUCTION START DATE.
EQUIPMENT TRACKING
SYSTEM NOTES:
1. THE EXISTING CEILING MOUNTED CENTRAK EQUIPMENT
TRACKING EQUIPMENT SYSTEM DEVICES PRESENTLY
INSTALLED IN THE SCOPE OF WORK AREA SHALL BE
RELOCATED TO NEW LOCATIONS PER THE VAMC I.T.
DEPT. DIRECTION. NEW DEVICES SHALL BE ADDED IN
NEW ADDITION AS INDICATED ON DRAWINGS.
W
W
15cd
C R
D C
D C
C R
D C
D
CA
O M
A O
M
D C
D C
A O
M
DOOR RELEASEDOOR RELEASE
S 15cd
15cd
15cd
(EN)
(EN)
S
15cd
15cd
C01
C01
ALL TELEPHONE, DATA, CCTV AND PUBLIC ADDRESS SPEAKER CABLING TO BE RUN FROM DEVICE TO EXISTING DATA AND CCTV RACKS IN I.T. CLOSET 100.
SP
SPSP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
C R
C R
C R
R E X
D
CA
O M
DOOR RELEASE
R E X
R E X
B S
(EN)
DH
S SP
S
PHASE 7
PHASE 5
DEMOLISH ALL PHASE 5 ELECTRICAL DEVICES TO ACCOMMODATE NEW PHASE 7 ELECTRICAL DEVICES.C02
C02
SP (EN)
15cd
S
N-2-CC
(UNISTRUT MOUNTED)
CB-2-CC
PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS A01.1 AND A01.2
FOR PROJECT PHASING AND ADDITIONAL PHASING NOTES.
AOM
ELEVATOR
DOOR RELEASE
NACP
W
W
W
W
W
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E30.1
APGJWT
SYSTEMS
SECOND FLOOR PART PLAN
1.8
4.3'
1.8
4.3'
1.8
4.3'
CYSTOSCOPY
CYSTOSCOPY
GENERATOR
PART PLAN - CYSTOSCOPY 263 - LIGHTING
SCALE: 1/4" = 1'-0"
PART PLAN - CYSTOSCOPY 263 - POWER
SCALE: 1/4" = 1'-0"
PART PLAN - CYSTOSCOPY 263 - SYSTEMS
SCALE: 1/4" = 1'-0"
C
C1
C1
C
CC1
C
D
C1
D
C1 C1C
75cd
S
C a,b a,b a,b a,b
L01
L01
L01
L02
L02
L03
L03
P01
P02
P03
S01
S02
S03
EPO
P04
BS
SP
SPEAKER
a,b a,b a,b
CB-2-CC#19
CB-2-CC#17
GENERATOR CABINET
WARMING UNIT
HYPO. UNIT
MED. DISP.
ANEST. CART
ANEST. APPAR.
MONITOR
EXTREM. PUMP
BLOOD WARMER
BLOOD WARMER
BLOOD WARMER
COMPUTER
CB
W
IPU-E-CYSTO1#2,6
IPU-E-CYSTO2#1,5
IPU-N-CYSTO#1,5
UTILITY COLUMN WITH (2) CRITICAL QUAD RECEPTACLES, (1) NORMAL QUAD RECEPTACLE AND (2) DATA OUTLETS.
P01
IPU-E-CYSTO1#1
IPU-E-CYSTO1#5
IPU-E-CYSTO1#9
IPU-E-CYSTO1#13
IPU-E-CYSTO1#17
IPU-E-CYSTO1#21
IPU-E-CYSTO1#23
IPU-E-CYSTO1#25
IPU-E-CYSTO2#2
IPU-E-CYSTO2#6
IPU-E-CYSTO2#10
IPU-E-CYSTO2#14
IPU-E-CYSTO2#18
IPU-E-CYSTO2#22
9 9
IPU-N-CYSTO#13
IPU-N-CYSTO#17
IPU-N-CYSTO#9
IPU-N-CYSTO#19
GENERATOR CABINET
3#14 IN 1/2" C TO X-RAY IN USE SIGN AT ALTERNATE DOOR TO CYSTO ROOM.
3#14 IN 1/2" C TO GENERATOR CABINET.
CONDUITS TO PENETRATE INTO GENERATOR CABINET WITHOUT THE NEED FOR A JUNCTION BOX.
