36E77619R0097-0004004.pdf

PDF Posted

Attached to
Construct Clean Core (VA-19-00058573) Federal contract opportunity
Solicitation number
36E77619R0097
Issued by
Department of Veterans Affairs Headquarters

About this file

This solicitation notice describes a federal construction contract opportunity for the Department of Veterans Affairs. The project consists of constructing a new clean core surgery suite space within and adjacent to existing operating rooms at the Providence VA Medical Center in Rhode Island. Work includes relocating the cystoscopy suite and minor surgery, adding an elevated clean core to access operating rooms and cystoscopy with sterile supplies, and renovating existing space. The solicitation will be a request for proposal evaluated using lowest price technically acceptable procedures. It is set aside for service-disabled veteran-owned small businesses with a size standard of $39.5 million. The contracting agency is the VA's Program Contracting Activity Central. The performance period is approximately 490 days from notice to proceed. The magnitude of construction is estimated between $5,000,000 to $10,000,000. Questions must be submitted in writing by the response deadline of October 16, 2019.

36E77619R0097 0004 P01 - SKA4 - REVISED CYSTOCOPY SUPPLY PIPING.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Construct Clean Core (VA-19-00058573), newest first.
File Type Posted
36E77619R0097-0007000.docx DOCX document
36E77619R0097-0006000.docx DOCX document
36E77619R0097-0005000.docx DOCX document
36E77619R0097-0005001.pdf PDF
36E77619R0097-0004001.docx DOCX document
36E77619R0097-0004005.pdf PDF
36E77619R0097-0004002.pdf PDF
36E77619R0097-0004000.docx DOCX document
36E77619R0097-0004003.pdf PDF
36E77619R0097-0003000.docx DOCX document
36E77619R0097-0003001.pdf PDF
36E77619R0097-0002001.pdf PDF
36E77619R0097-0002002.pdf PDF
36E77619R0097-0002000.docx DOCX document
36E77619R0097-0001031.pdf PDF
36E77619R0097-0001030.docx DOCX document
36E77619R0097-013.pdf PDF
36E77619R0097-009.pdf PDF
36E77619R0097-014.pdf PDF
36E77619R0097-011.pdf PDF
36E77619R0097-003.docx DOCX document
36E77619R0097-015.docx DOCX document
36E77619R0097-010.pdf PDF
36E77619R0097-006.pdf PDF
36E77619R0097-008.pdf PDF
36E77619R0097-007.pdf PDF
36E77619R0097-012.pdf PDF
36E77619R0097-004.pdf PDF
36E77619R0097-005.zip ZIP file
36E77619R0097-015.docx DOCX document
36E77619R0097-011.pdf PDF
36E77619R0097-014.pdf PDF
36E77619R0097-013.pdf PDF
36E77619R0097-005.zip ZIP file
36E77619R0097-006.pdf PDF
36E77619R0097-007.pdf PDF
36E77619R0097-009.pdf PDF
36E77619R0097-008.pdf PDF
36E77619R0097-012.pdf PDF
36E77619R0097-004.pdf PDF
36E77619R0097-003.docx DOCX document
36E77619R0097-010.pdf PDF
36E77619R0097-000.docx DOCX document
36E77619R0097-000.docx DOCX document
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2.52.221.81.510.5

B

A.5

A

C

P-519

DCWS- 1"

DHWS- 1"

DHWR- 3/4"

P25

CYSTOSCOPY

MN- 1/2"

MV- 1/2"

MO- 1/2"

MA- 1/2"

WAGD- 1/2"

MN02- 1/2"

MC02- 1/2"

P22

M N

/2

M V

/2

M O

/2

M A

/2

W A

G D

/2

M N

/2

M

C

/2

P26

MA- 1/2"

MO- 1/2"

MV- 1/2"

MA- 1/2"

MO- 1/2"

MV- 1/2"

DHWR- 3/4"

DHWS- 1"

DCWS- 1"

WAGD- 1/2"

MN02- 1/2"

MN- 1/2"

WAGD- 1/2"

MN02- 1/2"

DCWR- 3/4"

DCWR- 3/4"

M N

/2

P32

0 4' 8' 12'

HA Project No.

Scale

Date

1/8" = 1'-0"

Harriman Associatesc

Auburn

Boston

Portland

Portsmouth

1/8" = 1'-0"

SKA4

REVISED CYSTOSCOPY

SUPPLY PIPING

PROVIDENCE, RHODE ISLAND

650-337

12-4-19

CONSTRUCT CLEAN

CORE

ADDITION TO SURGICAL

SUITE

KEY NOTES

CODE DESCRIPTION

P01 2" W UP

P02 2" V UP

P03 4" S UP

P04 8" OD UP

P05 2" W & 1-1/2" V DN

P06 2" W IN WALL & 1-1/2" V DN

P07 4" S DN

P08 2" V DN

P09 2" V UP 3" VTR

P10 3" V UP 4" VTR

P11 2" W DN

P12 3" VTR

P13 4" VTR

P14 6" OD & 6" SD DN

P15 6" OD & 6" SD UP

P16 CONNECT 8" OD TO EXISTING 8" OD

P17 CONNECT 6" SD TO EXISTING

P18 3" SD UP TO 3" RD

P19 3" OD UP TO 3" RD

P20 3" W UP

P21 EXISTING ROOF DRAIN TO REMAIN

P22 PROVIDE MEDICAL GAS VALVE BOX & ALARM PANEL REFER TO

SPECIFICATIONS FOR MANUFACTURERS & MODELS. COORDINATE

EXACT LOCATION OF ALARM PANEL WITH ELECTRICAL

CONTRACTOR

P23 1/2" MA, MO. MV, WAGD,MNO2 &MN DN TO BOOM

P24 1/2" DHWS & DCWS DN

P25 1/2" HW & CW DN

P26 1/2" MCO2,MNO2, WAGD,MA, MO, MV, MN, MN FROM CONTROL

PANEL DN TO RETRACTABLE CEILING COLUMN

P27 PROVIDE ISOLATION VALVE, MAKE FINAL CONNECTIONS TO TWO

EVAC UNITS REFER TO MANUFACTURERS INSTALLATION MANUAL

P28 3/4" TEMPERED WATER FROM MIXING VALVE DN. RUN PIPE IN WALL

TO BACKFLOW PREVENTER LOCATION

P29 1" DCWR DN

P30 CONNECT TO EXISTING 1" CHWR RISER

P31 1" DCWR UP

P32 1/2" MN DOWN TO NITROGEN CONTROL PANEL,BEACONMEDAES

GAS CONTROL PANEL PART NUMBER 120276-01

Sheets
SKA4 - REVISED CYSTOSCOPY SUPPLY PIPING

File details come from the government source that posted it. Updated .