This document outlines specifications for maintenance and modification services for the fire alarm system at the Providence VA Medical Center in Rhode Island. The system utilizes Notifier panels and devices across multiple buildings. Services include maintaining and updating the system as devices are added, deleted or relocated. Modifications require engineering and programming support to ensure compliance with standards. The related opportunity is a solicitation for construction services to build a clean core addition and surgical suite at the facility. Offerors will design and construct approximately 2,900 square feet of renovated space and 3,900 square feet of new construction addition while maintaining hospital operations. The acquisition will be a total SDVOSB set-aside conducted under FAR Parts 15, 19, and 36 utilizing LPTA procedures. The projected value is between $5-10 million.
36E77619R0097 0004 P01 - Providence VAMC_Fire Alarm System Specifications_2017.docx
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The Providence VA Medical Center campus located at 830 Chalkstone Avenue in Providence, RI 02908-4799 utilizes (2) Notifier NFS2-3030 Fire Detection and Alarm System Control Panels (FACP’s) in the main building denoted as Building 1 and (1) NFS2-640 FACP in the E Wing of the main building. Current configuration of these panels provides a total of 10 signal line circuit (SLC) data addressable loops.
All initiating devices are and shall be addressable-no exceptions.
All networked panels in the outlying buildings on the campus utilize the Notifier NFS2-640 Fire Alarm Control Panels (FACP’s). Notifier FlashScan ® field devices are to be used with the described panels which greatly enhance the speed of communication between analog intelligent devices. Each building also utilizes, as a separate network node, the Digital Voice Command (DVC-EMF) with a Digital Audio Amplifier (DAA-5025F).
The Notifier fire alarm system was installed in 2010 utilizing state of the art network-based components utilizing (armored) multi-mode fiber distributed underground to connect each FACP and audio DVC. The Notifier NCM-F Network Communications Module in each FACP provides the network-base fiber (Style 7) loop connection to all the panels. The Notifier NCA-2 is provided at the Operations Center Room D1090 as the primary network command and control point of operation.
The DET-6B telegraph transmitters (electronic masterbox) are provided in the Fire Command Room 136 for transmission of general fire alarm signals to the Providence Fire Department for all campus networked FACP’s through a municipal cable that leaves the main building of the VA Medical Center underground and connects to the Providence Fire Department City Loop circuit located via street light pole by the Regent Street entrance to the VA Medical Center.
Building 1 audio is provided from (1) DVC-EMF located in the Operations Center Room D1090 and provides digital messages to (38) DAA-5025F audio amplifiers distributed within Building 1. Each DAA provides (4) each (Style Y) speaker circuits. Each identified “smoke zone” is provided with a separate “voice” circuit with its own dedicated amplifier.
An LCD – 160 is located in the Emergency Room D1176 reception desk area for 24 hour network monitoring & in the ACB area corridor. The Fire Command Center Room 136 is equipped with the Notifier ONYX First Vision Graphics Annunciator Panel. The ONYX Works provide graphical displays of the main building floor plans and outlying buildings to graphically display where an alarm condition has been initiated. This system shall be maintained and updated as the system evolves adding, deleting and relocating initiating devices. No exceptions!
The Notifier DVC Digital Voice Command is the heart of the integrated full-featured audio command center. The DVC is located in the Operations Center Room D1090 and provides the digital audio processor to generate audio messages and route them to the respective Notifier Digital Audio Amplifiers DAA-5025F (via Style 6/7 multi-mode fiber) and distributed System Sensor Wall Mounted Speakers. DVC’s are powered by 24 Vdc from the local FACP power supplies. DAA’s are powered from 120 VAC and are equipped with Battery Back-up.
Combination speaker-strobes and Strobe-only devices are powered and synchronized from “bell” circuits of the NFS2-640 FACP’s in the outlying buildings and from the Notifier FCPS-24S8 power supply panels within building 1. Building 1 NAC circuits are configured in two modes; Mode 1 (Type IV power supplies) provide (4) individual NAC circuits connected directly to FCPS, Mode 2 (Type I power supplies) provide power to a series of Notifier FCM – 1 Control Modules in conjunction with System Sensor Model MDL sync modules. Strobe synchronization in building 1 is provided from (3) individual sync circuits: (1) for the Sub-basement, (1) for 1st and 2nd Floors, and (1) for the 3rd Floor and above floors. All FCPS panels operate from 120 VAC and are equipped with battery back-up.
Additional FCPS panels (Type II Power Supplies) are utilized for 24Vdc power to door-holder and other ancillary/ auxiliary functions or 4-wire monitor/control devices such as Beam Detectors and Duct Smoke Detectors. Currently there are (6) FCPS panels installed for such devices throughout the main building.
The ONYX Work Stations located in the Operations Center Room D1090 and the Fire Command Room 136 provide graphical maps of the campus and main building floor plans for event reporting and historical data retrieval purposes for all network points on the system.