P02
"X-RAY IN USE" SIGN AND LIGHTING RELAY CONTROLLED VIA GENERATOR CABINET. LITHONIA 'X-RAY IN USE' SIGN
MODEL LQM-P-W-1-R-120/277-SW-09. PROVIDE LIGHTING RELAY AT SIGN TO CONTROL LIGHTING CIRCUIT.
S01
S02
EMERGENCY OFF PUSHBUTTON FOR OPERATION OF SHUNT TRIP MAIN CIRCUIT BREAKER. PROVIDE RED MUSHROOM BUTTON IN
PROTECTIVE LEXAN COVER.
2#12 IN 3/4"C FROM 'EPO' TO MAIN BREAKER.
8"x8"x6x DEEP JUNCTION BOX. SPLIT REMOVABLE COVER PLATE SHALL CONTAIN A 3" GROMMETTED OPENING. LOCATE BOX BELOW
COUNTER AND PROVIDE A 3" GROMMETTED OPENING IN COUNTERTOP FOR CABLE ACCESS TO EQUIPMENT.
S03
GENERATOR CABINET
S04
S04
VENDOR COMPUTER
S05
4" CONDUIT WITH PULLSTRING FROM JUNCTION BOX TO GENERATOR CABINET.
BASEPLATE
DC DC
DC
S06 2#12 IN 3/4"C FROM DOOR CONTACT SWITCH TO GENERATOR CABINET
S06
S06
5#4 IN 1 1/4"C FROM MAIN BREAKER TO GENERATOR CABINET. PROVIDE ADDITIONAL 10' CABLE LOOP AT GENERATOR CABINET.
P03
480V, 50A, 3-POLE SHUNT TRIP MAIN BREAKER
5#4 IN 1 1/4"C.
P04
S07
S07 3" AND 1 1/2" CONDUIT WITH PULLSTRING FROM JUNCTION BOX TO BASEPLATE.
S05
(2) 4" AND (2) 3" CONDUITS WITH PULLSTRINGS FROM GENERATOR CABINET TO BASEPLATE.
EPO
S01
S02
P05
P05
(4) PORT PATIENT GROUND MODULE WITH #10G TO PANEL IPU-N-CYSTO GROUND BUS. GROUND MODULE TO BE HOSPITAL
SYSTEMS, INC. CATALOG #358184 OR APPROVED EQUAL.
DP1-EQ-CC#2,4,6
a b a,b a,b a,b a,b
17,19 a,b a,b a,b
17,19
17,19
17,19
17,19 17,19 17,19
17,19
17,19
17,19
17,19
17,1917,1917,19 a b
LUTRON GRX-TVI
L04
17 19
L04
L05
LUTRON 3-WAY MAESTRO MASTER DIMMER CAT# MAF-6AM-120-IV CONNECTED TO LUTRON CAT# GRX-TVI POWER INTERFACE
MODULE CONTROLLING LIGHTING CIRCUIT.
LUTRON 3-WAY MAESTRO SLAVE DIMMER CAT# MA-R-120-IV CONNECTED TO MAESTRO MASTER 3-WAY DIMMER.
L05
W
P06 MOUNT POWER OULET AND DATA OUTLET AT 4'-6"AFF.
P06
P06
P06
IPU-E-CYSTO2#26
IPU-E-CYSTO2#30
30 30
MOUNT OUTLETS AT 6'-0" AFF.
MONITORS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E40.1
APGJWT
ENLARGED PART PLANS
CYSTOSCOPY 263
SECOND FLOOR
GROUND FLOOR
WING 'D'
BASEMENT LEVEL
SUB-BASEMENT LEVEL
P01
P02
P04
WING 'A'
P06
P01
GENERAL NOTES:
1. PROVIDE ALL PULLBOXES REQUIRED FOR NEW
AND EXTENDED FEEDERS, SIZE AS REQUIRED.
EXISTING 480/277V
SWITCHBOARD #1
800A 480/277
4-POLE
ATS
WITH
BYPASS
ISOLATION
P02
EXISTING 480/277V
SWITCHBOARD #4
EXISTING OUTDOOR
RUSSELECTRIC GENERATOR
PARALLELING GEAR
PROVIDE NEW 800A BREAKER IN EXISTING SPACE TO SERVE
NEW PANEL DP1-EQ-CC.
P03
WING 'B'
PULLBOX PULLBOX
CLEAN CORE ADDITION
EXISTING
PANEL
DP-CB-OR
DP-N-OR
IPU-E-CYSTO
PANEL TO BE DEMOLISHED
DP-EQ-OR
EXISTING
PULLBOX
IN BARBER
SHOP
STORAGE
ROOM
EXISTING
OFFICE
PULLBOX
EXISTING
PULLBOX
ELECTRICAL DUCTBANK
OR ADDITION
P03 REUTILIZE EXISTING 800A BREAKER TO SERVE NEW PANEL
DP1-EQ-CC
8#600MCM+2#1/0 IN (2)4"C.
P05
P04
6#250MCM+2#2 IN (2)2 1/2"C.
P05
P05 P04
P05 P05
4#350MCM+1#3 IN 4"C.
P06
P07
P08
P07 P07
3#10+1#10G IN 3/4"C.
P08
7.5 5
P07
P09 NEW NORMAL 600A, 480V AND 1200A, 208V POWER FEEDERS
BETWEEN EXISTING WING B PULLBOXES AND EXISTING WING A
PULLBOXES. NEW 480V FEEDER SHALL BE (8) 350MCM & (2) #1G
IN (2) 3"C. NEW 208V FEEDER SHALL BE (12) 600MCM & (3) 3/0G
IN (3) 4"C.
P09
P04
PANEL
DP1-EQ-CC
WITH
INTEGRAL
SURGE
PROTECTION
DEVICE
PANEL
IPU-N-CYSTO
WITH
EXTERNAL
SURGE
PROTECTION
DEVICE
PANEL
IPU-E-CYSTO1
WITH
EXTERNAL
SURGE
PROTECTION
DEVICE
P09
CB-2-CC
WITH
SURGE
PROTECTION
DEVICE
P09
P09 4#1+1#8G IN 1 1/2"C.
P07
IPU-E-CYSTO2
WITH
EXTERNAL
SURGE
PROTECTION
DEVICE
P10 PROVIDE #10 GROUND IN 3/4"C BETWEEN PANEL GROUND BUS BARS IN COMPLIANCE WITH NEC ARTICLE 517.
P10P10
PANEL
N-2-CC
WITH
SURGE
PROTECTION
DEVICE
P11 PROVIDE ALL REQUIRED PROGRAMMING FOR EXISTING RUSSELECTRIC GENERATOR PARALLELING GEAR TO ACCOMMODATE NEW STARTING CIRCUIT
FROM NEW ATS-EQ-CC1. COORDINATE LOADING AND UNLOADING SEQUENCE WITH VA FACILITIES STAFF.
P11
P12 PROVIDE (2) NEW 50A, 2-POLE BREAKERS TO SERVE NEW PANELS IPU-E-CYSTO1 AND IPU-E-CYSTO1. PROVIDE (1) NEW 100A, 3-POLE
BREAKER TO SERVE NEW PANEL CB-2-CC. NEW BREAKERS SHALL MATCH EXISTINTG TYPE INCLUDING AIC RATING.
P12 P13
P13
B-EQ-CC
WITH
SURGE
PROTECTION
DEVICE
30KVA
480V:
208/120V
XFMR
P15
P14
P15
P14 3#6+1#10G IN 1"C
4#1+1#8G IN 1 1/2"C.
57.5
3#12+1#12G IN 3/4"C.
P16 8#10 IN 1"C GENERATOR START/STOP SIGNAL CIRCUITING.
P16
OR CHILLER
CH-1GB001
OR CHILLER
CH-IGB002
AIR HANDLER 12B001
REUTILIZE EXISTING 600A BREAKER TO SERVE NEW OR
CHILLER CH-1GB002. PROVIDE NEW 450A RATING PLUG.
PROVIDE (1) NEW 100A, 3-POLE BREAKER TO SERVE NEW PANEL N-2-CC. NEW BREAKER SHALL MATCH EXISTING TYPE INCLUDING
AIC RATING.