In addition, there is a Notifier PRN-6 printer used to provide a written record of all events associated with the network fire alarm system. The printer is located in the Fire Command Center Room 136 which utilizes serial communication.
A Notifier NFN Gateway is provided in the Audio/NCA panel located in the Operations Center Room D1090 to provide connection (via owner provided connection) to owner’s server. The NFN Gateway provides a means to access and view the system from a remote computer or laptop.
Modifications to the system will require fire protection engineering redesign and support using licensed professionals. Existing fire alarm system “as built” or “shop drawings” will be verified by A/E against actual system assembly prior to any redesign modification. All modifications will require updated drawings to be delivered to the VA after testing and commissioning has been completed. All work performed must meet current JCAHO, Healthcare, and the National Fire Protection Code (NFPA) standards.
Modifications to the system in which to add, delete, extend, or relocate, field devices and or panels require extensive knowledge and experience with this state-of-the-art system. Use existing wiring conventions for all circuit types and perform additional load calculations for audio amplification circuits to ensure maintaining a consistent operable and reliable system by manufacturer’s specifications – no exceptions. 2 Hour Fire Rated Cable/Conduit is required from panel to panel. Wiring inside a smoke zone for another smoke zone must also be in 2 Hour Fire Rated Cable/Conduit. All tamper and flow switch devices must have their own exclusive addressable interface monitor module (Notifier P/N FMM-1 Flash Scan Monitor Module) – no exceptions. There will be no substitutes.
In addition to the hardware modifications, extensive programming and reprogramming may be required to update graphic files and audio file messages based on smoke zones and floor plans of field device modifications. Voice activated messages may have to be added, deleted, or modified within an evacuation zone or modify alert messages going out to additional DVC’s – DAA’s or FACP’s around the campus outside of the initiating zone. In this case, the ONYX Workstation, DVC’s (17), NCA-2 (1 each), NFS2-3030 (2), NFS2-640 (16), may require system reprogramming. Service personnel must be authorized and certified by Notifier to add, delete, modify, or repair any fire alarm system component. No exceptions.
Panel Types and Locations:
NFS2-3030 Building 1 - Room 136 (7 of 10 SLC loops installed) Building 1 - Room D1013 Elevator Lobby (3 of 10 SLC loops installed) NFS2-640 Buildings: 1 (E Wing only) 2, 3, 4, 5, 6, 7, 8, 9, 10, 14, 26, 32 and 35 T18 – VA Police Headquarters Trailer - TR32 Trailer - TR35 – Currently connected to the network (NCM active pass-through) but has no field devices connected to the panel – stand alone system is being utilized Note: The NFS2-640’s are equipped with only (1) SLC, a second SLC can be added if required.
Standard Cable & Wire Conventions: (No exceptions)
· Signal Line Circuit (SLC) Cable [ FPLR in conduit ] [ Style 6/7, Class A ] Solid Copper 16AWG – 2/C Twisted/Unshielded – Red Jacket
· Speaker Circuit Cable [ FPLR in conduit ] [ Style Y, Class B ] Solid Copper 16AWG – 2/C Twisted/Shielded - Red Jacket/Blue Stripe
· Strobe Circuit Cable [ FPLR in conduit ] [ Style Y, Class B ] Solid Copper 14AWG – 2/C Twisted/Unshielded - Red Jacket/Yellow Stripe
Notes:
· Any of the above circuit types which cross over or between identified smoke zones are wired using UL Listed CIC cable – listed CIC cable provides 2 hour rating when installed in conduit – see original submittals for type provided.
· Additional wiring information may be obtained from current project documents:
Door Holders – Yellow Blue (THHN/TFFN) Solid Copper 14 AWG Non-resettable power – Black/Red (THHN/TFFN) Solid Copper 14 AWG
· Additional wire should match existing and be minimum Solid Copper 18 AWG FPL or as specified by manufacturer’s installation guides/documents including; Remote indicator/test switches, Remote Annunciators/microphones, strobe circuit sync lines, RS232/RS485 or other data lines, Fire Fighter Phones/Risers and all other command, control, monitor, ancillary and auxiliary wiring and cables.
VERY IMPORTANT – SOFTWARE / APPLICATIONS
· Extreme care should be taken regarding software applications data and programmer versions/revisions. System equipment was ordered in 2007 and is currently programmed using Veri-fire 5.3 programmer version software. DVC’s and DAA’s are version 2.0 application/firmware data.
· Upgrading of firmware, hardware or programmer can have a cascade effect on other network panels/components. Replacement components should be brought to exact same version/revision as originally installed – compatibility issues can have a serious effect on system/network operations.
· Audio Libraries – Before downloading to DVC’s, great care should be taken in ensuring that the audio library (message segments/files) path matches to original programming, failure to do so can result in loss of message sequences.
Providence VAMC_Fire Alarm System Specifications_2017