2. CONTRACTOR SHALL FOLLOW ALL REQUIREMENTS
OF NFPA 70E FOR ALL WORK INCLUDING WORK
ASSOCIATED WITH THE RUSSELECTRIC GENERATOR
PARALLELING GEAR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F il e P a th
/1
/2
:3
:0
P
M
Office of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Auburn, ME
207.784.5100
Boston, MA
617.426.5050
Portland, ME
207.775.0053
Portsmouth, NH
603.626.1242 c
HA PROJECT NUMBER: 13586
PROVIDENCE, RHODE ISLAND
02-22-19
650-337
SPRINKLERED
SURGICAL SUITE
CONSTRUCT CLEAN CORE ADDITION TO
DOCUMENTS
FINAL CONSTRUCTION
E50.1
APGJWT
RISER DIAGRAM
ELECTRICAL
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTION
A M
P
P O
L E
CRKT
DWG
NO. P
O
L E
WATTS
PH A PH B PH C
WATTS
P O
L E
CRKT
DWG
NO. P
O
L E
A M
P
LOAD DESCRIPTION
FEEDER:AIC RATING:
MAIN BREAKER:VOLTAGE:
BUSES:
PH & WIRES:
120/208
3P 4W
MLO
22K AIC
SURFACE
SEE DRAWING E50.1CB-2-CC
TUB 1 OF 1 - REMARKS:
RM 217 & 211 RCPTS 20 1 1 1 800 1182 --- --- 382 2 2 1 20 BRONCOSCOPY LIGHTING
RM 217 & 211 RCPTS 20 1 3 3 800 --- 1175 --- 375 4 4 1 20 LIGHTING RM 217,256,257
CORRIDOR 210 RCPT 20 1 5 5 200 --- --- 700 500 6 6 1 20 RM 250 BOOM
RM 259 RCPT FREEZER 20 1 7 7 725 1225 --- --- 500 8 8 1 20 RM 250 BOOM
* RM 256 RCPTS 20 1 9 9 200 --- 1000 --- 800 10 10 1 20 RM 250 BOOM
* WIRELESS SPEAKERS 20 1 11 11 600 --- --- 1400 800 12 12 1 20 RM 250 BOOM
RM 253 RCPTS 20 1 13 13 1000 1400 --- --- 400 14 14 1 20 RM 250 RCPTS
RM 251 RCPTS 20 1 15 15 400 --- 800 --- 400 16 16 1 20 RM 250 RCPTS
RM 263 LIGHTS 20 1 17 17 1050 --- --- 1850 800 18 18 1 20 RM 250 RCPTS
RM 263 LIGHTS 20 1 19 19 1050 1050 --- --- 0 20 20 1 20 SPARE
SPARE 20 1 21 21 0 --- 0 --- 0 22 22 1 20 SPARE
SPARE 20 1 23 23 0 --- --- 0 0 24 24 1 20 SPARE
SPARE 20 1 25 25 0 0 --- --- 0 26 26 1 20 SPARE
SPARE 20 1 27 27 0 --- 0 --- 0 28 28 1 20 SPARE
SPARE 20 1 29 29 0 --- --- 0 0 30 30 1 20 SPARE
SPARE 20 1 31 31 0 0 --- --- 0 32 32 1 20 SPARE
SPARE 20 1 33 33 0 --- 0 --- 0 34 34 1 20 SPARE
SPARE 20 1 35 35 0 --- --- 0 0 36 36 1 20 SPARE
SPARE 20 1 37 37 0 0 --- --- 0 38 38 1 20 SPARE
SPARE 20 1 39 39 0 --- 0 --- 0 40 40 1 20 SPARE
SPARE 20 1 41 41 0 --- --- 0 0 42 42 1 20 SPARE
TOTAL AMPS: 32.7 4857 2975 3950 TOTAL WATTS: 11782
REMARKS:
* INDICATES GFCI CIRCUIT BREAKER.
10/11/2018
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTION
A M
P
P O
L E
CRKT
DWG
NO. P
O
L E
WATTS
PH A PH B PH C
WATTS
P O
L E
CRKT
DWG
NO. P
O
L E
A M
P
LOAD DESCRIPTION
FEEDER:AIC RATING:
MAIN BREAKER:VOLTAGE:
BUSES:
PH & WIRES:
120/208
3P 4W
45A MAIN BRKR
10K AIC
SEE DRAWING E50.1IPU-N-CYSTO
BOOM RCPT 20 2 1 1 400 200 --- --- 0 2 2 2 20 SPARE
- - - 3 --- 200 --- 4 - - -
BOOM RCPT 20 2 5 5 400 --- --- 200 0 6 6 2…